York XP Sunline R410A 13 SEER, ZF Sunline R410A 13 SEER, ZR Sunline MagnaDry R410A 13 SEER Technical Guide

TECHNICAL GUIDE
R-410A ZE/ZF/ZR/XN/XP SERIES 3 - 6 TON
251933-YTG-X-0615

Description

YORK® ZE/ZF/ZR/XN/XP Series units are convertibl e si ng l e package high efficiency rooftops with a common roof curb for the 3, 4, 5 and 6 Ton sizes (ZE, ZR, XN, XP not available in 6 Ton). Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof.
All ZE/ZF/ZR/XN/XP Series units are self-contained and assembled on rigid full perimeter base rails allowing for overhead rigging. Every unit is completely charged, wired, piped and tested at the factory to provide a quick and easy field installation.
All models (including those with an economizer) are convertible between bottom and horizontal duct connections.
60 Hertz
ZE/ZF/ZR Series units are available in the following configurations: cooling only, cooling with electric heat, and cooling with one or two stage gas heat. Electric heaters are available as factory-installed option or field installed accessory.
XN/XP Series units are available in the following configurations: cooling and heating only and cooling and heating with electric heat.
Tested in accordance with:
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
251933-YTG-X-0615
Smoke Detector
3/4” PVC Female Condensate Drain
GFCI
Convenience Outlet
Knockout For Side Control Entry
Simplicity® Lite™
Or Simplicity SE
Control Board
Knockout For Side Gas Supply Entry
Full Perimeter Baserails
With Forklift Slots And
Lifting Holes
Highly Efficient Enhanced Copper Tube/Enhanced Aluminum Fin Or Micro-Channel Aluminum Tube/Aluminum Fin Condenser
High Efficiency Compressor
Power Ventor Motor With
Post Purge Cycle
20 Gauge Aluminized
Steel Tubular Heat Exchanger
Belt Drive Or
Direct Drive
Blower
HACR Breaker
Economizer
Hood
Knockout For Side Power Entry
Slide-In Economizer

Table of Contents

Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Typical Field Power and Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147

Component Location

Gas/Electric

2 Johnson Controls Unitary Products

Electric/Electric and Heat Pump

Economizer
Hood
Electric Heat
Accessory Location
High Efficiency Compressor
Highly Efficient Enhanced Copper Tube/Enhanced Aluminum Fin Or Micro-Channel Aluminum Tube/Aluminum Fin Condenser
Full Perimeter Baserails
With Forklift Slots And
Lifting Holes
Simplicity® Lite™
Or Simplicity® SE Control Board
Belt Drive Or
Direct Drive
Blower
Knockout For Side Control Entry
GFCI
Convenience Outlet
3/4” PVC Female Condensate Drain
Smoke Detector
Slide-In Economizer
Knockout For Side Power Entry
HACR Breaker
251933-YTG-X-0615
Johnson Controls Unitary Products 3
251933-YTG-X-0615
Z E 048 N04 A 2 A AA 4 0 1 2 4 A
Z = A/C, Single Pkg., R-410A X = HP, Single Pkg., R-410A
Product Category
Airow
A = Direct Drive B = Direct Drive/Single Input Low Leak Econo D = Direct Drive/Motorized Damper N = Belt Drive P = Belt Drive/Single Input Low Leak Econo R = Belt Drive/Motorized Damper T = Belt Drive High Static U = Belt Drive High Static/Single Input Low Leak Economizer V = Belt Drive High Static/Motorized Damper
Product Generation
4 = Fourth Generation
*(D, T)10 = 92 MBH Output on 036 Models
036 = 3.0 Ton
Nominal Cooling Capacity
048 = 4.0 Ton 060 = 5.0 Ton 072 = 6.0 Ton
Product Identifier
= 11.2 EER2, A/C = 11.0 EER
3
, CLG/GAS R = 13.0 SEER Reheat P = 13.0 SEER HP
Product Style
A = Style A
SS Drain Pan
Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.
CPC Controller, DFS, APS
Honeywell Controller, DFS, APS
Novar Controller, DFS, APS
2" Pleated Filters, MERV 7
BAS Ready Economizer (2-10 V.D.C. Actuator Without a Controller)
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
1. 3 thru 5 Ton Units
2. 6 Ton Units Cooling Only / Cooling With Electric Heat
3. 6 Ton Unit Cooling With Gas Heat
F = 13.0 SEER
1
, A/C
E = 14.0 SEER, A/C
N = 14.0 SEER HP
Simplicity® Smart Equipment (SSE) w/Communication BACnet MS/TP (programmable to Modbus or N2 protocols)
Johnson Controller UNT 1126 (N2 protocol), DFS, APS
C00 = Cooling Only. Suitable for Field
Installed Electric Heat
Heat Type and Nominal Heat Capacity
N04 = 40 MBH Output Aluminized Steel, 1 Stage (036) N06 = 60 MBH Output Aluminized Steel, 1 Stage (048) N08 = 80 MBH Output Aluminized Steel, 1 Stage
(036, 060, 072)
N10 = 100 MBH Output Aluminized Steel, 1 Stage
(048, 060, 072)
D06 = 60 MBH Output Aluminized Steel, 2 Stage
(036, 048, 060, 072)
D10 = 100 MBH Output Aluminized Steel, 2 Stage
(036*, 048, 060, 072) S04 = 40 MBH Output Stainless Steel, 1 Stage (036) S06 = 60 MBH Output Stainless Steel, 1 Stage (048) S08 = 80 MBH Output Stainless Steel, 1 Stage
(036, 060, 072) S10 = 100 MBH Output Stainless Steel, 1 Stage
(048, 060, 072) T06 = 60 MBH Output Stainless Steel, 2 Stage
(036, 048, 060, 072) T10 = 100 MBH Output Stainless Steel, 2 Stage
(036*, 048, 060, 072)
E05 = 5 KW E07 = 7 KW E10 = 10 KW E15 = 15 KW E20 = 20 KW E30 = 30 KW
Gas Heat Options
Electric Heat Options
Voltage
1 = 208/230-1-60 2 = 208/230-3-60
4 = 460-3-60 5 = 575-3-60
York Commercial Comfort System (YCCS) Rtu Controller
3 = 380-3-60
A = No Options Installed
Installation Options
B = Option 1 C = Option 2 D = Options 1 & 2 E = Option 3 F = Option 4 G = Options 1 & 3 H = Options 1 & 4 J = Options 1, 2 & 3 K = Options 1, 2, & 4 L = Options 1,3 & 4 M = Options 1, 2, 3, & 4
N = Options 2 & 3 P = Options 2 & 4 Q = Options 2, 3, & 4 R = Options 3 & 4 S = Option 5 T = Options 1 & 5 U = Options 1, 3, & 5 V = Options 1, 4, & 5 W = Options 1, 3, 4, & 5 X = Options 3 &
5 Y = Options 4 & 5 Z = Options 3, 4 & 5
1 = Disconnect 2 = Non-Pwr'd Conv. Outlet 3 = Smoke Detector S.A. 4 = Smoke Detector R.A. 5 = Pwr'd Conv. Outlet
Options
AA = None AB = Phase Monitor AC = Coil Guard AD = Dirty Filter Switch AE = Phase Monitor & Coil Guard AF = Phase Monitor & Dirty Filter Switch AG = Coil Guard & Dirty Filter Switch AH = Phase Monitor, Coil Guard & Dirty Filter Switch AS = Bottom Drain Connection RC = Coil Guard & American Flag TA = Technicoat Condenser Coil TJ = Technicoat Evaporator Coil TS = Technicoat Evaporator and Condenser Coil EA = E-Coat Condenser Coil EJ = E-Coat Evaporator Coil ES = E-Coat Cond & Evap Coils 1A = Simplicity SE 1B = Phase Monitor & Simplicity SE 1C = Coil Guard & Simplicity SE 1D = Dirty Filter Switch & Simplicity SE 1E = Phase Monitor, Coil Guard, Simplicity SE 1F = Phase Monitor, Dirty Filter Switch, Simplicity SE 1G = Coil Guard & Dirty Filter Switch, Simplicity SE 1H = Phase Monitor, Coil Guard, Dirty Filter Switch, Simplicity SE
Standard Cabinet
Additional Options
ZZ = If desired option combination is not listed above, ZZ will be assigned and conguration options will be
located in digits 15-18.
Hinged & Toolless Access Cabinet
BA = Hinged & Toolless Filter, Motor and Electrical Access Panels BB = Phase Monitor, Hinged & Toolless Filter, Motor and Electrical Access Panels BC = Coil Guard, Hinged & Toolless Filter, Motor and Electrical Access Panels BD = Dirty Filter Switch, Hinged & Toolless Filter, Motor and Electrical Access Panels BE = Phase Monitor & Coil Guard, Hinged & Toolless Filter, Motor and Electrical Access Panels BF = Phase Monitor & Dirty Filter Switch, Hinged &
Toolless Filter, Motor and Electrical Access
Panels BG = Coil Guard & Dirty Filter Switch, Hinged &
Toolless Filter, Motor and Electrical Access
Panels
BH = Phase Monitor, Coil Guard & Dirty Filter Switch, Hinged & Toolless Filter, Motor and Electrical Access Panels 2A = Hinged & Toolless Access Panels, Simplicity SE 2B = Hinged & Toolless Access Panels, Phase Monitor, Simplicity SE 2C = Hinged & Toolless Access Panels, Coil Guard & Simplicity SE 2D = Hinged & Toolless Access Panels, Dirty Filter Switch, Simplicity SE 2E = Hinged & Toolless Access Panels, Phase Monitor, Coil Guard, Simplicity SE 2F = Hinged & Toolless Access Panels, Phase Monitor, Dirty Filter Switch, Simplicity SE 2G = Hinged & Toolless Access Panels, Coil Guard, Dirty Filter Switch, Simplicity SE 2H = Hinged & Toolless Access Panels, Phase Monitor, Coil Guard, Dirty Filter Switch, Simplicity SE

Nomenclature

4 Johnson Controls Unitary Products
251933-YTG-X-0615

Features and Benefits

Standard Features

High Efficiency - High efficiency 3 thru 5 Ton units reach
14.0/13.0 SEER, 6 Ton Cooling only or Cooling with Electric Heat reach 11.2 EER and 6 Ton Cooling with Gas Heat reach 11.0 EER. Gas/electric units have electronic spark ignition and power vented combustion with steady state efficiencies of 80%. High efficiency heat pumps reach 14/13 SEER and 8.0/7.7 H.S.P. F. These efficiencies exceed all legislated minimum levels and provide low operating costs.
Coil Technology – All ZE/ZF condensers utilize Micro­Channel “all-aluminum” condensers which provide improved heat transfer capabilities and reduced charge volumes. All evaporators utilize a conventional copper tube/aluminum fin design for proven reliability and performance.
Convertible Airflow Design - All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, remove the supply and return air panels on the rear of the unit.
System Protection - Suction line freezestats are supplied on all units to protect against loss of charge and coil frosting when the economizer operates at low outdoor air temperatures while the compressors are running. Every unit has solid-core liquid line filter-driers and high and low­pressure switches. Internal compressor protection is standard on all compressors.
Advanced Controls - ZE/ZF (Electric/Electric and Gas/ Electric) with no factory installed economizer or BAS options will come standard with the reliable Simplicity Lite™ control. All ZE/ZF models with factory installed economizers or any BAS option, reheat (ZR) and heat pump (XP, XN) Units will come with the new state of the art Simplicity SE (Smart Equipment) control system. The new unit control incorporates the best of the already proven Simplicity robust, intelligent control. The goal of this control is to utilize cutting edge technology making the equipment easier to install, operate, and service. All units are Factory commissioned, configured, and run tested.
®
unitary controls and creates a more

