YORK Sunline MagnaDRY™ units are convertible single
package high efficiency rooftops. All models have independent
dual refrigerant circuits for efficient part load operation.
Although the units are primarily designed for curb mounting on
a roof, they can also be slab-mounted at ground level or set on
steel beams above a finished roof.
All units include:
• Powder Paint finish that meets ASTM-B-117 1000 hour
salt spray standards
• Two-stage cooling provided by dual independent
refrigeration circuits with expansion valves, filter-driers,
high and low pressure/loss of charge switches and
freezestats
• Scroll compressors
• Two-stage heating provided by dual independent heat
exchangers with aluminized steel tubes, redundant gas
valves, spark ignition with induced draft logic
• Permanently lubricated motors
• Bottom or side air discharge configuration capability (field
convertible)
• Belt Drive Blower Motor with high static drive option
• Constant supply air volume (CV) with optional variable air
volume (VAV)
• Manufactured under the quality standards of ISO9001
• Simplicity® Control Board
• Zero-25% fixed air damper with hood
• Copper tube/aluminum fin coils
• Hinged filter access and toolless latched doors
• Rigging holes in base rails for lifting
• Single point power connection
• Complete factory package - tested, charged and wired
• CSA agency approvals on all units
WARRANTY
• One-year parts warranty
• A Five-year parts warranty on the compressors and
electric heat elements
• Ten-year parts warranty on the gas-fired heat exchangers
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
A=Std.Drive
B = Std. Drive/Single Input Econo.
C = Std. Drive/Single Input Econo./Power Exhaust
(Downflow Only)
D = Std. Drive/Motorized Damper
N = Hi Static Drive
P = Hi Static Drive/Single Input Econo.
Q = Hi Static Drive/Single Input Econo./Power Exhaust
All models are available with a wide variety of factory-mounted
options such as stainless steel heat exchangers, phase
monitor, dirty filter switch, and coil guard to make them suitable
for almost every application.
All units are self-contained and assembled on full perimeter
base rails with holes in the four corners for overhead rigging.
Every unit is completely piped, wired, charged and tested at the
factory to simplify the field installation and to provide years of
dependable operation.
All models (including those with an economizer) are suitable for
either bottom or horizontal duct connections. Models with
factory installed power exhaust are suitable for bottom
duct connections only. For bottom duct, you remove the
sheet metal panels from the supply and return air openings
through the base of the unit. For horizontal duct, you replace
the supply and return air panels on the rear of the unit with a
side duct flange accessory.
All models are available with these “factory mounted” outdoor
air damper options:
• Single enthalpy econom i z er
• Single enthalpy economizer with power exhaust
• Motorized outdoor air damper
A fixed outdoor air intake assembly will be shipped in the return
air compartment of all units ordered without an economizer or
motorized outdoor air damper option. The assembly includes a
rain hood with a damper that can be set for 10, 15 or 25%
outdoor air. With bottom duct connections, the intake damper
assembly should be mounted over the opening in the return air
panel. With horizontal ductwork, it should be mounted on the
return air duct.
All supply air blowers are equipped with a belt drive that can be
adjusted to meet the exact requirements of the job. A high static
drive option is available for applications with a higher CFM and/
or static pressure requirement. A variable air volume (VAV)
option using a variable frequency drive is available for
applications requiring a constant supply duct pressure. A
differential pressure transducer is used to monitor supply duct
static pressure and return a speed reference signal to the VFD
to control the output of the indoor blower motor.
All compressors include scroll compressors and internal
pressure relief. Every refrigerant circuit includes an expansion
valve, a liquid line filter-drier, a discharge line high pressure
switch and a suction line with a freezestat and low pressure/
loss of charge switch to protect all system components. A hot
gas bypass option, consisting of an adjustable compressor
discharge bypass valve, is available for low cooling load
applications.
• Simplicity® Controls - Simplicity® control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
• Low Ambient - An integrated low-ambient control allows
all units to operate in the cooling mode down to 0°F
outdoor ambient without additional assistance. Optionally,
the control board can be programmed to lockout the
compressors when the outdoor air temperature is low or
when free cooling is available.
• Anti-Short Cycle Protection - To aid compressor life, an
anti-short cycle delay is incorporated into the standard
controls. Compressor reliability is further ensured by
programmable minimum run times. For testing, the anti
short cycle delay can be temporarily overridden with the
push of a button.
• Lead-Lag - An integrated Lead-Lag option allows equal
run time hours on all compressors, thereby extending the
life of all compressors. This option is selectable on the unit
control board.
• Fan Delays - Fan on and fan off delays are fully
programmable. Furthermore, the heating and cooling fan
delay times are independent of one another. All units are
programmed with default values based upon their
configuration of cooling and heat.
• Safety Monitoring - The control board monitors the high
and low-pressure switches, the freezestats, the gas valve,
if applicable, and the temperature limit switch on gas and
electric heat units. The unit control board will alarm on
ignition failures, compressor lockouts and repeated limit
switch trips.
• Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a “three
times, you’re out” philosophy. The high and low-pressure
switches and the freezestats must trip three times within
two hours before the unit control board will lock out the
associated compressor.
• On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and flash
an alarm code on the control board LED. Each high and
low-pressure switch alarm as well as each freezestat
alarm has its own flash code. The control board saves the
five most recent alarms in memory, and these alarms can
be reviewed at any time. Alarms and programmed values
are retained through the loss of power.
All units have long lasting powder paint cabinets with 1000 hour
salt spray test approval under ASTM-B117 procedures.
All models are CSA approved.
• Warranty - All models include a one-year limited parts
warranty on the complete unit. Compressors and electric
heater elements carry a five-year warranty. Gas heat
exchangers carry a 10-year parts warranty.
• Gas Heat Operation - All gas heat units are built with two
heating sections for two equal stages of capacity control.
Each section includes a durable heat exchanger with
aluminized steel or optional stainless steel tubes, a
redundant gas valve, spark ignition, power venting, an
ignition module for 100% shut-off and all of the safety
controls required to meet the latest ANSI standards.
The gas supply piping can be routed into the heating
compartment through a hole in the base pan of the unit or
through a knockout in the piping panel on the front of the
unit.
