YORK
with a common footprint cabinet and common roof curb for
all 7-1/2 through 12-1/2 ton models. All units have two
compressors with independent refrigeration circuits to
provide 2 stages of cooling. The units were designed for
light commercial applications and can be easily installed on
a roof curb, slab, or frame.
All Predator
rigid full perimeter base rails allowing for 3-way forklift
access and overhead rigging. Every unit is completely
charged, wired, piped, and tested at the factory to provide a
quick and easy field installation.
All units are convertible between side and down airflow.
Independent economizer designs are used on side and
down discharge applications, as well as all tonnage sizes.
Predator
cooling only, cooling with electric heat, and cooling with gas
heat. Electric heaters are available as factory-installed
options or field-installed accessories.
All units provide constant supply air volume.
Predator® units are convertible single packages
®
units are self-contained and assembled on
®
units are available in the following configurations:
ZF 12-1/2 TON
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
862075-XTG-G-0415
Roof curbs in eight- and
fourteen-inch heights. Roof
curbs for transitioning from
York Sunline™ footprint to
the ZF Series footprints
are also available (field
installed accessory)
Base rails w/forklift
slots (three sides)
and lifting holes
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
AA = None
AB = Phase Monitor
AC = Coil Guard
AD = Dirty Filter Switch
AE = Phase Monitor & Coil Guard
AF = Phase Monitor & Dirty Filter Switch
AG = Coil Guard & Dirty Filter Switch
AH = Phase Monitor, Coil Guard & Dirty Filter Switch
Additional Options
RC = Coil Guard & American Flag
TA = Technicoat Condenser Coil
TJ = Technicoat Evaporator Coil
TS = Technicoat Evaporator & Condenser Coils
7.5-12.5 Ton York® Model Number Nomenclature
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
* No Electric Heat Options for ZF090
** Only Hi Static Is Offered On ZF150
11.0 EER 12.5 Ton A/C
2" Pleated Filters, MERV 7
4" Pleated Filters, MERV 13
EA = ElectroFin Condenser Coil
EJ = ElectroFin Evaporator Coil
ES = ElectroFin Cond & Evap Coils
N20 = 200 MBH Output Aluminized Steel
S20 = 200 MBH Output Stainless Steel
* N10/S10 Not Available on ZF120/150
Airow
A = Std. Motor
D = Std. Motor/Motorized Damper (Downow Only)
H = Std Motor/Low Leak Econ/Barometric Relief (Downow
& Horizontal End Return Only)
J = Std Motor/Low Leak Econ/Power Exhaust (Downow
& Horizontal End Return Only)
N = Hi Static
R = Hi Static/Motorized Damper (Downow Only)
V = Hi Static Mtr/Low Leak Econ/Barometric Relief
(Downow & Horizontal End Return Only)
W = Hi Static Mtr/Low Leak Econ/Power Exhaust
(Downow & Horizontal End Return Only)
862075-XTG-G-0415
Johnson Controls Unitary Products3
862075-XTG-G-0415
Features and Benefits
Standard Features
• High Efficiency – High efficiency units reach as high as
11.2 EER. Gas/electric units have electronic spark ignition
and power vented combustion with steady state efficiencies
of 80%. These efficiencies exceed all legislated minimum
levels and provide low operating costs.
• Service Friendly – The Predator
of enhancements which improve serviceability.
The motor and blower slide out of the unit as a common
assembly. This facilitates greater access to all the indoor
airflow components, thus simplifying maintenance and
adjustment.
Service time is reduced through the use of hinged,
toolless panels. Such panels provide access to frequently
inspected components and areas, including the control
box, compressors, filters, indoor motor & blower, and the
heating section. The panels are screwed in place at the
factory to prevent access by children or other
unauthorized persons. It is recommended that the panels
be secured with screws once service is complete.
Service windows have been placed in both condenser
section walls. Rotation of the cover allows easy access to
the condenser coils for cleaning or inspection.
The Simplicity® SE control board provides alarm
messages to help quickly identify any faults.
All units use the same standard filter size. This
standardization removes any confusion on which filter
sizes are needed for replacement.
The non-corrosive drain pan slides out of the unit to permit
easy cleaning. The drain pan is accessed by removing the
drain pan cover plate on the rear of the unit. Once the plate is
removed, the drain pan slides out through the rear of the unit.
®
All Predator
units have a second model nameplate
located inside the control access door. This is to prevent
deterioration of the nameplate through weathering.
• Coil Technology – ZF condensers utilize Micro-Channel
“all aluminum” condensers which provide improved heat
transfer capabilities and reduced charge volumes.
• Environmentally Aware – For improved Indoor Air
Quality, a combination of foil faced and elastometric
rubber insulation is used exclusively throughout the units.
• Balanced Heating – The Predator
Heating Comfort” with a balance between 1
gas heating. The first stage of a gas heat Predator
provides 60% of the heating capacity. Balanced heating
allows the unit to better maintain desired temperatures.
• Convertible Airflow Design – The side duct openings
are covered when they leave the factory. If a side supply/
return is desired, the installer simply removes the two side
duct covers from the outside of the unit and installs them
over the down shot openings. No panel cutting is required.
