Page 1
TECHNICAL GUIDE
SPLIT-SYSTEM
HEAT PUMPS
14.5 SEER – R-410A
MODELS:
YHJF18 THRU 60
(1.5 THRU 5 NOMINAL TONS, 1 PHASE)
Due to continuous product improvement, specif ic a t io ns
are subject to change without notice.
Visit us on the web at www.york.com
Additional rating information can be found at
www.ahridirectory.org
LISTED
ISO 9001
Certified Quality
Management System
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
510667-YTG-A-0409
DESCRIPTION
The heat pump condensing unit is the outdoor part of a versatile
system of heating and air conditioning. It is designed to be custom-matched with one of UPG’s complete line of evaporator
sections, with each serving a specific function. Matching Air
Handlers are available for upflow, downflow, or horizontal applications to provide a complete system. Electric Heaters are
available, if required. Add-on coils are available for use with
upflow, downflow, or horizontal furnaces and air handlers. Many
matches meet Federal Tax Rebate program.
WARRANTY
Single Phase Units:
5-year limited parts warranty.
10- year limited compressor warranty.
FEATURES
• QUALITY CONDENSER COILS - The coil is constructed of
copper tubing and enhanced aluminum fins for increased
efficiency and corrosion protection.
• PROTECTED COMPRESSOR - The complete scroll compressor line is internally protected against high pressure,
temperature, and externally by a factory installed high pressure switch. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor
which protects the compressor if undesirable operating conditions occur. A liquid line filter-drier further protects the compressor.
• DURABLE FINISH - The cabinet is made of pre-painted
steel. The pre-treated galvanized steel provides a better
paint to steel bond, which resists corrosion and rust creep.
Special primer formulas and matted-textured finish insure
less fading when exposed to sunlight.
• LOWER INSTALLED COST - Installation time and costs are
reduced by easy power and control wiring connections.
Available in sweat connect models only. The unit contains
enough refrigerant for matching indoor coils and 15 feet of
interconnecting piping. The small base dimension means
less space is required on the ground or roof.
• TOP DISCHARGE - The warm air from the top mounted fan
is blown up away from the structure and any landscaping.
This allows compact location on multi-unit applications.
• SWEPT FAN BLADE SOUND JACKET - The upward air
flow carries the normal operating noise away from the living
area. The rigid top panel effectively isolates any motor
sound. Isolator mounted compressor and the rippled fins of
the condenser coil muffle the normal fan motor and compressor operating sounds. The swept wing fan blade and compressor sound jacket futher reduce noise levels.
• LOW MAINTENANCE - Long life permanently lubricated
motor-bearings need no annual servicing.
• EASY SERVICE ACCESS - Fully exposed refrigerant connections, and a single panel covering the electrical controls
make for easy servicing of the unit.
• SECURED SERVICE VALVES - Secured re-usable service
valves are provided on both the liquid and vapor sweat connections for ease of evacuating and charging.
• U.L. and C.U.L. listed - approved for outdoor application.
• Agency Listed - U.L. and C.U.L. listed - approved for outdoor application. The unit is certified in accordance with the
Unitary Small Equipment cerification program, which is
based on ARI Standard 210/240.
Page 2
510667-YTG-A-0409
Physical and Electrical Data
MODEL
YHJF18
S41S1
YHJF24
S41S1
YHJF30
S41S1
YHJF36
S41S1
YHJF42
S41S1
YHJF48
S41S1
YHJF60
S41S1
Unit Supply Voltage 208-230V, 1 60Hz
Normal Voltage Range
1
187 to 252
Minimum Circuit Ampacity 11.9 17.6 17.3 23.7 26.1 28.8 35.3
Max. Overcurrent Device Amps
Min. Overcurrent Device Amps
2
3
20 30 30 40 45 50 60
15 20 20 25 30 30 40
Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Compressor Amps
Rated Load 9.0 13.4 12.8 17.9 19.8 28.8 35.3
Locked Rotor 48.0 58.3 64.0 96.7 115.0 115.0 118.0
Crankcase Heater No No No No No No No
Fan Motor Amps Rated Load 0.7 0.8 1.3 1.3 1.3 1.3 1.3
Fan Diameter Inches 24 22 24 24 24 24 24
Rated HP 1/10 1/8 1/4 1/4 1/4 1/4 1/4
Fan Motor
Nominal RPM 825 1075 850 850 850 850 850
Nominal CFM 2000 2000 3900 3900 3900 3800 3800
Face Area Sq. Ft. 15.72 19.17 23.58 23.58 23.58 23.58 23.58
Coil
R o w s D e e p 1111122
Fin / Inches 22 22 22 22 22 18 18
Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Vapor Line Set OD (Field Installed) 3/4 3/4 3/4 3/4 7/8 7/8 1-1/8
Unit Charge (Lbs. - Oz.)
4
6 – 15 7 – 14 9 – 14 10 – 9 10 – 9 14 – 2 14 – 2
Charge Per Foot, Oz. 0.62 0.62 0.62 0.62 0.67 0.67 0.75
Operating Weight Lbs. 145 145 176 193 198 248 290
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add
or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.
Unit
Model
18
Dimensions
(Inches)
1
A
B C Liquid Vapor
28 34 34
24 40 29 29
30 40 34 34
36 40 34 34
42 40 34 34
60 40 34 34
1. Including Fan Guard.
Refrigerant Connection
Service Valve Size
3/4”
3/8”
7/8” 48 40 34 34
2 Johnson Controls Unitary Products
Page 3
510667-YTG-A-0409
System Charge for Various Matched Systems
Outdoor Unit
Required Orifice or TXV
Factory Charge, lbs-oz 6 - 15 7 - 14 9 - 14 10 - 9 10 - 9 14 - 2 14 - 2
Indoor Coil
FC/MC/PC/UC32 .051 + 0 .059 + 0 – – – – –
FC/MC/PC/UC35 .051 + 0 .059 + 0 – – – – –
FC/MC/PC/UC37 .051 + 13 .059 + 12 .063 + 0 .071 + 0 – – –
FC/MC/PC/UC43 .051 + 13 .059 + 12 .063 + 0 .071 + 0 – – –
F C / P C 6 2 D 3 X –––– . 075 + 0 TXV + 0 TXV + 0
AHX30 .051 + 0 .059 + 0 – – – – –
AHX36 .051 + 13 .059 + 12 .063 + 0 .071 + 0 – – –
AHX60 .075 + 0 TXV + 0 TXV + 0
AV36 .051 + 13 .059 + 12 .063 + 0 .071 + 0 – – –
F6FP030H06 .051 + 0 .059 + 0 – – – – –
F6FP036H06 .051 + 0 .059 + 0 – – – – –
F6FP042H06 – – .063 + 3 .063 + 3 – – –
F6FP060H06 –––– . 075 + 0 TXV + 0 TXV + 0
FOOTNOTES:
1. For applications requiring a TXV use 1TVM900 series kit.
2. Approved orifice shipped with outdoor unit.
3. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
4. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the cond enser, the smallest evaporator and 15 feet of interconnecting
2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical Data Table.
4. For orifice or TXV matches requiring additional charge, the refrigerant needs to be weighed in for specific coil match and lineset length.
5. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator +
3,4
line tubing.
adder for line set.
1,2
YHJF18
S41S1
.051/1TVM4F1 .059/1TVM4G1 .063/1TVM4G1 .071/1TVM4H1 .075/1TVM4J1 1TVM4J1 1TV M4K1
YHJF24
S41S1
YHJF30
S41S1
YHJF36
S41S1
Additional Charge, Oz
YHJF42
S41S1
YHJF48
S41S1
YHJF60
S41S1
Johnson Controls Unitary Products 3
Page 4
510667-YTG-A-0409
COOLING CAPACITY - With Air Handler Coils
UNIT
MODEL
AIR HANDLER
MODEL W
COIL
MODEL
STAGE
1
RATED
CFM
TOTAL SENS.
14.5 SEER HP WITH MV - VARIABLE SPEED
YHJF18S41S1
YHJF24S41S1
YHJF30S41S1
YHJF36S41S1
MV12B 17 FC/MC35B – 600 18.0 13.0 15.00 12.50
MV12B 17 FC/MC43B – 600 18.0 13.3 15.00 12.50
MV12B 17 FC/MC35B – 800 22.8 17.2 15.00 12.50
MV12B 17 FC/MC43B – 800 23.4 18.0 15.00 12.50
MV12B 17 FC/MC43B – 1000 29.0 21.6 15.00 12.50
MV16C 21 FC/MC43C – 1000 29.0 21.6 15.00 12.50
MV12B 17 FC/MC43B – 1225 35.4 26.6 14.35 12.00
MV16C 21 FC/MC43C – 1200 35.2 26.4 14.50 12.00
YHJF42S41S1 MV20D 24 FC/MC62D – 1400 40.0 30.8 14.50 12.00
YHJF48S41S1 MV20D 24 FC/MC62D – 1630 48.0 36.2 15.00 12.50
YHJF60S41S1 MV20D 24 FC/MC62D
1 1160 48.0 31.0
2 1855 57.0 40.5 12.00
14.5 SEER HP WITH AV / SV / F*FV - VARIABLE SPEED
YHJF18S41S1 AV*36 21 – – 630 18.0 13.3 15.00 12.50
YHJF24S41S1 AV*36 21 – – 725 22.8 16.8 15.00 12.50
YHJF30S41S1 AV*36 21 – – 960 29.2 21.8 15.00 12.50
YHJF36S41S1 AV*36 21 – – 1190 35.4 26.4 14.50 12.00
14.5 SEER HP WITH AHP / SHP / AHX / F*FP
YHJF18S41S1 AHX30 17 – – 640 18.0 13.3 15.00 12.50
AHX30 17 – – 800 22.8 17.1 15.00 12.50
YHJF24S41S1
F6FP030 17 – – 850 22.8 17.3 14.50 12.00
F6FP036 21 – – 855 22.8 17.4 15.00 12.50
AHX36 21 – – 820 23.0 17.4 15.00 12.50
YHJF30S41S1
AHX36 21 – – 1030 29.4 22.2 15.00 12.50
F6FP042 21 – – 1065 29.4 22.2 15.00 12.50
AHX36 21 – – 1210 35.4 26.6 14.50 12.00
YHJF36S41S1
AHX42 21 – – 1190 35.8 26.8 15.00 12.50
F6FP042 24 – – 1290 36.0 27.6 15.00 12.50
YHJF42S41S1
YHJF48S41S1
YHJF60S41S1 AHX60 24
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210.
Cooling MBH based on 8 °F entering air temperature, 50% RH, and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power
input in watt-hours during the same period.
AHX60 24 – – 1355 40.0 30.2 14.50 12.00
F6FP060 24 – – 1475 40.5 31.4 14.50 12.00
AHX60 24 – – 1570 48.0 35.6 15.00 12.50
F6FP060 24 – – 1570 48.0 35.6 15.00 12.50
– 1 1160 47.5 30.5
– 2 1855 57.0 40.5 12.00
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
— = Not applicable.
COOLING
NET MBH
SEER EER
14.50
14.50
21.55
21.20
4 Johnson Controls Unitary Products
Page 5
COOLING CAPACITY - With High Efficiency Motor Furnaces
UNIT
MODEL
YHJF18S41S1
YHJF24S41S1
YHJF30S41S1
For Notes See Page 6.
