YORK® ZE/ZF/ZR/XN/XP Series units are convertibl e si ng l e
package high efficiency rooftops with a common roof curb for
the 3, 4, 5 and 6 Ton sizes (ZE, ZR, XN, XP not available in 6
Ton). Although the units are primarily designed for curb
mounting on a roof, they can also be slab-mounted at ground
level or set on steel beams above a finished roof.
All ZE/ZF/ZR/XN/XP Series units are self-contained and
assembled on rigid full perimeter base rails allowing for
overhead rigging. Every unit is completely charged, wired,
piped and tested at the factory to provide a quick and easy field
installation.
All models (including those with an economizer) are convertible
between bottom and horizontal duct connections.
60 Hertz
ZE/ZF/ZR Series units are available in the following
configurations: cooling only, cooling with electric heat, and
cooling with one or two stage gas heat. Electric heaters are
available as factory-installed option or field installed accessory.
XN/XP Series units are available in the following configurations:
cooling and heating only and cooling and heating with electric
heat.
Tested in accordance with:
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
251933-YTG-X-0615
Smoke
Detector
3/4” PVC Female
Condensate Drain
GFCI
Convenience Outlet
Knockout
For Side
Control Entry
Simplicity® Lite™
Or Simplicity SE
Control Board
Knockout For Side
Gas Supply Entry
Full Perimeter Baserails
With Forklift Slots And
Lifting Holes
Highly Efficient
Enhanced Copper
Tube/Enhanced
Aluminum Fin
Or
Micro-Channel
Aluminum
Tube/Aluminum
Fin Condenser
Highly Efficient
Enhanced Copper
Tube/Enhanced
Aluminum Fin
Or
Micro-Channel
Aluminum
Tube/Aluminum
Fin Condenser
Full Perimeter Baserails
With Forklift Slots And
Lifting Holes
Simplicity® Lite™
Or
Simplicity® SE
Control Board
Belt Drive Or
Direct Drive
Blower
Knockout
For Side
Control Entry
GFCI
Convenience Outlet
3/4” PVC Female
Condensate Drain
Smoke
Detector
Slide-In
Economizer
Knockout
For Side
Power Entry
HACR
Breaker
251933-YTG-X-0615
Johnson Controls Unitary Products3
251933-YTG-X-0615
Z E 048 N04 A 2 A AA 4 0 1 2 4 A
Z = A/C, Single Pkg., R-410A
X = HP, Single Pkg., R-410A
Product Category
Airow
A = Direct Drive
B = Direct Drive/Single Input Low Leak Econo
D = Direct Drive/Motorized Damper
N = Belt Drive
P = Belt Drive/Single Input Low Leak Econo
R = Belt Drive/Motorized Damper
T = Belt Drive High Static
U = Belt Drive High Static/Single Input Low Leak Economizer
V = Belt Drive High Static/Motorized Damper
Product Generation
4 = Fourth Generation
*(D, T)10 = 92 MBH Output on 036 Models
036 = 3.0 Ton
Nominal Cooling Capacity
048 = 4.0 Ton
060 = 5.0 Ton
072 = 6.0 Ton
Product Identifier
= 11.2 EER2, A/C
= 11.0 EER
3
, CLG/GAS
R = 13.0 SEER Reheat
P = 13.0 SEER HP
Product Style
A = Style A
SS Drain Pan
Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.
CPC Controller, DFS, APS
Honeywell Controller, DFS, APS
Novar Controller, DFS, APS
2" Pleated Filters, MERV 7
BAS Ready Economizer (2-10 V.D.C. Actuator Without a Controller)
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
1. 3 thru 5 Ton Units
2. 6 Ton Units Cooling Only / Cooling With Electric Heat
3. 6 Ton Unit Cooling With Gas Heat
F = 13.0 SEER
1
, A/C
E = 14.0 SEER, A/C
N = 14.0 SEER HP
Simplicity® Smart Equipment (SSE) w/Communication
BACnet MS/TP (programmable to Modbus or N2 protocols)
Johnson Controller UNT 1126 (N2 protocol), DFS, APS
• High Efficiency - High efficiency 3 thru 5 Ton units reach
14.0/13.0 SEER, 6 Ton Cooling only or Cooling with
Electric Heat reach 11.2 EER and 6 Ton Cooling with Gas
Heat reach 11.0 EER. Gas/electric units have electronic
spark ignition and power vented combustion with steady
state efficiencies of 80%. High efficiency heat pumps
reach 14/13 SEER and 8.0/7.7 H.S.P. F. These
efficiencies exceed all legislated minimum levels and
provide low operating costs.
• Coil Technology – All ZE/ZF condensers utilize MicroChannel “all-aluminum” condensers which provide
improved heat transfer capabilities and reduced charge
volumes. All evaporators utilize a conventional copper
tube/aluminum fin design for proven reliability and
performance.
• Convertible Airflow Design - All models (including those
with an economizer) are suitable for either bottom or
horizontal duct connections. For bottom duct, remove the
sheet metal panels from the supply and return air openings
through the base of the unit. For horizontal duct, remove
the supply and return air panels on the rear of the unit.
• System Protection - Suction line freezestats are supplied
on all units to protect against loss of charge and coil
frosting when the economizer operates at low outdoor air
temperatures while the compressors are running. Every
unit has solid-core liquid line filter-driers and high and lowpressure switches. Internal compressor protection is
standard on all compressors.
• Advanced Controls - ZE/ZF (Electric/Electric and Gas/
Electric) with no factory installed economizer or BAS
options will come standard with the reliable Simplicity
Lite™ control. All ZE/ZF models with factory installed
economizers or any BAS option, reheat (ZR) and heat
pump (XP, XN) Units will come with the new state of the
art Simplicity SE (Smart Equipment) control system. The
new unit control incorporates the best of the already
proven Simplicity
robust, intelligent control. The goal of this control is to
utilize cutting edge technology making the equipment
easier to install, operate, and service. All units are Factory
commissioned, configured, and run tested.
®
unitary controls and creates a more
Simplicity SE Control Board
• Versatile - The Simplicity SE (not applicable with units
utilizing Simplicity Lite) control can be configured to use
with a standard thermostat (easy to connect screw
terminals), A zone sensor, or can be setup to
communicate with multiple BAS communication
protocols to integrate with building automation systems.