4Unitary Products Group
Page 5
262292-YTG-B-0107
FIGURE 1: UNIT CUTAWAY
• Electric Heat Operation - All electric heat models
(factory installed only) are wired for a single power source
and include a bank of nickel chromium elements mounted
at the discharge of the supply air blower to provide a high
velocity and uniform distribution of air across the heating
elements. Every element is fully protected against
excessive current and temperature by fuses and two
thermal limit switches.
• The power supply wiring can be routed into the control
box through a threaded pipe connection in the base pan of
the unit or through a knockout in the wiring panel on the
front of the unit.
• BAS Controls - York’s Magnum series units offer factory
mounted BAS controls such as Novar, Honeywell,
Johnson, and CPC.
REHEAT MODE SEQUENCE OF OPERATION
The reheat control board allows the user to select two different
modes of operation via a jumper connection on the board. (See
Figure 2.) Each mode is described below. Refer to Figures 2 - 4
when reading this section.
LOCATION OF VFD (Optional)
LOCATION OF VFD BYPASS (Optional)
“NORMAL” MODE
When the reheat control board (RCB) detects a need for
dehumidification (24VAC) at "HUM" via the field supplied
dehumidistat connected to RHTB-1 and RHTB-2 and there is
not a call for cooling, it energizes the hot gas relay (HGR),
which energizes the 3-way valve (SOL 3), the condenser coil
valve (SOL 2), and de-energizes the reheat coil bleed valve
(SOL 1). The Y1 signal is passed to the unit control board
(UCB), which engages circuit # 1, resulting in circuit #1 reheat
mode operation.
When the room thermostat calls for first stage cooling, with or
without a call for dehumidification, the RCB senses a signal
through "Y1", de-energizing the HGR, which de-energizes SOL
3 and SOL 2, and energizes SOL 1, engaging circuit # 1,
resulting in circuit #1 cooling mode operation.
When the room thermostat calls for second stage cooling, the
RCB senses a signal through "Y1" & "Y2" and engages circuit
#1 and circuit #2 in the cooling mode.
Indoor blower operation is initiated upon a call for first stage
cooling, second stage cooling or dehumidification.
Unitary Products Group5
Page 6
262292-YTG-B-0107
Anytime there is a call for 2 stages of cooling, the unit will not
operate in the reheat mode, even if there is a call for
dehumidification at "HUM".
The unit will not operate in the reheat mode if there is any call
for heating.
On units with economizers, the unit will not operate in the
reheat mode if there is a call for cooling and the economizer is
operating as first stage of cooling.
All safety devices function as previously described.
"ALTERNATE” MODE
When the RCB detects a need for dehumidification (24VAC) at
"HUM" via the field supplied dehumidistat connected to RHTB-1
and RHTB-2, and there is not a call for cooling, it energizes the
HGR, which energizes the SOL 3, SOL 2, and de-energizes
SOL 1. The unit then operates with circuit #1 in reheat mode
and circuit #2 in cooling mode.
When the room thermostat calls for first stage cooling while
there is still a call for dehumidification, no operational change is
made. The call for cooling is ignored and the unit continues to
operate with circuit #1 in reheat mode and circuit #2 in cooling
mode.
When the room thermostat calls for second stage cooling, the
RCB senses a signal through "Y1" & "Y2" and de-energizes the
HGR, which de-energizes SOL 3 and SOL 2, and energizes
SOL 1. Both circuits operate in the cooling mode.
Indoor blower operation is initiated upon a call for first stage
cooling, second stage cooling or dehumidification.
Anytime there is a call for 2 stages of cooling, the unit will not
operate in the reheat mode, even if there is still a call for
dehumidification at "HUM".
The unit will not operate in the reheat mode if there is any call
for heating.
All safety devices function as previously described.
R
Y1
Y2
G
W1
W2
OCC
C
COM
P4
K1
K2
K4
K3
`
P6
P5
P3
HGRR
HGR
MODE
SELECTION
JUMPER
HUM
DEHUMIDISTAT
HARNESS
CONNECTION
FIGURE 2: REHEAT CONTROL BOARD
6Unitary Products Group
Page 7
262292-YTG-B-0107
FIGURE 3: REHEAT CONTROLS - PART 1
UCB
UNIT CONTROL
BOARD
RHB
REHEAT CONTROL
BOARD
TERMINAL
RHTB
REHEAT
BLOCK
HUM
HUMIDIFY
TERMINAL
RHR
REHEAT
RELAY
REHEAT
SOLENOID
1
REHEAT
SOLENOID
UCB
UNIT CONTROL
BOARD
RHB
REHEAT
SOLENOID
2
3
REHEAT
CONTROL
BOARD
FIGURE 4: REHEAT CONTROLS - PART 2
Unitary Products Group7
Page 8
262292-YTG-B-0107
FACTORY-INSTALLED OPTIONS
• SINGLE INPUT ELECTRONIC ENTHALPY
ECONOMIZERS - Includes a slide-in / plug-in damper
assembly with fully modulating spring-return motor
actuator capable of introducing up to 100% outdoor air
with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
• POWER EXHAUST - Our single economizer options are
available with power exhaust. Whenever the outdoor air
intake dampers are opened for free cooling, the exhaust
fan will be energized to prevent the conditioned space
from being over-pressurized during economizer operation.
The exhaust fan, motor and controls are installed and
wired at the factory. The rain hood must be assembled
and installed in the field.
• MOTORIZED OUTDOOR AIR INT A KE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and must
be field assembled before installing.
• PHENOLIC COATED EVAPORATOR, REHEAT, AND CONDENSER COILS - Special coating process that
utilizes Technicoat 10-1" processes. Coating is applied by
total immersion of the complete coil for maximum
protection.
• ELECTRIC HEATERS wired for single point power
supply. These nickel chromium heater elements are
provided with limit and automatic reset capability to
prevent operation at excessive temperatures.
• VARIABLE AIR VOLUME (VAV) - A factory-installed
variable frequency drive (VFD), mounted in the Blower
Access compartment, is used to control the speed of the
indoor blower motor in order to maintain a constant static
pressure in the supply duct. A pressure transducer and
VAV control board are mounted inside the control box.
The drive comes completely wired and pre-programmed
from the factory.
An optional, factory-installed manual bypass switch available with factory-installed VFD can be found in the Blower
Motor Access compartment. The switch can be used to
either route power to the VFD for modulating control of the
blower motor, to bypass the drive and operate the motor
at full speed, or to power the drive (and not the motor) for
diagnostic purposes.