FURNACE
MODEL
T*(8,L)X*A12 FC/MC/PC32A 14 – 590 18.0 13.0 15.00 12.50
Y*(8,L)(C,V)*A12 FC/MC/PC32A 14 – 590 18.0 13.0 15.00 12.50
Y*(8,L)(C,V)*B12 FC/MC/PC35B 17 – 650 18.0 13.4 15.00 12.50
Y*(8,L)(C,V)*C16 FC/MC/PC35C 21 – 600 18.0 13.0 15.00 12.50
Y*9(C,V)*B12 FC/MC/PC35B 17 – 570 18.0 13.0 15.00 12.50
Y*9(C,V)*C16 FC/MC/PC35C 21 – 645 18.0 13.4 15.00 12.50
Y*(8,L)(C,V)*A12 FC/MC/PC37A 14 – 625 18.0 13.3 15.00 12.50
Y*(8,L)(C,V)*B12 FC/MC/PC43B 17 – 560 18.0 12.8 15.00 12.50
T*(8,L)X*A12 FC/MC/PC32A 14 – 800 23.0 17.3 15.00 12.50
T*(8,L)X*B12 FC/MC/PC35B 17 – 850 23.0 17.8 15.00 12.50
T*(8,L)X*C16 FC/MC/PC35C 21 – 865 23.2 18.0 15.00 12.50
T*(8,L)X*C20 FC/MC/PC35C 21 – 865 23.2 18.1 15.00 12.50
T*9X*B12 FC/MC/PC35B 17 – 785 23.0 17.3 15.00 12.50
T*9X*C16 FC/MC/PC35C 21 – 765 23.0 17.3 15.00 12.50
T*9X*C20 FC/MC/PC35C 21 – 825 23.0 17.2 15.00 12.50
T*(8,L)X*A12 FC/MC/PC37A 14 – 840 23.4 18.0 15.00 12.50
T*(8,L)X*B12 FC/MC/PC43B 17 – 865 23.4 18.1 15.00 12.50
T*(8,L)X*C16 FC/MC/PC43C 21 – 855 23.4 18.1 15.00 12.50
T*9X*B12 FC/MC/PC43B 17 – 800 23.4 18.0 15.00 12.50
T*9X*C16 FC/MC/PC43C 21 – 785 23.2 17.5 15.00 12.50
T*9X*C20 FC/MC/PC43C 21 – 790 23.2 17.4 15.00 12.50
Y*(8,L)(C,V)*A12 FC/MC/PC32A 14 – 775 22.8 17.1 14.50 12.00
Y*(8,L)(C,V)*B12 FC/MC/PC35B 17 – 760 22.6 16.7 15.00 12.50
Y*(8,L)(C,V)*C16 FC/MC/PC35C 21 – 855 23.0 17.7 15.00 12.50
Y*(8,L)(C,V)*C20 FC/MC/PC35C 21 – 740 22.6 16.6 15.00 12.50
Y*9(C,V)*B12 FC/MC/PC35B 17 – 815 22.8 17.1 14.50 12.00
Y*9(C,V)*C16 FC/MC/PC35C 21 – 865 23.2 18.2 15.00 12.50
Y*9(C,V)*C20 FC/MC/PC35C 21 – 755 22.6 16.7 15.00 12.50
Y*(8,L)(C,V)*A12 FC/MC/PC37A 14 – 805 23.2 17.9 15.00 12.50
Y*(8,L)(C,V)*B12 FC/MC/PC43B 17 – 760 22.8 17.0 15.00 12.50
Y*(8,L)(C,V)*C16 FC/MC/PC43C 21 – 875 23.4 18.5 15.00 12.50
Y*(8,L)(C,V)*C20 FC/MC/PC43C 21 – 760 23.0 17.1 15.00 12.50
Y*9(C,V)*B12 FC/MC/PC43B 17 – 800 23.2 17.9 15.00 12.50
Y*9(C,V)*C16 FC/MC/PC43C 21 – 810 23.4 18.0 15.00 12.50
Y*9(C,V)*C20 FC/MC/PC43C 21 – 875 23.4 18.4 15.00 12.50
T*(8,L)X*A12 FC/MC/PC37A 14 – 1095 29.4 23.0 15.00 12.50
T*(8,L)X*B12 FC/MC/PC43B 17 – 1105 29.6 23.2 15.00 12.50
T*(8,L)X*C16 FC/MC/PC43C 21 – 955 29.2 21.6 15.00 12.50
T*9X*B12 FC/MC/PC43B 17 – 1095 29.4 23.0 15.00 12.50
T*9X*C16 FC/MC/PC43C 21 – 1055 29.4 22.6 15.00 12.50
Y*(8,L)(C,V)*A12 FC/MC/PC37A 14 – 980 28.6 21.4 14.50 12.00
Y*(8,L)(C,V)*B12 FC/MC/PC43B 17 – 990 28.8 21.4 15.00 12.50
Y*(8,L)(C,V)*C16 FC/MC/PC43C 21 – 990 29.0 21.6 15.00 12.50
Y*(8,L)(C,V)*C20 FC/MC/PC43C 21 – 1000 29.0 21.6 15.00 12.50
Y*9(C,V)*B12 FC/MC/PC43B 17 – 1035 29.0 22.0 14.50 12.00
Y*9(C,V)*C16 FC/MC/PC43C 21 – 1030 29.2 22.2 15.00 12.50
Y*9(C,V)*C20 FC/MC/PC43C 21 – 995 29.0 21.6 15.00 12.50
COIL
1
MODEL
14.5 SEER HP WITH VARIABLE SPEED FURNACES
WS T A G E
RATED
CFM
COOLING
Net MBH
TOTAL SENS.
2
510667-YTG-A-0409
SEER EER
Johnson Controls Unitary Products 5
Page 6
510667-YTG-A-0409
COOLING CAPACITY - With High Efficiency Motor Furnaces (Continued)
UNIT
MODEL
YHJF36S41S1
YHJF42S41S1
YHJF48S41S1
YHJF60S41S1
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. Variable speed furnaces have B.O.D (Blower on Delay) standard.
FURNACE
MODEL
COIL
MODEL
1
WS T A G E
RATED
CFM
14.5 SEER HP WITH VARIABLE SPEED FURNACES
T*(8,L)X*A12 FC/MC/PC37A 14 – 1290 35.8 27.4 14.50 12.00
T*(8,L)X*B12 FC/MC/PC43B 17 – 1300 35.8 27.4 14.50 12.00
T*(8,L)X*C16 FC/MC/PC43C 21 – 1175 35.4 26.4 15.00 12.50
T*(8,L)X*C20 FC/MC/PC43C 21 – 1250 36.0 27.4 15.00 12.50
T*9X*B12 FC/MC/PC43B 17 – 1270 35.8 27.4 14.50 12.00
T*9X*C16 FC/MC/PC43C 21 – 1260 36.0 27.4 14.50 12.00
T*9X*C20 FC/MC/PC43C 21 – 1185 35.2 26.4 14.50 12.00
Y*(8,L)(C,V)*C16 FC/MC/PC43C 21 – 1205 35.2 26.4 14.50 12.00
Y*(8,L)(C,V)*C20 FC/MC/PC43C 21 – 1190 35.2 26.4 14.50 12.00
Y*9(C,V)*C16 FC/MC/PC43C 21 – 1240 35.6 27.2 14.20 12.00
Y*9(C,V)*C20 FC/MC/PC43C 21 – 1200 35.2 26.4 14.35 12.00
T*(8,L)X*C16 FC/MC62D 21 – 1360 40.5 31.0 15.00 12.50
T*(8,L)X*C20 FC/MC62D 21 – 1485 40.5 31.8 15.00 12.50
T*9X*C16 FC/MC62D 21 – 1460 40.0 30.8 14.50 12.00
T*9X*C20 FC/MC62D 21 – 1460 40.5 31.0 14.50 12.00
T*9X*D20 FC/MC62D 24 – 1425 40.5 31.0 14.50 12.00
Y*(8,L)(C,V)*C16 FC/MC62D 21 – 1420 40.0 30.8 14.40 12.00
Y*(8,L)(C,V)*C20 FC/MC62D 21 – 1410 40.5 30.8 14.50 12.00
Y*9(C,V)*C20 FC/MC62D 21 – 1445 40.0 30.6 14.05 11.90
Y*9(C,V)*D20 FC/MC62D 24 – 1455 40.0 30.6 14.25 12.00
T*(8,L)X*C16 FC/MC62D 21 – 1610 48.0 36.2 14.50 12.00
T*(8,L)X*C20 FC/MC62D 21 – 1665 48.0 36.2 14.50 12.00
T*9X*C16 FC/MC62D 21 – 1550 48.0 36.0 14.50 12.00
T*9X*C20 FC/MC62D 21 – 1595 48.0 36.2 14.50 12.00
T*9X*D20 FC/MC62D 24 – 1610 48.0 36.0 14.50 12.00
Y*(8,L)(C,V)*C16 FC/MC62D 21 – 1635 48.0 36.0 14.50 12.00
Y*(8,L)(C,V)*C20 FC/MC62D 21 – 1615 48.0 36.0 14.50 12.00
Y*9(C,V)*C16 FC/MC62D 21 – 1590 47.5 36.0 14.35 12.00
Y*9(C,V)*C20 FC/MC62D 21 – 1655 47.5 35.8 14.05 12.00
Y*9(C,V)*D20 FC/MC62D 24 – 1630 47.5 35.8 14.25 12.00
T*(8,L)X*C20 FC/MC62D 21
T*9X*C20 FC/MC62D 21
T*9X*D20 FC/MC62D 24
Y*(8,L)(C,V)*C20 FC/MC62D 21
Y*9(C,V)*C20 FC/MC62D 21
Y*9(C,V)*D20 FC/MC62D 24
1 835 44.0 27.0
2 1665 57.0 39.5 12.00
1 1220 48.5 31.6
2 1595 56.5 38.5 12.00
1 1240 48.5 31.8
2 1645 56.5 39.0 12.00
1 1015 46.0 29.2
2 1615 56.5 38.5 12.00
1 1040 46.5 29.4
2 1655 56.0 38.5 12.00
1 1085 47.0 29.8
2 1630 56.0 38.5 12.00
COOLING
Net MBH
TOTAL SENS.
2
SEER EER
14.50
14.50
14.50
14.50
14.50
14.50
20.25
21.10
21.30
20.65
20.55
20.65
6 Johnson Controls Unitary Products
Page 7
\
510667-YTG-A-0409
HEATING PERFORMANCE - With Air Handler
UNIT
MODEL*
AIR
HANDLER
COIL
MODEL
1
47 F1 7F HSPF
MBH COP KW MBH COP KW STD
ARI HEATING
14.5 SEER HP WITH MV - VARIABLE SPEED
YHJF18S41S1
YHJF24S41S1
YHJF30S41S1
YHJF36S41S1
MV12B FC/MC35B 18.0 3.76 1.40 11.0 2.48 1.30 8.50
MV12B FC/MC43B 18.0 3.90 1.35 10.9 2.56 1.25 8.50
MV12B FC/MC35B 22.2 3.68 1.77 14.9 2.46 1.77 8.50
MV12B FC/MC43B 22.2 3.82 1.70 14.9 2.54 1.72 8.50
MV12B FC/MC43B 30.0 3.88 2.27 18.8 2.68 2.06 9.00
MV16C FC/MC43C 30.0 3.92 2.24 18.8 2.70 2.04 9.00
MV12B FC/MC43B 36.0 3.74 2.82 24.4 2.52 2.84 8.20
MV16C FC/MC43C 36.0 3.74 2.82 24.2 2.52 2.81 9.00
YHJF42S41S1 MV20D FC/MC62D 40.5 4.02 2.95 26.0 2.76 2.76 9.00
YHJF48S41S1 MV20D FC/MC62D 48.0 3.82 3.68 31.8 2.60 3.58 9.00
14.5 SEER HP WITH AV / SV / F*FV - VARIABLE SPEED
YHJF18S41S1 AV*36 – 18.0 3.98 1.33 10.8 2.62 1.21 8.50
YHJF24S41S1 AV*36 – 22.0 3.70 1.74 14.8 2.50 1.73 8.50
YHJF30S41S1 AV*36 – 29.8 3.98 2.19 18.6 2.74 1.99 9.00
YHJF36S41S1 AV*36 – 36.0 3.78 2.79 24.2 2.54 2.79 9.00
14.5 SEER HP WITH AHP / SHP / AHX / F*FP
YHJF18S41S1 AHX30 – 18.0 3.88 1.36 10.9 2.52 1.27 8.50
A H X 3 0 – 2 2 . 23 . 6 41 . 7 91 3 . 72 . 4 21 . 6 68 . 5 0
YHJF24S41S1
F 6 F P 0 3 0 – 2 2 . 23 . 6 41 . 7 91 5 . 12 . 4 21 . 8 38 . 2 0
F 6 F P 0 3 6 – 2 2 . 23 . 6 81 . 7 71 5 . 02 . 4 61 . 7 98 . 5 0
A H X 3 6 – 2 2 . 43 . 7 01 . 7 71 5 . 12 . 4 61 . 8 08 . 5 0
YHJF30S41S1
A H X 3 6 – 3 0 . 04 . 0 02 . 2 01 8 . 72 . 7 61 . 9 99 . 0 0
F 6 F P 0 4 2 – 3 0 . 04 . 0 02 . 2 01 8 . 72 . 7 61 . 9 99 . 0 0
A H X 3 6 – 3 6 . 03 . 8 22 . 7 62 4 . 22 . 5 62 . 7 79 . 0 0
YHJF36S41S1
A H X 4 2 – 3 6 . 03 . 8 42 . 7 52 2 . 22 . 5 62 . 5 49 . 0 0
F 6 F P 0 4 2 – 3 6 . 03 . 8 82 . 7 22 4 . 42 . 6 02 . 7 59 . 0 0
YHJF42S41S1
YHJF48S41S1
A H X 6 0 – 4 0 . 54 . 0 02 . 9 72 6 . 02 . 7 42 . 7 89 . 0 0
F 6 F P 0 6 0 – 4 1 . 04 . 0 42 . 9 72 6 . 22 . 7 42 . 8 09 . 0 0
A H X 6 0 – 4 8 . 03 . 8 23 . 6 83 1 . 62 . 6 03 . 5 69 . 0 0
F 6 F P 0 6 0 – 4 8 . 03 . 8 23 . 6 83 1 . 62 . 6 03 . 5 69 . 0 0
See notes below.
2
HEATING CAPACITY - With Air Handler Coils
UNIT
MODEL
AIR
HANDLER
COIL
MODEL
1
STAGE
RATED
CFM
HEATING
NET MBH
47 OD 17 OD
14.5 SEER HP WITH MV - VARIABLE SPEED
1 1160 43.0 – – –
YHJF60S41S1 MV20D FC/MC62D
2 1855 57.0 40.5 9.00 3.66
2 1160 54.9 39.0 8.85 3.04
14.5 SEER HP WITH AHX
1 1160 43.1 – – –
YHJF60S41S1 AHX60 –
2 1855 58.0 40.0 9.00 3.72
2 1170 57.5 40.0 8.90 3.24
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210.
