York Z Millennium R410A Technical Guide

351579-YTS-C-0111
ISO 9001
Certified Quality
Management System
TECHNICAL APPLICATION
AND
PROGRAMMING GUIDE
MILLENNIUM® SINGLE PACKAGE ROOFTOP UNITS 25, 30 & 40 TON EQUIPPED WITH
SIMPLICITY
®
ELITE CONTROLS

MILLENNIUM® 25-40 TON SINGLE PACKAGE COMMERCIAL ROOFTOP UNIT EQUIPPED WITH SIMPLICITY® CONTROLS

This manual includes application, programming and service procedures for the Millennium® 25-40 Ton Single Package Commercial Rooftop Unit equipped with Simplicity These procedures are the same for all 25-40 Ton Millennium® Rooftop units in this series except as noted.
This manual covers Simplicity information please refer to the following.
®
controls only, for unit installation
®
Controls.

RECOMMENDED TECHNICAL AND INSTALLATION AIDS

Millennium® 25-40 Ton Single Package Installation and Operation Manual - 524158
®
Millennium
25-40 Ton Technical Guide - 246837
351579-YTS-C-0111
TABLE OF CONTENTS
MILLENNIUM® 25-40 TON SINGLE PACKAGE COMMERCIAL ROOFTOP UNIT EQUIPPED WITH
SIMPLICITY® CONTROLS . . . . . . . . . . . . . . . . . . . .1
RECOMMENDED TECHNICAL AND
INSTALLATION AIDS . . . . . . . . . . . . . . . . . . . . . . . . 1
THE MILLENNIUM® SIMPLICITY® CONTROL . . . .3
INTRODUCTION AND OVERVIEW. . . . . . . . . . . . . . . . . 3
DIGITAL LINGO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
ANALOG TO DIGITAL CONVERTER . . . . . . . . . . . . . . . 4
COMMUNICATIONS BUS . . . . . . . . . . . . . . . . . . . . . . . . 5
OPTIONAL Simplicity
COMPONENT DESCRIPTION. . . . . . . . . . . . . . . . . . . . . 5
®
LINC TRANSLATOR. . . . . . . . . . 5
SIMPLICITY® PROGRAMMING OPTIONS . . . . . . .11
INTERACTING THROUGH THE MILLENNIUM®
SIMPLICITY® . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
INITIAL STARTUP OPTIONS . . . . . . . . . . . . . . . . . . . . 11
METRIC OPERATION (ENGLISH) . . . . . . . . . . . . . . . . 11
SETTABLE SYSTEM PARAMETERS . . . . . . . . . . . 11
MILLENNIUM® SEQUENCE OF OPERATION . . . .18
OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
RUN SEQUENCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
UNIT CONTROLS SEQUENCE. . . . . . . . . . . . . . . . . . . 18
VARIABLE AIR VOLUME UNIT (VFD & IGV) . . . . . . . . 20
OCCUPIED / UNOCCUPIED / MORNING WARM-UP . 21
UNIT CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
HEAD PRESSURE CONTROL . . . . . . . . . . . . . . . . . . . 26
SEQUENCE OF OPERATION - FOR HEAD PRESSURE
CONTROL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
INTELLI-START . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
DEVICES AND RULES . . . . . . . . . . . . . . . . . . . . . . . . . 27
COMFORT VENTILATION MODE. . . . . . . . . . . . . . . . . 28
HYDRONIC HEAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
COOLING LOCKOUT ON OAT . . . . . . . . . . . . . . . . . . . 29
WATER COIL FREEZE STAT (FSI). . . . . . . . . . . . . . . . 29
CV OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
THERMOSTAT OPERATION FOR COOLING WITH Y1,
Y2, Y3 AND Y4 INPUTS. . . . . . . . . . . . . . . . . . . . . . . . 30
OPERATION FOR HEATING WITH W1, W2, AND W3
INPUTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
SENSOR OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . 30
TYPES OF SPACE SENSORS . . . . . . . . . . . . . . . . . . . 31
VAV OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
SUPPLY DUCT PRESSURE CONTROL ALGORITHM. 34 MORNING WARM UP / VAV OCCUPIED HEATING
CONTROL ALGORITHM . . . . . . . . . . . . . . . . . . . . . . . 34
CONTROLLING EXCESSIVE SAT (SUPPLY AIR
TEMPERATURE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
SAT SETPOINTS USED DURING COOLING WITH
ECONOMIZER OPERATION . . . . . . . . . . . . . . . . . . . . .36
DEMAND VENTILATION . . . . . . . . . . . . . . . . . . . . . . . . .39
EXHAUST OPERATION . . . . . . . . . . . . . . . . . . . . . . . . .40
SCHEDULING OPERATION . . . . . . . . . . . . . . . . . . . . . .41
COMPRESSOR STATUS MONITORING . . . . . . . . . . . .41
TROUBLESHOOTING A MILLENNIUM®
SIMPLICITY® CONTROL . . . . . . . . . . . . . . . . . . . . 43
STATUS LED CHART . . . . . . . . . . . . . . . . . . . . . . . . . . .43
FAILURE MODES AND DEFAULT OPERATION . . . . . .43
SENSOR FAILURES AND DEFAULT OPERATION . . . .43
SYSTEM ERRORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
LIST OF FIGURES
Fig. # Pg. #
1 SIMPLICITY® CONTROLLER. . . . . . . . . . . . . . . . . . . 3
2 SIMPLICITY® CONTROLS PUSH BUTTONS . . . . . . 3
3 ANALOG TO DIGITAL CONVERTER . . . . . . . . . . . . . 4
4 VFD CONTROL WIRING. . . . . . . . . . . . . . . . . . . . . . . 8
5 SEQUENCE OF SETTING THE SET POINTS . . . . . 14
6 COMFORT VENTILATION ECONOMIZER
CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
7 SAT CONTROL BAND . . . . . . . . . . . . . . . . . . . . . . . 34
LIST OF TABLES
Tbl. # Pg. #
1 ACRONYMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 INPUT SIGNAL TO Y1 ACTUATOR POSITION . . . . . 8
3 SIMPLICITY® CONTROL INPUTS . . . . . . . . . . . . . . . 9
4 SIMPLICITY® CONTROL OUTPUTS . . . . . . . . . . . . 10
5 SETTABLE SYSTEM PARAMETERS. . . . . . . . . . . . 16
6 COOLING STAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
7 IGNITION CONTROL BOARD FLASH CODES . . . . 23
8 MODULATING GAS HEAT . . . . . . . . . . . . . . . . . . . . 24
9 MODULATING GAS HEAT CONTROL BOARD FLASH
CODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
10 COMPRESSOR MINIMUM OFF TIMES . . . . . . . . . . 30
11 WEEKLY SCHEDULE . . . . . . . . . . . . . . . . . . . . . . . . 34
12 HOLIDAY SCHEDULE. . . . . . . . . . . . . . . . . . . . . . . . 35
13 ALARM DEFAULT CODES . . . . . . . . . . . . . . . . . . . . 42
14 STATUS LED CHART . . . . . . . . . . . . . . . . . . . . . . . . 43
2 Johnson Controls Unitary Products

THE MILLENNIUM® SIMPLICITY® CONTROL

Program
Alarms / Change Data Address / Down
Test / Reset / Up

INTRODUCTION AND OVERVIEW

Welcome to the new Millennium® Simplicity® control, a digital control system designed specifically for the Millennium® 25 to 40 Ton single package rooftop unit. The Simp licity 72 monitored and controlled input and output points. The control logic of the Simplicity
®
extends on the rules built in to the Synthesys control, and provides character displays in additi on to LED flashes to display information to the technician.
The Simplicity
®
digital control performs all of the control and monitoring functions that were originally done by separate discrete relays, controls, and interlocking hardware. This reduces manufacturing, service, and maintenance costs. The
Simplicity
®
digital controller includes sophisticated control of the individual components of the HVAC cooling/heating unit, and has built-in rules that protect those components and optimize the control to its environment. The cooling and heating modes are protected against frequent cycling, slugging, multiple restarts, etc.
®
is composed of
351579-YTS-C-0111
®
The Millennium
Simplicity® control is resistor-configured for Constant Volume (CV) units or Variable Air Volume (VAV) units. The option settings for a specific option configuration will be made as part of unit test at the factory; however, if there is doubt about how a unit is responding in the field, check the option setting for the unexplained action.
If connected to a network, the control requests an address by a press of the Address/Down button.