• Reduce field installed complexity - Each unit (not
applicable with units utilizing Simplicity Lite) will comes
equipped with factory installed supply air, return air, and
outdoor air temperature sensors providing key
temperature readings thus reduce field installed
complexity.
®
• On-board USB Port - The new control (not applicable
with units utilizing Simplicity Lite) comes with a long list
of features including data logging, current and previous
system faults and software update capabilities using the
on board USB port and common flash drive. Energy use
monitoring capabilities allow custom tailoring to allow a
system to work more efficiently at all times and
occupancy levels. Self test and start-up reports also
available from the board VIA the USB port.
• Embedded LCD Display - The board (not applicable
with units utilizing Simplicity Lite) has a easy to read,
built-in LCD display and easy to use navigation joystick
and buttons allowing the user to quickly navigate the
menus displaying unit status, options, current function,
supply, return and outdoor temperatures, fault codes
and other information.
• Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down to
0F outdoor ambient without additional assistance.
Optionally, the control board can be programmed to
lockout the compressors when the outdoor air
temperature is low or when free cooling is available.
Johnson Controls Unitary Products5
251933-YTG-X-0615
The
Simplicity
this product will effectively operate the cooling system down to 0°F when this product is applied in a
comfort cooling application for people. An economizer is typically included in this type of application. When applying this product for process
cooling applications (computer rooms, switchgear,
etc.), please reference applications bulletin AE011-07 or call the applications department for Unitary Products @ 1-877-UPG-SERV for guidance.
Additional accessories may be needed for stable
operation at temperatures below 30° F.
• Anti-Short Cycle Protection - To aid compressor life,
an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti-short cycle delay can be temporarily
overridden with the push of a button.
• Fan Delays - Fan on and fan off delays are fully
programmable. Furthermore, the heating and cooling
fan delay times are independent of one another. All units
are programmed with default values based upon their
configuration of cooling and heat.
• Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the gas
valve, if applicable, and the temperature limit switch on
gas and electric heat units. The unit control board will
alarm on ignition failures, compressor lockouts and
repeated limit switch trips.
• Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a “three
times, you’re out” philosophy. The high and lowpressure switches and the freezestats must trip three
times within two hours before the unit control board will
lock out the associated compressor.
• On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and flash
an alarm code on the control board LED or on LCD with
Simplicity SE controlled units. Each high and lowpressure switch alarm as well as each freezestat alarm
has its own flash code. The control board saves the five
most recent alarms in memory, and these alarms can be
reviewed at any time. Alarms and programmed values
are retained through the loss of power.
• Reliable - From the beginning - All units undergo
computer automated testing before they leave the factory.
Units are tested for refrigerant charge and pressure, unit
amperage, and 100% functionality. For the long term - All
units are painted with a long lasting, powder paint that
stands up over the life of the unit. The paint used has
been proven by a 1000 hour salt spray test.
• Flexible Placement - All models and configurations share
the same cabinet/footprint and thus the same roof curb.
You have the flexibility to set one curb and choose the
® Lite or SE control board used in
correct tonnage size and heating option after the internal
loads have been determined.
• Full Perimeter Base Rails - The permanently attached
base rails provide a solid foundation for the entire unit and
protect the unit during shipment. The rails offer forklift
access from 3 sides, and rigging holes are available so that
an overhead crane can be used to place the units on a roof.
• Easy Installation - Gas and electric utility knockouts are
supplied in the unit underside as well as the side of the
unit. A clearly identified location is provided to mount a
field supplied electrical disconnect switch. Utility
connections can be made quickly and with a minimum
amount of field labor.
• Wide Range of Indoor Airflows - Indoor fan motors are
either direct-drive or belt-drive type providing maximum
flexibility to handle most airflow requirements.
• Gas Heat Operation - All single phase models with gas
heat have minimum annual fuel utilization efficiency
(AFUE) of 81%. All three phase models with gas heat
have minimum steady state efficiency of 80%. Each
section includes a durable heat exchanger with
aluminized steel or optional stainless steel tubes, a
redundant gas valve, spark ignition, power venting, an
ignition module for 100% shut-off and all of the safety
controls required to meet the latest ANSI standards.
The gas supply piping can be routed into the heating
compartment through a hole in the base pan of the unit or
through a knockout in the piping panel on the front of the
unit.
Electric Heat Operation - All electric heat models are
wired for a single power source and include a bank of
nickel chromium elements mounted at the discharge of
the supply air blower to provide a high velocity and
uniform distribution of air across the heating elements.
Every element is fully protected against excessive
temperature by thermal limit switches.
The power supply wiring can be routed into the control
box through a threaded pipe connection (field supplied) in
the base pan of the unit or through a knockout in the
wiring panel on the side of the unit.
• Warranty - All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater
elements each carry a 5-year warranty. Aluminized steel
and stainless steel tubular heat exchangers carry a 10year warranty.
Factory Installed Options
NOTE: Simplicity Lite models are only available with a field
installed Honeywell Jade economizer which is
equipped standard with single enthalpy control (dual
enthalpy available as field installed kit). Simplicity SE
models are available with factory or field installed
economizers including options for a SSE controlled
economizer or an externally controlled BAS economizer
where both feature standard dry bulb control (single
and dual enthalpy available as field installed kits).
• Economizers - All units offer a variety of optional factory
installed economizers that are shipped, installed and
wired with AMCA 511 Licensed Class 1A low leak
6Johnson Controls Unitary Products
251933-YTG-X-0615
dampers designed to exceed ASHRAE 90.1-2010 and the
International Energy Conservation Code (IECC)
certification requirements by achieving leakage rates of 3
cfm/ sq. ft. at 1" of static pressure. Each economizer goes
through a rigorous 60,000 cycle test. Dry bulb, single
enthalpy, and dual enthalpy (with field installed kit) can be
selected. All economizer options are fully integrated into
the Simplicity SE controls. The economizer has spring
return, fully modulating damper actuators and is capable
of introducing up to 100% outdoor air. As the outdoor air
intake dampers open, the return air dampers close. The
changeover from mechanical refrigeration to economizer
operation is regulated by the outdoor air dry bulb
temperature or the outdoor air enthalpy input. The dual
enthalpy kit provides a second input used to monitor the
return air (field installed). The installer needs only to
assemble the outdoor air hood, attach the enthalpy control
the hood and mount the hood to the unit (Hood and
control are provided).
