MILLENNIUM® SINGLE PACKAGE
ROOFTOP UNITS
25, 30 & 40 TON EQUIPPED WITH
SIMPLICITY
®
ELITE CONTROLS
MILLENNIUM® 25-40 TON SINGLE PACKAGE
COMMERCIAL ROOFTOP UNIT EQUIPPED
WITH SIMPLICITY® CONTROLS
This manual includes application, programming and service
procedures for the Millennium® 25-40 Ton Single Package
Commercial Rooftop Unit equipped with Simplicity
These procedures are the same for all 25-40 Ton Millennium®
Rooftop units in this series except as noted.
This manual covers Simplicity
information please refer to the following.
®
controls only, for unit installation
®
Controls.
RECOMMENDED TECHNICAL AND
INSTALLATION AIDS
Millennium® 25-40 Ton Single Package Installation and Operation
Manual - 524158
®
Millennium
25-40 Ton Technical Guide - 246837
351579-YTS-C-0111
TABLE OF CONTENTS
MILLENNIUM® 25-40 TON SINGLE PACKAGE
COMMERCIAL ROOFTOP UNIT EQUIPPED WITH
Welcome to the new Millennium® Simplicity® control, a digital
control system designed specifically for the Millennium® 25 to 40
Ton single package rooftop unit. The Simp licity
72 monitored and controlled input and output points. The control
logic of the Simplicity
®
extends on the rules built in to the
Synthesys control, and provides character displays in additi on to
LED flashes to display information to the technician.
The Simplicity
®
digital control performs all of the control and
monitoring functions that were originally done by separate
discrete relays, controls, and interlocking hardware. This
reduces manufacturing, service, and maintenance costs. The
Simplicity
®
digital controller includes sophisticated control of
the individual components of the HVAC cooling/heating unit,
and has built-in rules that protect those components and
optimize the control to its environment. The cooling and heating
modes are protected against frequent cycling, slugging,
multiple restarts, etc.
®
is composed of
351579-YTS-C-0111
®
The Millennium
Simplicity® control is resistor-configured for
Constant Volume (CV) units or Variable Air Volume (VAV) units.
The option settings for a specific option configuration will be
made as part of unit test at the factory; however, if there is
doubt about how a unit is responding in the field, check the
option setting for the unexplained action.
If connected to a network, the control requests an address by a
press of the Address/Down button.
DIAGNOSTICS VIA LED
There is an LED on the board that shows the status of the
control and alarms (see Status LED Table). There are two
character displays, one 2-digit and one 4-digit, to indicate
details of run conditions and alarms (see Alarms Table in the
Trouble Shooting section of this manual).
When the Alarm / Change Data button (See Figure 2 Simplicity
Controller Push Buttons) is pushed and released one time within
five seconds, it will re-enunciate the last five alarms on the
Display.
®
®
Figure 1: Simplicity
Controller
One result is that the system may not immediately respond as
you expect. For example, internal digital timers may delay the
start of a compressor even though the thermostat calls for
cooling. The control may be in the middle of a timing sequence;
without the observer knowing what has already happened and
the status of current inputs, the system may take action not
expected by the tech.
®
In the Simplicity
• a list of user-selected option settings and setpoints
recorded within the control;
control, there are:
• inputs monitored by the Simplicity®;
• specific fixed rules and timings built in to the control
• outputs to compressors, heat, economizers, and other
options.
The Simplicity
®
has a real-time clock function, with minimum of
ten hours “Time-of-day retention” with unit power off.
Johnson Controls Unitary Products3
Figure 2: Simplicity® Controls Push Buttons
When this button is pushed and released two times within five
seconds, it will clear all stored alarms.
The error details for most conditions are stored in summary in
the Simplicity
®
Control and can be accessed by the digital
display, personal computer interface, or Palm Pilot (Some
interfaces still in development).
Diagnosing requires patience because of internal timings.
Normal observable conditions are the same - contactor 1M
pulled in, compressor 1 running - but the control does not
identify what it has just done or is about to do. The Simplicity
®
control will take action according to its internal rules even
though action requests come from smart thermostats. A call for
cooling, for example, will be compared with supply air
temperature before energizing a cooling stage.
ERROR HISTORY
®
The Simplicity
control stores up to 5 of the most recent alarms
in a First In, First Out (FIFO) manner. As the control collects
351579-YTS-C-0111
BINARY NUMBER EQUIVALENT
0 1 2 3 4 5 6 7------------- n
alarms, it will overwrite the oldest alarm after the history buffer
becomes full.
Some system errors will initiate a controlling response as well
as being stored in the error memory buffer. See the
“Troubleshooting” chapter in this manual for a detailed
description of how controller errors are handled.
Data items stored for maintenance / run history, in addition to
Alarms:
• Accumulated run times for each compressor and heat st age
• Unit model number
• Unit serial number
•Unit Name
DIGITAL LINGO
This training manual is intended to help you with the
commissioning process by illustrating the use of tools like the
control’s digital input and software engineered specifically for
starting up and servicing a Millennium
You should become familiar with some common terminology
and lingo used in the digital controls industry. (If you are familiar
with the Synthesys controller, the logic of the Simplicity® will be
familiar territory.)
®
rooftop unit.
depending on how long the sensed value remains away from its
desired setpoint.
Fortunately, you do not have to determine all of these
parameters since they are pre-programmed at the factory. You
need only to set a desired setpoint and ensure that the inputs
and outputs are properly wired and working. This is referred to
as commissioning a system.
ANALOG TO DIGITAL CONVERTER
Computers can only understand a simple binary language.
Remember, “binary” means two states - ON or OFF. Analog
(continuous) values of voltages, currents, and resistances are
supplied by sensors and transducers to the control. These
values must be converted in to a binary code so that the
computer can understand them. This conversion process is
performed through a combination of hardware and software.
For example, the 0-5VDC analog value from a static pressure
transducer is divided into thousands of steps with a binary
coded number, often called “counts”, assigned to each step.
If this is your first exposure to the world of digital controls you
may experience a lot of new terms, acronyms and technical
lingo commonly used in the controls industry. For example, the
Simplicity
®
input and output hardware points are described as
analog, relating to a continuous scale of value readings such
as a temperature sensor ranging from -400F to 1600F range, or
binary, meaning 2-states, either on or off, open or closed, true
or false, one or zero. The term “digital” also means two states
and its use is often interchanged with “binary”. These points
may be either factory- or field-set.