DIAGNOSTICS VIA LED

There is an LED on the board that shows the status of the control and alarms (see Status LED Table). There are two character displays, one 2-digit and one 4-digit, to indicate details of run conditions and alarms (see Alarms Table in the Trouble Shooting section of this manual).
When the Alarm / Change Data button (See Figure 2 Simplicity
Controller Push Buttons) is pushed and released one time within
five seconds, it will re-enunciate the last five alarms on the Display.
®
®
Figure 1: Simplicity
Controller
One result is that the system may not immediately respond as you expect. For example, internal digital timers may delay the start of a compressor even though the thermostat calls for cooling. The control may be in the middle of a timing sequence; without the observer knowing what has already happened and the status of current inputs, the system may take action not expected by the tech.
®
In the Simplicity
• a list of user-selected option settings and setpoints recorded within the control;
control, there are:
• inputs monitored by the Simplicity®;
• specific fixed rules and timings built in to the control
• outputs to compressors, heat, economizers, and other options.
The Simplicity
®
has a real-time clock function, with minimum of
ten hours “Time-of-day retention” with unit power off.
Johnson Controls Unitary Products 3

Figure 2: Simplicity® Controls Push Buttons

When this button is pushed and released two times within five seconds, it will clear all stored alarms.
The error details for most conditions are stored in summary in the Simplicity
®
Control and can be accessed by the digital display, personal computer interface, or Palm Pilot (Some interfaces still in development).
Diagnosing requires patience because of internal timings. Normal observable conditions are the same - contactor 1M pulled in, compressor 1 running - but the control does not identify what it has just done or is about to do. The Simplicity
®
control will take action according to its internal rules even though action requests come from smart thermostats. A call for cooling, for example, will be compared with supply air temperature before energizing a cooling stage.

ERROR HISTORY

®
The Simplicity
control stores up to 5 of the most recent alarms
in a First In, First Out (FIFO) manner. As the control collects
351579-YTS-C-0111
BINARY NUMBER EQUIVALENT
0 1 2 3 4 5 6 7------------- n
alarms, it will overwrite the oldest alarm after the history buffer becomes full.
Some system errors will initiate a controlling response as well as being stored in the error memory buffer. See the “Troubleshooting” chapter in this manual for a detailed description of how controller errors are handled.
Data items stored for maintenance / run history, in addition to Alarms:
• Accumulated run times for each compressor and heat st age
• Unit model number
• Unit serial number
•Unit Name

DIGITAL LINGO

This training manual is intended to help you with the commissioning process by illustrating the use of tools like the control’s digital input and software engineered specifically for starting up and servicing a Millennium
You should become familiar with some common terminology and lingo used in the digital controls industry. (If you are familiar with the Synthesys controller, the logic of the Simplicity® will be familiar territory.)
®
rooftop unit.
depending on how long the sensed value remains away from its desired setpoint.
Fortunately, you do not have to determine all of these parameters since they are pre-programmed at the factory. You need only to set a desired setpoint and ensure that the inputs and outputs are properly wired and working. This is referred to as commissioning a system.

ANALOG TO DIGITAL CONVERTER

Computers can only understand a simple binary language. Remember, “binary” means two states - ON or OFF. Analog (continuous) values of voltages, currents, and resistances are supplied by sensors and transducers to the control. These values must be converted in to a binary code so that the computer can understand them. This conversion process is performed through a combination of hardware and software. For example, the 0-5VDC analog value from a static pressure transducer is divided into thousands of steps with a binary coded number, often called “counts”, assigned to each step.
If this is your first exposure to the world of digital controls you may experience a lot of new terms, acronyms and technical lingo commonly used in the controls industry. For example, the
Simplicity
®
input and output hardware points are described as analog, relating to a continuous scale of value readings such as a temperature sensor ranging from -400F to 1600F range, or binary, meaning 2-states, either on or off, open or closed, true or false, one or zero. The term “digital” also means two states and its use is often interchanged with “binary”. These points may be either factory- or field-set.

THE PI ALGORITHM

Another common “digital controls” term is the PI algorithm or Proportional-Integral control loop. The PI algorithm is a continuously updated math calculation that the controller uses to modulate an analog output point. For example, a variable speed drive uses a PI loop to maintain a desired setpoint (in this case, a duct static pressure value). The algorithm takes into account several parameters to calculate the output. The PI loop needs parameters such as the proportional operating bandwidth, integral time constant, deadband, desired setpoint value, sensed input value(s), start up ramp time, initial start value, maximum output control value, a status point to initiate the control action (i.e. a fan ON status), Direct or Reverse Controlling Action, and several other parameters to calculate a simple 0 to 100% analog output control. The PI algorithm is also called a PI loop because it “loops” the output back to the input (feedback) and determines a new output value based on the “error” or difference between the setpoint value and the sensed input value, and how that difference relates proportionally to the 0 to 100% output value. Time is the ”integral” constant that is factored in to increase or decrease the controlling output action
Figure 3: Analog to Digital Converter SOFTWARE TERMINOLOGY
A digital controller handles its control functions through software programming rather than with interlocking hardware and wiring. The software then becomes key to how controlled functions are handled. Software is a set of statements (referred to as the “program”) that define the function of the controller’s internal microprocessor computer.
Software procedurally tells the computer the sequence and order of tasks that need to be performed using a language that the computer can understand.
Software is stored in a computer’s memory. There are several types of memory in a computer. Each type has a specific function to perform.
4 Johnson Controls Unitary Products
351579-YTS-C-0111
EPROM - This is “nonvolatile” memory , meanin g it will not be erased on a power loss. This memory is usually programmed prior to assembly of the controller. Since this me mo ry is n ot changed during normal operation of the Simplicity
®
control, only
basic operation instructions are stored in this type of memory. EEPROM (Double “E” Prom) - Is also non-volatile, but this
type of memory requires a specia l process t o be writt en to. Thi s memory can be written to and changed by the microprocessor. This is the type of memory that the control program is stored in the Simplicity® control.
ROM - Read Only Memory is non-volatile but can not be written to. This memory is programmed only once before the controller is assembled. ROM contains instructions specifically for the internal microprocessor computer in the controller.
FIRMWARE - “Firmware” is software, program instructions or applications, but stored in EPROM or ROM memory.
RAM - Random Access Memory is a volatile memory. It will be erased when a power fail occurs. This memory is used as a kind of “scratch pad” for the controller. Temporary instructions and information such as an output controlling action like driving the economizer dampers open is stored here. When a power loss occurs or if the controller is sent a manual reset using a control push button, this memory is cleared and initialized.
Other filtered inputs include temperature and humidity sensors. You should be aware of this filtering effect because it will appear the controller is not acting as fast as you may think it should. In reality, it is acting and controlling on these time­averaged and weighted values.
®
FAULT TOLERANCE - Fault Tolerance of the Simplicity
control involves two issues: Hardware fault tolerance deals specifically with the electrical characteristics of the controller - how much over voltage or power surge the controller can withstand before damage occurs, and whether internal comparisons are verifying that the control is calculating and communicating properly. Software fault tolerance in this technology consists of comparing results to previous values and to reasonable values.

