YORK Sunline MagnaDRY™ units are convertible single
package high efficiency rooftops. All models have independent
dual refrigerant circuits for efficient part load operation.
Although the units are primarily designed for curb mounting on
a roof, they can also be slab-mounted at ground level or set on
steel beams above a finished roof.
All units include:
• Powder Paint finish that meets ASTM-B-117 1000 hour
salt spray standards
• Two-stage cooling provided by dual independent
refrigeration circuits with expansion valves, filter-driers,
high and low pressure/loss of charge switches and
freezestats
• Scroll compressors
• Two-stage heating provided by dual independent heat
exchangers with aluminized steel tubes, redundant gas
valves, spark ignition with induced draft logic
• Permanently lubricated motors
• Bottom or side air discharge configuration capability (field
convertible)
• Belt Drive Blower Motor with standard, high and low static
drive option
• Constant supply air volume (CV) with optional variable air
volume (VAV)
• Manufactured under the quality standards of ISO9001
• Simplicity® Control Board
• Zero-25% fixed air damper with hood
• Copper tube/aluminum fin coils
• Hinged filter access and tool free latched doors
A=Std.Drive
B = Std. Drive/Single Input Econo.
C = Std. Drive/Single Input Econo./Power Exhaust
(Downflow Only)
D = Std. Drive/Motorized Damper
E = Std. Drive/Motorized Damper/Barometric Relief
J = Std. Drive/Single Input Econo./Barometric Relief
N = Hi Static Drive
P = Hi Static Drive/Single Input Econo.
Q = Hi Static Drive/Single Input Econo./Power Exhaust
(Downflow Only)
R = Hi Static Drive/Motorized Damper
K = Hi Static Drive/Motorized Damper/Barometric Relief
S = Hi Static Drive/ Single Input Econo./Barometric Relief
2=LowStaticDrive
3 = Low Static Drive/Single Input Econo.
All models are available with a wide variety of factory-mounted
options such as stainless steel heat exchangers, phase
monitor, dirty filter switch, and coil guard to make them suitable
for almost every application.
All units are self-contained and assembled on full perimeter
base rails with holes in the four corners for overhead rigging.
Every unit is completely piped, wired, charged and tested at the
factory to simplify the field installation and to provide years of
dependable operation.
All models (including those with an economizer) are suitable for
either bottom or horizontal duct connections. Models with
factory installed power exhaust are suitable for bottom
duct connections only. For bottom duct, you remove the
sheet metal panels from the supply and return air openings
through the base of the unit. For horizontal duct, you replace
the supply and return air panels on the rear of the unit with a
side duct flange accessory.
All models are available with these “factory mounted” outdoor
air damper options:
•Single enthalpy economizer with or without power exhaust
•BAS-ready economizer with or without power exhaust
•Motorized outdoor air damper
•Barometric Relief Damper
A fixed outdoor air intake assembly will be shipped in the return
air compartment of all units ordered without an economizer or
motorized outdoor air damper option. The assembly includes a
rain hood with a damper that can be set for 10, 15 or 25%
outdoor air. With bottom duct connections, the intake damper
assembly should be mounted over the opening in the return air
panel. With horizontal ductwork, it should be mounted on the
return air duct.
All supply air blowers are equipped with a belt drive that can be
adjusted to meet the exact requirements of the job. A high static
drive option is available for applications with a higher CFM and/
or static pressure requirement. A variable air volume (VAV)
option using a variable frequency drive is available for
applications requiring a constant supply duct pressure. A
differential pressure transducer is used to monitor supply duct
static pressure and return a speed reference signal to the VFD
to control the output of the indoor blower motor.
All compressors include scroll compressors and internal
pressure relief. Every refrigerant circuit includes an expansion
valve, a liquid line filter-drier, a discharge line high pressure
switch and a suction line with a freezestat and low pressure/
loss of charge switch to protect all system components. A hot
gas bypass option, consisting of an adjustable compressor
discharge bypass valve, is available for low cooling load
applications.
