York Y32, Y34, Y33 User Manual

Y
TOMORROW’S UNIT TODAY
246653-YTG-E-0108
TECHNICAL GUIDE
MILLENNIUM SINGLE PACKAGE ROOFTOP UNITS
25, 30, & 40 TON
25 TON (10 EER) 30 & 40 TON (9.5 EER)
®
30 TON UNIT SHOWN
®

GENERAL

Introducing the YORK Millennium 25, 30, & 40 ton rooftop line - units designed to provide peak performance and value both today and for years to come. Millennium units are manu­factured at an ISO 9001 registered facility, and each rooftop is completely computer-run tested prior to shipment.
The Millennium is designed to be flexible enough to meet your needs today and in the future. The true value of YORK’s Millennium is that it can be designed to fit any need, from cooling only, constant volume applications to variable air vol­ume systems with variable frequency drive.

FEATURING:

Cooling Only Units
Cooling/Gas Heating Units (Natural) Standard or Modulating Gas Heat available
Cooling/Electric Heating Units
Cooling/Hot Water Heating Units
Cooling/Steam Heating Units
Industry Leading Efficiency
Double Wall Construction
Stainless Steel or Powder Coated Drain Pan
Multiple Scroll Compressors
Multiple Refrigeration Circuits
Upgradable Motor Efficiency
Enhanced Filtration
Vibration Isolated Supply Fan and Motor
Technicoated Evaporator and Condenser Coils
High Capacity Evaporator Coils
Single Power Point Connection
Easy Access Hinged Doors
Variable Air Volume
Constant Air Volume
Factory Installed Economizers/Disconnect/Convenience Outlet/Control Options
•Low Profile

MILLENNIUM SIMPLICITY® ELITE™ FEATURES:

Single Button Programming and LED Display
Designed to operate on both constant and variable air volume units
365-Day real time clock with automatic Daylight Savings time adjustment
Occupancy Schedule allowing two schedules per day
20 Holiday schedules with programmable schedules that can start at any time, day or night
Patented Comfort Ventilation operation for economical and comfortable economizer operation
ISO 9001
Certified Quality
Management System
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
Demand Ventilation option to assure proper IAQ condi­tions based on available space or return air CO
Temperature/Humidity programming algorithm allows programmable limits to help control humidity in the space
Smoke Purge automatically ventilates the space when smoke is detected
Monitors dirty filters and proves airflow before starting heating or cooling
Intelligent recovery to bring the space temperature up to occupied setting quicker and more economically
levels
2
246653-YTG-E-0108
TABLE OF CONTENTS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
FEATURING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
MILLENNIUM SIMPLICITY® ELITE™ FEATURES . . . . .1
OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
FEATURES AND BENEFITS . . . . . . . . . . . . . . . . . . . . . . .5
INSTALLATION FEATURES . . . . . . . . . . . . . . . . . . . . . . 6
CONSTRUCTION FEATURES . . . . . . . . . . . . . . . . . . . .7
LIST OF FEATURES AND BENEFITS . . . . . . . . . . . . . . .8
STANDARD FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . 8
FACTORY INSTALLED OPTIONS . . . . . . . . . . . . . . . . . . 8
FIELD INSTALLED ACCESSORIES . . . . . . . . . . . . . . . . . 8
NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
SELECTION PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . .11
SELECT UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
SELECT FAN SPEED AND HORSEPOWER
REQUIREMENTS OF SUPPLY AIR FAN . . . . . . . . . . .11
SIZE OVERCURRENT PROTECTION DEVICE AND
DETERMINE CIRCUIT AMPACITY . . . . . . . . . . . . . . . .11
HOT WATER HEATING . . . . . . . . . . . . . . . . . . . . . . . . . .14
PHYSICAL DATA HOT WATER COIL - 1 ROW . . . . . . 14
PIPING CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . .14
PHYSICAL DATA HOT WATER COIL - 2 ROW . . . . . . 20
STEAM HEATING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
PHYSICAL DATA STEAM COIL - 1 ROW . . . . . . . . . . . 25
PIPING CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . .25
SUPPLY AIR DRIVE ADJUSTMENT . . . . . . . . . . . . . . . .28
CFM, STATIC PRESSURE, AND POWER - ALTITUDE
AND TEMPERATURE CORRECTIONS . . . . . . . . . . . . 44
GUIDE SPECIFICATIONS - YORK
MILLENNIUM 25, 30, & 40 TON UNITS . . . . . . . . . . . . . . 89
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89
CONSTRUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89
BASE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
CASING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
SUPPLY AIR SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . .89
SUPPLY AIR FAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
OPTIONAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
BEARINGS AND DRIVES . . . . . . . . . . . . . . . . . . . . . . .89
AIR FILTERING SYSTEM . . . . . . . . . . . . . . . . . . . . . . .90
OPTIONAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
AIR INLET SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . .90
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
ECONOMIZER (OPTIONAL) . . . . . . . . . . . . . . . . . . . . . . 90
RELIEF SYSTEM (OPTIONAL) . . . . . . . . . . . . . . . . . . . . 90
BAROMETRIC RELIEF (OPTIONAL) . . . . . . . . . . . . . . . 90
EXHAUST AIR FANS (OPTIONAL) . . . . . . . . . . . . . . . . 90
ENERGY RECOVERY VENTILATION
(FIELD INSTALLED OPTION) . . . . . . . . . . . . . . . . . . . . 90
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
HEATING SYSTEM (OPTIONAL) . . . . . . . . . . . . . . . . . 90
GAS-FIRED HEATING SECTION . . . . . . . . . . . . . . . . . . 90
ELECTRIC HEATING SECTION . . . . . . . . . . . . . . . . . . . 91
HOT WATER HEATING COIL . . . . . . . . . . . . . . . . . . . . . 91
STEAM HEATING COIL . . . . . . . . . . . . . . . . . . . . . . . . . 91
REFRIGERATION SYSTEM . . . . . . . . . . . . . . . . . . . . . 91
EVAPORATOR COILS . . . . . . . . . . . . . . . . . . . . . . . . . . 91
COMPRESSORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
CONDENSER COILS . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
CONDENSER FANS AND MOTORS . . . . . . . . . . . . . . . 92
REFRIGERANT PIPING . . . . . . . . . . . . . . . . . . . . . . . . . 92
HOT GAS BYPASS (OPTIONAL ON CV; STANDARD
ON VAV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
GENERAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . 92
COMPRESSOR CONTROL . . . . . . . . . . . . . . . . . . . . . . 92
FAN CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
EQUIPMENT CONTROL FEATURES . . . . . . . . . . . . . . 93
COMFORT CONTROL FEATURES . . . . . . . . . . . . . . . 93
OPTIONAL COMMUNICATION TRANSLATOR . . . . . . 94
OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
OPTIONAL CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . 95
YORK COMMERCIAL COMFORT SYSTEM (YCCS) . . . 95
AVAILABLE ACCESSORIES . . . . . . . . . . . . . . . . . . . . . 95
PARTIAL PERIMETER ROOF CURBS . . . . . . . . . . . . . . 95
BURGLAR BARS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
FIELD INSTALLED BAROMETRIC RELIEF . . . . . . . . . . 95
PROGRAMMABLE THERMOSTAT, WITH OR WITHOUT REMOTE SENSOR (REQUIRED FOR CONSTANT
VOLUME UNITS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
REMOTE WALL MOUNTED TEMPERATURE
SENSORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
DIRTY FILTER SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . 95
PROPANE CONVERSION KITS . . . . . . . . . . . . . . . . . . . 95
HIGH ALTITUDE CONVERSION KITS . . . . . . . . . . . . . . 95
ENERGY RECOVERY VENTILATORS . . . . . . . . . . . . . 95
2 Johnson Controls Unitary Products
LIST OF FIGURES
246653-YTG-E-0108
Fig.# Pg.#
1 HOT WATER PIPING CROSS-SECTION . . . . . . . . . 15
2 HOT WATER COIL - 25 & 30 TON, 1 ROW,
AT 10 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3 HOT WATER COIL - 25 & 30 TON, 1 ROW,
AT 20 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4 HOT WATER COIL - 25 & 30 TON, 1 ROW,
AT 30 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5 HOT WATER COIL - 25 & 30 TON, 1 ROW,
AT 40 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6 HOT WATER COIL - 40 TON, 1 ROW,
AT 10 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
7 HOT WATER COIL - 40 TON, 1 ROW,
AT 20 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
8 HOT WATER COIL - 40 TON, 1 ROW,
AT 30 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
9 HOT WATER COIL - 40 TON, 1 ROW,
AT 40 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
10 HOT WATER COIL - 25 & 30 TON, 2 ROW,
AT 20 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
11 HOT WATER COIL - 25 & 30 TON, 2 ROW,
AT 40 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
12 HOT WATER COIL - 25 & 30 TON, 2 ROW,
AT 60 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
13 HOT WATER COIL - 25 & 30 TON, 2 ROW,
AT 80 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
14 HOT WATER COIL - 40 TON, 2 ROW, AT 20 GPM. . 23 15 HOT WATER COIL - 40 TON, 2 ROW, AT 40 GPM. . 23 16 HOT WATER COIL - 40 TON, 2 ROW, AT 60 GPM. . 24 17 HOT WATER COIL - 40 TON, 2 ROW, AT 80 GPM. . 24
Pg.#
Fig.#
18 STEAM PIPING CROSS SECTION . . . . . . . . . . . . . . 25
19 STEAM COIL - 25 & 30 TON, 1 ROW . . . . . . . . . . . . 26
20 STEAM COIL - 40 TON, 1 ROW . . . . . . . . . . . . . . . . 26
21 ALTITUDE/TEMPERATURE CONVERSION
FACTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
22 FAN PERFORMANCE - 25 TON . . . . . . . . . . . . . . . . 47
23 FAN PERFORMANCE - 30 TON . . . . . . . . . . . . . . . . 49
24 FAN PERFORMANCE - 40 TON . . . . . . . . . . . . . . . . 51
25 POWER EXHAUST - ONE FORWARD CURVE
FAN - 25 TONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
26 POWER EXHAUST - TWO FORWARD CURVED
FANS - 30 & 40 TONS . . . . . . . . . . . . . . . . . . . . . . . . 60
27 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . 78
28 COMPONENT LOCATION . . . . . . . . . . . . . . . . . . . . 80
29 END RETURN, BOTTOM SUPPLY . . . . . . . . . . . . . . 81
30 BOTTOM SUPPLY AND RETURN . . . . . . . . . . . . . . 82
31 BOTTOM RETURN, FRONT & REAR SUPPLY . . . . 83
32 END RETURN, FRONT & REAR SUPPLY . . . . . . . . 84
33 MILLENNIUM OVERHEAD VIEW . . . . . . . . . . . . . . . 85
34 MILLENNIUM MAJOR COMPONENT LAYOUT . . . . 85
35 MILLENNIUM CABINET DOOR CONFIGURATION . 86 36 CLEARANCES - HOOD/ECONOMIZER & MOTOR
DRIVE - SIDE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
37 CLEARANCES - HOOD/ECONOMIZER & MOTOR
DRIVE - FRONT & END . . . . . . . . . . . . . . . . . . . . . . 87
38 PARTIAL ROOF CURB MODEL 1RC0455P . . . . . . . 88
Johnson Controls Unitary Products 3
246653-YTG-E-0108
LIST OF TABLES
Tbl.# Pg.#
1 GENERAL PHYSICAL DATA . . . . . . . . . . . . . . . . . . .10
2 REFRIGERANT CHARGE . . . . . . . . . . . . . . . . . . . . .11
3 STANDARD GAS HEATING CAPACITIES . . . . . . . .12
4 TEMPERATURE RISE . . . . . . . . . . . . . . . . . . . . . . . .1 2
5 MINIMUM HEATING CFM . . . . . . . . . . . . . . . . . . . . .12
6 MODULATING GAS HEATING CAPACITIES . . . . . .12
7 MODULATING HEAT . . . . . . . . . . . . . . . . . . . . . . . . .13
8 ELECTRIC HEATING CAPACITIES . . . . . . . . . . . . . . 13
9 WATER PRESSURE DROP (1 ROW,
25 & 30 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
10 STATIC RESISTANCE HOT WATER COIL
(25 & 30 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
11 HOT WATER COIL (1 ROW, 25 & 30 TON) . . . . . . . .14
12 STATIC RESISTANCE HOT WATER COIL
(1 ROW, 40 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
13 HOT WATER COIL (1 ROW 40 TON) . . . . . . . . . . . .15
14 WATER PRESSURE DROP (2 ROW,
25 & 30 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
15 STATIC RESISTANCE HOT WATER COIL
(25 & 30 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
16 HOT WATER COIL (2 ROW, 25 & 30 TON) . . . . . . . .20
17 HOT WATER COIL (2 ROWS, 40 TON) . . . . . . . . . . .20
18 STATIC RESISTANCE HOT WATER COIL
(40 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
19 WATER PRESSURE DROP (2 ROW, 40 TON . . . . . 20
20 STEAM COIL (1 ROW, 25 & 30 TON) . . . . . . . . . . . .25
21 STATIC RESISTANCE STEAM COIL
(1 ROW, 25 & 30 TON) . . . . . . . . . . . . . . . . . . . . . . . .25
22 STEAM COIL (1 ROW, 40 TON) . . . . . . . . . . . . . . . .25
23 STATIC RESISTANCE STEAM COIL
(1 ROW, 40 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
24 EXHAUST FAN DRIVE DATA . . . . . . . . . . . . . . . . . .27
25 SUPPLY FAN MOTOR AND DRIVE DATA . . . . . . . .27
26 25 TON DRIVE ADJUSTMENT . . . . . . . . . . . . . . . . .29
27 30 TON DRIVE ADJUSTMENT . . . . . . . . . . . . . . . . .29
28 40 TON DRIVE ADJUSTMENT . . . . . . . . . . . . . . . . .29
29 DRIVE ADJUSTMENT FOR POWER EXHAUST
- 25 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
30 DRIVE ADJUSTMENT FOR POWER EXHAUST
- 30 & 40 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
31 COOLING PERFORMANCE 25 TON . . . . . . . . . . . . .31
32 COOLING PERFORMANCE 30 TON STANDARD
CAPACITY COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
33 COOLING PERFORMANCE 30 TON HIGH
CAPACITY COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Pg.#
Tbl.# 34 COOLING PERFORMANCE 40 TON STANDARD
CAPACITY COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
35 COOLING PERFORMANCE 40 TON HIGH
CAPACITY COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
36 ALTITUDE CORRECTION FACTORS . . . . . . . . . . . . 44
37 FAN PERFORMANCE - 25 TON . . . . . . . . . . . . . . . . 46
38 FAN PERFORMANCE - 30 TON . . . . . . . . . . . . . . . . 48
39 FAN PERFORMANCE - 40 TON . . . . . . . . . . . . . . . . 50
40 FAN PERFORMANCE - 25 & 30 TON AIRFOIL. . . . . 52
41 FAN PERFORMANCE - 40 TON AIRFOIL . . . . . . . . . 54
42 COMPONENT STATIC RESISTANCE. . . . . . . . . . . . 56
43 POWER EXHAUST - ONE FORWARD CURVED
FAN 25 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
44 POWER EXHAUST - TWO FORWARD CURVED
FANS - 30 & 40 TON . . . . . . . . . . . . . . . . . . . . . . . . . 59
45 ELECTRICAL DATA 25 TON BASIC UNIT R22 . . . . 61
46 ELECTRICAL DATA 30 TON BASIC UNIT R22 . . . . 61
47 ELECTRICAL DATA 40 TON BASIC UNIT R22 . . . . 62
48 ELECTRICAL DATA 25 TON WITH ELECTRIC
HEAT R22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
49 ELECTRICAL DATA 30 TON WITH ELECTRIC
HEAT R22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
50 ELECTRICAL DATA 40 TON WITH ELECTRIC
HEAT R22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
51 ELECTRICAL DATA 25 TON WITH POWER
EXHAUST R22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
52 ELECTRICAL DATA 30 TON WITH POWER
EXHAUST R22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
53 ELECTRICAL DATA 40 TON WITH POWER
EXHAUST R22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
54 ELECTRICAL DATA 25 TON WITH ELECTRIC HEAT
AND POWER EXHAUST R22 . . . . . . . . . . . . . . . . . . 69
55 ELECTRICAL DATA 30 TON WITH ELECTRIC HEAT
AND POWER EXHAUST R22 . . . . . . . . . . . . . . . . . . 72
56 ELECTRICAL DATA 40 TON WITH ELECTRIC HEAT
AND POWER EXHAUST R22 . . . . . . . . . . . . . . . . . . 75
57 UNIT WEIGHTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
58 SUPPLY FAN MOTOR VFD WEIGHTS . . . . . . . . . . . 78
59 EXHAUST FAN MOTOR VFD WEIGHTS . . . . . . . . . 78
60 UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . 78
61 UNIT CORNERWEIGHT . . . . . . . . . . . . . . . . . . . . . . 79
62 INDOOR SOUND POWER RATING . . . . . . . . . . . . . 79
63 ATTENUATION FACTORS . . . . . . . . . . . . . . . . . . . . 79
64 OUTDOOR SOUND POWER RATING . . . . . . . . . . . 79
4 Johnson Controls Unitary Products
246653-YTG-E-0108
YORK Millennium