Simplicity SE Control Board

Versatile - The Simplicity SE (not applicable with units utilizing Simplicity Lite) control can be configured to use with a standard thermostat (easy to connect screw terminals), A zone sensor, or can be setup to communicate with multiple BAS communication protocols to integrate with building automation systems.
Reduce field installed complexity - Each unit (not applicable with units utilizing Simplicity Lite) will comes equipped with factory installed supply air, return air, and outdoor air temperature sensors providing key temperature readings thus reduce field installed complexity.
®
On-board USB Port - The new control (not applicable with units utilizing Simplicity Lite) comes with a long list of features including data logging, current and previous system faults and software update capabilities using the on board USB port and common flash drive. Energy use monitoring capabilities allow custom tailoring to allow a system to work more efficiently at all times and occupancy levels. Self test and start-up reports also available from the board VIA the USB port.
Embedded LCD Display - The board (not applicable with units utilizing Simplicity Lite) has a easy to read, built-in LCD display and easy to use navigation joystick and buttons allowing the user to quickly navigate the menus displaying unit status, options, current function, supply, return and outdoor temperatures, fault codes and other information.
Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0F outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.
Johnson Controls Unitary Products 5
251933-YTG-X-0615
The
Simplicity
this product will effectively operate the cooling sys­tem down to 0°F when this product is applied in a comfort cooling application for people. An econo­mizer is typically included in this type of applica­tion. When applying this product for process cooling applications (computer rooms, switchgear, etc.), please reference applications bulletin AE­011-07 or call the applications department for Uni­tary Products @ 1-877-UPG-SERV for guidance. Additional accessories may be needed for stable operation at temperatures below 30° F.
Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti-short cycle delay can be temporarily overridden with the push of a button.
Fan Delays - Fan on and fan off delays are fully programmable. Furthermore, the heating and cooling fan delay times are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat.
Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the gas valve, if applicable, and the temperature limit switch on gas and electric heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.
Nuisance Trip Protection and Strikes - To prevent nuisance trouble calls, the control board uses a “three times, you’re out” philosophy. The high and low­pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the associated compressor.
On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED or on LCD with Simplicity SE controlled units. Each high and low­pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.
Reliable - From the beginning - All units undergo computer automated testing before they leave the factory. Units are tested for refrigerant charge and pressure, unit amperage, and 100% functionality. For the long term - All units are painted with a long lasting, powder paint that stands up over the life of the unit. The paint used has been proven by a 1000 hour salt spray test.
Flexible Placement - All models and configurations share the same cabinet/footprint and thus the same roof curb. You have the flexibility to set one curb and choose the
® Lite or SE control board used in
correct tonnage size and heating option after the internal loads have been determined.
Full Perimeter Base Rails - The permanently attached base rails provide a solid foundation for the entire unit and protect the unit during shipment. The rails offer forklift access from 3 sides, and rigging holes are available so that an overhead crane can be used to place the units on a roof.
Easy Installation - Gas and electric utility knockouts are supplied in the unit underside as well as the side of the unit. A clearly identified location is provided to mount a field supplied electrical disconnect switch. Utility connections can be made quickly and with a minimum amount of field labor.
Wide Range of Indoor Airflows - Indoor fan motors are either direct-drive or belt-drive type providing maximum flexibility to handle most airflow requirements.
Gas Heat Operation - All single phase models with gas heat have minimum annual fuel utilization efficiency (AFUE) of 81%. All three phase models with gas heat have minimum steady state efficiency of 80%. Each section includes a durable heat exchanger with aluminized steel or optional stainless steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards.
The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit.
Electric Heat Operation - All electric heat models are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uniform distribution of air across the heating elements.
Every element is fully protected against excessive temperature by thermal limit switches.
The power supply wiring can be routed into the control box through a threaded pipe connection (field supplied) in the base pan of the unit or through a knockout in the wiring panel on the side of the unit.
Warranty - All models include a 1-year limited warranty on the complete unit. Compressors and electric heater elements each carry a 5-year warranty. Aluminized steel and stainless steel tubular heat exchangers carry a 10­year warranty.

Factory Installed Options

NOTE: Simplicity Lite models are only available with a field
installed Honeywell Jade economizer which is equipped standard with single enthalpy control (dual enthalpy available as field installed kit). Simplicity SE models are available with factory or field installed economizers including options for a SSE controlled economizer or an externally controlled BAS economizer where both feature standard dry bulb control (single and dual enthalpy available as field installed kits).
Economizers - All units offer a variety of optional factory installed economizers that are shipped, installed and wired with AMCA 511 Licensed Class 1A low leak
6 Johnson Controls Unitary Products
251933-YTG-X-0615
dampers designed to exceed ASHRAE 90.1-2010 and the International Energy Conservation Code (IECC) certification requirements by achieving leakage rates of 3 cfm/ sq. ft. at 1" of static pressure. Each economizer goes through a rigorous 60,000 cycle test. Dry bulb, single enthalpy, and dual enthalpy (with field installed kit) can be selected. All economizer options are fully integrated into the Simplicity SE controls. The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the outdoor air dry bulb temperature or the outdoor air enthalpy input. The dual enthalpy kit provides a second input used to monitor the return air (field installed). The installer needs only to assemble the outdoor air hood, attach the enthalpy control the hood and mount the hood to the unit (Hood and control are provided).
Dry Bulb Economizer - Economizer operation is enabled by the outdoor air temperature being less than the setpoint of the economizer module.
Enthalpy Economizer - The added outdoor air enthalpy sensor enables economizer operation if the outdoor enthalpy is less than the setpoint of the economizer logic module.
Motorized Outdoor Air Intake Damper -Includes a slide­in / plug-in damper assembly with a 2-position, spring return motor actuator which opens to a pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must be field assembled before installing.
Technicoat Condenser Coils - The condenser coils are coated with a phenolic coating for protection against corrosion due to harsh environments.
• Technicoat Evaporator Coil - The evaporator coils are coated with a phenolic coating for protection against corrosion due to harsh environments.
• E-coat Condenser Coils - The condenser coils are coated with an epoxy polymer coating to protect against corrosion.
• E-coat Evaporator Coils - The evaporator coils are coated with an epoxy polymer coating to protect against corrosion.
Electric Heaters - Wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent operation at excessive temperatures.
Filter Options - Standard units are shipped with 1" throw­away filters installed. 2" Pleated Filters, MERV 7 are offered as a factory installed option.
Convenience Outlet - This 110 volt outlet can be “powered” by the unit with a stepdown transformer or the unit may be ordered with a “non-powered” convenience outlet that can be wired in the field.
Disconnect Switch - For gas heat units and cooling units with electric heat, a HACR breaker sized to th e unit is
provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only.
Smoke Detectors - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.
Factory installed smoke detectors in the return air, may be subjected to freezing temperatures during “off” times due to out side air infiltration. These smoke detectors have an operational limit of 32°F to 131°F. Smoke detectors installed in areas that could be out side those limitations will have to be moved to prevent having false alarms.
Coil Guard - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.
Stainless Steel Heat Exchanger - For applications in corrosive environments, this option provides a full stainless steel heat exchanger assembly.
Stainless Steel Drain Pan - An optional rustproof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environments.
Bottom Drain Connection - An optional bottom drain
• connection is available for inside the curb connections for applications in cold environments to reduce freezing drain lines.
Phase Monitors - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of phase condition.
Dirty Filter Switch - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.
Hinged & Toolless Filter, Motor and Electrical Access Panels - This option allows for easy access and maintenance.
NOTE: Knobs are shipped inside the unit to prevent shipping
damage. These must be field installed for tool-less operation.
High Static Drive - May include a belt, blower pulley, motor pulley or a motor change to enhance blower performance.

Control Options

Simplicity® SE with Communication Option Control ­The York® Simplicity® SE with Communication Option Control is factory installed. It includes all the features of the Simplicity® SE control with an additional gateway to BACnet MS/TP (programmable to Modbus or N2 protocols).
Johnson Controls Unitary Products 7
251933-YTG-X-0615
Novar® BAS Control - The Novar® building automation system controller is factory installed. Incudes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.
CPC BAS Control - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch and air proving switch.
Honeywell BAS Control - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch.
York Commercial Comfort System (YCCS) - Provides rooftop system integration for YCCS single zone and change-over bypass systems.

Field Installed Accessories

NOTE: Simplicity Lite models are only available with a field
installed Honeywell Jade economizer which is equipped standard with single enthalpy control (dual enthalpy available as field installed kit). Simplicity SE models are available with factory or field installed economizers including options for a SSE controlled economizer or an externally controlled BAS economizer where both feature standard dry bulb control (single and dual enthalpy available as field installed kits).
Economizers - All units offer a variety of optional field installed economizers that are shipped, installed and wired with AMCA 511 Licensed Class 1A low leak dampers designed to exceed ASHRAE 90.1-2010 and the International Energy Conservation Code (IECC) certification requirements by achieving leakage rates of 3 cfm/ sq. ft. at 1" of static pressure. Each economizer goes through a rigorous 60,000 cycle test. Dry bulb, single enthalpy, and dual enthalpy (with field installed kit) can be selected. All economizer options are fully integrated into the Simplicity SE controls. The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the outdoor air dry bulb temperature or the outdoor air enthalpy input. The dual enthalpy kit provides a second input used to monitor the return air (field installed). The installer needs only to assemble the outdoor air hood, attach the enthalpy control the hood and mount the hood to the unit (Hood and control are provided).
Dry Bulb Economizer - Economizer operation is
enabled by the outdoor air temperature being less than the setpoint of the economizer module.
Enthalpy Economizer - The added outdoor air enthalpy
sensor enables economizer operation if the outdoor enthalpy is less than the setpoint of the economizer logic module.
Motorized Outdoor Air Intake Damper -Includes a slide­in / plug-in damper assembly with a 2-position, spring
return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must be field assembled before installing.
Electric Heaters - wired for single point power supply. These nickel chromium heater elements are provided with
limit and automatic reset capability to prevent operation at excessive temperatures.
Roof Curbs - Eight and fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly.
Roof curbs are designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports.
High Altitude Natural Gas - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet.
Propane - Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane.
High Altitude Propane - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the basi c propane conversion kit.
Low Nox Kit - Required to reduce the emission of nitrogen oxides below 40 nano grams per joule.
Power Exhaust
- Our single input economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation.
The power exhaust option can only be used on bottom duct configurations.
Barometric Relief Damper - This damper accessory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.
Enthalpy Accessory Control Kit - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.
Burglar Bars - Mount in the supply and return openings to prevent entry into the duct work.
Flue Exhaust Extension Kit - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.
Sensor - Senses CO2 levels and automatically
CO
2
overrides the economizer when levels rise above the present limits.
8 Johnson Controls Unitary Products
251933-YTG-X-0615
Coil Guard - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.
Hail Guard - Hail Guard kit is available to prevent unit from hail damage. This is a sloped hood that fits above the coil.
Gas Piping Kit - This kit supplies all necessary fittings and shut off valve.

