Introducing the YORK Millennium 25, 30, & 40 ton rooftop
line - units designed to provide peak performance and value
both today and for years to come. Millennium units are manufactured at an ISO 9001 registered facility, and each rooftop
is completely computer-run tested prior to shipment.
The Millennium is designed to be flexible enough to meet
your needs today and in the future. The true value of YORK’s
Millennium is that it can be designed to fit any need, from
cooling only, constant volume applications to variable air volume systems with variable frequency drive.
FEATURING:
•Cooling Only Units
•Cooling/Gas Heating Units (Natural) Standard or
Modulating Gas Heat available
14 HOT WATER COIL - 40 TON, 2 ROW, AT 20 GPM. . 23
15 HOT WATER COIL - 40 TON, 2 ROW, AT 40 GPM. . 23
16 HOT WATER COIL - 40 TON, 2 ROW, AT 60 GPM. . 24
17 HOT WATER COIL - 40 TON, 2 ROW, AT 80 GPM. . 24
Introducing the YORK Millennium 25, 30, & 40 ton rooftop
line - units designed to provide peak performance and value
both today and for years to come. When we aske d our customers what they wanted in a new rooftop line, we were careful to listen to both the needs of today and tomorrow. So,
you'll find that Millennium units not only help you solve
today's problems, but can handle tomorrow's difficulties as
well:
Industry Leading Efficiency
EER 25 ton) rating makes it the most frugal energy consumer
in its class. When it comes to lower operating costs, Millennium simply outperforms the competition.
Double Wall Construction
walled as standard. The galvanized sheet metal liner provides the best protection against microbial growth, helping
both the unit and the indoor air stay fresh and clean. And, the
rigid sheet metal inner liner keeps the insulation completely
out of the air stream, eliminating concerns about fiberglass
particles.
Drain Pan Whisks Away Condensate
quently the source of microbial contamination. Competitive
drain pans often are insufficiently sloped to properly drain all
of the condensate, causing drain pan corrosion and bacterial
growth to begin almost immediately. The YORK design is
sloped at the 1/4” per foot recommended by the ASHRAE
62.1-2004 ventilation draft standard, with an extra large drain
connection capable of removing up to three gallons of condensate per minute. It is available in either powder coat
painted steel or stainless steel for long life.
- The Millennium's 9.5 EER (10
- Millennium units come double
- Condensate is fre-
®
Efficient, Durable Scroll Compressors
design uses industrial grade hermetic scroll compressors for
peak efficiency and low noise operation. The compressor
design is so durable that it can actually hold more liquid
charge without slugging than is present in each refrigerant
circuit at shipment, dramatically reducing the chances of ever
slugging a compressor with liquid charge.
Multiple Refrigeration Circuits for Greater Turndown
YORK Millennium unit has intertwined 10 ton circuits (12.5
ton circuits on the 25 ton) - giving the best unloading capability in the industry. With more and more designs requiring
higher outside air quantities, the lower capacity capability is
an outstanding way to neutralize outside air without over-conditioning the space on off-peak days. And, Millennium's high
quality balance-port thermal expansion valves are more
effective at metering refrigerant flow in part-load conditions,
making Millennium a peak-performer across a wide capacity
range.
- The Millennium
- The
FEATURES AND BENEFITS
When it comes to flexibility, Millennium really shines. Our customers were clear about one thing - not all installations are
the same. Some have very simple needs, others are more
involved. The YORK Millennium serves both markets - and all
of those in between - extremely well. YORK engineers crafted
a design which is both uniquely flexible and competitive, giving you the best of both worlds. In addition to a competitive
base product, Millennium offers unparalleled flexibility.
Optional features include:
Variable Air Volume
volume by inlet guide vanes or variable frequency drive - the
choice is yours. All Millennium VAV units come standard with
hot gas bypass to give extended operation range.
- YORK gives you the ability to vary air
Johnson Controls Unitary Products5
246653-YTG-E-0108
Optional Head Pressure Control - For those applications
where mechanical cooling is required below 40°F, optional
low ambient operation allows compressor operation down to
0°F.
Easily Upgrade Motor Efficiency to Meet Tighter Codes
Optional high efficiency motors help you make simple
upgrades to meet more demanding building and energy
codes.