• Simplicity® Controls - Simplicity® control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
• Low Ambient - An integrated low-ambient control allows
all units to operate in the cooling mode down to 0°F
outdoor ambient without additional assistance. Optionally,
the control board can be programmed to lockout the
compressors when the outdoor air temperature is low or
when free cooling is available.
• Anti-Short Cycle Protection - To aid compressor life, an
anti-short cycle delay is incorporated into the standard
controls. Compressor reliability is further ensured by
programmable minimum run times. For testing, the anti
short cycle delay can be temporarily overridden with the
push of a button.
• Lead-Lag - An integrated Lead-Lag option allows equal
run time hours on all compressors, thereby extending the
life of all compressors. This option is selectable on the unit
control board.
• Fan Delays - Fan on and fan off delays are fully
programmable. Furthermore, the heating and cooling fan
delay times are independent of one another. All units are
programmed with default values based upon their
configuration of cooling and heat.
• Safety Monitoring
and low-pressure switches, the freezestats, the gas valve,
if applicable, and the temperature limit switch on gas and
electric heat units. The unit control board will alarm on
ignition failures, compressor lockouts and repeated limit
switch trips.
• Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a “three
times, you’re out” philosophy. The high and low-pressure
switches and the freezestats must trip three times within
two hours before the unit control board will lock out the
associated compressor.
• On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and flash
an alarm code on the control board LED. Each high and
low-pressure switch alarm as well as each freezestat
alarm has its own flash code. The control board saves the
five most recent alarms in memory, and these alarms can
be reviewed at any time. Alarms and programmed values
are retained through the loss of power.
All units have long lasting powder paint cabinets with 1000 hour
salt spray test approval under ASTM-B117 procedures.
All models are CSA approved.
• Warranty - All models include a one-year limited parts
warranty on the complete unit. Compressors and electric
heater elements carry a five-year warranty. Gas heat
exchangers carry a 10-year parts warranty.
• Gas Heat Operation - All gas heat units are built with two
heating sections for two equal stages of capacity control.
Each section includes a durable heat exchanger with
aluminized steel or optional stainless steel tubes, a
redundant gas valve, spark ignition, power venting, an
ignition module for 100% shut-off and all of the safety
controls required to meet the latest ANSI standards.
The gas supply piping can be routed into the heating
compartment through a hole in the base pan of the unit or
through a knockout in the piping panel on the front of the
unit.
- The control board monitors the high
4Unitary Products Group
262292-YTG-C-0707
FIGURE 1: UNIT CUTAWAY
• Electric Heat Operation - All electric heat models
(factory installed only) are wired for a single power source
and include a bank of nickel chromium elements mounted
at the discharge of the supply air blower to provide a high
velocity and uniform distribution of air across the heating
elements. Every element is fully protected against
excessive current and temperature by fuses and two
thermal limit switches.
• The power supply wiring can be routed into the control
box through a threaded pipe connection in the base pan of
the unit or through a knockout in the wiring panel on the
front of the unit.
• BAS Controls - York’s Magnum series units offer factory
mounted BAS controls such as Novar, Honeywell,
Johnson, and CPC.
REHEAT MODE SEQUENCE OF OPERATION
The reheat control board allows the user to select two different
modes of operation via a jumper connection on the board. (See
Figure 2.) Each mode is described below. Refer to Figures 2 - 4
when reading this section.
LOCATION OF VFD (Optional)
LOCATION OF VFD BYPASS (Optional)
“NORMAL” MODE
When the reheat control board (RCB) detects a need for
dehumidification (24VAC) at "HUM" via the field supplied
dehumidistat connected to RHTB-1 and RHTB-2 and there is
not a call for cooling, it energizes the hot gas relay (HGR),
which energizes the 3-way valve (SOL 3), the condenser coil
valve (SOL 2), and de-energizes the reheat coil bleed valve
(SOL 1). The Y1 signal is passed to the unit control board
(UCB), which engages circuit # 1, resulting in circuit #1 reheat
mode operation.
