York ZF Sunline R410A User Manual

®
1056292-XTG-A-0613
TECHNICAL GUIDE R-410A
ZF SERIES 15 & 20 TON/53 & 70 KW 50 Hertz

Description

YORK® ZF Series Sunline™ units are convertible single package high efficiency rooftops. All models have independent refrigeration circuits for efficient part load operation.
Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof.
All ZF units are self-contained and assembled on rigid full perimeter base rails allowing for overhead rigging. Every unit is completely charged, wired, piped, and tested at the factory to provide a quick and easy field installation.
All models (including those with an economizer) are convertible between bottom and horizontal duct connections.
ZF units are available in the following configurations: cooling only, cooling with electric heat, and cooling with gas heat. Electric heaters are available as factory-installed options only.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
1056292-XTG-A-0613

Table of Contents

Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
2 Johnson Controls Unitary Products

Component Location

ELECTRIC HEATER LOCATION
(OPTIONAL ELECTRIC/ELECTRIC UNITS)
HIGH
EFFICIENCY
COMPRESSORS
COPPER TUBE/ALUMINUM FIN
CONDENSER COILS
ELECTRICAL
DISCONNECT
MOUNTING
LOCATION
(Field installed)
KNOCKOUT FOR
SIDE CONTROL WIRING ENTRY
KNOCKOUT
FOR SIDE
POWER WIRING
ENTRY SIDE
KNOCKOUTS FOR SIDE
GAS SUPPLY ENTRY
HOLE FOR BOTTOM
GAS SUPPLY ENTRY
POWER VENTOR MOTOR
WITH POST PURGE CYCLE
BELT-DRIVE
BLOWER MOTOR
FULL PERIMETER
14 GAUGE BASE RAILS
WITH LIFTING HOLES
1" NPTI
CONDENSATE DRAIN
2" DISPOSABLE
FILTERS
LONG LASTING
POWDER PAINT FINISH
20 GAUGE
ALUMINIZED STEEL
TUBULAR HEAT EXCHANGERS
GAS/ELECTRIC
UNIT SHOWN

(ZF shown)

1056292-XTG-A-0613
Johnson Controls Unitary Products 3
1056292-XTG-A-0613
Z F 180 N24 A 7 A AA 1 0 1 2 4 A
Z = A/C, Single Pkg.
Product Category
Airflow
A = Hi Static B = Hi Static/Economizer C = Hi Static/Economizer/Power Exhaust
(Downflow Only) D = Hi Static/Motorized Damper E = Hi Static/Motorized Damper/Barometric Relief J = Hi Static/Economizer/Barometric Relief
1 = First Generation
Product Generation
C00 = Cooling Only. No field installed
electric heat
Heat Type and Nominal Heat Capacity
N24 = 240 MBH Output Aluminized Steel N32 = 320 MBH Output Aluminized Steel S24 = 240 MBH Output Stainless Steel S32 = 320 MBH Output Stainless Steel
E18 = 18 KW E36 = 36 KW E54 = 54 KW E72 = 72 KW
Gas Heat Options
Electric Heat Options
180 = 15 Ton
Nominal Cooling Capacity
240 = 20 Ton
Product Identifier
F = R-410A
Voltage
7 = 380/415-3-50
Product Style
A = Style A
A = No Options Installed
Installation Options
B = Option 1 E = Option 3 F = Option 4 G = Options 1 & 3 H = Options 1 & 4 L = Options 1,3 & 4 R = Options 3 & 4
1 = Disconnect 3 = Smoke Detector S.A. 4 = Smoke Detector R.A.
Options
SS Drain Pan
Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.
CPC Controller, DFS, APS
Johnson Controller, DFS, APS
Honeywell Controller, DFS, APS
Novar Controller, DFS, APS
Simplicity IntelliComfort Controller
Simplicity IntelliComfort Controller w/ModLinc
2" Pleated filters
4" Pleated filters
BAS Ready Economizer (2-10 V.D.C. Actuator without a controller)
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
AA = None
Standard Cabinet
AB = Phase Monitor AC = Coil Guard
AD = Dirty Filter Switch AE = Phase Monitor & Coil Guard AF = Phase Monitor & Dirty Filter Switch AG = Coil Guard & Dirty Filter Switch AH = Phase Monitor, Coil Guard & Dirty Filter Switch RC = Coil Guard & American Flag TA = Technicoat Condenser Coil TJ = Technicoat Evaporator Coil TS = Technicoat Evaporator & Condenser Coils
BA = Hinged Filter Door & Tool Free Acce
ss Panels
Additional Options
Hinged Filter Door & Tool Free Access Cabinet
BB = Phase Monitor, Hinged Filter Door & Tool Free
Access Panels
BC = Coil Guard, Hinged Filter Door & Tool Free
Access Panels
BD = Dirty Filter Switch, Hinged Filter Door &
Tool Free Access Panels
BE = Phase Monitor & Coil Guard, Hinged Filter
Door & Tool Free Access Panels
BF = Phase Monitor & Dirty Filter Switch, Hinged
Filter Door & Tool Free Access Panels
BG = Coil Guard & Dirty Filter Switch, Hinged Filter
Door & Tool Free Access Panels
BH = Phase M
onitor, Coil Guard & Dirty Filter Switch,
Hinged Filter Door & Tool Free Access Panels
15 & 20 Ton Sunline Model Number Nomenclature
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.

