York XP R410A Technical Guide

®
TECHNICAL GUIDE
®
R-410A XP SERIES
6.5 THRU 12.5 TON 60 Hertz
528195-YTG-L-1014

Description

ASHRAE 90.1 COMPLIANT
YORK common footprint cabinet and common roof curb for all 6.5 through 12.5 ton models. All units have two compressors with independent refrigeration circuits to provide 2 stages of cooling. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, or fra me.
All Predator full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged, wired, piped, and tested at the factory to provide a quick and easy field installation.
Predator side airflow and down airflow, with corresponding economizer if economizer option is desired.
Predator® units are convertible single packages with a
units are self-contained and assembled on rigid
units in all tonnage sizes are convertible between
6.5 THROUGH 10 TON
Predator® XP units are available in the following configurations: heat pump and heat pump with electric heat. Electric heaters are available as factory-installed options or field-installed accessories.
Tested in accordance with:
12.5 TON
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
528195-YTG-L-1014
Compressor #1 Access (High-Eff Compressor)
Toolless Door Latch
Side entry power and control wiring knockouts
Slide-out drain pain with steel 3/4” NPT, Female Connection
Belt-drive blower motor
Condenser section
Filter drier (solid core)
Filter access
(2” or 4” filter options)
Disconnect location (optional disconnect switch)
Compressor #2 Access (High-Eff Compressor)
Simplicity
TM
SE Control board w/screw connec­tors for T-stat wiring and network connection
Roof curbs in eight- and fourteen-inch heights. Roof curbs for transitioning from Sunline™ footprint to the XP series footprint are also available (field installed accessory)
Base Rails w/ Fork­lift Slots (3 Sides) & Lifting Holes
Terminal block for hi-voltage connection
Dual stage cool­ing for maximum comfort (7-1/2 ­12-1/2 Only)
Second Model Nameplate Inside Control Door
Slide-out motor and blower assembly for easy adjustment and service.

Table of Contents

Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Economizer Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

Component Location

Heat Pump

2 Johnson Controls Unitary Products

Nomenclature

X P 090 C00 A 2 A AA 7 0 1 2 4 A
Product Category
X = HP, Single Pkg., R-410A
7 = Seventh Generation
Product Generation
C00 = Cooling Only. No heat installed
Heat Type and Nominal Heat Capacity
E09=9KW E18 = 18 KW E24 = 24 KW E36 = 36 KW E54 = 54 KW
Electric Heat Options
078 = 6.5 Ton
Nominal Cooling Capacity
090 = 7.5 Ton 102 = 8.5 Ton 120 = 10.0 Ton 150 = 12.5 Ton
Product Identifier
P = 11.0 EER HP
Voltage
2 = 208/230-3-60 4 = 460-3-60 5 = 575-3-60
Product Style
A = Style A B = Style B C = Style C
A = No Options Installed
Installation Options
B=Option1 C = Option 2 D = Options 1 & 2 E = Option 3 F=Option4 G = Options 1 & 3 H = Options 1 & 4 J = Options 1, 2 & 3 K = Options 1, 2, & 4 L = Options 1,3 & 4 M = Options 1, 2, 3, & 4 N = Options 2 & 3 P=Options2&4 Q = Options 2, 3, & 4 R = Options 3 & 4 S=Option5 T = Options 1 & 5 U = Options 1, 3, & 5 V = Options 1, 4, & 5 W = Options 1, 3, 4, & 5 X=Options3&5 Y=Options4&5 Z = Options 3, 4 & 5
1 = Disconnect 2 = Non-Pwr'd Conv. Outlet 3 = Smoke Detector S.A. 4 = Smoke Detector R.A. 5=Pwr'dConv.Out
let
Options
SS Drain Pan
Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.
CPC Controller, DFS, APS
2" Pleated Filters, MERV 7
Shipping Bag
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
AA = None AB = Phase Monitor AC = Coil Guard AD = Dirty Filter Switch AE = Phase Monitor & Coil Guard AF = Phase Monitor & Dirty Filter Switch AG = Coil Guard & Dirty Filter Switch AH = Phase Monitor, Coil Guard & Dirty Filter Switch
Additional Options
RC = Coil Guard, Shipping Bag & American Flag TA = Technicoat Condenser Coil TJ = Technicoat Evaporator Coil TS = Technicoat Evaporator & Condenser Coils
6.5-12.5 Ton York® Model Number Nomenclature
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
BAS Ready Economizer (2-10 V.D.C. Actuator without a Controller)
4" Pleated Filters, MERV 13
EA = E-Coat Condenser Coil EJ = E-Coat Evaporator Coil ES = E-Coat Cond & Evap Coils
IntelliSpeed with VFD
IntelliSpeed, VFD and Manual Bypass
IntelliSpeed, VFD Ready (for customer-provided, field-installed drive)
Airow
Honeywell Controller, DFS, APS
Novar Controller, DFS, APS
Simplicity®Smart Equipment w/Comm Card (BACnet, N2, Mod-Bus)
A = Std. Motor D = Std. Motor/Motorized Damper (Downow Only) H = Std Motor/Low Leak Econ/Barometric Relief (Downow & Horizontal End Return Only) J = Std Motor/Low Leak Econ/Power Exhaust (Downow & Horizontal End Return Only) N = Hi Static R = Hi Static/Motorized Damper (Downow Only) V = Hi Static Mtr/Low Leak Econ/Barometric Relief (Downow & Horizontal End Return Only) W = Hi Static Mtr/Low Leak Econ/Power Exhaust (Downow & Horizontal End Return Only)
528195-YTG-L-1014
Johnson Controls Unitary Products 3
528195-YTG-L-1014

Features and Benefits

Standard Features

High Efficiency – High efficiency units reach as high as
11.5 EER. These efficiencies exceed all legislated minimum levels and provide low operating costs.
Service Friendly - The Predator® incorporates a number of key features for ease of serviceability.
Service time is reduced through the use of hinged, toolless panels. Such panels provide access to frequently inspected components and areas, including the control box, compressors, filters, indoor motor & blower, and the heating section. The panels are screwed in place at the factory to prevent access by children or other unauthorized persons. It is recommended that the panels be secured with screws once service is complete.
Service windows have been placed in both condenser section walls. Rotation of the cover allows easy access to the condenser coils for cleaning or inspection.
The Simplicity® SE control board provides alarm messages to help quickly identify any faults.
All units use the same standard filter size. This standardization removes any confusion on which filter sizes are needed for replacement.
The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing the drain pan cover plate on the rear of the unit. Once the plate is removed, the drain pan slides out through the rear of the unit.
All Predator located inside the control access door. This is to prevent deterioration of the nameplate through weathering.
Environmentally Aware - For improved Indoor Air Quality, a combination of aluminum foil faced and elastometric rubber insulations are used exclusively throughout the units.
Convertible Airflow Design – The side duct openings are covered when they leave the factory. If a side supply/ return is desired, the installer simply removes the two side duct covers from the outside of the unit and installs them over the down shot openings. No panel cutting is required. Convertible airflow design allows maximum field flexibility and minimum inventory.
System Protection - Suction line freezestats are supplied on all units to protect against loss of charge and coil frosting when the economizer operates at low outdoor air temperatures while the compressors are running. Every unit has solid-core liquid line filter-driers and high and low­pressure switches. Internal compressor protection is standard on all compressors. Crankcase heaters are standard on reciprocating compressors. Scroll compressors do not require crankcase heaters. Phase Monitors are standard on units with scroll compressors. This accessory monitors the incoming power to the unit and protects the unit from phase loss and reversed phase rotation.
Advanced Controls - Simplicity® SE control boards have standardized a number of features previously available only as options or by utilizing additional controls.
units have a second model nameplate
The Simplicity® SE control board used in this product will effectively operate the cooling system down to 0°F when this product is applied in a comfort cooling application for people. An economizer is typically included in this type of application. When applying this product for process cooling applications (computer rooms, switchgear, etc.), please reference applications bulletin AE-011-07 or call the applications department for Unitary Products @ 1­877-UPG-SERV for guidance. Additional accessories may be needed for stable operation at temperatures below 30°F.
Units will come with the new state of the art Simplicity SE (Smart Equipment) control system. The new unit control incorporates the best of the already proven Simplicity™ unitary controls and creates a more robust, intelligent control. The goal of this control is to utilize cutting edge technology making the equipment easier to install, operate, and service. All units are Factory commissioned, configured, and run tested.
Versatile - The Simplicity SE control can be configured to use with a standard thermostat (easy to connect screw terminals), A zone sensor, or can be setup to communicate with multiple BAS communication protocols to integrate with building automation systems.
Reduce field installed complexity - Each unit will comes equipped with factory installed supply air, return air, and outdoor air temperature sensors providing key temperature readings thus reduce field installed complexity.
On-board USB Port - The new control comes with a long list of features including data logging, current and previous system faults and software update capabilities using the on board USB port and common flash drive. Energy use monitoring capabilities allow custom tailoring to allow a system to work more efficiently at all times and occupancy levels. Self test and start-up reports also available from the board VIA the USB port.
4 Johnson Controls Unitary Products
528195-YTG-L-1014
Embedded LCD Display - The board has a easy to read, built-in LCD display and easy to use navigation joystick and buttons allowing the user to quickly navigate the menus displaying unit status, options, current function, supply, return and outdoor temperatures, fault codes and other information.
Safety Monitoring - The control monitors the outdoor, supply, and return air temperatures and the high and low pressure switch status on the independent refrigerant circuits. On units with heating the gas valve and high temperature limit switches are monitored on gas and electric heating units. The control also monitors the voltage supplied to the unit and will protect the unit if low voltage due to a brown out, or other electrical issue occurs.
Low Ambient - An integrated low-ambient control allows units to operate in the cooling mode down to 0°F outdoor ambient without additional components or intervention. Optionally, the control board can be programmed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.
Anti-Short Cycle Protection - To aid compressor life, an anti- short cycle delay is incorporated into the standard control. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti­short cycle delay can be temporarily overridden with the push of a button.
Fan Delays - Fan on and fan off delays are fully programmable. Furthermore, the heating and cooling fan delay times are independent of one another. All units are programmed with default values based upon their configuration of cooling and/or heating capacity.
Nuisance Trip Protection and Three Strikes - To prevent nuisance calls, the control board uses a three times, you're out philosophy. The high, low-pressure switch, anti-freeze protection, low voltage or heating high limit must trip three times within two hours before the unit control board will lock out the associated compressor.An alarm message will be displayed on the LCD screen.
Lead-Lag - An integrated Lead-Lag option allows equal run time hours on all compressors, thereby extending the life of all compressors. This option is selectable on the unit control board.
Low Limit Control (LLC) - To prevent the supply air from dropping below a specified set point, when there is a demand for cooling during cold outside conditions. (Programmable Set point)
Reliable - From the beginning - All units undergo computer automated testing before they leave the factory. Units are tested for refrigerant charge and pressure, unit amperage, and 100% functionality. For the long term - All units are painted with a long lasting, powder paint that stands up over the life of the unit. The paint used has been proven by a 1000 hour salt spray test.
Full Perimeter Base Rails - The permanently attached base rails provide a solid foundation for the entire unit and protect the unit during shipment. The rails offer rigging holes so that an overhead crane can be used to place the units on a roof.
Easy Installation - Gas and electric utility knockouts are supplied in the unit underside as well as the side of the unit. Utility connections can be made quickly and with a minimum amount of field labor. All units are shipped with 2" throw-away filters installed.
Wide Range of Indoor Airflows - All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job. A high static drive option is available for applications with a higher CFM and/ or static pressure requirement.
Warranty - All models include a 1-year limited warranty on the complete unit. Compressors and electric heater elements each carry a 5-year warranty. Aluminized steel (10 yr.) and stainless steel tubular heat exchangers carry a 15- year warranty.