COMMUNICATIONS BUS

Networked communications may also be new to you. It relates to connecting several Millennium that can be monitored and controlled remotely from network computer workstations. You will find this typically on large installations where central control, monitoring, and energy management issues become a critical factor in operating a large complex such as a manufacturing facility.
®
The Simplicity
Control has the ability to be networke d in to a larger system using the MODBUS communication protocol. A communication protocol is simply a set of rules that determine how two systems communicate with each other over some medium such as a pair of wires, phone line, radio waves, etc. The transmission medium may also be called a gateway, pathway, or bus. An “open” protocol such as MODBUS is a publicly published set of rules that any equipment manufacturer can use to network into another manufacturers equipment.
®
rooftop units to a network

OPTIONAL Simplicity® LINC TRANSLATOR

OVERVIEW

The Simplicity
®
LINC translator operates as a Modbus® Client providing an interface between a BACnet® control system and devices that communicate using the Modbus® RTU protocol. The
Simplicity
®
LINC is preconfigured to provide an interface to YORK UPG products equipped with an Intelli-Comfort or Simplicity Elite™ controller and allows monitoring and control by a third-party BACnet
The Simplicity
®
Building Automation System (BAS).
®
LINC communicates using the Modbus® RTU protocol on one port and BACnet® MS/TP . By providing different communication protocols on the two ports, data can be retrieved from and provided to two different systems.
®
The Simplicity
LINC mounts inside the control panel of the UPG unit and utilizes 24 VAC power from the unit's control transformer. One port is connected to the UPG controller. The other port must be connected to the BACnet
The Simplicity operational data points from the controller and expose them on a BACnet
"The Simplicity
®
LINC translator is preconfigured to obtain
®
network.
®
LINC device is primary a control offered and configured by York's ESG (Engineering Systems Group). The device is designed to tie into and function with a BACnet
®
network.
®
MS/TP network. The device can be used with other BACnet® MS/TP systems, but a qualified controls contractor must be involved. UPG cannot support the Simplicity
®
LINC device beyond its hardware functionality and cannot guarantee functionality with other third party BAS devices."
®
Please refer to the Simplicity
LINC Installation Manual P/N
514066 and Application Guide Part Number 514067.

COMPONENT DESCRIPTION

This section describes the main components of Millennium®
Simplicity
controllers, hardware to handle signal input and control output and the Tstat interface terminals.

THE Simplicity® CONTROLLER

Simplicity
use in HVAC applications. The controller provides monitoring and control for either VAV or CAV for a total of 22 outputs.

WIRING AND TERMINATION, COMMUNICATIONS

Most connections to the Simplicity harnesses. There are also screw terminal connections for thermostat inputs and for communications via an RS-485 port.

COMMUNICATION ADDRESS

The communication address button (lower right of the display) is used to identify a Millennium “capture” the next available network address for that unit. Millenniums can be networked together for centralized
®
control. These components consist primarily of
®
is a proprietary , microprocessor-based controller for
®
Control are by wiring
®
rooftop unit to a network, and
Johnson Controls Unitary Products 5
351579-YTS-C-0111
monitoring and control. Much like we need a unique street address in our homes so we can receive our postal mail or emergency services, these units also need a unique address so the central Facilities Management System (FMS) can “talk” to each unit individually. The Simplicity
®
board has the model and serial number of the specific unit and has a memory space for a customer name to be applied. So the entire identification for a specific unit available to the network could be, for example, Y2AC04M3KDGABA, NCNM123456, SOUTH OFFICE.
The one-time commands to Override ASCD timers and/or to start Run Test can be issued by the Test/Reset/Up pushbutton. When this button is pushed and released within five seconds, the control will zero all ASCD’s for one cycle.

ACRONYMS

A number of acronyms are used throughout this training manual. These are specific to the Simplicity
®
control. They are also used in the T echnical Guide and Installation and Operation manuals. Acronyms are used to refer to input and output hardware points and software parameters such as timing delays and setpoints.
Table 1: Acronyms
Inputs Description
APS Air Proving Switch
IAQ Air Quality (CO2 Sensor)
BAS Economizer
BPS Building Pressure Sensor
C1O-C4O Compressor Status
DF Dirty Filter Status
DPS Duct Pressure Sensor
FSI Hot Water Coil Freeze Input
G Thermostat input for Fan
GV1-3 Monitors gas valve actuation call
HPS1-4
LPS1-4 Lim 1-3 Over-temperature limit switch from heat stages
OAT Outside Air Temperature
OCC Building Occupied Status
Purge Building Purge input
RAT Return Air Temperature SAT Supply Air Temperature
SD System Shutdown Connector OAH Outside Air Enthalpy RAH Return Air Enthalpy
SSA Setpoint Adjust
ST Space Temperature
W1, 2, 3 Heating Stages from Tstat
Y1,2 3, 4 Cooling Stages from Tstat
Passes BAS economizer command through to
Economizer output
High pressure switch monitored for
compressor discharge
Low pressure switch monitored for compressor
suction
Table 1: Acronyms (Continued)
Pushbuttons Description
Test/Reset / 'Up 'Test / control reset / Data value increment
Address / 'Down 'Change data / Data value decrement
Alarms / Advance data Show alarms / go to next data point
Program Go to program mode
Real Time Clock Incorporated on the board
Outputs Description
Status LED
Digital displays One 2-character and one 4-character
C1-C4 Cooling Outputs 1 through 4 CF1, 2 Cond Fan Bank 1, 2
ECO Economizer damper output EXH Exhaust Fan relay output
EXD
Fan
H1, 2, 3 Heating Stages 1, 2, and 3 output
HGR Hot gas reheat [future] HWV Hot Water Valve output VFD Supply Fan IGV or VFD Signal Output
X Alarm signal
Miscellaneous Description
AI Analog Input
AO Analog Output
BI Binary Input same as
BO Binary Output CAV Constant Air Volume VAV Variable Air Volume
VFD Variable Frequency Drive
IGV Inlet Guide Vane IAQ Indoor Air Quality
PI Proportional-Integral Control
ASCD Anti Short Cycle Timer (Compressor)
Flash to indicate alarm, otherwise
'heartbeat'
Exhaust Air Damper / Exhaust VFD Signal
Output
Supply Fan relay output [contactor or
permission relay]
The acronyms used throughout this training manual are listed in the Acronym Table 1. They are described in much more detail below.

INPUTS

There are two types of hardwired input points on the Simplicity control: Analog and Binary. These may be sensors, feedback, or adjustable setpoints. Typical analog inputs [AI] include Sp ace Temperature (ST), Supply and Return Air Temperatures (SAT, RAT), and Building Pressure Sensor (BPS). The binary inputs (BI) on the Millennium
®
Simplicity® use a dry contact input to determine the status of a monitored point. Typical BI points are Fan Status (APS), Filter Status (DFS), and Compressor Status (HPS1-4, LPS1-4, C1O-4O).
®
6 Johnson Controls Unitary Products
351579-YTS-C-0111

ANALOG INPUTS (AI)