Due to space limitations, VAV is not available with any of
the factory-installed BAS options described below, but is
available with ‘BAS-ready’ models. Terminal blocks are
provided in the control box for field wiring of the customerinstalled BAS.
A ‘VFD-ready’ option provides the provisions for a customer-installed drive. The unit comes with a mounting
bracket installed in the Blower Access compartment which
may accommodate other vendor’s drives depending on
their size. In order to utilize the unit’s mounting bracket,
the maximum recommended drive dimensions are as follows:
For 5-hp motor applications........................13” H x 6” W x 7” D
For 7.5 thru 15-hp motor applications.........13” H x 8” W x 8” D
If the customer-installed drive will not fit in the allotted
space, then it will have to be mounted within a NEMA-4
enclosure for outside installation or inside the building on
a perpendicular wall not subjected to excessive temperature, vibration, humidity, dust, corrosive gas, explosive
gas, etc.
A terminal block located in the control box is provided for
field connection of the VFD controls.
•HOT GAS BYPASS - To allow for low cooling load operation, a direct-acting pressure-modulating bypass control
valve installed on the system #1 discharge line is used to
divert high temperature, high pressure refrigerant around
the TXV in order to maintain a desired minimum evaporator
pressure. HGBP is standard on all units with VAV and
optional with CV units.
• FILTER OPTIONS - Standard units are shipped with 2”
throw-away filters installed. 2” pleated and 4” pleated
filters are offered as a factory installed op t io n .
• CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or you
may order the unit with a “non-powe re d” convenience
outlet that can be wired in the field.
• DISCONNECT SWITCH - For gas heat units and cooling
units with electric heat, a HACR breaker sized to the unit
is provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
• DOUBLE WALL CONSTRUCTION - Optional double wall
construction is available to provide smooth inner surfaces
for easy and effective cleaning to reduce risk of dirt and
bacterial accumulation. Fiberglass insulation is
sandwiched between heavy gauge steel sheets to form a
durable, rigid casing to withstand higher working
pressures and impact forces. The heavy-duty construction
provides excellent acoustic and thermal insulation and
eliminates erosion of insulation material and
contamination of the air stream.
• BAS - Building Automation System Controls
(available on two-system cooling product only).
Simplicity® INTELLI-Comfort™ CONTROL - The York®
Simplicity® INTELLI-Comfort™ control is factory installed.
It includes a supply air sensor, a return air sensor , and an
outside air sensor. There are provisions for a field installed
dirty filter indicator switch, an air-proving switch, an Outside Air Humidity sensor, a Return Air Humidity sensor, an
Inside IAQ sensor, and an Outside Air IAQ sensor. Con-
8Unitary Products Group
Page 9
262292-YTG-B-0107
struction mode operation, 365-day real time clock with 7
day programming plus holiday scheduling is built-in. Two
different modes of demand ventilation are achieved
through the INTELLI-Comfort™ using CO
sensors. It
2
uses an inside CO2 sensor to perform Demand Ventilation. It can also use an Outside CO2 sensor to perform Differential Demand Ventilation. It uses a Patented Comfort
Ventila ti on algorithm to provide comfortable ventilation air
temperature. The patented economizer-loading algorithm
will protect the equipment when harsh operating conditions exist. Humidity in the occupied space or return duct
can be monitored and controlled via humidity sensors and
the on-board connection for hot gas re-heat system. It
uses the INTELLI-Start™ algorithm to maximize energy
savings by recovering the building from the Unoccupied
Setpoints to the Occupied Setpoints just in time for the
Occupied Time Period to begin. The Simplicity® INTELLIComfort™ balances space temperature, ventilation air
temperature, CO
and humidity for ultimate comfort.
2
Simplicity® INTELLI-Comfort™ with ModLINC CON-
TROL - The York® Simplicity® INTELLI-Comf ort™ with
ModLINC control is factory installed. It includes all the features of the INTELLI-Comfort™ control with an additional
control to translate communications from MODBUS to the
BACnet MSTP protocol.
Novar® BAS CONTROL - The Novar® ETC-3 building
automation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch, and air proving switch.
JOHNSON CONTROLS BAS CONTROL - The Johnson
Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor, return
air sensor, dirty filter indicator switch, and air proving
switch.
CPC BAS CONTROL - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes supply air sensor , ret ur n air sens or, dirty filter indicator switch
and air proving switch.
HONEYWELL BAS CONTROL - The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
• COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
• SMOKE DETECTORS - (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.
Factory installed smoke detectors in the return air,
may be subjected to freezing temperatures during
“off” times due to out side air infiltration. these smoke
detectors have an operational limit of 32°F to 131°F.
smoke detectors installed in areas that could be out
side those limitations will have to be moved to prevent
having false alarms.
• STAINLESS STEEL HEAT EXCHANGER - For
applications in corrosive environments, this option
provides a full stainless steel heat exchanger assembly.
• STAINLESS STEEL DRAIN PAN - An optional rust-proof
stainless steel drain pan is available to provide years of
trouble-free operation in corrosive environments.
• PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-ofphase condition.
• HIGH SPEED DRIVE - May include a belt, blower pulley,
motor pulley or a motor change to enhance blower
performance.
• DIRTY FILTER SWITCH - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option or
field installed accessory.
• HINGED FILTER DOOR/”TOOLLESS” BLOWER AND ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.
NOTE: Knobs are shipped separately within the unit to
prevent shipping damage. These must be field
installed for toolless operation.
• LOW SPEED DRIVE - Includes a motor change when
high airflow is not required. (WR300 & WR240 only)
FIELD-INSTALLED ACCESSORIES
• SINGLE INPUT ELECTRONIC ENTHALPY
ECONOMIZERS - Includes a slide-in / plug-in damper
assembly with fully modulating spring-return motor
actuator capable of introducing up to 100% outdoor air
with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
• MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and must
be field-assembled before installing.
Unitary Products Group9
Page 10
262292-YTG-B-0107
Power exhaust is not available as a field installed
option.
• ROOF CURBS - Fourteen-inch high roof curbs provide a
water-tight seal between the unit and the finished roof.
These full perimeter curbs meet the requirements of the
National Roofing Contractors Association (NRCA) and are
shipped knocked-down for field assembly.
They're designed to fit inside the base rails of the unit and
include both a wood nailing strip and duct hanger
supports.