Convertible airflow design allows maximum field flexibility
and minimum inventory.
• System Protection - Suction line freezestats are supplied
on all units to protect against loss of charge and coil frosting
when the economizer operates at low outdoor air
®
incorporates a number
®
offers “Ultimate
st
and 2nd stage
®
temperatures while the compressors are running. Every unit
has solid-core liquid line filter-driers and high and lowpressure switches. Internal compressor protection is
standard on all compressors. Crankcase heaters are
standard on reciprocating compressors. Scroll compressors
do not require crankcase heaters. Phase Monitors are
standard on units with scroll compressors. This accessory
monitors the incoming power to the unit and protects the
unit from phase loss and reversed phase rotation.
• Advanced Controls - Simplicity® SE control boards have
standardized a number of features previously available only
as options or by utilizing additional controls.
The Simplicity® SE control board used in this
product will effectively operate the cooling system
down to 0°F when this product is applied in a comfort
cooling application for people. An economizer is
typically included in this type of application. When
applying this product for process cooling applications
(computer rooms, switchgear, etc.), please
reference applications bulletin AE-011-07 or call the
applications department for Unitary Products @ 1877-UPG-SERV for guidance. Additional
accessories may be needed for stable operation at
temperatures below 30°F.
unit
• Units will come with the new state of the art SimplicitySE (Smart Equipment) control system. The new unit
control incorporates the best of the already proven
Simplicity™ unitary controls and creates a more robust,
intelligent control. The goal of this control is to utilize
cutting edge technology making the equipment easier to
install, operate, and service. All units are Factory
commissioned, configured, and run tested.
• Versatile - The Simplicity SE control can be configured to
use with a standard thermostat (easy to connect screw
terminals), A zone sensor, or can be setup to
4Johnson Controls Unitary Products
862075-XTG-G-0415
communicate with multiple BAS communication protocols
to integrate with building automation systems.
• Reduce field installed complexity - Each unit will comes
equipped with factory installed supply air, return air, and
outdoor air temperature sensors providing key
temperature readings thus reduce field installed
complexity.
• On-board USB Port - The new control comes with a long
list of features including data logging, current and
previous system faults and software update capabilities
using the on board USB port and common flash drive.
Energy use monitoring capabilities allow custom tailoring
to allow a system to work more efficiently at all times and
occupancy levels. Self test and start-up reports also
available from the board VIA the USB port.
• Embedded LCD Display - The board has a easy to read,
built-in LCD display and easy to use navigation joystick
and buttons allowing the user to quickly navigate the
menus displaying unit status, options, current function,
supply, return and outdoor temperatures, fault codes and
other information.
• Safety Monitoring - The control monitors the outdoor,
supply, and return air temperatures and the high and low
pressure switch status on the independent refrigerant
circuits. On units with heating the gas valve and high
temperature limit switches are monitored on gas and
electric heating units. The control also monitors the
voltage supplied to the unit and will protect the unit if low
voltage due to a brown out, or other electrical issue
occurs.
• Low Ambient - An integrated low-ambient control allows
units to operate in the cooling mode down to 0°F outdoor
ambient without additional components or intervention.
Optionally, the control board can be programmed to
lockout the compressors when the outdoor air
temperature is low or when free cooling is available.
• Anti-Short Cycle Protection - To aid compressor life, an
anti- short cycle delay is incorporated into the standard
control. Compressor reliability is further ensured by
programmable minimum run times. For testing, the antishort cycle delay can be temporarily overridden with the
push of a button.
• Fan Delays - Fan on and fan off delays are fully
programmable. Furthermore, the heating and cooling fan
delay times are independent of one another. All units are
programmed with default values based upon their
configuration of cooling and/or heating capacity.
• Nuisance Trip Protection and Three Strikes - To
prevent nuisance calls, the control board uses a three
times, you're out philosophy. The high, low-pressure
switch, anti-freeze protection, low voltage or heating high
limit must trip three times within two hours before the unit
control board will lock out the associated compressor.An
alarm message will be displayed on the LCD screen.
• Lead-Lag - An integrated Lead-Lag option allows equal
run time hours on all compressors, thereby extending the
life of all compressors. This option is selectable on the unit
control board.
• Low Limit Control (LLC) - To prevent the supply air from
dropping below a specified set point, when there is a
demand for cooling during cold outside conditions.
(Programmable Set point)
• Reliable – From the beginning – All units undergo
computer automated testing before they leave the factory.
Units are tested for refrigerant charge and pressure, unit
amperage, and 100% functionality. For the long term – All
Predator
®
units are painted with a long lasting, powder
paint that stands up over the life of the unit. The paint
used has been proven by a 1000 hour salt spray test.
• Flexible Placement – All models and configurations
share the same cabinet/footprint and thus the same roof
curb. You have the flexibility to set one curb and choose
the correct tonnage size and heating option after the
internal loads have been determined.
®
To further simplify planning and installation, Predator
ZF
cabinets are designed to fit your roof. With the optional
roof curb, the unit ductwork is designed to fit around 24”
on-center joists or between 48” on-center joists.