THE PI ALGORITHM
Another common “digital controls” term is the PI algorithm or
Proportional-Integral control loop. The PI algorithm is a
continuously updated math calculation that the controller uses
to modulate an analog output point. For example, a variable
speed drive uses a PI loop to maintain a desired setpoint (in this
case, a duct static pressure value). The algorithm takes into
account several parameters to calculate the output. The PI loop
needs parameters such as the proportional operating
bandwidth, integral time constant, deadband, desired setpoint
value, sensed input value(s), start up ramp time, initial start
value, maximum output control value, a status point to initiate
the control action (i.e. a fan ON status), Direct or Reverse
Controlling Action, and several other parameters to calculate a
simple 0 to 100% analog output control. The PI algorithm is also
called a PI loop because it “loops” the output back to the input
(feedback) and determines a new output value based on the
“error” or difference between the setpoint value and the sensed
input value, and how that difference relates proportionally to the
0 to 100% output value. Time is the ”integral” constant that is
factored in to increase or decrease the controlling output action
Figure 3: Analog to Digital Converter
SOFTWARE TERMINOLOGY
A digital controller handles its control functions through software
programming rather than with interlocking hardware and wiring.
The software then becomes key to how controlled functions are
handled. Software is a set of statements (referred to as the
“program”) that define the function of the controller’s internal
microprocessor computer.
Software procedurally tells the computer the sequence and
order of tasks that need to be performed using a language that
the computer can understand.
Software is stored in a computer’s memory. There are several
types of memory in a computer. Each type has a specific
function to perform.
4Johnson Controls Unitary Products
351579-YTS-C-0111
EPROM - This is “nonvolatile” memory , meanin g it will not be
erased on a power loss. This memory is usually programmed
prior to assembly of the controller. Since this me mo ry is n ot
changed during normal operation of the Simplicity
®
control, only
basic operation instructions are stored in this type of memory.
EEPROM (Double “E” Prom) - Is also non-volatile, but this
type of memory requires a specia l process t o be writt en to. Thi s
memory can be written to and changed by the microprocessor.
This is the type of memory that the control program is stored in
the Simplicity® control.
ROM - Read Only Memory is non-volatile but can not be written
to. This memory is programmed only once before the controller
is assembled. ROM contains instructions specifically for the
internal microprocessor computer in the controller.
FIRMWARE - “Firmware” is software, program instructions or
applications, but stored in EPROM or ROM memory.
RAM - Random Access Memory is a volatile memory. It will be
erased when a power fail occurs. This memory is used as a
kind of “scratch pad” for the controller. Temporary instructions
and information such as an output controlling action like driving
the economizer dampers open is stored here. When a power
loss occurs or if the controller is sent a manual reset using a
control push button, this memory is cleared and initialized.
Other filtered inputs include temperature and humidity sensors.
You should be aware of this filtering effect because it will
appear the controller is not acting as fast as you may think it
should. In reality, it is acting and controlling on these timeaveraged and weighted values.
®
FAULT TOLERANCE - Fault Tolerance of the Simplicity
control
involves two issues: Hardware fault tolerance deals specifically
with the electrical characteristics of the controller - how much
over voltage or power surge the controller can withstand before
damage occurs, and whether internal comparisons are verifying
that the control is calculating and communicating properly.
Software fault tolerance in this technology consists of comparing
results to previous values and to reasonable values.
COMMUNICATIONS BUS
Networked communications may also be new to you. It relates
to connecting several Millennium
that can be monitored and controlled remotely from network
computer workstations. You will find this typically on large
installations where central control, monitoring, and energy
management issues become a critical factor in operating a
large complex such as a manufacturing facility.
®
The Simplicity
Control has the ability to be networke d in to a
larger system using the MODBUS communication protocol. A
communication protocol is simply a set of rules that determine
how two systems communicate with each other over some
medium such as a pair of wires, phone line, radio waves, etc.
The transmission medium may also be called a gateway,
pathway, or bus. An “open” protocol such as MODBUS is a
publicly published set of rules that any equipment manufacturer
can use to network into another manufacturers equipment.
®
rooftop units to a network
OPTIONAL Simplicity® LINC TRANSLATOR
OVERVIEW
The Simplicity
®
LINC translator operates as a Modbus® Client
providing an interface between a BACnet® control system and
devices that communicate using the Modbus® RTU protocol. The
Simplicity
®
LINC is preconfigured to provide an interface to
YORK UPG products equipped with an Intelli-Comfort or
Simplicity Elite™ controller and allows monitoring and control by
a third-party BACnet
The Simplicity
®
Building Automation System (BAS).
®
LINC communicates using the Modbus® RTU
protocol on one port and BACnet® MS/TP . By providing different
communication protocols on the two ports, data can be
retrieved from and provided to two different systems.
®
The Simplicity
LINC mounts inside the control panel of the
UPG unit and utilizes 24 VAC power from the unit's control
transformer. One port is connected to the UPG controller. The
other port must be connected to the BACnet
The Simplicity
operational data points from the controller and expose them on
a BACnet
"The Simplicity
®
LINC translator is preconfigured to obtain
®
network.
®
LINC device is primary a control offered and
configured by York's ESG (Engineering Systems Group). The
device is designed to tie into and function with a BACnet
®
network.
®
MS/TP network. The device can be used with other BACnet®
MS/TP systems, but a qualified controls contractor must be
involved. UPG cannot support the Simplicity
®
LINC device
beyond its hardware functionality and cannot guarantee
functionality with other third party BAS devices."
®
Please refer to the Simplicity
LINC Installation Manual P/N
514066 and Application Guide Part Number 514067.
COMPONENT DESCRIPTION
This section describes the main components of Millennium®
Simplicity
controllers, hardware to handle signal input and control output
and the Tstat interface terminals.
THE Simplicity® CONTROLLER
Simplicity
use in HVAC applications. The controller provides monitoring
and control for either VAV or CAV for a total of 22 outputs.
WIRING AND TERMINATION, COMMUNICATIONS
Most connections to the Simplicity
harnesses. There are also screw terminal connections for
thermostat inputs and for communications via an RS-485 port.
COMMUNICATION ADDRESS
The communication address button (lower right of the display)
is used to identify a Millennium
“capture” the next available network address for that unit.