Factory Installed Options

YORK® offers several equipment options factory installed, for the Predator®line.
Optional Factory Installed Economizers - Predator units offer a variety of optional factory installed economizers with low leak dampers. The outdoor air dry bu lb sensor enables economizer operation if the outdoor air temperature is less than the set point of the economizer logic module. See economizer options section to determine the correct economizer for your application.
Down flow / End Return Economizers (with barometric relief and fresh air hood) - All units offer a va riety of optional factory installed down flow eco no mizers th at are shipped, installed and wired with low l ea k da mpers designed to meet ASHRAE 90.1-2010, AMCA 511 Class 1A damper, and the International Energy Conservation Code (IECC) certification requirements by achieving leakage rates of 3 cfm/sq. ft. at 1" of static pressure. Each economizer goes through a rigorous 60,000 cycle test. Dry bulb, single enthalpy, and dual enthalpy (wit h field installed kit) can be selected. The economizer has spring return , fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the outdoor air dry bulb temperature or the outdoor air enthalpy i nput. The optional (field installed) single or dual enthalpy kits provi de additional inputs to monitor outdoor air/ or return air humidity and temperature for true enthalpy co ntrol. The installer needs only to assemble the outdoor air hood, attach the enthalpy control the hood and mo un t the hood to the unit (Hood and control are provided).
Power Exhaust - Power Exhaust - This factory option allows down flow or horizontal end return economizer operation. The power exhaust must be removed from
the unit and mounted in the horizontal end return duct work when applying the product in the horizontal, end return configuration.
Motorized Outdoor Air Damper - The motorized outdoor air damper includes a slide-in/plug-in damper assembly with an outdoor air hood and filters. The outdoor air dampers open to the preset position when the indoor fan motor is energized. The damper has a range of 0% to 100% outdoor air entry.
Johnson Controls Unitary Products 5
528195-YTG-L-1014
Alternate Indoor Blower Motor - For applications with high static restrictions, units are offered with optional indoor motors that provide higher static output and/or higher airflow, depending upon the installer’s needs.
Stainless Steel Drain Pan - An optional rust-proof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environments.
Electric Heaters - The electric heaters range from 9kW to 54kW and are available in all the voltage options of the base units. All heaters are dual staged. All heaters are intended for single point power supply.
IntelliSpeed™ Supply Fan Control Option (ASHRAE
90.1 compliant, section 6.4.3.10) - Units configured with the IntelliSpeed™ Supply Fan Option will contain a VFD for multi-speed supply fan operation. This option allows the supply fan RPM to vary based on the number of compressors or heating stages energized. The economizer's minimum position will also be configurable to vary based on the supply fan VFD frequency output.
Disconnect Switch - For heat pump units with electric heat, a HACR breaker sized to the unit is provid e d. For heat pump units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only.
Convenience Outlet - (Non-Powered/Powered) - This option locates a 120V single-phase GFCI outlet with cover, on the corner of the unit housing adjacent to the compressors. The “Non-powered” option requires the installer to provide the 120V single-phase power source and wiring. The “Powered” option is powered by a stepdown transformer in the unit. Factory installed option only.
Smoke Detectors - The smoke detectors stop operation of the unit and provide a fault message to the control board. Smoke detectors are available for both the supply and/or return air configurations.
Factory installed smoke detectors in the return air, may be subjected to freezing temperatures during "off" times due to out side air infiltration. These smoke detectors have an operational limit of 32 °F to 131°F. Smoke detectors installed in areas that could be out side those limitations will have to be moved to prevent having false alarms.
Filters – 2” Pleated MERV 7 or 4” Pleated MERV 13 are available to meet LEED requirements. A 2” Throwaway is shipped as standard.
Phase Monitors - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of phase condition. (Standard on units with Scroll Compressors.)
Coil Guard - Customers can purchase a coil guard kit to protect the condenser coil from damage. Additionally, this kit stops animals and foreign objects from entering the space between the inner condenser coil and the main cabinet. This is not a hail guard kit.
Dirty Filter Switch - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option or field installed accessory.
Technicoat Condenser Coils - The condenser coils are coated with a phenolic coating for protection against corrosion due to harsh environments.
Technicoat Evaporator Coil - The evaporator coils are coated with a phenolic coating for protection against corrosion due to harsh environments.
E-coat Condenser Coils coated with an epoxy polymer coating to protect against corrosion.
E-coat Evaporator Coils - The evaporator coils are coated with an epoxy polymer coating to protect against corrosion.
- The condenser coils are

Control Options

Simplicity® SE with Communication Option Control ­The York® Simplicity® SE with Communication Option Control is factory installed. It includes all the features of the Simplicity® SE control with an additional gateway to BACnet MS/TP (programmable to Modbus or N2 protocols).
Novar® BAS Control - The Novar® building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.
CPC BAS Control - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes supply air sensor, return air sensor, with optional dirty filter indicator switch and air proving switch .
Honeywell BAS Control - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, with optional dirty filter indicator switch, and air proving switch.
York Commercial Comfort System (YCCS) - Provides rooftop system integration for YCCS single zone and change-over bypass systems.