Enhanced Filtration Options
- Millennium gives designers the
flexibility to meet various IAQ requirements with a full range
of rigid and throwaway filters at different efficiency levels.
Vibration Isolation
- The Millennium's neoprene mounts are
typically sufficient for most applications but when sound and
vibration transmission are a major concern, YORK offers 1"
and 2" isolation springs for even greater protection from supply air fan noise and vibration.
Corrosion Resistant Coils
- Many industrial and seacoast
applications require enhanced protection from corrosive environments.
Optional TechniCoated Coated Condenser and Evaporator Coils - Many industrial and seacoast applications
require enhanced protection from corrosive environments. The special dipped phenolic coating process
provides a high level of protection for the exposed condenser coil.
Optional Copper-Copper Condenser and Evaporator
Coils - For corrosion resistance.
High Capacity Evaporator Coils
- For those applications
which require slightly more capacity than offered by the standard Millennium product, YORK offers the option of higher
capacity evaporator coils, boosting cooling output without
increasing unit size. (30 & 40 Ton R-22 only)
ers. Comparative enthalpy, single enthalpy and dry bulb control are available.
Optional Factory Installed Disconnect
- A conveniently
located actuator handle in the front of the unit can disconnect
-
line power to the entire unit, eliminating the need for a field
provided disconnect. The handle may also be locked in either
position through the use of a standard padlock. Millennium's
single point power connection makes this option particularly
appealing. If desired, the disconnect may be ordered with a
115 volt, GFCI protected convenience outlet, including a factory wired transformer to power the outlet from the single
point power connection; the convenience outlet remains
operational when the disconnect is open.
Heating Done Your Way
- Millennium offers the choice of natural gas standard or modulating gas heat, electric resistance
heat, hot water heat, steam, or no heat at all. Very simply, the
choice is yours.
INSTALLATION FEATURES
With YORK Millennium, high performance doesn't mean high
complexity. YORK listened carefully to make sure that Millennium was as simple as possible, and service convenience
comes standard with each unit. From a single curb size to the
easy service access, you'll find that Millennium was designed
to be easy from start to finish.
Full Range of Air Flows and Static Pressures
nium design gives a complete offering of supply air flows and
static pressure combinations to meet most every application
requirement.
Single Power Point Connection - Millennium units have a single gas and electric connection, minimizing time at the job
site. For further installation flexibility, power and gas connections may be brought up from the curb or through the side of
the unit.
- The Millen-
Variety of Exhaust Air Options
wide variety of exhaust air options, including barometric
relief, non-modulating power exhaust, and modulating power
exhaust. And, because Millennium units use forward-curved
- YORK Millennium offers a
Simple Controls
- Millennium's controls system is easy to
understand and apply, and it doesn't lock you into proprietary
devices. A choice for YORK Millennium today doe s not limit
your choices tomorrow.
blowers for power exhaust fans, they can exhaust up to 100%
of the nominal supply air at much greater static pressure
loads than competitive units. Not available on end return.
Rain Hoods Rotate Into Place - No bulky, field--installed rain
hoods here. Millennium rain hoods ship rotated inside the
unit. Once on the job, installer merely rotates the hood
NOTE: In most applications, the supply fan will keep the
return at negative pressure. A barometric relief will
function better when ducted to building space, not
the return.
Optional Factory Installed Economizers
- Millennium units
offer economizers with Standard or Optional low leak damp-
6Johnson Controls Unitary Products
upward and puts in a few screws - an easy one-person job.
Excellent Access for Service
- Service access on Millennium
is a snap. Hinged and latched door options give access on
both sides of the unit to all major components. Some doors
have positive action slide latches for even greater ease of
access. All service fittings are conveniently located to minimize time and effort.
A
NGLED CONDENSER
COILS
246653-YTG-E-0108
PITCHED ROOF
SOLID, CLASS II FAN CONSTRUCTION
INTERTWINED COIL
DOUBLE WALL CONSTRUCTION
LOW LEAK DAMPERS
CONSTRUCTION FEATURES
YORK's Millennium rooftop line is built for the long haul, with
high end features and construction offered at a competitive
price. Millennium units are manufactured at an ISO 9001 registered facility, and each rooftop is completely computer-run
tested prior to shipment. Some of the valuable construction
features of the Millennium which are not found on competitive
units include:
Double Wall Construction
and an interior wall, which make for a more rigid design with
panels and doors that are solid, not flimsy. The unit features a
fully framed construction for even greater stability.