The drain pan can be rotated to drain to either the front or
the rear of the unit. Additionally, the drain pan can be
fitted to drain through the roof curb. As it is sometimes
difficult to have a level installation, the drain pan features
a generous slope to ensure proper drainage.
• Full Perimeter Base Rails – The permanently attached
base rails provide a solid foundation for the entire unit and
protect the unit during shipment. The rails offer forklift
access from 3 sides, and rigging holes are available so that
an overhead crane can be used to place the units on a roof.
• Easy Installation – Gas and electric utility knockouts are
supplied in the unit underside as well as the side of the unit.
A clearly identified location is provided to mount a field
supplied electrical disconnect switch. Utility connections can
be made quickly and with a minimum amount of field labor.
All units are shipped with 2” throw-away filters installed.
• Wide Range of Indoor Airflows – All indoor fan moto rs
are belt-drive type providing maximum flexibility to handle
most airflow requirements. For high static applications,
factory installed alternate indoor fan motors are available.
With the optional indoor fan motor, all units can supply
nominal airflow at a minimum of 1.5” ESP.
• Warranty - All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater
elements each carry a 5-year warranty. Aluminized steel
and stainless steel tubular heat exchangers carry a 10year warranty.
Factory Installed Options
YORK® offers several equipment options factory installed, for
the Predator
• Optional Factory Installed Economizers - Predator units
®
line.
offer a variety of optional factory installed economizers
with low leak dampers. The outdoor air enthal py se nsor
enables economizer operation if the outdoor enthalpy is
less than the setpoint of the economizer logic module. See
economizer options section to determine the correct
economizer for your application.
Johnson Controls Unitary Products5
862075-XTG-G-0415
• Down flow / End Return Economizers (with barometric relief and fresh air hood) - All units offer a variety of
optional factory installed down flow eco no m ize rs that are
shipped, installed and wired with low leak dampers
designed to meet ASHRAE 90.1-2010, AMCA 511 Class
1A damper, and the International Energy Con se rvati on
Code (IECC) certification requir emen ts by a c hi eving
leakage rates of 3 cfm/sq. ft. at 1" of static pressure. Each
economizer goes through a rigorous 60,000 cycle test. Dry
bulb, single enthalpy, and dual enthalpy (with field installed
kit) can be selected. The economizer has spring return,
fully modulating damper actuators and is capabl e o f
introducing up to 100% outdoor air. As the outdoor ai r
intake dampers open, the return air dampers close. The
changeover from mechanical refrigeration to economizer
operation is regulated by the outdoor ai r dry bulb
temperature or the outdoor air enthalpy input. The optional
(field installed) single or dual ent hal py ki ts pro vi de
additional inputs to monitor outdoor ai r/ or re turn ai r
humidity and temperature for true enthalpy contro l. The
installer needs only to assemble the outdoor air hood,
attach the enthalpy control the hood and mount th e h oo d
to the unit (Hood and control are provided).
• Power Exhaust - This factory option allows down flow or
horizontal end return economizer operation. The power
exhaust must be removed from the unit and mounted
in the horizontal end return duct work when applying
the product in the horizontal, end return
configuration.
• Motorized Outdoor Air Damper - The motorized outdoor
air damper includes a slide-in/plug-in damper assembly
with an outdoor air hood and filters. The outdoor air
dampers open to the preset position when the indoor fan
motor is energized. The damper has a range of 0% to
100% outdoor air entry. Factory installed option or field
installed accessory.
• Alternate Indoor Blower Motor - For applications with
high static restrictions, units are offered with optional
indoor motors that provide higher static output and/or
higher airflow, depending upon the installer’s needs.
• Aluminized Steel Gas Heat Exchanger - For
applications in non-corrosive environments.
• Stainless Steel Gas Heat Exchanger - For applications
in corrosive environments, this option provides a full
stainless steel heat exchanger assembly.
• Stainless Steel Drain Pan - An optional rust-proof
stainless steel drain pan is available to provide years of
trouble-free operation in corrosive environments.
• Electric Heaters (10 & 12.5 Ton Only) - The electric
heaters range from 18KW to 54kW and are available in all
the voltage options of the base units. All heaters are dual
staged. All heaters are intended for single point power
supply.
• Disconnect Switch - For gas heat units and cooling units
with electric heat, a HACR breaker sized to th e unit is
provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed optio n onl y.
• Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment. Available
for both the supply and/or return air configurations.
• Filters – 2” Pleated MERV 7 or 4” Pleated MERV 13 are
available to meet LEED requirements. A 2” Throwaway is
shipped as standard.
Factory-installed smoke detectors may be subjected to
extreme temperatures during "off" times due to outside air
infiltration. These smoke detectors have an operational
range of -4 °F to 158°F. Smoke detectors installed in areas
that could be outside this range will have to be relocated to
prevent false alarms.
• Phase Monitors - Designed to prevent unit damage. The
phase monitor will shut the unit down in an out-of phase
condition. (Standard on units with Scroll Compressors.)
• Coil Guard - Customers can purchase a coil guard kit to
protect the condenser coil from damage. Additionally, this
kit stops animals and foreign objects from entering the
space between the inner condenser coil and the main
cabinet. This is not a hail guard kit.
• Dirty Filter Switch - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option or
field installed accessory.