Field Installed Accessories

YORK® offers several equipment accessories for field installation, for the Predator
Down flow and End Return Economizers (with fresh air hood and barometric relief) - All units offer a variety of optional factory installed down flow economizers that are shipped, installed and wired with low leak dampers designed to meet ASHRAE 90.1-2010, AMCA 511 Class 1A damper, and the International Energy Conservation Code (IECC) certification requirements by achieving leakage rates of 3 cfm/sq. ft. at 1" of static pressure. Each econo mizer goes through a rigorous 60,000 cycle test. Dry bulb, single enthalpy, and dual enthalpy (with field installed kit) can be selected. The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the outdoor air dry bulb temperature or the outdoor air enthalpy input. The dual enthalpy kit provides a second input used to monitor the return air (field installed). The installer needs only
line.
6 Johnson Controls Unitary Products
528195-YTG-L-1014
to assemble the outdoor air hood, attach the enthalpy control the hood and mount the hood to the unit (Hood and control are provided).
Single or Dual Enthalpy Control, Accessories - These kits contain the required components to convert a dry bulb economizer to a single enthalpy and/or dual enthalpy economizer.
Barometric Relief Damper - Zero to 100% capacity barometric relief dampers for use with horizontal flow, or field installed economizers.
Power Exhaust - This accessory installs in the unit with a down flow or horizontal end return economizer. Power exhaust plugs into the connector in the unit bulkhead.
User must purchase the 1EH0408 barometric relief and hood kit when applying the product in a horizontal flow application. The power exhaust must be mounted in the horizontal end return ductwork.
Manual Outdoor Air Damper - Like the motorized outdoor air damper, each manual outdoor air damper includes a slide-in damper assembly with an outdoor air hood and filters. Customers have a choice of dampers with ranges of 0% to 100% or 0% to 35% outdoor air entry.
Motorized Outdoor Air Damper - The motorized outdoor air damper includes a slide-in/plug-in damper assembly with an outdoor air hood and filters. The outdoor air dampers open to the preset position when the indoor fan motor is energized. The damper has a range of 0% to 100% outdoor air entry. Factory installed option or field installed accessory.
Smoke Detectors - The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.
Sensor - Senses CO2 levels and automatically
CO
2
overrides the economizer when levels rise above the preset limits.
Dirty Filter Switch - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters.
Coil Guard - Field installed decorative wire coil guard.
Hail Guard - This kit includes a sloped hood which installs over the outside condenser coil and prevents damage to the coil fins from hail strikes. Field installed accessory only.
Electric Heaters - The electric heaters range from 9 kW to 54kW and are available in all the voltage options of the base units. All heaters are dual staged. All units include an adapter panel for easy installation of the electric heaters. Necessary hardware and connectors are included with the heaters. All heaters are intended for single point power supply.
• Low Limit / Compressor Lockout Kit
Compressor Lockout (CLO): To prevent mechanical
(compressorized) operation of the unit during cold outdoor conditions where there is a risk of returning liquid refrigerant back to the compressors.
Low Limit Control (LLC): To prevent the supply air
from dropping below a specified setpoint by utilizing the units first stage heating means when there is a demand for cooling during cold outside conditions.
Metal Frame Filter Kit - Metal frame with polyester filter medium.
Permanent Filters - Permanent filters are available.
Roof Curbs - The roof curbs have insulated decks and are shipped disassembled The roof curbs are available in 8” and 14” heights. For applications with security concerns, burglar bars are available for the duct openings of the roof curbs.
Roof Curb Transition - Single Piece Adapter (10” High) ­Roof curbs for transitioning from Sunline™ units to Predator
units. Fits 7.5 to 12.5 Sunline™ roof curbs only.
Burglar Bars - Mount in the supply and return openings to prevent entry into the duct work.
Thermostat - The units are designed to operate with 24­volt electronic and electro-mechanical thermostats. All units (with or without an economizer) operate with two­stage heat/two-stage cool or two-stage cooling only thermostats, depending upon unit configuration.
Johnson Controls Unitary Products 7
528195-YTG-L-1014
Accessories
Part Number Description
1RC0470 Roof Curb, 8" Height 1RC0471 Roof Curb, 14" Height 1RC0472 Roof Curb, Transition (7.5 T th rough 12.5 T) 1BD0408 Burglar Bars, Downflow 2TP04520925 Electric Heat 9kW 230V 2TP04521825 Electric Heat 18kW 230V 2TP04522425 Electric Heat 24kW 230V 2TP04523625 Electric Heat 36kW 230V 2TP04525425 Electric Heat 54kW 230V 2TP04520946 Electric Heat 9kW 460V 2TP04521846 Electric Heat 18kW 460V 2TP04522446 Electric Heat 24kW 460V 2TP04523646 Electric Heat 36kW 460V 2TP04525446 Electric Heat 54kW 460V 2TP04520958 Electric Heat 9kW 575V 2TP04521858 Electric Heat 18kW 575V 2TP04522458 Electric Heat 24kW 575V 2TP04523658 Electric Heat 36kW 575V 2TP04525458 Electric Heat 54kW 575V 2TP04540925 Electric Heat 9kW 230V, 42" Tall Cabinet 2TP04541825 Electric Heat 18kW 230V, 42" Tall Cabinet 2TP04542425 Electric Heat 24kW 230V, 42" Tall Cabinet 2TP04543625 Electric Heat 36kW 230V, 42" Tall Cabinet 2TP04540946 Electric Heat 9kW 460V, 42" Tall Cabinet 2TP04541846 Electric Heat 18kW 460V, 42" Tall Cabinet 2TP04542446 Electric Heat 24kW 460V, 42" Tall Cabinet 2TP04543646 Electric Heat 36kW 460V, 42" Tall Cabinet 2TP04540958 Electric Heat 9kW 575V, 42" Tall Cabinet 2TP04541858 Electric Heat 18kW 575V, 42" Tall Cabinet 2TP04542458 Electric Heat 24kW 575V, 42" Tall Cabinet 2TP04543658 Electric Heat 36kW 575V, 42" Tall Cabinet 2MD04703824 Motorized Damper, Downflow without Barometric Relief 2MD04703924 Motorized Damper, Horizontal
2EE04707624 Economizer for Downflow, End Return Horizontal, or ERV Applications. Includes FA Hood, Exhaust Hood w/Baro Relief 2EE04707424 Economizer for Downflow, End Return Horizontal, or ERV Applications. Includes FA Hood, Exhaust Hood w/Baro Relief 2EE04706924 Horizontal Economizer without Barometric Relief
2PE04704706* Power Exhaust 230V Downflow or Horizontal 2PE04704746* Power Exhaust 460V Downflow or Horizontal 2PE04704758* Power Exhaust 575V Downflow or Horizontal 2EC04700924 Dual Enthalpy Control (Use with Si ngle Enthalpy Economizer) 2EC0401 Single Enthalpy Control 2EC0402 Dual En thalpy Control (Includes 2 Sensor s)
1EH0408 Barometric Relief Kit for Power Exhaust, Horizontal Application
1FA0413 Manual Outside Air Damper 0-35%, Downflow 1FA0414 Manual Outside Air Damper 0-100%, Downfl ow 2AQ04700424 CO2 Detector Unit Mount 2AQ04700324 CO2 Detector Space Mount 2SD04700824 Smoke Detector for Supply ( 2SD04700924 Smoke Detector for Return ( 2SD04701024 Smoke Detector for Supply and Return (All Gen 5 units and greater with 2" & 4" Filters) 2MK04700624 Low Limit / Compress or Lockout Kit 1CG0419 Coil Guard (Electric / Electric & HP models), 8-1/2 and 10 Ton 1CG0424 Coil Guard (Electric / Electric and HP models), 12-1/2 Ton 1CG0427 Coil Guard (Electric / Electric & HP Models), 6-1/2 and 7-1/2 Ton 1HG0411 Hail Guard Kit 1HG0415 Hail Guard Kit, 42" Tall Cabinet 1FL0402 Permanent Filter Kit 1FL0423 Permanent Filter Kit, 42" Tall Cabinet 2DF0401 Dirty Filter Switch 1FF0414 2” only Metal Filter Frame Kit, 50” Tall Cabinet 1FF0415 2” only Metal Filter Frame Kit, 42" Tall Cabinet S1-YK-MAP1810-0P MAP (Mobile Access Portal) Gateway- For use with Simplicity SE Control.
S1-MP-PRTKIT-0P
MAP (Mobile Access Portal ) Gate way Ki t- Repl aceme nt MAP g atewa y prote ctive case, lanyar d and communi cation cable . Use only to replace worn or damaged components.
All Gen 5 units and greater with 2" & 4" Filters) All Gen 5 units and greater with 2" & 4" Filters)
8 Johnson Controls Unitary Products
528195-YTG-L-1014