• HIGH ALTITUDE NATURAL GAS - Burner orifices and
pilot orifices are provided for proper furnace operation at
altitudes up to 6,000 feet.
• PROPANE - Burner orifices, pilot orifices and gas valve
parts are provided to convert a natural gas furnace to
propane.
• HIGH ALTITUDE PROPANE - Burner orifices and pilot
orifices are provided for proper furnace operation at
altitudes up to 6,000 feet. This accessory supplements the
basic propane conversion kit.
• SIDE DUCT FLANGES - One-inch flanges replace the
supply and return air panels on the rear of the unit to
accommodate horizontal duct connections. These flanges
can also be used individually for bottom supply/horizontal
return or horizontal supply/bottom return. They cannot be
used on units with power exhaust.
• BAROMETRIC RELIEF DAMPER - This damper
accessory can be used to relieve internal building air
pressure on units with an economizer without power
exhaust. This accessory includes a rain hood, a bird
screen and a fully assembled damper. With bottom duct
connections, the damper should be mounted over the
opening in the return air panel. With horizontal ductwork,
the accessory should be mounted on the return air duct.
• ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.
• BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.
• FLUE EXHAUST EXTENSION KIT - In locations with
wind or weather conditions which may interfere with
proper exhausting of furnace combustion products, this kit
can be installed to prevent the flue exhaust from entering
nearby fresh air intakes.
• WOOD SKID - Allows unit to be handled with 90” forks.
SENSOR - Senses CO2 levels and automatically
• CO
2
overrides the economizer when levels rise above the
present limits.
• COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
• PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-ofphase condition.
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA
2. At a distance of 10 feet from the blower.
CFM
values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture
has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA
value or sound data in any other form than sound power level ratings.
1. Certified in accordance with the Unitary Large Equipment
certification program which is based on ARI Standard 340/
360.
2. EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power input in
watts, expressed in Btuh per watt (Btuh/watt).
First stage is 50% of total.
S.S.E. = Steady State Efficiency (80%) - output divided by input.
For units with VFD and electric or gas heat, the
speed of the indoor blower motor continues to
be controlled by duct static pressure via the
VAV control board.
If there are VAV boxes present in the duct system, the boxes must be driven to th e full-open
position using a customer-supplied power
source to assure adequate airflow across electric heating elements or gas heat exchanger
tubes.
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
*
Total
Cap.
(MBH)
2
Total
1
Input
(kW)
Sensible Capacity (MBH)
Return Dry Bulb (°F)
239228199171142114
238238205175145115
*
All Sensible Capacity
Unitary Products Group17
Page 18
262292-YTG-B-0107
TABLE 7: COOLING CAPACITIES FOR WR180 (ALTERNATE REHEAT MODE)
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
All Sensible Capacity
Temperature of Air on Condenser Coil
*
Return Dry Bulb (°F)
Total
Cap.
(MBH)
2
Total
1
Input
Sensible Capacity (MBH)
Return Dry Bulb (°F)
(kW)
*
18Unitary Products Group
Page 19
262292-YTG-B-0107
TABLE 8: COOLING CAPACITIES FOR WR240 (ALTERNATE REHEAT MODE)
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
*
Return Dry Bulb (°F)
Total
Cap.
(MBH)
2
Total
1
Input
Sensible Capacity (MBH)
Return Dry Bulb (°F)
(kW)
*
All Sensible Capacity
Unitary Products Group19
Page 20
262292-YTG-B-0107
TABLE 9: COOLING CAPACITIES FOR WR300 (ALTERNATE REHEAT MODE)
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Alternate mode @ various indoor (wet bulb/dry bulb) conditions
0
65758595105
Outdoor Temp ºF
75/7180/7175/6785/7180/6785/67
FIGURE 7: WR240 MOISTURE REMOVAL - ALTERNATE MODE
20-Ton Moisture Removal @ 8000 cfm
70
60
50
40
30
Lbs/Hr
20
10
Normal mode @ various indoor (wet bulb/dry bulb) conditions
0
65758595105
Outdoor Temp ºF
75/7180/7175/6785/71
FIGURE 8: WR240 MOISTURE REMOVAL - NORMAL MODE
22Unitary Products Group
Page 23
262292-YTG-B-0107
Lbs/Hr
25-Ton Moisture Removal @ 8000 cfm
Alternate mode @ various indoor (wet bulb/dry bulb) conditions
180
160
140
120
100
80
60
40
20
0
65758595105
Outdoor Temp ºF
75/7180/7175/6785/7180/6785/67
FIGURE 9: WR300 MOISTURE REMOVAL - ALTERNATE MODE
25-Ton Moisture Removal @ 8000 cfm
Normal mode @ various indoor (wet bulb/dry bulb) conditions
100
90
80
70
60
50
Lbs/Hr
40
30
20
10
0
65758595105
Outdoor Temp ºF
75/7180/7175/6785/7180/67
FIGURE 10:WR300 MOISTURE REMOVAL - NORMAL MODE
Unitary Products Group23
Page 24
262292-YTG-B-0107
CFM, STATIC PRESSURE, AND POWER - ALTITUDE
AND TEMPERATURE CORRECTIONS
The information below should be used to assist in application of
product when being applied at altitudes at or exceeding 1000
feet above sea level.
use the indoor blower tables for high altitude applications,
certain corrections are necessary.
A centrifugal fan is a "constant volume" device. This means
that, if the rpm remains constant, the CFM delivered is the
same regardless of the density of the air. However, since the
air at high altitude is less dense, less static pressure will be
The air flow rates listed in the standard blower performance
tables are based on standard air at sea level. As the altitude or
temperature increases, the density of air decreases. In order to
generated and less power will be required than a similar
application at sea level. Air density correction factors are
shown in Table 10 and Figure 11.
The examples below will assist in determining the airflow
performance of the product at altitude.
Example 1: What are the corrected CFM, static pressure, and
BHP at an elevation of 5,000 ft. if the blower performance data
ALTITUDE (FEET)
blower tables to select the blower speed and the BHP
requirement.
Solution: As in the example above, no temperature
information is given so 70°F is assumed.
is 6,000 CFM, 1.5 IWC and 4.0 BHP?