OVERVIEW

Introducing the YORK Millennium 25, 30, & 40 ton rooftop line - units designed to provide peak performance and value both today and for years to come. When we aske d our cus­tomers what they wanted in a new rooftop line, we were care­ful to listen to both the needs of today and tomorrow. So, you'll find that Millennium units not only help you solve today's problems, but can handle tomorrow's difficulties as well:
Industry Leading Efficiency EER 25 ton) rating makes it the most frugal energy consumer in its class. When it comes to lower operating costs, Millen­nium simply outperforms the competition.
Double Wall Construction walled as standard. The galvanized sheet metal liner pro­vides the best protection against microbial growth, helping both the unit and the indoor air stay fresh and clean. And, the rigid sheet metal inner liner keeps the insulation completely out of the air stream, eliminating concerns about fiberglass particles.
Drain Pan Whisks Away Condensate quently the source of microbial contamination. Competitive drain pans often are insufficiently sloped to properly drain all of the condensate, causing drain pan corrosion and bacterial growth to begin almost immediately. The YORK design is sloped at the 1/4” per foot recommended by the ASHRAE
62.1-2004 ventilation draft standard, with an extra large drain connection capable of removing up to three gallons of con­densate per minute. It is available in either powder coat painted steel or stainless steel for long life.
- The Millennium's 9.5 EER (10
- Millennium units come double
- Condensate is fre-
®
Efficient, Durable Scroll Compressors design uses industrial grade hermetic scroll compressors for peak efficiency and low noise operation. The compressor design is so durable that it can actually hold more liquid charge without slugging than is present in each refrigerant circuit at shipment, dramatically reducing the chances of ever slugging a compressor with liquid charge.
Multiple Refrigeration Circuits for Greater Turndown YORK Millennium unit has intertwined 10 ton circuits (12.5 ton circuits on the 25 ton) - giving the best unloading capabil­ity in the industry. With more and more designs requiring higher outside air quantities, the lower capacity capability is an outstanding way to neutralize outside air without over-con­ditioning the space on off-peak days. And, Millennium's high quality balance-port thermal expansion valves are more effective at metering refrigerant flow in part-load conditions, making Millennium a peak-performer across a wide capacity range.
- The Millennium
- The

FEATURES AND BENEFITS

When it comes to flexibility, Millennium really shines. Our cus­tomers were clear about one thing - not all installations are the same. Some have very simple needs, others are more involved. The YORK Millennium serves both markets - and all of those in between - extremely well. YORK engineers crafted a design which is both uniquely flexible and competitive, giv­ing you the best of both worlds. In addition to a competitive base product, Millennium offers unparalleled flexibility. Optional features include:
Variable Air Volume volume by inlet guide vanes or variable frequency drive - the choice is yours. All Millennium VAV units come standard with hot gas bypass to give extended operation range.
- YORK gives you the ability to vary air
Johnson Controls Unitary Products 5
246653-YTG-E-0108
Optional Head Pressure Control - For those applications where mechanical cooling is required below 40°F, optional low ambient operation allows compressor operation down to 0°F.
Easily Upgrade Motor Efficiency to Meet Tighter Codes Optional high efficiency motors help you make simple upgrades to meet more demanding building and energy codes.
Enhanced Filtration Options
- Millennium gives designers the flexibility to meet various IAQ requirements with a full range of rigid and throwaway filters at different efficiency levels.
Vibration Isolation
- The Millennium's neoprene mounts are typically sufficient for most applications but when sound and vibration transmission are a major concern, YORK offers 1" and 2" isolation springs for even greater protection from sup­ply air fan noise and vibration.
Corrosion Resistant Coils
- Many industrial and seacoast applications require enhanced protection from corrosive envi­ronments.
Optional TechniCoated Coated Condenser and Evapo­rator Coils - Many industrial and seacoast applications require enhanced protection from corrosive environ­ments. The special dipped phenolic coating process provides a high level of protection for the exposed con­denser coil.
Optional Copper-Copper Condenser and Evaporator Coils - For corrosion resistance.
High Capacity Evaporator Coils
- For those applications which require slightly more capacity than offered by the stan­dard Millennium product, YORK offers the option of higher capacity evaporator coils, boosting cooling output without increasing unit size. (30 & 40 Ton R-22 only)
ers. Comparative enthalpy, single enthalpy and dry bulb con­trol are available.
Optional Factory Installed Disconnect
- A conveniently
located actuator handle in the front of the unit can disconnect
-
line power to the entire unit, eliminating the need for a field provided disconnect. The handle may also be locked in either position through the use of a standard padlock. Millennium's single point power connection makes this option particularly appealing. If desired, the disconnect may be ordered with a 115 volt, GFCI protected convenience outlet, including a fac­tory wired transformer to power the outlet from the single point power connection; the convenience outlet remains operational when the disconnect is open.
Heating Done Your Way
- Millennium offers the choice of nat­ural gas standard or modulating gas heat, electric resistance heat, hot water heat, steam, or no heat at all. Very simply, the choice is yours.