• Dry Bulb Economizer - Economizer operation is
enabled by the outdoor air temperature being less than
the setpoint of the economizer module.
• Enthalpy Economizer - The added outdoor air enthalpy
sensor enables economizer operation if the outdoor
enthalpy is less than the setpoint of the economizer
logic module.
• Motorized Outdoor Air Intake Damper -Includes a slidein / plug-in damper assembly with a 2-position, spring
return motor actuator which opens to a pre-set position
whenever the supply air blower is operating and will drive
fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must
be field assembled before installing.
• Technicoat Condenser Coils - The condenser coils are
coated with a phenolic coating for protection against
corrosion due to harsh environments.
• Technicoat Evaporator Coil - The evaporator coils are
coated with a phenolic coating for protection against
corrosion due to harsh environments.
• E-coat Condenser Coils - The condenser coils are
coated with an epoxy polymer coating to protect against
corrosion.
• E-coat Evaporator Coils - The evaporator coils are
coated with an epoxy polymer coating to protect against
corrosion.
• Electric Heaters - Wired for single point power supply.
These nickel chromium heater elements are provided with
limit and automatic reset capability to prevent operation at
excessive temperatures.
• Filter Options - Standard units are shipped with 1" throwaway filters installed. 2" Pleated Filters, MERV 7 are
offered as a factory installed option.
• Convenience Outlet - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or the
unit may be ordered with a “non-powered” convenience
outlet that can be wired in the field.
• Disconnect Switch - For gas heat units and cooling units
with electric heat, a HACR breaker sized to th e unit is
provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
• Smoke Detectors - (supply air & return air) The smoke
detectors stop operation of the unit by interrupting power
to the control board if smoke is detected within the air
compartment.
Factory installed smoke detectors in the return air, may
be subjected to freezing temperatures during “off” times
due to out side air infiltration. These smoke detectors
have an operational limit of 32°F to 131°F. Smoke
detectors installed in areas that could be out side those
limitations will have to be moved to prevent having false
alarms.
• Coil Guard - Customers can purchase a coil guard kit to
protect the condenser coil from damage. This is not a hail
guard kit.
• Stainless Steel Heat Exchanger - For applications in
corrosive environments, this option provides a full
stainless steel heat exchanger assembly.
• Stainless Steel Drain Pan - An optional rustproof
stainless steel drain pan is available to provide years of
trouble-free operation in corrosive environments.
Bottom Drain Connection - An optional bottom drain
•
connection is available for inside the curb connections for
applications in cold environments to reduce freezing drain
lines.
• Phase Monitors - Designed to prevent unit damage. The
phase monitor will shut the unit down in an out-of phase
condition.
• Dirty Filter Switch - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option or
field installed accessory.
• Hinged & Toolless Filter, Motor and Electrical Access Panels - This option allows for easy access and
maintenance.
NOTE: Knobs are shipped inside the unit to prevent shipping
damage. These must be field installed for tool-less
operation.
• High Static Drive - May include a belt, blower pulley,
motor pulley or a motor change to enhance blower
performance.
Control Options
• Simplicity® SE with Communication Option Control The York® Simplicity® SE with Communication Option
Control is factory installed. It includes all the features of
the Simplicity® SE control with an additional gateway to
BACnet MS/TP (programmable to Modbus or N2
protocols).
Johnson Controls Unitary Products7
251933-YTG-X-0615
• Novar® BAS Control - The Novar® building automation
system controller is factory installed. Incudes supply air
sensor, return air sensor, dirty filter indicator switch, and
air proving switch.
• CPC BAS Control - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building
automation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
• Honeywell BAS Control - The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
• York Commercial Comfort System (YCCS) - Provides
rooftop system integration for YCCS single zone and
change-over bypass systems.
Field Installed Accessories
NOTE: Simplicity Lite models are only available with a field
installed Honeywell Jade economizer which is
equipped standard with single enthalpy control (dual
enthalpy available as field installed kit). Simplicity SE
models are available with factory or field installed
economizers including options for a SSE controlled
economizer or an externally controlled BAS economizer
where both feature standard dry bulb control (single
and dual enthalpy available as field installed kits).
• Economizers - All units offer a variety of optional field
installed economizers that are shipped, installed and
wired with AMCA 511 Licensed Class 1A low leak
dampers designed to exceed ASHRAE 90.1-2010 and the
International Energy Conservation Code (IECC)
certification requirements by achieving leakage rates of 3
cfm/ sq. ft. at 1" of static pressure. Each economizer goes
through a rigorous 60,000 cycle test. Dry bulb, single
enthalpy, and dual enthalpy (with field installed kit) can be
selected. All economizer options are fully integrated into
the Simplicity SE controls. The economizer has spring
return, fully modulating damper actuators and is capable
of introducing up to 100% outdoor air. As the outdoor air
intake dampers open, the return air dampers close. The
changeover from mechanical refrigeration to economizer
operation is regulated by the outdoor air dry bulb
temperature or the outdoor air enthalpy input. The dual
enthalpy kit provides a second input used to monitor the
return air (field installed). The installer needs only to
assemble the outdoor air hood, attach the enthalpy control
the hood and mount the hood to the unit (Hood and
control are provided).
• Dry Bulb Economizer - Economizer operation is
enabled by the outdoor air temperature being less than
the setpoint of the economizer module.
• Enthalpy Economizer - The added outdoor air enthalpy
sensor enables economizer operation if the outdoor
enthalpy is less than the setpoint of the economizer
logic module.
• Motorized Outdoor Air Intake Damper -Includes a slidein / plug-in damper assembly with a 2-position, spring
return motor actuator which opens to some pre-set
position whenever the supply air blower is operating and
will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must
be field assembled before installing.
• Electric Heaters - wired for single point power supply.
These nickel chromium heater elements are provided with
limit and automatic reset capability to prevent operation at
excessive temperatures.
• Roof Curbs - Eight and fourteen-inch high roof curbs
provide a water-tight seal between the unit and the finished
roof. These full perimeter curbs meet the requirements of
the National Roofing Contractors Association (NRCA) and
are shipped knocked-down for field assembly.
Roof curbs are designed to fit inside the base rails of the
unit and include both a wood nailing strip and duct hanger
supports.
• High Altitude Natural Gas - Burner orifices and pilot
orifices are provided for proper furnace operation at
altitudes up to 6,000 feet.