Millenniums can be networked together for centralized
®
control. These components consist primarily of
®
is a proprietary , microprocessor-based controller for
®
Control are by wiring
®
rooftop unit to a network, and
Johnson Controls Unitary Products5
351579-YTS-C-0111
monitoring and control. Much like we need a unique street
address in our homes so we can receive our postal mail or
emergency services, these units also need a unique address so
the central Facilities Management System (FMS) can “talk” to
each unit individually. The Simplicity
®
board has the model and
serial number of the specific unit and has a memory space for a
customer name to be applied. So the entire identification for a
specific unit available to the network could be, for example,
Y2AC04M3KDGABA, NCNM123456, SOUTH OFFICE.
The one-time commands to Override ASCD timers and/or to
start Run Test can be issued by the Test/Reset/Up pushbutton.
When this button is pushed and released within five seconds,
the control will zero all ASCD’s for one cycle.
ACRONYMS
A number of acronyms are used throughout this training
manual. These are specific to the Simplicity
®
control. They are
also used in the T echnical Guide and Installation and Operation
manuals. Acronyms are used to refer to input and output
hardware points and software parameters such as timing delays
and setpoints.
Table 1: Acronyms
InputsDescription
APS Air Proving Switch
IAQ Air Quality (CO2 Sensor)
BAS Economizer
BPS Building Pressure Sensor
C1O-C4OCompressor Status
DF Dirty Filter Status
DPS Duct Pressure Sensor
FSIHot Water Coil Freeze Input
GThermostat input for Fan
GV1-3Monitors gas valve actuation call
HPS1-4
LPS1-4
Lim 1-3 Over-temperature limit switch from heat stages
OAT Outside Air Temperature
OCC Building Occupied Status
Purge Building Purge input
RAT Return Air Temperature
SAT Supply Air Temperature
SDSystem Shutdown Connector
OAHOutside Air Enthalpy
RAHReturn Air Enthalpy
SSA Setpoint Adjust
ST Space Temperature
W1, 2, 3 Heating Stages from Tstat
Y1,2 3, 4Cooling Stages from Tstat
Passes BAS economizer command through to
Economizer output
High pressure switch monitored for
compressor discharge
Low pressure switch monitored for compressor
suction
Table 1: Acronyms (Continued)
PushbuttonsDescription
Test/Reset / 'Up'Test / control reset / Data value increment
Address / 'Down'Change data / Data value decrement
Alarms / Advance data Show alarms / go to next data point
ProgramGo to program mode
Real Time ClockIncorporated on the board
OutputsDescription
Status LED
Digital displaysOne 2-character and one 4-character
C1-C4Cooling Outputs 1 through 4
CF1, 2 Cond Fan Bank 1, 2
ECOEconomizer damper output
EXHExhaust Fan relay output
EXD
Fan
H1, 2, 3 Heating Stages 1, 2, and 3 output
HGRHot gas reheat [future]
HWVHot Water Valve output
VFDSupply Fan IGV or VFD Signal Output
X Alarm signal
MiscellaneousDescription
AIAnalog Input
AOAnalog Output
BI Binary Input same as
BO Binary Output
CAV Constant Air Volume
VAVVariable Air Volume
VFDVariable Frequency Drive
IGVInlet Guide Vane
IAQ Indoor Air Quality
PIProportional-Integral Control
ASCD Anti Short Cycle Timer (Compressor)
Flash to indicate alarm, otherwise
'heartbeat'
Exhaust Air Damper / Exhaust VFD Signal
Output
Supply Fan relay output [contactor or
permission relay]
The acronyms used throughout this training manual are listed in
the Acronym Table 1. They are described in much more detail
below.
INPUTS
There are two types of hardwired input points on the Simplicity
control: Analog and Binary. These may be sensors, feedback,
or adjustable setpoints. Typical analog inputs [AI] include Sp ace
Temperature (ST), Supply and Return Air Temperatures (SAT,
RAT), and Building Pressure Sensor (BPS). The binary inputs
(BI) on the Millennium
®
Simplicity® use a dry contact input to
determine the status of a monitored point. Typical BI points are
Fan Status (APS), Filter Status (DFS), and Compressor Status
(HPS1-4, LPS1-4, C1O-4O).
®
6Johnson Controls Unitary Products
351579-YTS-C-0111
ANALOG INPUTS (AI)
Analog inputs require parameters that define the input’s
characteristics. Attributes of an AI include the linear range,
alarm limits, alarm differential, change of state (COS) enable,
and filter weight. The input values may be overridden by a
external system command or by using the input buttons on
the Simplicity
®
board. This is useful to override current
conditions to test certain control functions or modes.
BAS - Economizer override; if this option is enabled, an
external BAS system will control the economizer 2-10 VDC
signal through this pair of terminals.
ST - Space Temperature sensor is a field installed sensor
(PN: 025-38928-000 - w/ Override Button). The sequence of
control for space temperature is different depending on
whether the system is a VAV or CAV. See chapter on
Sequence of Operation for a detailed description of the ST
control modes.
SSA - Space Temperature Adjust is field installed. It is a slide
adjustment located on a space sensor (PN: 025-38927-000)
with a slide bar potentiometer . It is used to offset the space
temperature setpoint. This slide-bar is a 10K ohm
potentiometer. The programmable rang e fo r the Setpoint
adjust is +/- 5 °F. For example, if the Space Temperature
setpoint is set to 74 °F, the SSA is programmed to +/- 3 °F and
the SSA is adjusted fully to the + position, the new controlling
space setpoint will be 78 °F.
OAT - The outside air temperature sensor (PN: 031-01916000A) is a factory-installed 10 K NTC sensor. Its linear
ranging is from -50 °F to 250 °F.
voltage and drop the contactors and shut down if the voltage
drops below 16 VAC and flash the appropriate flash code.
REMOTE - the control will use 0-10 VDC from third-party
BAS to control SAT set points. Thermostat input s override if in
conflict with Remote Control voltage input.
SPC TEMP - offset value from the space sensor offset
potentiometer.
CV/VAV - resistive value across terminals, to determine
which supply fan rules the control will follow.