INSTALLATION FEATURES

With YORK Millennium, high performance doesn't mean high complexity. YORK listened carefully to make sure that Millen­nium was as simple as possible, and service convenience comes standard with each unit. From a single curb size to the easy service access, you'll find that Millennium was designed to be easy from start to finish.
Full Range of Air Flows and Static Pressures nium design gives a complete offering of supply air flows and static pressure combinations to meet most every application requirement.
Single Power Point Connection - Millennium units have a sin­gle gas and electric connection, minimizing time at the job site. For further installation flexibility, power and gas connec­tions may be brought up from the curb or through the side of the unit.
- The Millen-
Variety of Exhaust Air Options wide variety of exhaust air options, including barometric relief, non-modulating power exhaust, and modulating power exhaust. And, because Millennium units use forward-curved
- YORK Millennium offers a
Simple Controls
- Millennium's controls system is easy to understand and apply, and it doesn't lock you into proprietary devices. A choice for YORK Millennium today doe s not limit your choices tomorrow.
blowers for power exhaust fans, they can exhaust up to 100% of the nominal supply air at much greater static pressure loads than competitive units. Not available on end return.
Rain Hoods Rotate Into Place - No bulky, field--installed rain hoods here. Millennium rain hoods ship rotated inside the unit. Once on the job, installer merely rotates the hood
NOTE: In most applications, the supply fan will keep the
return at negative pressure. A barometric relief will function better when ducted to building space, not the return.
Optional Factory Installed Economizers
- Millennium units
offer economizers with Standard or Optional low leak damp-
6 Johnson Controls Unitary Products
upward and puts in a few screws - an easy one-person job. Excellent Access for Service
- Service access on Millennium is a snap. Hinged and latched door options give access on both sides of the unit to all major components. Some doors have positive action slide latches for even greater ease of access. All service fittings are conveniently located to mini­mize time and effort.
A
NGLED CONDENSER
COILS
246653-YTG-E-0108
PITCHED ROOF
SOLID, CLASS II FAN CONSTRUCTION
INTERTWINED COIL
DOUBLE WALL CONSTRUCTION
LOW LEAK DAMPERS

CONSTRUCTION FEATURES

YORK's Millennium rooftop line is built for the long haul, with high end features and construction offered at a competitive price. Millennium units are manufactured at an ISO 9001 reg­istered facility, and each rooftop is completely computer-run tested prior to shipment. Some of the valuable construction features of the Millennium which are not found on competitive units include:
Double Wall Construction and an interior wall, which make for a more rigid design with panels and doors that are solid, not flimsy. The unit features a fully framed construction for even greater stability.
Powder Paint keeps the unit in great condition for years to come.
- Industry leading 1000 salt spray hour paint
- Each unit has both an exterior
HINGED, LATCHED ACCESS DOORS
Low Profile curb, minimizing potential aesthetic conflicts.
Extended flue connection mounted external flue. The flue lifts all products of furnace combustion far above the unit - eliminating the possibility of corrosion in the furnace heat exchanger from recirculating flue gases.
Protective Covering cover the distributor tubing keep distributor tubes from con­tacting each other and wearing out.
Built-in Hail Guard from the vertical are inherently protected from damage due to shipment, hail, etc.
Induced Draft Furnace exhaust of all combustion products.
- Millennium units stand only 64” above their
- Each gas unit ships with a field
- Special polyurethane sleeves which
- Condenser coils angled at 30 degrees
- This design provides a positive
Johnson Controls Unitary Products 7
246653-YTG-E-0108

LIST OF FEATURES AND BENEFITS

Standard Features

9.5 EER (10 EER on 25 ton)
Double wall construction
Major components have hinged and latched access doors
Industrial duty scroll compressors
Sturdy framed construction
Sloped stainless steel or powder coated drain pan
Separate 10 ton circuits (30 and 40 ton units) or 12.5 ton (25 ton unit)
Intertwined evaporator coil
Angled condenser coils for superior protection
Single power point connection
Through-the-curb or through-the-base utility connections
Retractable outside air hoods
Powder paint tested to 1000 salt spray hours
Mechanical cooling from 40° F to 125° F
1-1/2” insulation
Sloped unit roof with drip lip
High and low refrigerant pressure protection
Polyurethane sleeves to protect small diameter tubing
Steel framing around blowers with deflection springs or rubber isolators for low vibration
Fully factory packaged and run-tested
10 year gas heat exchanger warranty
One year compressor warranty
One year warranty on all parts

Factory Installed Options

Economizer with standard or low leak dampers
Natural gas standard or modulating gas heat with reli­able induced draft design
Electric heat in three sizes
Variable air volume using either inlet guide vanes, wired for VFD (variable frequency drive), or factory installed VFD.
1, 2” blower isolator springs or rubber isolators
A variety of blower horsepower offerings
High efficiency motors
High efficiency filtration
Barometric relief
Power exhaust of 100% of nominal air flow
Technicoat corrosive resistant coating on condenser and evaporator coils
Copper-Copper corrosive resistant condenser and evap­orator coils
0°F low ambient operation of mechanical cooling
Hot gas bypass (standard on all VAV units)
High capacity evaporator coils
Single unit disconnect
Convenience outlet and transformer factory wired
Hot water heating coil with one or two rows
One row steam heating coil
Simplicity
®
Elite™ controls
ModLINC translator
York Commercial Comfort System (YCCS)

Field Installed Accessories

7-Day Programmable Wall Thermostat-Can be used with or without remote sensors. Can be used on CV and VAV units when wall thermostat is required for scheduling and temperature control.
Energy Recovery Ventilators- 8,000 and 13,000 CFM models available. Great for applications involving 30% or more of required outdoor air where energy use and com­fort must be optimized.
Wall Sensors- Remote space sensors used with CV or VAV unit for unit control via the Simplicity® Elite™ con­trol. Standard sensor, sensor with override and sensor with override and + 5 degree adjustment.
Simplicity® Transporter- Device allows internet control and monitoring of HVAC units equipped with Simplicity® Elite™ controls.
Phase Monitor Kit- Includes control and wiring to monitor and protect the unit from phase reversal, phase loss and low voltage.
Burglar Bars- Prevent any type of building entry through the RTU unit with bars that block the return and supply openings on downflow applications.
Partial perimeter roofcurb- Designed for application on all 25-40 ton Millennium rooftop units. 14" height.
Barometric Relief Kit- Provides barometric relief hood and dampers for duct mounting on units requiring end return.
Natural Gas to Propane Conversion Kits- Contains ori­fices and gas valves parts to convert from Natural Gas to Propane. (Not available on modulating heat.)
High Altitude Kit- Natural gas kit designed for natural gas heating applications between 2,000 and 6,000 feet above sea level.
8 Johnson Controls Unitary Products