Cooling MBH based on 8 °F entering air temperature, 50% RH, and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BT U’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power
input in watt-hours during the same period.
1. Rated CFM same as for cooling.
2. Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and no
supplemental electric heat operation.
CP equals MBH output divided by (total KW input x 3.412).
HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the
total electric power input during the same period.
— = Not Applicable.
Johnson Controls Unitary Products 7
2
HSPF COP @ 47
Page 8
510667-YTG-A-0409
HEATING CAPACITY - With High Efficiency Motor Furnaces
MODEL
YHJF18S41S1
YHJF24S41S1
YHJF30S41S1
For Notes See Page 9.
FURNACE
MODEL
T*(8,L)X*A12 FC/MC/PC32A 17.9 3.84 1.37 10.8 2.54 1.25 9.00
Y*(8,L)(C,V)*A12 FC/MC/PC32A 18.0 3.76 1.40 11.0 2.48 1.30 8.50
Y*(8,L)(C,V)*B12 FC/MC/PC35B 18.0 3.84 1.37 10.9 2.50 1.28 8.50
Y*(8,L)(C,V)*C16 FC/MC/PC35C 18.0 3.82 1.38 10.9 2.52 1.27 8.50
Y * 9 ( C , V ) * B 1 2F C / M C / P C 3 5 B1 8 . 03 . 8 01 . 3 91 0 . 92 . 5 01 . 2 8 8 . 5 0
Y*9(C,V)*C16 FC/MC/PC35C 18.0 3.84 1.37 10.9 2. 50 1.28 8.50
Y*(8,L)(C,V)*A12 FC/MC/PC37A 18.0 3.90 1.35 10.9 2.58 1.24 8.50
Y*(8,L)(C,V)*B12 FC/MC/PC43B 18.0 3.80 1.39 10.8 2.52 1.26 8.50
T*(8,L)X*A12 FC/MC/PC32A 22.0 3.72 1.73 14.8 2.48 1.75 8.50
T*(8,L)X*B12 FC/MC/PC35B 22.0 3.74 1.72 14.8 2.48 1.75 8.50
T*(8,L)X*C16 FC/MC/PC35C 22.0 3.76 1.71 14.8 2.50 1.73 8.50
T*(8,L)X*C20 FC/MC/PC35C 22.0 3.76 1.71 14.8 2.48 1.75 8.50
T * 9 X * B 1 2F C / M C / P C 3 5 B2 2 . 03 . 7 21 . 7 31 4 . 82 . 4 81 . 7 5 8 . 5 0
T*9X*C16 FC/MC/PC35C 22.0 3.78 1.71 14.7 2.50 1.72 9.00
T*9X*C20 FC/MC/PC35C 22.2 3.72 1.75 14.9 2.48 1.76 8.50
T*(8,L)X*A12 FC/MC/PC37A 22.2 3.88 1.68 14.8 2.56 1.69 8.50
T*(8,L)X*B12 FC/MC/PC43B 22.0 3.88 1.66 14.8 2.58 1.68 8.50
T*(8,L)X*C16 FC/MC/PC43C 22.0 3.88 1.66 14.8 2.58 1.68 8.50
T * 9 X * B 1 2F C / M C / P C 4 3 B2 2 . 23 . 8 81 . 6 81 4 . 82 . 5 61 . 6 9 8 . 5 0
T*9X*C16 FC/MC/PC43C 22.0 3.80 1.70 14.8 2.54 1.71 9.00
T*9X*C20 FC/MC/PC43C 22.0 3.74 1.72 14.9 2.50 1.75 8.50
Y*(8,L)(C,V)*A12 FC/MC/PC32A 22.2 3.62 1.80 15.0 2.42 1.82 8.50
Y*(8,L)(C,V)*B12 FC/MC/PC35B 22.0 3.56 1.81 14.9 2.40 1.82 8.50
Y*(8,L)(C,V)*C16 FC/MC/PC35C 22.2 3.68 1.77 14.9 2.44 1.79 8.50
Y*(8,L)(C,V)*C20 FC/MC/PC35C 21.8 3.60 1.77 14.8 2.42 1.79 8.50
Y * 9 ( C , V ) * B 1 2F C / M C / P C 3 5 B2 2 . 23 . 6 41 . 7 91 5 . 02 . 4 21 . 8 2 8 . 5 0
Y*9(C,V)*C16 FC/MC/PC35C 22.2 3.70 1.76 15.0 2. 44 1.80 8.50
Y*9(C,V)*C20 FC/MC/PC35C 22.0 3.58 1.80 14.8 2. 42 1.79 8.50
Y*(8,L)(C,V)*A12 FC/MC/PC37A 22.4 3.76 1.75 15.0 2.50 1.76 8.50
Y*(8,L)(C,V)*B12 FC/MC/PC43B 22.0 3.68 1.75 14.9 2.46 1.77 8.50
Y*(8,L)(C,V)*C16 FC/MC/PC43C 22.2 3.84 1.69 14.9 2.52 1.73 8.50
Y*(8,L)(C,V)*C20 FC/MC/PC43C 22.0 3.72 1.73 14.8 2.50 1.73 8.50
Y * 9 ( C , V ) * B 1 2F C / M C / P C 4 3 B2 2 . 23 . 7 81 . 7 21 5 . 02 . 5 21 . 7 4 8 . 5 0
Y*9(C,V)*C16 FC/MC/PC43C 22.2 3.82 1.70 14.9 2. 52 1.73 8.50
Y*9(C,V)*C20 FC/MC/PC43C 22.4 3.82 1.72 14.9 2. 52 1.73 8.50
T*(8,L)X*A12 FC/MC/PC37A 30.0 4.02 2.19 18.9 2.74 2.02 9.00
T*(8,L)X*B12 FC/MC/PC43B 30.0 4.00 2.20 18.9 2.72 2.04 9.00
T*(8,L)X*C16 FC/MC/PC43C 30.0 3.96 2.22 18.6 2.74 1.99 9.00
T * 9 X * B 1 2F C / M C / P C 4 3 B3 0 . 03 . 9 82 . 2 11 8 . 82 . 7 22 . 0 3 9 . 0 0
T*9X*C16 FC/MC/PC43C 30.0 3.96 2.22 18.8 2.72 2.03 9.00
Y*(8,L)(C,V)*A12 FC/MC/PC37A 30.0 3.80 2.31 19.1 2.62 2.14 8.50
Y*(8,L)(C,V)*B12 FC/MC/PC43B 30.0 3.86 2.28 18.9 2.66 2.08 8.50
Y*(8,L)(C,V)*C16 FC/MC/PC43C 30.0 3.92 2.24 18.7 2.70 2.03 9.00
Y*(8,L)(C,V)*C20 FC/MC/PC43C 30.0 3.94 2.23 18.7 2.72 2.01 9.00
Y*9(C,V)*B12 FC/MC/PC43B 30.0 3.84 2.29 19.0 2.64 2.11 8.50
Y*9(C,V)*C16 FC/MC/PC43C 30.0 3.90 2.25 18.9 2. 68 2.07 9.00
Y*9(C,V)*C20 FC/MC/PC43C 30.0 3.90 2.25 18.8 2. 70 2.04 9.00
1
COIL
MODEL
MBH COP KW MBH COP KW STD
47 F1 7FH S P F
14.5 SEER HP WITH VARIABLE SPEED FURNACES
ARI HEATING
3
2
8 Johnson Controls Unitary Products
Page 9
510667-YTG-A-0409
HEATING CAPACITY - With High Efficiency Motor Furnaces (Continued)
MODEL
YHJF36S41S1
YHJF42S41S1
YHJF48S41S1
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and no
supplemental electric heat operation.
3. Variable speed furnaces have B.O.D (Blower on Delay) standard.
CP equals MBH output divided by (total KW input x 3.412).
HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the
total electric power input during the same period.
— = Not Applicable.
FURNACE
MODEL
T*(8,L)X*A12 FC/MC/PC37A 36.0 3.80 2.78 24.6 2.54 2.84 8.50
T*(8,L)X*B12 FC/MC/PC43B 36.0 3.80 2.78 24.6 2.54 2.84 8.50
T*(8,L)X*C16 FC/MC/PC43C 36.0 3.78 2.79 24.0 2.56 2.75 9.00
T*(8,L)X*C20 FC/MC/PC43C 36.0 3.88 2.72 24.4 2.60 2.75 9.00
T*9X*B12 FC/MC/PC43B 36.0 3.80 2.78 24.6 2.54 2.84 8.50
T*9X*C16 FC/MC/PC43C 36.0 3.82 2.76 24.4 2.56 2.79 8.50
T*9X*C20 FC/MC/PC43C 36.0 3.74 2.82 24.2 2.52 2.81 8.50
Y*(8,L)(C,V)*C16 FC/MC/PC43C 36.0 3.72 2.84 24.4 2.50 2.86 8.50
Y*(8,L)(C,V)*C20 FC/MC/PC43C 36.0 3.74 2.82 24.2 2.52 2.81 8.50
Y*9(C,V)*C16 FC/MC/PC43C 36.0 3.76 2.81 24.6 2.52 2.86 8.50
Y*9(C,V)*C20 FC/MC/PC43C 36.0 3.70 2.85 24.4 2.50 2.86 8.50
T*(8,L)X*C16 FC/MC62D 40.5 4.06 2.92 26.0 2.78 2.74 9.00
T*(8,L)X*C20 FC/MC62D 41.0 4.08 2.94 26.2 2.78 2.76 9.00
T*9X*C16 FC/MC62D 41.0 3.98 3.02 26.2 2.72 2.82 9.00
T*9X*C20 FC/MC62D 40.5 4.02 2.95 26.2 2.74 2.80 9.00
T*9X*D20 FC/MC62D 40.5 4.02 2.95 26.0 2.76 2.76 9.00
Y*(8,L)(C,V)*C16 FC/MC62D 41.0 3.96 3.03 26.4 2.70 2.86 9.00
Y*(8,L)(C,V)*C20 FC/MC62D 41.0 4.00 3.00 26.2 2.74 2.80 9.00
Y*9(C,V)*C16 FC/MC62D 41.5 3.86 3.15 26.6 2.64 2.95 9.00
Y*9(C,V)*C20 FC/MC62D 41.0 3.90 3.08 26.4 2.68 2.89 9.00
Y*9(C,V)*D20 FC/MC62D 41.0 3.94 3.05 26.4 2.70 2.86 9.00
T*(8,L)X*C16 FC/MC62D 48.0 3.78 3.72 32.0 2.56 3.66 9.00
T*(8,L)X*C20 FC/MC62D 48.0 3.80 3.70 31.8 2.58 3.61 9.00
T*9X*C16 FC/MC62D 48.0 3.76 3.74 32.0 2.56 3.66 9.00
T*9X*C20 FC/MC62D 48.0 3.80 3.70 32.0 2.58 3.63 9.00
T*9X*D20 FC/MC62D 48.0 3.76 3.74 32.0 2.56 3.66 9.00
Y*(8,L)(C,V)*C20 FC/MC62D 48.0 3.76 3.74 32.0 2.56 3.66 9.00
Y*9(C,V)*C16 FC/MC62D 48.0 3.72 3.78 32.2 2.54 3.71 9.00
Y*9(C,V)*C20 FC/MC62D 48.0 3.68 3.82 32.4 2.50 3.80 9.00
Y*9(C,V)*D20 FC/MC62D 48.0 3.72 3.78 32.2 2.52 3.74 9.00
COIL
MODEL
1
47 F1 7F HSPF
MBH COP KW MBH COP KW STD
ARI HEATING
2
Johnson Controls Unitary Products 9
Page 10
510667-YTG-A-0409
HEATING CAPACITY - With High Efficiency Motor Furnaces
UNIT
MODEL
YHJF60S41S1
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and no
supplemental electric heat operation.
3. Variable speed furnaces have B.O.D (Blower on Delay) standard.
CP equals MBH output divided by (total KW input x 3.412).
HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the
total electric power input during the same period.
— = Not Applicable.
VARIABLE SPEED
FURNACE MODEL
14.5 SEER HP WITH VARIABLE SPEED FURNACES
T*(8,L)X*C20 FC/MC62D
T*9X*C20 FC/MC62D
T*9X*D20 FC/MC62D
Y*(8,L)(C,V)*C20 FC/MC62D
Y*9(C,V)*C20 FC/MC62D
Y*9(C,V)*D20 FC/MC62D
COIL
MODEL
1
STAGE
1 835 42.0 – – 2.98
2 1665 57.0 39.5 9.00 3.64
2 835 56.5 38.5 8.85 2.62
1 1220 43.5 – – 3.38
2 1595 57.0 40.0 9.00 3.58
2 1220 55.6 39.0 8.60 3.08
1 1240 43.5 – – 3.42
2 1645 57.0 40.0 9.00 3.60
2 1240 55.6 39.0 8.65 3.10
1 1015 42.5 – – 3.20
2 1615 57.0 40.0 9.00 3.58
2 1015 55.6 39.0 8.75 2.86
1 1040 43.0 – – 3.20
2 1655 57.0 40.5 9.00 3.54
2 1040 54.9 39.0 8.70 2.88
1 1085 43.0 – – 3.26
2 1630 57.0 40.0 9.00 3.54
2 1085 55.6 39.0 8.65 2.94
RATED
CFM
HEATING
NET MBH
47 OD 17 OD
3
2
HSPF COP @ 47
ACCESSORIES
Refer to Price Manual for specific model numbers.