Guide Specifications

General
Units shall be manufactured by Johnson Controls Unitary Products in an ISO 9001 certified facility.
York's ZE/ZF/ZR/XN/XP units are convertible single package units. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof. Cooling only, cooling with gas heat and cooling with electric heat models are available with a wide variety of factory-mounted options and field-installed accessories to make them suitable for almost every application. All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation. All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with power exhaust are suitable for bottom duct connections only. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, remove the supply and return air panels on the rear of the unit.
All non-Scroll compressors include crankcase heaters and all compressors have internal pressure relief. Every refrigerant circuit includes a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch.The unit control circuit includes a 75 VA transformer, a 24-volt circuit breaker and a relay board with a compressor lockout circuit, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify the interface of additional field controls. All models are CSA listed. All models include a 1-year limited warranty on the complete unit. Compressors and electric heater elements carry a 5-year warranty. Aluminized steel and Stainless steel tubular heat exchangers carry a 10-year warranty.
Cooling only or Cooling with Electric Heat shall have 11.2 EER, 6 Ton Cooling with Gas Heat shall have 11.0 EER. They shall have built-in field convertible duct connections for down discharge supply/return or horizontal discharge supply/return, and be available with factory installed options or field installed accessories. The units shall be factory wired, piped, charged with R-410A refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. All units the cooling performance shall be rated in accordance with DOE and AHRI test procedures. Units shall be CSA listed, classified to ANSI Z21.47, UL 1995/CSA No. 236 standards.
Unit Cabinet
Unit cabinet shall be constructed of galvanized steel, with exterior surfaces coated with a non-chalking, powdered paint finish, certified at 1000 hours salt spray test per ASTMB117 standards. Indoor blower section shall be insulated with a minimum 1/2” thick insulation, coated on the airside. Aluminum foil faced insulation shall be used in the furnace compartment and be fastened with ridged fasteners to prevent insulation from entering the air stream. Cabinet panels shall be “large” size, easily removable for servicing and maintenance. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging and proper sealing on roof curb applications. Disposable 1" filters shall be furnished and be accessible through a removable access door, sealed airtight. Units filter track shall be designed to accommodate either 1" or 2" filters. Fan performance measuring ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator fan performance without removing panels or creating air by-pass of the coils. Condensate pan shall be internally sloped and conform to ASHRAE 62-89 self­draining standards. Condensate connection shall be a minimum of 3/4” I.D. female and be a ridged mount connection.
Indoor (Evaporator) Fan Assembly
The indoor fan shall be a factory installed direct-drive or belt­drive assembly that includes an adjustable pitch motor pulley. Job site selected (B.H.P.) brake horsepower shall not exceed the motors nameplate horsepower rating, plus the service factor. Units shall be designed not to operate above service factor. Fan wheel shall be double-inlet type with forward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume. Bearings shall be sealed and permanently lubricated for longer life and no maintenance.
Outdoor (Condenser) Fan Assembly

Description

Units shall be factory-assembled, single packaged, Electric Cooling/Gas Heat, Electric Cooling/Optional Electric Heat, Heat Pump/Optional Electric Heat are designed for outdoor mounted installation.
The 3 ton, 4 ton and 5 ton units shall have minimum SEER rating of 13.0 with heat pumps having a 7.7 H.S.P.F. The 6 Ton
Johnson Controls Unitary Products 9
The outdoor fan shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to a corrosion resistant steel spider bracket and shall be dynamically balanced for smooth operation. The outdoor fan motor shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and staged independently.
251933-YTG-X-0615
Refrigerant Components
Compressor:
a. Shall be internally protected with internal high-pressure
relief and over temperature protection.
b. Shall have internal spring isolation and sound muffling to
minimize vibration and noise, and be externally isolated on a dedicated, independent mounting.
Coils:
a. Evaporator coils shall have aluminum plate fins
mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option.
b. Evaporator coils shall be of the direct expansion, draw-
thru design.
c. Condenser coils shall have aluminum plate fins
mechanically bonded to seamless internally enhanced copper tubes with all joints brazed or Micro-Channel aluminum tube, aluminum fins.
d. Condenser coils shall be of the direct expansion, draw-
thru design.
Refrigerant Circuit and Refrigerant Safety Components shall include:
a. Independent fixed-orifice or thermally operated
expansion devices.
b. Filter drier/strainer to eliminate any moisture or foreign
matter.
c. Accessible service gage connections on both suction
and liquid lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting, without losing charge.
d. The refrigeration system shall provide at least 15°F of
sub-cooling at design conditions.
i. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to 0°F.
j. Control board shall monitor each refrigerant safety switch
independently.
k. Control board shall retain last 5 fault codes in non volatile
memory which will not be lost in the event of a power loss.
Gas Heating Section (Single Or 2 Stage)
Shall be designed with induced draft combustion with post purge logic, energy saving direct spark ignition, and redundant main gas valve. Venter wheel shall be constructed of stainless steel for corrosion resistance. The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized steel for corrosion resistance and allowing minimum mixed air entering temperature of 25°F. Burners shall be of the inshot type, constructed of aluminum coated steel and contain air mixture adjustments. All gas piping shall enter the unit cabinet at a single location through either the side or curb without any field modifications. Integrated control boards shall provide timed control of evaporator fan functioning and burner ignition. Heating section shall be provided with the following minimum protection:
a. Primary and auxiliary high-temperature limit switches. b. Induced draft motor speed sensor. c. Flame roll out switch. d. Flame proving controls. e. If any of the above safety devices trip, a LED (light-
emitting diode) indicator shall flash a diagnostic code that indicates which safety switch has tripped.
st
NOTE: All 2 Stage Gas Heat, 60% Capacity 1
Stage, 40%
Capacity 2nd Stage.
Electric Heating Section
Unit Controls
An electric heating section, with nickel chromium elements, shall be provided in a range of 5 thru 30 KW, offering two
a. Unit shall be complete with self-contained low-voltage
control circuit protected by a resettable circuit breaker on the 24-volt transformer side.
b. Unit shall incorporate a lockout circuit which provides
reset capability at the space thermostat or base unit, should any of the following standard safety devices trip
and shut off compressor. c. Loss-of-charge/Low-pressure switch. d. High-pressure switch. e. Freeze-protection thermostat, evaporator coil. f. Unit shall incorporate “AUTO RESET” compressor over
temperature, over current protection. g. Unit shall operate with conventional thermostat designs
and have a low voltage terminal strip for easy hook-up.
stages of capacity - 16 KW and above on 208/230 volt heaters and 20 KW and above on 460 and 575 volt heaters. The heating section shall have a primary limit control(s) and automatic reset to prevent the heating element system from operating at an excessive temperature. The heating section assembly shall slide out of the unit for easy maintenance and service. Units with Electric Heating shall be wired for a single point power supply with branch circuit fusing (where required).
Unit Operating Characteristics
Unit shall be capable of starting and running at 125°F outdoor temperature, exceeding maximum load criteria of AHRI Standard 210/240. The compressor, with standard controls, shall be capable of operation down to 0°F outdoor temperature. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up (Gas heat only).
h. Unit control board shall have on-board diagnostics and
fault code display.
10 Johnson Controls Unitary Products
251933-YTG-X-0615
Electrical Requirements
All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.
Standard Limited Warranties
• Compressor 5 Years
• Heat Exchanger 10 Years
• Electric Heat Element 5 Years
• Other Parts 1 Year
Optional Outdoor Air
Shall be made available by either/or:
Dry Bulb Automatic Economizer - Outdoor and return air
dampers that are interlocked and positioned by a fully­modulating, spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall be designed to meet ASHRAE 90.1-2010, AMCA 511 Class 1A damper, and the International Energy Conservation Code (IECC) certification requirements by achieving leakage rates of 3 cfm/sq. ft. at 1" of static pressure. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss. Available with barometric relief and power exhaust..
Motorized Outdoor Air Dampers - Outdoor air dampers
are positioned by a 2-position, spring-return damper actuator. A unit-mounted potentiometer shall be provided to adjust the outdoor damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected positions
- regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de­energized. Dampers shall fully close on power loss.
Other Pre-engineered Accessories Available
Roof Curb - 14"and 8” high, full perimeter curb with wood
nailer (shipped knocked-down).
Barometric Relief Damper - Contains a rain hood, air
inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure through the unit.
Propane Conversion Kit - Contains new orifices and gas
valve parts to convert from natural to L.P. gas. One per unit required.
High Altitude - Natural Gas - Contains orifices required for applications between 2000 and 6000 feet altitude.
High Altitude - Propane Gas - Contains orifice s requ ired for applications between 2000 and 6000 feet altitude. Must be used with propane conversion kit.
Low Nox - Required to reduce the emission of nitrogen oxides below 40 nanograms per joule.
Gas Piping - Contains 1/2” pipe nipples, fittings and gas cock (including panel assess gaskets) required for bottom gas supply connection with external shut off.
Power Exhaust Option - To work in conjunction with economizers.
• Electric Heaters
Economizer/motorized Damper Rain Hood - Contains all hood panels and the hardware for assembling.
• Manual Outdoor Air Damper
Coil Guard Kit - Guard for cooling coil.
• Hail Guard
• Flue Exhaust Extension
OTHER FACTORY INSTALLED OPTIONS
Power Exhaust Option - To work in conjunction with economizers.
• Stainless Steel Heat Exchanger
• Stainless Steel Drain Pan
• Bottom Drain Connection
• Technicoat Phenolic Coated Condenser And Evaporator Coil
• Electronic Single Enthalpy Economizer
• Dirty Filter Switch
• Phase Monitor
• Coil Guard
• Powered GFI Convenience Outlet
• Non-powered GFI Convenience Outlet
• BAS Controls - Simplicity® SE with BAS Communication (BACnet MS/TP, Modbus, and Johnson Controls N2) Option, CPC, HONEYWELL, NOVAR, YORK
• Bas Ready Economizer (2-10 V.D.C. Actuator Without a Controller)
• Hinged Filter Door Access And Toolless Access Panels
• 2" Pleated Filters, MERV 7
• Disconnect Switch
• Supply Air Smoke Detector
• Return Air Smoke Detector
• Direct Drive Or Belt Drive Blower With High Static Drive Option
• Hot Gas Reheat with Hot Gas Bypass (Not available on 6 Ton)
Johnson Controls Unitary Products 11
251933-YTG-X-0615

Physical Data

ZE036-060 Physical Data

Component
Nominal Tonnage 3 4 5
ARI COOLING PERFORMANCE
Gross Capacity @ AHRI A point (Btu) 36600 49100 59000 AHRI net capacity (Btu) 35500 47500 57000 EER 12.0 12.0 11.8 SEER 14.0 14.0 14.0 IPLV --­CFM 1200 1450 1680 System power (KW) 2.96 3.96 4.83 Refrigerant type R-410A R-410A R-410A Refrigerant charge (lb-oz) System 1 4-4 5-6 6-6
AHRI HEATING PERFORMANCE
Heating model N04 N08 D06 D10 N06 N10 D06 D10 N08 N10 D06 D10 Heat input (K Btu) 50 100 75 115 75 125 75 125 100 125 75 125 Heat output (K Btu) 40 80 60.8 92 60 100 60.8 100.6 80 100 60.8 100.6 AFUE % 8181 - - 8181 - - 8181 - ­Steady state efficiency (%) - - 81.1 80.2 - - 81.1 80.5 - - 81.1 80.5 No. burners 243535354535 No. stages 1 1 2 2 1 1 2 2 1 1 2 2 Temperature Rise Range (ºF) 15-45 45-75 35-70 55-90 25-70 45-75 25-70 45-75 25-55 35-75 20-55 35-75 Gas Limit Setting (ºF) - Direct Drive 240 170 210 200 210 165 210 165 170 165 210 165 Gas Limit Setting (ºF) - Belt Drive 240 210 240 200 240 210 240 210 210 210 210 210 Gas piping connection (in.) 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 DIMENSIONS (inches) Length 82 1/4 82 1/4 82 1/4 Width 44 7/8 44 7/8 44 7/8 Height 32 5/8 32 5/8 32 5/8
OPERATING WT. (lbs.) 470 598 632
COMPRESSORS
Type SCROLL SCROLL SCROLL Quantity 1 1 1 Unit Capacity Steps (%) 100 100 100
CONDENSER COIL DATA
Face area (Sq. Ft.) 16.3 16.3 16.3 Rows 111 Fins per inch 23 23 23 Tube diameter (in.) 0.7 1 / 18 0.71 / 18 1.00 / 25.4 Circuitry Type 2-pass Microchannel 2-pass Microchannel 2-pass Microchannel
EVAPORATOR COIL DATA
Face area (Sq. Ft.) 5.06 5.06 5.06 Rows 344 Fins per inch 13 13 13 Tube diameter 0.375 0.375 0.375 Circuitry Type Intertwined Intertwined Intertwined Refrigerant control Orifice Orifice TXV
ZE036 ZE048 ZE060
Models
12 Johnson Controls Unitary Products
ZE036-060 Physical Data (Continued)
251933-YTG-X-0615
Component
Nominal Tonnage 3 4 5
CONDENSER FAN DATA
Quantity of fans 1 1 1 Fan diameter (Inch) 24 24 24 Type Prop Prop Prop Drive type Direct Direct Direct Quantity of motors 1 1 1 Motor HP each 1/2 1/2 1/2 No. speeds 1 1 1 RPM 1090 1090 1100 CFM 4000 4000 4200
BELT DRIVE EVAP FAN DATA
Quantity 1 1 1 Fan Size (Inch) 12 x 10 12 x 10 12 x 10 Type Centrifugal Centrifugal Centrifugal Motor Sheave 1VL44 1VP56 1VL44 1VP56 1VL44 1VP56 Blower Sheave AK64 AK66 AK56 AK61 AK56 AK56 Belt A37 A39 A36 A38 A36 A38 Motor HP each 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 2 RPM 1740 1740 1740 Frame size 56 56 56
DIRECT DRIVE EVAP FAN DATA
Quantity 1 1 1 Fan Size (Inch) 12 x 10 12 x 10 12 x 10 Type Centrifugal Centrifugal Centrifugal Motor HP each 1/2 1 1 RPM 1050 1050 1050 FILTERS 15" x 20" x 1" or 2" 2 2 2 14" x 25" x 1" or 2" 1 1 1 NOTE: All 2 Stage Gas Heat, 60% Capacity 1
st
ZE036 ZE048 ZE060
Stage , 40% 2nd Stage
Models
Johnson Controls Unitary Products 13
251933-YTG-X-0615