Powder Paint
keeps the unit in great condition for years to come.
Extended flue connection
mounted external flue. The flue lifts all products of furnace
combustion far above the unit - eliminating the possibility of
corrosion in the furnace heat exchanger from recirculating
flue gases.
Protective Covering
cover the distributor tubing keep distributor tubes from contacting each other and wearing out.
Built-in Hail Guard
from the vertical are inherently protected from damage due to
shipment, hail, etc.
Induced Draft Furnace
exhaust of all combustion products.
- Millennium units stand only 64” above their
- Each gas unit ships with a field
- Special polyurethane sleeves which
- Condenser coils angled at 30 degrees
- This design provides a positive
Johnson Controls Unitary Products7
246653-YTG-E-0108
LIST OF FEATURES AND BENEFITS
Standard Features
•9.5 EER (10 EER on 25 ton)
•Double wall construction
•Major components have hinged and latched access
doors
•Industrial duty scroll compressors
•Sturdy framed construction
•Sloped stainless steel or powder coated drain pan
•Separate 10 ton circuits (30 and 40 ton units) or 12.5 ton
(25 ton unit)
•Intertwined evaporator coil
•Angled condenser coils for superior protection
•Single power point connection
•Through-the-curb or through-the-base utility connections
•Retractable outside air hoods
•Powder paint tested to 1000 salt spray hours
•Mechanical cooling from 40° F to 125° F
•1-1/2” insulation
•Sloped unit roof with drip lip
•High and low refrigerant pressure protection
•Polyurethane sleeves to protect small diameter tubing
•Steel framing around blowers with deflection springs or
rubber isolators for low vibration
•Fully factory packaged and run-tested
•10 year gas heat exchanger warranty
•One year compressor warranty
•One year warranty on all parts
Factory Installed Options
•Economizer with standard or low leak dampers
•Natural gas standard or modulating gas heat with reliable induced draft design
•Electric heat in three sizes
•Variable air volume using either inlet guide vanes, wired
for VFD (variable frequency drive), or factory installed
VFD.
•1, 2” blower isolator springs or rubber isolators
•A variety of blower horsepower offerings
•High efficiency motors
•High efficiency filtration
•Barometric relief
•Power exhaust of 100% of nominal air flow
•Technicoat corrosive resistant coating on condenser and
evaporator coils
•Copper-Copper corrosive resistant condenser and evaporator coils
•0°F low ambient operation of mechanical cooling
•Hot gas bypass (standard on all VAV units)
•High capacity evaporator coils
•Single unit disconnect
•Convenience outlet and transformer factory wired
•Hot water heating coil with one or two rows
•One row steam heating coil
•Simplicity
®
Elite™ controls
•ModLINC translator
•York Commercial Comfort System (YCCS)
Field Installed Accessories
•7-Day Programmable Wall Thermostat-Can be used with
or without remote sensors. Can be used on CV and VAV
units when wall thermostat is required for scheduling and
temperature control.
•Energy Recovery Ventilators- 8,000 and 13,000 CFM
models available. Great for applications involving 30% or
more of required outdoor air where energy use and comfort must be optimized.
•Wall Sensors- Remote space sensors used with CV or
VAV unit for unit control via the Simplicity® Elite™ control. Standard sensor, sensor with override and sensor
with override and + 5 degree adjustment.
•Simplicity® Transporter- Device allows internet control
and monitoring of HVAC units equipped with Simplicity®
Elite™ controls.
•Phase Monitor Kit- Includes control and wiring to monitor
and protect the unit from phase reversal, phase loss and
low voltage.
•Burglar Bars- Prevent any type of building entry through
the RTU unit with bars that block the return and supply
openings on downflow applications.
•Partial perimeter roofcurb- Designed for application on
all 25-40 ton Millennium rooftop units. 14" height.
•Barometric Relief Kit- Provides barometric relief hood
and dampers for duct mounting on units requiring end
return.
•Natural Gas to Propane Conversion Kits- Contains orifices and gas valves parts to convert from Natural Gas to
Propane. (Not available on modulating heat.)