Guide Specifications

GENERAL
Units shall be manufactured by York International Unitary Products in an ISO 9001 certified facility. YORK® Predator units are convertible single packages with a common footprint cabinet and common roof curb for all 6-1/2 through 12-1/2 ton models. All units have two compressors with independent R­410a refrigeration circuits to provide 2 stages of cooling. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, or frame. All Predator units are self-contained and assembled on rigid full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged with R-410a, wired, piped, and tested at the factory to provide a quick and easy field installation. All units are convertible between side and down airflow. Independent economizer designs are used on side and down discharge applications, as well as all tonnage sizes. Predator
units are available in the following configurations: heat pump and heat pump with electric heat. Electric heaters are available as factory-installed options or field-installed accessories.
DESCRIPTION
Units shall be factory assembled, single package (Heat Pump), designed for outdoor installation. They shall have built in field convertible duct connections for down discharge supply/return or horizontal discharge supply/return and be available with factory installed options or field installed accessories. The units shall be factory wired, piped and charged with R-410a refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. The cooling performance shall be rated in accordance with DOE and AHRI test procedures. Units shall be CSA certified to ANSI Z21.47 and UL 1995/CAN/CSA No. 236-M90 standards.
UNIT CABINET
Unit cabinet shall be constructed of galvanized steel with exterior surfaces coated with a non-chalking, powder paint finish, certified at 1000 hour salt spray test per ASTM-B117 standards. Indoor blower sections shall be insulated with up to 1” thick insulation coated on the airside. Either aluminum foil faced or elastometric rubber insulation shall be used in the unit’s compartments and be fastened to prevent insulation from entering the air stream. Cabinet doors shall be hinged with toolless access for easy servicing and maintenance. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging, fork truck access and proper sealing on roof curb applications. Disposable 2” filters shall be furnished and be accessible through hinged access door. Fan performance measuring ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator fan performance without removing panels or creating bypass of the coils. Condensate pan shall be slide out design, constructed of a non corrosive material, internally sloped and conforming to ASHRAE 62-B9 standards. Condensate connection shall be a minimum of ¾” I.D. female and be rigid mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be a belt drive assembly and include an adjustable pitch motor pulley. Job site selected brake horsepower shall not exceed the motors nameplate horsepower rating plus the ser­vice factor. Units shall be designed to operate within the service factor. Fan wheel shall be double inlet type with forward curve blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant volume. Bearings shall be sealed and permanently lubricated for longer life and no maintenance. Entire blower assembly and motor shall be slide out design.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fans shall be of the direct drive type, discharge air vertically, have aluminum blades riveted to corrosion resistant steel spider brackets and shall be dynamically balanced for smooth operation. The outdoor fan motors shall have permanently lubricated bearings internally protected against overload conditions and staged independently. A cleaning window shall be provided on two sides of the units for coil cleaning.
REFRIGERANT COMPONENTS
Compressors:
a. Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over temperature protection. The hermetic motor shall be suction gas cooled and have a voltage range of + or – 10% of the unit nameplate voltage.
b. Shall have internal spring isolation and sound muffling to
minimize vibration and noise, and be externally isolated on a dedicated, independent mounting.
Coils:
a. Evaporator and condenser coils shall have aluminum
plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option.
b. Evaporator and condenser coils shall be of the direct
expansion, draw-thru design.
Refrigerant Circuit and Refrigerant Safety Components shall include:
a. Independent fixed-orifice or thermally operated
expansion devices.
b. Solid core filter drier/strainer to eliminate any moisture or
foreign matter.
c. Accessible service gage connections on both suction
and discharge lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting, without losing charge.
d. The unit shall have two independent refrigerant circuits,
equally split in 50% capacity increments.
Johnson Controls Unitary Products 9
528195-YTG-L-1014
Unit Controls:
a. Unit shall be complete with self-contained low-voltage
control circuit protected by a resettable circuit breaker on the 24-volt transformer side.
b. Unit shall incorporate a lockout circuit which provides
reset capability at the space thermostat or base unit, should any of the following standard safety devices trip and shut off compressor.
1.Loss-of-charge/Low-pressure switch.
2.High-pressure switch.
3.Freeze condition sensor on evaporator coil. If any of these safety devices trip, the LCD screen will display the alarm message.
c. Unit shall incorporate "AUTO RESET" compressor over
temperature, over current protection.
d. Unit shall operate with conventional thermostat designs
and have a low voltage terminal strip for easy hook-up.
e. Unit control board shall have on-board diagnostics and
fault message display.
f. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to a selectable value as low as 0 °F.
g. Control board shall monitor each refrigerant safety switch
independently.
maximum leakage rate for the outdoor air intake dampers shall be designed to meet ASHRAE 90.1-2010, AMCA 511 Class 1A damper, and the International Energy Conservation Code (IECC) certification requirements by achieving leakage rates of 3 cfm/sq. ft. at 1" of static pressure. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided.
Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss. Available with barometric relief and power exhaust.
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and return air dampers that are interlocked and positioned by a 2- position, spring-return damper actuator. A unit­mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected positions
- regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de­energized. Dampers shall fully close on power loss.
ADDITIONAL FACTORY INSTALLED OPTIONS
ELECTRIC HEATING SECTION (IF EQUIPPED)
An electric heating section, with nickel chromium elements, shall be provided in a range of 9 thru 54 KW, offering two states of capacity all sizes. The heating section shall have a primary limit control(s) (automatic reset) to prevent the heating element system from operating at an excessive temperature. The Heat­ing Section assembly shall slide out of the unit for easy mainte­nance and service. Units with Electric Heating Sections shall be wired for a single point power supply with branch circuit fusing (where required).
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125 ºF outdoor temperature, exceeding maximum load criteria of AHRI Stan­dard 340/360. The compressor, with standard controls, shall be capable of operation down to 0 ºF outdoor temperature.
ELECTRICAL REQUIREMENTS - All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.
ST ANDARD LIMITED WARRANTIES - Compressor – 5 Years, Elect. Heat Elem. – 5 Years, Parts – 1 Year
FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall be made available by either/or):
DRY BULB AUTOMATIC ECONOMIZER - Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring-return damper actuator. The
ALTERNATE INDOOR BLOWER MOTOR – For applications with high restrictions, units are available with optional indoor blower motors that provide higher static output and/or higher airflow.
CONVENIENCE OUTLET (POWERED/NON-POWERED)– Unit can be provided with an optional 120VAC GFCI outlet with cover on the corner of the unit housing the compressors.
ELECTRIC HEAT - Electric Heaters range from 9 kW to 54 kW and are available in all the voltage options of the base unit.
PHASE MONITOR - Designed to prevent damage in out­of-phase condition.
COIL GUARD - Designed to prevent condenser coil damage.
BAS CONTROLS HARDWARE - Include supply air sensor, return air sensor, dirty filter indicator and air proving switch.
DIRTY FILTER SWITCH – This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high­pressure drop across the filters.
BREAKER – An HACR breaker can be factory installed on heat pumps or heat pumps with electric heat.
DISCONNECT SWITCH - A disconnect can be factory installed on a cooling only units sized for the largest electric heat available.
SMOKE DETECTOR – A smoke detector can be factory mounted and wired in the supply and/or return air compartments.
10 Johnson Controls Unitary Products
528195-YTG-L-1014
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
ROOF CURB - 14” and 8” high, full perimeter knockdown curb, with hinged design for quick assembly.
BAROMETRIC RELIEF DAMPER – (Unit mounted – Downflow, Duct Mounted – Horizontal) – Contains a rain hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through the unit during economizer operation.
ECONOMIZER (Downflow and Horizontal flow)
POWER EXHAUST – (Unit mount – Downflow, Duct mount – Horizontal flow)
DUAL ENTHALPY KIT - Provides a second input to economizer to monitor return air.
Johnson Controls Unitary Products 11
528195-YTG-L-1014

Physical Data

XP078-150 Physical Data

Component
Nominal Tonnage 6.5 7.5 8.5 10 12.5
AHRI COOLING PERFORMANCE
Gross Capacity @ AHRI A point (Mbh) 80000 92550 105600 122000 158300 AHRI net capacity (Mbh) 78000 90000 102000 117000 150000 EER 11.5 11.2 11.2 11.2 11.0 IEER 12.0 12.0 11.4 11.4 10.5 IPLV 12.4 12.4 12.4 12.4 11.9 Nominal CFM 2600 3000 3750 3750 4900 System power (KW) 6.78 8.18 9.27 10.45 13.64 Refrigerant type R-410A R-410A R-410A R-410A R-410A Refrigerant charge (lb-oz)
System 1 14-2 13-0 13-12 12-14 17-6 System 2 12-10 13-2 13-13 12-12 17-8
AHRI HEATING PERFORMANCE
47°F capacity rating (Mbh) 75.0 88.0 90.5 102.0 135.0 System power (KW) / COP 6.2 / 3.35 7.7 / 3.35 7.9 / 3.35 8.6 / 3.30 13.2 / 3.2 17°F capacity rating (Mbh) 43.0 51.0 53.0 58.0 90.0 System power (KW) / COP 5.7 / 2.20 6.4 / 2.25 6.9 / 2.25 7.8 / 2.20 13.5 / 2.05 HSPF (Btu/Watts-hr) -----
DIMENSIONS (inches)
Length 89 89 89 89 119-7/16 Width 5959595959 Height 50-3/4 50-3/4 50-3/4 50-3/4 50-3/4
OPERATING WT. (lbs.) 1080 1090 1137 1135 1403
COMPRESSORS
Type Scroll Scroll Scroll Scroll Scroll Quantity 2 2 2 2 2 Unit Capacity Steps (%) 50 / 100 50 / 100 50 / 100 50 / 100 50/100
CONDENSER COIL DATA
Face area (Sq. Ft.) 29.0 29.0 29.0 29.0 47.5 Rows 22222 Fins per inch 16 16 16 16 15 Tube diameter (in.) 3/8 3/8 3/8 3/8 3/8 Circuitry Type Split-face Split-face Split-face Split-face Split-face Refrigerant control TXV 29.0 29.0 TXV TXV
EVAPORATOR COIL DATA
Face area (Sq. Ft.) 13.2 13.2 13.2 13.2 13.2 Rows 44444 Fins per inch 15 15 15 15 15 Tube diameter 3/8 3/8 3/8 3/8 3/8 Circuitry Type Split-face Split-face Split-face Split-face Split-face Refrigerant control TXV TXV TXV TXV TXV
XP078 XP090 XP102 XP120 XP150
Models
12 Johnson Controls Unitary Products
XP078-150 Physical Data (Continued)
528195-YTG-L-1014
Component
XP078 XP090 XP102 XP120 XP150
Models
Nominal Tonnage 6.5 7.5 8.5 10 12.5
CONDENSER FAN DATA
Quantity of Fans 2 2 2 2 4 Fan diameter (Inch) 24 24 24 24 24 Type Prop Prop Prop Prop Prop Drive Type Direct Direct Direct Direct Direct Quantity of motors 2 2 2 2 4 Motor HP each 1/3 1/3 1/3 1/3 1/3 No. speeds 1 1 1 1 1 RPM 850 850 850 850 850 Nominal total CFM 6800 6800 6800 6800 14000
BELT DRIVE EVAP FAN DATA
Quantity 1 1 1 1 1 Fan Size (Inch) 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15 Type Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal Motor Sheave VL40 VL44 1VL40 1VM50 1VP50 1VP50 1VM50 1VM50 1VM50 1VP56 Blower Sheave AK84 AK71 AK69 AK69 AK89 AK74 AK84 AK74 AK74 BK77 Belt A54 A52 A52 A54 A56 A54 A56 A54 A54 BX56 Motor HP each 1-1/2 2 1-1/2 3 2 3 2 3 3 5 RPM 1725 1725 1725 1725 1725 1725 1725 1725 1725 1725 Frame size 56 56 56 56 56 56 56 56 56 184 T
FILTERS
Quantity - Size
1. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value) 3.
2. 2 In. Pleated, Optional, MERV 7.
3. 4 In. Pleated, Optional, MERV 13.
4 - (24 x 20 x 2)
4 - (24 x 20 x 2)34 - (24 x 20 x 4)34 - (24 x 20 x 4)34 - (24 x 20 x 2)34 - (24 x 20 x 4)
1,2
4 - (24 x 20 x 2)
1,2
4 - (24 x 20 x 2)
1,2
4 - (24 x 20 x 2)
1,2
4 - (24 x 20 x 2)
1,2
3