Demand Ventilation / IAQ - Indoor Air Quality. The IAQ
expects a 0-10 VDC signal to the control from a field supplied
and installed Carbon Dioxide (CO
) sensor. Indoor air quality
2
is monitored for adequate ventilation. In Demand Ventilation
Mode, as the CO
levels in the building rise above the
2
programmed setpoint, more fresh air must be brought in. The
economizer is therefore adjusted to a more open position as
necessary. The linear ranging for IAQ sensor input is from 0
to 10,000 ppm. The Demand Ventilation setpoint is adjustable
from 0 to 2000 ppm and is set at the factory at 1000 ppm.
DPS - Duct Pressure Sensor is monitored by a factoryinstalled 0-5 VDC transducer (PN: 031-01209-000A). The
high-pressure port sensing tube is installed in the field. The
sense tube should be located approximately two thirds of the
way down the duct plenum. To prevent an unstable signal
due to air turbulence, there should be no obstructions, turns
or VAV terminal boxes up or down-stream of the sense tube
location for at least 6 to 10 times the diameter of the duct.
The sensor is located in the control box just below the
Millennium
®
Simplicity® control.
OAH - Outside Air Humidity (PN: 031-09127-000-A) is a
factory-installed sensor manufactured by MAMAO. The OAH
sensor, installed only with enthalpy economizer , provides a 010 VDC signal to the controller over a range of 0 to 100%
relative humidity. This input is used for the economizer
calculation to determine whether free cooling is available and
to switch between minimum outside air and using outside air
as the first stage of cooling.
SAT - Supply Air T emperature sensor (PN: 031-01915-000A)
is a factory-installed -50 °F to 250 °F, 10 K NTC sensor.
RAT - Return Air Temperature sensor (PN: 031-01917-000A)
is a factory-installed -50 °F to 250 °F, 10 K NTC sensor.
RAH - Return Air Humidity (PN: 031-09127-000-A) is a
factory-installed sensor manufactured by MAMAO, installed
only with dual enthalpy economizer. The control will calculate
the return air enthalpy using the relative humidity and return
temperature inputs.
LOW VOLTAGE DETECTION - This input monitors the 24
VAC for low voltage conditions. The input has two thresholds,
one at 16 VAC and one at 19.2 VAC. If the control needs to
turn on a contactor, it will look to see if the voltage is
above19.2 VAC before it will turn it on. If the voltage is not
above 19.2 VAC, it will hold off the contactor and flash the
appropriate flash code. This flash code is not an alarm. If the
control already has contactors pulled in, it will monitor the
BPS - The Building Pressure Sensor (PN: 031-01262-000A) is
a factory-installed Johnson Controls DPT -2640-522 transducer
that provides a 0 to 5 VDC signal to the controller over a range
from -0.25”WC to +0.25”WC. The transducer is located in the
control box just below the Millennium® Simplicity® control. The
sense tubes are field installed with the outside pressure being
sensed external to the unit. To avoid an erratic pressure
reading, the building pressure sense tube should be mounted
in an area away from the return air grill, discharge diffusers,
doors and windows.
BINARY INPUTS (BI)
APS - Supply Fan status is monitored by an Air Proving
Status switch (PN: 024-27557-000A) installed at the factory.
The APS monitors the difference in pressure between the
suction and discharge of the fan.
FOVR - Monitoring loop through the supply fan overload
module or VFD over torque indication.
HPS1-4, LPS1-4 - The refrigerant high pressure (HP) and low
pressure (LP) safety switches, are independently monitored
by the Millennium
®
Simplicity®. If any switch opens, the
control voltage from the control binary output is interrupted
and the status is monitored by the control.
G, OCC, P - These signals represent Fan (G), Building
Occupancy (OCC), and Building Purge (P) calls from the
Johnson Controls Unitary Products7
351579-YTS-C-0111
VFD
FR
FR
Fan
VFD +
VFD -
Simplicity
12
18
53
55
P13-1
P14-1
P14-2
Wht
Blk
TB2
thermostat. If a thermostat is installed on the system, these
inputs are connected to the thermostat interface board just as
are the cooling/heating calls. These inputs are connected
through the Tstat Interface board directly to the respective
binary inputs of the Controller. These signals are, however,
each loaded with a resistor to maintain voltage levels and to
prevent “floating” of signals. Thermostat wiring is typically not
shielded and may have induced voltages that could cause
errant signal readings by the controller.
FILT - Dirty Filter switch [customer supplied, field installed on
factory-provided harness connections] input to provide a filter
status to the control. The control will alarm only after 24V has
been sensed for ten minutes.
GV1-3 - Monitoring that voltage is being supplied to gas valves
on optional heat stages.
LIM1-3 - Overtemperature inputs from optional heat stages.
FSI - Freeze Stat is a customer installed temperature switch on
the FSI input to the controller to tell the control that a
temperature has occurred that risks the hot water or steam coil.
Y1-4, W1-3 - If a thermostat is installed on the system, these
inputs will take priority over software programmed setpoints and
limits.
SD - This terminal set allows attachment of an external
shutdown NC contact. 24VAC power is supplied to the board at
SD2; a factory installed jumper passes that power to terminal R
to power the Simplicity Elite™ board. If an external shutdown
signal is required at a particular installation, remove the jumper
and connect the NC shutdown circuit between SD1 and R.
position of the guide vane. If the unit has a factory-installed
Variable Frequency Drive, the 2 to 10 VDC signal is wired from
VFD+/- output directly to the VFD’s signal input terminals to
control fan motor speed.
Table 2: Input Signal to Y1 Actuator Position
Input Signal to Y1Actuator Position
10 VDC90 degrees
978
867
756
645
533
422
311
20
0-5
8VDC over a 90 degree Span = 11.25 degrees/VDC
OUTPUTS
Analog Outputs (AO) - Analog outputs provide a 2-10 VDC
signal to operate controlled devices. The Simplicity
configured to use only 2-10 VDC outputs to the Variable
Frequency Drive, Inlet Guide Vane, Economizer Damper,
Power Exhaust Dampers or VFD, and Heating water valves.
Since these outputs are analog, they are continuous between 2
and 10 Volts and are proportional to the 0 to 100% drive
position of the device.