The 1.5" static pressure given is at an elevation of 5,000 ft. The
Solution: At an elevation of 5,000 ft the indoor blower will still
deliver 6,000 CFM if the rpm is unchanged. However, Table 10
first step is to convert this static pressure to equivalent sea level
conditions.
must be used to determine the static pressure and BHP. Since
no temperature data is given, we will assume an air
Sea level static pressure = 1.5 / .832 = 1.80"
temperature of 70°F. Table 10 shows the correction factor to
be 0.832.
Enter the blower table at 6000 sCFM and static pressure of
1.8". The rpm listed will be the same rpm needed at 5,000 ft.
Corrected static pressure = 1.5 x 0.832 = 1.248 IWC
Suppose that the corresponding BHP listed in the table is 3.2.
Corrected BHP = 4.0 x 0.832 = 3.328
This value must be corrected for elevation.
Example 2: A system, located at 5,000 feet of elevation, is to
BHP at 5,000 ft = 3.2 x .832 = 2.66
deliver 6,000 CFM at a static pressure of 1.5". Use the unit
24Unitary Products Group
Page 25
262292-YTG-B-0107
$OWLWXGH7HPSHUDWXUH&RQYHUVLRQ)DFWRU
&255(&7,21)$&725
6($/(9(/
IW
7(03(5$785()
FIGURE 11:ALTITUDE/TEMPERATURE CONVERSION FACTOR
Unitary Products Group25
Page 26
262292-YTG-B-0107
TABLE 11: WR180 BLOWER PERFORMANCE - 15 TON STANDARD DRIVE (COOLING ONLY) DOWNFLOW
25-Ton High Static Drive, Gas Heat, Bottom Duct Connection
13000
12000
11000
10000
SCFM
9000
8000
7000
6000
1 Turn
2 Turns
3 Turns
4 Turns
5 Turns
6 Turns
0.20.40.60.81.01.21.41.61.82.02.22.42.6
1VP71 & 1B5V94
External Static ("WC)
Unitary Products Group37
Page 38
262292-YTG-B-0107
TABLE 23: BLOWER MOTOR AND DRIVE DATA
1
MODEL
SIZE
Standard 790/9705184 T 89.5
15 TON
20 TON
25 TON
1. All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their servi ce factor becau se they are
located in the moving air, upstream of any heating device.
CENTRIFUGAL BLOWER (Dia. x Wd.)15x1518x15
FAN MOTOR HP5/7.57.5/10.0/15.07.5/15.0
ROWS DEEP6
FINS PER INCH13
FACE AREA (Sq. Ft.)20.52
PROPELLER DIA. (In.)(Each)2430
FAN MOTOR HP(Each)1/33/4
NOM. CFM TOTAL(Each)4,0005,000
ROWS DEEP2
FINS PER INCH20
FACE AREA (Sq. Ft.)63.8
ROWS DEEP2
FINS PER INCH13
FACE AREA (Sq. Ft.)17.2
SCROLL2
QUANTITY PER UNIT (16” X 25” X 2”)4
QUANTITY PER UNIT (16” X 20” X 2”)4
TOTAL FACE AREA (Sq. Ft.)20
REFRIGERANT 22
(Lb./Oz.)
MODELSWR180WR240WR300
SYSTEM No. 124/028/828/0
SYSTEM No. 223/027/026/4
BASIC
UNIT
OPTIONS
ACCESSORIES
COOLING ONLY241027102810
GAS / ELECTRIC
DOUBLE WALL260
ECONOMIZER160
ECONOMIZER WITH
POWER EXHAUST
MOTORIZED DAMPER150
ELECTRIC
HEATER
HOT GAS BYPASS10
SUPPLY FAN VFDSee Table 33
ROOF CURB185
BAROMETRIC DAMPER45
ECONOMIZER / MOTORIZED
DAMPER RAIN HOOD
ECONOMIZER / POWER
EXHAUST RAIN HOOD
WOOD SKID220
N24261029103010
N32265029503050
245
18 KW25
36 KW30
54 KW35
72 KW40
55
90
TABLE 33: SUPPLY FAN VFD WEIGHTS, IN LBS.
SUPPLY FAN MOTOR230V460V575V
W/O MANUAL BYPASS
5.0 hp
7.5 hp
10.0 hp
15.0 hp
W/MANUAL BYPASS
5.0 hp
7.5 hp
10.0 hp
15.0 hp
Unitary Products Group45
252530
303030
303035
303040
303035
353535
353540
403545
Page 46
BLOWER
COMPARTMENT
ACCESS
BLOWER MOTOR
ACCESS (Location of
Optional VFD Bypass)
BLOWER ACCESS
(Location of
Optional VFD)
ECONOMIZER / MOTORIZED DAMPER
FIXED OUTDOOR INTAKE AIR AND
POWER EXHAUST RAIN HOODS
(See detail Y)
180-19/32
COMPRESSOR ACCESS
262292-YTG-B-0107
DOT PLUG
(For pressure
drop reading)
GAS OR ELECTRIC
HEAT
ACCESS
VENT AIR
OUTLET
HOODS
UNIT BASE RAILS
Shown separately to illustrate
Bottom Duct openings. Power
and Gas Piping Connection
location.
NOTE:
For curb mounted units, refer to the curb hanger
dimensions of the curb for proper size of the
supply and return air duct connections.
52-5/8
COMBUSTION
AIR INLET HOOD
CONTROL BOX
ACCESS
(D)
GAS SUPPLY
ENTRY
(C) GAS
SUPPLY
ENTRY
136-1/4
35
35-1/4
11-1/8
7-1/8
46-5/8
2-3/4
5-7/8
33
12-1/2
21.00
6-3/8
9-3/4
46-5/8
RETURN
AIR
21-1/2
5
SUPPLY
AIR
9-1/4
11-1/2
8-1/8
9-3/4
92
(B) POWER
WIRING
ENTRY
BOTTOM SUPPLY
AND RETURN
AIR OPENINGS
(See Note)
(B) POWER WIRING
ENTRY
(A) CONTROL WIRING
ENTRY
CONDENSER
COILS
(A) CONTROL WIRING
ENTRY
DISCONNECT
SWITCH
LOCATION
All dimensions are in inches. They are
subject to change without notice.
Certified dimensions will be provided
upon request.
2. Opening in the bottom of the unit can be located by the slice in
1-1/8” KO
3/4” NPS (Fem.)Bottom
3-5/8” KO
3” NPS (Fem.)Bottom
2-3/8” KO
1-11/16” Hole
Control Wiring
Power Wiring
USED FOR
Gas Piping (Front)
Gas Piping (Bottom)
the insulation.