• Technicoat Condenser Coils - The condenser coils are
coated with a phenolic coating for protection against
corrosion due to harsh environments.
• Technicoat Evaporator Coil - The evaporator coils are
coated with a phenolic coating for protection against
corrosion due to harsh environments.
• ElectroFin® E-coat Condenser Coils - The condenser
coils are coated with an epoxy polymer coating to protect
against corrosion.
• ElectroFin® E-coat Evaporator Coils - The evaporator
coils are coated with an epoxy polymer coating to protect
against corrosion.
Control Options
• Simplicity® SE with Communication Option Control The York® Simplicity® SE with Communication Option
Control is factory installed. It includes all the features of
the Simplicity® SE control with an additional gateway to
BACnet MS/TP (programmable to Modbus or N2
protocols).
• Novar® BAS Control - The Novar® building automation
system controller is factory installed. Incudes supply air
sensor, return air sensor, dirty filter indicator switch, and
air proving switch.
• CPC BAS Control - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building
automation system controller is factory installed. Includes
6Johnson Controls Unitary Products
862075-XTG-G-0415
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
• Honeywell BAS Control - The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
Field Installed Accessories
YORK® offers several equipment accessories for field
installation, for the Predator
• Down flow and End Return Economizers (with fresh air hood and barometric relief) - All units offer a variety of
optional factory installed down flow economizers that are
shipped, installed and wired with low leak dampers designed
to meet ASHRAE 90.1-2010, AMCA 511 Class 1A damper,
and the International Energy Conservation Code (IECC)
certification requirements by achieving leakage rates of 3
cfm/sq. ft. at 1" of static pressure. Each economizer goes
through a rigorous 60,000 cycle test. Dry bulb, single
enthalpy, and dual enthalpy (with field installed kit) can be
selected. The economizer has spring return, fully modulating
damper actuators and is capable of introducing up to 100%
outdoor air. As the outdoor air intake dampers open, the
return air dampers close. The changeover from mechanical
refrigeration to economizer operation is regulated by the
outdoor air dry bulb temperature or the outdoor air enthalpy
input. The dual enthalpy kit provides a second input used to
monitor the return air (field installed). The installer needs only
to assemble the outdoor air hood, attach the enthalpy control
the hood and mount the hood to the unit (Hood and control
are provided).
• Single or Dual Enthalpy Control, Accessories - These
kits contain the required components to convert a dry bulb
economizer to a single enthalpy and/or dual enthalpy
economizer.
• Barometric Relief Damper - Zero to 100% capacity
barometric relief dampers for use with horizontal flow, or
field installed slab economizers.
• Power Exhaust - This accessory installs in the unit with a
down flow economizer. Power exhaust plugs into the
connector in the unit bulkhead. You must purchase
1EH0408 barometric relief when applying to a
horizontal flow application.
• Manual Outdoor Air Damper - Like the motorized outdoor
air damper, each manual outdoor air damper includes a
slide-in damper assembly with an outdoor air hood and
filters. Customers have a choice of dampers with ranges of
0% to 100% or 0% to 35% outdoor air entry.
• Motorized Outdoor Air Damper - The motorized outdoor
air damper includes a slide-in/plug-in damper assembly with
an outdoor air hood and filters. The outdoor air dampers
open to the preset position when the indoor fan motor is
energized. The damper has a range of 0% to 100% outdoor
air entry. Factory installed option or field installed accessory.
• Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment.
®
line.
Sensor- Senses CO2 levels and automatically
• CO
2
overrides the economizer when levels rise above the
preset limits.
• Dirty Filter Switch - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters.
• Coil Guard - Field installed decorative wire coil guard.
• Hail Guard - This kit includes a sloped hood which installs
over the outside condenser coil and prevents damage to
the coil fins from hail strikes. Field installed accessory only.
• Flue Exhaust Extension Kit - In locations with wind or
weather conditions which may interfere with proper
exhausting of furnace combustion products, this kit can be
installed to prevent the flue exhaust from entering nearby
fresh air intakes.
• -60°F Gas Heat Kit - For installations which require gas
heat units to perform in low ambient temperatures, a gas
section heating kit is available. This kit provides electric
heat in the gas heat controls section to ensure the gas
valve and controls will continue to function properly at
extremely low temperatures.
• Gas Heat High Altitude Kit - This kit converts a gas heat
unit to operate at high altitudes, 2,000 to 6,000 feet.
Conversion kits are available for natural gas and propane.
• Gas Heat Propane Conversion Kit - This kit converts a
gas-fired heater from natural gas to propane. It contains the
main burner orifices and gas valve replacement springs.
• Gas Piping Kit - Contains pipe nipples, fittings and gas cock
required for gas supply connection with external shut off.
• Electric Heaters (10 & 12.5 Ton Only) - The electric
heaters range from 18 kW to 54kW.
All heaters are dual staged. Cooling units include an
adapter panel for easy installation of the electric heaters.
Necessary hardware and connectors are included with the
heaters. All heaters are intended for single point power
supply.
• Low Limit / Compressor Lockout Kit
• Compressor Lockout (CLO): To prevent mechanical
(compressorized) operation of the unit during cold
outdoor conditions where there is a risk of returning
liquid refrigerant back to the compressors.