NOMENCLATURE

R
W = 1,4,0,7
A = 1,3,5,7
L = 2,4,5,8
OPTIONS
ADDITIONAL
CONFIGURATION
123 4
14
D
13
A
12
C
CONTROL
Cu/Cu Condenser Coil
Cu/Cu Evaporator Coil
Exhaust VFD (Customer)
(see notes 3 & 7)
* Premium Cabinet (6 doors)
* Standard Cabinet (4 doors)
* Drain Pan - powder coat
D = SYNTHESYS CONTROL
E = SYNTHESYS CONTROL,
110V OUTLET
J = SIMPLICITY CONTROL,
F = SYNTHESYS, DISC.
H = SIMPLICITY CONTROL
I = SIMPLICITY CONTROL, DISC
DISC., 110V OUTLET
make selections
must
in these options
* Drain Pan - stainless steel
*
DISC, 110V OUTLET
DISC, NO 110V OUTLET
K = SIMPLICITY CONTROL W/MODLINC
L = SIMPLICITY CONTROL W/ MODLINC
M = SIMPLICITY CONTROL W/MODLINC
DISC, NO 110V OUTLET
N = YCCS CONTROL
P = YCCS CONTROL W/DISC., 110V OUTLET
Q = YCCS ZONING CONTROL
R = YCCS ZONING CONTROL W/DISC.,
110V OUTLET
ECONOMIZER
S = YCCS - VAV CONTROL
T = YCCS - VAV CONTROL W/DISC.,
110V OUTLET
D = MANUAL Low leak (Not w/PE)
A = DUAL ENTH Low leak type
B = SINGLE ENTH Low leak type
C = DRY BULB ENTH Low leak type
(See note 5)
EXHAUST
E = NONE
F = DUAL ENTH Std type
G = SINGLE ENTH Std type
H = DRY BULB Std type
A = BARO J = 2, 5 S = A, 3
B = 1, 3 K = 2, 6 T = A, 4
C = 1, 4 L = 2, 7 U = A, 5
D = 1, 5 M = 2, 8 V = A, 6
E = 1, 6 N = NONE W = A, 7
F = 1, 7 O = 1, 9 X = A, 8
G = 1, 8 P = 1, 0 Y = A, 9
3 = 13,000 CFM ERV
9 = Non Std Config
H = 2, 3 Q = 2, 9 Z = A, 0
I = 2, 4 R = 2, 0 2 = 8,000 CFM ERV
246653-YTG-E-0108
MOTOR
Motor
Power Exhaust
1 = MODULATING DAMPERS A = VFD MODULATING
2 = NON-MOD. (ON/OFF)
0 = 5 HP HI-EFF (25T Only) 9 = 5 HP (25T Only)
3 = 7.5 HP 6 = 7.5 HP HI-EFF
4 = 10 HP 7 = 10 HP HI-EFF
5 = 15 HP (Except 25 Ton) 8 = 15 HP HI-EFF (Except 25 Ton)
11
A
10
A
9
1
8
B
7
4
6
3
5
N
4
A
3
3
2
3
1
Y
FILTERS
A = STAND.
VOLTAGE
2 = 208/230-60
PACKAGE
Y = York Brand R22
B = 65%
C = 95%
D = 2" HI-EFF
3 = 380-60
4 = 460-60
5 = 575-60
minimum efficiency regulations mandated
1. 108KW not available with 208/230V.
2. Standard efficiency motor meets Canadian
NOTES:
(See note 4)
(30T/40T)
ID BLOWER
7 = 380/415-50
A = a, f, i L = d, g, j W = d, e, j
B = a, g, i M = b, f, i X = d, f, h
BASIC UNIT
GENERATION
3 = 30 TON
4 = 40 TON
2 = 25 TON
in Canadian Energy Efficiency Regulations.
only; VFD will be customer supplied and
field installed. If VFD Exh is also
specified, it will also be cust supplied.
3. (VFD-CUSTOMER) = Wired for VFD
C = a, f, j N = b, f, j Y = b, e, h
D = a, g, j O = b, g, i Z = b, e, i
CONFIGURATION
A = 1,2 1 - BOTTOM RETURN
available in end return configuration.
4. VAV ID Blower requires hot gas bypass .
5. Power exhaust and barometric relief not
E = a, e, h P = b, g, j 2 = b, e, j
F = a, e, i Q = c, f, i 3 = b, f, h
G = a, e, j R = c, f, j 4 = c, e, h
H = a, f, h S = c, g, i 6 = c, e, i
I = d, f, i T = c, g, j 7 = c, e, j
(5)
3 - END RETURN
B = 1,4 2 - BOTTOM SUPPLY
C = 1,5
D = 3,2 4 - REAR SUPPLY
E = 3,4 5 - FRONT SUPPLY
F = 3,5
REFRIGERATION
Contact engineering for
air foil applications.
6. Air foil fan available on cooling only.
7. Only available with Hi EFF motors
9 = d, g, h
J = d, f, j U = d, e, h 8 = c, f, h
K = d, g, i V = d, e, i
(3)
Air Volume
d = VAV (VFD-CUSTOMER)
a = CV
b = VAV (VFD-FACTORY INSTALLED)
c = BYPASS FACTORY VFD
HEAT SOURCE
FRONT SUPPLY - COOLING ONLY
HOT WATER, STEAM & ELECTRIC HEAT -
N = NATURAL GAS
BOTTOM SUPPLY ONLY
GAS HEAT - BOTTOM OR REAR SUPPLY ONLY
Config
9 = Non-Std
E = 1,3,6,7 P = 2,4,6,8 2 = 2,4,9,8
F = 2,3,6,7 Q = 1,3,9,7 3 = 1,3,0,8
B = 2,3,5,7 M = 1,3,6,8 X = 2,4,0,7
C = 1,4,5,7 N = 2,3,6,8 Y = 1,3,9,8
D = 2,4,5,7 O = 1,4,6,8 Z = 2,3,9,8
Fan (See note 6)
e = FORWARD CURVE FAN Class I
f = FORWARD CURVE FAN Class II
g = AIR FOIL FAN [always Class II]
Class I blower is limited to 15HP in 25/30Ton
K = 1,4,5,8 V = 2,3,0,7
G = 1,4,6,7 R = 2,3,9,7 4 = 2,3,0,8
J = 2,3,5,8 U = 1,3,0,7 7 = 1,4,9,8
I = 1,3,5,8 T = 2,4,9,7 6 = 2,4,0,8
H = 2,4,6,7 S = 1,4,9,7 5 = 1,4,0,8
h = Neoprene
j = 2 inch deflection spring
i = 1 inch deflection spring
Class I blower is limited to 20HP in 40Ton
Class II blowers are not HP limited
Blower Mount
HEAT CAPACITY
X = STEAM COIL
3 = 267 MBH
W = HOT WATER COIL
C = COOLING ONLY
E = ELECTRIC HEAT
S = NATURAL GAS, SS HEAT EXCHANGER
HEAT EXCHANGE
T = NATURAL GAS, MODULATING HEAT, SS *
D = NATURAL GAS, MODULATING HEAT*
(See note 4)
Condenser Coil Head Press. Ctrl.
Piping
Evaporator Coil
3 = STANDARD 4 = HOT GAS BYPASS
2 = TECHNICOAT 8 = NO
5 = STANDARD
1 = STANDARD 7 = YES
(See note 2)
ID MOTOR
5 = 10 HI-EFF
1 = 10 HP STD
5 = 533 MBH
8 = 800 MBH (40T ONLY)
6 = 15 HI-EFF
2 = 15 HP STD
3 = 20 HP STD
4 = 25 HP STD (Except 25T)
(1)
0 (ZERO) NO HEAT
4 = 40 KW
8 = 80 KW
1 = 108 KW
1 = 1 ROW
0 = HI-CAP W/T-COAT (30T/40T R22)
6 = HI-CAP (30T/40T R22 ONLY)
9 = STD W/TECHNICOAT
7 = 20 HI-EFF
0 = 7.5 HI-EFF (25T Only)
8 = 25 HI-EFF (Except 25T)
9 = 7.5 HP STD (25T Only)
2 = 2 ROW
1 = 1 ROW
Johnson Controls Unitary Products 9
246653-YTG-E-0108

TABLE 1: GENERAL PHYSICAL DATA

UNIT SIZE 25 TON 30 TON 40 TON
U
NIT EER / IPLV
TANDARD CAPACITY EVAPORATOR)
(S
NUMBER/SIZE 2 x 12.5 Ton 3 x 10 T on 4 x 10 Ton
T
YPE Scroll Scroll Scroll
U
NIT CAPACITY STEPS 50%, 100% 33%, 67%, 100% 25%, 50%, 75%, 100%
NUMBER / TYPE 1 / FC 1 / FC 1 / FC
D
IAMETER X WIDTH (INCHES) 22 x20 22 x 20 25 x 22
ANGE 7.5 - 20 10 - 25 10 - 25
HP R
ANGE (FULL LOAD) 6,000 - 12,500 6,000 - 15,000 8,000 - 18,000
CFM R
ESP R
ANGE 0.2” - 4.0” 0.2" - 4.0” 0.2" - 4.0"
NUMBER/SIZE/TYPE 1/FC 2/FC 2/FC
HP R
ANGE (SINGLE MOTOR) 5 - 10 7.5 - 15 7.5 - 15
CFM 3,000 - 9,000 4,000 - 18,000 4,000 - 18,000
SIZE (SQ. FT.) 26.0 26.0 30.4
OWS/FPI 3 / 13 3 / 16 4 / 13
R
SIZE (SQ. FT.) 26.0 26.0 30.4
OWS/FPI 2/16 4 / 16 4 / 16
R
SIZE (SQ. FT.) 52.0 48.8 65.0
OWS/FPI 2/16 2 /16 2 /16
R
QUANTITY / DIAMETER (INCHES) 4 / 24 3 / 24 4 / 24
OMINAL CFM 4,600 6,800 6,800
N
OTOR HP 3 / 4 1.0 1.0
M
W RANGE 40 - 108 40 - 108 40 - 108
K
KW 111
80
AND 108 KW / CAPACITY STEPS (CV/VAV) 2 / 1 2 / 1 2 / 1
40
UNIT SIZE 25 TON 30 TON 40 TON 267 MBH C 533 MBH C 800 MBH C
267 MBH “M 533 MBH “M 800 MBH “M
APACITY STEPS (CV/VAV) 1 / 1 1 / 1 1 / 1 APACITY STEPS (CV/VAV) 2 / 1 2 / 1 2 / 1
APACITY STEPS (CV/VAV) --3 / 1* ODULATING” CAPACITY STEPS (CV ONLY) 6 / 1 6 / 1 6 / 1 ODULATING” CAPACITY STEPS (CV ONLY) 12 / 2 12 / 2 12 / 2 ODULATING” CAPACITY STEPS (CV ONLY) --17 / 3
SIZE (INCHES) 22.5” x 65” 22.5" X 65” 22.5" X 65”
APACITY 25 Ton 30 Ton 40 Ton
C
SIZE (INCHES) 21" X 65"
YPE Steam Coil
T
N
UMBER / SIZE 4 / 16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25
ACE AREA (SQ. FT.) 30.4 30.4 30.4
F
N
UMBER / SIZE 4 / 16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25
ACE AREA (SQ. FT.) 30.4 30.4 30.4
F
F
NUMBER / SIZE 4 / 16 x 25 & 6 / 20 x 25 4 /16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25
ACE AREA (SQ. FT.) 30.4 30.4 30.4
F
F
NUMBER / SIZE 4 ea. 16 x 25 / 6 ea. 20 x 25 4 ea. 16 x 25 / 6 ea. 20 x 25 4 ea. 16 x 25 / 6 ea. 20 x 25
ACE AREA (SQ. FT.) 30.4 30.4 30.4
F
* Unit Control Board with 3 heating outputs only, all other Unit Control Boards 2/1.
C
NDOOR FAN AND DRIVE
I
TANDARD EVAPORATOR COIL
S
IGH CAPACITY EVAPORATOR COIL
H
C
N
ILTERS 2" PLEATED, 30%
F
ILTERS 65% RIGID W/ 2” TA PREFILTERS
ILTERS 95% RIGID W/ 2” TA PREFILTERS
10.0 / 10.92 9.5 / 10.97 9.5 / 9.73
OMPRESSOR DATA
XHAUST FAN
E
ONDENSER COIL
C
ONDENSER FANS
E
LECTRIC HEAT
ATURAL GAS HEAT
OT WATER COIL
H
TEAM COIL
S
ILTERS 2" TA
F
10 Johnson Controls Unitary Products

TABLE 2: REFRIGERANT CHARGE

UNIT (TONS) MODEL TYPE
25 wo/ H GBP R22 Factory 25 lb. / 8 oz. 26lb / 0oz - ­25 w/HGBP R22 Factory 26 lb. / 0 oz. 26 lb. / 0oz - ­30 wo/HGBP R22 Factory 13 lb. / 4 oz. 13 lb. / 8 oz. 13 lb. / 8 oz. ­30 30 w/HGBP R22 Factory 14 lb. / 0 oz. 13 lb. / 8 oz. 13 lb. / 8 oz. ­30 w/HGBP 40 wo/HGBP R22 Factory 15 lb. / 5 oz. 15 lb. / 4 oz. 15 lb. / 5 oz. 15 lb. / 15 oz. 40 w/HGBP R22 Factory 15 lb. / 13 oz. 15 lb. / 4 oz. 15 lb. / 5 oz. 15 lb. / 15 oz.
1.
With high capacity evaporator coil.
wo/HGBP
1
1
R22 Factory 14 lb. / 6 oz. 14 lb. / 10 oz. 14 lb. / 10 oz. -
R22 Factory 15 lb. / 2 oz. 14 lb. / 10 oz. 14 lb. / 10 oz. -
F
ACTORY/ FIELD
HARGED
C
246653-YTG-E-0108
CHARGE
SYS #1 SYS #2 SYS #3 SYS #4