Nomenclature

4 Johnson Controls Unitary Products
1056292-XTG-A-0613

Features and Benefits

Standard Features

High Efficiency - High efficiency units reach as high as
10.9 EER. Gas/electric units have electronic spark ignition and power vented combustion with steady state efficiencies of 80%.
Balanced Heating -
Gas Heat - All gas heat units are built with two heating sections for two equal stages of capacity control. Each section includes a durable heat exchanger with aluminized steel or optional stainless steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards.
The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit.
Electric Heat - All electric heat models (factory installed only) are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uniform distribution of air across the heating elements. Every element is fully protected against excessive current and temperature by fuses and two thermal limit switches.
The power supply wiring can be routed into the control box through a threaded pipe connection in the base pan of the unit or through a knockout in the wiring panel on the front of the unit.
BAS Controls - York’s Sunline™ series units offe r factory mounted BAS controls such as Simplicity
II
, Novar, Honeywell, Johnson, York Commercial
Comfort System (YCCS) and CPC.
Convertible Airflow Design - All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with factory
installed power exhaust are suitable for bottom duct connections only. For bottom duct, you remove the sheet
metal panels from the supply and return air openings through the base of the unit. For horizontal duct, you replace the supply and return air panels on the rear of the unit with a side duct flange accessory.
Factory Mounted Outdoor Air Dampers - All models are available with these "factory mounted" outdoor air damper options:
• Single enthalpy economizer with or without power
exhaust
• BAS-ready economizer with or without power exhaust
• Motorized outdoor air damper
• Barometric Relief Damper A fixed outdoor air intake assembly will be shipped in the
return air compartment of all units ordered without an economizer or motorized outdoor air damper option. The assembly includes a rain hood with a damper that can be set for 10, 15 or 25% outdoor air. With bottom duct connections, the fixed outdoor air intake assembly should be mounted
®
Intelli-Comfort
over the opening in the return air panel. With horizontal ductwork, it should be mounted on the return air duct.
System Protection - Suction line freezestats are supplied on all units to protect against loss of charge and coil frosting when the economizer operates at low outdoor air temperatures while the compressors are running. Every unit has solid-core liquid line filter-driers and high and low­pressure switches. Internal compressor protection is standard on all compressors. Phase Monitors are optional on all units. This accessory monitors the incoming power to the unit and protects the unit from phase loss and reversed phase rotation.
Advanced Controls - Simplicity™ ZF control boards have standardized a number of features previously available only as options or by utilizing additional controls.
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down to 0F outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.
The Simplicity® control board used in this product will effectively operate the cooling system down to 25°F when this product is applied in a comfort cooling application for people. An economizer is typically included in this type of application. When applying this product for process cooling applications (computer rooms, switchgear, etc.), please reference applications bulletin AE-011-07 or call the applications department for Unitary Products @ 1­877-UPG-SERV for guidance.
Anti-Short Cycle Protection - To aid compressor life,
an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti-short cycle delay can be temporarily overridden with the push of a button.
Lead-Lag - An integrated Lead-Lag option allows equal
run time hours on all compressors, thereby extending the life of all compressors. This option is selectable on the unit control board.
Fan Delays - Fan on and fan off delays are fully
programmable. Furthermore, the heating and cooling fan delay times are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat.
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the gas valve, if applicable, and the temperature limit switch on gas and electric heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.
Nuisance Trip Protection and Strikes
nuisance trouble calls, the control board uses a “three
- To prevent
Johnson Controls Unitary Products 5
1056292-XTG-A-0613
times, you’re out” philosophy. The high and low­pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the associated compressor.
On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipp ed, an d flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.
Reliable - From the beginning - All units undergo computer automated testing before they leave the factory. Units are tested for refrigerant charge and pressure, unit amperage, and 100% functionality. For the long term - All units are painted with a long lasting, powder paint that stands up over the life of the unit. The paint used has been proven by a 1000 hour salt spray test.
Full Perimeter Base Rails - The permanently attached base rails provide a solid foundation for the entire unit and protect the unit during shipment. The rails offer rigging holes so that an overhead crane can be used to place the units on a roof.
Easy Installation - Gas and electric utility knockouts are supplied in the unit underside as well as the side of the unit. Utility connections can be made quickly and with a minimum amount of field labor. All units are shipped with 2" throw-away filters installed.
Wide Range of Indoor Airflows - All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job.
Warranty - All models include a 1-year limited warranty on the complete unit. Compressors and electric heater elements each carry a 5-year warranty. Aluminized steel and stainless steel tubular heat exchangers carry a 10­year warranty.