•High Altitude Kit- Natural gas kit designed for natural gas
heating applications between 2,000 and 6,000 feet
above sea level.
8Johnson Controls Unitary Products
NOMENCLATURE
R
W = 1,4,0,7
A = 1,3,5,7
L = 2,4,5,8
OPTIONS
ADDITIONAL
CONFIGURATION
123 4
14
D
13
A
12
C
CONTROL
Cu/Cu Condenser Coil
Cu/Cu Evaporator Coil
Exhaust VFD (Customer)
(see notes 3 & 7)
* Premium Cabinet (6 doors)
* Standard Cabinet (4 doors)
* Drain Pan - powder coat
D = SYNTHESYS CONTROL
E = SYNTHESYS CONTROL,
110V OUTLET
J = SIMPLICITY CONTROL,
F = SYNTHESYS, DISC.
H = SIMPLICITY CONTROL
I = SIMPLICITY CONTROL, DISC
DISC., 110V OUTLET
make selections
must
in these options
* Drain Pan - stainless steel
*
DISC, 110V OUTLET
DISC, NO 110V OUTLET
K = SIMPLICITY CONTROL W/MODLINC
L = SIMPLICITY CONTROL W/ MODLINC
M = SIMPLICITY CONTROL W/MODLINC
DISC, NO 110V OUTLET
N = YCCS CONTROL
P = YCCS CONTROL W/DISC., 110V OUTLET
Q = YCCS ZONING CONTROL
R = YCCS ZONING CONTROL W/DISC.,
110V OUTLET
ECONOMIZER
S = YCCS - VAV CONTROL
T = YCCS - VAV CONTROL W/DISC.,
110V OUTLET
D = MANUAL Low leak (Not w/PE)
A = DUAL ENTH Low leak type
B = SINGLE ENTH Low leak type
C = DRY BULB ENTH Low leak type
(See note 5)
EXHAUST
E = NONE
F = DUAL ENTH Std type
G = SINGLE ENTH Std type
H = DRY BULB Std type
A = BAROJ = 2, 5S = A, 3
B = 1, 3K = 2, 6T = A, 4
C = 1, 4L = 2, 7U = A, 5
D = 1, 5M = 2, 8V = A, 6
E = 1, 6N = NONEW = A, 7
F = 1, 7O = 1, 9X = A, 8
G = 1, 8P = 1, 0Y = A, 9
3 = 13,000 CFM ERV
9 = Non Std Config
H = 2, 3Q = 2, 9Z = A, 0
I = 2, 4R = 2, 02 = 8,000 CFM ERV
246653-YTG-E-0108
MOTOR
Motor
Power Exhaust
1 = MODULATING DAMPERS A = VFD MODULATING
2 = NON-MOD. (ON/OFF)
0 = 5 HP HI-EFF (25T Only) 9 = 5 HP (25T Only)
3 = 7.5 HP6 = 7.5 HP HI-EFF
4 = 10 HP7 = 10 HP HI-EFF
5 = 15 HP (Except 25 Ton)8 = 15 HP HI-EFF (Except 25 Ton)
2.Reference Cooling Capacity Table for a 40 ton unit with
standard evaporator coil.
a.Locate the table for a standard evaporator coil with
95° F air on the condenser.
b.Enter table at 13,000 CFM and 67°F WB air on
evaporator
c.Trace to 83° F Entering Dry Bulb column.
d.Read 493 MBH total capacity and 403 MBH sensi-
ble capacity.
The 40 ton unit will meet the cooling requirements. From
the nomenclature, the unit will be a Y34. Choose the
appropriate configuration for the next digit. Assuming
bottom return and supply, the fourth digit would be an
“A,” making the model Y34A.
3.Find Gas Heating Capacity Table.
a.Trace down Output column.
b.Find output which exceeds 320,000 Btuh require-
ment. The N5 option gives 426 MBH output.
c.Ensure that it is offered in the Y34 unit. Read option
model as N5.
From the basic nomenclature, the model now becomes
Y34AN5. Add voltage code of “4” for 460-3-60. Nomenclature becomes Y34AN54.