When the room thermostat calls for first stage cooling, with or
without a call for dehumidification, the RCB senses a signal
through "Y1", de-energizing the HGR, which de-energizes SOL
3 and SOL 2, and energizes SOL 1, engaging circuit # 1,
resulting in circuit #1 cooling mode operation.
When the room thermostat calls for second stage cooling, the
RCB senses a signal through "Y1" & "Y2" and engages circuit
#1 and circuit #2 in the cooling mode.
Indoor blower operation is initiated upon a call for first stage
cooling, second stage cooling or dehumidification.
Anytime there is a call for 2 stages of cooling, the unit will not
dehumidification at "HUM".
operate in the reheat mode, even if there is a call for
Unitary Products Group5
262292-YTG-C-0707
The unit will not operate in the reheat mode if there is any call
for heating.
On units with economizers, the unit will not operate in the
reheat mode if there is a call for cooling and the economizer is
operating as first stage of cooling.
All safety devices function as previously described.
"ALTERNATE” MODE
When the RCB detects a need for dehumidification (24VAC) at
"HUM" via the field supplied dehumidistat connected to RHTB-1
and RHTB-2, and there is not a call for cooling, it energizes the
HGR, which energizes the SOL 3, SOL 2, and de-energizes
SOL 1. The unit then operates with circuit #1 in reheat mode
and circuit #2 in cooling mode.
When the room thermostat calls for first stage cooling while
there is still a call for dehumidification, no operational change is
R
made. The call for cooling is ignored and the unit continues to
operate with circuit #1 in reheat mode and circuit #2 in cooling
mode.
When the room thermostat calls for second stage cooling, the
RCB senses a signal through "Y1" & "Y2" and de-energizes the
HGR, which de-energizes SOL 3 and SOL 2, and energizes
SOL 1. Both circuits operate in the cooling mode.
Indoor blower operation is initiated upon a call for first stage
cooling, second stage cooling or dehumidification.
Anytime there is a call for 2 stages of cooling, the unit will not
operate in the reheat mode, even if there is still a call for
dehumidification at "HUM".
The unit will not operate in the reheat mode if there is any call
for heating.
All safety devices function as previously described.
Y1
Y2
G
W1
W2
OCC
C
COM
P4
K1
K2
K4
K3
`
P6
HGR
P5
P3
HGRR
HUM
MODE
SELECTION
JUMPER
DEHUMIDISTAT
HARNESS
CONNECTION
FIGURE 2: REHEAT CONTROL BOARD
6Unitary Products Group
262292-YTG-C-0707
FIGURE 3: REHEAT CONTROLS - PART 1
UCB
UNIT CONTROL
BOARD
RHB
REHEAT CONTROL
BOARD
TERMINAL
RHTB
REHEAT
BLOCK
HUM
HUMIDIFY
TERMINAL
RHR
REHEAT
RELAY
REHEAT
SOLENOID
1
REHEAT
SOLENOID
UCB
UNIT CONTROL
BOARD
RHB
BOARD
REHEAT
SOLENOID
2
3
REHEAT
CONTROL
FIGURE 4: REHEAT CONTROLS - PART 2
Unitary Products Group7
262292-YTG-C-0707
FACTORY-INSTALLED OPTIONS
• SINGLE INPUT ELECTRONIC ENTHALPY
ECONOMIZERS - Includes a slide-in / plug-in damper
assembly with fully modulating spring-return motor
actuator capable of introducing up to 100% outdoor air
with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
• BAS-READY ECONOMIZER - Includes a slide-in / plug-in
damper assembly with fully modulating spring-return
motor actuator with zero to 95-degree rotation capable of
introducing up to 100% outdoor air with nominal 1% leakage type dampers.