Analog inputs require parameters that define the input’s characteristics. Attributes of an AI include the linear range, alarm limits, alarm differential, change of state (COS) enable, and filter weight. The input values may be overridden by a external system command or by using the input buttons on the Simplicity
®
board. This is useful to override current
conditions to test certain control functions or modes. BAS - Economizer override; if this option is enabled, an
external BAS system will control the economizer 2-10 VDC signal through this pair of terminals.
ST - Space Temperature sensor is a field installed sensor (PN: 025-38928-000 - w/ Override Button). The sequence of control for space temperature is different depending on whether the system is a VAV or CAV. See chapter on Sequence of Operation for a detailed description of the ST control modes.
SSA - Space Temperature Adjust is field installed. It is a slide adjustment located on a space sensor (PN: 025-38927-000) with a slide bar potentiometer . It is used to offset the space temperature setpoint. This slide-bar is a 10K ohm potentiometer. The programmable rang e fo r the Setpoint adjust is +/- 5 °F. For example, if the Space Temperature setpoint is set to 74 °F, the SSA is programmed to +/- 3 °F and the SSA is adjusted fully to the + position, the new controlling space setpoint will be 78 °F.
OAT - The outside air temperature sensor (PN: 031-01916­000A) is a factory-installed 10 K NTC sensor. Its linear ranging is from -50 °F to 250 °F.
voltage and drop the contactors and shut down if the voltage drops below 16 VAC and flash the appropriate flash code.
REMOTE - the control will use 0-10 VDC from third-party BAS to control SAT set points. Thermostat input s override if in conflict with Remote Control voltage input.
SPC TEMP - offset value from the space sensor offset potentiometer.
CV/VAV - resistive value across terminals, to determine which supply fan rules the control will follow.
Demand Ventilation / IAQ - Indoor Air Quality. The IAQ expects a 0-10 VDC signal to the control from a field supplied and installed Carbon Dioxide (CO
) sensor. Indoor air quality
2
is monitored for adequate ventilation. In Demand Ventilation Mode, as the CO
levels in the building rise above the
2
programmed setpoint, more fresh air must be brought in. The economizer is therefore adjusted to a more open position as necessary. The linear ranging for IAQ sensor input is from 0 to 10,000 ppm. The Demand Ventilation setpoint is adjustable from 0 to 2000 ppm and is set at the factory at 1000 ppm.
DPS - Duct Pressure Sensor is monitored by a factory­installed 0-5 VDC transducer (PN: 031-01209-000A). The high-pressure port sensing tube is installed in the field. The sense tube should be located approximately two thirds of the way down the duct plenum. To prevent an unstable signal due to air turbulence, there should be no obstructions, turns or VAV terminal boxes up or down-stream of the sense tube location for at least 6 to 10 times the diameter of the duct. The sensor is located in the control box just below the Millennium
®
Simplicity® control.
OAH - Outside Air Humidity (PN: 031-09127-000-A) is a factory-installed sensor manufactured by MAMAO. The OAH sensor, installed only with enthalpy economizer , provides a 0­10 VDC signal to the controller over a range of 0 to 100% relative humidity. This input is used for the economizer calculation to determine whether free cooling is available and to switch between minimum outside air and using outside air as the first stage of cooling.
SAT - Supply Air T emperature sensor (PN: 031-01915-000A) is a factory-installed -50 °F to 250 °F, 10 K NTC sensor.
RAT - Return Air Temperature sensor (PN: 031-01917-000A) is a factory-installed -50 °F to 250 °F, 10 K NTC sensor.
RAH - Return Air Humidity (PN: 031-09127-000-A) is a factory-installed sensor manufactured by MAMAO, installed only with dual enthalpy economizer. The control will calculate the return air enthalpy using the relative humidity and return temperature inputs.
LOW VOLTAGE DETECTION - This input monitors the 24 VAC for low voltage conditions. The input has two thresholds, one at 16 VAC and one at 19.2 VAC. If the control needs to turn on a contactor, it will look to see if the voltage is above19.2 VAC before it will turn it on. If the voltage is not above 19.2 VAC, it will hold off the contactor and flash the appropriate flash code. This flash code is not an alarm. If the control already has contactors pulled in, it will monitor the
BPS - The Building Pressure Sensor (PN: 031-01262-000A) is a factory-installed Johnson Controls DPT -2640-522 transducer that provides a 0 to 5 VDC signal to the controller over a range from -0.25”WC to +0.25”WC. The transducer is located in the control box just below the Millennium® Simplicity® control. The sense tubes are field installed with the outside pressure being sensed external to the unit. To avoid an erratic pressure reading, the building pressure sense tube should be mounted in an area away from the return air grill, discharge diffusers, doors and windows.
BINARY INPUTS (BI) APS - Supply Fan status is monitored by an Air Proving
Status switch (PN: 024-27557-000A) installed at the factory. The APS monitors the difference in pressure between the suction and discharge of the fan.
FOVR - Monitoring loop through the supply fan overload module or VFD over torque indication.
HPS1-4, LPS1-4 - The refrigerant high pressure (HP) and low pressure (LP) safety switches, are independently monitored by the Millennium
®
Simplicity®. If any switch opens, the
control voltage from the control binary output is interrupted and the status is monitored by the control.
G, OCC, P - These signals represent Fan (G), Building Occupancy (OCC), and Building Purge (P) calls from the
Johnson Controls Unitary Products 7
351579-YTS-C-0111
VFD
FR
FR
Fan
VFD +
VFD -
Simplicity
12
18
53
55
P13-1
P14-1
P14-2
Wht
Blk
TB2
thermostat. If a thermostat is installed on the system, these inputs are connected to the thermostat interface board just as are the cooling/heating calls. These inputs are connected through the Tstat Interface board directly to the respective binary inputs of the Controller. These signals are, however, each loaded with a resistor to maintain voltage levels and to prevent “floating” of signals. Thermostat wiring is typically not shielded and may have induced voltages that could cause errant signal readings by the controller.
FILT - Dirty Filter switch [customer supplied, field installed on factory-provided harness connections] input to provide a filter status to the control. The control will alarm only after 24V has been sensed for ten minutes.
GV1-3 - Monitoring that voltage is being supplied to gas valves on optional heat stages.
LIM1-3 - Overtemperature inputs from optional heat stages. FSI - Freeze Stat is a customer installed temperature switch on
the FSI input to the controller to tell the control that a temperature has occurred that risks the hot water or steam coil.
Y1-4, W1-3 - If a thermostat is installed on the system, these inputs will take priority over software programmed setpoints and limits.
SD - This terminal set allows attachment of an external shutdown NC contact. 24VAC power is supplied to the board at SD2; a factory installed jumper passes that power to terminal R to power the Simplicity Elite™ board. If an external shutdown signal is required at a particular installation, remove the jumper and connect the NC shutdown circuit between SD1 and R.
position of the guide vane. If the unit has a factory-installed Variable Frequency Drive, the 2 to 10 VDC signal is wired from VFD+/- output directly to the VFD’s signal input terminals to control fan motor speed.

Table 2: Input Signal to Y1 Actuator Position

Input Signal to Y1 Actuator Position
10 VDC 90 degrees
978 867 756 645 533 422 311 20 0-5
8VDC over a 90 degree Span = 11.25 degrees/VDC
OUTPUTS Analog Outputs (AO) - Analog outputs provide a 2-10 VDC
signal to operate controlled devices. The Simplicity configured to use only 2-10 VDC outputs to the Variable Frequency Drive, Inlet Guide Vane, Economizer Damper, Power Exhaust Dampers or VFD, and Heating water valves. Since these outputs are analog, they are continuous between 2 and 10 Volts and are proportional to the 0 to 100% drive position of the device.
ECO - Economizer Actuator - The modulating Economizer uses a Johnson Controls M9220GGAYK30 spring-return actuator (PN: 025-30869-000A). This actuator uses a 2-10 VDC signal to drive the dampers open. The actuator drives 95 degree rotation. Note the chart below for a correlation between the input drive signal at terminal 3 (Y1) of the actuator and the corresponding output drive position of the damper:
VFD - Inlet Guide Vane or VFD - The Inlet Guide Vane uses a Johnson Controls M9220GGAYK30 spring-return actuator. This actuator uses the 2-10 VDC signal from VFD+/- terminals to drive the dampers open. The actuator drives 95 degree rotation. Note the chart below for a correlation between the input drive signal at terminal 3 (Y1) and the corresponding output drive
8 Johnson Controls Unitary Products
®
is currently
Figure 4: VFD Control Wiring EXD - Power Exhaust Damper Vane or VFD - Power Exhaust
Damper Actuator is a Johnson Controls M9220GGAYK30. It uses a full open/ Full Closed scheme and operates a 95 degree rotation. If VFD Power Exhaust is configured, the same signal controls the exhaust fan motor drive frequency.
HWV - Heating W ater V alve - Customer supplied and installed, connect to factory-provided harness.
BINARY OUTPUTS (BO) FAN - Fan Start/Stop Relay, VFD “permission” relay FR H1-3 - HEAT STAGES 1 TO 3 [OPTIONAL] C1 through C4 - Cooling Stages 1 through 4 CF1 & CF2 - Condenser Fan Banks 1 and 2 X - Controller Alarm is field-wired from the thermostat interface
board to signify a controller alarm has occurred.
351579-YTS-C-0111