SELECT FAN SPEED AND HORSEPOWER
REQUIREMENTS OF SUPPLY AIR FAN
1.Find Supply Air Performance Tables for the 40 ton unit.
a.Check footnotes and make necessary additions or
Total Static Resistance2.0 IWG
b.Enter Fan Performance Table at 13,000 CFM and
2.0 IWG static pressure:
RPM = 690
BHP = 10.7
NOTE: Either a Class I or Class II blower could be used.
c.Enter the Fan Motor Drive Tables. Selecting a 15 hp
motor allows (service factor of 1.5) for a maximum
operating BHP greater than the 10.7 BHP requirement.
SIZE OVERCURRENT PROTECTION DEVICE AND
DETERMINE CIRCUIT AMPACITY
1.Find electrical tables for the basic 40 ton unit.
a.Enter table for 460-3-60 voltage.
b.Find 15 hp in the Suppl y Air Fan column.
c.Trace to Minimum Circuit Ampacity column - read
104.
d.Trace to Max. Fuse/Breaker Size column - read 110.
e.Size wire and overprotection device accordingly.
f.Check all footnotes.
Heating capacity is only staged on CV models. VAV models use only one stage at full capacity.
3.
For 208 volts, multiply kW and MBH values by .751. For 230 volts, multiply kW and MBH values by .918
4.
For 460 volts, multiply kW and MBH values by .918.
AVAILABLEON MODELSRATED VOLTAGE
3
/4804/575
2
/4803/575802734013740136
3
/5751083697224636123
NOMINAL
KW
401374013700
N
OMINAL
MBH
1
MBH
S
TAGE 1STAGE 2
KWMBHKWMBH
Johnson Controls Unitary Products13
2
246653-YTG-E-0108
HOT WATER HEATING
1
The YORK Millennium Rooftop units (30 - 40 Ton sizes) can
be furnished with a YORK hot water coil as the source of heat
(Bottom Supply Only). A one or two row coil will be factory
installed in the heating section downstream of the supply air
fan and just above the supply air opening in the bottom of the
unit.
The hot water control valve will not be provided. The installer
will need to field supply a water valve. The installer must also
connect the hot water piping, and valve wiring at th e job site
for the hot water heat section to be operational.
For all hot water coils the enteri ng water temperature should
not exceed 200°F.
IR PRESSURE DROP 1 ROW0.070.110.160.32
IR PRESSURE DROP 2 ROW0.140.230.330.65
A
CFM 600080001000015000
DO NOT use tin based solder. Brazing with tin
based solder could cause equipment damage or
possible injury to OCCUPANTS of the structure
that is being conditioned.
Based on 60°F entering air temperature, 2.00” maximum pressure drop across the hot water coil.
C
140 °F160 °F180 °F200 °F
EMPERATURE
T
PIPING CONNECTIONS
The hot water piping must enter the unit through the floor of
the heat section compartment. The access doors to the compartment are gasketed so the compartment can be sealed.
However, as added protection for water leakage into the
space, the piping access holes should be sealed with a heat
resistant mastic (see the following illustration for approximate
location of the compartment and piping connections.
NOTE: Water pressure drop numbers are based on 60°F
entering air temperature, 2.00” maximum air pressure drop across the hot water coil(s). ARI certified
ratings at covering other conditions are available
upon request. Hot water coils are approved for use
with glycol (rates available upon request).
1. Hot water, steam or electric heat is not available for
front or rear supply.
NOTE: Water pressure drop numbers are based on 60°F
entering air temperature, 2.00” maximum air pressure drop across the hot water coil(s). ARI certified
ratings at covering other conditions are available
upon request. Hot water coils are approved for use
with glycol (rates available upon request.)
Based on 60°F entering air temperature, 2.00” maximum air
pressure drop across the hot water coil.
ARI certified ratings at other conditions available upon request.
Hot water coils are approved for use with glycol (ratings available upon request).
FIGURE 17 - HOT WATER COIL - 40 TON, 2 ROW, AT 80 GPM
24Johnson Controls Unitary Products
246653-YTG-E-0108
STEAM HEATING
The YORK Millennium units (25, 30, and 40 ton sizes) can be
manufactured with a steam heat coil (Bottom Supply only).
YORK's one row steam coil is installed in the heating section
just downstream of the supply air fan and just above the supply air opening in the bottom of the unit.