ECO - Economizer Actuator - The modulating Economizer uses
a Johnson Controls M9220GGAYK30 spring-return actuator
(PN: 025-30869-000A). This actuator uses a 2-10 VDC signal
to drive the dampers open. The actuator drives 95 degree
rotation. Note the chart below for a correlation between the
input drive signal at terminal 3 (Y1) of the actuator and the
corresponding output drive position of the damper:
VFD - Inlet Guide Vane or VFD - The Inlet Guide Vane uses a
Johnson Controls M9220GGAYK30 spring-return actuator. This
actuator uses the 2-10 VDC signal from VFD+/- terminals to
drive the dampers open. The actuator drives 95 degree rotation.
Note the chart below for a correlation between the input drive
signal at terminal 3 (Y1) and the corresponding output drive
8Johnson Controls Unitary Products
®
is currently
Figure 4: VFD Control Wiring
EXD - Power Exhaust Damper Vane or VFD - Power Exhaust
Damper Actuator is a Johnson Controls M9220GGAYK30. It
uses a full open/ Full Closed scheme and operates a 95 degree
rotation. If VFD Power Exhaust is configured, the same signal
controls the exhaust fan motor drive frequency.
HWV - Heating W ater V alve - Customer supplied and installed,
connect to factory-provided harness.
BINARY OUTPUTS (BO)
FAN - Fan Start/Stop Relay, VFD “permission” relay FR
H1-3 - HEAT STAGES 1 TO 3 [OPTIONAL]
C1 through C4 - Cooling Stages 1 through 4
CF1 & CF2 - Condenser Fan Banks 1 and 2
X - Controller Alarm is field-wired from the thermostat interface
board to signify a controller alarm has occurred.
351579-YTS-C-0111
Table 3: Simplicity® Control Inputs
NameRangeResolutionPrecisionDescription
Y118 - 30 VACOn - Off+/- .5 VACRequest for the first stage of Cooling (24 VAC sense) Tstat Screw Terminal
Y218 - 30 VACOn - Off+/- .5 VACRequest for the second stage of Cooling (24 VAC sense) Tstat Screw Terminal
Y318 - 30 VACOn - Off+/- .5 VACRequest for the third stage of Cooling (24 VAC sense) Tstat Screw Terminal
Y418 - 30 VACOn - Off+/- .5 VACRequest for the fourth stage of Cooling (24 VAC sense) Tstat Screw Terminal
W118 - 30 VACOn - Off+/- .5 VACRequest for the first Stage of Heating (24 VAC sense) Tstat Screw Terminal
W218 - 30 VACOn - Off+/- .5 VACRequest for the second Stage of Heating (24 VAC sense) Tstat Screw Terminal
W318 - 30 VACOn - Off+/- .5 VACRequest for the third Stage of Heating (24 VAC sense) Tstat Screw Terminal
G18 - 30 VACOn - Off+/- .5 VACRequest for the Fan (24 VAC sense) Tstat Screw Terminal
R18 - 30 VAC-CEarth Ground--These terminals are a ¼' Faston and a Thermostat Screw terminal.
--Exhaust Fan contactor output (Relay Contacts - 24 VAC/120 VAC)
6 "Seven Segment LED /W decimal point"
Compressor number one contactor output
(Relay Contacts - 24 VAC/120 VAC)
Compressor number two contactor output
(Relay Contacts - 24 VAC/120 VAC)
Compressor number three contactor outpu t
(Relay Contacts - 24 VAC/120 VAC)
Compressor number four contactor output
(Relay Contacts - 24 VAC/120 VAC)
2 - 10 VDC.1 VDC.1 VDCThis is a 2 - 10 volt output capable of 10 ma
2 - 10 VDC.1 VDC.1 VDCThis is a 2 - 10 volt output capable of 10 ma
10Johnson Controls Unitary Products
351579-YTS-C-0111
SIMPLICITY
The paragraphs below provide a definition of, and specify the
function related to, each of the parameters that are fieldadjustable using the interfaces available. The Millennium
is shipped from the factory with the necessary options preprogrammed as indicated by the model nomenclature. It is
always a good practice, though, to verify that the correct
parameters are properly configured for the unit you are
commissioning. You can find a complete list of field-adjustable
parameters in the “Settable System Parameters”.
For a description of the parameters, see the Settable System
Parameters below and Table 5.
INTERACTING THROUGH THE MILLENNIUM
SIMPLICITY
SET THE CLOCK
• Power up the unit.
• Press the Program button [upper left].
• Press the Test/Up button [upper right]. Hold it in and it will
step through the parameters, or push in to advance one
parameter at a time. Advance to parameter 63, Hours.
• Press Change [lower left] Press Up [upper right] or Down
[lower right] to the correct hour [24 hour time].
• Press Change to en te r th e ne w valu e.
• Press Up to get to parameter 64, Minutes.
• Press Change.
• Press Up or Down to get to the correct minute value. Press
Change to enter the new value.
• If you are done changing parameters, press Program to
exit the program mode.
PARAMETER SETTING
The buttons allow the operator to go to a specific parameter and
to view and change the data in that parameter.
• To enter the parameter setting mode, press the Program
button. The control will display the current parameter number in the two-digit display, and the present value of that
parameter in the four-digit display.
• To change to another parameter, press the /Up or /Down
button to move to the address of the desired parameter.
The present value of that parameter will display.
• To change the data, press the /Change button. The value
will flash. While it is flashing, press the /Up or /Down button to increase or decrease the value.
• When the desired new value is showing, press the
/Change Data button again to tell the control to store the
new value. You can verify that the new value is in place
when the value stops flashing.
• To exit Program mode, press the Program button again.
®
PROGRAMMING OPTIONS
®
®
Unit
®
INITIAL STARTUP OPTIONS
Commissioning a new Millennium® installation requires some
field adjustments to the Simplicity
these adjustments simply involve setting up the various
®
control program. Most of
setpoints that are specific to your customer’s needs (i.e.
building pressure) or enabling some extended options that are
integrated into the Simplicity control. Also, if there are field
changes, i.e. a modulating power exhaust option, the control
configuration will need to be modified for the new option.
METRIC OPERATION (ENGLISH)
The factory default for this option is OFF. The metric (SI)
conversions are part of the controller software; when the Metric
parameter is selected, temperature setpoints and readings will
convert to Centigrade (°C).
SETTABLE SYSTEM PARAMETERS
The following headings list each parameter’s name and its
default setting. The control is set at the factory for the options of
the specific unit; if a replacement control is being installed, the
entire parameter set must be matched to the unit. The number
in (parentheses) is the value of a parameter in an un-configured
control.