All entry holes should be field sealed to prevent rain
NOTE:
water entry into the building.
Side
Side
1
,
1
2
46Unitary Products Group
Page 47
262292-YTG-B-0107
Dimensions listed are for side
duct flange openings; see
Field Accessories for Side
Duct Flange Kit.
FIGURE 13:REAR VIEW DIMENSIONS
40-3/8"
COMPRESSOR
ACCESS
SUPPLY AIR
ACCESS
RETURN AIR
ACCESS
SUPPLY
AIR
18-5/8"
REAR
VIEW
5-1/8"
RETURN
AIR
27-3/4"
OUTDOOR
AIR
39-5/8"
40-1/2"
OUTDOOR AIR
COMPARTMENT
ACCESS
EVAPORATOR
SECTION
DOT PLUG
(For pressure
drop reading)
FILTER
ACCESS
1" NPT FEMALE
COND. DRAIN
CONNECTION
NOTE:Units are shipped with the bottom duct openings
covered. An accessory flange kit is available for
connecting side ducts.
For bottom
duct applications:
1. Remove the side panels from the supply and return air
compartments to gain access to the bottom supply and
return air duct covers.
2. Remove and discard the bottom duct covers. Duct
openings are closed with sheet metal covers except when
the unit includes a power exhaust option. The covering
consists of a heavy black paper composition.
3. Replace the side sup ply and return air compartment
panels.
For side duct applications:
1. Replace the side panels on the supply and return air
compartments with the side duct flange accessory kit
panels.
2. Connect ductwork to the flanges on those panels.
Unitary Products Group47
Page 48
262292-YTG-B-0107
TABLE 35: MINIMUM CLEARANCES
LOCATION
Front
Rear
Left Side (Filter Access)
Right Side (Cond. Coil)
Below Unit
Above Unit
1
2
CLEARANCE
36”
24” (Less Economizer)
49” (With Economizer)
24” (Less Economizer)
36” (With Economizer)
36”
72” With 36” Maximum
Horizontal Overhang (For
Condenser Air Discharge)
1. Units may be installed on combustible floors made from wood or
class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging structures or
shrubs should not obstruct condenser air discharge outlet.
3. If economizer is factory installed, the unassembled rain hood
must be removed from its ride along position in front of evaporator coil, or in the outdoor air compartment, prior to final installation.
ECONOMIZER
MOTORIZED
SUPPLYAIR
COMPARTMENT
POWER EXHAUST
RAIN HOOD
(on Return Air Compartment)
DAMPER
RAIN HOOD
(on Outdoor Air Compartment)
NOTE: ELEC / ELEC Models: Units and ductwork are approved
for zero clearance to combustible material when
equipped with electric heaters.
GAS / ELEC Models
: A 1” clearance must be provided
between any combustible material and the supply air
3
0”
ductwork for a distance of 3 feet from the unit.
The products of combustion must not be allowed to
accumulate within a confined space and recirculate.
Locate unit so that the vent air outlet hood is at least:
• Three (3) feet above any force air inlet located within
10 horizontal feet (excluding those integral to the unit).
• Four (4) feet below, four horizontal feet from, or one
foot above any door or gravity air inlet into the building.
• Four (4) feet from electric and gas meters, regulators
and relief equipment.
ECONOMIZER / MOTORIZED DAMPER
AND POWER EXHAUST RAIN HOODS
1. The 2” space betwee n the ducts allows for “jumping” an
existing roof joist.
2. The 58-1/2” overall dimension of the ducts allows ductwork
penetration between roof joists that are spaced on 72”
centers.
NOTE: Ducts can be install ed into the curb from the roof. All
electrical and gas line connections can be made inside
the curb.
FIGURE 20:CUT AWAY OF ROOF CURB
Unitary Products Group51
Page 52
262292-YTG-B-0107
Y
THERMOSTAT
TERMINALS
1
RC
RH
Y1
Y2
W1
W2
G
C
X1
X3
X4
A1
A2
T
T
TO REMOTE SENSOR
2ET04701324 IF USED
1
Electronic programmable Thermostat 2ET0770010024
( includes subbase).
2
Terminals A1 and A2 provide a relay output to close the
outdoor economizer dampers when the thermostat
switches to the set-back position.
3
Dehumidistat closes on rise in humidity.
2
CONTROL BOARD
( RCB )
REHEAT
R
Y1
Y2
W1
W2
G
C
OCC
HUM
HUM
TERMINAL BLOCK
RH
1
2
3
4
TYPICAL
THERMOSTAT
RC
RH
Y1
Y2
G
W1
W2
C
R
Y1
Y2
G
W1
W2
OCC
C
DEHUMIDISTAT
( RCB )
REHEAT
CONTROL
BOARD
HUM
3
TERMINAL
BLOCK
RH
1
2
DEHUMIDISTAT
1
3
4
1
Dehumidistat closes on rise in humidity.
TERMINAL BLOCK TB1
GROUND
LUG
FACTORY OR FIELD
SUPPLIED DISCONNECT
THREE
PHASE
POWER
SUPPL
FIGURE 21:TYPICAL FIELD WIRING
52Unitary Products Group
Page 53
262292-YTG-B-0107
GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility.
York's Sunline Magnum™ units are convertible single package
units. All models have dual independent refrigerant circuits for
efficient part load operation and maximum comfort control.
Although the units are primarily designed for curb mounting on
a roof, they can also be slab-mounted at ground level or set on
steel beams above a finished roof. Cooling only, cooling with
gas heat and cooling with electric heat models are available
with a wide variety of factory-mounted options and fieldinstalled accessories to make them suitable for almost every
application. All units are self-contained and assembled on full
perimeter base rails with holes in the four corners for overhead
rigging. Every unit is completely piped, wired, charged and
tested at the factory to simplify the field installation and to
provide years of dependable operation. All models (including
those with an economizer) are suitable for either bottom or
horizontal duct connections. Models with power exhaust are
suitable for bottom duct connections only. For bottom duct,
remove the sheet metal panels from the supply and return air
openings through the base of the unit. For horizontal duct,
replace the supply and return air panels on the rear of the unit
with a side duct flange accessory. All supply air blowers are
equipped with a belt drive that can be adjusted to meet the
exact requirements of the job.