The steam control valve will not be provided. The installer
will need to field supply a steam control valve. Connect the
steam piping and valve power wiring at the job site for th e
steam heat section to be operational.
There are no provisions in the coil or control sequence to prevent freezing of condensate. The control val ve, piping and
field installed wiring connections are particularly vulnerable
because they are installed in the vestibule outside of the conditioned air stream.
All piping, control valves, and wiring that is field installed must
conform to all local and national codes
Condensate can freeze on the control valve and piping if they
are not properly insulated.
The steam piping must enter the unit through the floor of the
heat section compartment. The access doors to the compartment are gasketed to the compartment can be sealed. However, as added protection for condensate leakage into the
space, the piping access holes should be sealed with a heat
resistant mastic. The following figure illustrates the approximate location of the compartment and piping connections.
Based on 60°F entering air temperature, 2.00” maximum air
pressure drop across the coil.
C
261015
1
FIGURE 18 - STEAM PIPING CROSS SECTION
DO NOT use tin based solder. Brazing with tin
based solder could cause equipment damage or
possible injury to OCCUPANTS of the structure that
is being conditioned.
kW = (BHP X 0.746) / Motor Eff.
MBH = kW X 3.414
MBH = (BHP X 2.546) / Motor Eff.
NOTES: 1) Class I Blowers are limited to 15 HP motors on 25 and 30 Ton units.
2) Class I Blowers are limited to 20 HP motors on the 40 Ton units.
3) Class II Blowers are not HP limited, can use 25 HP.
MOTORMOTOR PULLEY BLOWER PULLEYBELTS
M
MOTOR
FFICIENCY
E
TD. MOTOR)
(S
OTOR
E
FFICIENCY
LTRA HI
(U
FF OPT)
E
1
ITCH DIA
P
NCHES)
(I
B
ORE
NCHES)
(I
P
ITCH DIA
NCHES)
(I
B
ORE
NCHES)
(I
D
ESIGNA
TION
QTY
Johnson Controls Unitary Products27
246653-YTG-E-0108
SUPPLY AIR DRIVE ADJUSTMENT
At unit start-up, the measured CFM may be higher or lower
than the specified CFM shown in Figures 22, 23, and 24. To
achieve the specified CFM, the speed of the drive may have
to be decreased or increased by changing the pitch diameter
(PD) of the motor sheave as outlined below:
Failure to properly adjust the total system air quantity can result in extensive blower damage.
Before making any blower speed changes review
the installation for any installation errors, leaks or
undesirable systems effects that can result in loss
of air flow.
Even small changes in blower speed can result in
substantial changes in static pressure and bhp.
Bhp or amp draw of the blower motor will increase
(see table) by the cube ratio of the blower speed.
Static pressure will increase by the square ratio of
the blower speed. Tables 26, 27 and 28 are for
reference only. All blower speed changes must be
made by qualified personnel with strict adherence
to the fan laws.
Example:
A 30-ton unit was selected to deliver 12,000 CFM with a 20
HP motor and a 856 RPM drive, but the unit is only delivering
11,000 CFM per Figure 23.
Use the equation to determine the required PD for the new
motor sheave (12,000 CFM / 11,000 CFM) x 6.7” = 7.31”.
Use the 30-ton table to select a Browning 2B5V74 which will
increase the speed of the unit's drive and its supply air CFM
109%.
New drive speed = 1.091 x 856 = 933 RPM
New supply air = 1.091 x 11,000 = 12,000 CFM
Re-use the existing belts and blower sheave.
New motor BHP = (speed increase)3 x estimated motor
BHP at original start-up with 11,000 CFM and 856 RPM =
(1.091)3 x 11.0 BHP = 1.2986 x 11.0 BHP = 14.3 BHP
New motor amps = (speed increase)3 x measured motor
amps at original start-up with 11,000 CFM and 856 RPM.
28Johnson Controls Unitary Products
246653-YTG-E-0108
TABLE 26: 25 TON DRIVE ADJUSTMENT
7.5 HP MOTOR & 567 RPM DRIVE10 HP MOTOR & 692 RPM DRIVE15 HP MOTOR & 793 RPM DRIVE20 HP MOTOR & 894 RPM DRIVE