Start Assist Kit - Provides starting torque for low voltage appli-
cations.
Blower Time Delay - Available to increase efficiency when
installed. Installs on indoor section and maintains blower for
approximately one minute after cooling thermostat has been
satisfied.
Low Temperature Cutout (2LT06700224) - Prevents heat
pump operation below -1 °F ambient temperature.
Thermal Expansion Valve Kit - 1TVM4 Series TXV kit used
when required.
Outdoor Thermostat (2TD06700124) - Provides additional
staging of supplement al electric heat.
Room Thermost ats - A wide selection of matching thermostats
is available to provide features required for any installation.
* For the most current accessory information, refer to the price
book or consult factory.
10 Johnson Controls Unitary Products
Page 11
SOUND LEVEL - TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)
THERMOSTAT
SEAL OPENING(S) WITH
PERMAGUM OR EQUIVALENT
TO INDOOR COIL
TO FURNACE OR
AIR HANDLER
TERMINAL BLOCK
NEC CLASS 2 WIRING
NEC CLASS 1 WIRING
ALL OUTDOOR WIRING
MUST BE WEATHERPROOF.
CONTROL
ACCESS
PANEL
WEATHERPROOF
DISCONNECT
SWITCH
MINIMUM 24” SERVICE
ACCESS CLEARANCE
ON ONE SIDE
48” OVERHEAD
CLEARANCE
10” CLEARANCE
AROUND PERIMETER
NOTE:
THERMOSTAT
INDOOR UNIT
OUTDOOR UNIT
LOW VOLTAGE TERMINAL BLOCK
IN AIR HANDLER WITH ELECTRIC HEAT
DEFROST
CONTROL
FIELD
INSTALLED
JUMPER
DEHUMIDIFICATION CONTROL CONNECTION
(Humidistat* Jumper must be removed)
GND.
SCREW
CONTACTOR
T2
T1
L2
L1
M
R
LorX
Y
O
W
G
T
2
E
2
R
R
Y
Y
O
O
W2
W
W1
C
C
X/L
G
W1
BK
GND.
LUG
CIRCUIT
BREAKER***
POWER WIRING
24V CONTROL WIRING
(NEC CLASS 2)
JUMPER TERMINALS E AND W TO HEAT
ON FIRST STAGE DURING EMERGENCY HEAT.
TERMINAL NOT USED ON ALL THERMOSTATS.
POWER WIRING
208/230-1-60
230-1-50
CHECK THE LOW VOLTAGE TERMINAL BLOCK ON THE INDOOR UNIT FOR THE ACTUAL ARRANGEMENT OF THE TERMINALS.
CONNECT POWER WIRING TO TERMINAL BLOCK 3TB ON UNITS WITHOUT ELECTRIC HEAT OR CIRCUIT BREAKER.
BorC
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
RED
BLK
YEL
ORG
BRN
PUR
WHT
CC
GRY
/66
GRAY FOR USE WITH OPTIONAL OUTDOOR THERMOSTAT KITS.
5
1
2
3
4
5
1
3,4
Test Condition 63 125 250 500 1000 2000 4000 8000 dBA SQI
Size
RSS Sound Power Calibration 1091 402 82.8 85.4 85.9 85.3 88.1 88.6 86.6 83.9 – –
Cooling Mode 67.3 69.2 64.6 67.3 65.5 61.5 58.2 51.8 70.0 19.21
18
Heating Mode 68.9 69.0 64.0 66.4 66.6 59.6 56.4 52.6 69.7 19.17
Cooling Mode 70.0 73.6 64.0 70.0 71.8 63.2 57.3 52.3 73.9 19.19
24
Heating Mode 72.2 71.0 68.5 74.1 71.9 63.4 59.8 53.4 75.4 19.14
Cooling Mode 70.5 68.8 64.3 65.3 65.5 60.3 55.8 50.6 69.0 19.01
30
Heating Mode 72.2 70.1 67.5 66.7 69.4 62.5 58.3 52.7 72.0 19.03
Cooling Mode 70.9 69.3 65.3 66.4 66.3 59.7 56.7 50.8 69.6 19.14
36
Heating Mode 73.2 70.1 66.9 68.5 68.4 61.6 59.4 55.5 71.7 19.12
Cooling Mode 71.7 69.5 72.1 69.0 71.3 60.6 56.9 54.0 73.3 19.01
42
Heating Mode 72.6 72.6 68.1 70.5 70.9 62.7 59.2 56.9 73.6 19.02
Cooling Mode 71.0 71.0 68.4 68.1 67.9 60.1 55.8 51.3 70.8 19.11
48
Heating Mode 73.6 72.5 74.0 73.6 75.8 64.0 63.2 56.8 77.6 19.08
Cooling Mode - High Stage 71.2 69.4 71.4 73.2 71.2 61.1 57.6 52.8 74.7 19.09
60
Heating Mode - High Stage 71.6 72.7 69.6 71.3 72.4 63.4 61.5 57.4 75.0 19.05
* Rated in accordance with ARI 270-2008 Standards.
TYPICAL INSTALLATION
510667-YTG-A-0409
TYPICAL FIELD WIRING
Johnson Controls Unitary Products 11
Page 12
510667-YTG-A-0409
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. YHJF18S41S1
INDOOR COIL MODEL NO. AHX30
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
AV*36 – 1.00 1.00 1.08
MV12B FC/MC35B 1.00 0.98 1.08
MV12B FC/MC43B 1.00 1.00 1.08
IDCFM 400 600 800
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 17.2 18.8 18.8 20.5 22.2 19.2 19.9 20.1 21.7 22.9 21.2 20.9 21.3 22.8 23.6
S.C. 16.8 14.9 12.9 12.9 11.0 18.8 17.7 15.2 14.7 11.7 20.8 20.5 17.4 16.5 12.5
KW 0.9 0.9 0.9 0.9 0.9 0.9 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
T.C. 16.4 17.9 17.9 19.7 21.3 18.4 19.1 19.0 20.8 22.1 20.4 20.2 20.2 21.8 22.9
S.C. 16.1 14.5 12.5 12.5 10.5 18.0 17.1 14.8 14.4 11.5 20.0 19.8 17.0 16.3 12.4
KW 1.0 1.0 1.0 1.0 1.0 1.1 1.1 1.1 1.1 1.1 1.2 1.2 1.2 1.2 1.2
T.C. 15.7 17.0 17.0 18.9 20.4 17.7 18.3 18.0 19.9 21.3 19.6 19.5 19.1 20.8 22.1
S.C. 15.4 14.1 12.1 12.1 10.1 17.3 16.6 14.3 14.2 11.2 19.2 19.1 16.6 16.2 12.2
KW 1.1 1.1 1.1 1.2 1.2 1.2 1.2 1.2 1.2 1.3 1.3 1.3 1.3 1.3 1.3
T.C. 15.0 16.1 16.1 18.1 19.6 16.9 17.4 17.0 19.0 20.4 18.8 18.8 18.0 19.8 21.3
S.C. 14.7 13.7 11.6 11.8 9.7 16.5 16.0 13.9 13.9 10.9 18.4 18.4 16.2 16.0 12.1
KW 1.3 1.3 1.3 1.3 1.3 1.4 1.4 1.4 1.4 1.4 1.5 1.5 1.5 1.5 1.5
T.C. 14.0 14.7 14.8 16.7 18.4 15.9 16.2 15.7 17.6 19.2 17.7 17.7 16.6 18.5 20.1
S.C. 13.7 13.1 11.0 11.2 9.2 15.5 15.2 13.3 13.4 10.4 17.3 17.3 15.6 15.6 11.6
KW 1.4 1.4 1.4 1.5 1.5 1.5 1.5 1.5 1.5 1.6 1.6 1.6 1.6 1.6 1.7
T.C. 13.1 13.4 13.4 15.4 17.2 14.8 15.0 14.4 16.2 18.0 16.6 16.6 15.3 17.1 18.8
S.C. 12.8 12.5 10.5 10.6 8.7 14.5 14.4 12.7 12.9 9.9 16.2 16.2 15.0 15.1 11.2
KW 1.6 1.6 1.6 1.6 1.7 1.7 1.7 1.7 1.7 1.7 1.8 1.8 1.8 1.8 1.8
T.C. 12.2 12.1 12.1 14.0 16.1 13.8 13.8 13.0 14.9 16.8 15.5 15.5 14.0 15.7 17.5
S.C. 11.9 11.9 9.9 10.1 8.2 13.5 13.5 12.1 12.3 9.5 15.1 15.1 14.0 14.6 10.7
KW 1.7 1.7 1.7 1.8 1.8 1.8 1.8 1.8 1.9 1.9 2.0 2.0 1.9 2.0 2.0
Variable Speed
Furnace
T*(8,L)X*A12 FC/MC/PC32A 1.00 0.98 1.08
Y*(8,L)(C,V)*A12 FC/MC/PC32A 1.00 0.98 1.08
Y*(8,L)(C,V)*B12 FC/MC/PC35B 1.00 1.01 1.08
Y*(8,L)(C,V)*C16 FC/MC/PC35C 1.00 0.98 1.08
Y*9(C,V)*B12 FC/MC/PC35B 1.00 0.98 1.08
Y*9(C,V)*C16 FC/MC/PC35C 1.00 1.01 1.08
Y*(8,L)(C,V)*A12 FC/MC/PC37A 1.00 1.00 1.08
Y*(8,L)(C,V)*B12 FC/MC/PC43B 1.00 0.96 1.08
Coil T.C. S.C. KW
12 Johnson Controls Unitary Products
Page 13
510667-YTG-A-0409
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. YHJF24S41S1
INDOOR COIL MODEL NO. AHX30
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES I N CL UDE INDOO R FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
AHX36 – 1.01 1.02 1.03
AV*36 – 1.00 0.98 1.02
F6FP030 – 1.00 1.01 1.07
F6FP036 – 1.00 1.02 1.02
MV12B FC/MC35B 1.00 1.01 1.02
MV12B FC/MC43B 1.03 1.05 1.05
Variable Speed
Furnace
T*(8,L)X*A12 FC/MC/PC32A 1.01 1.01 1.03
T*(8,L)X*B12 FC/MC/PC35B 1.01 1.04 1.03
T*(8,L)X*C16 FC/MC/PC35C 1.02 1.05 1.04
T*(8,L)X*C20 FC/MC/PC35C 1.02 1.06 1.04
T*9X*B12 FC/MC/PC35B 1.01 1.01 1.03
T*9X*C16 FC/MC/PC35C 1.01 1.01 1.03
T*9X*C20 FC/MC/PC35C 1.01 1.01 1.03
T*(8,L)X*A12 FC/MC/PC37A 1.03 1.05 1.05
T*(8,L)X*B12 FC/MC/PC43B 1.03 1.06 1.05
IDCFM 600 800 1000
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 21.7 23.6 23.5 25.2 26.6 23.4 24.1 24.3 26.0 27.2 25.1 24.6 25.1 26.9 27.8
S.C. 21.4 19.4 16.6 16.2 13.7 23.1 21.8 18.5 17.9 14.3 24.8 24.3 20.5 19.5 15.0
KW 1.2 1.2 1.2 1.2 1.2 1.3 1.3 1.3 1.3 1.3 1.4 1.4 1.4 1.4 1.4
T.C. 20.8 22.3 22.2 24.0 25.7 22.4 23.0 23.0 24.8 26.3 24.1 23.8 23.8 25.7 26.9
S.C. 20.5 18.8 16.0 15.7 13.1 22.1 21.1 18.0 17.5 13.9 23.8 23.5 19.9 19.2 14.6
KW 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.5 1.5 1.5 1.5 1.5 1.5 1.5
T.C. 19.8 20.9 20.9 22.9 24.8 21.4 21.9 21.6 23.7 25.5 23.1 22.9 22.4 24.5 26.1
S.C. 19.5 18.2 15.4 15.3 12.5 21.2 20.4 17.4 17.1 13.4 22.8 22.6 19.4 18.9 14.3
KW 1.5 1.5 1.5 1.5 1.6 1.6 1.6 1.6 1.6 1.6 1.7 1.7 1.7 1.7 1.7
T.C. 18.8 19.5 19.6 21.8 23.9 20.5 20.8 20.3 22.5 24.6 22.1 22.1 21.1 23.2 25.3
S.C. 18.6 17.5 14.8 14.8 11.9 20.2 19.7 16.8 16.7 12.9 21.8 21.8 18.8 18.7 14.0
KW 1.7 1.7 1.7 1.7 1.7 1.8 1.8 1.7 1.8 1.8 1.9 1.9 1.8 1.9 1.9
T.C. 17.7 18.0 18.0 20.2 22.4 19.2 19.3 18.7 20.9 23.1 20.7 20.7 19.4 21.6 23.7
S.C. 17.4 16.8 14.1 14.2 11.3 18.9 18.7 16.1 16.1 12.4 20.5 20.5 18.2 18.1 13.5
KW 1.9 1.9 1.9 1.9 2.0 2.0 2.0 1.9 2.0 2.0 2.1 2.1 2.0 2.1 2.1
T.C. 16.5 16.4 16.4 18.7 20.9 17.9 17.9 17.0 19.3 21.6 19.4 19.4 17.7 20.0 22.2
S.C. 16.3 16.1 13.4 13.5 10.8 17.7 17.6 15.4 15.5 11.9 19.2 19.2 17.5 17.5 13.0