Table 3: Simplicity® Control Inputs

Name Range Resolution Precision Description
Y1 18 - 30 VAC On - Off +/- .5 VAC Request for the first stage of Cooling (24 VAC sense) Tstat Screw Terminal Y2 18 - 30 VAC On - Off +/- .5 VAC Request for the second stage of Cooling (24 VAC sense) Tstat Screw Terminal Y3 18 - 30 VAC On - Off +/- .5 VAC Request for the third stage of Cooling (24 VAC sense) Tstat Screw Terminal
Y4 18 - 30 VAC On - Off +/- .5 VAC Request for the fourth stage of Cooling (24 VAC sense) Tstat Screw Terminal W1 18 - 30 VAC On - Off +/- .5 VAC Request for the first Stage of Heating (24 VAC sense) Tstat Screw Terminal W2 18 - 30 VAC On - Off +/- .5 VAC Request for the second Stage of Heating (24 VAC sense) Tstat Screw Terminal W3 18 - 30 VAC On - Off +/- .5 VAC Request for the third Stage of Heating (24 VAC sense) Tstat Screw Terminal
G 18 - 30 VAC On - Off +/- .5 VAC Request for the Fan (24 VAC sense) Tstat Screw Terminal R 18 - 30 VAC - ­C Earth Ground - - These terminals are a ¼' Faston and a Thermostat Screw terminal.
OCC 18 - 30 VAC On - Off +/- .5 VAC Occupied input (24 VAC sense) Tstat Screw Terminal
SD 18 - 30 VAC - +/- .5 VAC Shut Down input Tstat Screw Terminal
Purge 18 - 30 VAC On - Off +/- .5 VAC Building Purge input (24 VAC sense) Tstat Screw Terminal
BAS Economizer 2 - 10 VDC Not Read by micro - Input that routes to the Economizer output Two Tstat Screw Terminals +&-
HPS1 18 - 30 VAC On - Off +/- .5 VAC High Pressure Switch for Circuit # 1 (24 VAC sense) HPS2 18 - 30 VAC On - Off +/- .5 VAC High Pressure Switch for Circuit # 2 (24 VAC sense) HPS3 18 - 30 VAC On - Off +/- .5 VAC High Pressure Switch for Circuit # 3 (24 VAC sense) HPS4 18 - 30 VAC On - Off +/- .5 VAC High Pressure Switch for Circuit # 4 (24 VAC sense) LPS1 18 - 30 VAC On - Off +/- .5 VAC Low Pressure Switch for Circuit # 1 (24 VA C sense) LPS2 18 - 30 VAC On - Off +/- .5 VAC Low Pressure Switch for Circuit # 2 (24 VA C sense) LPS3 18 - 30 VAC On - Off +/- .5 VAC Low Pressure Switch for Circuit # 3 (24 VA C sense)
LPS4 18 - 30 VAC On - Off +/- .5 VAC Low Pressure Switch for Circuit # 4 (24 VA C sense) Limit Switch 1 18 - 30 VAC On - Off +/- .5 VAC High Limit Switch input (24 VAC sense) For Burner sect ion 1 Limit Switch 2 18 - 30 VAC On - Off +/- .5 VAC High Limit Switch input (24 VAC sense) For Burner section 2 Limit Switch 3 18 - 30 VAC On - Off +/- .5 VAC High Limit Switch input (24 VAC sense) For Burner section 3
GV1 18 - 30 VAC On - Off +/- .5 VAC Gas Valve input (24 VAC sense) For Burner section 1 GV2 18 - 30 VAC On - Off +/- .5 VAC Gas Valve input (24 VAC sense) For Burner section 2 GV3 18 - 30 VAC On - Off +/- .5 VAC Gas Valve input (24 VAC sense) For Burner section 3
Test / Reset / Up ON - Off ON - Off - Test / Reset Button and Increment Data Input
Address / Down ON - Off ON - Off - Address Button and Decrement Data Input
Alarms / Advance Data ON - Off ON - Off - Alarm Button and Advance Data Input
Program ON - Off ON - Off - Program Button Input
24 hours, 365 Days
Real Time Clock
Water Coil Freeze Stat
(FSI)
Supply Air Temp Sensor
(SAT)
Outside Air Temp Sensor
(OAT)
Space Temp Sensor
(ST)
Return Air Temp Sensor
(RAT)
Space Setpoint Offset
(SSA)
Building Pressure
Sensor
(BPS)
Duct Pressure Sensor
(DPS)
APS (APS) 18 - 30 VAC On - Off +/- .5 VAC Air Proving Switch (24 VAC sense)
Fan Overload (FOVR) 18 - 30 VAC On - Off +/- .5 VAC Fan Overload Switch (24 VAC sense)
CV / VAV Input 0 - 20 K 1 + / - 5
including Leap year
and Daylight
Savings Time
18 - 30 VAC On - Off +/- .5 VAC Hot Water Freeze Stat (24 VAC sense) two ¼ Fastons
-40° - +180° F .1° F
-40° - +180° F .1° F
32° - 100° F .1° F .5° F This is a 10K type 3 Thermistor
-40° - +180° F .1° F
0 - 20 K 1 K + and - 250
0 - 5 VDC-.25 - +.25
"WC
0 - 5 VDC0 - 5 "WC .01 "WC
Seconds - Real Time Clock Chip
-40° - 180 °F
+/- 2 °F across
range
-40° - 180 °F
+/- 2 °F across
range
-4 0° - 1 80 °F
+/- 2 °F across
range
.001 "WC
.005 "WC
1% Across range
.0 5 " W C 1 %
across range
These terminals are a ¼' Female Faston and a Thermostat Screw terminal connected to the power supply of the board.
This is a 10K type 3 Thermistor
This is a 10K type 3 Thermistor
This is a 10K type 3 Thermistor
3 position Mini Screw Terminal shared with S pace Temp The common terminal in the center is common for both the Space Temp and Setpoint Offset.
0 - 5 volt input
0 - 5 volt input
Resistive Input 0 - 5.5K = CV 10K - 20K = VAV
Johnson Controls Unitary Products 9
351579-YTS-C-0111
Table 3: Simplicity® Control Inputs (Continu e d)
Name Range Resolution Precision Description
Demand Ventilation
Input
Remote Control 0 - 10 VDC .05 VDC 0.01 0 - 10 VDC Screw terminal two position Small screw terminal
Dirty Filter Switch
(FILT)
Low Voltage Detection 12 - 35 VAC .1 VAC .5 VAC This input monitors the 24 VAC for Low Voltage Detection
Return Air Humidity
(RAH)
Outside Air Humidity
(OAH)
Comm Port 128 nodes
24 VAC - Class 1 18 - 30 VAC - - ¼'' quick connect for power to the contactors through the Relays.
0 - 10 VDC
0 - 2000 PPM
of CO2
18 - 30 VAC On - Off +/- .5 VAC This is the Dirty Filter Switch (24 VAC sense)
0 - 5 VDC0 - 100%
RH
0 - 5 VDC0 - 100%
RH
1 PPM
.05 VDC1% RH
.05 VDC1% RH
See
Communications
20 PP M
1% Across Range
.1 VD C
2% Across Range
.1 VD C
2% Across Range
- Asynchronous Serial Port (RS485) three position Small screw terminal
0 - 10 volt input
Scaleable 0 - 10 volts Screw terminal two position Small screw terminal
Scaleable 0 - 10 volts Screw terminal two position Small screw terminal