ZF036-060 Physical Data

Component
Nominal Tonnage 3.0 4.0 5.0
AHRI COOLING PERFORMANCE
Gross Capacity @ AHRI A point (Btu) AHRI net capacity (Btu) EER SEER IPLV CFM System power (KW) Refrigerant type Refrigerant charge (lb-oz)
System 1 4-4 5-8 5-8
AHRI HEATING PERFORMANCE
Heating model Heat input (K Btu) Heat output (K Btu) AFUE % Steady state efficiency (%) No. burners No. stages Temperature Rise Range (ºF) 15-45 45-75 35-70 55-90 25-70 45-75 25-70 45-75 25-55 35-75 20-55 35-75 Gas Limit Setting (ºF) - Direct Drive 240 170 210 200 210 165 210 165 170 165 210 165 Gas Limit Setting (ºF) - Belt Drive 240 210 240 200 240 210 240 210 210 210 210 210 Gas piping connection (in.)
DIMENSIONS (inches)
Length Width Height
OPERATING WT. (lbs.)
COMPRESSORS
Type Quantity Unit Capacity Steps (%)
CONDENSER COIL DATA
Face area (Sq. Ft.) 16.3 16.3 16.3 Rows Fins per inch Tube diameter (in.) Circuitry Type
EVAPORATOR COIL DATA
Face area (Sq. Ft.) Rows Fins per inch Tube diameter Circuitry Type Refrigerant control
N04 N08 D06 D10 N06 N10 D06 D10 N08 N10 D06 D10
50 100 75 115 75 125 75 125 100 125 75 125 40 80 60.8 92 60 100 60.8 100.6 80 100 60.8 100.6
- - - - - - - - - - --
- - 80.0 80.0 - - 80.0 80.0 - - 80.0 80.0 2 4 3 5 3 5 3 5 4 5 35 1 1 2 2 1 1 2 2 1 1 22
1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
ZF036 ZF048 ZF060
37000 49300 59000 35500 47500 56500
11.0 11.0 10.8
13.0 13.0 13.0
- - -
1200 1500 1750
3.23 4.32 5.23
R-410A R-410A R-410A
82 1/4 82 1/4 82 1/4 44 7/8 44 7/8 44 7/8 32 5/8 32 5/8 32 5/8
468 541 569
Recip Recip Recip
1 1 1
100 100 100
1 1 1
23 23 23
0.71 / 18 0.71 / 18 0.71 / 18
2-pass Microchannel 2-pass Microchannel 2-pass Microchannel
5.06 5.06 5.06 3 3 4
13 13 13
0.375 0.375 0.375
Intertwined Intertwined Intertwined
Orifice Orifice Orifice
Models
14 Johnson Controls Unitary Products
ZF036-060 Physical Data (Continued)
251933-YTG-X-0615
Component
Nominal Tonnage 3.0 4.0 5.0
CONDENSER FAN DATA
Quantity Fan diameter (Inch) Type Drive type Quantity of motors Motor HP each No. speeds RPM CFM
BELT DRIVE EVAP FAN DATA
Quantity Fan Size (Inch) Type Motor Sheave 1VL44 1VP56 1VL44 1VP56 1VL44 1VP56 Blower Sheave AK64 AK66 AK56 AK61 AK56 AK56 Belt A37 A39 A36 A38 A36 A38 Motor HP each 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 2 RPM Frame size
DIRECT DRIVE EVAP FAN DATA
Quantity Fan Size (Inch) Type Motor HP each RPM
FILTERS
15” x 20” x 1” or 2” 14” x 25” x 1” or 2”
ZF036 ZF048 ZF060
1 1 1
24 24 24
Prop Prop Prop
Direct Direct Direct
1 1 1
1/2 1/2 1/2
1 1 1
1090 1090 1090 3800 4200 4200
1 1 1
11 x 10 11 x 10 11 x 10
Centrifugal Centrifugal Centrifugal
1725 1725 1725
56 56 56
1 1 1
12 x 10 12 x 10 12 x 10
Centrifugal Centrifugal Centrifugal
1/2 1 1
1050 1050 1050
2 2 2 1 1 1
Models
NOTE: All 2 Stage Gas Heat, 60% Capacity 1
st
Stage, 40% Capacity 2nd Stage.
Johnson Controls Unitary Products 15
251933-YTG-X-0615

ZF072 Physical Data

Component
Models
ZF072
Nominal Tonnage 6.0
AHRI COOLING PERFORMANCE
Gross Capacity @ AHRI A point (Btu) 70360 AHRI net capacity (Btu) 68000
1
EER 11.2
/ 11.0
2
IEER 11.3 CFM 2000 System power (KW) 6.07 Refrigerant type R-410A Refrigerant charge (lb-oz)
System 1 6-4
AHRI HEATING PERFORMANCE
Heating model N08 N10 D06 D10 Heat input (K Btu) 100 125 75 125 Heat output (K Btu) 80 100 60.8 100.6 AFUE % ---­Steady state efficiency (%) - - 80.0 80.0 No. burners 4535 No. stages 1122 Temperature Rise Range (ºF) 25-55 30-75 15-45 30-75 Gas Limit Setting (ºF) - Direct Drive 170 165 210 165 Gas Limit Setting (ºF) - Belt Drive 210 210 210 210 Gas piping connection (in.) 1/2 1/2 1/2 1/2
DIMENSIONS (inches)
Length 82 1/4 Width 44 7/8 Height 32 5/8
OPERATING WT. (lbs.) 640
COMPRESSORS
Type Scroll Quantity 1 Unit Capacity Steps (%) 100
CONDENSER COIL DATA
Face area (Sq. Ft.) 16.3 Rows 1 Fins per inch 23 Tube diameter (in.) 1.0 / 25.4 Circuitry Type 2-pass Microchannel
EVAPORATOR COIL DATA
Face area (Sq. Ft.) 5.06 Rows 4 Fins per inch 13 Tube diameter 0.375 Circuitry Type Intertwined Refrigerant control Fixed Orifice
16 Johnson Controls Unitary Products
ZF072 Physical Data (Continued)
251933-YTG-X-0615
Component
Models
ZF072
Nominal Tonnage 6.0
CONDENSER FAN DATA
Quantity 1 Fan diameter (Inch) 24 Type Prop Drive type Direct Drive No. speeds 1 Number of motors 1 Motor HP each 1/2
3
1/2
4
RPM 1100 1090 CFM 4200 4200
BELT DRIVE EVAP FAN DATA
Quantity 1 Fan Size (Inch) 12 x 10 Type Centrifugal Motor Sheave 1VL44 1VP56 Blower Sheave AK56 AK56 Belt A36 A38 Motor HP each 1-1/2 3 RPM 1725 Frame size 56
DIRECT DRIVE EVAP FAN DATA
Quantity 1 Fan Size (Inch) 12 x 10 Type Centrifugal Motor HP each 1 RPM 1050
FILTERS
15” x 20” x 1” or 2” 2 14” x 25” x 1” or 2” 1
1. Cooling Only or Cooling with Electric Heat Unit
2. Cooling with Gas Heat Unit
3. Cooling Only or Cooling with Electric Heat Unit (ECM O.D. Fan Motor)
4. Cooling with Gas Heat Unit (PSC O.D. Fan Motor) NOTE: All 2 Stage Gas Heat, 60% Capacity 1st Stage, 40% Capacity 2nd Stage.
Johnson Controls Unitary Products 17
251933-YTG-X-0615

ZR036-060 Physical Data

Component
Nominal Tonnage 3.0 4.0 5.0
AHRI COOLING PERFORMANCE
Gross Capacity @ AHRI A point (Btu) 36300 49600 60800 AHRI net capacity (Btu) 35000 48000 58500 EER 11.2 11.2 11.2 SEER 13.0 13.0 13.0 IPLV --­CFM 1200 1600 2000 System power (KW) 3.13 4.18 5.3 Refrigerant type R-410a R-410a R-410a Refrigerant charge (lb-oz)
System 1 11-2 12-4 11-12
AHRI HEATING PERFORMANCE
Heating model N04 N08 D06 D10 N06 N10 D06 D10 N08 N10 D06 D10 Heat input (K Btu) 50 100 75 115 75 125 75 125 100 125 75 125 Heat output (K Btu) 40 80 60.8 92 60 100 60.8 100.6 80 100 60.8 100.6 AFUE % -----------­Steady state efficiency (%) - - 80.0 80.0 - - 80.0 80.0 - - 80.0 80.0 No. burners 243535354535 No. stages 112211221122 Temperature Rise Range (ºF) 15-45 45-75 35-70 55-90 25-70 45-75 25-70 45-75 25-55 35-75 20-55 35-75 Gas Limit Setting (ºF) - Direct Drive 240 170 210 200 210 165 210 165 170 165 210 165 Gas Limit Setting (ºF) - Belt Drive 240 210 240 200 240 210 240 210 210 210 210 210 Gas piping connection (in.) 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
DIMENSIONS (inches)
Length 82 1/4 82 1/4 82 1/4 Width 44 7/8 44 7/8 44 7/8 Height 32 5/8 32 5/8 32 5/8
OPERATING WT. (lbs.) 575 585 590
COMPRESSORS
Type Scroll Scroll Scroll Quantity 1 1 1 Unit Capacity Steps (%) 100 100 100
CONDENSER COIL DATA
Face area (Sq. Ft.) 16.9 16.9 16.9 Rows 222 Fins per inch 18 18 18 Tube diameter (in.) 3/8 3/8 3/8 Circuitry Type Split-face Split-face Split-face
EVAPORATOR COIL DATA
Face area (Sq. Ft.) 5.06 5.06 5.06 Rows 334 Fins per inch 13 13 13 Tube diameter 0.375 0.375 0.375 Circuitry Type Split-face Split-face Split-face Refrigerant control TXV TXV TXV
ZR036 ZR048 ZR060
Models
18 Johnson Controls Unitary Products
ZR036-060 Physical Data (Continued)
251933-YTG-X-0615
Component
Nominal Tonnage 3.0 4.0 5.0
CONDENSER FAN DATA
Quantity 1 1 1 Fan diameter (Inch) 24 24 24 Type Prop Prop Prop Drive type Direct Drive Direct Drive Direct Drive No. speeds 1 1 1 Number of motors 1 1 1 Motor HP each 1/2 1/2 1/2 RPM 1090 1090 1090 CFM 4200 4200 4200
BELT DRIVE EVAP FAN DATA
Quantity 1 1 1 Fan Size (Inch) 11 x 10 11 x 10 11 x 10 Type Centrifugal Centrifugal Centrifugal Motor Sheave 1VL44 1VP56 1VL44 1VP56 1VL44 1VP56 Blower Sheave AK64 AK66 AK56 AK61 AK56 AK56 Belt A37 A39 A36 A38 A36 A38 Motor HP each 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 2 RPM 1725 1725 1725 Frame size 56 56 56
DIRECT DRIVE EVAP FAN DATA
Quantity 1 1 1 Fan Size (Inch) 11 x 10 11 x 10 11 x 10 Type Centrifugal Centrifugal Centrifugal Motor HP each 1/2 1 1 RPM 1050 1050 1050
FILTERS
15” x 20” x 1” or 2” 2 2 2 14” x 25” x 1” or 2” 1 1 1
ZR036 ZR048 ZR060
Models
NOTE: All 2 Stage Gas Heat, 60% Capacity 1
st
Stage, 40% Capacity 2nd Stage.
Johnson Controls Unitary Products 19
251933-YTG-X-0615