• Propane - Burner orifices, pilot orifices and gas valve
parts are provided to convert a natural gas furnace to
propane.
• High Altitude Propane - Burner orifices and pilot orifices
are provided for proper furnace operation at altitudes up
to 6,000 feet. This accessory supplements the basi c
propane conversion kit.
• Low Nox Kit - Required to reduce the emission of
nitrogen oxides below 40 nano grams per joule.
• Power Exhaust
- Our single input economizer options are
available with power exhaust. Whenever the outdoor air
intake dampers are opened for free cooling, the exhaust
fan will be energized to prevent the conditioned space from
being over-pressurized during economizer operation.
The power exhaust option can only be used on bottom
duct configurations.
• Barometric Relief Damper - This damper accessory can
be used to relieve internal building air pressure on units
with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the return
air panel. With horizontal ductwork, the accessory should
be mounted on the return air duct.
• Enthalpy Accessory Control Kit - This kit contains the
required components to convert a single enthalpy
economizer to dual enthalpy.
• Burglar Bars - Mount in the supply and return openings
to prevent entry into the duct work.
• Flue Exhaust Extension Kit - In locations with wind or
weather conditions which may interfere with proper
exhausting of furnace combustion products, this kit can be
installed to prevent the flue exhaust from entering nearby
fresh air intakes.
Sensor - Senses CO2 levels and automatically
• CO
2
overrides the economizer when levels rise above the
present limits.
8Johnson Controls Unitary Products
251933-YTG-X-0615
• Coil Guard - Customers can purchase a coil guard kit to
protect the condenser coil from damage. This is not a hail
guard kit.
• Hail Guard - Hail Guard kit is available to prevent unit
from hail damage. This is a sloped hood that fits above
the coil.
• Gas Piping Kit - This kit supplies all necessary fittings
and shut off valve.
Guide Specifications
General
Units shall be manufactured by Johnson Controls Unitary
Products in an ISO 9001 certified facility.
York's ZE/ZF/ZR/XN/XP units are convertible single package
units. Although the units are primarily designed for curb
mounting on a roof, they can also be slab-mounted at ground
level or set on steel beams above a finished roof. Cooling only,
cooling with gas heat and cooling with electric heat models are
available with a wide variety of factory-mounted options and
field-installed accessories to make them suitable for almost
every application. All units are self-contained and assembled on
full perimeter base rails with holes in the four corners for
overhead rigging. Every unit is completely piped, wired,
charged and tested at the factory to simplify the field installation
and to provide years of dependable operation. All models
(including those with an economizer) are suitable for either
bottom or horizontal duct connections. Models with power
exhaust are suitable for bottom duct connections only. For
bottom duct, remove the sheet metal panels from the supply
and return air openings through the base of the unit. For
horizontal duct, remove the supply and return air panels on the
rear of the unit.
All non-Scroll compressors include crankcase heaters and all
compressors have internal pressure relief. Every refrigerant
circuit includes a liquid line filter-drier, a discharge line high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch.The unit control circuit includes
a 75 VA transformer, a 24-volt circuit breaker and a relay board
with a compressor lockout circuit, a terminal strip for thermostat
wiring, plus an additional set of pin connectors to simplify the
interface of additional field controls. All models are CSA listed.
All models include a 1-year limited warranty on the complete
unit. Compressors and electric heater elements carry a 5-year
warranty. Aluminized steel and Stainless steel tubular heat
exchangers carry a 10-year warranty.
Cooling only or Cooling with Electric Heat shall have 11.2 EER,
6 Ton Cooling with Gas Heat shall have 11.0 EER. They shall
have built-in field convertible duct connections for down
discharge supply/return or horizontal discharge supply/return,
and be available with factory installed options or field installed
accessories. The units shall be factory wired, piped, charged
with R-410A refrigerant and factory tested prior to shipment. All
unit wiring shall be both numbered and color coded. All units
the cooling performance shall be rated in accordance with DOE
and AHRI test procedures. Units shall be CSA listed, classified
to ANSI Z21.47, UL 1995/CSA No. 236 standards.
Unit Cabinet
Unit cabinet shall be constructed of galvanized steel, with
exterior surfaces coated with a non-chalking, powdered paint
finish, certified at 1000 hours salt spray test per ASTMB117
standards. Indoor blower section shall be insulated with a
minimum 1/2” thick insulation, coated on the airside. Aluminum
foil faced insulation shall be used in the furnace compartment
and be fastened with ridged fasteners to prevent insulation from
entering the air stream. Cabinet panels shall be “large” size,
easily removable for servicing and maintenance. Full perimeter
base rails shall be provided to assure reliable transit of
equipment, overhead rigging and proper sealing on roof curb
applications. Disposable 1" filters shall be furnished and be
accessible through a removable access door, sealed airtight.
Units filter track shall be designed to accommodate either 1" or
2" filters. Fan performance measuring ports shall be provided
on the outside of the cabinet to allow accurate air
measurements of evaporator fan performance without removing
panels or creating air by-pass of the coils. Condensate pan
shall be internally sloped and conform to ASHRAE 62-89 selfdraining standards. Condensate connection shall be a minimum
of 3/4” I.D. female and be a ridged mount connection.
Indoor (Evaporator) Fan Assembly
The indoor fan shall be a factory installed direct-drive or beltdrive assembly that includes an adjustable pitch motor pulley.
Job site selected (B.H.P.) brake horsepower shall not exceed
the motors nameplate horsepower rating, plus the service
factor. Units shall be designed not to operate above service
factor. Fan wheel shall be double-inlet type with forward-curved
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Airflow design shall be constant
air volume. Bearings shall be sealed and permanently
lubricated for longer life and no maintenance.
Outdoor (Condenser) Fan Assembly
Description
Units shall be factory-assembled, single packaged, Electric
Cooling/Gas Heat, Electric Cooling/Optional Electric Heat, Heat
Pump/Optional Electric Heat are designed for outdoor mounted
installation.
The 3 ton, 4 ton and 5 ton units shall have minimum SEER
rating of 13.0 with heat pumps having a 7.7 H.S.P.F. The 6 Ton
Johnson Controls Unitary Products9
The outdoor fan shall be of the direct-driven propeller type,
discharge air vertically, have aluminum blades riveted to a
corrosion resistant steel spider bracket and shall be
dynamically balanced for smooth operation. The outdoor fan
motor shall be totally enclosed with permanently lubricated
bearings, internally protected against overload conditions and
staged independently.