Actuator requires 2-10 VDC input from an external source,
such as a field-installed or factory-installed BAS controller.
BAS-ready actuators have an adjustable auxiliary endswitch for optional power exhaust control.
For units with optional VAV or Simplicity® Intelli-Comfort™
control, a factory-installed, dry bulb sensor determines if
outdoor air temperature is low enough to provide free-cooling operation. (Field-installed humidity sensors for either
outdoor air or outdoor & return air streams are a vailable for
single enthalpy and differential enthalpy configurations,
respectively).
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
• POWER EXHAUST - Our economizer options are
available with power exhaust. Whenever the outdoor air
intake dampers are opened for free cooling, the exhaust
fan will be energized to prevent the conditioned space
from being over-pressurized during economizer operation.
BAS-ready economizer actuators have an adjustable
auxiliary end-switch to provide a range of damper positions
available to energize power exhaust. For units with optional
VAV , power exhaust is energized by means of a binary
output signal from the unit's VAV control board.
The exhaust fan, motor and controls are installed and
wired at the factory. The rain hood must be assembled
and installed in the field.
• MOTORIZED OUTDOOR AIR INT A KE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to a preset position whenever the supply air blower is operating
and will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must
be field assembled before installing.
• BAROMETRIC RELIEF DAMPER - This damper option
can be used to relieve internal building air pressure on
units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the return
air panel. With horizontal ductwork, the accessory should
be mounted on the return air duct.
• PHENOLIC COATED EVAPORATOR, REHEAT, AND CONDENSER COILS - Special coating process that utilizes
Technicoat 10-1" processes. Coating is applied by total
immersion of the complete coil for maximum protection.
• ELECTRIC HEA TERS wired for single point power
supply. These nickel chromium heater elements are
provided with limit and automatic reset capability to
prevent operation at excessive temperatures.
• VARIABLE AIR VOLUME (VAV) - A factory-installed
variable frequency drive (VFD), mounted in the Blower
Access compartment, is used to control the sp ee d of the
indoor blower motor in order to maintain a constant static
pressure in the supply duct. A pressure transducer and
VAV control board are mounted inside the control box.
The drive comes completely wired and pre-programmed
from the factory.
An optional, factory-installed manual bypass switch available with factory-installed VFD can be found in the Blower
Motor Access compartment. The switch can be used to
either route power to the VFD for modulating control of the
blower motor, to bypass the drive and operate the motor
at full speed, or to power the drive (and not the motor) for
diagnostic purposes.
Due to space limitations, VAV is not available with any of
the factory-installed BAS options described below, but is
available with ‘BAS-ready’ models. Terminal blocks are
provided in the control box for field wiring of the customerinstalled BAS.
A ‘VFD-ready’ option provides the provisions for a customer-installed drive. The unit comes with a mounting
bracket installed in the Blower Access compartment which
may accommodate other vendor’s drives depending on
their size. In order to utilize the unit’s mounting bracket, the
maximum recommended drive dimensions are as follows:
For 5-hp motor applications........................13” H x 6” W x 7” D
For 7.5 thru 15-hp motor applications.........13” H x 8” W x 8” D
If the drive will not fit in the allotted space, then it will have to
be mounted elsewhere; either within the building on a perpendicular wall which is not subjected to excessive temperature, vibration, humidity , dust, corrosive gas, explosive gas,
etc., or within an appropriate enclosure rated for outside
installation to safeguard against moisture, dust and excessive heat.
A terminal block located in the control box is provided for
field connection of the VFD controls.
• HOT GAS BYPASS - To allow for low cooling load opera-
tion, a direct-acting pressure-modulating bypass control
valve installed on the system #1 discharge line is used to
divert high temperature, high pressure refrigerant around
the TXV in order to maintain a desired minimum evaporator pressure. HGBP is standard on all units with VAV and
optional with CV units.