Compressors - (2) - This tells the control the number of
compressors available. The Factory Default [the value in an
unconfigured replacement control] is 2 and can be adjusted
from 1 to 4.
Heat Stages - (2) - This tells the control the number of heating
stages available. This parameter may be set from 0 to 3. The
default setting is 2 stages of heat. When modulating gas heat is
installed the parameters is always set to 2.
Hydronic Heat - (OFF) - This tells the control that a Hot Water Coil
is installed. If the control is going to modulate the Hot Water Va lve
it will also turn on the Heat One output. This is to energize the VAV
heat relay for the VAV boxes. The default is OFF for this option. If
this parameter is enabled, remember to set the Hydronic Heat First
and Second Stage Setpoints and the Economizer Loading
Setpoint found in the ”Simplicity
Stage 1 Hydronic Heat SAT Setpoint - (120 °F) - When the
Hydronic Heat option is enabled, the control will maintain this SAT
setpoint for a call for first stage Heating, by modulating the Hot
Water Valve. This is the reset temperature when operating a VAV
unit in the Heating mode. The reset range for SAT setpoint is from
80 °F to 180 °F with 120 °F shipped as the default.
Hydronic Heat Reverse Actuated Valve - (OFF) - Th is setting
is to allow convenient use of reverse acting w at er valves;
setting this parameter to (ON) will change the signal to 2VDC =
open, 10 VDC = closed.
SAT Control for Cooling - (ON) - This tells the control if it is
going to do excessive SAT monitoring and tripping or not, for
Cooling. The SAT should be maintained in an acceptable
range in order to achieve reliable compressor operation. The
compressor trip limits are user adjustable between 40 °F and
65 °F in one degree increments. The default cooling trip
limits are 50 °F for stages 2-4, and 45 °F for stage 1. When
the SAT drops below the trip limit for each respective
compressor, that compressor is locked out and a 5 minute
ASCD is initiated for that compressor. If this option is
enabled, remember to set the compressor cooling limits for
low limit trip.
®
Setpoints”.
Johnson Controls Unitary Products11
351579-YTS-C-0111
Power Exhaust - (ON) - This tells the control if it has the Power
Exhaust option installed.
Economizer Damper Position for Exhaust Fan to turn ON
(Non-Modulating PE Only) - (60%) - This tells the control the
Economizer Damper position to turn on the Exhaust Fan. This
value is based on the 0%-100% output drive signal from the
controller to the economizer damper actuator.
Economizer Damper Position for Exhaust Fan to turn OFF
(Non-Modulating PE only) - (20%) - This tells the control the
Economizer Damper position to turn off the Exhaust Fan. This
value is based on the 0%-100% output drive signal from the
controller to the economizer damper actuator.
Modulating Exhaust - (OFF) - This tells the control if the
Power Exhaust is Modulating or not. A modulating exhaust will
be equipped with a Building Pressure Sensor [BPS]. A NonModulating exhaust will look to the economizer damper position
to energize the EXD output. If the sensor gets disconnected, or
fails, an alarm is set. The alarm can be turned off by correcting
the sensor problem (or; by turning off this option). The control is
not in this case self-configuring. It will not automatically use the
Building Pressure Sensor if the sensor is connected.
Exhaust VFD Installed - (OFF) - If the unit has a VFD, the EXD
output will be enabled when the supply fan is ON.
Exhaust Damper Position For The Exhaust Fan To Turn On
(Modulating Only) - (80%) - This tells the control the Exhaust
Damper position at which to turn on the Exhaust Fan. This
value is based on the 0%-100% output drive signal from the
controller to the damper actuator.
Exhaust Damper Position For Exhaust Fan To Turn Off
(Modulating Only) - (20%) - This tells the control the Exhaust
Damper position to turn off the Exhaust Fan. This value is
based on the 0%-100% output drive signal from the controller to
the damper actuator.
Building Pressure Setpoint - (+0.100”WG) - This is the
pressure setpoint the control will maintain when op era ting a
Power Exhaust. The Building Pressure Setpoint is adjustable
from -0.200”WG to +0.200”WG. The factory programmed default
is +0.100”WC. This setpoint is used when the exhaust control is
implemented as Proportional Control (with a Modulating Exhaust
Air Damper or VFD controlled from building static pressure), or
as a Two-posi tion Co ntrol using bui lding static (Power Exhaust
Fan controlled on-off from building static pressure).
Economizer - (ON) - This tells the control that there is an
Economizer Installed.
Economizer Min Position - (20%) - This tells the control what
the minimum outdoor damper position will be for the Occupied
mode. Adjustable from 0-100%, the Economizer Minimum
Position default is 20%.
Economizer First Stage Setpoint - (55 °F) - This tells the
control what Supply Air Temperature to maintain for a call for
first stage of cooling. This is used only during Constant Volume
cooling mode with Economizer operation. The setpoint is set at
55 °F with an adjustable range from 40 °F to 65 °F.
Economizer Second Stage Setpoint - (50 °F) - This tells the
control what Supply Air Temperature to maintain for a call for
second stage of cooling. This is used only during Constant
Volume cooling mode with Economizer operation. This setpoint
is set at 50 °F with a range from 40 °F to 65 °F.
Outside Air Humidity (OAH) Sensor Enable - (OFF) - This
setting tells the control that it is expected to use Outside Air
Enthalpy (calculated from Outside Air Temperature and Outside
Air Relative Humidity sensed values) to decide if Outside Air
can be used for cooling.
The control is self-configuring to the best available decision
strategy for free cooling availability. For example, if it detects
that OAT and OAH and RAT and RAH sensors are all
connected and reliable, will self-configure for Differential
Enthalpy operation. If one of the return air sensors should fail,
the control will reconfigure for Outside Enthalpy operation, etc.
If the OAH Sensor Enable option is turned ON, it means that the
Outside Enthalpy Operation, or better decision strategy, is
expected (and supported by installed sensors). If the
appropriate sensors are not installed, or one of them failed, a
sensor failure alarm is set. The alarm can be turned off by
turning off the OAH Sensor Enable option. Thus, the option
setting is used to reflect the desired operation and mainly to
control sensor failure alarms
.