251933-YTG-X-0615
Refrigerant Components
Compressor:
a. Shall be internally protected with internal high-pressure
relief and over temperature protection.
b. Shall have internal spring isolation and sound muffling to
minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.
Coils:
a. Evaporator coils shall have aluminum plate fins
mechanically bonded to seamless internally enhanced
copper tubes with all joints brazed. Special Phenolic
coating shall be available as a factory option.
b. Evaporator coils shall be of the direct expansion, draw-
thru design.
c. Condenser coils shall have aluminum plate fins
mechanically bonded to seamless internally enhanced
copper tubes with all joints brazed or Micro-Channel
aluminum tube, aluminum fins.
d. Condenser coils shall be of the direct expansion, draw-
thru design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Independent fixed-orifice or thermally operated
expansion devices.
b. Filter drier/strainer to eliminate any moisture or foreign
matter.
c. Accessible service gage connections on both suction
and liquid lines to charge, evacuate, and measure
refrigerant pressure during any necessary servicing or
troubleshooting, without losing charge.
d. The refrigeration system shall provide at least 15°F of
sub-cooling at design conditions.
i. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to
0°F.
j. Control board shall monitor each refrigerant safety switch
independently.
k. Control board shall retain last 5 fault codes in non volatile
memory which will not be lost in the event of a power loss.
Gas Heating Section (Single Or 2 Stage)
Shall be designed with induced draft combustion with post
purge logic, energy saving direct spark ignition, and redundant
main gas valve. Venter wheel shall be constructed of stainless
steel for corrosion resistance. The heat exchanger shall be of
the tubular type, constructed of T1-40 aluminized steel for
corrosion resistance and allowing minimum mixed air entering
temperature of 25°F. Burners shall be of the inshot type,
constructed of aluminum coated steel and contain air mixture
adjustments. All gas piping shall enter the unit cabinet at a
single location through either the side or curb without any field
modifications. Integrated control boards shall provide timed
control of evaporator fan functioning and burner ignition.
Heating section shall be provided with the following minimum
protection:
a. Primary and auxiliary high-temperature limit switches.
b. Induced draft motor speed sensor.
c. Flame roll out switch.
d. Flame proving controls.
e. If any of the above safety devices trip, a LED (light-
emitting diode) indicator shall flash a diagnostic code that
indicates which safety switch has tripped.
st
NOTE: All 2 Stage Gas Heat, 60% Capacity 1
Stage, 40%
Capacity 2nd Stage.
Electric Heating Section
Unit Controls
An electric heating section, with nickel chromium elements,
shall be provided in a range of 5 thru 30 KW, offering two
a. Unit shall be complete with self-contained low-voltage
control circuit protected by a resettable circuit breaker on
the 24-volt transformer side.
b. Unit shall incorporate a lockout circuit which provides
reset capability at the space thermostat or base unit,
should any of the following standard safety devices trip
and shut off compressor.
c. Loss-of-charge/Low-pressure switch.
d. High-pressure switch.
e. Freeze-protection thermostat, evaporator coil.
f. Unit shall incorporate “AUTO RESET” compressor over
temperature, over current protection.
g. Unit shall operate with conventional thermostat designs
and have a low voltage terminal strip for easy hook-up.
stages of capacity - 16 KW and above on 208/230 volt heaters
and 20 KW and above on 460 and 575 volt heaters. The
heating section shall have a primary limit control(s) and
automatic reset to prevent the heating element system from
operating at an excessive temperature. The heating section
assembly shall slide out of the unit for easy maintenance and
service. Units with Electric Heating shall be wired for a single
point power supply with branch circuit fusing (where required).
Unit Operating Characteristics
Unit shall be capable of starting and running at 125°F outdoor
temperature, exceeding maximum load criteria of AHRI
Standard 210/240. The compressor, with standard controls,
shall be capable of operation down to 0°F outdoor temperature.
Unit shall be provided with fan time delay to prevent cold air
delivery before heat exchanger warms up (Gas heat only).
h. Unit control board shall have on-board diagnostics and
fault code display.
10Johnson Controls Unitary Products
251933-YTG-X-0615
Electrical Requirements
All unit power wiring shall enter unit cabinet at a single factory
provided location and be capable of side or bottom entry, to
minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
control wiring.
Standard Limited Warranties
• Compressor 5 Years
• Heat Exchanger 10 Years
• Electric Heat Element 5 Years
• Other Parts 1 Year
Optional Outdoor Air
Shall be made available by either/or:
• Dry Bulb Automatic Economizer - Outdoor and return air
dampers that are interlocked and positioned by a fullymodulating, spring-return damper actuator. The maximum
leakage rate for the outdoor air intake dampers shall be
designed to meet ASHRAE 90.1-2010, AMCA 511 Class
1A damper, and the International Energy Conservation
Code (IECC) certification requirements by achieving
leakage rates of 3 cfm/sq. ft. at 1" of static pressure.
Changeover from compressor to economizer operation
shall be provided by an integral electronic enthalpy control
that feeds input into the basic module. The outdoor intake
opening shall be covered with a rain hood that matches the
exterior of the unit. Water eliminator/filters shall be
provided. Simultaneous economizer/compressor operation
is also possible. Dampers shall fully close on power loss.
Available with barometric relief and power exhaust..
• Motorized Outdoor Air Dampers - Outdoor air dampers
are positioned by a 2-position, spring-return damper
actuator. A unit-mounted potentiometer shall be provided
to adjust the outdoor damper assembly to take in the
design CFM of outdoor air to meet the ventilation
requirements of the conditioned space during normal
operation. Whenever the indoor fan motor is energized,
the dampers open up to one of two pre-selected positions
- regardless of the outdoor air enthalpy. Dampers return to
the fully closed position when the indoor fan motor is deenergized. Dampers shall fully close on power loss.
Other Pre-engineered Accessories Available
• Roof Curb - 14"and 8” high, full perimeter curb with wood
nailer (shipped knocked-down).
• Barometric Relief Damper - Contains a rain hood, air
inlet screen, exhaust damper and mounting hardware.
Used to relieve internal air pressure through the unit.
• Propane Conversion Kit - Contains new orifices and gas
valve parts to convert from natural to L.P. gas. One per
unit required.
• High Altitude - Natural Gas - Contains orifices required
for applications between 2000 and 6000 feet altitude.