KW 2.1 2.1 2.1 2.1 2.2 2.2 2.2 2.1 2.2 2.2 2.3 2.3 2.2 2.3 2.3
T.C. 15.3 14.8 14.8 17.1 19.4 16.7 16.4 15.4 17.7 20.0 18.1 18.1 16.1 18.3 20.6
S.C. 15.1 14.8 12.7 12.9 10.2 16.5 16.4 14.7 14.9 11.3 17.8 17.8 16.1 16.9 12.5
KW 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.5 2.5 2.5 2.5 2.5
Coil T.C. S.C. KW
Variable Speed
Furnace
T*(8,L)X*C16 FC/MC/PC43C 1.03 1.06 1.05
T*9X*B12 FC/MC/PC43B 1.03 1.05 1.05
T*9X*C16 FC/MC/PC43C 1.02 1.02 1.04
T*9X*C20 FC/MC/PC43C 1.02 1.02 1.04
Y*(8,L)(C,V)*A12 FC/MC/PC32A 1.00 1.00 1.07
Y*(8,L)(C,V)*B12 FC/MC/PC35B 0.99 0.98 1.02
Y*(8,L)(C,V)*C16 FC/MC/PC35C 1.01 1.04 1.03
Y*(8,L)(C,V)*C20 FC/MC/PC35C 0.99 0.97 1.02
Y*9(C,V)*B12 FC/MC/PC35B 1.00 1.00 1.07
Y*9(C,V)*C16 FC/MC/PC35C 1.02 1.06 1.04
Y*9(C,V)*C20 FC/MC/PC35C 0.99 0.98 1.02
Y*(8,L)(C,V)*A12 FC/MC/PC37A 1.02 1.05 1.04
Y*(8,L)(C,V)*B12 FC/MC/PC43B 1.00 0.99 1.02
Y*(8,L)(C,V)*C16 FC/MC/PC43C 1.03 1.08 1.05
Y*(8,L)(C,V)*C20 FC/MC/PC43C 1.01 1.00 1.03
Y*9(C,V)*B12 FC/MC/PC43B 1.02 1.05 1.04
Y*9(C,V)*C16 FC/MC/PC43C 1.03 1.05 1.05
Y*9(C,V)*C20 FC/MC/PC43C 1.03 1.08 1.05
Coil T.C. S.C. KW
Johnson Controls Unitary Products 13
Page 14
510667-YTG-A-0409
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. YHJF30S41S1
INDOOR COIL MODEL NO. AHX36
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
AV*36 – 0.99 0.98 1.09
F6FP42 – 0.99 0.98 1.09
MV12B FC/MC43B 0.99 0.97 1.09
MV16C FC/MC43C 0.99 0.97 1.09
IDCFM 800 1000 1200
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 28.4 30.2 30.1 33.0 34.3 30.2 31.2 31.2 33.5 34.8 32.0 32.2 32.2 34.0 35.3
S.C. 28.4 26.3 22.5 22.3 18.2 30.2 29.6 24.6 23.7 18.7 32.0 32.2 26.8 25.1 19.1
KW 1.5 1.5 1.5 1.6 1.5 1.6 1.6 1.6 1.6 1.6 1.7 1.7 1.7 1.7 1.7
T.C. 27.3 28.7 28.7 31.5 33.2 29.0 29.7 29.6 32.1 33.7 30.7 30.6 30.6 32.7 34.2
S.C. 27.3 25.7 21.8 21.6 17.7 29.0 28.4 23.9 23.2 18.2 30.7 30.6 26.1 24.8 18.7
KW 1.7 1.7 1.7 1.7 1.7 1.8 1.8 1.8 1.8 1.8 1.9 1.9 1.9 1.8 1.8
T.C. 26.2 27.2 27.2 30.0 32.2 27.8 28.1 28.1 30.7 32.6 29.5 29.0 29.0 31.4 33.1
S.C. 26.2 25.0 21.1 21.0 17.1 27.8 27.3 23.3 22.8 17.7 29.5 29.0 25.4 24.6 18.4
KW 1.8 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.0 2.0 2.0 2.0 2.0 2.0 2.0
T.C. 25.1 25.8 25.8 28.6 31.1 26.7 26.6 26.6 29.3 31.5 28.2 27.3 27.3 30.1 32.0
S.C. 25.1 24.4 20.4 20.4 16.5 26.7 26.1 22.6 22.4 17.3 28.2 27.3 24.7 24.4 18.1
KW 2.0 2.0 2.0 2.0 2.1 2.1 2.1 2.1 2.1 2.1 2.2 2.1 2.1 2.2 2.2
T.C. 23.7 23.8 23.9 26.9 29.5 25.2 25.1 24.6 27.6 29.9 26.7 26.3 25.4 28.2 30.3
S.C. 23.7 23.4 19.6 19.7 15.7 25.2 25.1 21.7 21.7 16.6 26.7 26.3 23.9 23.7 17.5
KW 2.2 2.2 2.2 2.3 2.3 2.3 2.3 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4
T.C. 22.2 21.9 21.9 25.2 27.8 23.7 23.6 22.7 25.8 28.3 25.2 25.2 23.4 26.4 28.7
S.C. 22.2 21.9 18.7 19.0 15.0 23.7 23.6 20.9 21.0 16.0 25.2 25.2 23.1 23.0 17.0
KW 2.4 2.4 2.4 2.5 2.5 2.5 2.5 2.5 2.6 2.6 2.6 2.6 2.6 2.7 2.7
T.C. 20.8 19.9 20.0 23.5 26.2 22.2 22.1 20.7 24.0 26.7 23.7 24.2 21.5 24.5 27.1
S.C. 20.8 19.9 17.8 18.3 14.2 22.2 22.1 20.1 20.3 15.3 23.7 24.2 21.5 22.3 16.4
KW 2.6 2.6 2.6 2.7 2.8 2.7 2.8 2.7 2.8 2.8 2.8 2.9 2.9 2.9 2.9
Variable Speed
Furnace
T*(8,L)X*A12 FC/MC/PC37A 1.00 1.04 1.10
T*(8,L)X*B12 FC/MC/PC43B 1.01 1.05 1.11
T*(8,L)X*C16 FC/MC/PC43C 0.99 0.97 1.09
T*9X*B12 FC/MC/PC43B 1.00 1.04 1.10
T*9X*C16 FC/MC/PC43C 1.00 1.02 1.10
Y*(8,L)(C,V)*A12 FC/MC/PC37A 0.97 0.96 1.11
Y*(8,L)(C,V)*B12 FC/MC/PC43B 0.98 0.96 1.08
Y*(8,L)(C,V)*C16 FC/MC/PC43C 0.99 0.97 1.09
Y*(8,L)(C,V)*C20 FC/MC/PC43C 0.99 0.97 1.09
Y*9(C,V)*B12 FC/MC/PC43B 0.99 0.99 1.13
Y*9(C,V)*C16 FC/MC/PC43C 0.99 1.00 1.09
Y*9(C,V)*C20 FC/MC/PC43C 0.99 0.97 1.09
Coil T.C. S.C. KW
14 Johnson Controls Unitary Products
Page 15
510667-YTG-A-0409
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. YHJF36S41S1
INDOOR COIL MODEL NO. AHX36
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES I N CL UDE INDOO R FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
AHX42 – 1.01 1.01 1.03
AV*36 – 1.00 0.99 1.06
F6FP042 – 1.02 1.04 1.03
MV12B FC/MC43B 1.00 1.00 1.06
MV16C FC/MC43C 0.99 0.99 1.05
IDCFM 1000 1200 1400
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 34.5 36.4 37.1 40.1 42.7 36.2 37.6 37.8 41.2 43.4 38.0 38.7 38.5 42.3 44.1
S.C. 34.5 36.4 32.5 32.1 26.5 36.2 37.6 34.8 34.5 27.5 38.0 38.7 37.1 36.9 28.4
KW 1.9 2.0 2.0 2.0 2.0 2.0 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.2 2.2
T.C. 33.0 34.5 34.9 38.1 41.1 34.7 35.6 35.7 39.2 41.7 36.4 36.6 36.5 40.2 42.4
S.C. 33.0 34.5 31.4 31.1 25.5 34.7 35.6 33.8 33.5 26.5 36.4 36.6 36.1 35.9 27.5
KW 2.2 2.2 2.2 2.3 2.3 2.3 2.3 2.3 2.3 2.4 2.4 2.4 2.4 2.4 2.4
T.C. 31.5 32.6 32.8 36.2 39.4 33.2 33.6 33.6 37.1 40.0 34.9 34.5 34.4 38.1 40.6
S.C. 31.5 32.6 30.2 30.1 24.5 33.2 33.6 32.7 32.5 25.6 34.9 34.5 34.4 34.9 26.7
KW 2.4 2.5 2.5 2.5 2.6 2.5 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.7 2.7
T.C. 29.9 30.7 30.6 34.3 37.8 31.6 31.6 31.5 35.1 38.3 33.3 32.4 32.4 36.0 38.9
S.C. 29.9 30.7 29.1 29.2 23.4 31.6 31.6 31.5 31.5 24.6 33.3 32.4 32.4 33.9 25.8
KW 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.9 2.9 2.9 2.9 2.9 2.9 2.9
T.C. 28.2 28.1 28.0 31.8 35.3 29.8 29.4 28.9 32.6 35.9 31.4 30.8 29.7 33.4 36.6
S.C. 28.2 28.1 27.6 28.0 22.3 29.8 29.4 28.9 30.3 23.6 31.4 30.8 29.7 32.7 24.8
KW 3.0 3.0 3.0 3.0 3.1 3.1 3.1 3.1 3.1 3.2 3.2 3.2 3.2 3.2 3.2
T.C. 26.5 25.5 25.3 29.4 32.7 28.0 27.3 26.2 30.1 33.5 29.5 29.2 27.1 30.9 34.2
S.C. 26.5 25.5 25.3 26.8 21.2 28.0 27.3 26.2 29.2 22.5 29.5 29.2 27.1 30.9 23.8
KW 3.3 3.3 3.3 3.3 3.3 3.4 3.4 3.4 3.4 3.4 3.5 3.5 3.4 3.5 3.5
T.C. 24.7 22.9 22.6 27.0 30.2 26.2 25.2 23.6 27.7 31.0 27.6 27.6 24.5 28.3 31.9
S.C. 24.7 22.9 22.6 25.6 20.1 26.2 25.2 23.6 27.7 21.4 27.6 27.6 24.5 28.3 22.7
KW 3.5 3.5 3.5 3.6 3.6 3.6 3.6 3.6 3.7 3.7 3.8 3.7 3.7 3.7 3.8
Variable Speed
Furnace
T*(8,L)X*A12 FC/MC/PC37A 1.01 1.03 1.07
T*(8,L)X*B12 FC/MC/PC43B 1.01 1.03 1.07
T*(8,L)X*C16 FC/MC/PC43C 1.00 0.99 1.02
T*(8,L)X*C20 FC/MC/PC43C 1.02 1.03 1.03
T*9X*B12 FC/MC/PC43B 1.01 1.03 1.07
T*9X*C16 FC/MC/PC43C 1.02 1.03 1.08
T*9X*C20 FC/MC/PC43C 0.99 0.99 1.05
Y*(8,L)(C,V)*C16 FC/MC/PC43C 0.99 0.99 1.02
Y*(8,L)(C,V)*C20 FC/MC/PC43C 0.99 0.99 1.05
Y*9(C,V)*C16 FC/MC/PC43C 1.01 1.02 1.06
Y*9(C,V)*C20 FC/MC/PC43C 0.99 0.99 1.05
Coil T.C. S.C. KW
Johnson Controls Unitary Products 15
Page 16
510667-YTG-A-0409
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. YHJF42S41S1
INDOOR COIL MODEL NO. AHX60
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
F6FP060 – 1.01 1.04 1.04
MV20D FC/MC62D 1.00 1.02 1.03
IDCFM 1155 1355 1555
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 38.5 40.6 41.2 44.8 48.2 40.3 41.9 41.0 45.8 49.3 42.2 43.3 40.7 46.7 50.4
S.C. 38.5 35.5 30.5 30.2 24.7 40.3 39.2 32.0 32.1 25.8 42.2 42.9 33.6 33.9 26.8
KW 2.2 2.2 2.2 2.2 2.4 2.3 2.3 2.3 2.3 2.4 2.3 2.3 2.3 2.5 2.5
T.C. 36.9 38.6 39.0 42.8 46.3 38.7 39.7 39.1 43.7 47.3 40.6 40.8 39.2 44.6 48.3
S.C. 36.9 34.8 29.6 29.4 23.8 38.7 37.7 31.3 31.3 24.9 40.6 40.6 33.0 33.2 26.0
KW 2.5 2.5 2.5 2.5 2.6 2.6 2.6 2.6 2.6 2.7 2.6 2.7 2.6 2.7 2.8
T.C. 35.3 36.7 36.9 40.8 44.3 37.2 37.5 37.2 41.6 45.3 39.0 38.3 37.6 42.4 46.2
S.C. 35.3 34.0 28.6 28.6 23.0 37.2 36.2 30.5 30.5 24.1 39.0 38.3 32.5 32.4 25.1
KW 2.8 2.8 2.8 2.8 2.9 2.9 2.9 2.9 2.9 3.0 3.0 3.0 2.9 3.0 3.1
T.C. 33.7 34.8 34.7 38.8 42.3 35.6 35.3 35.4 39.6 43.2 37.4 35.8 36.1 40.3 44.1
S.C. 33.7 33.3 27.7 27.7 22.2 35.6 34.7 29.8 29.7 23.2 37.4 35.8 31.9 31.6 24.3
KW 3.0 3.1 3.1 3.1 3.1 3.2 3.2 3.2 3.2 3.2 3.3 3.3 3.2 3.3 3.4
T.C. 31.7 32.2 31.4 35.9 39.8 33.4 33.3 32.3 36.7 40.5 35.1 34.3 33.1 37.5 41.3
S.C. 31.7 31.6 26.3 26.6 21.1 33.4 33.1 28.5 28.6 22.2 35.1 34.3 30.7 30.6 23.3
KW 3.3 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.6 3.6 3.5 3.5 3.6 3.7
T.C. 29.7 29.7 28.2 33.0 37.2 31.2 31.2 29.2 33.8 37.8 32.7 32.7 30.2 34.7 38.5
S.C. 29.7 29.7 24.9 25.4 20.1 31.2 31.2 27.2 27.5 21.2 32.7 32.7 29.5 29.6 22.3