XP078-150 Unit Limitations

Size
(Tons)
078
(6.5)
090
(7.5)
102
(8.5)
120 (10)
150
(12.5)
Model Unit Vo ltag e
208/230-3-60 187 252 125
XP
460-3-60 432 504 125 575-3-60 540 630 125
208/230-3-60 187 252 125
XP
460-3-60 432 504 125 575-3-60 540 630 125
208/230-3-60 187 252 125
XP
460-3-60 432 504 125 575-3-60 540 630 125
208/230-3-60 187 252 125
XP
460-3-60 432 504 125 575-3-60 540 630 125
208/230-3-60 187 252 125
XP
460-3-60 432 504 125 575-3-60 540 630 125
Unit Limitations
Applied Voltage Outdoor DB Temp
Min Max Max (° F)
Johnson Controls Unitary Products 13
528195-YTG-L-1014

Capacity Performance

XP078-150 Cooling Capacities

XP078 (6.5 Ton)

Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
1625
1950
2275
2600
2925
3250
WB (°F)
77 107.3 4.8 47.0 38.9 30.7 - - - 103.2 5.5 45.6 37.7 29.7 - - ­72 99.2 4.7 57.9 49.8 41.7 33.5 - - 94.7 5.4 56.2 48.3 40.4 32.5 - ­67 91.1 4.7 68.8 60.7 52.6 44.5 36.4 - 86.3 5.4 66.8 58.9 51.0 43.1 35.2 ­62 81.6 4.6 81.6 70.5 61.8 53.7 45.5 37.4 78.4 5.3 78.4 70.8 61.1 53.2 45.3 37.4 77 112.8 4.8 53.0 43.7 34.4 - - - 107.7 5.5 51.3 42.1 32.9 - - ­72 104.3 4.8 65.2 55.9 46.6 37.3 - - 98.9 5.5 63.0 53.8 44.6 35.5 - ­67 95.7 4.7 77.4 68.1 58.8 49.5 40.2 - 90.1 5.4 74.7 65.6 56.4 47.2 38.0 ­62 85.8 4.7 85.8 78.4 69.1 59.8 50.5 41.2 81.8 5.4 81.8 76.8 67.6 58.4 49.2 40.0 57 83.3 4.6 83.3 81.9 72.6 63.3 54.0 44.7 80.0 5.4 80.0 79.0 69.8 60.6 51.4 42.3 77 118.3 4.9 58.9 48.5 38.0 - - - 112.3 5.5 56.9 46.5 36.0 - - ­72 109.4 4.8 72.5 62.0 51.5 41.1 - - 103.1 5.5 69.8 59.4 48.9 38.5 - ­67 100.4 4.8 86.0 75.5 65.1 54.6 44.1 - 93.9 5.5 82.7 72.2 61.8 51.3 40.9 ­62 90.0 4.7 90.0 86.3 76.5 66.0 55.6 45.1 85.2 5.4 85.2 82.7 74.0 63.6 53.1 42.7 57 87.4 4.7 87.4 86.7 80.3 69.8 59.4 48.9 83.4 5.4 83.4 82.9 76.5 66.0 55.6 45.1 77 123.8 4.9 64.9 53.3 41.6 - - - 116.8 5.6 62.6 50.9 39.2 - - ­72 114.4 4.9 79.7 68.1 56.5 44.8 - - 107.2 5.5 76.6 64.9 53.2 41.5 - ­67 105.1 4.8 94.5 82.9 71.3 59.7 48.0 - 97.6 5.5 90.6 78.9 67.2 55.5 43.7 ­62 94.2 4.8 94.2 94.2 83.8 72.2 60.6 48.9 88.7 5.4 88.7 88.7 80.5 68.8 57.1 45.3 57 91.5 4.7 91.5 91.5 88.0 76.4 64.7 53.1 86.7 5.4 86.7 86.7 83.2 71.4 59.7 48.0 72 117.9 4.9 85.1 72.4 59.7 47.0 - - 109.4 5.5 82.4 69.5 56.6 43.8 - ­67 108.2 4.8 102.9 88.1 75.4 62.6 49.9 - 99.6 5.5 96.1 84.4 71.5 58.7 45.8 ­62 97.1 4.8 97.1 97.1 90.5 77.8 65.1 52.4 90.5 5.4 90.5 90.5 85.7 72.9 60.0 47.1 57 94.2 4.7 94.2 94.2 92.5 79.8 67.1 54.3 88.5 5.4 88.5 88.5 86.7 73.8 61.0 48.1 72 121.3 4.9 90.6 76.7 62.9 49.1 - - 111.6 5.5 88.1 74.1 60.1 46.1 - ­67 111.3 4.9 111.3 93.3 79.5 65.6 51.8 - 101.6 5.5 101.6 89.9 75.9 61.9 47.9 ­62 99.9 4.8 99.9 99.9 97.3 83.5 69.6 55.8 92.3 5.4 92.3 92.3 91.0 77.0 62.9 48.9 57 97.0 4.8 97.0 97.0 97.0 83.2 69.4 55.6 90.2 5.4 90.2 90.2 90.2 76.2 62.2 48.2
77 99.2 6.2 44.1 36.5 28.8 - - - 92.8 7.0 39.9 33.2 25.5 - - ­72 90.3 6.1 54.5 46.8 39.1 31.4 - - 84.1 7.0 51.2 43.5 35.8 28.1 - ­67 81.5 6.1 64.8 57.1 49.4 41.7 34.0 - 75.4 7.0 62.6 53.9 46.2 38.5 30.8 ­62 75.1 6.1 75.1 71.1 60.4 52.7 45.0 37.3 69.4 6.9 69.4 67.0 55.6 47.9 40.2 32.5 77 102.7 6.2 49.6 40.5 31.4 - - - 95.7 7.0 46.0 37.0 28.0 - - ­72 93.5 6.2 60.8 51.7 42.7 33.6 - - 86.8 7.0 57.3 48.3 39.3 30.3 - ­67 84.4 6.1 72.1 63.0 53.9 44.9 35.8 - 77.8 7.0 68.7 59.7 50.7 41.7 32.7 ­62 77.8 6.1 77.8 75.1 66.0 57.0 47.9 38.8 71.6 6.9 71.6 70.0 61.0 52.0 43.0 34.0 57 76.7 6.1 76.7 76.1 67.0 57.9 48.9 39.8 71.9 6.9 71.9 70.8 61.8 52.8 43.8 34.8 77 106.2 6.2 55.0 44.5 34.1 - - - 98.7 7.0 52.1 40.8 30.5 - - ­72 96.8 6.2 67.2 56.7 46.3 35.8 - - 