8Unitary Products Group
262292-YTG-C-0707
• FILTER OPTIONS - Standard units are shipped with 2”
throw-away filters installed. 2” pleated and 4” pleated
filters are offered as a factory installed option.
• CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or you
may order the unit with a “non-powered” convenience
outlet that can be wired in the field.
• DISCONNECT SWITCH - For gas heat units and cooling
units with electric heat, a HACR breake r size d to th e un i t
is provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed optio n onl y.
• DOUBLE WALL CONSTRUCTION - Optional double wall
construction is available to provi de s moo th i nne r surfa ces
for easy and effective cleaning to reduce risk of dirt and
bacterial accumulation. Fiberglass insulation is
sandwiched between heavy gauge steel sheets to form a
durable, rigid casing to withstand higher working
pressures and impact forces. The heavy-duty construction
provides excellent acoustic and thermal insulation and
eliminates erosion of insulation material and
contamination of the air stream.
• BAS - Building Automation System Controls
(available on two-system cooling product only).
Simplicity® INTELLI-Comfort™ CONTROL - The York®
Simplicity® INTELLI-Comfort™ control is factory installed. It
includes a supply air sensor, a return air sensor, and an outside air sensor. There are provisions for a field installed dirty
filter indicator switch, an air-proving switch, an Outside Air
Humidity sensor, a Return Air Humidity sensor, an Inside IAQ
sensor, and an Outside Air IAQ sensor. Construction mode
operation, 365-day real time clock with 7 day programming
plus holiday scheduling is built-in. Two different modes of
demand ventilation are achieved through the INTELLI-Comfort™ using CO
sensors. It uses an inside CO2 sensor to
2
perform Demand Ventilation. It can also use an Outside CO
sensor to perform Dif ferent ial D emand Ventilation. It uses a
Patented Comfort Ventilation algorithm to provide comfortable ventilation air temperature. Th e pate nted econ omizerloading algorithm will protect the equipment when harsh
operating conditions exist. Humidity in the occupied space or
return duct can be monitored and controlled via humidity
sensors and the on-board connection for hot gas re-heat
system. It uses the INTELLI-St art™ algorithm to maximize
energy savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the
Occupied Time Period to begin. The Simplicity® INTELLIComfort™ balances space temperature, ventilation air temperature, CO
and humidity for ultimate comfort.
2
Simplicity® INTELLI-Comfort™ with ModLINC CON-
TROL - The York® Simplicity® INTELLI-Comfort™ with
ModLINC control is factory installed. It includes all the features of the INTELLI-Comfort™ control with an additional
control to translate communications from MODBUS to the
BACnet MSTP protocol.
Novar® BAS CONTROL - The Novar® ETC-3 building
automation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch, and air proving switch.
JOHNSON CONTROLS BAS CONTROL - The Johnson
Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor, return air
sensor, dirty filter indicator switch, and air p roving switch.
CPC BAS CONTROL - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes supply air sensor , return air sens or, dirty filter indicator switch
and air proving switch.
HONEYWELL BAS CONTROL - The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
• COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
• SMOKE DETECTORS - (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.
Factory installed smoke detectors in the return air,
may be subjected to freezing temperatures during
“off” times due to out side air infiltration. these smoke
detectors have an operational limit of 32°F to 131°F.
smoke detectors installed in areas that could be out
side those limitations will have to be moved to
prevent having false alarms.
• STAINLESS STEEL HEAT EXCHANGER - For
applications in corrosive environments, this option
2
provides a full stainless steel heat exchanger assembly.
• STAINLESS STEEL DRAIN PAN - An optional rust-proof
stainless steel drain pan is available to provide years of
trouble-free operation in corrosive environments.
• PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-ofphase condition.
• HIGH STATIC DRIVE - May include a belt, blower pulley,
motor pulley or a motor change to enhance blower
performance.
• LOW STATIC DRIVE - May include a belt, blower pulley,
motor pulley or a motor change when standard airflow is
not required. (WR300 & WR240 only)
• DIRTY FILTER SWITCH - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option or
field installed accessory.