• High Altitude - Propane Gas - Contains orifice s requ ired
for applications between 2000 and 6000 feet altitude.
Must be used with propane conversion kit.
• Low Nox - Required to reduce the emission of nitrogen
oxides below 40 nanograms per joule.
• Gas Piping - Contains 1/2” pipe nipples, fittings and gas
cock (including panel assess gaskets) required for bottom
gas supply connection with external shut off.
• Power Exhaust Option - To work in conjunction with
economizers.
• Electric Heaters
• Economizer/motorized Damper Rain Hood - Contains
all hood panels and the hardware for assembling.
• Manual Outdoor Air Damper
• Coil Guard Kit - Guard for cooling coil.
• Hail Guard
• Flue Exhaust Extension
OTHER FACTORY INSTALLED OPTIONS
• Power Exhaust Option - To work in conjunction with
economizers.
• Stainless Steel Heat Exchanger
• Stainless Steel Drain Pan
• Bottom Drain Connection
• Technicoat Phenolic Coated Condenser And
Evaporator Coil
• Electronic Single Enthalpy Economizer
• Dirty Filter Switch
• Phase Monitor
• Coil Guard
• Powered GFI Convenience Outlet
• Non-powered GFI Convenience Outlet
• BAS Controls - Simplicity® SE with BAS
Communication (BACnet MS/TP, Modbus, and
Johnson Controls N2) Option, CPC, HONEYWELL,
NOVAR, YORK
• Bas Ready Economizer (2-10 V.D.C. Actuator Without
a Controller)
• Hinged Filter Door Access And Toolless Access
Panels
• 2" Pleated Filters, MERV 7
• Disconnect Switch
• Supply Air Smoke Detector
• Return Air Smoke Detector
• Direct Drive Or Belt Drive Blower With High Static
Drive Option
• Hot Gas Reheat with Hot Gas Bypass (Not available
on 6 Ton)
Johnson Controls Unitary Products11
251933-YTG-X-0615
Physical Data
ZE036-060 Physical Data
Component
Nominal Tonnage345
ARI COOLING PERFORMANCE
Gross Capacity @ AHRI A point (Btu)366004910059000
AHRI net capacity (Btu)355004750057000
EER12.012.011.8
SEER14.014.014.0
IPLV--CFM120014501680
System power (KW)2.963.964.83
Refrigerant typeR-410AR-410AR-410A
Refrigerant charge (lb-oz)
System 1 4-45-66-6
TypeSCROLLSCROLLSCROLL
Quantity111
Unit Capacity Steps (%)100100100
CONDENSER COIL DATA
Face area (Sq. Ft.)16.316.316.3
Rows111
Fins per inch232323
Tube diameter (in.)0.7 1 / 180.71 / 181.00 / 25.4
Circuitry Type2-pass Microchannel2-pass Microchannel2-pass Microchannel
EVAPORATOR COIL DATA
Face area (Sq. Ft.)5.065.065.06
Rows344
Fins per inch131313
Tube diameter0.3750.3750.375
Circuitry TypeIntertwinedIntertwinedIntertwined
Refrigerant controlOrificeOrificeTXV
ZE036ZE048ZE060
Models
12Johnson Controls Unitary Products
ZE036-060 Physical Data (Continued)
251933-YTG-X-0615
Component
Nominal Tonnage345
CONDENSER FAN DATA
Quantity of fans111
Fan diameter (Inch)242424
TypePropPropProp
Drive typeDirectDirectDirect
Quantity of motors111
Motor HP each1/21/21/2
No. speeds111
RPM109010901100
CFM400040004200
BELT DRIVE EVAP FAN DATA
Quantity111
Fan Size (Inch)12 x 1012 x 1012 x 10
TypeCentrifugalCentrifugalCentrifugal
Motor Sheave1VL441VP561VL441VP561VL441VP56
Blower SheaveAK64AK66AK56AK61AK56AK56
BeltA37A39A36A38A36A38
Motor HP each1-1/21-1/21-1/21-1/21-1/22
RPM174017401740
Frame size565656
DIRECT DRIVE EVAP FAN DATA
Quantity111
Fan Size (Inch)12 x 1012 x 1012 x 10
TypeCentrifugalCentrifugalCentrifugal
Motor HP each1/211
RPM105010501050
FILTERS
15" x 20" x 1" or 2"222
14" x 25" x 1" or 2"111
NOTE: All 2 Stage Gas Heat, 60% Capacity 1
st
ZE036ZE048ZE060
Stage , 40% 2nd Stage
Models
Johnson Controls Unitary Products13
251933-YTG-X-0615
ZF036-060 Physical Data
Component
Nominal Tonnage3.04.05.0
AHRI COOLING PERFORMANCE
Gross Capacity @ AHRI A point (Btu)
AHRI net capacity (Btu)
EER
SEER
IPLV
CFM
System power (KW)
Refrigerant type
Refrigerant charge (lb-oz)
System 14-45-85-8
AHRI HEATING PERFORMANCE
Heating model
Heat input (K Btu)
Heat output (K Btu)
AFUE %
Steady state efficiency (%)
No. burners
No. stages
Temperature Rise Range (ºF)15-45 45-75 35-70 55-90 25-70 45-75 25-70 45-75 25-55 35-75 20-55 35-75
Gas Limit Setting (ºF) - Direct Drive240170210200210165210165170165210165
Gas Limit Setting (ºF) - Belt Drive240210240200240210240210210210210210
Gas piping connection (in.)
DIMENSIONS (inches)
Length
Width
Height
OPERATING WT. (lbs.)
COMPRESSORS
Type
Quantity
Unit Capacity Steps (%)
CONDENSER COIL DATA
Face area (Sq. Ft.)16.316.316.3
Rows
Fins per inch
Tube diameter (in.)
Circuitry Type
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter
Circuitry Type
Refrigerant control
Quantity
Fan diameter (Inch)
Type
Drive type
Quantity of motors
Motor HP each
No. speeds
RPM
CFM
BELT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
Motor Sheave1VL441VP561VL441VP561VL441VP56
Blower SheaveAK64AK66AK56AK61AK56AK56
BeltA37A39A36A38A36A38
Motor HP each1-1/21-1/21-1/21-1/21-1/22
RPM
Frame size
DIRECT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
Motor HP each
RPM
FILTERS
15” x 20” x 1” or 2”
14” x 25” x 1” or 2”
ZF036ZF048ZF060
111
242424
PropPropProp
DirectDirectDirect
111
1/21/21/2
111
109010901090
380042004200
111
11 x 1011 x 1011 x 10
CentrifugalCentrifugalCentrifugal
172517251725
565656
111
12 x 1012 x 1012 x 10
CentrifugalCentrifugalCentrifugal
1/211
105010501050
222
111
Models
NOTE: All 2 Stage Gas Heat, 60% Capacity 1
st
Stage, 40% Capacity 2nd Stage.