89.4 7.0 63.4 53.1 42.8 32.5 - ­67 87.3 6.1 79.4 68.9 58.5 48.1 37.6 - 80.2 7.0 74.8 65.5 55.2 44.9 34.6 ­62 80.4 6.1 80.4 79.1 71.6 61.2 50.7 40.3 73.8 6.9 73.8 73.0 66.4 56.1 45.8 35.5 57 79.3 6.1 79.3 79.0 72.7 62.2 51.8 41.3 74.1 6.9 74.1 73.5 67.3 57.0 46.7 36.4 77 109.8 6.2 60.4 48.6 36.7 - - - 101.6 7.0 58.2 44.6 33.0 - - ­72 100.0 6.2 73.5 61.7 49.9 38.1 - - 92.1 7.0 69.5 57.9 46.3 34.7 - ­67 90.2 6.1 86.7 74.9 63.1 51.2 39.4 - 82.6 7.0 80.8 71.3 59.7 48.1 36.5 ­62 83.1 6.1 83.1 83.1 77.2 65.4 53.6 41.8 76.0 6.9 76.0 76.0 71.8 60.2 48.6 37.0 57 82.0 6.1 82.0 82.0 78.4 66.5 54.7 42.9 76.3 6.9 76.3 76.3 72.8 61.2 49.6 38.0 72 100.9 6.1 79.6 66.6 53.6 40.6 - - 92.9 7.0 75.7 62.8 49.8 36.9 - ­67 91.1 6.1 89.3 80.7 67.7 54.7 41.7 - 83.3 6.9 82.4 76.3 64.2 51.3 38.3 ­62 83.9 6.1 83.9 83.9 80.9 67.9 54.9 41.9 76.6 6.9 76.6 76.6 74.6 61.6 48.7 35.7 57 82.7 6.1 82.7 82.7 80.9 67.9 54.9 41.9 77.0 6.9 77.0 77.0 75.2 62.3 49.3 36.3 72 101.9 6.1 85.7 71.4 57.2 43.0 - - 93.7 6.9 81.9 67.6 53.3 39.0 - ­67 91.9 6.1 91.9 86.5 72.3 58.1 43.9 - 84.0 6.9 84.0 81.4 68.7 54.4 40.1 ­62 84.7 6.0 84.7 84.7 84.7 70.5 56.2 42.0 77.3 6.9 77.3 77.3 77.3 63.0 48.7 34.4 57 83.5 6.0 83.5 83.5 83.5 69.3 55.1 40.8 77.7 6.9 77.7 77.7 77.7 63.3 49.0 34.7
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
14 Johnson Controls Unitary Products
528195-YTG-L-1014
XP078 (6.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
WB (°F)
77 86.5 7.8 35.6 29.9 22.2 - - - 80.1 8.7 30.4 26.7 19.0 - - ­72 77.9 7.8 48.0 40.3 32.6 24.9 - - 71.7 8.6 44.8 37.1 29.4 21.7 - ­67 69.4 7.8 60.5 50.7 43.0 35.3 27.6 - 63.3 8.6 58.3 47.5 39.8 32.1 24.4 ­62 63.7 7.8 63.7 62.9 50.7 43.0 35.3 27.6 58.0 8.6 58.0 58.0 45.8 38.1 30.4 22.7 77 88.8 7.8 42.4 33.5 24.6 - - - 81.8 8.7 38.8 30.0 21.1 - - ­72 80.0 7.8 53.8 44.9 36.0 27.1 - - 73.2 8.6 50.4 41.5 32.6 23.8 - ­67 71.2 7.8 65.3 56.4 47.4 38.5 29.6 - 64.6 8.6 61.9 53.0 44.2 35.3 26.5 ­62 65.4 7.8 65.4 64.9 55.9 47.0 38.1 29.2 59.2 8.6 59.2 59.2 50.9 42.0 33.2 24.3 57 67.1 7.7 67.1 65.5 56.5 47.6 38.7 29.8 62.4 8.5 62.4 60.2 51.3 42.5 33.6 24.7 77 91.1 7.8 49.3 37.0 26.9 - - - 83.5 8.6 47.3 33.3 23.2 - - ­72 82.1 7.8 59.7 49.5 39.4 29.2 - - 74.7 8.6 55.9 45.9 35.9 25.9 - ­67 73.1 7.8 70.1 62.0 51.9 41.7 31.6 - 65.9 8.6 65.5 58.6 48.6 38.6 28.6 ­62 67.1 7.8 67.1 66.8 61.2 51.0 40.9 30.7 60.4 8.6 60.4 60.4 56.0 46.0 36.0 26.0 57 68.9 7.7 68.9 68.1 61.9 51.7 41.5 31.4 63.7 8.5 63.7 62.6 56.5 46.4 36.4 26.4 77 93.4 7.8 56.1 40.5 29.2 - - - 85.2 8.6 55.7 36.5 25.4 - - ­72 84.2 7.8 65.5 54.1 42.8 31.4 - - 76.2 8.6 61.5 50.3 39.2 28.0 - ­67 74.9 7.8 74.9 67.7 56.3 45.0 33.6 - 67.3 8.6 67.3 64.1 53.0 41.8 30.7 ­62 68.8 7.8 68.8 68.8 66.5 55.1 43.7 32.3 61.6 8.6 61.6 61.6 61.1 49.9 38.8 27.6 57 70.6 7.7 70.6 70.6 67.2 55.8 44.4 33.0 65.0 8.5 65.0 65.0 61.6 50.4 39.3 28.1 72 84.9 7.8 71.9 59.0 46.1 33.2 - - 76.8 8.6 68.0 55.2 42.4 29.5 - ­67 75.6 7.8 75.6 72.0 60.7 47.8 35.0 - 67.8 8.6 67.8 67.6 57.3 44.4 31.6 ­62 69.4 7.8 69.4 69.4 68.2 55.3 42.4 29.5 62.1 8.6 62.1 62.1 61.8 49.0 36.2 23.3 57 71.2 7.7 71.2 71.2 69.5 56.6 43.7 30.8 65.5 8.5 65.5 65.5 63.8 51.0 38.1 25.3 72 85.6 7.8 78.2 63.8 49.4 35.0 - - 77.4 8.6 74.5 60.0 45.5 31.0 - ­67 76.2 7.8 76.2 76.2 65.1 50.7 36.3 - 68.3 8.6 68.3 68.3 61.5 47.0 32.5 ­62 69.9 7.8 69.9 69.9 69.9 55.5 41.1 26.7 62.6 8.6 62.6 62.6 62.6 48.1 33.6 19.1 57 71.8 7.7 71.8 71.8 71.8 57.4 43.0 28.6 66.0 8.5 66.0 66.0 66.0 51.5 37.0 22.5
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 15
528195-YTG-L-1014

XP090 (7.5 Ton)