Factory Installed Options

YORK® offers several equipment options factory installed, for the ZF Series.
Single Input Electronic Enthalpy Economizers ­Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must be field-assembled before installing.
• BAS-Ready Economizer - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator with zero to 95-degree rotation capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
Actuator requires 2-10 VDC input from an external source, such as a field-installed or factory-installed BAS
controller. BAS-ready actuators have an adjustable auxiliary end-switch for optional power exhaust control.
For units with optional VAV or Simplicity® Intelli-Comfort II™ control, a factory-installed, dry bulb sensor determines if outdoor air temperature is low enough to provide free-cooling operation. (Field-installed humidity sensors for either outdoor air or outdoor & return air streams are available for single enthalpy and differential enthalpy configurations, respectively).
The rain hood is painted to match the basic unit and must be field-assembled before installing.
Power Exhaust - Our economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation.
The exhaust fan, motor and controls are installed and wired at the factory. The rain hood must be assembled and installed in the field.
The power exhaust option can only be used on bottom duct configurations.
Motorized Outdoor Air Intake Damper - Includes a slide-in / plug-in damper assembly with a 2- position, spring return motor actuator which opens to a pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must be field assembled before installing.
Barometric Relief Damper - This damper option can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.
• Technicoat Condenser Coils - The condenser coils are coated with a phenolic coating for protection against corrosion due to harsh environments.
• Technicoat Evaporator Coil - The evaporator coils are coated with a phenolic coating for protection against corrosion due to harsh environments.
Electric Heaters - wired for single point power supply. These nickel chromium heater elements are provided with
limit and automatic reset capability to prevent operation at excessive temperatures.
Filter Options - Standard units are shipped with 2" throw­away filters installed. 2" pleated and 4" pleated filters are offered as a factory installed option.
Disconnect Switch - For gas heat units and cooling units with electric heat, a HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only.
York Commercial Comfort System (YCCS) - Provides rooftop system integration for YCCS single zone, change­over bypass and VAV systems.
6 Johnson Controls Unitary Products
1056292-XTG-A-0613
Smoke Detectors - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.
Factory installed smoke detectors in the return air, may be subjected to freezing temperatures during “off” times due to out side air infiltration. these smoke detectors have an operational limit of 32°F to 131°F. smoke detectors installed in areas that could be out side those limitations will have to be moved to prevent having false alarms.
Coil Guard - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.
Stainless Steel Heat Exchanger - For applications in corrosive environments, this option provides a full stainless steel heat exchanger assembly.
Stainless Steel Drain Pan - An optional rustproof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environments.
Phase Monitors - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of phase condition.
Dirty Filter Switch - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.
Hinged Filter Door/"Tool Free" Blower And Access Panels (Not Hinged) - This option allows for easy access and maintenance.
NOTE: Knobs are shipped separately within the unit to prevent
shipping damage. These must be field installed for tool free operation.
Hinged/"Tool Free" Blower, Blower Motor, Filter And Electric Access Panels - This option allows for complete hinged and tool free access to the unit’s blower, blower motor, filters and electrical panel sections.