XN036-060 Physical Data

Component
Nominal Tonnage 3 4 5
AHRI COOLING PERFORMANCE
Gross Capacity @ AHRI A point (Btu) 38,400 48,700 AHRI net capacity (MBH) 37,000 47,000 EER 12.0 11.8 SEER 14.0 14.0 CFM 1200 1450 System power (KW) 3.08 3.98 Refrigerant type R410A R410A
Refrigerant charge (lb-oz) System 1 13-8 13-10
ARI HEATING PERFORMANCE
47ºF capacity rating (MBH) 36,000 44,000 System power (KW) / COP 3.15 (kW) / 3.35 4.03 (kW) / 3.20 17ºF capacity rating (MBH) 19,000 24,900 System power (KW) / COP 2.5 (kW) / 2.2 3.48 (kW) / 2.10 HSPF (Btu/Watts-hr) 8.00 8.00
DIMENSIONS (inches)
Length 82-1/4 82-1/4 Width 44-7/8 44-7/8 Height 32-5/8 32-5/8
OPERATING WT. (lbs.) 610 616
COMPRESSORS
Type SCROLL SCROLL Quantity 1 1
CONDENSER COIL DATA
Face area (Sq. Ft.) 16.88 16.88 Rows 2 2 Fins per inch 18 18 Tube diameter 3/8 3/8 Circuitry Type Split-face Split-face
Refrigerant control TXV TXV TXV
EVAPORATOR COIL DATA
Face area (Sq. Ft.) 5.06 5.06 Rows 4 4 Fins per inch 13 13 Tube diameter 0.375 0.375 Circuitry Type Split-face Split-face Refrigerant control TXV TXV
XN036 XN048 XN060
Models
5,750
55,400
11.0
14.0
1275/1850
5.04
R410A
11-10
51,500
4.5 (kW) / 3.35 30,000
4.11 (kW) / 2.14
8.00
82-1/4 44-7/8 32-5/8
620
SCROLL
1
16.88 2
18
3/8
Split-face
5.06 4
13
0.375
Split-face
TXV
20 Johnson Controls Unitary Products
XN036-060 Physical Data (Continued)
251933-YTG-X-0615
Component
Nominal Tonnage 3 4 5
CONDENSER FAN DATA
Quantity 1 1 Fan diameter (Inch) 24 24 Type Prop Prop Drive type DIRECT DRIVE DIRECT DRIVE No. speeds 1 1 Number of motors 1 1 Motor HP each 1/4 1/4 RPM 850 850 CFM 3000 3300
BELT DRIVE EVAP FAN DATA
Quantity 1 1 Fan diameter (Inch) 12 x 10 12 x 10 Type Centrifugal Centrifugal
Motor Sheave 1VL44 1VP56 1VL44 1VP56 1VL44 1VP56 Blower Sheave AK64 AK66 AK56 AK61 AK56 AK56 Belt A37 A39 A36 A38 A36 A38 Motor HP each 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 2
RPM 1740 1740 Frame size 56 56
DIRECT DRIVE EVAP FAN DATA
Quantity 1 1 Fan Size (Inch) 12 x 10 12 x 10 Type Centrifugal Centrifugal Motor HP each 1/2 1 RPM 1050 1050
FILTERS
15" x 20" x 1" or 2" 2 2 14" x 25" x 1" or 2" 1 1
XN036 XN048 XN060
Models
1
24
Prop
DIRECT DRIVE
2 1
1/2
850/1100
2800/3800
1
12 x 10
Centrifugal
1740
56
1
12 x 10
Centrifugal
1
1050
2 1
Johnson Controls Unitary Products 21
251933-YTG-X-0615

XP036-060 Physical Data

Component
Nominal Tonnage 3.0 4.0 5.0
AHRI COOLING PERFORMANCE
Gross Capacity @ AHRI A point (Btu) 37,500 46500 60100 AHRI net capacity (Btu) 36,000 44500 57500 EER 11.4 11.0 10.6 SEER 13.0 13.0 13.0 CFM 1300 1600 1850 System power (KW) 3.30 4.05 5.42 Refrigerant type R410A R410A R-410A Refrigerant charge (lb-oz) 13-8 13-12 12-10
AHRI HEATING PERFORMANCE
47°F capacity rating (MBH) 35,000 41,000 56500 System power (KW) / COP 3.10 (kW) / 3.30 4.0 (kW) / 3.20 5.4 (kW) / 3.10 17°F capacity rating (MBH 21,200 22,400 34400 System power (KW) / COP 2.89(kW) / 2.15 3.8 (kW) / 2.10 4.75 (kW) / 2.10 HSPF (Btu/Watts-hr) 7.70 7.70 7.70
DIMENSIONS (inches)
Length 82-1/4 82-1/4 82-1/4 Width 44-7/8 44-7/8 44-7/8 Height 32-5/8 32-5/8 32-5/8
OPERATING WT. (lbs.) 575 585 590
COMPRESSORS
Type Scroll Scroll Scroll Quantity 1 1 1
CONDENSER COIL DATA
Face area (Sq. Ft.) 16.88 16.88 16.88 Rows 222 Fins per inch 18 18 18 Tube diameter 3/8 3/8 3/8 Circuitry Type Split-face Split-face Split-face
EVAPORATOR COIL DATA
Face area (Sq. Ft.) 5.06 5.06 5.06 Rows 444 Fins per inch 13 13 13 Tube diameter 0.375 0.375 0.375 Circuitry Type Split-face Split-face Split-face Refrigerant control TXV TXV TXV
XP036 XP048 XP060
Models
22 Johnson Controls Unitary Products
XP036-060 Physical Data (Continued)
251933-YTG-X-0615
Component
Nominal Tonnage 3.0 4.0 5.0
CONDENSER FAN DATA
Quantity 1 1 1 Fan diameter (Inch) 24 24 24 Type Prop Prop Prop Drive type Direct Drive Direct Drive Direct Drive No. speeds 1 1 1 Number of motors 1 1 1 Motor HP each 1/4 1/4 1/2 RPM 850 850 1090 Nominal total CFM 3275 3800 4200
BELT DRIVE EVAP FAN DATA
Quantity 1 1 1 Fan Size (Inch) 11 x 10 11 x 10 11 x 10 Type Centrifugal Centrifugal Centrifugal Motor Sheave 1VL44 1VP56 1VL44 1VP56 1VL44 1VP56 Blower Sheave AK64 AK66 AK56 AK61 AK56 AK56 Belt A37 A39 A36 A38 A36 A38 Motor HP each 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 2 RPM 1725 1725 1725 Frame size 56 56 56
DIRECT DRIVE EVAP FAN DATA
Quantity 1 1 1 Fan Size (Inch) 11 x 10 11 x 10 11 x 10 Type Centrifugal Centrifugal Centrifugal Motor HP each 3/4 1 1 RPM 1050 1050 1050
FILTERS
15” x 20” x 1” or 2” 2 2 2 14” x 25” x 1” or 2” 1 1 1
XP036 XP048 XP060
Models
Johnson Controls Unitary Products 23
251933-YTG-X-0615

ZF/ZR/XP036-072 Unit Limitations

Size
(Tons)
ZF/ZR/XP036
(3.0)
ZF/ZR/XP048
(4.0)
ZF/ZR/XP060
(5.0)
ZF072
(6.0)
Unit Voltage
208/230-3-60 187 252 125
460-3-60 432 504 125 575-3-60 540 630 125
208/230-3-60 187 252 125
460-3-60 432 504 125 575-3-60 540 630 125
208/230-3-60 187 252 125
460-3-60 432 504 125 575-3-60 540 630 125
208/230-3-60 187 252 125
460-3-60 432 504 125 575-3-60 540 630 125

ZE/XN036-060 Unit Limitations

Size
(Tons)
ZE/XN036
(3.0)
ZE/XN048
(4.0)
ZE/XN060
(5.0)
Unit Voltage
208/230-1-60 187 252 125 208/230-3-60 187 252 125
460-3-60 432 504 125
575-3-60 540 630 125 208/230-1-60 187 252 125 208/230-3-60 187 252 125
460-3-60 432 504 125
575-3-60 540 630 125 208/230-1-60 187 252 125 208/230-3-60 187 252 125
460-3-60 432 504 125
575-3-60 540 630 125
Unit Limitations
Applied Voltage Outdoor DB Temp
Min Max Max (°F)
Unit Limitations
Applied Voltage Outdoor DB Temp
Min Max Max (°F)
24 Johnson Controls Unitary Products

Capacity Performance

ZE036-060 Cooling Capacities

ZE036 (3.0 Ton)