SELECTION PROCEDURE

GIVEN: Required Cooling Capacity 460,000 Btuh
Required Sensible Cooling 390,000 Btuh Required Heating (Gas) 320,000 Btuh Entering Air on Evaporator 83° F DB/ 67° F WB Outside Design Temperature 95° F Supply Fan CFM 13,000 CFM External Static Pressure 1.25 IWG Electrical Supply Voltage 460-3-60 Economizer Required 2” Throw Away Filters Constant Volume

SELECT UNIT:

1. Determine nominal tons: 460,000 / 12,000 = 38.33 Tons
Thus, a nominal 40 ton unit is selected.
2. Reference Cooling Capacity Table for a 40 ton unit with standard evaporator coil.
a. Locate the table for a standard evaporator coil with
95° F air on the condenser.
b. Enter table at 13,000 CFM and 67°F WB air on
evaporator c. Trace to 83° F Entering Dry Bulb column. d. Read 493 MBH total capacity and 403 MBH sensi-
ble capacity. The 40 ton unit will meet the cooling requirements. From
the nomenclature, the unit will be a Y34. Choose the appropriate configuration for the next digit. Assuming bottom return and supply, the fourth digit would be an “A,” making the model Y34A.
3. Find Gas Heating Capacity Table. a. Trace down Output column. b. Find output which exceeds 320,000 Btuh require-
ment. The N5 option gives 426 MBH output.
c. Ensure that it is offered in the Y34 unit. Read option
model as N5.
From the basic nomenclature, the model now becomes Y34AN5. Add voltage code of “4” for 460-3-60. Nomen­clature becomes Y34AN54.

SELECT FAN SPEED AND HORSEPOWER REQUIREMENTS OF SUPPLY AIR FAN

1. Find Supply Air Performance Tables for the 40 ton unit. a. Check footnotes and make necessary additions or
deductions to static resistance of ductwork:
Ductwork static resistance 1.25 IWG Economizer static resistance addition (interpolate) =.25 IWG + Gas Heat (High) = 0.5 IWG
Total Static Resistance 2.0 IWG b. Enter Fan Performance Table at 13,000 CFM and
2.0 IWG static pressure:
RPM = 690 BHP = 10.7
NOTE: Either a Class I or Class II blower could be used.
c. Enter the Fan Motor Drive Tables. Selecting a 15 hp
motor allows (service factor of 1.5) for a maximum operating BHP greater than the 10.7 BHP require­ment.

SIZE OVERCURRENT PROTECTION DEVICE AND DETERMINE CIRCUIT AMPACITY

1. Find electrical tables for the basic 40 ton unit. a. Enter table for 460-3-60 voltage. b. Find 15 hp in the Suppl y Air Fan column. c. Trace to Minimum Circuit Ampacity column - read
104. d. Trace to Max. Fuse/Breaker Size column - read 110. e. Size wire and overprotection device accordingly. f. Check all footnotes.
Johnson Controls Unitary Products 11
246653-YTG-E-0108

TABLE 3: STANDARD GAS HEATING CAPACITIES

GAS HEAT
PTION
O
AVAILABLE ON
ODELS
M
INPUT CAPACITY (MBH)
1ST STAGE TOTAL 1ST STAGE TOTAL
N3 Y32/Y33/Y34 267 267 213 247 247 N5 Y32/Y33/Y34 267 533 426 247 495 N8 Y34 ONLY 267
1.
Heating capacity is only staged on CV models. VAV models use only one stage at full capacity.
2.
Blower motor heat not included.
3.
Based on a heat content of 1075 Btu/Ft.
4.
Unit Control Board with 3 heating outputs only. For all other Unit Control Boards the 1st Stage is 533 MBH.
4
3

TABLE 4: TEMPERATURE RISE

TON
123
25 5-35 25-55 ­30 5-35 20-50 ­40 5-30 10-45 25-55
MODULES
1
UTPUT
O
APACITY
C
(MBH)
AS RATE, CU. FT./HR.
G
2
800 638 247 742

TABLE 5: MINIMUM HEATING CFM

TON
25 5,644 7,183 ­30 5,644 7,901 ­40 6,584 8,779 13,169
123

TABLE 6: MODULATING GAS HEATING CAPACITIES

GAS HEAT OPTION
2
D3
2
D5
2
D8
1.
Output Capacity at Full Fire.
2.
Modulating Gas Heat available on CV models only.
AVAILABLE ON
ODELS
M
Y32/Y33/Y34 69 267 6 213 64 247 Y32/Y33/Y34 69 533 12 426 64 495
Y34 ONLY 69 800 17 638 64 744
INPUT CAPACITY (MBH)
INIMUM MAXIMUM MINIMUM MAXIMUM
M
STEPS
O
UTPUT CAPACITY
(MBH)
1
MODULES
3
G
AS RATE, CU. FT./HR.
12 Johnson Controls Unitary Products

TABLE 7: MODULATING HEAT

G
AS HEAT OPTION AVAILABLE ON MODELS STEP INPUT OUTPUT % OF TOTAL OUTPUT
D3
(Turn down ration
3.8 to 1)
D5
(Turn down ration
7.7 to 1)
D8
(Turn down ration
11.5 to 1)
STAGES OF GAS CONTROL (% OF FULL HEAT OUTPUT)
1 69,333 55,466 26% 2 106,666 85,333 40%
Y32, Y33, Y34
3 165,332 132,266 62% 4 202,665 162,132 76% 5 229,332 183,466 86% 6 266,666 213,333 100% 1 69,333 55,466 13% 2 106,666 85,333 20% 3 165,332 132,266 31% 4 202,665 162,132 38% 5 229,332 183,466 43%
Y32, Y33, Y34
6 266,666 213,333 50% 7 325,331 260,265 61% 8 362,664 290,132 68%
9 389,331 311,465 73% 10 426,664 341,331 80% 11 495,997 396,798 93% 12 533,330 426,664 100%
1 69,333 55,466 9%
2 106,666 85,333 13%
3 165,332 132,266 21%
4 202,665 162,132 25%
5 229,332 183,466 29%
6 266,666 213,333 33%
7 325,331 260,265 41%
8 362,664 290,132 45%
Y34 Only
9 389,331 311,465 49% 10 426,664 341,331 53% 11 495,997 396,798 62% 12 533,330 426,664 67% 13 586,663 469,330 73% 14 655,996 524,797 82% 15 693,329 554,663 87% 16 762,662 610,130 95% 17 799,995 639,996 100%
246653-YTG-E-0108

TABLE 8: ELECTRIC HEATING CAPACITIES

AND KW PER STAGE
ELECTRIC
HEAT OPTION
E4 Y32, Y33, Y34 240 E8 Y32, Y33, Y34 2 40 E1 Y32, Y33, Y34 (460 & 575 volt only) 480
1.
Supply air fan motor heat not included.
2.
Heating capacity is only staged on CV models. VAV models use only one stage at full capacity.
3.
For 208 volts, multiply kW and MBH values by .751. For 230 volts, multiply kW and MBH values by .918
4.
For 460 volts, multiply kW and MBH values by .918.
AVAILABLE ON MODELS RATED VOLTAGE
3
/4804/575
2
/4803/575 80 273 40 137 40 136
3
/575 108 369 72 246 36 123
NOMINAL
KW
40 137 40 137 0 0
N
OMINAL
MBH
1
MBH
S
TAGE 1STAGE 2
KW MBH KW MBH
Johnson Controls Unitary Products 13
2
246653-YTG-E-0108

HOT WATER HEATING

1
The YORK Millennium Rooftop units (30 - 40 Ton sizes) can be furnished with a YORK hot water coil as the source of heat (Bottom Supply Only). A one or two row coil will be factory installed in the heating section downstream of the supply air fan and just above the supply air opening in the bottom of the unit.
The hot water control valve will not be provided. The installer will need to field supply a water valve. The installer must also connect the hot water piping, and valve wiring at th e job site for the hot water heat section to be operational.
For all hot water coils the enteri ng water temperature should not exceed 200°F.

PHYSICAL DATA HOT WATER COIL - 1 ROW

Coil Casing . . . . . . . . . . . . . . . . . . . .Galvanized Steel
Coil Construction. . . . . . . . . . . . . . . . Al Fin / Cu. Tube
Rows Deep . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Fin Thickness . . . . . . . . . . . . . . . . . . . . . . . . . . . .006”
Tube Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .016”
Tubes / Circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Fins Per Inch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Tubes High . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.50”
Tube Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65”
Face Area . . . . . . . . . . . . . . . . . . . . . . . . . . . .10.16ft.
2
Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71lbs.
Operating Weight . . . . . . . . . . . . . . . . . . . . . . . .83lbs.
TABLE 9: WATER PRESSURE DROP (1 ROW, 25 &
30 TON)
GPM 102030 40
W
ATER PRESSURE DROP 0.9 3.0 6.0 10.0
T ABLE 10: STATIC RESIST ANCE HOT W ATER COIL
(25 & 30 TON)
A
IR PRESSURE DROP 1 ROW 0.07 0.11 0.16 0.32 IR PRESSURE DROP 2 ROW 0.14 0.23 0.33 0.65
A
CFM 6000 8000 10000 15000
DO NOT use tin based solder. Brazing with tin based solder could cause equipment damage or possible injury to OCCUPANTS of the structure that is being conditioned.
TABLE 11: HOT WATER COIL (1 ROW, 25 & 30
1
TON)
APACITY (MBH) AT ENTERING WATER
GPM CFM
6000 91.4 115.3 139.3 163.6
10
20
30
40
1.
8000 102 128.8 155.8 182.9 10000 110.4 139.5 168.8 198.4 12000 117.3 148.4 179.6 211.2 15000 125.9 159.2 192.9 226.9
6000 103 129.4 156 182.7
8000 116.8 147 177.2 207.7 10000 128.2 161.3 194.7 228.2 12000 137.8 173.6 209.5 245.6 15000 150 189 228.2 267.8
6000 107.6 135 162.5 190.1
8000 122.8 154.3 185.8 217.5 10000 135.5 170.3 205.1 240.2 12000 146.4 184 221.8 259.7 15000 160.3 201.6 243 284.8
6000 110.1 138 166 194.1
8000 126.1 158.2 190.5 222.8 10000 139.6 175.2 210.9 246.8 12000 151.2 189.8 228.5 267.5 15000 166.1 208.6 251.3 294.1
Based on 60°F entering air temperature, 2.00” maximum pres­sure drop across the hot water coil.
C
140 °F 160 °F 180 °F 200 °F
EMPERATURE
T