Each unit shall have 4 condenser fan motors. A high speed
drive accessory is available for applications with a higher CFM
and/or static pressure requirement. All compressors include
crankcase heat and internal pressure relief. Every refrigerant
circuit includes an expansion valve, a liquid line filter-drier, a
discharge line high pressure switch and a suction line with a
freezestat and low pressure/loss of charge switch. The unit
control circuit includes a 75 VA transformer, a 24-volt circuit
breaker and a relay board with two compressor lockout circuits,
a terminal strip for thermostat wiring, plus an additional set of
pin connectors to simplify the interface of additional field
controls. All units have long lasting powder paint cabinets with
1000 hour salt spray test approval under ASTM-B117
procedures. All 208/230 and 460-volt models are ETL
approved. All 208/230 and 575-volt models are CGA approved.
All models include a 1-year limited warranty on the complete
unit. Compressors and electric heater elements carry an
additional 4-year warranty. Aluminized steel tubular heat
exchangers carry an additional 9-year warranty.
DESCRIPTION
Units shall be factory-assembled, single packaged, WR***N
Electric Cooling/Gas Heat, WR***C/E Electric Cooling/Optional
Electric Heat, designed for outdoor mounted installation. The 15
and 20 ton units shall have minimum EER ratings of 9.7. The 25
ton unit shall have a minimum EER rating of 9.5.
They shall have built-in field convertible duct connections for
down discharge supply/return or horizontal discharge supply/
return, and be available with factory installed options or field
installed accessories. The units shall be factory wired, piped,
charged with R-22 refrigerant and factory tested prior to
shipment. All unit wiring shall be both numbered and color
coded. All units shall be manufactured in a facility certified to
ISO 9001 standards and the cooling performance shall be rated
in accordance with DOE and ARI test procedures. Units shall
be ETL & CGA listed, classified to ANSIZ21.47 standards, UL
1995/CAN/CSA No. 236-M90 conditions.
UNIT CABINET
Unit cabinet shall be constructed of G90 galvanized steel, with
exterior surfaces coated with a non-chalking, powdered paint
finish, certified at 1000 hour salt spray test per ASTM-B117
standards. Indoor blower section shall be insulated with a
minimum 1/2" thick insulation, coated on the airside. Aluminum
foil faced insulation shall be used in the furnace compartment
and be fastened with ridged fasteners to prevent insulation from
entering the air stream. Cabinet panels shall be "large" size,
easily removable for servicing and maintenance. Full perimeter
base rails shall be provided to assure reliable transit of
equipment, overhead rigging and proper sealing on roof curb
applications. Disposable 2" filters shall be furnished and be
accessible through a removable access door, sealed airtight.
Units filter track shall be designed to accommodate either 1" or
2" filters. Fan performance measuring ports shall be provided
on the outside of the cabinet to allow accurate air
measurements of evaporator fan performance without removing
panels or creating air by-pass of the coils. Condensate pan
shall be internally sloped and conform to ASHRAE 62-89 selfdraining standards. Condensate connection shall be a minimum
of 1" I.D. female and be a ridged mount connection. Unit shall
incorporate a fixed outdoor air damper with an outdoor air
intake opening covered with a bird screen and a rain hood
painted to match the exterior of the unit.
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be a belt drive assembly and include an adjustablepitch motor pulley. Job site selected (B.H.P.) brake horsepower
shall not exceed the motors nameplate horsepower rating, plus
the service factor. Units shall be designed not to operate above
service factor. Fan wheel shall be double-inlet type with
forward-curved blades, dynamically balanced to operate
smoothly throughout the entire range of operation. Airflow
design shall be constant air volume.
A variable air volume (VAV) option using a variable frequency
drive (VFD) is available for applications requiring a constant
supply duct static pressure. Units equipped for VAV shall be
controlled by a duct pressure transducer with a 0 - 5” WC pressure range. The pressure transducer shall provide a 0 - 5 VDC
output signal to a VAV control board which, in turn shall provide
a 2 - 10 VDC speed reference signal to the VFD. Units
equipped with VFD’s shall have factory-installed manual bypass
as an option.
Unitary Products Group53
Page 54
262292-YTG-B-0107
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fans shall be of the direct-driven propeller type,
discharge air vertically, have aluminum blades riveted to
corrosion resistant steel spider brackets and shall be
dynamically balanced for smooth operation. The 4 outdoor fan
motors shall be totally enclosed with permanently lubricated
bearings, internally protected against overload conditions and
staged independently.
REFRIGERANT COMPONENTS
Compressors:
a. Shall be Scroll compressors internally protected with
internal high-pressure relief and over temperature
protection.
b. Shall have internal spring isolation and sound muffling to
minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.
Coils:
a. Evaporator and condenser coils shall have aluminum
plate fins mechanically bonded to seamless internally
enhanced copper tubes with all joints brazed. Special
Phenolic coating shall be available as a factory option.
b. Evaporator and Condenser coils shall be of the direct
expansion, draw-thru, design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Balance-port thermostatic expansion valve with
independent circuit feed system.
b. Filter drier/strainer to eliminate any moisture or foreign
matter.
c. Accessible service gage connections on both suction
and discharge lines to charge, evacuate, and measure
refrigerant pressure during any necessary servicing or
troubleshooting, without losing charge.
d. The refrigeration system shall provide at least 10° F of
sub-cooling at design conditions.
e. All models shall have two independent circuits.
f. Hot gas bypass option shall be factory-installed on
compressor #1 discharge line to provide cooling in low-
load applications. HGBP shall be a standard feature on
VAV models and an optional feature on CV models.
UNIT CONTROLS
a. Unit shall be complete with self-contained low-voltage
control circuit protected by a resetable circuit breaker on
the 24-volt transformer side.
b. Unit shall incorporate a lockout circuit which provides
reset capability at the space thermostat or base unit,
should any of the following standard safety devices trip
and shut off compressor.
c. Loss-of-charge/Low-pressure switch.
1. High-pressure switch.
2. Freeze-protection thermostat, evaporator coil. If any of
the above safety devices trip, a LED (light-emitting
diode) indicator shall flash a diagnostic code that
indicates which safety switch has tripped.
d. Unit shall incorporate "AUTO RESET" compressor over
temperature, over current protection.
e. Unit shall operate with conventional thermostat designs
and have a low voltage terminal strip for easy hook-up.
f. Unit control board shall have on-board diagnostics and
fault code display.
g. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to
0 °F.
h. Control board shall monitor each refrigerant safety switch
independently.
i. Control board shall retain last 5 fault codes in non volatile
memory, which will not be lost in the event of a power
loss.