The option setting can be viewed as specifying that (the selfconfigured economizer decision strategy has to be at least this,
or better, otherwise an alarm is set). If the option is OFF, the
control still may self configure to Outside Enthalpy Operation, or
even to Differential Enthalpy Operation (if all needed sensors
are available), but this option setting will allow also the decision
strategy based on only OAT (in case other sensors fail, or are
not installed) without setting an alarm.
Outside Air Enthalpy Setpoint - (27 BTU/LB) - This tells the
control an outside air enthalpy limit. Below this limit, outside air
is available for cooling. See enthalpy chart. This parameter
uses a one BTU/LB hysteresis on each side of the limit. The
limit is preset to 27 BTU/ LB with an adjustable range from 10 to
50 BTU/LB.
Return Air Humidity (RAH) Sensor enable - (OFF) - This tells
the control that it will compare Outside Air Enthalpy (calculated
from Outside Air Temperature an d Outside Air Relative
Humidity sensed values) and Return Air Enthalpy (calculated
from Return Air Temperature and Return Air Relative Humidity
sensed values). The control will use the air stream with the
lower enthalpy for cooling.
The control is self-configuring to the best available decision
strategy for free cooling availability . For example, if it detect s that
OA T and OAH and RAT and RAH sensors are all connected and
reliable, will self-configure for Differential Enthalpy operation. If
one of the return air sensors should fail, the control will stop using
rules that involve RAH and set an alarm.
If the RAH Sensor Enable option is turned ON (and supported
by installed sensors), Differential Enthalpy Operation can be
enabled. If the appropriate sensors are not installed, or one of
them failed, a sensor failure alarm is set. The RAH alarm can
12Johnson Controls Unitary Products
351579-YTS-C-0111
be turned off by turning off the RAH Sensor Enable option.
Thus, the option setting is used to reflect the desired operation
and mainly to control sensor failure alarms.
Economizer Loading to Control SAT - (ON) - This tells the
control if it is going to use Economizer Loading to control
excessive SAT [supplying warmer outside air to keep SAT from
going too low]. This parameter is only applicable outside the
normal Economizer operation. During the Economizer
operation, the loading function is always performed and is an
integral part of the control algorithm.
Duct Static Setpoint - (1.5”WG) - This parameter is applicable
only to V A V mode of operation. This is the pressure setpoint that
the control will maintain when operating the fan in a VAV unit.
This setpoint is adjustable between 0”WG and 5”WG with the
default set to 1.5”WG.
Duct Static High Limit Setpoint - (4.5”WG) - This parameter is
applicable only to V AV mode of operation. This tells the control at
what Static Pressure to shu t down the unit due to a Fan control
failure. This setpoint is to insure that we don't continue to operate
the Fan with an Inlet Guide Vane or VFD problem that could
cause the ductwork to fail from duct pressure. When the St a tic
Pressure reaches this setpoint (4.5”WG default), the control will
drive the supply fan control output to zero. If the static pressure
does decrease below the “Duct St at ic High Li mit Setpoi nt” within
3 seconds after decreasing the supply fan control output to zero,
the control will resume normal operation. If there is no change in
static pressure after 3 seconds, the control will generate a High
Duct Static alarm, shut do wn all the outputs including the Fan and
shut down the unit. The alarm is written to the Error History Buffer
and will trigger storing a snapshot of Points Screen data alon g
with a date and time stamp. In networked applications, the ala rm
flag is readable by the network. This parameter can be adjusted
from 0”WG to 5”WG with the factory default set to 4.5”WG.
The customer must be aware of the duct pressure design limit,
and what the duct pressure sensor will be reading when the peak
pressure is reached [the pressure pickup tube may not have
been located at the place of highest pressure in the system].
The alarm must be reset (after the problem that caused the
alarm is corrected) by resetting the controller by turning power
to the unit off and back on, or by reset command issued by an
external connection.
Morning Warm Up - Is inferred from the entries in
Occupied/Unoccupied
Occupied - (from settings in Weekly Schedule and Holiday
Schedule Tables 11 and 12.) - See discussion in Sequence of
Operation.
Unoccupied - (from settings in Weekly Schedule and Holiday
Schedule Tables 11 and 12.) - See discussion in Sequence of
Operation.
VAV High Temperature SAT Setpoint for Cooling - (60 °F) -
The control will maintain this SAT when operating in VAV mode
with a thermostat that is calling for first stage cooling. This
parameter may be adjusted from 40 °F to 70 °F with 60 °F set
as the default value.
VAV Low Temperature SAT Setpoint for Cooling - (55 °F) -
The control will maintain this SAT when operating in VAV mode
with a thermostat that is calling for second stage cooling. This
parameter may also be adjusted from 40 °F to 70 °F with 55 °F
set as the default value.
VAV SAT Reset Setpoint - (72 °F) - This parameter is used
only in V AV mode with a Space Sensor. The control will switch
from the VAV Lower Cooling SAT Setpoint to the VAV Upper
Cooling SAT Setpoint when this Space Temperature Setpoint
minus 0.5 °F is reached. The control will switch from High
setpoint back to Low setpoint when the space temperature gets
2 °F above this setpoint. This is SAT reset based on Space
Temperature. The reset occurs in both Occupied and
Unoccupied modes and may be adjusted from 40 °F to 85 °F.
The factory default is 72 °F.
V AV Occupied Heating - (OFF) - This option applies in VAV
mode with a Space Sensor and does not affect VAV Occupied
heating if requested by a thermostat. When this option is
toggled on, a VAV unit is able to operate heating in the occupied
mode as long as it is operating with a Space Sensor. If the
Space Temperature drops to 2 °F below the VAV SAT Reset
Setpoint the control will read the RAT. If the RAT is below the
Morning Warm Up RAT Setpoint the unit will enter the Occupied
Heating mode. Operation is the same as Morning Warm Up.
This parameter is factory set to OFF.
Comfort Ventilation Mode - (OFF) - Comfort Ventilation is a
SAT control mode that controls SAT during “satisfied” periods in
a fairly wide temperature band, using mostly Outside Air, and
also cooling and heating stages as necessary. It is available
only on the Constant Volume unit.
To enable Comfort Ventilation, the programmable parameter
“Comfort Ventilation Mode” must be set to ON (default setting is
OFF).
For a detailed explanation of Comfort Ventilation, refer to the
Sequence of Operation in this manual.