Table 4: Simplicity® Control Outputs

Name Range Resolution Precision Description
LED On - Off - - Status LED
Display
H1
H2
H3
C1
C2
C3
C4
CF1
CF2
Fan
Exhaust Fan (EXH)
Supply Fan VFD 2 - 10 VDC - - This is a 2 - 10 volt output capable of 10 ma
Exhaust Fan Damper
(EXD)
Hot Water V alve
(HWV)
Hot Gas Reheat 2 - 10 VDC .1 VDC .1 VDC This is a 2 - 10 volt output capa bl e of 10 ma
Economizer (ECO) 2 - 10 VDC .1 VDC .1 VDC This is a 2 - 10 volt output capable of 10 ma
X 24VDC - - This is a 24VDC output for Alarms
7 segment W/ Decimal Point
Class 1 Relay
Contacts
Class 1 Relay
Contacts
Class 1 Relay
Contacts
Class 1 Relay
Contacts
Class 1 Relay
Contacts
Class 1 Relay
Contacts
Class 1 Relay
Contacts
Class 1 Relay
Contacts
Class 1 Relay
Contacts
Class 1 Relay
Contacts
Class 1 Relay
Contacts
- - Heat 1 contactor output (Relay Contacts - 24 VAC/120 VAC)
- - Heat 2 contactor output (Relay Contacts - 24 VAC/120 VAC)
- - Heat 3 contactor output (Relay Contacts - 24 VAC/120 VAC)
--
--
--
--
- - Condenser Fan contactor output (Relay Contacts - 24 VAC/120 VAC)
- - Condenser Fan contactor output (Relay Contacts - 24 VAC/120 VAC)
- - Fan contactor output (Relay Contacts - 24 VAC/120 VAC)
- - Exhaust Fan contactor output (Relay Contacts - 24 VAC/120 VAC)
6 "Seven Segment LED /W decimal point"
Compressor number one contactor output (Relay Contacts - 24 VAC/120 VAC)
Compressor number two contactor output (Relay Contacts - 24 VAC/120 VAC)
Compressor number three contactor outpu t (Relay Contacts - 24 VAC/120 VAC)
Compressor number four contactor output (Relay Contacts - 24 VAC/120 VAC)
2 - 10 VDC .1 VDC .1 VDC This is a 2 - 10 volt output capable of 10 ma
2 - 10 VDC .1 VDC .1 VDC This is a 2 - 10 volt output capable of 10 ma
10 Johnson Controls Unitary Products
351579-YTS-C-0111
SIMPLICITY
The paragraphs below provide a definition of, and specify the function related to, each of the parameters that are field­adjustable using the interfaces available. The Millennium is shipped from the factory with the necessary options pre­programmed as indicated by the model nomenclature. It is always a good practice, though, to verify that the correct parameters are properly configured for the unit you are commissioning. You can find a complete list of field-adjustable parameters in the “Settable System Parameters”.
For a description of the parameters, see the Settable System
Parameters below and Table 5.
INTERACTING THROUGH THE MILLENNIUM
SIMPLICITY

SET THE CLOCK

• Power up the unit.
• Press the Program button [upper left].
• Press the Test/Up button [upper right]. Hold it in and it will step through the parameters, or push in to advance one parameter at a time. Advance to parameter 63, Hours.
• Press Change [lower left] Press Up [upper right] or Down [lower right] to the correct hour [24 hour time].
• Press Change to en te r th e ne w valu e.
• Press Up to get to parameter 64, Minutes.
• Press Change.
• Press Up or Down to get to the correct minute value. Press Change to enter the new value.
• If you are done changing parameters, press Program to exit the program mode.

PARAMETER SETTING

The buttons allow the operator to go to a specific parameter and to view and change the data in that parameter.
• To enter the parameter setting mode, press the Program button. The control will display the current parameter num­ber in the two-digit display, and the present value of that parameter in the four-digit display.
• To change to another parameter, press the /Up or /Down button to move to the address of the desired parameter. The present value of that parameter will display.
• To change the data, press the /Change button. The value will flash. While it is flashing, press the /Up or /Down but­ton to increase or decrease the value.
• When the desired new value is showing, press the /Change Data button again to tell the control to store the new value. You can verify that the new value is in place when the value stops flashing.
• To exit Program mode, press the Program button again.
®
PROGRAMMING OPTIONS
®
®
Unit
®

INITIAL STARTUP OPTIONS

Commissioning a new Millennium® installation requires some field adjustments to the Simplicity these adjustments simply involve setting up the various
®
control program. Most of
setpoints that are specific to your customer’s needs (i.e. building pressure) or enabling some extended options that are integrated into the Simplicity control. Also, if there are field changes, i.e. a modulating power exhaust option, the control configuration will need to be modified for the new option.

METRIC OPERATION (ENGLISH)

The factory default for this option is OFF. The metric (SI) conversions are part of the controller software; when the Metric parameter is selected, temperature setpoints and readings will convert to Centigrade (°C).