GAS HEATING SECTION (WR***N MODELS)
Shall be designed with induced draft combustion with post
purge logic and energy saving direct spark ignition, redundant
main gas valve. Ventor wheel shall be constructed of stainless
steel for corrosion resistance. The heat exchanger shall be of
the tubular type, constructed of T1-40 aluminized steel for
corrosion resistance and allowing minimum mixed air entering
temperature of 25° F. Burners shall be of the in-shot type,
constructed of aluminum coated steel and contain air mixture
adjustments. All gas piping shall enter the unit cabinet at a
single location through either the side or curb, without any field
modifications. An integrated control board shall provide timed
control of evaporator fan functioning and burner ignition.
Heating section shall be provided with the following minimum
protection:
a. Primary and auxiliary high-temperature limit switches.
b. Induced draft motor speed sensor.
c. Flame roll out switch (automatic reset).
d. Flame proving controls. Unit shall have two independent
stages of capacity.
ELECTRIC HEATING (WR***C/E MODELS)
Nickel chromium electric heating elements shall be provided as
required by the application with 1 or 2 stage control, as
required, from 13.5 KW to 72 KW capacities. The heating
section shall have a primary limit control(s) and automatic reset
to prevent the heating element system from operating at an
excessive temperature. Units with Electric Heating shall be
wired for a single point power supply with branch circuit fusing
(where required).
54Unitary Products Group
Page 55
262292-YTG-B-0107
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125° F outdoor
temperature, exceeding maximum load criteria of ARI Standard
340/360. The compressor, with standard controls, shall be
capable of operation down to 25° F outdoor temperature.
Accessory low ambient kit shall be available for operation to 0°
F. Unit shall be provided with fan time delay to prevent cold air
delivery before heat exchanger warms up (Gas heat only).
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory
provided location and be capable of side or bottom entry, to
minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
control wiring.
STANDARD LIMITED WARRANTIES
•Compressor 5 Yea r s
•Heat Exchanger 10 Years
•Electric Heat Element 5 Years
•Other Parts 1 Year
OPTIONAL OUTDOOR AIR (Shall be made available by
either/or):
• ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER
- Outdoor and return air dampers that are interlocked and
positioned by a fully-modulating, spring-return damper
actuator. The maximum leakage rate for the outdoor air
intake dampers shall not exceed 2% when dampers are
fully closed and operating against a pressure differential
of 0.5 IWG. A unit-mounted potentiometer shall be
provided to adjust the outdoor and return air damper
assembly to take in CFM of outdoor air to meet the
minimum ventilation requirement of the conditioned space
during normal operation. During economizer operation, a
mixed-air temperature control shall modulate the outdoor
and return air damper assembly to prevent the supply air
temperature from dropping below 55°F. Changeover from
compressor to economizer operation shall be provided by
an integral electronic enthalpy control that feeds input into
the basic module. The outdoor intake opening shall be
covered with a rain hood that matches the exterior of the
unit. Water eliminator/filters shall be provided.
Simultaneous economizer/compressor operation is also
possible. Dampers shall fully close on power loss.
• MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and
return air dampers that are interlocked and positioned by
a 2-position, spring-return damper actuator. The
maximum leakage rate for the outdoor air intake dampers
shall not exceed 2% when dampers are fully closed and
operating against a pressure differential of 0.5 IWG. A
unit-mounted potentiometer shall be provided to adjust
the outdoor and return air damper assembly to take in the
design CFM of outdoor air to meet the ventilation
requirements of the conditioned space during normal
operation. Whenever the indoor fan motor is energized,
the dampers open up to one of two pre-selected positions
- regardless of the outdoor air enthalpy. Dampers return to
the fully closed position when the indoor fan motor is deenergized. Dampers shall fully close on power loss.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
• ROOF CURB - 14" high, full perimeter curb with wood
nailer (shipped knocked-down).
• 100% BAROMETRIC RELIEF DAMPER - Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit.
• PROPANE CONVERSION KIT - Contains new orifices
and gas valve parts to convert from natural to L.P. gas.
One per unit required.
• HIGH ALTITUDE - NATURAL GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude.
• HIGH ALTITUDE - PROPANE GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude. Must be used with propane conversion kit.
• BURGLAR BARS - Designed to work with above roof
curbs, depending on unit model. Fits duct openings of
curb supply and return air openings.
• SIDE DUCT FLANGE - Supply and return air duct flanges
for side duct applications. Do not use on units with power
exhaust.
• HIGH SPEED DRIVE - Includes blower pulley and belt for
higher CFM and/or static pressure requirements.
• WOOD SKID - Allows unit to be handled with 90" forks.
• ECONOMIZER/MOTORIZED DAMPER RAIN HOOD (WRN/E/C30 only) - Contains all hood panels and the
hardware for assembling.
• ANTI-RECYCLE TIMER - Assures 5-minute off time
between compressor cycles.
• LOW AMBIENT KIT - Provides unit cooling operation
down to 0°F.
• COIL GUARD KIT - Guard for cooling coil.
OTHER FACTORY INSTALLED OPTIONS
• POWER EXHAUST OPTION - To work in conjunction
with economizers.
• STAINLESS STEEL HEAT EXCHANGER
• STAINLESS STEEL DRAIN PAN
• TECHNICOAT PHENOLIC COATED CONDENSER AND
EVAPORATOR COIL
• ELECTRONIC SINGLE ENTHALPY ECONOMIZER
• DIRTY FILTER SWITCH
•DOUBLE WALL
• PHASE MONITOR
• COIL GUARD
• POWERED GFI CONVENIENCE OUTLET
• NON-POWERED GFI CONVENIENCE OUTLET
• BAS CONTROLS (Simplicity® INTELLI-Comfort™, CPC,
JOHNSON, HONEYWELL, NOVAR)
Unitary Products Group55
Page 56
• BAS READY ECONOMIZER (BELIMO ACTUATOR
WITHOUT A CONTROLLER)
• HINGED FILTER DOOR ACCESS AND TOOLLESS
ACCESS PANELS