Johnson Controls Unitary Products15
251933-YTG-X-0615
ZF072 Physical Data
Component
Models
ZF072
Nominal Tonnage6.0
AHRI COOLING PERFORMANCE
Gross Capacity @ AHRI A point (Btu)70360
AHRI net capacity (Btu)68000
1
EER11.2
/ 11.0
2
IEER11.3
CFM2000
System power (KW)6.07
Refrigerant typeR-410A
Refrigerant charge (lb-oz)
System 16-4
AHRI HEATING PERFORMANCE
Heating modelN08N10D06D10
Heat input (K Btu)10012575125
Heat output (K Btu)8010060.8100.6
AFUE %---Steady state efficiency (%)--80.080.0
No. burners4535
No. stages1122
Temperature Rise Range (ºF)25-55 30-75 15-45 30-75
Gas Limit Setting (ºF) - Direct Drive170165210165
Gas Limit Setting (ºF) - Belt Drive210210210210
Gas piping connection (in.)1/21/21/21/2
DIMENSIONS (inches)
Length82 1/4
Width44 7/8
Height32 5/8
OPERATING WT. (lbs.)640
COMPRESSORS
TypeScroll
Quantity1
Unit Capacity Steps (%)100
CONDENSER COIL DATA
Face area (Sq. Ft.)16.3
Rows1
Fins per inch23
Tube diameter (in.)1.0 / 25.4
Circuitry Type2-pass Microchannel
EVAPORATOR COIL DATA
Face area (Sq. Ft.)5.06
Rows4
Fins per inch13
Tube diameter0.375
Circuitry TypeIntertwined
Refrigerant controlFixed Orifice
16Johnson Controls Unitary Products
ZF072 Physical Data (Continued)
251933-YTG-X-0615
Component
Models
ZF072
Nominal Tonnage6.0
CONDENSER FAN DATA
Quantity1
Fan diameter (Inch)24
TypeProp
Drive typeDirect Drive
No. speeds1
Number of motors1
Motor HP each1/2
3
1/2
4
RPM11001090
CFM42004200
BELT DRIVE EVAP FAN DATA
Quantity1
Fan Size (Inch)12 x 10
TypeCentrifugal
Motor Sheave1VL441VP56
Blower SheaveAK56AK56
BeltA36A38
Motor HP each1-1/23
RPM1725
Frame size56
DIRECT DRIVE EVAP FAN DATA
Quantity1
Fan Size (Inch)12 x 10
TypeCentrifugal
Motor HP each1
RPM1050
FILTERS
15” x 20” x 1” or 2”2
14” x 25” x 1” or 2”1
1. Cooling Only or Cooling with Electric Heat Unit
2. Cooling with Gas Heat Unit
3. Cooling Only or Cooling with Electric Heat Unit (ECM O.D. Fan Motor)
4. Cooling with Gas Heat Unit (PSC O.D. Fan Motor)
NOTE: All 2 Stage Gas Heat, 60% Capacity 1st Stage, 40% Capacity 2nd Stage.
Johnson Controls Unitary Products17
251933-YTG-X-0615
ZR036-060 Physical Data
Component
Nominal Tonnage3.04.05.0
AHRI COOLING PERFORMANCE
Gross Capacity @ AHRI A point (Btu)363004960060800
AHRI net capacity (Btu)350004800058500
EER11.211.211.2
SEER13.013.013.0
IPLV--CFM120016002000
System power (KW)3.134.185.3
Refrigerant typeR-410aR-410aR-410a
Refrigerant charge (lb-oz)
System 111-212-411-12
AHRI HEATING PERFORMANCE
Heating modelN04N08D06D10N06N10D06D10N08N10D06D10
Heat input (K Btu)5010075115751257512510012575125
Heat output (K Btu)408060.8926010060.8100.68010060.8100.6
AFUE %-----------Steady state efficiency (%)--80.080.0--80.080.0--80.080.0
No. burners243535354535
No. stages112211221122
Temperature Rise Range (ºF)15-45 45-75 35-70 55-90 25-70 45-75 25-70 45-75 25-55 35-75 20-55 35-75
Gas Limit Setting (ºF) - Direct Drive240170210200210165210165170165210165
Gas Limit Setting (ºF) - Belt Drive240210240200240210240210210210210210
Gas piping connection (in.)1/21/21/21/21/21/21/21/21/21/21/21/2
TypeScrollScrollScroll
Quantity111
Unit Capacity Steps (%)100100100
CONDENSER COIL DATA
Face area (Sq. Ft.)16.916.916.9
Rows222
Fins per inch181818
Tube diameter (in.)3/83/83/8
Circuitry TypeSplit-faceSplit-faceSplit-face
EVAPORATOR COIL DATA
Face area (Sq. Ft.)5.065.065.06
Rows334
Fins per inch131313
Tube diameter0.3750.3750.375
Circuitry TypeSplit-faceSplit-faceSplit-face
Refrigerant controlTXVTXVTXV
ZR036ZR048ZR060
Models
18Johnson Controls Unitary Products
ZR036-060 Physical Data (Continued)
251933-YTG-X-0615
Component
Nominal Tonnage3.04.05.0
CONDENSER FAN DATA
Quantity111
Fan diameter (Inch)242424
TypePropPropProp
Drive typeDirect DriveDirect DriveDirect Drive
No. speeds111
Number of motors111
Motor HP each1/21/21/2
RPM109010901090
CFM420042004200
BELT DRIVE EVAP FAN DATA
Quantity111
Fan Size (Inch)11 x 1011 x 1011 x 10
TypeCentrifugalCentrifugalCentrifugal
Motor Sheave1VL441VP561VL441VP561VL441VP56
Blower SheaveAK64AK66AK56AK61AK56AK56
BeltA37A39A36A38A36A38
Motor HP each1-1/21-1/21-1/21-1/21-1/22
RPM172517251725
Frame size565656
DIRECT DRIVE EVAP FAN DATA
Quantity111
Fan Size (Inch)11 x 1011 x 1011 x 10
TypeCentrifugalCentrifugalCentrifugal
Motor HP each1/211
RPM105010501050
FILTERS
15” x 20” x 1” or 2”222
14” x 25” x 1” or 2”111
ZR036ZR048ZR060
Models
NOTE: All 2 Stage Gas Heat, 60% Capacity 1
st
Stage, 40% Capacity 2nd Stage.