Control Options

• BAS - Building Automation System Controls (available on two-system cooling product only).
®
Simplicity™ Intelli-Comfort II™ Control - The York Simplicity™ INTELLI-CO
sensor to perform Differential
2
Demand Ventilation. It uses a Patented Comfort Ventilation algorithm to provide comfortable ventilation air temperature. The patented economizer-loading algorithm will protect the equipment when harsh operating conditions exist. It uses the INTELLI-Start™ algorithm to maximize energy savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the Occupied Time Period to begin. The Simplicity™ Intelli-Comfort II™ balances space temperature, ventilation air tempera t ure , C O
and
2
humidity for ultimate comfort.
Simplicity™ Intelli-Comfort II™ with Simplicity™LINC Control - The York® Simplicity™ Intelli-Comfort II™ with
Simplicity™LINC control is factory installed. It includes all the features of the Intelli-Comfort II™ control with an additional control to translate communications from MODBUS to the BACnet MSTP protocol.
Novar® BAS Control - The Novar® building automation system controller is factory installed. Incudes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.
Johnson Controls BAS Control - The Johnson Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.
CPC BAS Control - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch and air proving switch.
Honeywell BAS Control - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch.

Field Installed Accessories

YORK® offers several equipment accessories for field installation, for the ZF Series.
Single Input Electronic Enthalpy Economizers - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.
The rain hood is painted to match the basic unit and must be field-assembled before installing.
Motorized Outdoor Air Intake Damper - Includes a slide-in / plug-in damper assembly with a 2-position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must be field assembled before installing.
Roof Curbs - Fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof.
These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly.
They're designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports.
High Altitude Natural Gas - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet.
Propane - Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane.
High Altitude Propane - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up
Johnson Controls Unitary Products 7
1056292-XTG-A-0613
to 6,000 feet. This accessory supplements the basic propane conversion kit.
Side Duct Flanges - One-inch flanges replace the supply and return air panels on the rear of the unit to accommodate horizontal duct connections. These flanges can also be used individually for bottom supply / horizontal return or horizontal supply/bottom return. They cannot be used on units with power exhaust.
Barometric Relief Damper - This damper accessory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.
Enthalpy Accessory Control Kit - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.
Burglar Bars - Mount in the supply and return openings to prevent entry into the duct work.
Flue Exhaust Extension Kit - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.
Wood Skid - Allows unit to be handled with 90" forks.
Sensor - Senses CO2 levels and automatically
CO
2
overrides the economizer when levels rise above the present limits.
Coil Guard - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.
Phase Monitors - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of phase condition.