PIPING CONNECTIONS

The hot water piping must enter the unit through the floor of the heat section compartment. The access doors to the com­partment are gasketed so the compartment can be sealed. However, as added protection for water leakage into the space, the piping access holes should be sealed with a heat resistant mastic (see the following illustration for approximate location of the compartment and piping connections.
NOTE: Water pressure drop numbers are based on 60°F
entering air temperature, 2.00” maximum air pres­sure drop across the hot water coil(s). ARI certified ratings at covering other conditions are available upon request. Hot water coils are approved for use with glycol (rates available upon request).
1. Hot water, steam or electric heat is not available for front or rear supply.
14 Johnson Controls Unitary Products
246653-YTG-E-0108
(1 OR 2 ROW)
CONDENSING
SECTION
88.75"
OUTSIDE OF
BASE RAIL
15.8"
11.88"
HEAT SECTION COMPARTMENT
2.25"
HOT WATER
COIL
26"
INLET (2")
C
L
OUTLET (2")
8.38"
2.55"
FIGURE 1 - HOT WATER PIPING CROSS-SEC-
TION
T ABLE 12: STATIC RESIST ANCE HOT WA TER COIL
(1 ROW, 40 TON)
CFM 8000 11000 14000 20000
IR PRESSURE DROP 1 ROW 0.11 0.19 0.29 0.52
A
IR PRESSURE DROP 2 ROW 0.23 0.39 0.58 1.06
A

TABLE 13: HOT WATER COIL (1 ROW 40 TON)

C
GPM CFM
APACITY (MBH) AT ENTERING WATER
140 °F 160 °F 180 °F 200 °F
8000 102 128.8 155.8 182.9
11000 114 144.1 174.4 205.1
10
14000 123.2 155.9 188.8 222.1 17000 130.6 165.4 200.4 235.8 20000 136.8 173.3 210.1 247.3
8000 116.8 147 177.2 207.7
11000 133.2 167.7 202.3 237.2
20
14000 146.2 184.2 222.4 260.8 17000 157 197.9 239 280.5 20000 166.2 209.6 253.2 297.3
8000 122.8 154.3 185.8 217.5
11000 141.2 177.4 213.8 250.3
30
14000 155.9 196.1 236.4 276.9 17000 168.3 211.8 255.4 299.3 20000 179.1 225.3 271.8 318.6
8000 126.1 158.2 190.5 222.8
11000 145.6 182.7 220 257.5
40
14000 161.4 202.6 244.1 285.8 17000 174.7 219.5 264.5 309.7 20000 186.3 234.2 282.3 330.6
1.
Based on 60°F entering air temperature, 2.00” maximum pres­sure drop across the hot water coil.
EMPERATURE
T
1
Johnson Controls Unitary Products 15
246653-YTG-E-0108
230.0
220.0
210.0
200.0
190.0
180.0
170.0
160.0
150.0
CAPACITY (MBH)
140.0
130.0
120.0
110.0
100.0
90.0
80.0
6000 7000 8000 9000 10000 11000 12000 13000 14000 15000
140 °F 160 °F 180 °F 200 °F
FLOW R ATE (CFM )

FIGURE 2 - HOT WATER COIL - 25 & 30 TON, 1 ROW, AT 10 GPM

270.0
260.0
250.0
240.0
230.0
220.0
210.0
200.0
190.0
180.0
170.0
CAPACITY (MBH)
160.0
150.0
140.0
130.0
120.0
110.0
100.0
90.0 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000
FLOW R ATE (CFM)
140 °F 160 °F 180 °F 200 °F

FIGURE 3 - HOT WATER COIL - 25 & 30 TON, 1 ROW, AT 20 GPM

16 Johnson Controls Unitary Products
290.0
280.0
270.0
260.0
250.0
240.0
230.0
220.0
210.0
200.0
190.0
180.0
CAPACITY (MBH)
170.0
160.0
150.0
140.0
130.0
120.0
110.0
100.0 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000
FLOW R ATE (CFM)
246653-YTG-E-0108
140 °F 160 °F 180 °F 200 °F

FIGURE 4 - HOT WATER COIL - 25 & 30 TON, 1 ROW, AT 30 GPM

300.0
290.0
280.0
270.0
260.0
250.0
240.0
230.0
220.0
210.0
200.0
190.0
CAPACITY (MBH)
180.0
170.0
160.0
150.0
140.0
130.0
120.0
110.0
100.0 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000
FLOW RATE (CFM )
140 °F 160 °F 180 °F 200 °F

FIGURE 5 - HOT WATER COIL - 25 & 30 TON, 1 ROW, AT 40 GPM

Johnson Controls Unitary Products 17
246653-YTG-E-0108
250.0
240.0
230.0
220.0
210.0
200.0
190.0
180.0
170.0
160.0
CAPACITY (MBH)
150.0
140.0
130.0
120.0
110.0
100.0
90.0 8000 9000 10000 11000 12000 13000 14000 15000 16000 17000 18000 19000 20000
140 °F 160 °F 180 °F 200 °F
FLOW RATE (CFM )

FIGURE 6 - HOT WATER COIL - 40 TON, 1 ROW, AT 10 GPM

300.0
290.0
280.0
270.0
260.0
250.0
240.0
230.0
220.0
210.0
200.0
190.0
CAPACITY (MBH)
180.0
170.0
160.0
150.0
140.0
130.0
120.0
110.0
100.0 8000 9000 10000 11000 12000 13000 14000 15000 16000 17000 18000 19000 20000
FLOW RATE (CFM)
140 °F 160 °F 180 °F 200 °F

FIGURE 7 - HOT WATER COIL - 40 TON, 1 ROW, AT 20 GPM

18 Johnson Controls Unitary Products
320.0
310.0
300.0
290.0
280.0
270.0
260.0
250.0
240.0
230.0
220.0
210.0
200.0
CAPACITY (MBH)
190.0
180.0
170.0
160.0
150.0
140.0
130.0
120.0
110.0 8000 9000 10000 11000 12000 13000 14000 15000 16000 17 000 18000 19000 20000
FLOW RATE (CFM )
246653-YTG-E-0108
140 °F 160 °F 180 °F 200 °F

FIGURE 8 - HOT WATER COIL - 40 TON, 1 ROW, AT 30 GPM

340.0
330.0
320.0
310.0
300.0
290.0
280.0
270.0
260.0
250.0
240.0
230.0
220.0
210.0
CAPACITY (MBH)
200.0
190.0
180.0
170.0
160.0
150.0
140.0
130.0
120.0 8000 9000 10000 11000 12000 13000 14000 15000 16000 1700 0 18000 19000 200 00
FLOW RATE (CFM)
140 °F 160 °F 180 °F 200 °F

FIGURE 9 - HOT WATER COIL - 40 TON, 1 ROW, AT 40 GPM

Johnson Controls Unitary Products 19
246653-YTG-E-0108

PHYSICAL DATA HOT WATER COIL - 2 ROW

Coil Casing . . . . . . . . . . . . . . . . . . . .Galvanized Steel
Coil Construction. . . . . . . . . . . . . . . . Al Fin / Cu. Tube
Rows Deep . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Fin Thickness . . . . . . . . . . . . . . . . . . . . . . . . . . . .006”
Tube Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .016”
Tubes / Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Fins Per Inch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Tubes High . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.50”
Tube Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65”
Face Area . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.16 ft.
2
Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90 lbs
Operating Weight . . . . . . . . . . . . . . . . . . . . . . .110 lbs
T ABLE 14: WA TER PRESSURE DROP (2 ROW, 25 &
30 TON)
GPM20406080
ATER
W
P
RESSURE
ROP
D
0.9 3.0 6.0 10.0
T ABLE 15: STATIC RESISTANCE HOT WATER COIL
(25 & 30 TON)
CFM 6000 8000 10000 15000
A
IR PRESSURE DROP
OW
1 R
A
IR PRESSURE DROP
OW
2 R
0.07 0.11 0.16 0.32
0.14 0.23 0.33 0.65
NOTE: Water pressure drop numbers are based on 60°F
entering air temperature, 2.00” maximum air pres­sure drop across the hot water coil(s). ARI certified ratings at covering other conditions are available upon request. Hot water coils are approved for use with glycol (rates available upon request.)
TABLE 16: HOT WATER COIL (2 ROW, 25 & 30
1
TON)
APACITY (MBH) AT ENTERING WATER TEMPERATURE
GPM CFM
6000 177.5 223.8 270.4 317.3 8000 203.8 257.2 311.1 365.5
20
10000 224.8 284.1 343.9 404.2 12000 242.2 306.4 371.1 436.4 15000 263.6 333.8 404.6 476.1
6000 198.1 248.9 300.0 351.3 8000 232.2 292.0 352.2 412.7
40
10000 260.7 328.1 395.9 464.1 12000 285.0 359.0 433.4 508.3 15000 316.0 398.4 481.3 564.8
C 140 °F 160 °F 180 °F 200 °F
TABLE 16: HOT WATER COIL (2 ROW, 25 & 30
1
(CONTINUED)
TON)
APACITY (MBH) AT ENTERING WATER TEMPERATURE
GPM CFM
6000 206.1 258.7 311.4 364.2 8000 243.6 305.9 368.4 431.1
60
10000 275.3 345.9 416.8 488.0 12000 302.9 380.7 458.9 537.6 15000 338.4 425.7 513.4 601.7
6000 210.5 263.9 317.4 371.1 8000 249.8 313.3 377.1 441.1
10000 283.3 355.6 428.2 501.0
80
12000 312.7 392.7 473.0 553.6 15000 351.0 440.9 531.3 622.1
1.
Based on 60°F entering air temperature, 2.00” maximum pres­sure drop across the hot water coil.
C 140 °F 160 °F 180 °F 200 °F

TABLE 17: HOT WATER COIL (2 ROWS, 40 TON)