• Low Limit Control (LLC): To prevent the supply air
from dropping below a specified setpoint by utilizing the
units first stage heating means when there is a demand
for cooling during cold outside conditions.
• Metal Frame Filter Kit - Metal frame with polyester filter
medium.
• Permanent Filters - Permanent filters are available.
• Roof Curbs - The roof curbs have insulated decks and are
shipped disassembled The roof curbs are available in 8” and
14” heights. For applications with security concerns, burglar
bars are available for the duct openings of the roof curbs.
• Roof Curb Transition - Single Piece Adapter (10” High) Roof curbs for transitioning from Sunline™ units to
Predator
®
units. Fits 7.5 to 12.5 Sunline™ roof curbs only.
Johnson Controls Unitary Products7
862075-XTG-G-0415
• Burglar Bars - Mount in the supply and return openings
to prevent entry into the duct work.
• Thermostat - The units are designed to operate with 24-
units (with or without an economizer) operate with twostage heat/two-stage cool or two-stage cooling only
thermostats, depending upon unit configuration.
volt electronic and electro-mechanical thermostats. All
Accessories
Field Installed Accessories - Non-Electrical
MODELVOLTAGE DESCRIPTIONWHERE USED
1BD0408AllBurglar Bars, DownflowAll Cabinets
1CG0419AllCoil Guard(Electric / Electric Models), 50” Tall Standard Cabinets
1CG0420AllCoil Guard(Gas / Electric Models), 50" Tall Standard Cabinets
1CG0427AllCoil Guard(Electric / Electric Models), 42” Tall Cabinets
1CG0428AllCoil Guard(Gas / Electric Models), 42" Tall Cabinets
All Tall (50") Standard Cabinets, (Excludes 12.5T "V"
1HG0411AllHail Guard Kit
1HG0415AllHail Guard KitAll Short (42") Standard Cabinets
1FE0411AllFlue Exhaust Extension KitAll Cabinets
1FF0414All2" only Metal Filter Frame KitAll Tall 50" Cabinets
1FF0415All2" only Metal Filter Frame KitAll Tall 42" Cabinets
1FL0402AllPermanent 2" only Filter Kit Includes (4) Four Filters)All Tall 50" Cabinets
1FL0423AllPermanent 2" only Filter Kit (Includes (4) four Filters)All Tall 42" Cabinets
1GP0405AllGas Piping KitAll Cabinets
1HA0442AllHigh Altitude Kit for Natural GasAll 7 1/2 - 12T Cabinets
1HA0443AllHigh Altitude Kit for PropaneAll 7 1/2 - 12T Cabinets
1NP0442AllPropane Conversion KitAll 6 - 12T Cabinets
1RC0470AllRoof Curb, 8" HeightAll Cabinets
1RC0471AllRoof Curb, 14" HeightAll Cabinets
Roof Curb, Transition (7.5 T thru 12.5T Sunline to
1RC0472All
1WC0412All
Predator 3- 12T)All Cabinets
Wooden Crate for extra protection during shipping and
handling
cabinets)
Standard Cabinets Only (not applicable to units 119" in
length)
Field Installed Accessories - Electric Heat
MODELVOLTAGE DESCRIPTIONWHERE USED
2TP04521850380/415-3-50 18kW Electric HeatAll 50" Cabinet 10 Ton Models
2TP04522450380/415-3-50 24kW Electric HeatAll 50" Cabinet 10 and 12.5 Ton Models
2TP04523650380/415-3-50 36kW Electric HeatAll 50" Cabinet 10 and 12.5 Ton Models
2TP04525450380/415-3-50 54kW Electric HeatAll 50" Cabinet 10 and 12.5 Ton Models
No factory or field installed electric heater available for 42” Cabinet ZF090
*Note:
8Johnson Controls Unitary Products
862075-XTG-G-0415
Accessories (Continued)
Field Installed Accessories - Fresh Air
MODELVOLTAGE DESCRIPTIONWHERE USED
1FA0413AllManual Outside Air Damper 0-35%, DownflowAll Cabinets
1FA0414AllManual Outside Air Damper 0-100%, DownflowAll Cabinets
2EC0402AllDual Enthalpy Control (Includes 2 Sensors)All Cabinets
2EE04707624All
2EE04707424All
2EE04706924AllHorizontal Economizer without Barometric ReliefAll Cabinets
2MD04703824AllMotorized Damper, Downflow without Barometric Relief All Cabinets
2MD04703924All
2PE04704706*230Power Exhaust 230V Downflow or HorizontalAll Cabinets
2PE04704746*460Power Exhaust 460V Downflow or HorizontalAll Cabinets
2PE04704758*575Power Exhaust 575V Downflow or HorizontalAll Cabinets
* Must be installed in return Duct on Horizontal Applications and a 1EH0408 is required. Approved for operation on 50Hz
Barometric Relief Kit for Power Exhaust, Horizontal
Application
Economizer for Downflow, End Return Horizontal, or
ERV Applications. Includes FA Hood, Exhaust Hood w/
Baro Relief
Economizer for Downflow, End Return Horizontal, or
ERV Applications. Includes FA Hood, Exhaust Hood w/
Baro Relief
Motorized Damper, Horizontal without Barometric
Relief
Field Installed Accessories - Controls
MODELVOLTAGE DESCRIPTIONWHERE USED
2AP0401AllAir Proving SwitchAll Units
2AQ04700324AllCO2 Space AccessoryAll Units
2AQ04700424AllCO2 Unit AccessoryAll Units
2DF0402AllDirty Air SwitchAll Units
2SH0401All
2SD04700824AllSmoke Detector for SupplyAll Gen 5 units and greater with 2" & 4" Filters
2SD04700924AllSmoke Detector for ReturnAll Gen 5 units and greater with 2" & 4" Filters
2SD04701024AllSmoke Detector for Supply and ReturnAll Gen 5 units and greater with 2" & 4" Filters
S1-YKMAP1810-0P
S1-MP-PRTKIT0P
All
All
Wall Mounted humidity sensor-For use with MagnaDry
Reheat or space humidity input to Simplicity SE board.