Air on
Evaporator Coil
CFM
750
900
1050
1200
1350
1500
750
900
1050
1200
1350
1500
WB (°F)
77 44.0 2.0 19.5 16.3 13.2 - - - 42.2 2.3 18.7 15.6 12.5 - - ­72 41.5 2.0 24.6 21.5 18.3 15.2 - - 39.2 2.2 23.6 20.4 17.3 14.1 - ­67 39.1 2.0 29.7 26.6 23.4 20.3 17.2 - 36.2 2.2 28.4 25.2 22.1 18.9 15.8 ­62 36.2 1.9 36.2 31.7 28.5 25.4 22.2 19.1 33.4 2.2 33.4 31.1 26.9 23.8 20.6 17.5 77 45.5 2.0 21.4 17.9 14.3 - - - 43.7 2.3 20.8 17.2 13.6 - - ­72 43.0 2.0 27.0 23.4 19.9 16.3 - - 40.6 2.2 26.1 22.5 18.9 15.3 - ­67 40.5 2.0 32.6 29.0 25.4 21.9 18.3 - 37.5 2.2 31.3 27.7 24.1 20.5 16.9 ­62 37.5 1.9 37.5 34.5 31.0 27.4 23.8 20.2 34.6 2.2 34.6 33.0 29.4 25.8 22.2 18.6 57 35.9 1.9 35.9 35.9 34.3 30.7 27.1 23.5 34.1 2.2 34.1 34.1 31.2 27.6 24.0 20.4 77 47.1 2.0 23.4 19.4 15.4 - - - 45.3 2.3 22.9 18.9 14.8 - - ­72 44.5 2.0 29.4 25.4 21.4 17.4 - - 42.0 2.2 28.6 24.6 20.5 16.4 - ­67 41.9 1.9 35.4 31.4 27.4 23.4 19.5 - 38.8 2.2 34.3 30.3 26.2 22.1 18.1 ­62 38.8 1.9 38.8 37.3 33.4 29.4 25.4 21.4 35.8 2.2 35.8 35.0 31.9 27.9 23.8 19.7 57 37.1 1.9 37.1 37.1 37.0 33.0 29.0 25.0 35.3 2.2 35.3 35.3 33.8 29.8 25.7 21.6 77 48.7 2.0 25.4 21.0 16.5 - - - 46.8 2.3 25.0 20.5 15.9 - - ­72 46.0 1.9 31.8 27.4 23.0 18.6 - - 43.4 2.2 31.2 26.6 22.1 17.6 - ­67 43.3 1.9 38.3 33.9 29.4 25.0 20.6 - 40.1 2.2 37.3 32.8 28.3 23.7 19.2 ­62 40.1 1.9 40.1 40.1 35.8 31.4 27.0 22.6 37.0 2.2 37.0 37.0 34.5 29.9 25.4 20.9 57 38.4 1.9 38.4 38.4 38.4 35.3 30.8 26.4 36.5 2.2 36.5 36.5 36.5 32.0 27.4 22.9 72 47.4 1.9 35.0 30.4 25.7 21.1 - - 44.2 2.2 33.4 28.5 23.5 18.6 - ­67 44.6 1.9 42.1 37.6 32.9 28.3 23.6 - 40.8 2.2 39.5 35.0 30.1 25.2 20.2 ­62 41.3 1.9 41.3 41.3 39.5 34.9 30.2 25.6 37.7 2.2 37.7 37.7 36.4 31.5 26.6 21.6 57 39.5 1.9 39.5 39.5 39.5 36.2 31.5 26.9 37.2 2.2 37.2 37.2 37.2 32.2 27.3 22.4 72 48.8 1.9 38.2 33.3 28.5 23.6 - - 45.1 2.2 35.7 30.3 25.0 19.6 - ­67 45.9 1.9 45.9 41.3 36.4 31.6 26.7 - 41.6 2.2 41.6 37.3 31.9 26.6 21.3 ­62 42.5 1.9 42.5 42.5 42.5 38.4 33.5 28.7 38.4 2.2 38.4 38.4 38.4 33.1 27.7 22.4 57 40.7 1.9 40.7 40.7 40.7 37.1 32.2 27.4 37.9 2.2 37.9 37.9 37.9 32.5 27.2 21.8
77 40.5 2.5 18.0 14.9 11.7 - - - 36.0 2.9 13.6 11.5 8.5 - - ­72 36.9 2.5 22.5 19.4 16.2 13.1 - - 33.0 2.9 19.9 16.8 13.7 10.7 - ­67 33.3 2.5 27.0 23.8 20.7 17.6 14.5 - 30.0 2.9 26.1 22.0 19.0 15.9 12.8 ­62 30.6 2.5 30.6 30.4 25.3 22.2 19.1 15.9 27.7 2.9 27.7 27.5 22.5 19.4 16.3 13.3 77 42.0 2.5 20.2 16.6 13.0 - - - 37.3 2.9 16.6 13.0 9.4 - - ­72 38.2 2.5 25.2 21.5 17.9 14.3 - - 34.2 2.9 22.5 18.9 15.3 11.7 - ­67 34.5 2.5 30.1 26.5 22.8 19.2 15.6 - 31.1 2.9 28.4 24.8 21.2 17.5 13.9 ­62 31.7 2.5 31.7 31.5 27.9 24.3 20.6 17.0 28.6 2.9 28.6 28.6 25.0 21.4 17.8 14.2 57 32.4 2.5 32.4 31.7 28.1 24.4 20.8 17.2 29.1 2.9 29.1 28.7 25.1 21.5 17.8 14.2 77 43.4 2.5 22.4 18.3 14.2 - - - 38.5 2.9 19.6 14.5 10.3 - - ­72 39.5 2.5 27.8 23.7 19.6 15.4 - - 35.3 2.9 25.1 21.0 16.8 12.7 - ­67 35.7 2.5 33.2 29.1 25.0 20.8 16.7 - 32.1 2.9 30.7 27.5 23.3 19.2 15.0 ­62 32.8 2.5 32.8 32.7 30.5 26.4 22.2 18.1 29.6 2.8 29.6 29.6 27.6 23.5 19.3 15.2 57 33.5 2.5 33.5 33.1 30.7 26.5 22.4 18.3 30.1 2.8 30.1 29.9 27.6 23.5 19.3 15.2 77 44.9 2.5 24.6 20.0 15.4 - - - 39.8 2.9 22.6 16.0 11.3 - - ­72 40.9 2.5 30.5 25.8 21.2 16.6 - - 36.5 2.9 27.8 23.1 18.4 13.7 - ­67 36.9 2.5 36.3 31.7 27.1 22.4 17.8 - 33.2 2.9 32.9 30.2 25.5 20.8 16.1 ­62 33.9 2.5 33.9 33.9 33.1 28.4 23.8 19.2 30.6 2.8 30.6 30.6 30.2 25.5 20.8 16.1 57 34.6 2.5 34.6 34.6 33.3 28.6 24.0 19.4 31.1 2.8 31.1 31.1 30.2 25.5 20.8 16.1 72 41.1 2.6 31.8 26.6 21.4 16.1 - - 36.8 2.9 29.4 24.1 18.9 13.7 - ­67 37.1 2.5 36.8 32.5 27.3 22.0 16.8 - 33.5 2.9 33.3 31.0 26.3 21.1 15.9 ­62 34.1 2.5 34.1 34.1 33.3 28.1 22.9 17.7 30.9 2.9 30.9 30.9 30.5 25.2 20.0 14.8 57 34.8 2.5 34.8 34.8 33.5 28.3 23.1 17.8 31.4 2.9 31.4 31.4 30.6 25.4 20.2 14.9 72 41.3 2.6 33.1 27.3 21.5 15.7 - - 37.1 2.9 31.0 25.2 19.5 13.7 - ­67 37.3 2.6 37.3 33.3 27.4 21.6 15.8 - 33.8 2.9 33.8 31.7 27.1 21.4 15.6 ­62 34.3 2.5 34.3 34.3 33.5 27.7 21.9 16.1 31.1 2.9 31.1 31.1 30.8 25.0 19.2 13.5 57 35.0 2.5 35.0 35.0 33.7 27.9 22.1 16.3 31.7 2.9 31.7 31.7 31.0 25.3 19.5 13.8
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
251933-YTG-X-0615
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 25
251933-YTG-X-0615
ZE036 (3.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
750
900
1050
1200
1350
1500
WB (°F)
77 31.5 3.3 9.2 8.2 5.2 - - - 27.0 3.7 5.7 4.1 1.9 - - ­72 29.1 3.3 17.2 14.2 11.2 8.2 - - 25.2 3.6 14.6 11.6 8.7 5.7 - ­67 26.7 3.2 25.2 20.2 17.2 14.2 11.2 - 23.4 3.6 23.4 18.4 15.5 12.6 9.6 ­62 24.7 3.3 24.7 24.7 19.6 16.6 13.6 10.6 21.8 3.6 21.8 21.8 16.8 13.9 10.9 8.0 77 32.6 3.3 13.0 9.4 5.8 - - - 27.9 3.7 10.1 5.9 2.3 - - ­72 30.1 3.2 19.8 16.2 12.7 9.1 - - 26.1 3.6 17.2 13.6 10.0 6.5 - ­67 27.7 3.2 26.6 23.1 19.5 15.9 12.3 - 24.2 3.6 24.2 21.4 17.8 14.2 10.7 ­62 25.6 3.2 25.6 25.6 22.2 18.6 15.0 11.4 22.5 3.6 22.5 22.5 19.3 15.8 12.2 8.6 57 25.9 3.2 25.9 25.7 22.1 18.5 14.9 11.3 22.7 3.6 22.7 22.6 19.1 15.5 11.9 8.4 77 33.7 3.3 16.8 10.7 6.5 - - - 28.8 3.6 14.5 7.6 2.7 - - ­72 31.1 3.2 22.5 18.3 14.1 9.9 - - 26.9 3.6 19.8 15.6 11.4 7.2 - ­67 28.6 3.2 28.1 25.9 21.7 17.5 13.4 - 25.0 3.6 25.0 24.3 20.1 15.9 11.7 ­62 26.4 3.2 26.4 26.4 24.7 20.6 16.4 12.2 23.3 3.6 23.3 23.3 21.8 17.7 13.5 9.3 57 26.8 3.2 26.8 26.7 24.6 20.4 16.3 12.1 23.4 3.6 23.4 23.4 21.6 17.4 13.2 9.0 77 34.8 3.3 20.6 11.9 7.2 - - - 29.8 3.6 18.9 9.3 3.1 - - ­72 32.2 3.2 25.1 20.3 15.6 10.8 - - 27.8 3.6 22.4 17.6 12.7 7.9 - ­67 29.5 3.2 29.5 28.7 23.9 19.2 14.4 - 25.8 3.5 25.8 25.8 22.4 17.6 12.7 ­62 27.3 3.2 27.3 27.3 27.3 22.5 17.8 13.0 24.0 3.6 24.0 24.0 24.0 19.6 14.7 9.9 57 27.7 3.2 27.7 27.7 27.1 22.4 17.6 12.9 24.2 3.5 24.2 24.2 24.1 19.2 14.4 9.6 72 32.5 3.3 26.9 21.7 16.5 11.3 - - 28.3 3.6 24.5 19.3 14.1 8.8 - ­67 29.9 3.2 29.9 29.5 25.4 20.1 14.9 - 26.3 3.6 26.3 26.3 24.4 19.2 14.0 ­62 27.6 3.2 27.6 27.6 27.6 22.4 17.2 11.9 24.4 3.6 24.4 24.4 24.4 19.5 14.3 9.1 57 28.0 3.2 28.0 28.0 27.7 22.5 17.3 12.0 24.6 3.6 24.6 24.6 24.6 19.6 14.4 9.1 72 32.9 3.3 28.8 23.1 17.4 11.7 - - 28.7 3.6 26.7 21.0 15.4 9.7 - ­67 30.2 3.3 30.2 30.2 26.8 21.1 15.4 - 26.7 3.6 26.7 26.7 26.5 20.8 15.2 ­62 28.0 3.3 28.0 28.0 28.0 22.3 16.6 10.9 24.8 3.6 24.8 24.8 24.8 19.5 13.9 8.2 57 28.3 3.3 28.3 28.3 28.3 22.6 16.9 11.2 25.0 3.6 25.0 25.0 25.0 20.0 14.3 8.7
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input (kW)
Sensible Capacity (MBh)
2
26 Johnson Controls Unitary Products

ZE048 (4.0 Ton)