Air on
Evaporator Coil
Capacity
CFM
1875
2250
2625
3000
3375
3750
1875
2250
2625
3000
3375
3750
WB (°F)
(MBh)
77 116.6 5.8 48.6 40.0 31.5 - - - 110.0 6.5 45.8 37.4 29.0 - - ­72 107.8 5.7 62.9 54.3 45.7 37.2 - - 101.4 6.5 59.8 51.4 43.0 34.6 - ­67 99.0 5.6 77.2 68.6 60.0 51.5 42.9 - 92.8 6.4 73.8 65.4 57.0 48.6 40.2 ­62 93.7 5.5 93.7 85.2 74.6 66.1 57.5 48.9 86.4 6.3 86.4 82.1 70.6 62.2 53.8 45.4 77 120.7 5.8 53.8 44.0 34.1 - - - 113.5 6.5 50.7 41.1 31.5 - - ­72 111.7 5.7 69.3 59.5 49.6 39.8 - - 104.7 6.5 65.9 56.3 46.7 37.1 - ­67 102.6 5.6 84.8 75.0 65.1 55.3 45.5 - 95.8 6.4 81.2 71.5 61.9 52.3 42.7 ­62 97.0 5.6 97.0 91.3 81.0 71.2 61.4 51.5 89.2 6.3 89.2 86.3 76.7 67.1 57.5 47.9 57 93.4 5.6 93.4 93.4 85.1 75.3 65.4 55.6 87.2 6.3 87.2 87.2 80.0 70.3 60.7 51.1 77 124.9 5.8 59.0 47.9 36.8 - - - 117.1 6.6 55.6 44.8 34.0 - - ­72 115.5 5.7 75.7 64.6 53.5 42.5 - - 108.0 6.5 72.1 61.2 50.4 39.6 - ­67 106.1 5.6 92.4 81.3 70.2 59.2 48.1 - 98.8 6.4 88.5 77.7 66.8 56.0 45.2 ­62 100.3 5.6 100.3 97.5 87.3 76.3 65.2 54.1 92.0 6.4 92.0 90.5 82.8 72.0 61.1 50.3 57 96.6 5.6 96.6 96.6 91.8 80.7 69.6 58.6 90.0 6.4 90.0 90.0 86.3 75.5 64.6 53.8 77 129.1 5.8 64.1 51.8 39.5 - - - 120.7 6.6 60.5 48.5 36.5 - - ­72 119.4 5.7 82.1 69.7 57.4 45.1 - - 111.2 6.5 78.2 66.1 54.1 42.1 - ­67 109.6 5.6 100.0 87.7 75.4 63.0 50.7 - 101.8 6.4 95.8 83.8 71.7 59.7 47.7 ­62 103.7 5.6 103.7 103.7 93.7 81.4 69.1 56.7 94.8 6.4 94.8 94.8 88.8 76.8 64.8 52.7 57 99.8 5.6 99.8 99.8 98.4 86.1 73.8 61.5 92.7 6.4 92.7 92.7 92.6 80.6 68.5 56.5 72 120.8 5.7 87.0 73.9 60.7 47.6 - - 112.2 6.5 83.4 70.4 57.4 44.5 - ­67 111.0 5.7 106.1 92.8 79.6 66.5 53.3 - 102.7 6.5 99.7 89.1 76.2 63.2 50.2 ­62 104.9 5.6 104.9 104.9 99.9 86.8 73.6 60.5 95.6 6.4 95.6 95.6 92.6 79.6 66.7 53.7 57 101.1 5.6 101.1 101.1 100.4 87.2 74.1 60.9 93.5 6.4 93.5 93.5 93.4 80.5 67.5 54.6 72 122.3 5.7 91.9 78.0 64.0 50.0 - - 113.1 6.5 88.6 74.7 60.8 46.9 - ­67 112.3 5.7 112.3 97.9 83.9 69.9 55.9 - 103.5 6.5 103.5 94.5 80.6 66.7 52.8 ­62 106.2 5.6 106.2 106.2 106.2 92.2 78.2 64.2 96.4 6.4 96.4 96.4 96.4 82.5 68.6 54.7 57 102.3 5.6 102.3 102.3 102.3 88.3 74.3 60.3 94.3 6.4 94.3 94.3 94.3 80.4 66.5 52.6
77 103.4 7.3 43.0 34.8 26.5 - - - 95.4 8.2 37.5 31.2 23.2 - - ­72 95.0 7.2 56.8 48.5 40.3 32.0 - - 87.7 8.1 53.1 45.1 37.0 29.0 - ­67 86.6 7.2 70.5 62.3 54.0 45.8 37.5 - 79.9 8.1 68.7 58.9 50.9 42.9 34.8 ­62 79.0 7.1 79.0 79.0 66.6 58.4 50.1 41.9 74.0 8.0 74.0 74.0 62.0 54.0 45.9 37.9 77 106.3 7.3 47.7 38.2 28.8 - - - 97.6 8.2 43.7 34.5 25.3 - - ­72 97.7 7.3 62.6 53.2 43.8 34.4 - - 89.7 8.2 58.8 49.6 40.4 31.2 - ­67 89.0 7.2 77.6 68.1 58.7 49.3 39.9 - 81.8 8.1 73.9 64.7 55.5 46.3 37.1 ­62 81.3 7.1 81.3 81.3 72.4 63.0 53.6 44.2 75.7 8.0 75.7 75.7 67.6 58.4 49.2 40.0 57 81.1 7.1 81.1 81.1 74.8 65.4 56.0 46.6 75.4 8.0 75.4 75.4 69.1 59.9 50.7 41.5 77 109.3 7.4 52.3 41.7 31.1 - - - 99.9 8.3 49.8 37.7 27.4 - - ­72 100.4 7.3 68.4 57.9 47.3 36.7 - - 91.8 8.2 64.5 54.1 43.8 33.4 - ­67 91.5 7.2 84.6 74.0 63.4 52.8 42.2 - 83.7 8.1 79.2 70.5 60.2 49.8 39.4 ­62 83.6 7.1 83.6 83.6 78.2 67.6 57.0 46.5 77.5 8.1 77.5 77.5 73.3 62.9 52.5 42.2 57 83.4 7.1 83.4 83.4 80.8 70.2 59.6 49.0 77.1 8.1 77.1 77.1 74.8 64.5 54.1 43.7 77 112.2 7.4 56.9 45.2 33.4 - - - 102.1 8.3 56.0 41.0 29.5 - - ­72 103.1 7.3 74.3 62.5 50.8 39.0 - - 93.8 8.2 70.2 58.7 47.1 35.6 - ­67 94.0 7.2 91.6 79.9 68.1 56.3 44.6 - 85.6 8.1 84.4 76.3 64.8 53.3 41.7 ­62 85.8 7.2 85.8 85.8 84.0 72.2 60.5 48.7 79.2 8.1 79.2 79.2 78.9 67.4 55.8 44.3 57 85.6 7.2 85.6 85.6 86.8 75.0 63.3 51.5 78.8 8.1 78.8 78.8 80.6 69.1 57.5 46.0 72 103.5 7.3 79.7 67.0 54.2 41.4 - - 93.9 8.2 75.2 62.7 50.2 37.7 - ­67 94.4 7.3 93.2 85.5 72.7 59.9 47.2 - 85.6 8.2 85.1 80.1 69.0 56.5 44.1 ­62 86.2 7.2 86.2 86.2 85.3 72.5 59.7 47.0 79.3 8.1 79.3 79.3 79.1 66.7 54.2 41.7 57 86.0 7.2 86.0 86.0 86.5 73.8 61.0 48.2 78.9 8.1 78.9 78.9 79.8 67.3 54.8 42.3 72 104.0 7.3 85.2 71.4 57.6 43.8 - - 94.0 8.3 80.1 66.7 53.3 39.8 - ­67 94.8 7.3 94.8 91.1 77.3 63.5 49.7 - 85.7 8.2 85.7 83.9 73.2 59.8 46.4 ­62 86.5 7.2 86.5 86.5 86.5 72.8 59.0 45.2 79.4 8.1 79.4 79.4 79.4 65.9 52.5 39.1 57 86.3 7.2 86.3 86.3 86.3 72.5 58.7 45.0 79.0 8.1 79.0 79.0 79.0 65.6 52.1 38.7
Total
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
16 Johnson Controls Unitary Products
528195-YTG-L-1014
XP090 (7.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
WB (°F)
77 87.4 9.1 32.0 27.6 19.8 - - - 79.5 10.1 25.8 23.8 16.5 - - ­72 80.3 9.1 49.4 41.6 33.8 26.0 - - 73.0 10.0 45.8 38.2 30.6 23.0 - ­67 73.3 9.0 66.9 55.6 47.8 40.0 32.2 - 66.6 9.9 65.4 52.3 44.7 37.1 29.5 ­62 68.9 8.9 68.9 68.9 57.4 49.6 41.7 33.9 63.9 9.9 63.9 63.9 52.7 45.1 37.5 29.9 77 89.0 9.2 39.7 30.7 21.7 - - - 80.3 10.1 35.7 26.9 18.1 - - ­72 81.7 9.1 55.0 46.0 37.0 28.1 - - 73.8 10.0 51.2 42.4 33.7 24.9 - ­67 74.5 9.0 70.3 61.3 52.4 43.4 34.4 - 67.3 9.9 66.7 57.9 49.2 40.4 31.7 ­62 70.1 9.0 70.1 70.1 62.9 53.9 44.9 35.9 64.5 9.9 64.5 64.5 58.1 49.3 40.6 31.8 57 69.6 9.0 69.6 69.6 63.3 54.4 45.4 36.4 63.9 9.9 63.9 63.9 57.6 48.8 40.1 31.3 77 90.5 9.2 47.4 33.7 23.6 - - - 81.1 10.1 45.5 30.1 19.8 - - ­72 83.2 9.1 60.6 50.4 40.3 30.1 - - 74.5 10.0 56.6 46.7 36.8 26.8 - ­67 75.8 9.0 73.7 67.1 56.9 46.8 36.6 - 68.0 9.9 68.0 63.6 53.7 43.8 33.8 ­62 71.3 9.0 71.3 71.3 68.3 58.2 48.1 37.9 65.2 9.9 65.2 65.2 63.4 53.5 43.6 33.6 57 70.8 9.0 70.8 70.8 68.9 58.7 48.6 38.4 64.6 9.9 64.6 64.6 62.9 53.0 43.0 33.1 77 92.0 9.2 55.1 36.8 25.5 - - - 81.9 10.1 55.4 33.2 21.5 - - ­72 84.6 9.1 66.1 54.8 43.5 32.2 - - 75.3 10.1 62.0 50.9 39.9 28.8 - ­67 77.1 9.1 77.1 72.8 61.5 50.2 38.9 - 68.7 10.0 68.7 68.7 58.2 47.1 36.0 ­62 72.5 9.0 72.5 72.5 73.8 62.5 51.2 39.9 65.9 9.9 65.9 65.9 65.9 57.6 46.6 35.5 57 72.0 9.0 72.0 72.0 74.4 63.1 51.8 40.5 65.2 9.9 65.2 65.2 65.2 57.1 46.0 34.9 72 84.3 9.2 70.6 58.4 46.2 34.0 - - 74.8 10.1 66.0 54.1 42.2 30.3 - ­67 76.9 9.1 76.9 74.8 65.3 53.1 41.0 - 68.2 10.0 68.2 68.2 61.6 49.8 37.9 ­62 72.4 9.0 72.4 72.4 73.0 60.8 48.6 36.4 65.4 10.0 65.4 65.4 65.4 55.0 43.1 31.2 57 71.8 9.0 71.8 71.8 73.0 60.8 48.7 36.5 64.8 10.0 64.8 64.8 64.8 54.4 42.5 30.6 72 84.1 9.2 75.1 62.0 48.9 35.9 - - 74.2 10.1 70.0 57.3 44.6 31.9 - ­67 76.7 9.1 76.7 76.7 69.2 56.1 43.0 - 67.7 10.0 67.7 67.7 65.1 52.4 39.7 ­62 72.2 9.1 72.2 72.2 72.2 59.1 46.0 33.0 65.0 10.0 65.0 65.0 65.0 52.3 39.6 26.9 57 71.7 9.0 71.7 71.7 71.7 58.6 45.5 32.5 64.3 10.0 64.3 64.3 64.3 51.6 38.9 26.2
Total
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
Johnson Controls Unitary Products 17
528195-YTG-L-1014