Comfort Ventilation High Supply Air Setpoint - (80 °F) - This
is the High Limit Setpoint for the Comfort Ventilation mode. For
a stable operation of Comfort Ventilation function, the High
Supply Air Setpoint should be set 10.0 °F or more above the
Low Setpoint.
Comfort Ventilation Low Supply Air Setpoint - (70 °F) - This
is the Low Limit Setpoint for the Comfort Ventilation mode. For
a stable operation of Comfort Ventilation function, the Low
Supply Air Setpoint should be set 10.0 °F or more below the
High Setpoint.
Dirty Filter Switch - (OFF) - This tells the control that a Dirty
Filter Switch is connected to it. The control will wait for ten
minutes after the switch has closed before declaring a Dirty
Filter Alarm. The alarm is written to the Error History Buffer. In
networked applications, the error flag is readable by the
network. The alarm will automatically reset when the error
condition is corrected.
The default is OFF.
Johnson Controls Unitary Products13
351579-YTS-C-0111
UnOcc.
Htg.
Occ.
Htg.
UnOcc.
Clg.
Occ.
Clg.
Heating Lockout on OAT - (75 °F) - This is the Outside Air
Temperature Setpoint that the control will use to lock out Heating
when the OA T is a bove this setpoint. There is a one-degree
hysteresis on each side of the setpoint. This parameter is
adjustable between 0 °F and 100 °F with the default set to 75 °F.
Heating Lockout on OAT affect s only staged heating, it does not
affect hydronic heat. If the heating is energized when OAT
reaches this setpoint, the Status LED will indicate the lockout
condition immediately, but the control will finish the heating
mode and then lock out the heating.
Note that a Heating Lockout on OAT may occur while the
control is in a heating mode and there is a demand for heating.
If the OAT then decreases below the lockout setting while the
call for several heat stages exists, the heat stages will turn on
simultaneously. This is considered acceptable as this situation
is not expected to occur frequently.
Cooling Lockout on OAT - (45 °F) - This is the Outside Air
Temperature Setpoint that the control uses to lock out Cooling
when the OAT is below this setpoint. Adjustable from 0 °F to
100 °F, the default is 45 °F.
Unoccupied Heating Setpoint - (60 °F) - This value is the
Unoccupied Heating Setpoint. It is used in both CV and VAV
mode of operation (in VAV, it controls Unoccupied heating with
a Space Sensor).
Figure 5: Sequence Of Setting The Set Points
The control will attempt to correct wrong temperature overlap
settings; for example, if a change is made that would put
Occupied Heating above Occupied Cooling, the Occupied
Cooling setting will change to stay above the heating setpoint.
Occupied Heating Setpoint - (68 °F) - This value is the
Occupied Heating Setpoint. It is used only in CV mode of
operation. Its relationship to the related setpoints is as defined
in the Unoccupied Heating Setpoint paragraph above.
Unoccupied Cooling Setpoint - (85 °F) - This value is the
Unoccupied Cooling Setpoint. It is used in both CV and VAV
mode of operation (in VAV, it controls Unoccupied cooling with a
Space Sensor).
Occupied Cooling Setpoint - (72 °F) - This value is the
Occupied Cooling Setpoint. It is used only in CV mode of
operation. Its relationship to the related setpoints is as defined
in the Unoccupied Heating Setpoint paragraph above.
[Input] FSI (Hot Water Freeze Protection) - (OFF) - This
option is used only on rooftop units with hydronic heat
(Hydronic Heat Option is turned ON). Freeze protection should
always be placed on units that use hydronic heating. When the
control senses 24VAC, the control will turn on the Hot Water
valve to 100%. The control will continue to drive the valve at
100% until five minutes after the switch has opened. Then the
valve will revert to normal operation. If the control is operating
the Fan, it will close the Economizer fully until the freeze
condition is over. If the fan is off and the RA T drops below 40 °F,
the Hot Water Valve will turn on 100%.
Supply AirTemp (SA T) Alarm Setpoint for Cooling - (0 °F) - If
the SAT does not drive below this setpoint when all stages of
compression are operating and 10 minutes has elapsed since
the last compressor was energized, the control will declare a
Cooling SAT Failure Alarm.
The alarm is written to the Error History Buffer. In networked
applications, the alarm flag is readable by the network.
The alarm will reset automatically if the SAT does decrease
below the setpoint (the alarm condition no longer exists), or
when a compressor is turned off (the control does not request
all compressors operate). The SAT Alarm Setpoint for Cooling
can be adjusted from 50 °F - 80 °F. If the value is set to 0 °F
(default) this feature is disabled.
Before the control declares an error, it will read the OAT and the
Economizer position. If the OAT is more than 20 °F warmer than
the setpoint and the Economizer is open more than 20%, the
control will close the Economizer for 10 minutes and then read
the SAT. If the SAT falls below the setpoint, the control will
declare an Economizer Minimum Position alarm. The control
will keep the Economizer closed and finish the Cooling mode.
After the Cooling mode has been satisfied, the control will move
the Economizer back to the minimum position.
Supply Air Temp (SAT) Alarm Setpoint for Heating - (0 °F) -
The SAT must drive above this setpoint when all stages of heating
are operating and 10 minutes has elapsed since the last stage was
energized. If this does not happen, the control will declare a
Heating SAT Failure Alarm. The alarm is written to the Error
History Buffer. In networked applications, the alarm flag is readable
by the network. The alarm will reset automatically if the SAT does
increase above the setpoint (the alarm condition no longer exists),
or when a heating stage is turned off (the control does not request
all heat stages to operate).
The SAT Alarm Setpoint for Cooling can be adjusted from 70 °F 120 °F. If the value is set to 0 °F (default) this feature is disabled.
Before the control declares an error, it will read the OAT and the
Economizer position. If the OAT is more than 20 °F colder than
the setpoint and the Economizer is open more than 20%, the
control will close the Economizer for 10 minutes and then read
the SAT. If the SAT rises above the setpoint, the control will
declare an Economizer Minimum Position alarm. The control
will keep the Economizer closed and finish the Heating mode.
After the Heating mode has been satisfied, the control will move
the Economizer back to the minimum position.
Unoccupied Override Time Period - (60 min) - The
Unoccupied Override Time Limit function will determine how
long the unit will operate in the Unoccupied Override mode
when the Override button is pressed on the Space Sensor.
14Johnson Controls Unitary Products
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.