SETTABLE SYSTEM PARAMETERS

The following headings list each parameter’s name and its default setting. The control is set at the factory for the options of the specific unit; if a replacement control is being installed, the entire parameter set must be matched to the unit. The number in (parentheses) is the value of a parameter in an un-configured control.
Compressors - (2) - This tells the control the number of compressors available. The Factory Default [the value in an unconfigured replacement control] is 2 and can be adjusted from 1 to 4.
Heat Stages - (2) - This tells the control the number of heating stages available. This parameter may be set from 0 to 3. The default setting is 2 stages of heat. When modulating gas heat is installed the parameters is always set to 2.
Hydronic Heat - (OFF) - This tells the control that a Hot Water Coil is installed. If the control is going to modulate the Hot Water Va lve it will also turn on the Heat One output. This is to energize the VAV heat relay for the VAV boxes. The default is OFF for this option. If this parameter is enabled, remember to set the Hydronic Heat First and Second Stage Setpoints and the Economizer Loading Setpoint found in the ”Simplicity
Stage 1 Hydronic Heat SAT Setpoint - (120 °F) - When the Hydronic Heat option is enabled, the control will maintain this SAT setpoint for a call for first stage Heating, by modulating the Hot Water Valve. This is the reset temperature when operating a VAV unit in the Heating mode. The reset range for SAT setpoint is from 80 °F to 180 °F with 120 °F shipped as the default.
Hydronic Heat Reverse Actuated Valve - (OFF) - Th is setting is to allow convenient use of reverse acting w at er valves; setting this parameter to (ON) will change the signal to 2VDC = open, 10 VDC = closed.
SAT Control for Cooling - (ON) - This tells the control if it is going to do excessive SAT monitoring and tripping or not, for Cooling. The SAT should be maintained in an acceptable range in order to achieve reliable compressor operation. The compressor trip limits are user adjustable between 40 °F and 65 °F in one degree increments. The default cooling trip limits are 50 °F for stages 2-4, and 45 °F for stage 1. When the SAT drops below the trip limit for each respective compressor, that compressor is locked out and a 5 minute ASCD is initiated for that compressor. If this option is enabled, remember to set the compressor cooling limits for low limit trip.
®
Setpoints”.
Johnson Controls Unitary Products 11
351579-YTS-C-0111
Power Exhaust - (ON) - This tells the control if it has the Power Exhaust option installed.
Economizer Damper Position for Exhaust Fan to turn ON (Non-Modulating PE Only) - (60%) - This tells the control the
Economizer Damper position to turn on the Exhaust Fan. This value is based on the 0%-100% output drive signal from the controller to the economizer damper actuator.
Economizer Damper Position for Exhaust Fan to turn OFF (Non-Modulating PE only) - (20%) - This tells the control the
Economizer Damper position to turn off the Exhaust Fan. This value is based on the 0%-100% output drive signal from the controller to the economizer damper actuator.
Modulating Exhaust - (OFF) - This tells the control if the Power Exhaust is Modulating or not. A modulating exhaust will be equipped with a Building Pressure Sensor [BPS]. A Non­Modulating exhaust will look to the economizer damper position to energize the EXD output. If the sensor gets disconnected, or fails, an alarm is set. The alarm can be turned off by correcting the sensor problem (or; by turning off this option). The control is not in this case self-configuring. It will not automatically use the Building Pressure Sensor if the sensor is connected.
Exhaust VFD Installed - (OFF) - If the unit has a VFD, the EXD output will be enabled when the supply fan is ON.
Exhaust Damper Position For The Exhaust Fan To Turn On (Modulating Only) - (80%) - This tells the control the Exhaust
Damper position at which to turn on the Exhaust Fan. This value is based on the 0%-100% output drive signal from the controller to the damper actuator.
Exhaust Damper Position For Exhaust Fan To Turn Off (Modulating Only) - (20%) - This tells the control the Exhaust
Damper position to turn off the Exhaust Fan. This value is based on the 0%-100% output drive signal from the controller to the damper actuator.
Building Pressure Setpoint - (+0.100”WG) - This is the pressure setpoint the control will maintain when op era ting a Power Exhaust. The Building Pressure Setpoint is adjustable from -0.200”WG to +0.200”WG. The factory programmed default is +0.100”WC. This setpoint is used when the exhaust control is implemented as Proportional Control (with a Modulating Exhaust Air Damper or VFD controlled from building static pressure), or as a Two-posi tion Co ntrol using bui lding static (Power Exhaust Fan controlled on-off from building static pressure).
Economizer - (ON) - This tells the control that there is an Economizer Installed.
Economizer Min Position - (20%) - This tells the control what the minimum outdoor damper position will be for the Occupied mode. Adjustable from 0-100%, the Economizer Minimum Position default is 20%.
Economizer First Stage Setpoint - (55 °F) - This tells the control what Supply Air Temperature to maintain for a call for first stage of cooling. This is used only during Constant Volume cooling mode with Economizer operation. The setpoint is set at 55 °F with an adjustable range from 40 °F to 65 °F.
Economizer Second Stage Setpoint - (50 °F) - This tells the control what Supply Air Temperature to maintain for a call for second stage of cooling. This is used only during Constant Volume cooling mode with Economizer operation. This setpoint is set at 50 °F with a range from 40 °F to 65 °F.
Outside Air Humidity (OAH) Sensor Enable - (OFF) - This setting tells the control that it is expected to use Outside Air Enthalpy (calculated from Outside Air Temperature and Outside Air Relative Humidity sensed values) to decide if Outside Air can be used for cooling.
The control is self-configuring to the best available decision strategy for free cooling availability. For example, if it detects that OAT and OAH and RAT and RAH sensors are all connected and reliable, will self-configure for Differential Enthalpy operation. If one of the return air sensors should fail, the control will reconfigure for Outside Enthalpy operation, etc.
If the OAH Sensor Enable option is turned ON, it means that the Outside Enthalpy Operation, or better decision strategy, is expected (and supported by installed sensors). If the appropriate sensors are not installed, or one of them failed, a sensor failure alarm is set. The alarm can be turned off by turning off the OAH Sensor Enable option. Thus, the option setting is used to reflect the desired operation and mainly to control sensor failure alarms
.
The option setting can be viewed as specifying that (the self­configured economizer decision strategy has to be at least this, or better, otherwise an alarm is set). If the option is OFF, the control still may self configure to Outside Enthalpy Operation, or even to Differential Enthalpy Operation (if all needed sensors are available), but this option setting will allow also the decision strategy based on only OAT (in case other sensors fail, or are not installed) without setting an alarm.
Outside Air Enthalpy Setpoint - (27 BTU/LB) - This tells the control an outside air enthalpy limit. Below this limit, outside air is available for cooling. See enthalpy chart. This parameter uses a one BTU/LB hysteresis on each side of the limit. The limit is preset to 27 BTU/ LB with an adjustable range from 10 to 50 BTU/LB.
Return Air Humidity (RAH) Sensor enable - (OFF) - This tells the control that it will compare Outside Air Enthalpy (calculated from Outside Air Temperature an d Outside Air Relative Humidity sensed values) and Return Air Enthalpy (calculated from Return Air Temperature and Return Air Relative Humidity sensed values). The control will use the air stream with the lower enthalpy for cooling.
The control is self-configuring to the best available decision strategy for free cooling availability . For example, if it detect s that OA T and OAH and RAT and RAH sensors are all connected and reliable, will self-configure for Differential Enthalpy operation. If one of the return air sensors should fail, the control will stop using rules that involve RAH and set an alarm.
If the RAH Sensor Enable option is turned ON (and supported by installed sensors), Differential Enthalpy Operation can be enabled. If the appropriate sensors are not installed, or one of them failed, a sensor failure alarm is set. The RAH alarm can
12 Johnson Controls Unitary Products
351579-YTS-C-0111
be turned off by turning off the RAH Sensor Enable option. Thus, the option setting is used to reflect the desired operation and mainly to control sensor failure alarms.
Economizer Loading to Control SAT - (ON) - This tells the control if it is going to use Economizer Loading to control excessive SAT [supplying warmer outside air to keep SAT from going too low]. This parameter is only applicable outside the normal Economizer operation. During the Economizer operation, the loading function is always performed and is an integral part of the control algorithm.
Duct Static Setpoint - (1.5”WG) - This parameter is applicable only to V A V mode of operation. This is the pressure setpoint that the control will maintain when operating the fan in a VAV unit. This setpoint is adjustable between 0”WG and 5”WG with the default set to 1.5”WG.
Duct Static High Limit Setpoint - (4.5”WG) - This parameter is applicable only to V AV mode of operation. This tells the control at what Static Pressure to shu t down the unit due to a Fan control failure. This setpoint is to insure that we don't continue to operate the Fan with an Inlet Guide Vane or VFD problem that could cause the ductwork to fail from duct pressure. When the St a tic Pressure reaches this setpoint (4.5”WG default), the control will drive the supply fan control output to zero. If the static pressure does decrease below the “Duct St at ic High Li mit Setpoi nt” within 3 seconds after decreasing the supply fan control output to zero, the control will resume normal operation. If there is no change in static pressure after 3 seconds, the control will generate a High Duct Static alarm, shut do wn all the outputs including the Fan and shut down the unit. The alarm is written to the Error History Buffer and will trigger storing a snapshot of Points Screen data alon g with a date and time stamp. In networked applications, the ala rm flag is readable by the network. This parameter can be adjusted from 0”WG to 5”WG with the factory default set to 4.5”WG.
The customer must be aware of the duct pressure design limit, and what the duct pressure sensor will be reading when the peak pressure is reached [the pressure pickup tube may not have been located at the place of highest pressure in the system].
The alarm must be reset (after the problem that caused the alarm is corrected) by resetting the controller by turning power to the unit off and back on, or by reset command issued by an external connection.
Morning Warm Up - Is inferred from the entries in Occupied/Unoccupied
Occupied - (from settings in Weekly Schedule and Holiday Schedule Tables 11 and 12.) - See discussion in Sequence of Operation.
Unoccupied - (from settings in Weekly Schedule and Holiday Schedule Tables 11 and 12.) - See discussion in Sequence of Operation.
VAV High Temperature SAT Setpoint for Cooling - (60 °F) - The control will maintain this SAT when operating in VAV mode with a thermostat that is calling for first stage cooling. This parameter may be adjusted from 40 °F to 70 °F with 60 °F set as the default value.
VAV Low Temperature SAT Setpoint for Cooling - (55 °F) - The control will maintain this SAT when operating in VAV mode with a thermostat that is calling for second stage cooling. This parameter may also be adjusted from 40 °F to 70 °F with 55 °F set as the default value.
VAV SAT Reset Setpoint - (72 °F) - This parameter is used only in V AV mode with a Space Sensor. The control will switch from the VAV Lower Cooling SAT Setpoint to the VAV Upper Cooling SAT Setpoint when this Space Temperature Setpoint minus 0.5 °F is reached. The control will switch from High setpoint back to Low setpoint when the space temperature gets 2 °F above this setpoint. This is SAT reset based on Space Temperature. The reset occurs in both Occupied and Unoccupied modes and may be adjusted from 40 °F to 85 °F. The factory default is 72 °F.
V AV Occupied Heating - (OFF) - This option applies in VAV mode with a Space Sensor and does not affect VAV Occupied heating if requested by a thermostat. When this option is toggled on, a VAV unit is able to operate heating in the occupied mode as long as it is operating with a Space Sensor. If the Space Temperature drops to 2 °F below the VAV SAT Reset Setpoint the control will read the RAT. If the RAT is below the Morning Warm Up RAT Setpoint the unit will enter the Occupied Heating mode. Operation is the same as Morning Warm Up. This parameter is factory set to OFF.
Comfort Ventilation Mode - (OFF) - Comfort Ventilation is a SAT control mode that controls SAT during “satisfied” periods in a fairly wide temperature band, using mostly Outside Air, and also cooling and heating stages as necessary. It is available only on the Constant Volume unit.
To enable Comfort Ventilation, the programmable parameter “Comfort Ventilation Mode” must be set to ON (default setting is OFF).
For a detailed explanation of Comfort Ventilation, refer to the Sequence of Operation in this manual.
Comfort Ventilation High Supply Air Setpoint - (80 °F) - This is the High Limit Setpoint for the Comfort Ventilation mode. For a stable operation of Comfort Ventilation function, the High Supply Air Setpoint should be set 10.0 °F or more above the Low Setpoint.
Comfort Ventilation Low Supply Air Setpoint - (70 °F) - This is the Low Limit Setpoint for the Comfort Ventilation mode. For a stable operation of Comfort Ventilation function, the Low Supply Air Setpoint should be set 10.0 °F or more below the High Setpoint.
Dirty Filter Switch - (OFF) - This tells the control that a Dirty Filter Switch is connected to it. The control will wait for ten minutes after the switch has closed before declaring a Dirty Filter Alarm. The alarm is written to the Error History Buffer. In networked applications, the error flag is readable by the network. The alarm will automatically reset when the error condition is corrected.
The default is OFF.
Johnson Controls Unitary Products 13
351579-YTS-C-0111
UnOcc. Htg.
Occ. Htg.
UnOcc. Clg.
Occ. Clg.
Heating Lockout on OAT - (75 °F) - This is the Outside Air Temperature Setpoint that the control will use to lock out Heating when the OA T is a bove this setpoint. There is a one-degree hysteresis on each side of the setpoint. This parameter is adjustable between 0 °F and 100 °F with the default set to 75 °F.
Heating Lockout on OAT affect s only staged heating, it does not affect hydronic heat. If the heating is energized when OAT reaches this setpoint, the Status LED will indicate the lockout condition immediately, but the control will finish the heating mode and then lock out the heating.
Note that a Heating Lockout on OAT may occur while the control is in a heating mode and there is a demand for heating.
If the OAT then decreases below the lockout setting while the call for several heat stages exists, the heat stages will turn on simultaneously. This is considered acceptable as this situation is not expected to occur frequently.
Cooling Lockout on OAT - (45 °F) - This is the Outside Air Temperature Setpoint that the control uses to lock out Cooling when the OAT is below this setpoint. Adjustable from 0 °F to 100 °F, the default is 45 °F.
Unoccupied Heating Setpoint - (60 °F) - This value is the Unoccupied Heating Setpoint. It is used in both CV and VAV mode of operation (in VAV, it controls Unoccupied heating with a Space Sensor).