Johnson Controls Unitary Products19
251933-YTG-X-0615
XN036-060 Physical Data
Component
Nominal Tonnage345
AHRI COOLING PERFORMANCE
Gross Capacity @ AHRI A point (Btu)38,40048,700
AHRI net capacity (MBH)37,00047,000
EER12.011.8
SEER14.014.0
CFM12001450
System power (KW)3.083.98
Refrigerant typeR410AR410A
Refrigerant charge (lb-oz)
System 113-813-10
ARI HEATING PERFORMANCE
47ºF capacity rating (MBH)36,00044,000
System power (KW) / COP3.15 (kW) / 3.35 4.03 (kW) / 3.20
17ºF capacity rating (MBH)19,00024,900
System power (KW) / COP2.5 (kW) / 2.2 3.48 (kW) / 2.10
HSPF (Btu/Watts-hr)8.008.00
Face area (Sq. Ft.)16.8816.88
Rows22
Fins per inch1818
Tube diameter3/83/8
Circuitry TypeSplit-faceSplit-face
Refrigerant controlTXVTXVTXV
EVAPORATOR COIL DATA
Face area (Sq. Ft.)5.065.06
Rows44
Fins per inch1313
Tube diameter0.3750.375
Circuitry TypeSplit-faceSplit-face
Refrigerant controlTXVTXV
XN036XN048XN060
Models
5,750
55,400
11.0
14.0
1275/1850
5.04
R410A
11-10
51,500
4.5 (kW) / 3.35
30,000
4.11 (kW) / 2.14
8.00
82-1/4
44-7/8
32-5/8
620
SCROLL
1
16.88
2
18
3/8
Split-face
5.06
4
13
0.375
Split-face
TXV
20Johnson Controls Unitary Products
XN036-060 Physical Data (Continued)
251933-YTG-X-0615
Component
Nominal Tonnage345
CONDENSER FAN DATA
Quantity11
Fan diameter (Inch)2424
TypePropProp
Drive typeDIRECT DRIVE DIRECT DRIVE
No. speeds11
Number of motors11
Motor HP each1/41/4
RPM850850
CFM30003300
BELT DRIVE EVAP FAN DATA
Quantity11
Fan diameter (Inch)12 x 1012 x 10
TypeCentrifugalCentrifugal
Motor Sheave1VL44 1VP56 1VL44 1VP56 1VL44 1VP56
Blower SheaveAK64 AK66 AK56AK61 AK56AK56
BeltA37A39A36A38A36A38
Motor HP each1-1/21-1/21-1/21-1/21-1/22
RPM17401740
Frame size5656
DIRECT DRIVE EVAP FAN DATA
Quantity11
Fan Size (Inch)12 x 1012 x 10
TypeCentrifugalCentrifugal
Motor HP each1/21
RPM10501050
FILTERS
15" x 20" x 1" or 2"22
14" x 25" x 1" or 2"11
XN036XN048XN060
Models
1
24
Prop
DIRECT DRIVE
2
1
1/2
850/1100
2800/3800
1
12 x 10
Centrifugal
1740
56
1
12 x 10
Centrifugal
1
1050
2
1
Johnson Controls Unitary Products21
251933-YTG-X-0615
XP036-060 Physical Data
Component
Nominal Tonnage3.04.05.0
AHRI COOLING PERFORMANCE
Gross Capacity @ AHRI A point (Btu)37,5004650060100
AHRI net capacity (Btu)36,0004450057500
EER11.411.010.6
SEER13.013.013.0
CFM130016001850
System power (KW)3.304.055.42
Refrigerant typeR410AR410AR-410A
Refrigerant charge (lb-oz)13-813-1212-10
AHRI HEATING PERFORMANCE
47°F capacity rating (MBH)35,00041,00056500
System power (KW) / COP3.10 (kW) / 3.304.0 (kW) / 3.205.4 (kW) / 3.10
17°F capacity rating (MBH21,20022,40034400
System power (KW) / COP2.89(kW) / 2.153.8 (kW) / 2.104.75 (kW) / 2.10
HSPF (Btu/Watts-hr)7.707.707.70
Face area (Sq. Ft.)16.8816.8816.88
Rows222
Fins per inch181818
Tube diameter3/83/83/8
Circuitry TypeSplit-faceSplit-faceSplit-face
EVAPORATOR COIL DATA
Face area (Sq. Ft.)5.065.065.06
Rows444
Fins per inch131313
Tube diameter0.3750.3750.375
Circuitry TypeSplit-faceSplit-faceSplit-face
Refrigerant controlTXVTXVTXV
XP036XP048XP060
Models
22Johnson Controls Unitary Products
XP036-060 Physical Data (Continued)
251933-YTG-X-0615
Component
Nominal Tonnage3.04.05.0
CONDENSER FAN DATA
Quantity111
Fan diameter (Inch)242424
TypePropPropProp
Drive typeDirect DriveDirect DriveDirect Drive
No. speeds111
Number of motors111
Motor HP each1/41/41/2
RPM8508501090
Nominal total CFM327538004200
BELT DRIVE EVAP FAN DATA
Quantity111
Fan Size (Inch)11 x 1011 x 1011 x 10
TypeCentrifugalCentrifugalCentrifugal
Motor Sheave1VL441VP561VL441VP561VL441VP56
Blower SheaveAK64AK66AK56AK61AK56AK56
BeltA37A39A36A38A36A38
Motor HP each1-1/21-1/21-1/21-1/21-1/22
RPM172517251725
Frame size565656
DIRECT DRIVE EVAP FAN DATA
Quantity111
Fan Size (Inch)11 x 1011 x 1011 x 10
TypeCentrifugalCentrifugalCentrifugal
Motor HP each3/411
RPM105010501050
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
(kW)
Total
Input
Sensible Capacity (MBh)
2
30Johnson Controls Unitary Products