XP102 (8.5 Ton)

Air on
Evaporator Coil
Capacity
CFM
2125
2550
2975
3400
3825
4250
2125
2550
2975
3400
3825
4250
WB (°F)
(MBh)
77 120.9 6.2 58.3 45.7 36.0 - - - 118.6 7.0 52.6 42.8 32.9 - - ­72 113.7 6.1 69.9 60.2 50.5 40.8 - - 109.4 6.9 67.3 57.4 47.6 37.7 - ­67 106.4 6.0 81.4 74.6 65.0 55.3 45.6 - 100.2 6.9 82.0 72.1 62.3 52.4 42.5 ­62 96.7 5.9 96.7 94.3 79.3 69.6 59.9 50.2 92.3 6.8 92.3 91.1 75.4 65.6 55.7 45.9 77 126.2 6.2 62.1 51.0 39.8 - - - 123.3 7.0 59.3 47.9 36.6 - - ­72 118.6 6.1 78.1 67.0 55.8 44.7 - - 113.7 7.0 75.6 64.2 52.9 41.5 - ­67 110.9 6.0 94.1 83.0 71.8 60.7 49.5 - 104.2 6.9 91.9 80.5 69.2 57.8 46.4 ­62 100.9 6.0 100.9 99.3 87.7 76.5 65.4 54.3 96.0 6.8 96.0 95.2 83.8 72.4 61.0 49.7 57 100.3 5.9 100.3 100.5 89.7 78.6 67.5 56.3 95.7 6.8 95.7 95.7 84.5 73.1 61.7 50.3 77 131.4 6.2 65.9 56.2 43.6 - - - 128.0 7.0 66.0 53.1 40.2 - - ­72 123.5 6.1 86.3 73.7 61.2 48.6 - - 118.1 7.0 83.9 71.0 58.1 45.2 - ­67 115.5 6.0 106.8 91.3 78.7 66.1 53.5 - 108.1 6.9 101.8 89.0 76.1 63.2 50.3 ­62 105.1 6.0 105.1 104.3 96.1 83.5 70.9 58.3 99.6 6.9 99.6 99.2 92.2 79.3 66.4 53.5 57 104.4 6.0 104.4 104.6 98.3 85.8 73.2 60.6 99.3 6.9 99.3 99.3 92.9 80.0 67.1 54.2 77 136.7 6.2 69.7 61.5 47.5 - - - 132.7 7.1 72.7 58.3 43.8 - - ­72 128.4 6.1 94.6 80.5 66.5 52.5 - - 122.4 7.0 92.2 77.8 63.4 49.0 - ­67 120.1 6.0 119.5 99.6 85.6 71.5 57.5 - 112.1 7.0 111.8 97.4 83.0 68.5 54.1 ­62 109.3 6.0 109.3 109.3 104.5 90.4 76.4 62.4 103.3 6.9 103.3 103.3 100.5 86.1 71.7 57.3 57 108.6 6.0 108.6 108.6 106.9 92.9 78.9 64.9 103.0 6.9 103.0 103.0 101.3 86.9 72.5 58.1 72 132.2 6.2 101.6 86.1 70.7 55.3 - - 125.5 7.1 99.2 83.4 67.6 51.8 - ­67 123.6 6.1 123.3 106.7 91.0 75.5 60.1 - 115.0 7.0 114.8 104.3 88.4 72.6 56.8 ­62 112.5 6.0 112.5 112.5 110.1 94.7 79.2 63.8 105.9 6.9 105.9 105.9 104.5 88.7 72.9 57.1 57 111.8 6.0 111.8 111.8 111.0 95.5 80.1 64.7 105.6 6.9 105.6 105.6 104.8 88.9 73.1 57.3 72 136.0 6.3 108.6 91.8 74.9 58.1 - - 128.6 7.1 106.2 89.0 71.8 54.5 - ­67 127.2 6.2 127.2 113.8 96.4 79.5 62.7 - 117.8 7.0 117.8 111.1 93.9 76.7 59.4 ­62 115.7 6.1 115.7 115.7 115.7 98.9 82.1 65.2 108.6 7.0 108.6 108.6 108.6 91.3 74.1 56.8 57 115.0 6.1 115.0 115.0 115.0 98.2 81.4 64.5 108.2 7.0 108.2 108.2 108.2 91.0 73.7 56.5
77 116.2 7.8 46.9 39.8 29.8 - - - 107.5 8.9 44.1 37.9 28.3 - - ­72 105.1 7.8 64.7 54.7 44.7 34.7 - - 97.2 8.8 62.6 52.5 42.4 32.3 - ­67 94.0 7.8 82.5 69.6 59.6 49.5 39.5 - 86.8 8.8 81.1 67.1 56.5 46.4 36.3 ­62 87.9 7.7 87.9 87.9 71.6 61.6 51.5 41.5 80.7 8.7 80.7 80.7 68.6 58.5 48.4 38.3 77 120.4 7.8 56.5 44.9 33.3 - - - 111.4 8.9 56.2 43.5 31.8 - - ­72 108.9 7.8 73.1 61.5 49.9 38.3 - - 100.6 8.9 71.1 59.4 47.6 35.9 - ­67 97.4 7.8 89.7 78.1 66.5 54.9 43.3 - 89.9 8.8 86.0 75.2 63.5 51.7 40.0 ­62 91.1 7.7 91.1 91.1 79.9 68.3 56.7 45.1 83.5 8.7 83.5 83.5 77.0 65.3 53.5 41.8 57 91.1 7.7 91.1 90.8 79.2 67.6 56.0 44.4 85.1 8.8 85.1 85.0 73.3 61.6 49.8 38.1 77 124.5 7.9 66.1 50.0 36.8 - - - 115.2 9.0 68.4 49.2 35.3 - - ­72 112.6 7.9 81.5 68.3 55.1 41.9 - - 104.0 8.9 79.7 66.3 52.9 39.4 - ­67 100.7 7.8 96.9 86.6 73.4 60.2 47.0 - 92.9 8.9 91.0 83.4 70.4 57.0 43.6 ­62 94.2 7.7 94.2 94.2 88.2 75.0 61.8 48.6 86.4 8.8 86.4 86.4 85.5 72.1 58.7 45.2 57 94.2 7.7 94.2 94.1 87.5 74.3 61.0 47.8 88.0 8.8 88.0 87.9 81.4 67.9 54.5 41.1 77 128.7 7.9 75.7 55.0 40.2 - - - 119.0 9.0 80.5 54.8 38.8 - - ­72 116.4 7.9 89.9 75.1 60.3 45.5 - - 107.5 9.0 88.3 73.2 58.1 43.0 - ­67 104.1 7.9 104.1 95.2 80.4 65.6 50.8 - 96.0 8.9 96.0 91.5 77.4 62.3 47.2 ­62 97.4 7.8 97.4 97.4 96.6 81.8 67.0 52.2 89.2 8.8 89.2 89.2 93.9 78.9 63.8 48.7 57 97.4 7.8 97.4 97.4 95.7 80.9 66.1 51.3 90.9 8.8 90.9 90.9 89.4 74.3 59.2 44.1 72 118.8 7.9 96.9 80.7 64.4 48.2 - - 109.5 9.0 95.4 78.8 62.2 45.6 - ­67 106.3 7.9 106.3 101.8 85.9 69.7 53.4 - 97.8 8.9 97.8 95.6 82.9 66.3 49.7 ­62 99.4 7.8 99.4 99.4 99.0 82.8 66.5 50.3 90.9 8.8 90.9 90.9 93.3 76.7 60.1 43.5 57 99.4 7.8 99.4 99.4 98.6 82.3 66.1 49.9 92.6 8.8 92.6 92.6 91.9 75.3 58.7 42.1 72 121.3 7.9 103.9 86.2 68.6 50.9 - - 111.6 9.0 102.5 84.4 66.3 48.2 - ­67 108.4 7.9 108.4 108.4 91.4 73.8 56.1 - 99.7 8.9 99.7 99.7 88.4 70.3 52.2 ­62 101.4 7.8 101.4 101.4 101.4 83.8 66.1 48.4 92.6 8.9 92.6 92.6 92.6 74.6 56.5 38.4 57 101.4 7.8 101.4 101.4 101.4 83.8 66.1 48.5 94.4 8.9 94.4 94.4 94.4 76.3 58.2 40.1
Total
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
Total Input
(kW)
Sensible Capacity (MBh)
2
18 Johnson Controls Unitary Products
Loading...