KW 3.7 3.7 3.7 3.7 3.8 3.8 3.8 3.8 3.8 3.9 3.9 3.8 3.8 3.9 4.0
T.C. 27.6 27.1 25.0 30.1 34.6 29.0 29.2 26.1 31.0 35.1 30.4 31.2 27.2 31.9 35.6
S.C. 27.6 27.1 23.6 24.3 19.1 29.0 29.2 25.9 26.4 20.2 30.4 31.2 27.2 28.6 21.4
KW 4.0 4.0 4.0 3.9 4.1 4.1 4.1 4.1 4.1 4.2 4.2 4.1 4.1 4.2 4.3
Variable Speed
Furnace
T*(8,L)X*C16 FC/MC62D 1.01 1.03 1.00
T*(8,L)X*C20 FC/MC62D 1.01 1.05 1.00
T*9X*C16 FC/MC62D 1.00 1.02 1.01
T*9X*C20 FC/MC62D 1.01 1.03 1.04
T*9X*D20 FC/MC62D 1.01 1.03 1.04
Y*(8,L)(C,V)*C20 FC/MC62D 1.01 1.02 1.04
Y*9(C,V)*C16 FC/MC62D 1.00 1.01 1.06
Y*9(C,V)*C20 FC/MC62D 1.00 1.01 1.04
Y*9(C,V)*D20 FC/MC62D 1.00 1.01 1.03
Coil T.C. S.C. KW
16 Johnson Controls Unitary Products
Page 17
510667-YTG-A-0409
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. YHJF48S41S1
INDOOR COIL MODEL NO. F6FP060
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES I N CL UDE INDOO R FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
AHX60 – 1.00 0.99 1.04
MV20D FC/MC62D 1.00 1.01 1.04
IDCFM 1400 1600 1800
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 46.3 48.5 48.5 53.1 57.3 48.0 50.1 49.9 53.5 58.0 49.8 51.6 51.4 53.9 58.7
S.C. 46.3 42.2 35.8 35.4 29.2 48.0 45.7 38.1 36.7 29.9 49.8 49.3 40.4 38.0 30.6
KW 2.7 2.7 2.7 2.8 2.7 2.8 2.8 2.8 2.8 2.8 2.9 2.9 2.9 2.9 2.9
T.C. 44.4 46.1 46.1 50.7 55.0 46.2 47.4 47.3 51.3 55.8 48.0 48.7 48.5 51.8 56.5
S.C. 44.4 41.2 34.8 34.4 28.2 46.2 44.2 37.0 36.0 29.0 48.0 47.1 39.2 37.5 29.8
KW 3.0 3.0 3.0 3.0 3.1 3.1 3.1 3.1 3.1 3.2 3.2 3.2 3.2 3.2 3.2
T.C. 42.4 43.6 43.6 48.3 52.7 44.3 44.7 44.7 49.0 53.5 46.2 45.7 45.7 49.8 54.3
S.C. 42.4 40.2 33.7 33.5 27.1 44.3 42.6 35.8 35.3 28.0 46.2 45.0 38.0 37.0 29.0
KW 3.3 3.3 3.3 3.3 3.4 3.4 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.6 3.6
T.C. 40.5 41.1 41.2 45.9 50.5 42.5 42.0 42.0 46.8 51.3 44.4 42.8 42.8 47.7 52.1
S.C. 40.5 39.2 32.7 32.6 26.0 42.5 41.0 34.7 34.6 27.1 44.4 42.8 36.8 36.5 28.2
KW 3.7 3.7 3.7 3.6 3.8 3.8 3.8 3.8 3.8 3.9 3.9 3.9 3.9 3.9 4.0
T.C. 37.9 38.3 37.6 42.7 47.5 39.7 39.5 38.5 43.5 48.2 41.5 40.7 39.3 44.3 48.8
S.C. 37.9 37.4 31.1 31.4 24.8 39.7 39.1 33.2 33.3 25.9 41.5 40.7 35.3 35.3 26.9
KW 4.0 4.0 4.0 4.1 4.2 4.2 4.2 4.1 4.2 4.3 4.3 4.3 4.2 4.3 4.4
T.C. 35.2 35.5 34.0 39.5 44.6 36.9 37.1 34.9 40.2 45.1 38.7 38.7 35.8 41.0 45.5
S.C. 35.2 35.5 29.6 30.1 23.6 36.9 37.1 31.7 32.1 24.7 38.7 38.7 33.9 34.1 25.7
KW 4.4 4.4 4.4 4.6 4.6 4.6 4.6 4.5 4.7 4.7 4.7 4.7 4.6 4.7 4.8
T.C. 32.6 32.7 30.4 36.3 41.7 34.2 34.7 31.3 37.0 42.0 35.8 36.6 32.2 37.7 42.3
S.C. 32.6 32.7 28.0 28.8 22.4 34.2 34.7 30.2 30.9 23.5 35.8 36.6 32.2 32.9 24.5
KW 4.8 4.8 4.8 5.0 5.1 5.0 5.0 4.9 5.1 5.1 5.1 5.1 5.0 5.2 5.2
Variable Speed
Furnace
T*(8,L)X*C16 FC/MC62D 1.00 1.01 1.08
T*(8,L)X*C20 FC/MC62D 1.00 1.01 1.08
T*9X*C16 FC/MC62D 1.00 1.00 1.08
T*9X*C20 FC/MC62D 1.00 1.01 1.08
T*9X*D20 FC/MC62D 1.00 1.00 1.08
Y*(8,L)(C,V)*C16 FC/MC62D 1.00 1.00 1.08
Y*(8,L)(C,V)*C20 FC/MC62D 1.00 1.00 1.08
Y*9(C,V)*C16 FC/MC62D 0.99 1.00 1.07
Y*9(C,V)*C20 FC/MC62D 0.99 0.99 1.07
Y*9(C,V)*D20 FC/MC62D 0.99 0.99 1.07
Coil T.C. S.C. KW
Johnson Controls Unitary Products 17
Page 18
510667-YTG-A-0409
COOLING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION
CONDENSING UNIT MODEL NO. YHJF60S41S1
INDOOR COIL MODEL NO. AHX60
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
LOW CFM
Air Handler Coil T.C. S.C. KW
MV20D FC/MC62D 1.00 1.00 0.99
IDCFM 965 1165 1365
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 37.3 41.8 41.6 45.5 50.9 40.4 43.7 43.3 47.7 52.2 43.5 45.6 45.1 49.9 53.6
S.C. 35.2 32.0 27.8 27.8 23.7 38.1 35.1 30.0 30.0 24.9 41.1 38.2 32.2 32.3 26.1
KW 2.1 2.1 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.3 2.3 2.3 2.3 2.3
T.C. 36.2 39.9 39.8 43.6 48.4 39.0 41.6 41.3 45.5 49.8 41.8 43.3 42.8 47.4 51.2
S.C. 34.2 31.2 27.0 27.0 22.7 36.8 34.3 29.1 29.1 23.9 39.5 37.3 31.3 31.3 25.1
KW 2.4 2.4 2.4 2.4 2.4 2.5 2.5 2.5 2.5 2.5 2.6 2.6 2.6 2.6 2.6
T.C. 35.2 38.0 37.9 41.8 46.0 37.6 39.4 39.2 43.3 47.4 40.1 40.9 40.5 44.8 48.8
S.C. 33.2 30.5 26.1 26.1 21.7 35.5 33.5 28.3 28.3 22.9 37.8 36.5 30.4 30.4 24.0
KW 2.7 2.7 2.8 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.9 2.9 2.9 2.9 2.9
T.C. 34.1 36.0 36.0 39.9 43.6 36.2 37.3 37.1 41.1 45.0 38.3 38.5 38.2 42.3 46.5
S.C. 32.2 29.7 25.3 25.3 20.7 34.2 32.7 27.4 27.4 21.9 36.2 35.7 29.5 29.4 23.0
KW 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.2 3.2 3.2 3.2 3.2
T.C. 32.4 33.7 33.7 37.3 40.9 34.2 34.7 34.6 38.3 42.1 36.1 35.7 35.5 39.3 43.3
S.C. 30.6 28.8 24.3 24.3 19.6 32.3 31.1 26.4 26.3 20.8 34.1 33.3 28.5 28.4 22.0
KW 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.6 3.6 3.6 3.6 3.6
T.C. 30.6 31.4 31.4 34.7 38.3 32.3 32.1 32.1 35.5 39.2 33.9 32.8 32.8 36.3 40.1
S.C. 28.9 27.8 23.3 23.2 18.6 30.5 29.4 25.4 25.3 19.7 32.0 31.0 27.4 27.3 20.9
KW 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 4.0 4.0 4.0 4.0 4.0
T.C. 28.9 29.1 29.1 32.1 35.7 30.3 29.5 29.6 32.7 36.3 31.7 29.9 30.1 33.4 37.0
S.C. 27.3 26.9 22.4 22.2 17.5 28.6 27.8 24.4 24.2 18.7 30.0 28.6 26.4 26.3 19.9
KW 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4
Variable Speed
Furnace
T*(8,L)X*C20 FC/MC62D 0.92 0.87 0.97
T*9X*C20 FC/MC62D 1.01 1.02 1.02
T*9X*D20 FC/MC62D 1.02 1.03 1.01
Y*(8,L)(C,V)*C20 FC/MC62D 0.97 0.94 0.99
Y*9(C,V)*C20 FC/MC62D 0.97 0.95 1.00
Y*9(C,V)*D20 FC/MC62D 0.98 0.96 1.01
Coil T.C. S.C. KW
18 Johnson Controls Unitary Products
Page 19
510667-YTG-A-0409
COOLING PERFORMANCE DA TA - HIGH CFM 2-STAGE OPERATION
CONDENSING UNIT MODEL NO. YHJF60S41S1
INDOOR COIL MODEL NO. AHX60
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES I N CL UDE INDOO R FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
HIGH CFM
Air Handler Coil T.C. S.C. KW
MV20D FC/MC62D 1.03 1.01 0.96
IDCFM 1650 1850 2050
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 56.5 60.0 59.6 65.6 70.6 58.5 61.2 60.8 66.7 72.5 60.5 62.3 62.0 67.8 74.4
S.C. 55.7 50.3 42.9 42.5 34.9 57.7 53.1 44.9 44.5 36.0 59.6 55.9 47.0 46.5 37.1
KW 3.4 3.5 3.5 3.5 3.6 3.5 3.6 3.5 3.6 3.7 3.6 3.6 3.6 3.7 3.8
T.C. 54.4 57.2 56.8 62.6 67.6 56.3 58.2 57.9 63.6 69.1 58.1 59.2 59.0 64.6 70.6
S.C. 53.6 49.1 41.6 41.3 33.5 55.4 51.9 43.7 43.2 34.6 57.3 54.7 45.7 45.2 35.7
KW 3.8 3.9 3.8 3.9 4.0 3.9 3.9 3.9 4.0 4.1 4.0 4.0 4.0 4.1 4.2
T.C. 52.3 54.4 54.0 59.6 64.6 54.0 55.2 55.0 60.5 65.8 55.7 56.1 56.0 61.3 66.9
S.C. 51.5 48.0 40.3 40.1 32.2 53.2 50.7 42.4 42.0 33.2 54.9 53.4 44.4 43.9 34.3
KW 4.2 4.2 4.2 4.3 4.4 4.3 4.3 4.3 4.4 4.5 4.4 4.4 4.4 4.5 4.6
T.C. 50.2 51.6 51.2 56.5 61.7 51.8 52.3 52.1 57.3 62.4 53.3 52.9 53.0 58.1 63.2
S.C. 49.5 46.8 39.1 38.9 30.8 51.0 49.5 41.1 40.8 31.8 52.5 52.1 43.1 42.6 32.9
KW 4.6 4.6 4.6 4.7 4.8 4.7 4.7 4.7 4.8 4.9 4.8 4.8 4.8 4.9 5.0
T.C. 47.5 48.0 47.8 52.6 57.5 48.8 49.0 48.4 53.3 58.1 50.2 50.0 49.1 54.0 58.8
S.C. 46.8 45.2 37.6 37.4 29.2 48.1 47.3 39.6 39.2 30.2 49.5 49.3 41.5 41.1 31.3
KW 5.1 5.1 5.1 5.2 5.3 5.2 5.2 5.2 5.3 5.4 5.3 5.3 5.3 5.4 5.5
T.C. 44.7 44.4 44.4 48.7 53.3 45.9 45.7 44.8 49.3 53.9 47.1 47.1 45.2 49.8 54.4
S.C. 44.1 43.7 36.1 35.8 27.6 45.2 45.0 38.0 37.7 28.6 46.4 46.4 39.9 39.5 29.7
KW 5.6 5.6 5.6 5.7 5.8 5.7 5.7 5.7 5.8 5.9 5.8 5.8 5.8 5.9 6.0
T.C. 42.0 40.7 41.0 44.8 49.2 43.0 42.5 41.1 45.3 49.6 44.0 44.2 41.3 45.7 50.0
S.C. 41.4 40.7 34.6 34.3 26.0 42.3 42.5 36.5 36.2 27.0 43.3 43.5 38.4 38.0 28.1
KW 6.1 6.1 6.1 6.2 6.3 6.2 6.2 6.2 6.3 6.4 6.3 6.3 6.3 6.4 6.5
Variable Speed
Furnace
T*(8,L)X*C20 FC/MC62D 1.02 0.97 0.93
T*9X*C20 FC/MC62D 1.01 0.95 0.93
T*9X*D20 FC/MC62D 1.02 0.97 0.93
Y*(8,L)(C,V)*C20 FC/MC62D 1.01 0.96 0.93
Y*9(C,V)*C20 FC/MC62D 1.01 0.96 0.96
Y*9(C,V)*D20 FC/MC62D 1.01 0.96 0.95
Coil T.C. S.C. KW
Johnson Controls Unitary Products 19
Page 20
510667-YTG-A-0409
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO YHJF18S41S1
EVAPORATOR COIL MODEL NO AHX30
AIR TEMP.