MAP (Mobile Access Portal) Gateway- For use with
Simplicity SE Control.
MAP (Multiple Access Portal) Gateway KitReplacement MAP gateway protective case, lanyard
and communication cable. Use only to replace worn or
damaged components.
All Cabinets
All 50" Cabinets
All 42" Cabinets
All Cabinets
All Cabinets
All Units
All Units
Field Installed Accessories - Electrical
MODELVOLTAGE DESCRIPTIONWHERE USED
2BC04700106230Gas heat kit, -60ºFAll Units
2BC04700151460Gas heat kit, -60ºFAll Units
2BC04700154575Gas heat kit, -60ºFAll Units
2LA04704632AllLow Ambient KitAll 3 - 10T units (excludes 12.5T "V" cabinets)
Guide Specifications
GENERAL
Units shall be manufactured by York International Unitary
Products in an ISO 9001 certified facility. YORK® Predator
units are convertible single packages with a common footprint
cabinet and common roof curb for all 7-1/2 through 12-1/2 ton
models. All units have two compressors with independent R410A refrigeration circuits to provide 2 stages of cooling. The
units were designed for light commercial applications and can
be easily installed on a roof curb, slab, or frame. All Predator
units are self-contained and assembled on rigid full perimeter
base rails allowing for 3-way forklift access and overhead
rigging. Every unit is completely charged with R-410A, wired,
®
piped, and tested at the factory to provide a quick and easy
field installation. All units are convertible between side and
down airflow. Independent economizer designs are used on
side and down discharge applications, as well as all tonnage
sizes. Predator
®
units are available in the following
configurations: cooling only, cooling with electric heat, cooling
with gas heat, heat pump, and heat pump with electric heat.
Electric heaters are available as factory-installed options or
field-installed accessories.
®
DESCRIPTION
Units shall be factory assembled, single package, (Elec/Elec, Gas/
Elec), designed for outdoor installation. They shall have built in
Johnson Controls Unitary Products9
862075-XTG-G-0415
field convertible duct connections for down discharge supply/return
or horizontal discharge supply/return and be available with factory
installed options or field installed accessories. The units shall be
factory wired, piped and charged with R-410A refrigerant and
factory tested prior to shipment. All unit wiring shall be both
numbered and color coded. The cooling performance shall be
rated in accordance with DOE and AHRI test procedures and
MEW-2010.
UNIT CABINET
Unit cabinet shall be constructed of galvanized steel with
exterior surfaces coated with a non-chalking, powder paint
finish, certified at 1000 hour salt spray test per ASTM-B117
standards. Indoor blower sections shall be insulated with up to
1” thick insulation coated on the airside. Either aluminum foil
faced or elastometric rubber insulation shall be used in the
unit’s compartments and be fastened to prevent insulation from
entering the air stream. Cabinet doors shall be hinged with
toolless access for easy servicing and maintenance. Full
perimeter base rails shall be provided to assure reliable transit
of equipment, overhead rigging, fork truck access and proper
sealing on roof curb applications. Disposable 2” filters shall be
furnished as standard and be accessible through hinged access
door. Fan performance measuring ports shall be provided on
the outside of the cabinet to allow accurate air measurements
of evaporator fan performance without removing panels or
creating bypass of the coils. Condensate pan shall be slide out
design, constructed of a non corrosive material, internally
sloped and conforming to ASHRAE 62-B9 standards.
Condensate connection shall be a minimum of ¾” I.D. female
and be rigid mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be a belt drive assembly and include an adjustable
pitch motor pulley. Job site selected brake horsepower shall not
exceed the motors nameplate horsepower rating plus the service factor. Units shall be designed to operate within the service
factor. Fan wheel shall be double inlet type with forward curve
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Airflow design shall be constant
volume. Bearings shall be sealed and permanently lubricated
for longer life and no maintenance. Entire blower assembly and
motor shall be slide out design.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fans shall be of the direct drive type, discharge air
vertically, have aluminum blades riveted to corrosion resistant
steel spider brackets and shall be dynamically balanced for
smooth operation. The outdoor fan motors shall have permanently
lubricated bearings internally protected against overload
conditions and staged independently. A cleaning window shall be
provided on two sides of the units for coil cleaning.