APACITY (MBH) AT ENTERING WATER
GPM CFM
8000 203.8 257.2 311.1 365.5
20
40
60
80
1.
11000 233.9 295.7 358.1 421.0 14000 257.0 325.3 394.2 463.8 17000 275.5 349.0 423.3 498.3 20000 290.9 368.7 447.4 526.9
8000 232.2 292.0 352.2 412.7 11000 273.3 344.1 415.3 487.0 14000 306.3 386.0 466.3 547.1 17000 333.9 421.1 508.9 597.3 20000 357.5 451.1 545.4 640.5
8000 243.6 305.9 368.4 431.1 11000 289.5 363.9 438.5 513.6 14000 327.2 411.5 496.3 581.5 17000 359.2 452.0 545.3 639.2 20000 386.9 487.1 587.9 689.4
8000 249.8 313.3 377.1 441.1 11000 298.5 374.7 451.2 528.1 14000 338.9 425.7 512.8 600.5 17000 373.4 469.3 565.6 662.5 20000 403.6 507.5 611.8 716.8
Based on 60°F entering air temperature, 2.00” maximum air pressure drop across the hot water coil. ARI certified ratings at other conditions available upon request. Hot water coils are approved for use with glycol (ratings avail­able upon request).
C
140 °F 160 °F 180 °F 200 °F
EMPERATURE
T
TABLE 18: STATIC RESISTANCE HOT WATER
COIL (40 TON)
CFM 8000 11000 14000 20000
IR PRESSURE DROP 1 ROW 0.11 0.19 0.29 0.52
A A
IR PRESSURE DROP 2 ROW 0.23 0.39 0.58 1.06
TABLE 19: WATER PRESSURE DROP (2 ROW, 40
TON)
GPM 204060 80
W
ATER PRESSURE DROP 0.9 3.0 6.0 10.0
1
20 Johnson Controls Unitary Products
480.0
460.0
440.0
420.0
400.0
380.0
360.0
340.0
320.0
300.0
CAPACITY (MBH)
280.0
260.0
240.0
220.0
200.0
180.0
160.0 6000 7000 80 00 9000 10000 11000 12000 13000 14000 15000
FLOW RATE (CFM)
246653-YTG-E-0108
140 °F 160 °F 180 °F 200 °F

FIGURE 10 - HOT WATER COIL - 25 & 30 TON, 2 ROW, AT 20 GPM

580.0
560.0
540.0
520.0
500.0
480.0
460.0
440.0
420.0
400.0
380.0
360.0
CAPACITY (MBH)
340.0
320.0
300.0
280.0
260.0
240.0
220.0
200.0
180.0 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000
FLOW R ATE (CFM)
140 °F 160 °F 180 °F 200 °F

FIGURE 11 - HOT WATER COIL - 25 & 30 TON, 2 ROW, AT 40 GPM

Johnson Controls Unitary Products 21
246653-YTG-E-0108
610.0
590.0
570.0
550.0
530.0
510.0
490.0
470.0
450.0
430.0
410.0
390.0
370.0
CAPACITY (MBH)
350.0
330.0
310.0
290.0
270.0
250.0
230.0
210.0
190.0 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000
140 °F 160 °F 180 °F 200 °F
FLOW RATE (CFM )

FIGURE 12 - HOT WATER COIL - 25 & 30 TO N, 2 ROW, AT 60 GPM

640.0
620.0
600.0
580.0
560.0
540.0
520.0
500.0
480.0
460.0
440.0
420.0
400.0
380.0
CAPACITY (MBH)
360.0
340.0
320.0
300.0
280.0
260.0
240.0
220.0
200.0 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000
FLOW RATE (CFM )
140 °F 160 °F 180 °F 200 °F

FIGURE 13 - HOT WATER COIL - 25 & 30 TO N, 2 ROW, AT 80 GPM

22 Johnson Controls Unitary Products
530.0
510.0
490.0
470.0
450.0
430.0
410.0
390.0
370.0
350.0
330.0
CAPACITY (MBH)
310.0
290.0
270.0
250.0
230.0
210.0
190.0 8000 9000 10000 11000 12000 13000 14000 15000 16000 17000 18000 19000 20000
FLOW R ATE (CFM)
246653-YTG-E-0108
140 °F 160 °F 180 °F 200 °F

FIGURE 14 - HOT WATER COIL - 40 TON, 2 ROW, AT 20 GPM

650.0
630.0
610.0
590.0
570.0
550.0
530.0
510.0
490.0
470.0
450.0
430.0
410.0
390.0
CAPACITY (MBH)
370.0
350.0
330.0
310.0
290.0
270.0
250.0
230.0
210.0 8000 9000 10000 11000 12000 13000 14000 15000 16000 17000 18000 19000 20000
FLOW RATE (CFM )
140 °F 160 °F 180 °F 200 °F

FIGURE 15 - HOT WATER COIL - 40 TON, 2 ROW, AT 40 GPM

Johnson Controls Unitary Products 23
246653-YTG-E-0108
700.0
680.0
660.0
640.0
620.0
600.0
580.0
560.0
540.0
520.0
500.0
480.0
460.0
440.0
420.0
CAPACITY (MBH)
400.0
380.0
360.0
340.0
320.0
300.0
280.0
260.0
240.0
220.0 8000 9000 10000 11000 12000 13000 14000 15000 16000 17000 18000 19000 20000
140 °F 160 °F 180 °F 200 °F
FLOW RATE (CFM)

FIGURE 16 - HOT WATER COIL - 40 TON, 2 ROW, AT 60 GPM

730.0
710.0
690.0
670.0
650.0
630.0
610.0
590.0
570.0
550.0
530.0
510.0
490.0
470.0
450.0
CAPACITY (MBH)
430.0
410.0
390.0
370.0
350.0
330.0
310.0
290.0
270.0
250.0
230.0 8000 9000 10000 11000 12000 13000 14000 15000 16000 17000 18000 19000 20000
FLOW RATE (CFM)
140 °F 160 °F 180 °F 200 °F

FIGURE 17 - HOT WATER COIL - 40 TON, 2 ROW, AT 80 GPM

24 Johnson Controls Unitary Products
246653-YTG-E-0108

STEAM HEATING

The YORK Millennium units (25, 30, and 40 ton sizes) can be manufactured with a steam heat coil (Bottom Supply only). YORK's one row steam coil is installed in the heating section just downstream of the supply air fan and just above the sup­ply air opening in the bottom of the unit.
The steam control valve will not be provided. The installer will need to field supply a steam control valve. Connect the steam piping and valve power wiring at the job site for th e steam heat section to be operational.
There are no provisions in the coil or control sequence to pre­vent freezing of condensate. The control val ve, piping and field installed wiring connections are particularly vulnerable because they are installed in the vestibule outside of the con­ditioned air stream.
All piping, control valves, and wiring that is field installed must conform to all local and national codes
Condensate can freeze on the control valve and piping if they are not properly insulated.

PHYSICAL DATA STEAM COIL - 1 ROW

Coil Casing . . . . . . . . . . . . . . . . . . . . Galvanized Steel
Coil Construction . . . . . . . . . . . . . . . Al Fin / Cu. Tube
Rows Deep. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Fin Thickness . . . . . . . . . . . . . . . . . . . . . . . . . . . ..010”
Tube Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..035”
Tubes / Circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Fins Per Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Tubes High. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21”
Tube Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65”
Face Area. . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.48 ft.
Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 lbs.
*Hot water, steam coil or electric heat not available for front or rear supply.
2

TABLE 22: STEAM COIL (1 ROW, 40 TON)

APACITY (MBH) AT STEAM PRESSURE (PSI)
CFM
8000 221.1 236.9 250.4 265.0 11000 252.9 271.0 286.4 303.1 14000 278.2 298.0 315.0 333.4 17000 299.4 320.7 339.0 358.8 20000 317.6 340.2 359.6 380.6
C
2 6 10 15
TABLE 23: STATIC RESISTANCE STEAM COIL
(1 ROW, 40 TON)
CFM 8000 11000 14000 17000 20000
IR PRESSURE DROP 0.18 0.31 0.48 0.67 0.88
A

PIPING CONNECTIONS

The steam piping must enter the unit through the floor of the heat section compartment. The access doors to the compart­ment are gasketed to the compartment can be sealed. How­ever, as added protection for condensate leakage into the space, the piping access holes should be sealed with a heat resistant mastic. The following figure illustrates the approxi­mate location of the compartment and piping connections.
T O P V I E W
C O N D E N S I N G
S E C T I O N
8 8 . 7 5 "
O U T S I D E O F
B A S E R A I L
1 5 . 8 "
H E A T S E C T I O N
C O M P A R T M E N T
S T E A M
C O I L
2 6 "
O U T L E T ( 1 1 / 2 " )
I N L E T ( 2 " )
8 "
9 "
C
L
8 . 3 8 "
2 . 5 5 "

TABLE 20: STEAM COIL (1 ROW, 25 & 30 TON)

APACITY (MBH) AT STEAM PRESSURE (PSI)
CFM 6000 194.1 207.9 219.8 232.6
8000 221.1 236.9 250.4 265.0 10000 243.2 260.5 275.4 291.4 12000 261.9 280.6 296.6 313.9 15000 285.6 306.0 323.5 342.4
1.
Based on 60°F entering air temperature, 2.00” maximum air pressure drop across the coil.
C
261015
1

FIGURE 18 - STEAM PIPING CROSS SECTION

DO NOT use tin based solder. Brazing with tin based solder could cause equipment damage or possible injury to OCCUPANTS of the structure that is being conditioned.
TABLE 21: STATIC RESISTANCE STEAM COIL
(1 ROW, 25 & 30 TON)
CFM 6000 8000 10000 12000 15000
IR PRESSURE DROP 0.11 0.18 0.26 0.36 0.54
A
Johnson Controls Unitary Products 25
246653-YTG-E-0108
350 340 330 320 310 300 290 280 270 260 250
CAPACITY (MBH)
240 230 220 210 200 190 180
6000 7000 8000 9000 10000 11000 12000 13000 14000 15000
2 psi 6 psi 10 psi 15 psi
FLOW RATE (CFM)

FIGURE 19 - STEAM COIL - 25 & 30 TON, 1 ROW

390 380 370 360 350 340 330 320 310 300 290
CAPACITY (MBH)
280 270 260 250 240 230 220 210
8000 9000 10000 11000 12000 13000 14000 15000 16000 17000 18000 19000 20000
FLOW R ATE (CFM)
2 psi 6 psi 10 psi 15 psi