ENTERING
OUTDOOR UNIT
60
47
40
30
17
10
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
AIR TEMP.
ENTERING
INDOOR COIL
60 21.1 4.1 1.3 22.2 4.5 1.2 23.3 4.9 1.1
70 20.5 3.6 1.5 21.6 4.0 1.4 22.6 4.3 1.3
80 19.9 3.2 1.6 20.9 3.5 1.5 21.9 3.9 1.4
60 18.6 3.8 1.3 19.2 4.0 1.2 19.8 4.2 1.1
70 17.7 3.3 1.4 18.4 3.5 1.3 19.1 3.7 1.2
80 16.8 2.8 1.6 17.6 3.1 1.5 18.4 3.3 1.4
60 16.7 3.4 1.3 17.3 3.6 1.2 17.9 3.8 1.1
70 16.1 3.0 1.4 16.8 3.2 1.3 17.4 3.4 1.2
80 15.6 2.7 1.5 16.3 2.9 1.4 17.0 3.1 1.3
60 14.6 3.1 1.2 15.1 3.2 1.2 15.5 3.4 1.1
70 14.2 2.7 1.4 14.6 2.9 1.3 15.0 3.0 1.2
80 13.7 2.4 1.5 14.1 2.5 1.4 14.4 2.6 1.3
60 11.7 2.6 1.2 12.0 2.6 1.1 12.3 2.7 1.1
70 11.2 2.2 1.3 11.6 2.3 1.2 11.9 2.4 1.2
80 10.8 2.0 1.5 11.1 2.0 1.4 11.5 2.1 1.3
60 10.1 2.3 1.1 10.3 2.3 1.1 10.4 2.3 1.0
70 9.6 1.9 1.3 9.9 2.0 1.2 10.2 2.1 1.2
80 9.1 1.7 1.4 9.5 1.8 1.4 9.9 1.9 1.3
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
450 600 750
ID CFM
Multipliers for determining the performance with other indoor sections.
Air Handler Coil MBH KW COP
AV*36 – 1.00 1.03 0.97
MV12B FC/MC35B 1.00 0.97 1.03
MV12B FC/MC43B 1.00 1.01 0.99
Variable Speed
Furnace
T*(8,L)X*A12 FC/MC/PC32A 0.99 0.99 1.00
Y*(8,L)(C,V)*A12 FC/MC/PC32A 1.00 0.97 1.03
Y*(8,L)(C,V)*B12 FC/MC/PC35B 1.00 0.99 1.01
Y*(8,L)(C,V)*C16 FC/MC/PC35C 1.00 0.98 1.02
Y*9(C,V)*B12 FC/MC/PC35B 1.00 0.98 1.02
Y*9(C,V)*C16 FC/MC/PC35C 1.00 0.99 1.01
Y*(8,L)(C,V)*A12 FC/MC/PC37A 1.00 1.01 0.99
Y*(8,L)(C,V)*B12 FC/MC/PC43B 1.00 0.98 1.02
Coil MBH KW COP
20 Johnson Controls Unitary Products
Page 21
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO YHJF24S41S1
EVAPORATOR COIL MODEL NO AHX30
AIR TEMP.
ENTERING
OUTDOOR UNIT
60
47
40
30
17
10
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
AIR TEMP.
ENTERING
INDOOR COIL
60 26.8 4.0 1.7 27.6 4.3 1.6 28.4 4.5 1.5
70 25.1 3.4 1.9 26.1 3.7 1.8 27.2 4.0 1.6
80 23.3 2.9 2.1 24.7 3.2 2.0 26.1 3.5 1.8
60 24.8 3.8 1.7 25.0 4.0 1.5 25.2 4.1 1.4
70 22.7 3.2 1.8 23.2 3.4 1.7 23.7 3.6 1.6
80 20.7 2.7 2.0 21.5 2.9 1.9 22.2 3.1 1.8
60 20.8 3.3 1.6 21.5 3.5 1.5 22.3 3.7 1.4
70 19.5 2.9 1.8 20.3 3.0 1.7 21.2 3.2 1.6
80 18.2 2.4 2.0 19.1 2.6 1.8 20.0 2.8 1.7
60 18.7 3.1 1.6 18.8 3.1 1.5 18.9 3.2 1.4
70 17.5 2.6 1.7 17.8 2.7 1.6 18.1 2.8 1.5
80 16.2 2.3 1.9 16.8 2.4 1.8 17.3 2.5 1.7
60 15.5 2.7 1.5 15.8 2.7 1.4 16.2 2.8 1.4
70 13.1 2.1 1.6 13.8 2.2 1.6 14.5 2.3 1.5
80 10.8 1.6 1.8 11.8 1.7 1.7 12.8 1.9 1.6
60 13.5 2.4 1.5 13.8 2.4 1.4 14.0 2.4 1.3
70 12.2 1.9 1.6 12.5 2.0 1.5 12.8 2.0 1.5
80 10.8 1.6 1.8 11.2 1.7 1.7 11.6 1.7 1.6
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
600 800 1000
ID CFM
510667-YTG-A-0409
Multipliers for determining the performance with other indoor sections.
Air Handler Coil MBH KW COP
AHX36 – 1.01 1.02 0.99
AV*36 – 0.99 1.02 0.97
F6FP030 – 1.00 1.00 1.00
F6FP036 – 1.00 1.01 0.99
MV12B FC/MC35B 1.00 1.01 0.99
MV12B FC/MC43B 1.00 1.05 0.95
Variable Speed
Furnace
T*(8,L)X*A12 FC/MC/PC32A 0.99 1.02 0.97
T*(8,L)X*B12 FC/MC/PC35B 0.99 1.03 0.96
T*(8,L)X*C16 FC/MC/PC35C 0.99 1.03 0.96
T*(8,L)X*C20 FC/MC/PC35C 0.99 1.03 0.96
T*9X*B12 FC/MC/PC35B 0.99 1.02 0.97
T*9X*C16 FC/MC/PC35C 0.99 1.04 0.95
T*9X*C20 FC/MC/PC35C 1.00 1.02 0.98
T*(8,L)X*A12 FC/MC/PC37A 1.00 1.07 0.94
T*(8,L)X*B12 FC/MC/PC43B 0.99 1.07 0.93
Coil MBH KW COP
Variable Speed
Furnace
T*(8,L)X*C16 FC/MC/PC43C 0.99 1.07 0.93
T*9X*B12 FC/MC/PC43B 1.00 1.07 0.94
T*9X*C16 FC/MC/PC43C 0.99 1.04 0.95
T*9X*C20 FC/MC/PC43C 0.99 1.03 0.96
Y*(8,L)(C,V)*A12 FC/MC/PC32A 1.00 0.99 1.01
Y*(8,L)(C,V)*B12 FC/MC/PC35B 0.99 0.98 1.01
Y*(8,L)(C,V)*C16 FC/MC/PC35C 1.00 1.01 0.99
Y*(8,L)(C,V)*C20 FC/MC/PC35C 0.98 0.99 0.99
Y*9(C,V)*B12 FC/MC/PC35B 1.00 1.00 1.00
Y*9(C,V)*C16 FC/MC/PC35C 1.00 1.02 0.98
Y*9(C,V)*C20 FC/MC/PC35C 0.99 0.98 1.01
Y*(8,L)(C,V)*A12 FC/MC/PC37A 1.01 1.03 0.98
Y*(8,L)(C,V)*B12 FC/MC/PC43B 0.99 1.01 0.98
Y*(8,L)(C,V)*C16 FC/MC/PC43C 1.00 1.05 0.95
Y*(8,L)(C,V)*C20 FC/MC/PC43C 0.99 1.02 0.97
Y*9(C,V)*B12 FC/MC/PC43B 1.00 1.04 0.96
Y*9(C,V)*C16 FC/MC/PC43C 1.00 1.05 0.95
Y*9(C,V)*C20 FC/MC/PC43C 1.01 1.05 0.96
Coil MBH KW COP
Johnson Controls Unitary Products 21
Page 22
510667-YTG-A-0409
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO YHJF30S41S1
EVAPORATOR COIL MODEL NO AHX36
AIR TEMP.
ENTERING
OUTDOOR UNIT
60
47
40
30
17
10
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
AIR TEMP.
ENTERING
INDOOR COIL
60 36.9 4.6 2.1 37.4 4.8 1.9 38.0 5.0 1.8
70 35.9 4.0 2.3 36.5 4.2 2.2 37.1 4.4 2.0
80 34.8 3.5 2.6 35.5 3.8 2.4 36.2 4.0 2.2
60 31.3 4.1 2.0 31.8 4.2 1.8 32.3 4.4 1.7
70 30.5 3.6 2.2 31.0 3.7 2.1 31.5 3.9 1.9
80 29.8 3.1 2.5 30.2 3.3 2.3 30.7 3.5 2.2
60 28.4 3.7 1.9 28.9 3.9 1.8 29.3 4.0 1.7
70 27.6 3.3 2.2 28.1 3.4 2.0 28.6 3.6 1.9
80 26.8 2.9 2.4 27.4 3.0 2.3 27.9 3.2 2.1
60 24.8 3.3 1.9 25.1 3.4 1.8 25.4 3.5 1.7
70 23.9 2.9 2.1 24.3 3.0 2.0 24.6 3.1 1.9
80 23.0 2.6 2.3 23.4 2.7 2.2 23.8 2.7 2.1
60 19.9 2.8 1.8 20.1 2.8 1.7 20.4 2.9 1.7
70 18.8 2.4 2.0 19.2 2.4 2.0 19.6 2.5 1.9
80 17.8 2.0 2.3 18.3 2.1 2.2 18.8 2.2 2.1
60 17.1 2.4 1.8 17.4 2.4 1.7 17.6 2.5 1.6
70 15.8 2.0 2.0 16.3 2.1 1.9 16.7 2.1 1.8
80 14.4 1.7 2.2 15.1 1.8 2.1 15.8 1.9 2.0
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
800 1000 1200
ID CFM
Multipliers for determining the performance with other indoor sections.