REFRIGERANT COMPONENTS
Compressors:
a. Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over
temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of + or –
10% of the unit nameplate voltage.
b. Shall have internal spring isolation and sound muffling to
minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.
Coils:
a. Evaporator coils shall have aluminum plate fins
mechanically bonded to seamless internally enhanced
copper tubes with all joints brazed. Special Phenolic
coating shall be available as a factory option.
b. Evaporator coils shall be of the direct expansion, draw-
thru design.
c. Condenser coils shall have Micro-Channel aluminum
tube, aluminum fins.
d. Condenser coils shall be of the draw-thru design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Independent thermally operated expansion devices.
b. Solid core filter drier/strainer to eliminate any moisture or
foreign matter.
c. Accessible service gage connections on both suction
and discharge lines to charge, evacuate, and measure
refrigerant pressure during any necessary servicing or
troubleshooting, without losing charge.
d. The unit shall have two independent refrigerant circuits,
equally split in 50% capacity increments.
Unit Controls:
a. Unit shall be complete with self-contained low-voltage
control circuit protected by a resettable circuit breaker on
the 24-volt transformer side.
b. Unit shall incorporate a lockout circuit which provides
reset capability at the space thermostat or base unit
should any of the following standard safety devices trip
and shut off compressor:
c. Loss-of-charge/Low-pressure switch.
• High-pressure switch.
• Freeze-protection thermostat, evaporator coil. If any of
the above safety devices trip, an LED (light-emitting
diode) indicator shall flash a diagnostic code that
indicates which safety switch has tripped.
d. Unit shall incorporate “AUTO RESET” compressor over
temperature, over current protection.
e. Unit shall operate with conventional thermostat designs
and have a low voltage terminal strip for easy hook-up.
f. Unit control board shall have on-board diagnostics and
fault code display.
g. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to
0 ºF.
10Johnson Controls Unitary Products
862075-XTG-G-0415
h. Control board shall monitor each refrigerant safety switch
independently.
i. Control board shall retain last 5 fault codes in non-
volatile memory, which will not be lost in the event of a
power loss.
GAS HEATING SECTION (IF EQUIPPED)
Heat exchanger and exhaust system shall be constructed of
aluminized steel and shall be designed with induced draft combustion with post purge logic, energy saving direct spark ignition, and redundant main gas valve. The heat exchanger shall
be of the tubular type, constructed of T1-40 aluminized steel for
corrosion resistance and allowing minimum mixed air entering
temperature of 40 ºF. Burners shal l be of the in-shot type, constructed of aluminum-coated steel. All gas piping shall enter the
unit cabinet at a single location, through either the side or bottom, without any field modifications. An integrated control board
shall provide timed control of evaporator fan functioning and
burner ignition. Heating section shall be provided with the following minimum protection:
a. Primary and auxiliary high-temperature limit switches.
b. Induced draft pressure sensor.
c. Flame roll out switch (manual reset).
d. Flame proving controls.
e. All two stage units shall have two independent stages of
capacity (60% 1
st
stage, 100% 2nd stage).
ELECTRIC HEATING SECTION (IF EQUIPPED)
FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall be
made available by either/or):
• DRY BULB AUTOMATIC ECONOMIZER - Outdoor and
return air dampers that are interlocked and positioned by
a fully-modulating, spring-return damper actuator. The
maximum leakage rate for the outdoor air intake dampers
shall be designed to meet ASHRAE 90.1-2010, AMCA
511 Class 1A damper, and the International Energy
Conservation Code (IECC) certification requirements by
achieving leakage rates of 3 cfm/sq. ft. at 1" of static
pressure. Changeover from compressor to economizer
operation shall be provided by an integral electronic
enthalpy control that feeds input into the basic module.
The outdoor intake opening shall be covered with a rain
hood that matches the exterior of the unit. Water
eliminator/filters shall be provided.
• MOTORIZED OUTDOOR AIR DAMPERS – Outdoor and
return air dampers that are interlocked and positioned by
a 2-position, spring-return damper actuator. The
maximum leakage rate for the outdoor air intake dampers
shall not exceed 2% when dampers are fully closed and
operating against a pressure differential of 0.5 IWG. A
unit-mounted potentiometer shall be provided to adjust
the outdoor and return air damper assembly to take in the
design CFM of outdoor air to meet the ventilation
requirements of the conditioned space during normal
operation. Whenever the indoor fan motor is energized,
the dampers open up to one of two pre-selected positions
– regardless of the outdoor air enthalpy. Dampers return
to the fully closed position when the indoor fan motor is
de-energized. Dampers shall fully close on power loss.
An electric heating section, with nickel chromium elements,
shall be provided in a range of 18 thru 54 KW, offering two
states of capacity all sizes. The heating section shall have a primary limit control(s) (automatic reset) to prevent the heating
element system from operating at an excessive temperature.
The Heating Section assembly shall slide out of the unit for
easy maintenance and service. Units with Electric Heating Sections shall be wired for a single point power supply with branch
circuit fusing (where required).