Figure 5: Sequence Of Setting The Set Points

The control will attempt to correct wrong temperature overlap settings; for example, if a change is made that would put Occupied Heating above Occupied Cooling, the Occupied Cooling setting will change to stay above the heating setpoint.
Occupied Heating Setpoint - (68 °F) - This value is the Occupied Heating Setpoint. It is used only in CV mode of operation. Its relationship to the related setpoints is as defined in the Unoccupied Heating Setpoint paragraph above.
Unoccupied Cooling Setpoint - (85 °F) - This value is the Unoccupied Cooling Setpoint. It is used in both CV and VAV mode of operation (in VAV, it controls Unoccupied cooling with a Space Sensor).
Occupied Cooling Setpoint - (72 °F) - This value is the Occupied Cooling Setpoint. It is used only in CV mode of operation. Its relationship to the related setpoints is as defined in the Unoccupied Heating Setpoint paragraph above.
[Input] FSI (Hot Water Freeze Protection) - (OFF) - This option is used only on rooftop units with hydronic heat (Hydronic Heat Option is turned ON). Freeze protection should
always be placed on units that use hydronic heating. When the control senses 24VAC, the control will turn on the Hot Water valve to 100%. The control will continue to drive the valve at 100% until five minutes after the switch has opened. Then the valve will revert to normal operation. If the control is operating the Fan, it will close the Economizer fully until the freeze condition is over. If the fan is off and the RA T drops below 40 °F, the Hot Water Valve will turn on 100%.
Supply AirTemp (SA T) Alarm Setpoint for Cooling - (0 °F) - If the SAT does not drive below this setpoint when all stages of compression are operating and 10 minutes has elapsed since the last compressor was energized, the control will declare a Cooling SAT Failure Alarm.
The alarm is written to the Error History Buffer. In networked applications, the alarm flag is readable by the network.
The alarm will reset automatically if the SAT does decrease below the setpoint (the alarm condition no longer exists), or when a compressor is turned off (the control does not request all compressors operate). The SAT Alarm Setpoint for Cooling can be adjusted from 50 °F - 80 °F. If the value is set to 0 °F (default) this feature is disabled.
Before the control declares an error, it will read the OAT and the Economizer position. If the OAT is more than 20 °F warmer than the setpoint and the Economizer is open more than 20%, the control will close the Economizer for 10 minutes and then read the SAT. If the SAT falls below the setpoint, the control will declare an Economizer Minimum Position alarm. The control will keep the Economizer closed and finish the Cooling mode. After the Cooling mode has been satisfied, the control will move the Economizer back to the minimum position.
Supply Air Temp (SAT) Alarm Setpoint for Heating - (0 °F) - The SAT must drive above this setpoint when all stages of heating are operating and 10 minutes has elapsed since the last stage was energized. If this does not happen, the control will declare a Heating SAT Failure Alarm. The alarm is written to the Error History Buffer. In networked applications, the alarm flag is readable by the network. The alarm will reset automatically if the SAT does increase above the setpoint (the alarm condition no longer exists), or when a heating stage is turned off (the control does not request all heat stages to operate).
The SAT Alarm Setpoint for Cooling can be adjusted from 70 °F ­120 °F. If the value is set to 0 °F (default) this feature is disabled.
Before the control declares an error, it will read the OAT and the Economizer position. If the OAT is more than 20 °F colder than the setpoint and the Economizer is open more than 20%, the control will close the Economizer for 10 minutes and then read the SAT. If the SAT rises above the setpoint, the control will declare an Economizer Minimum Position alarm. The control will keep the Economizer closed and finish the Heating mode. After the Heating mode has been satisfied, the control will move the Economizer back to the minimum position.
Unoccupied Override Time Period - (60 min) - The Unoccupied Override Time Limit function will determine how long the unit will operate in the Unoccupied Override mode when the Override button is pressed on the Space Sensor.
14 Johnson Controls Unitary Products
Loading...
+ 30 hidden pages