Guide Specifications

General
Units shall be manufactured by Johnson Controls Unitary Products in an ISO 9001 certified facility.
ZF models have 2 condenser fan motors and compressors. All compressors include crankcase heat and internal discharge temperature protection. Every refrigerant circuit includes an expansion valve, a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch. The unit control circuit includes 75 VA and 150 VA transformers, a 24-volt circuit breaker and a relay board with two compressor lockout circuits, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify the interface of additional field controls. All units have long lasting powder paint cabinets with 1000 hour salt spray test approval under ASTM-B117 procedures. All models include a 1-year limited warranty on the complete unit.
Compressors and electric heater elements carry an additional 4-year warranty. Aluminized steel tubular heat exchangers carry an additional 9-year warranty.
Description
ZF units shall be factory-assembled, single packaged, ZF***N Electric Cooling/Gas Heat, ZF***C/E Electric Cooling/Optional Electric Heat, designed for outdoor mounted installation.
They shall have built-in field convertible duct connections for down discharge supply/return or horizontal discharge supply/ return, and be available with factory installed options or field installed accessories. The units shall be factory wired, piped, charged with R-410A refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. All units shall be manufactured in a facility certified to ISO 9001 standards and the cooling performance shall be rated in accordance with DOE and AHRI test procedures. Units shall be classified to ANSIZ21.47 standards, UL 1995/CAN/CSA No. 236-M90 conditions.
Unit Cabinet
Unit cabinet shall be constructed of galvanized steel, with exterior surfaces coated with a non-chalking, powdered paint finish, certified at 1000 hours salt spray test per ASTM-B117 standards. Indoor blower section shall be insulated with a minimum 1/2" thick insulation, coated on the airside. Aluminum foil faced insulation shall be used in the furnace compartment and be fastened with rigid fasteners to prevent insulation from entering the air stream. Cabinet panels shall be easily removable for servicing and maintenance. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging and proper sealing on roof curb applications. Disposable 2" filters shall be furnished and be accessible through a removable access door, sealed airtight. Units filter track shall be designed to accommodate either 2" or 4" filters. Fan performance measuring ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator fan performance without removing panels or creating air by-pass of the coils. Condensate pan shall be internally sloped and conform to ASHRAE 62-89 self-draining standards. Condensate connection shall be a minimum of 1" I.D. female and be a ridged mount connection. Unit shall incorporate a fixed outdoor air damper with an outdoor air intake opening covered with a bird screen and a rain hood painted to match the exterior of the unit.
Indoor (Evaporator) Fan Assembly
Fan shall be a belt drive assembly and include an adjustable­pitch motor pulley. Job site selected (B.H.P.) brake horsepower shall not exceed the motors nameplate horsepower rating, plus the service factor. Units shall be designed not to operate above service factor. Fan wheel shall be double-inlet type with forward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume.
8 Johnson Controls Unitary Products
1056292-XTG-A-0613
Outdoor (Condenser) Fan Assembly
The outdoor fans shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to corrosion resistant steel spider brackets and shall be dynamically balanced for smooth operation. The 2 outdoor fan motors shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and staged independently.
Refrigerant Components
Compressors:
a. Shall be Scroll compressors internally protected with
internal discharge temperature protection over temperature protection.
b. Shall have internal spring isolation and sound muffling to
minimize vibration and noise, and be externally isolated on a dedicated, independent mounting.
Coils:
a. Evaporator and condenser coils shall have aluminum
plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option.
b. Evaporator and Condenser coils shall be of the direct
expansion, draw-thru, design.
Refrigerant Circuit and Refrigerant Safety Components shall include:
a. Balance-port thermostatic expansion valve with
independent circuit feed system.
b. Filter drier/strainer to eliminate any moisture or foreign
matter.
c. Accessible service gage connections on both suction
and discharge lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting, without losing charge.
d. The refrigeration system shall provide at least 10° F of
sub-cooling at design conditions.
e. All models shall have two independent circuits.
Unit Controls
a. Unit shall be complete with self-contained low-voltage
control circuit protected by a resettable circuit breaker on the 24-volt transformer side.
b. Unit shall incorporate a lockout circuit which provides
reset capability at the space thermostat or base unit, should any of the following standard safety devices trip and shut off compressor.
c. Loss-of-charge/Low-pressure switch.
1.High-pressure switch.