Air Handler Coil MBH KW COP
AV*36 – 0.99 1.00 1.00
F6FP042 – 0.99 1.00 1.00
MV12B FC/MC43B 1.00 0.97 1.03
MV16C FC/MC43C 1.00 0.98 1.02
Variable Speed
Furnace
T*(8,L)X*A12 FC/MC/PC37A 1.00 1.01 1.00
T*(8,L)X*B12 FC/MC/PC43B 1.00 1.00 1.00
T*(8,L)X*C16 FC/MC/PC43C 1.00 0.99 1.01
T*9X*B12 FC/MC/PC43B 1.00 1.00 1.01
T*9X*C16 FC/MC/PC43C 1.00 0.99 1.01
Y*(8,L)(C,V)*A12 FC/MC/PC37A 1.00 0.95 1.05
Y*(8,L)(C,V)*B12 FC/MC/PC43B 1.00 0.97 1.04
Y*(8,L)(C,V)*C16 FC/MC/PC43C 1.00 0.98 1.02
Y*(8,L)(C,V)*C20 FC/MC/PC43C 1.00 0.99 1.02
Y*9(C,V)*B12 FC/MC/PC43B 1.00 0.96 1.04
Y*9(C,V)*C16 FC/MC/PC43C 1.00 0.98 1.03
Y*9(C,V)*C20 FC/MC/PC43C 1.00 0.98 1.03
Coil MBH KW COP
22 Johnson Controls Unitary Products
Page 23
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO YHJF36S41S1
EVAPORATOR COIL MODEL NO AHX36
AIR TEMP.
ENTERING
OUTDOOR UNIT
60
47
40
30
17
10
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
AIR TEMP.
ENTERING
INDOOR COIL
60 47.2 4.2 2.9 47.9 4.4 2.7 48.6 4.6 2.6
70 46.3 3.7 3.3 46.8 3.9 3.1 47.3 4.1 2.9
80 45.3 3.3 3.7 45.6 3.4 3.4 46.0 3.6 3.2
60 40.0 3.7 2.8 40.4 3.8 2.7 40.9 4.0 2.5
70 39.5 3.3 3.2 39.8 3.4 3.0 40.1 3.5 2.8
80 38.9 2.9 3.5 39.2 3.0 3.3 39.4 3.2 3.2
60 36.8 3.5 2.7 37.0 3.6 2.6 37.2 3.7 2.5
70 36.3 3.1 3.1 36.4 3.2 2.9 36.6 3.3 2.8
80 35.7 2.7 3.5 35.9 2.8 3.3 36.0 2.9 3.1
60 31.9 3.1 2.7 32.0 3.1 2.5 32.1 3.2 2.4
70 31.5 2.7 3.1 31.6 2.8 2.9 31.7 2.9 2.7
80 31.0 2.4 3.4 31.2 2.5 3.2 31.4 2.6 3.1
60 25.3 2.6 2.5 25.4 2.6 2.4 25.4 2.6 2.3
70 24.2 2.2 2.9 24.7 2.3 2.8 25.2 2.3 2.6
80 23.1 1.9 3.2 24.1 2.0 3.1 25.0 2.1 3.0
60 21.6 2.3 2.3 20.9 2.3 2.3 20.2 2.2 2.2
70 21.4 2.0 2.7 20.3 2.0 2.6 19.2 1.9 2.5
80 21.1 1.8 3.1 19.6 1.7 2.9 18.2 1.6 2.7
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
1000 1200 1400
ID CFM
510667-YTG-A-0409
Multipliers for determining the performance with other indoor sections.
Air Handler Coil MBH KW COP
AHX42 – 1.00 1.01 0.99
AV*36 – 1.00 0.99 1.01
F6FP042 – 1.00 1.02 0.98
MV12B FC/MC43B 1.00 0.98 1.02
MV16C FC/MC43C 1.00 0.98 1.02
Variable Speed
Furnace
T*(8,L)X*A12 FC/MC/PC37A 1.00 1.00 1.00
T*(8,L)X*B12 FC/MC/PC43B 1.00 1.00 1.00
T*(8,L)X*C16 FC/MC/PC43C 1.00 0.99 1.01
T*(8,L)X*C20 FC/MC/PC43C 1.00 1.02 0.98
T*9X*B12 FC/MC/PC43B 1.00 1.00 1.00
T*9X*C16 FC/MC/PC43C 1.00 1.01 0.99
T*9X*C20 FC/MC/PC43C 1.00 0.98 1.02
Y*(8,L)(C,V)*C16 FC/MC/PC43C 1.00 0.98 1.02
Y*(8,L)(C,V)*C20 FC/MC/PC43C 1.00 0.98 1.02
Y*9(C,V)*C16 FC/MC/PC43C 1.00 0.99 1.01
Y*9(C,V)*C20 FC/MC/PC43C 1.00 0.97 1.03
Coil MBH KW COP
Johnson Controls Unitary Products 23
Page 24
510667-YTG-A-0409
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO YHJF42S41S1
EVAPORATOR COIL MODEL NO AHX60
AIR TEMP.
ENTERING
OUTDOOR UNIT
60
47
40
30
17
10
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
AIR TEMP.
ENTERING
INDOOR COIL
60 45.3 4.1 2.8 45.0 4.1 2.7 44.6 4.2 2.6
70 45.1 3.8 3.0 44.9 3.8 2.9 44.6 3.9 2.8
80 44.9 3.5 3.3 44.8 3.6 3.1 44.7 3.6 3.0
60 41.3 4.1 2.5 41.2 4.1 2.5 41.1 4.1 2.4
70 40.7 3.6 2.8 40.7 3.7 2.7 40.7 3.7 2.6
80 40.0 3.3 3.1 40.2 3.3 3.0 40.3 3.4 2.9
60 38.2 3.8 2.5 38.4 3.9 2.4 38.5 3.9 2.3
70 37.4 3.4 2.8 37.7 3.5 2.7 38.1 3.5 2.6
80 36.6 3.1 3.0 37.1 3.1 3.0 37.7 3.2 2.9
60 33.3 3.4 2.4 33.4 3.4 2.4 33.5 3.4 2.3
70 32.7 3.0 2.7 32.8 3.1 2.6 32.9 3.1 2.5
80 32.0 2.7 3.0 32.2 2.8 2.9 32.3 2.8 2.8
60 26.7 2.9 2.2 26.9 2.9 2.2 27.2 2.8 2.2
70 25.2 2.5 2.5 20.9 2.5 2.4 26.7 2.5 2.5
80 23.6 2.1 2.8 14.9 2.2 2.7 26.3 2.3 2.7
60 22.8 2.5 2.3 23.3 2.5 2.2 23.8 2.5 2.2
70 22.9 2.2 2.6 23.2 2.3 2.5 23.6 2.3 2.4
80 22.9 2.1 2.8 23.1 2.1 2.8 23.3 2.1 2.7
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
1200 1400 1600
ID CFM
Multipliers for determining the performance with other indoor sections.
Air Handler Coil MBH KW COP
F6FP060 – 1.01 1.01 1.00
MV20D FC/MC62D 1.00 1.01 1.00
Variable Speed
Furnace
T*(8,L)X*C16 FC/MC62D 1.00 1.02 0.99
T*(8,L)X*C20 FC/MC62D 1.01 1.02 0.99
T*9X*C16 FC/MC62D 1.01 1.00 1.02
T*9X*C20 FC/MC62D 1.00 1.01 1.00
T*9X*D20 FC/MC62D 1.00 1.01 1.00
Y*(8,L)(C,V)*C20 FC/MC62D 1.01 1.00 1.01
Y*9(C,V)*C16 FC/MC62D 1.02 0.97 1.06
Y*9(C,V)*C20 FC/MC62D 1.01 0.98 1.04
Y*9(C,V)*D20 FC/MC62D 1.01 0.99 1.03
Coil MBH KW COP
24 Johnson Controls Unitary Products
Page 25
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO YHJF48S41S1
EVAPORATOR COIL MODEL NO F6FP060
AIR TEMP.
ENTERING
OUTDOOR UNIT
60
47
40
30
17
10
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
AIR TEMP.
ENTERING
INDOOR COIL
60 62.2 4.3 3.7 62.7 4.5 3.5 63.2 4.6 3.3
70 60.9 3.8 4.2 61.2 3.9 4.0 61.6 4.1 3.8
80 59.5 3.3 4.8 59.8 3.5 4.5 60.0 3.6 4.2
60 53.1 3.6 3.8 53.1 3.7 3.6 53.1 3.8 3.4
70 52.0 3.2 4.3 52.0 3.2 4.1 52.1 3.3 3.9
80 50.9 2.8 4.8 51.0 2.9 4.6 51.0 2.9 4.5
60 47.9 3.2 3.8 47.8 3.3 3.6 47.8 3.4 3.4
70 47.2 2.8 4.4 47.0 2.9 4.2 46.9 3.0 3.9
80 46.5 2.5 5.0 46.2 2.6 4.7 45.9 2.6 4.4
60 40.1 2.9 3.6 40.2 2.9 3.5 40.3 2.9 3.3
70 38.9 2.7 3.8 39.3 2.7 3.8 39.6 2.6 3.7
80 37.8 2.5 4.0 38.3 2.4 4.0 38.8 2.4 4.1
60 30.2 2.6 2.8 31.3 2.8 2.8 32.4 2.9 2.7
70 28.7 2.4 3.0 29.5 2.4 3.0 30.3 2.5 2.9
80 27.3 2.2 3.2 27.7 2.2 3.2 28.1 2.2 3.1
60 25.2 2.4 2.6 24.8 2.3 2.5 24.4 2.3 2.5
70 24.5 2.1 2.9 25.3 2.1 3.0 26.1 2.0 3.2
80 23.8 1.9 3.1 25.7 1.8 3.5 27.7 1.8 3.9
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
1400 1600 1800
ID CFM
510667-YTG-A-0409
Multipliers for determining the performance with other indoor sections.
Air Handler Coil MBH KW COP
AHX60 – 1.00 0.99 1.01
MV20D FC/MC62D 1.00 0.99 1.01
Variable Speed
Furnace
T*(8,L)X*C16 FC/MC62D 1.00 0.98 1.02
T*(8,L)X*C20 FC/MC62D 1.00 0.99 1.01
T*9X*C16 FC/MC62D 1.00 0.98 1.02
T*9X*C20 FC/MC62D 1.00 0.99 1.01
T*9X*D20 FC/MC62D 1.00 0.98 1.02
Y*(8,L)(C,V)*C16 FC/MC62D 1.00 0.98 1.02
Y*(8,L)(C,V)*C20 FC/MC62D 1.00 0.98 1.02
Y*9(C,V)*C16 FC/MC62D 1.00 0.97 1.03
Y*9(C,V)*C20 FC/MC62D 1.00 0.96 1.04
Y*9(C,V)*D20 FC/MC62D 1.00 0.97 1.03
Coil MBH KW COP
Johnson Controls Unitary Products 25
Page 26
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO YHJF60S41S1
EVAPORATOR COIL MODEL NO AHX60
AIR TEMP.
ENTERING
OUTDOOR UNIT
60
47
40
30
17
10
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
AIR TEMP.
ENTERING
INDOOR COIL
60 70.70 4.28 4.25 71.76 4.41 4.11 72.83 4.54 3.97
70 69.78 3.85 4.72 70.63 3.95 4.57 71.49 4.07 4.41
80 68.86 3.48 5.19 69.51 3.58 5.03 70.15 3.67 4.86
60 61.77 3.89 4.05 62.15 3.97 3.92 62.54 4.05 3.78
70 60.84 3.47 4.53 61.18 3.55 4.39 61.52 3.62 4.23
80 59.90 3.13 5.01 60.20 3.19 4.86 60.50 3.27 4.69
60 56.20 3.64 3.93 56.47 3.70 3.80 56.74 3.76 3.69
70 55.47 3.24 4.42 55.62 3.30 4.27 55.76 3.35 4.13
80 54.75 2.92 4.90 54.77 2.96 4.75 54.79 3.02 4.57
60 49.33 3.30 3.78 49.52 3.33 3.70 49.72 3.34 3.61
70 47.84 2.83 4.36 47.68 2.87 4.21 47.52 2.90 4.06
80 46.36 2.45 4.94 45.84 2.49 4.71 45.31 2.53 4.51
60 40.18 2.78 3.64 37.45 2.80 3.50 34.72 2.80 3.40
70 40.02 2.47 4.14 38.68 2.60 4.00 37.36 2.50 3.91
80 39.86 2.23 4.65 39.91 2.25 4.53 39.99 2.27 4.42
60 35.02 2.49 3.52 35.29 2.51 3.45 35.54 2.53 3.38
70 33.76 2.16 3.98 34.56 2.22 3.90 35.35 2.27 3.82
80 32.50 1.89 4.44 33.83 1.97 4.34 35.15 2.06 4.26
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
1600 1800 2000
ID CFM
Multipliers for determining the performance with other indoor sections.
Air Handler Coil MBH KW COP
MV20D FC/MC62D 0.99 1.00 0.99
Variable Speed
Furnace
T*(8,L)X*C20 FC/MC62D 0.97 0.89 1.10
T*9X*C20 FC/MC62D 1.00 1.01 1.00
T*9X*D20 FC/MC62D 1.00 1.02 0.99
Y*(8,L)(C,V)*C20 FC/MC62D 0.99 0.95 1.04
Y*9(C,V)*C20 FC/MC62D 0.99 0.96 1.04
Y*9(C,V)*D20 FC/MC62D 1.00 0.97 1.03
Coil MBH KW COP
Subject to change without notice. Printed in U.S.A. 510667-YTG-A-0409