• HINGED FILTER DOOR/”TOOL FREE” BLOWER AND ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.
Unitary Products Group9
262292-YTG-C-0707
NOTE: Knobs are shipped separately within the unit to
prevent shipping damage. These must be field
installed for tool free operation.
• HINGED/"TOOL FREE" BLOWER, BLOWER MOTOR, FILTER AND ELECTRIC ACCESS PANELS - This option
allows for complete hinged and tool free access to the unit's
blower, blower motor, filters and electrical panel sections.
FIELD-INSTALLED ACCESSORIES
• SINGLE INPUT ELECTRONIC ENTHALPY
ECONOMIZERS - Includes a slide-in / plug-in damper
assembly with fully modulating spring-return motor
actuator capable of introducing up to 100% outdoor air
with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
• MOTORIZED OUTDOOR AIR INT A KE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and must
be field-assembled before installing.
Power exhaust is not available as a field installed
option.
• ROOF CURBS - Fourteen-inch high roof curbs provide a
water-tight seal between the unit and the finished roof.
These full perimeter curbs meet the requirements of the
National Roofing Contractors Association (NRCA) and are
shipped knocked-down for field assembly.
They're designed to fit inside the base rails of the unit and
include both a wood nailing strip and duct hanger
supports.
• HIGH ALTITUDE NATURAL GAS - Burner orifices and
pilot orifices are provided for proper furnace operation at
altitudes up to 6,000 feet.
• PROPANE - Burner orifices, pilot orifices and gas valve
parts are provided to convert a natural gas furnace to
propane.
• HIGH ALTITUDE PROPANE - Burner orifices and pilot
orifices are provided for proper furnace operation at
altitudes up to 6,000 feet. This accessory supplements the
basic propane conversion kit.
• SIDE DUCT FLANGES - One-inch flanges replace the
supply and return air panels on the rear of the unit to
accommodate horizontal duct connections. These flanges
can also be used individually for bottom supply/horizontal
return or horizontal supply/bottom return. They cannot be
used on units with power exhaust.
• BAROMETRIC RELIEF DAMPER - This damper
accessory can be used to relieve internal building air
pressure on units with an economizer without power
exhaust. This accessory includes a rain hood, a bird
screen and a fully assembled damper. With bottom duct
connections, the damper should be mounted over the
opening in the return air panel. With horizontal ductwork,
the accessory should be mounted on the return air duct.
• ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.
• BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.
• FLUE EXHAUST EXTENSION KIT - In locations with
wind or weather conditions which may interfere with
proper exhausting of furnace combustion products, this kit
can be installed to prevent the flue exhaust from entering
nearby fresh air intakes.
• WOOD SKID - Allows unit to be handled with 90” forks.
SENSOR - Senses CO2 levels and automatically
• CO
2
overrides the economizer when levels rise above the
present limits.
• COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
• PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-ofphase condition.
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA
2. At a distance of 10 feet from the blower.
CFM
values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture
has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA
value or sound data in any other form than sound power level ratings.
1. Certified in accordance with the Unitary Large Equipment
certification program which is based on ARI Standard 340/
360.
2. EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power input in
watts, expressed in Btuh per watt (Btuh/watt).
First stage is 50% of total.
S.S.E. = Steady State Efficiency (80%) - output divided by input.
For units with VFD and electric or gas heat, the
speed of the indoor blower motor continues to
be controlled by duct static pressure via the
VAV control board.
If there are VAV boxes present in the duct system, the boxes must be driven to th e full-open
position using a customer-supplied power
source to assure adequate airflow across electric heating elements or gas heat exchanger
tubes.
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
*
Total
Cap.
(MBH)
2
Total
1
Input
(kW)
Sensible Capacity (MBH)
Return Dry Bulb (°F)
239228199171142114
238238205175145115
*
All Sensible Capacity
Unitary Products Group17