2.Freeze-protection thermostat, evaporator coil. If any of the above safety devices trip, a LED (light-emitting diode) indicator shall flash a diagnostic code that indicates which safety switch has tripped.
d. Unit shall incorporate "AUTO RESET" compressor over
temperature, over current protection.
e. Unit shall operate with conventional thermostat designs
and have a low voltage terminal strip for easy hook-up.
f. Unit control board shall have on-board diagnostics and
fault code display.
g. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to 25°F.
h. Control board shall monitor each refrigerant safety switch
independently.
i. Control board shall retain last 5 fault codes in non volatile
memory, which will not be lost in the event of a power loss.
Gas Heating Section (ZF***N Models)
Shall be designed with induced draft combustion with post purge logic and energy saving direct spark ignition, redundant main gas valve. Ventor wheel shall be constructed of stainless steel for corrosion resistance. The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized steel for corrosion resistance and allowing minimum mixed air entering temperature of 25 °F. Burners shall be of the in-shot type, constructed of aluminum coated steel and contain air mixture adjustments. All gas piping shall enter the unit cabinet at a single location through either the side or curb, without any field modifications. An integrated control board shall provide timed control of evaporator fan functioning and burner ignition. Heating section shall be provided with the following minimum protection:
a. Primary and auxiliary high-temperature limit switches. b. Induced draft motor speed sensor. c. Flame roll out switch (automatic reset). d. Flame proving controls. Unit shall have two independent
stages of capacity.
Electric Heating (ZF***C/E Models)
Nickel chromium electric heating elements shall be provided as required by the application with 1 or 2 stage control, as required, from 18 KW to 72 KW nominal capacities. The heating section shall have a primary limit control(s) and automatic reset to prevent the heating element system from operating at an excessive temperature. Units with Electric Heating shall be wired for a single point power supply with branch circuit fusing (where required).
Unit Operating Characteristics
Unit shall be capable of starting and running at 125° F outdoor temperature, exceeding maximum load criteria of AHRI Standard 340/360. The compressor, with standard controls, shall be capable of operation down to 25° F outdoor temperature. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up (Gas heat only).
Johnson Controls Unitary Products 9
1056292-XTG-A-0613
Electrical Requirements
All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.
Standard Limited Warranties
• Compressor 5 Years
• Heat Exchanger 10 Years
• Electric Heat Element 5 Years
• Other Parts 1 Year
Optional Outdoor Air (Shall be made avai lable by either/or):
Electronic Enthalpy Automatic Economizer - Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55°F. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss.
Motorized Outdoor Air Dampers - Outdoor and return air dampers that are interlocked and positioned by a 2­position, spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected positions - regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.
Other Pre-engineered Accessories Available
Roof Curb - 14" high, full perimeter curb with wood nailer (shipped knocked-down).
100% Barometric Relief Damper - Contains a rain hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure through the unit.
Propane Conversion Kit - Contains new orifices and gas valve parts to convert from natural to L.P. gas. One per unit required.
High Altitude - Natural Gas - Contains orifices required for applications between 2000 and 6000 feet altitude.
High Altitude - Propane Gas - Contains orifice s requ ired for applications between 2000 and 6000 feet altitude. Must be used with propane conversion kit.
Burglar Bars - Designed to work with above roof curbs, depending on unit model. Fits duct openings of curb supply and return air openings.
Side Duct Flange - Supply and return air duct flanges for side duct applications. Do not use on units with power exhaust.
Wood Skid - Allows unit to be handled with 90" forks.
Economizer/motorized Damper Rain Hood (ZFN/E/C240 only) - Contains all hood panels and the hardware for assembling.
Anti-Recycle Timer - Assures 5-minute off time between compressor cycles.
Coil Guard Kit - Guard for cooling coil.
OTHER FACTORY INSTALLED OPTIONS
Power Exhaust Option - To work in conjunction with economizers.
• Stainless Steel Heat Exchanger
• Stainless Steel Drain Pan
• Technicoat Phenolic Coated Condenser And Evaporator Coil
Electronic Single Enthalpy Economizer
• Dirty Filter Switch
• Phase Monitor
• Coil Guard
Bas Controls - Simplicity
®
Intelli-Comfort II ™, CPC, JOHNSON, HONEYWELL, NOVAR, YORK COMMERCIAL COMFORT SYSTEM (YCCS)
BAS Ready Economizer (2-10 V.D.C. Actuator Without a Controller)
• Hinged Filter Door Access And Tool Free Acc ess Panels
• Hinged Tool Free Blower, Blower Mo tor, Filter And Electrical Access Panels
• 2" Pleated Filters, MERV 7
• 4" Pleated Filters, MERV 13
• Disconnect Switch
• Supply Air Smoke Detector
• Return Air Smoke Detector
10 Johnson Controls Unitary Products