FIGURE 20 - STEAM COIL - 40 TON, 1 ROW

26 Johnson Controls Unitary Products

TABLE 24: EXHAUST FAN DRIVE DATA

MOTOR MOTOR PULLEY BLOWER PULLEY BELTS
OTOR EFF
M
TD.
IZE
(S
M
OTOR)
MODEL
25 Ton
30 Ton
40 Ton
BLOWER
RPM
ANGE
R
HP
FRAME
S
758 5 213T 87.5 89.5 4.9 1-3/8 11.3 2-3/16 BX63 2 852 7.5 215T 88.5 91.7 5.5 1-3/8 11.3 2-3/16 BX63 2 976 10 215T 89.5 91 6.3 1-5/8 11.3 2-3/16 BX63 2 852 7.5 213T 84 86.5 5.5 1-3/8 11.3 1-11/16 B65 2 976 10 215T 86.5 89.5 6.3 1-3/8 11.3 1-11/16 B65 2
1069 15 254T 85.7 89.5 6.9 1-3/8 11.3 1-11/16 B65 2
852 7.5 184T 84 86.5 5.5 1-3/8 11.3 1-11/16 B65 2 976 10 215T 86.5 89.5 6.3 1-3/8 11.3 1-11/16 B65 2
1069 15 254T 85.7 89.5 6.9 1-3/8 11.3 1-11/16 B65 2
OTOR
M
FF (HI
E
E
FF OPT)
ITCH DIA
P
NCHES)
(I
B
ORE
NCHES)
(I
P
ITCH DIA
NCHES)
(I
B
NCHES)
(I
246653-YTG-E-0108
ORE
D
ESIGNATION QTY

TABLE 25: SUPPLY FAN MOTOR AND DRIVE DATA

MODEL
RPM
ANGE
R
HP
F
RAME
SIZE
567 7.5 213T 88.5 91.7 4.5 1-3/8 13.9 2-3/16 BX56 2
BLOWER
25 Ton
692 10 215T 89.5 91 5.5 1-3/8 13.9 2-3/16 BX56 2 793 15 254T 91 91.7 6.3 1-5/8 13.9 2-3/16 BX56 2 894 20 256T 91 93 7.1 1-5/8 13.9 2-3/16 BX56 2 617 10 215T 89.5 91 4.9 1-3/8 13.9 2-3/16 BX56 2
30 Ton
743 15 254T 91 91.7 5.9 1-5/8 13.9 2-3/16 BX56 2 856 20 256T 91 93 6.7 1-5/8 13.7 2-3/16 5VX610 2 907 25 284T 91.7 93.6 7.1 1-7/8 13.7 2-3/16 5VX610 2 617 10 215T 89.5 91 4.9 1-3/8 13.9 2-7/16 BX67 2
40 Ton
652 15 254T 91 91.7 5.1 1-5/8 13.7 2-7/16 5VX710 2 728 20 256T 91 93 5.7 1-5/8 13.7 2-7/16 5VX710 2 780 25 284T 91.7 93.6 6.1 1-7/8 13.7 2-7/16 5VX710 2
1.
kW = (BHP X 0.746) / Motor Eff. MBH = kW X 3.414 MBH = (BHP X 2.546) / Motor Eff.
NOTES: 1) Class I Blowers are limited to 15 HP motors on 25 and 30 Ton units.
2) Class I Blowers are limited to 20 HP motors on the 40 Ton units.
3) Class II Blowers are not HP limited, can use 25 HP.
MOTOR MOTOR PULLEY BLOWER PULLEY BELTS
M
MOTOR
FFICIENCY
E
TD. MOTOR)
(S
OTOR
E
FFICIENCY
LTRA HI
(U
FF OPT)
E
1
ITCH DIA
P
NCHES)
(I
B
ORE
NCHES)
(I
P
ITCH DIA
NCHES)
(I
B
ORE
NCHES)
(I
D
ESIGNA
TION
QTY
Johnson Controls Unitary Products 27
246653-YTG-E-0108

SUPPLY AIR DRIVE ADJUSTMENT

At unit start-up, the measured CFM may be higher or lower than the specified CFM shown in Figures 22, 23, and 24. To achieve the specified CFM, the speed of the drive may have to be decreased or increased by changing the pitch diameter (PD) of the motor sheave as outlined below:
Failure to properly adjust the total system air quan­tity can result in extensive blower damage.
Before making any blower speed changes review the installation for any installation errors, leaks or undesirable systems effects that can result in loss of air flow.
Even small changes in blower speed can result in substantial changes in static pressure and bhp. Bhp or amp draw of the blower motor will increase (see table) by the cube ratio of the blower speed. Static pressure will increase by the square ratio of the blower speed. Tables 26, 27 and 28 are for reference only. All blower speed changes must be made by qualified personnel with strict adherence to the fan laws.
Example: A 30-ton unit was selected to deliver 12,000 CFM with a 20
HP motor and a 856 RPM drive, but the unit is only delivering 11,000 CFM per Figure 23.
Use the equation to determine the required PD for the new motor sheave (12,000 CFM / 11,000 CFM) x 6.7” = 7.31”.
Use the 30-ton table to select a Browning 2B5V74 which will increase the speed of the unit's drive and its supply air CFM 109%.
New drive speed = 1.091 x 856 = 933 RPM New supply air = 1.091 x 11,000 = 12,000 CFM Re-use the existing belts and blower sheave. New motor BHP = (speed increase)3 x estimated motor
BHP at original start-up with 11,000 CFM and 856 RPM = (1.091)3 x 11.0 BHP = 1.2986 x 11.0 BHP = 14.3 BHP New motor amps = (speed increase)3 x measured motor amps at original start-up with 11,000 CFM and 856 RPM.
28 Johnson Controls Unitary Products
246653-YTG-E-0108

TABLE 26: 25 TON DRIVE ADJUSTMENT

7.5 HP MOTOR & 567 RPM DRIVE 10 HP MOTOR & 692 RPM DRIVE 15 HP MOTOR & 793 RPM DRIVE 20 HP MOTOR & 894 RPM DRIVE
%RPM & CFM
REQD
PD
B
ROWNING
2B5V_ _
%RPM & CFM
R
EQD
PD
B
ROWNING
B5V_ _
2
%RPM & CFM
R
EQD
PD
B
ROWNING
B5V_ _
2
%RPM
& CFM
R
EQD
PD
B
- - - 82 4.5 42 84 5.3 50 86 6.1 58
- - - 86 4.7 44 87 5.5 52 89 6.3 60 100 (Std.)4.5 42 89 4.9 46 90 5.7 54 91 6.5 62 104 4.7 44 93 5.1 48 94 5.9 56 94 6.7 64 109 4.9 46 96 5.3 50 97 6.1 58 97 6.9 66
113 5.1 48 100
(Std.)
5.5
52 100
(Std)
6.3
60 100
(Std.)
7.1
118 5.3 50 104 5.7 54 103 6.5 62 103 7.3 70 122 5.5 52 107 5.9 56 106 6.7 64 108 7.7 74 126 5.7 54 111 6.1 58 110 6.9 66 117 8.3 80
- - - 115 6.3 60 113 7.1 68 125 8.9 86
- - - 118 6.5 62 116 7.3 70 - - -
- - - 122 6.7 64 122 7.7 74 - - -

TABLE 27: 30 TON DRIVE ADJUSTMENT

10 HP MOTOR & 617 RPM DRIVE 15 HP MOTOR & 743 RPM DRIVE 20 HP MOTOR & 856 RPM DRIVE 25 HP MOTOR & 907 RPM DRIVE
%RPM
& CFM
91.8 4.5 42 86.4 5.1 48 82.1 5.5 54 86.3 6.1 60
95.9 4.7 44 89.8 5.3 50 85.1 5.7 56 89.0 6.3 62
100.0
104.1 5.1 48 96.6 5.7 54 91.0 6.1 60 94.5 6.7 66
108.2 5.3 50 100.0
112.2 5.5 52 103.4 6.1 58 97.0 6.5 64 100.0
116.3 5.7 54 106.8 6.3 60 100.0
120.4 5.9 56 110.2 6.5 62 103.0 6.9 68 113.7 8.1 80
124.5 6.1 58 113.6 6.7 64 106.0 7.1 70 121.9 8.7 86
- - - 116.9 6.9 66 112.0 7.5 74 - - -
- - - 120.3 7.1 68 120.9 8.1 80 - - -
- - - 123.7 7.3 70 129.9 8.7 86 - - -
REQD PDBROWNING
(Std.)
4.9
2B5V_ _
46 93.2 5.5 52 88.1 5.9 58 91.8 6.5 64
%RPM & CFM
EQD
R
PD
(Std.)
5.9
BROWNING
2B5V_ _
%RPM & CFM
R
EQD
PD
BROWNING
2B5V_ _
%RPM & CFM
R
EQD
PD
56 94.0 6.3 62 97.3 6.9 68
(Std.)
7.1
(Std.)
6.7
66 105.5 7.5 74
BROWNING
2B5V_ _
ROWNING
B5V_ _
2
68
70

TABLE 28: 40 TON DRIVE ADJUSTMENT

10 HP MOTOR & 617 RPM DRIVE 15 HP MOTOR & 652 RPM DRIVE 20 HP MOTOR & 728 RPM DRIVE 25 HP MOTOR & 780 RPM DRIVE
%RPM & CFM
REQD
PD
BROWNING
2B5V_ _
91.8 4.5 42 88.2 4.5 44 82.5 4.7 46 83.7 5.1 50
95.9 4.7 44 92.1 4.7 46 86.0 4.9 48 86.9 5.3 52
100.0
(Std.)
4.9
46 96.0 4.9 48 89.5 5.1 50 90.2 5.5 54
104.1 5.1 48 100.0
108.2 5.3 50 103.9 5.3 52 96.5 5.5 54 96.7 5.9 58
112.2 5.5 52 107.8 5.5 54 100.0
116.3 5.7 54 111.7 5.7 56 103.5 5.9 58 103.3 6.3 62
- - - 115.6 5.9 58 107.0 6.1 60 106.6 6.5 64
- - - 119.5 6.1 60 110.5 6.3 62 109.8 6.7 66
- - - 123.4 6.3 62 114.0 6.5 64 113.1 6.9 68
- - - 127.4 6.5 64 117.5 6.7 66 116.4 7.1 70
- - - - - 66 121.1 6.9 68 119.7 7.5 74 NOTES: 1) Class I Blowers are limited to 15 HP motors on 25 and 30 Ton units.
2) Class I Blowers are limited to 20 HP motors on the 40 Ton units.
3) Class II Blowers are not HP limited, can use 25 HP.
Johnson Controls Unitary Products 29
% RPM
& CFM
R
EQD
PD
(Std.)
5.1
BROWNING
2B5V_ _
%RPM & CFM
R
EQD
PD
BROWNING
2B5V_ _
%RPM & CFM
REQD PDBROWNING
50 93.0 5.3 52 93.4 5.7 56
(Std.)
5.7
56 100.0
(Std.)
6.1
2B5V_ _
60