Air on
Evaporator Coil
CFM
1000
1200
1400
1600
1800
2000
1000
1200
1400
1600
1800
2000
WB (°F)
77 60.0 2.6 27.4 22.9 18.4 - - - 58.1 3.1 26.4 22.0 17.5 - - ­72 56.4 2.5 34.3 29.8 25.3 20.8 - - 54.1 3.0 33.1 28.6 24.2 19.7 - ­67 52.8 2.4 41.1 36.6 32.1 27.6 23.1 - 50.1 2.9 39.7 35.3 30.8 26.4 22.0 ­62 48.4 2.4 48.4 43.6 38.7 34.2 29.7 25.2 45.8 2.9 45.8 43.4 37.4 33.0 28.6 24.1 77 62.1 2.7 30.0 25.0 20.0 - - - 59.8 3.1 29.0 24.0 19.0 - - ­72 58.3 2.6 37.4 32.4 27.4 22.3 - - 55.7 3.0 36.2 31.2 26.2 21.1 - ­67 54.6 2.5 44.8 39.8 34.8 29.7 24.7 - 51.6 3.0 43.4 38.4 33.4 28.3 23.3 ­62 50.1 2.5 50.1 46.9 41.9 36.9 31.9 26.8 47.1 2.9 47.1 45.5 40.5 35.5 30.4 25.4 57 47.7 2.4 47.7 47.7 44.8 39.8 34.8 29.7 46.1 2.9 46.1 46.1 42.4 37.3 32.3 27.3 77 64.2 2.7 32.6 27.0 21.5 - - - 61.6 3.2 31.6 26.0 20.4 - - ­72 60.3 2.6 40.5 35.0 29.5 23.9 - - 57.3 3.1 39.4 33.8 28.1 22.5 - ­67 56.5 2.6 48.5 43.0 37.4 31.9 26.3 - 53.1 3.0 47.1 41.5 35.9 30.3 24.6 ­62 51.7 2.5 51.7 50.2 45.1 39.5 34.0 28.5 48.5 3.0 48.5 47.7 43.6 37.9 32.3 26.7 57 49.3 2.4 49.3 49.3 48.2 42.7 37.1 31.6 47.4 2.9 47.4 47.4 45.6 40.0 34.3 28.7 77 66.3 2.8 35.1 29.1 23.0 - - - 63.3 3.2 34.3 28.0 21.8 - - ­72 62.3 2.7 43.7 37.6 31.5 25.5 - - 58.9 3.1 42.6 36.3 30.1 23.9 - ­67 58.3 2.6 52.2 46.1 40.1 34.0 28.0 - 54.5 3.1 50.8 44.6 38.4 32.2 26.0 ­62 53.4 2.6 53.4 53.4 48.3 42.2 36.2 30.1 49.9 3.0 49.9 49.9 46.6 40.4 34.2 28.0 57 50.9 2.5 50.9 50.9 50.9 45.6 39.5 33.4 48.8 3.0 48.8 48.8 48.8 42.6 36.3 30.1 72 63.7 2.7 46.3 39.8 33.2 26.6 - - 60.0 3.2 45.7 38.9 32.1 25.2 - ­67 59.6 2.6 56.6 48.7 42.1 35.5 29.0 - 55.5 3.1 53.6 47.7 40.9 34.1 27.2 ­62 54.7 2.6 54.7 54.7 52.1 45.5 38.9 32.3 50.7 3.0 50.7 50.7 49.1 42.3 35.4 28.6 57 52.1 2.5 52.1 52.1 52.1 45.9 39.3 32.7 49.6 3.0 49.6 49.6 49.6 42.8 36.0 29.1 72 65.2 2.7 49.0 41.9 34.8 27.7 - - 61.0 3.2 48.9 41.5 34.0 26.6 - ­67 61.0 2.6 61.0 51.3 44.2 37.1 30.0 - 56.4 3.1 56.4 50.8 43.4 36.0 28.5 ­62 55.9 2.6 55.9 55.9 55.9 48.8 41.7 34.5 51.6 3.1 51.6 51.6 51.6 44.2 36.7 29.3 57 53.3 2.5 53.3 53.3 53.3 46.1 39.0 31.9 50.5 3.0 50.5 50.5 50.5 43.0 35.6 28.1
77 56.3 3.6 25.4 21.0 16.6 - - - 52.0 4.1 21.4 18.5 14.2 - - ­72 51.8 3.5 31.9 27.5 23.1 18.7 - - 47.3 4.0 29.3 25.0 20.7 16.4 - ­67 47.3 3.4 38.3 34.0 29.6 25.2 20.8 - 42.7 3.9 37.1 31.5 27.2 22.9 18.6 ­62 43.2 3.4 43.2 43.1 36.2 31.8 27.4 23.1 39.2 3.9 39.2 39.2 32.4 28.1 23.8 19.5 77 57.6 3.6 28.1 23.0 18.0 - - - 53.3 4.2 25.6 20.5 15.5 - - ­72 53.1 3.5 35.1 30.0 25.0 19.9 - - 48.6 4.1 32.7 27.7 22.6 17.6 - ­67 48.5 3.4 42.1 37.0 32.0 26.9 21.9 - 43.8 4.0 39.9 34.8 29.8 24.8 19.7 ­62 44.2 3.4 44.2 44.2 39.1 34.1 29.0 24.0 40.2 3.9 40.2 40.2 35.5 30.4 25.4 20.4 57 44.6 3.4 44.6 44.6 40.0 34.9 29.9 24.8 41.0 3.9 41.0 40.8 36.0 31.0 26.0 21.0 77 59.0 3.6 30.7 25.0 19.3 - - - 54.7 4.2 29.7 22.6 16.8 - - ­72 54.3 3.5 38.2 32.5 26.8 21.1 - - 49.8 4.1 36.2 30.4 24.6 18.8 - ­67 49.6 3.5 45.8 40.1 34.3 28.6 22.9 - 45.0 4.0 42.6 38.2 32.4 26.6 20.9 ­62 45.3 3.4 45.3 45.2 42.0 36.3 30.6 24.9 41.3 4.0 41.3 41.3 38.5 32.8 27.0 21.2 57 45.6 3.4 45.6 45.6 43.0 37.2 31.5 25.8 42.1 3.9 42.1 42.0 39.2 33.4 27.6 21.9 77 60.4 3.6 33.4 27.0 20.6 - - - 56.0 4.2 33.8 24.7 18.2 - - ­72 55.6 3.6 41.4 35.1 28.7 22.3 - - 51.1 4.1 39.6 33.1 26.6 20.1 - ­67 50.8 3.5 49.5 43.1 36.7 30.3 24.0 - 46.1 4.0 45.4 41.5 35.0 28.5 22.0 ­62 46.3 3.4 46.3 46.3 45.0 38.6 32.2 25.8 42.3 4.0 42.3 42.3 41.6 35.1 28.6 22.1 57 46.7 3.4 46.7 46.7 45.9 39.6 33.2 26.8 43.1 4.0 43.1 43.1 42.3 35.8 29.3 22.8 72 56.2 3.6 45.1 38.1 31.0 23.9 - - 51.9 4.1 43.0 35.9 28.7 21.5 - ­67 51.3 3.5 50.7 46.7 39.7 32.6 25.5 - 46.8 4.0 46.5 44.1 37.8 30.6 23.5 ­62 46.8 3.5 46.8 46.8 46.1 39.1 32.0 24.9 42.9 4.0 42.9 42.9 42.6 35.4 28.3 21.1 57 47.2 3.5 47.2 47.2 46.8 39.7 32.7 25.6 43.8 4.0 43.8 43.8 43.4 36.2 29.1 21.9 72 56.8 3.6 48.8 41.1 33.3 25.5 - - 52.6 4.2 46.5 38.7 30.8 23.0 - ­67 51.9 3.5 51.9 50.4 42.6 34.8 27.1 - 47.5 4.1 47.5 46.8 40.6 32.8 25.0 ­62 47.3 3.5 47.3 47.3 47.3 39.5 31.8 24.0 43.6 4.0 43.6 43.6 43.6 35.8 28.0 20.2 57 47.7 3.5 47.7 47.7 47.7 39.9 32.1 24.4 44.5 4.0 44.5 44.5 44.5 36.7 28.8 21.0
Total
Capacity
(MBh)
251933-YTG-X-0615
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input (kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 27
251933-YTG-X-0615
ZE048 (4.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
1000
1200
1400
1600
1800
2000
WB (°F)
77 47.6 4.7 17.5 15.9 11.7 - - - 43.3 5.3 14.6 12.5 9.3 - - ­72 42.9 4.6 26.6 22.5 18.3 14.1 - - 38.4 5.2 24.0 19.9 15.9 11.8 - ­67 38.1 4.5 35.8 29.0 24.8 20.6 16.5 - 33.5 5.0 33.5 26.5 22.5 18.4 14.3 ­62 35.3 4.4 35.3 35.3 28.6 24.4 20.2 16.0 31.3 5.0 31.3 31.3 24.7 20.7 16.6 12.5 77 49.0 4.7 23.0 18.0 13.0 - - - 44.7 5.3 21.4 15.6 10.6 - - ­72 44.1 4.6 30.3 25.3 20.3 15.3 - - 39.6 5.2 28.0 23.0 18.0 13.0 - ­67 39.2 4.5 37.6 32.6 27.6 22.6 17.6 - 34.6 5.1 34.6 30.5 25.5 20.5 15.5 ­62 36.3 4.5 36.3 36.3 31.8 26.8 21.8 16.8 32.3 5.0 32.3 32.3 28.1 23.2 18.2 13.2 57 37.5 4.4 37.5 37.1 32.1 27.1 22.1 17.1 34.0 4.9 34.0 33.4 28.2 23.2 18.2 13.2 77 50.3 4.8 28.6 20.2 14.4 - - - 46.0 5.4 28.3 18.6 11.9 - - ­72 45.3 4.7 34.1 28.2 22.4 16.6 - - 40.8 5.2 32.0 26.1 20.2 14.3 - ­67 40.3 4.6 39.5 36.3 30.5 24.6 18.8 - 35.6 5.1 35.6 34.4 28.5 22.6 16.8 ­62 37.3 4.5 37.3 37.3 35.0 29.2 23.4 17.6 33.3 5.0 33.3 33.3 31.5 25.7 19.8 13.9 57 38.6 4.4 38.6 38.3 35.4 29.5 23.7 17.9 35.0 5.0 35.0 34.7 31.6 25.7 19.8 14.0 77 51.7 4.8 34.1 22.3 15.7 - - - 47.4 5.4 35.2 21.6 13.2 - - ­72 46.5 4.7 37.8 31.1 24.5 17.8 - - 42.0 5.3 35.9 29.1 22.4 15.6 - ­67 41.4 4.6 41.4 39.9 33.3 26.6 20.0 - 36.7 5.1 36.7 36.7 31.5 24.8 18.0 ­62 38.3 4.5 38.3 38.3 38.3 31.6 25.0 18.4 34.3 5.1 34.3 34.3 34.3 28.2 21.4 14.6 57 39.6 4.5 39.6 39.6 38.6 32.0 25.4 18.7 36.0 5.0 36.0 36.0 35.0 28.2 21.5 14.7 72 47.5 4.7 40.9 33.7 26.4 19.2 - - 43.2 5.3 38.8 31.5 24.2 16.8 - ­67 42.2 4.6 42.2 41.5 35.9 28.7 21.4 - 37.7 5.1 37.7 37.7 34.1 26.7 19.4 ­62 39.1 4.5 39.1 39.1 39.1 31.8 24.6 17.3 35.2 5.1 35.2 35.2 35.2 28.2 20.9 13.6 57 40.4 4.5 40.4 40.4 39.9 32.7 25.5 18.2 37.0 5.0 37.0 37.0 36.5 29.2 21.9 14.5 72 48.5 4.7 44.1 36.3 28.4 20.5 - - 44.4 5.2 41.8 33.9 26.0 18.1 - ­67 43.1 4.6 43.1 43.1 38.6 30.7 22.9 - 38.7 5.1 38.7 38.7 36.6 28.7 20.8 ­62 39.9 4.5 39.9 39.9 39.9 32.0 24.2 16.3 36.2 5.1 36.2 36.2 36.2 28.3 20.4 12.5 57 41.3 4.5 41.3 41.3 41.3 33.4 25.5 17.7 38.0 5.0 38.0 38.0 38.0 30.1 22.2 14.4
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
Capacity
(MBh)
Total
1
Input (kW)
Sensible Capacity (MBh)
2
28 Johnson Controls Unitary Products

ZE060 (5.0 Ton)