Physical Data

ZF180-240 Physical Data

1056292-XTG-A-0613
Component
Nominal Tonnage 15 20
AHRI COOLING PERFORMANCE
Gross Capacity @ AHRI A point (K Btu) 204 259 AHRI net capacity (K Btu) 195 246 EER 10.9 10.4 SEER - ­IEER 11.26 10.88 Nominal CFM 6000 8000 System power (KW) 17.9 23.7 Refrigerant type R-410A R-410A Refrigerant charge (lb-oz)
System 1 22-8 20-4 System 2 21-8 21-4
AHRI HEATING PERFORMANCE
Heating model 24 32 24 32 Heat input (K Btu) 300 400 300 400 Heat output (K Btu) 240 320 240 320 AFUE% - - - ­Steady state efficiency (%) 80 80 80 80 No. burners 6 8 6 8 No. stages 2 2 2 2 Temperature Rise Range (ºF) 20-50 35-65 20-50 35-65 Gas Limit Setting (ºF) 195 195 195 195 Gas piping connection (in.) 1 1 1 1
DIMENSIONS (inches)
Length 125-1/4 136-1/4 Width 92 92 Height 48-5/8 52-5/8
OPERATING WT. (lbs.) 1680 2400
COMPRESSORS
Type Scroll Scroll Quantity 2 2 Unit Capacity Steps (%) 50 / 100 50 / 100
CONDENSER COIL DATA
Face area (Sq. Ft.) 36.0 43.3 Rows 3 3 Fins per inch 13.5 15 Tube diameter (in.) 3/8 3/8 Circuitry Type Standard Standard
EVAPORATOR COIL DATA
Face area (Sq. Ft.) 15.5 20.1 Rows 4 4 Fins per inch 14 14 Tube diameter 3/8 3/8 Circuitry Type Intertwined Intertwined Refrigerant control TXV TXV
ZF180 ZF240
Models
Johnson Controls Unitary Products 11
1056292-XTG-A-0613
ZF180-240 Physical Data (Continued)
Component
ZF180 ZF240
Models
Nominal Tonnage 15 20
CONDENSER FAN DATA
Quantity 2 2 Fan diameter (Inch) 30 30 Type Prop Prop Drive type Direct Direct No. speeds 1 1 Number of motors 2 2 Motor HP each 1.25 1.25 RPM 950 950 Nominal total CFM 6000 8000
BELT DRIVE EVAP FAN DATA
Quantity 1 1 Fan Size (Inch) 15 X 15 18 X 15 Type Centrifugal Centrifugal Motor Sheave 1VP62 1VP75 Blower Sheave BK75 BK100 Belt BX68 BX75 Motor HP each 4.0 6.3 RPM 1450 1450 Frame size 184T 213T
FILTERS
1,2
12 - (12 x 24 x 2)
--
3
2 - (20 x 24 x 4),
Quantity - Size
5 - (18 x 24 x 2)
5 - (18 x 24 x 4)
- 4 - (24 x 24 x 4)
1. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value) 3.
2. 2 In. Pleated, Optional, MERV 7.
3. 4 In. Pleated, Optional, MERV 13.
1,2
3
ZF180-240 Unit Limitations
Unit Limitations
Size (Tons) Unit Voltage
180 (15) 380/415-3-50 342 457 125.6 / 52 240 (20) 380/415-3-50 342 457 125.6 / 52
12 Johnson Controls Unitary Products
Applied Voltage Outdoor DB Temp
Min Max Max (°F) / (°C)