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125 ºF outdoor
temperature, exceeding maximum load criteria of AHRI Standard 340/360. The compressor, with standard controls, shall be
capable of operation down to 0 ºF outdoor temperature. Unit
shall be provided with fan time delay to prevent cold air delivery
before heat exchanger warms up. (Gas heat only)
ELECTRICAL REQUIREMENTS - All unit power wiring shall
enter unit cabinet at a single factory provided location and be
capable of side or bottom entry to minimize roof penetrations
and avoid unit field modifications. Separate side and bottom
openings shall be provided for the control wiring.
ST ANDARD LIMITED WARRANTIES - Compressor – 5 Years,
Heat Exchanger – 10 Years, Elect. Heat Elem. – 5 Years,
Parts – 1 Year
ADDITIONAL FACTORY INSTALLED OPTIONS
• ALTERNATE INDOOR BLOWER MOTOR – For
applications with high restrictions, units are available with
optional indoor blower motors that provide higher static
output and/or higher airflow.
• ELECTRIC HEAT (10 & 12.5 Ton Only) - Electric Heaters
range from 18 kW to 54 kW and are available in all the
voltage options of the base unit.
• PHASE MONITOR - Designed to prevent damage in outof-phase condition.
• COIL GUARD - Designed to prevent condenser coil
damage.
• BAS CONTROLS - Include supply air sensor, return air
sensor, dirty filter indicator and air proving switch.
• DIRTY FILTER SWITCH – This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally highpressure drop across the filters.
• BREAKER – An HACR breaker can be factory installed
on gas heat units or cooling units with electric heat.
• DISCONNECT SWITCH - A disconnect can be factory
installed on a cooling only units sized for the largest
electric heat available.
Johnson Controls Unitary Products11
862075-XTG-G-0415
• STAINLESS STEEL HEAT EXCHANGER – For
applications in a corrosive environment, this option
provides a full stainless steel heat exchanger assembly.
• SMOKE DETECTOR – A smoke detector can be factory
mounted and wired in the supply and/or return air
compartments.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
• ROOF CURB - 14” and 8” high, full perimeter knockdown
curb, with hinged design for quick assembly.
• BAROMETRIC RELIEF DAMPER – (Unit mounted –
Downflow, Duct Mounted – Horizontal) – Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit during economizer operation.
• PROPANE CONVERSION KIT – Contains new orifices
and gas valve springs to convert from natural to L.P. gas.
• 60ºF GAS HEAT KIT – Provides an electric heat kit for the
gas compartment for use in extreme low ambient
conditions.
• ECONOMIZER (Downflow and Horizontal flow)
• POWER EXHAUST – (Unit mount – Downflow, Duct
mount – Horizontal flow)
• DUAL ENTHALPY KIT - Provides a second input to
economizer to monitor return air.
12Johnson Controls Unitary Products
Physical Data
ZF090-150 Physical Data
Component
ZF090ZF120ZF150
Nominal Tonnage7.51012.5
Gross Capacity @ AHRI A point (Mbh)88200115300151500
EER11.211.211.0
Nominal CFM300040005000
System power (KW)7.2110.0512.7
Refrigerant typeR-410AR-410AR-410A
Refrigerant charge (lb-oz)
System 14-127-128-3
System 24-127-88-10
Face area (Sq. Ft.)18.529.029.0
Rows111
Fins per inch232323
Tube diameter (in.)/mm.71/181/25 1/25
Circuitry Type2-pass Microchannel 2-pass Microchannel 2-pass Microchannel
EVAPORATOR COIL DATA
Face area (Sq. Ft.)10.613.213.2
Rows344
Fins per inch151515
Tube diameter0.3750.3750.375
Circuitry TypeIntertwinedIntertwinedIntertwined
Refrigerant controlTXVTXVTXV
Models
1
2
1
2
1
2
1
2
862075-XTG-G-0415
Johnson Controls Unitary Products13
862075-XTG-G-0415
ZF090-150 Physical Data (Continued)
Component
ZF090ZF120ZF150
Nominal Tonnage7.51012.5
CONDENSER FAN DATA
Quantity of Fans224
Fan diameter (Inch)242424
TypePropPropProp
Drive typeDirectDirectDirect
Quantity of motors224
Motor HP each @ 50 Hz. 3/4 3/4 3/4
No. speeds111
RPM @ 50 Hz.940
2
Nominal total CFM7600950013900
BELT DRIVE EVAP FAN DATA
Quantity111
Fan Size (Inch)12 x 1215 x 1515 x 15
TypeCentrifugalCentrifugalCentrifugal
Motor Sheave1VM501VM501VM501VP561VP56
Blower SheaveAK59AK54AK74AK66BK72
BeltA49A47A54A56BX56
Motor HP each @ 50 Hz.22244
RPM @ 50 Hz.1425
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. Capacity rating are based on 80 F (26.6 C) Entering Air Dry Bulb Temperature.
3. These ratings include the condenser fan motors, the compressor motors and supply air blower motor (External Static Pressure 0.25 IWG/
62.3 Pa).
Temperature of Air on Condenser Coil
Total
1,2
Capacity
(MBh)
(kW)
Total
Input
Sensible Capacity (MBh)
3
Johnson Controls Unitary Products17
Loading...
+ 38 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.