Air on
Evaporator Coil
CFM
1250
1500
1750
2000
2250
2500
1250
1500
1750
2000
2250
2500
WB (°F)
77 74.6 3.2 34.0 28.7 23.4 - - - 70.6 3.8 31.6 26.4 21.1 - - ­72 69.2 3.2 42.2 36.9 31.6 26.3 - - 65.3 3.7 39.7 34.4 29.2 23.9 - ­67 63.8 3.2 50.4 45.1 39.8 34.5 29.2 - 60.1 3.7 47.7 42.5 37.2 32.0 26.7 ­62 58.4 3.1 58.4 56.3 48.8 43.5 38.2 32.9 55.1 3.7 55.1 53.7 45.6 40.4 35.1 29.9 77 76.5 3.3 37.3 31.2 25.1 - - - 72.4 3.8 35.0 29.0 23.0 - - ­72 71.0 3.2 46.1 40.0 33.9 27.9 - - 67.1 3.7 43.8 37.7 31.7 25.7 - ­67 65.4 3.2 54.9 48.8 42.8 36.7 30.6 - 61.7 3.7 52.5 46.5 40.5 34.5 28.5 ­62 59.9 3.2 59.9 58.5 52.4 46.4 40.3 34.2 56.6 3.7 56.6 55.6 49.6 43.6 37.6 31.6 57 59.0 3.1 59.0 59.0 54.1 48.0 41.9 35.9 56.2 3.7 56.2 56.2 50.6 44.5 38.5 32.5 77 78.4 3.3 40.6 33.7 26.9 - - - 74.3 3.8 38.4 31.6 24.9 - - ­72 72.7 3.3 50.0 43.1 36.3 29.5 - - 68.8 3.8 47.8 41.1 34.3 27.5 - ­67 67.1 3.2 59.4 52.5 45.7 38.9 32.1 - 63.3 3.7 57.3 50.5 43.8 37.0 30.2 ­62 61.4 3.2 61.4 60.7 56.1 49.2 42.4 35.6 58.1 3.7 58.1 57.6 53.6 46.9 40.1 33.3 57 60.5 3.2 60.5 60.5 57.8 51.0 44.2 37.4 57.7 3.7 57.7 57.7 54.6 47.9 41.1 34.3 77 80.3 3.3 43.8 36.3 28.7 - - - 76.1 3.8 41.8 34.2 26.7 - - ­72 74.5 3.3 53.9 46.3 38.7 31.1 - - 70.5 3.8 51.9 44.4 36.9 29.4 - ­67 68.7 3.2 63.9 56.3 48.7 41.1 33.6 - 64.9 3.8 62.1 54.6 47.0 39.5 32.0 ­62 62.8 3.2 62.8 62.8 59.7 52.1 44.6 37.0 59.5 3.7 59.5 59.5 57.7 50.1 42.6 35.1 57 62.0 3.2 62.0 62.0 61.6 54.0 46.5 38.9 59.1 3.7 59.1 59.1 58.7 51.2 43.7 36.2 72 81.4 2.6 59.5 51.3 43.0 34.7 - - 71.7 3.8 55.7 47.5 39.3 31.1 - ­67 75.0 2.6 72.6 63.7 54.1 45.8 37.5 - 66.0 3.8 64.6 58.3 50.1 42.0 33.8 ­62 68.6 2.5 68.6 68.6 67.1 58.8 50.5 42.2 60.5 3.7 60.5 60.5 59.6 51.4 43.3 35.1 57 67.8 2.5 67.8 67.8 67.6 59.3 51.0 42.7 60.1 3.7 60.1 60.1 59.9 51.8 43.6 35.4 72 88.2 1.9 65.2 56.2 47.2 38.2 - - 73.0 3.8 59.4 50.6 41.7 32.9 - ­67 81.3 1.9 81.3 71.2 59.6 50.5 41.5 - 67.1 3.8 67.1 62.1 53.2 44.4 35.6 ­62 74.4 1.9 74.4 74.4 74.4 65.4 56.4 47.4 61.6 3.7 61.6 61.6 61.6 52.7 43.9 35.1 57 73.6 1.9 73.6 73.6 73.6 64.5 55.5 46.5 61.1 3.7 61.1 61.1 61.1 52.3 43.5 34.7
77 66.5 4.3 29.3 24.1 18.9 - - - 61.4 4.9 24.0 19.8 14.7 - - ­72 61.5 4.2 37.1 32.0 26.8 21.6 - - 56.9 4.9 34.1 29.0 23.9 18.7 - ­67 56.4 4.2 45.0 39.8 34.6 29.4 24.2 - 52.5 4.9 44.2 38.1 33.0 27.9 22.8 ­62 51.9 4.2 51.9 51.1 42.4 37.3 32.1 26.9 48.7 4.8 48.7 48.3 39.8 34.7 29.6 24.4 77 68.3 4.3 32.7 26.8 20.8 - - - 62.8 5.0 27.9 22.1 16.2 - - ­72 63.2 4.3 41.4 35.5 29.5 23.6 - - 58.3 4.9 38.0 32.2 26.3 20.4 - ­67 58.0 4.2 50.1 44.2 38.2 32.3 26.3 - 53.7 4.9 48.1 42.2 36.4 30.5 24.6 ­62 53.3 4.2 53.3 52.8 46.8 40.9 34.9 29.0 49.9 4.8 49.9 49.6 43.8 38.0 32.1 26.2 57 53.4 4.2 53.4 53.0 47.1 41.1 35.1 29.2 50.2 4.8 50.2 50.0 44.1 38.3 32.4 26.5 77 70.2 4.3 36.2 29.5 22.8 - - - 64.3 5.0 31.9 24.3 17.7 - - ­72 64.9 4.3 45.7 39.0 32.3 25.6 - - 59.7 5.0 42.0 35.3 28.7 22.1 - ­67 59.5 4.3 55.2 48.5 41.8 35.1 28.4 - 55.0 4.9 52.0 46.3 39.7 33.1 26.4 ­62 54.8 4.2 54.8 54.5 51.2 44.5 37.8 31.1 51.0 4.9 51.0 50.9 47.9 41.2 34.6 28.0 57 54.8 4.2 54.8 54.6 51.5 44.7 38.0 31.3 51.4 4.9 51.4 51.3 48.2 41.6 34.9 28.3 77 72.0 4.3 39.7 32.2 24.7 - - - 65.8 5.0 35.9 26.6 19.2 - - ­72 66.5 4.3 50.0 42.5 35.1 27.6 - - 61.0 5.0 45.9 38.5 31.1 23.7 - ­67 61.1 4.3 60.3 52.9 45.4 37.9 30.4 - 56.3 5.0 55.9 50.4 43.0 35.6 28.3 ­62 56.2 4.2 56.2 56.2 55.6 48.2 40.7 33.2 52.2 4.9 52.2 52.2 51.9 44.5 37.1 29.7 57 56.2 4.2 56.2 56.2 55.9 48.4 40.9 33.4 52.6 4.9 52.6 52.6 52.3 44.9 37.5 30.1 72 62.1 5.0 51.8 43.7 35.7 27.6 - - 59.2 5.3 48.5 40.5 32.4 24.4 - ­67 57.0 4.9 56.6 52.9 46.2 38.1 30.0 - 54.6 5.3 54.4 51.7 45.0 37.0 29.0 ­62 52.5 4.9 52.5 52.5 52.2 44.1 36.1 28.0 50.7 5.2 50.7 50.7 50.5 42.5 34.5 26.5 57 52.5 4.9 52.5 52.5 52.3 44.2 36.2 28.1 51.1 5.2 51.1 51.1 50.9 42.9 34.9 26.9 72 57.7 5.6 53.5 44.9 36.3 27.6 - - 57.4 5.6 51.1 42.4 33.8 25.1 - ­67 53.0 5.6 53.0 53.0 46.9 38.3 29.6 - 53.0 5.6 53.0 53.0 46.9 38.3 29.6 ­62 48.7 5.5 48.7 48.7 48.7 40.1 31.4 22.8 49.2 5.5 49.2 49.2 49.2 40.5 31.9 23.2 57 48.7 5.5 48.7 48.7 48.7 40.1 31.5 22.8 49.6 5.5 49.6 49.6 49.6 40.9 32.3 23.7
Total
Capacity
(MBh)
251933-YTG-X-0615
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
(kW)
Total Input
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 29
251933-YTG-X-0615
ZE060 (5.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
1250
1500
1750
2000
2250
2500
WB (°F)
77 56.2 5.6 18.7 15.6 10.5 - - - 51.0 6.2 13.2 11.3 6.3 - - ­72 52.4 5.6 31.1 26.0 20.9 15.9 - - 47.8 6.3 28.0 23.0 18.0 13.0 - ­67 48.5 5.6 43.4 36.5 31.4 26.3 21.3 - 44.6 6.3 42.7 34.8 29.8 24.8 19.8 ­62 45.5 5.5 45.5 45.5 37.2 32.1 27.1 22.0 42.2 6.1 42.2 42.2 34.6 29.6 24.6 19.6 77 57.3 5.6 23.1 17.3 11.5 - - - 51.8 6.3 18.3 12.6 6.9 - - ­72 53.4 5.6 34.6 28.8 23.0 17.2 - - 48.5 6.3 31.2 25.5 19.8 14.0 - ­67 49.5 5.6 46.1 40.3 34.5 28.7 22.9 - 45.2 6.3 44.1 38.4 32.6 26.9 21.2 ­62 46.4 5.5 46.4 46.4 40.9 35.0 29.2 23.4 42.9 6.2 42.9 42.9 37.9 32.1 26.4 20.7 57 47.1 5.5 47.1 47.0 41.2 35.4 29.6 23.8 44.0 6.2 44.0 44.0 38.3 32.6 26.9 21.1 77 58.4 5.6 27.6 19.1 12.6 - - - 52.6 6.3 23.5 13.9 7.4 - - ­72 54.4 5.6 38.2 31.6 25.1 18.5 - - 49.2 6.3 34.4 27.9 21.5 15.0 - ­67 50.5 5.6 48.8 44.1 37.6 31.0 24.5 - 45.9 6.3 45.5 41.9 35.5 29.0 22.5 ­62 47.3 5.5 47.3 47.3 44.5 38.0 31.4 24.9 43.5 6.2 43.5 43.5 41.2 34.7 28.2 21.8 57 48.1 5.5 48.1 48.0 44.9 38.4 31.8 25.3 44.7 6.2 44.7 44.7 41.7 35.2 28.7 22.3 77 59.6 5.7 32.0 20.9 13.6 - - - 53.3 6.3 28.6 15.2 8.0 - - ­72 55.5 5.7 41.7 34.4 27.1 19.8 - - 50.0 6.3 37.6 30.4 23.2 16.0 - ­67 51.4 5.7 51.4 48.0 40.7 33.4 26.1 - 46.6 6.3 46.6 45.5 38.3 31.1 23.9 ­62 48.2 5.5 48.2 48.2 48.2 40.9 33.6 26.3 44.2 6.2 44.2 44.2 44.2 37.3 30.1 22.8 57 49.0 5.6 49.0 49.0 48.6 41.3 34.0 26.7 45.4 6.3 45.4 45.4 45.0 37.8 30.6 23.4 72 56.3 5.6 45.2 37.2 29.2 21.3 - - 53.4 6.0 41.8 33.9 26.0 18.1 - ­67 52.2 5.6 52.2 50.5 43.8 35.8 27.9 - 49.8 6.0 49.8 49.2 42.6 34.7 26.8 ­62 48.9 5.5 48.9 48.9 48.9 40.9 33.0 25.0 47.1 5.9 47.1 47.1 47.1 39.3 31.4 23.5 57 49.7 5.6 49.7 49.7 49.5 41.6 33.6 25.6 48.3 5.9 48.3 48.3 48.1 40.2 32.3 24.4 72 57.1 5.6 48.6 39.9 31.3 22.7 - - 56.9 5.6 46.1 37.5 28.8 20.2 - ­67 53.0 5.6 53.0 53.0 46.9 38.3 29.6 - 53.0 5.6 53.0 53.0 46.9 38.3 29.6 ­62 49.6 5.5 49.6 49.6 49.6 41.0 32.3 23.7 50.1 5.5 50.1 50.1 50.1 41.4 32.8 24.1 57 50.4 5.5 50.4 50.4 50.4 41.8 33.2 24.5 51.3 5.5 51.3 51.3 51.3 42.6 34.0 25.4
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
(kW)
Total Input
Sensible Capacity (MBh)
2
30 Johnson Controls Unitary Products