York Whole-House Fan Powered Humidifiers, Whole-House Bypass Humidifiers User Manual

The Automatic Humidifier Control is a precision instrument that can be used to determine the RH accurately in your home during the winter. If you would like to determine the relative humidity in your home, follow these steps:
1. Activate the furnace blower by setting your thermostat fan switch to the “On” position, or by setting your thermostat to a higher temperature.
Check the Humidifier Operation
(both automatic and manual modes). Set the knob to “Test/Reset” make sure that the water saddle valve is open and that there is electricity to the unit. The furnace blower motor must be operating for the humidifier to function. After the humidifier has operated for one minute and water is entering the unit and coming out at the drain, reset the humidistat to it’s original setting.
Change Humidifier Pad light
(both automatic and manual modes). If the Change Humidifier Pad light remains lit, your Humidifier Pad needs to be replaced. After changing the Humidifier Pad, turn the knob to “Test/Reset” until the Change Humidifier Pad light starts to blink. Note: Control must be powered (furnace on) to reset the Humidifier Pad Change indicator.
If the Change Humidifier Pad light is blinking, your unit is in Test mode. Do not leave in Test mode or humidifier will not operate. Turn the knob to it’s original setting for normal operation.
INSTALLER:
Please leave these
Operating Instructions with the homeowner.
AUTOMATIC
HUMIDIFIER CONTROL
OPERATING
INSTRUCTIONS
Manual Mode (Automatic Mode – see page 1)
Your Automatic Humidifier Control is installed in the cold air return. When installed in the manual mode it is important to anticipate a drop in outdoor temperature and reduce the setting accordingly to avoid excessive condensation. For example, with an outdoor temperature of 20˚ the correct setting will be 35% relative humidity. If the temperature is expected to fall to 0˚ that evening, then merely reduce the setting to 25% several hours prior to the temperature change.
The recommended settings on the humidistat are based on years of research (see table 3) for the average home. These settings represent a compromise between RH levels that would be most desirable for comfort reasons and humidity levels that are suitable for protection of your home and to avoid condensation on your windows. For example, a wintertime indoor RH of 50% may be considered ideal for comfort, but unfortunately, it probably would result in damage to your home. Observance of the recommended RH levels on your humidistat, therefore, is an important safeguard. Condensation of water on inside windows in the form of fogging or frost is usually an indication of too much relative humidity. This same condensation can take place in other areas in your home with the possibility of damage resulting.
Outside Temperature
+40˚F +30˚F +20˚F +10˚F
0˚F
-10˚F
-20˚F
Recommended RH
45% 40% 35% 30% 25% 20% 15%
10007640 1.08 Form 358011 Printed in U.S.A. B2204496A
(Figure B)
(Table 3) Outdoor– Indoor Relative Humidity
- 4 - - 5 -
©2008 Unitary Products Group
5005 York Drive, Norman, OK 73069
90-1055
YOUR HUMIDIFIER
Your Humidifier is controlled by the Automatic Humidifier Control. It offers two modes of operation. Automatic or Manual. No other humidification system is fully automatic when operating in the automatic mode, and computer equipped for your complete comfort and satisfaction.This system will benefit you in the following ways:
1. Automatically adjusts your home’s relative humidity
(RH) based on the outdoor temperature.
You always
receive the optimum amount of humidity.
2. Eliminates the need to manually adjust the control when
outdoor temperature changes – a common occurrence
with manual humidistats.
3. Precisely controls the relative humidity in your home,
and increases the time in which maximum comfort is
maintained.
Your home and its furnishings are always protected from the damaging effects of excess condensation or low humidity.
4. Eliminates the need to turn the dial setting to “Off” during the summer season.
Simple operation with
few adjustments.
OPERATING INSTRUCTIONS
Automatic Mode
(Manual Mode – see page 4)
Your Automatic Humidifier Control is installed in the cold
air return. During the first heating season, your Automatic Humidifier Control needs to be set initially to match your home’s condition. Please follow these steps when adjusting your control (refer to Figure A).
1. Turn the dial setting knob to “5”, which is within the normal range. During the next 24-48 hours, it may be necessary to adjust the dial for more or less humidity, depending on your personal comfort and home’s requirements. Refer to the “Operation Guide” (
Table 1
).
2. During the coldest portion of the first heating season, minor adjustments may be necessary. This is dependent upon your individual home construction; refer to the “Operation Guide” (
Table 1
).
The relative humidity in your home will now be accurately controlled to meet your needs and should not need further adjustment during future heating seasons. Make note of the dial setting in the event you temporarily move the knob when performing annual maintenance of the humidifier.
Additional Information
Your humidifier is a high precision system that will accurately maintain the relative humidity in your home. For every 1˚F change in outdoor temperature, the Automatic Humidifier will automatically adjust the indoor relative humidity (RH) by 1/2%. If you would like to determine the relative humidity in your home, follow these steps:
1. Determine the outdoor temperature.
2. Activate the furnace blower by setting your thermostat
to a higher temperature.
(Table 1) Operation Guide
Condition Solution
Condensation on windows. Reduce the setting on the control
dial by 1 increment.
Lack of humidity. Increase the setting on the control
dial by 1 increment.
Humidifier does not operate. Turn dial to “Test/Reset”. Make certain furnace (Solenoid does not “click” blower is operating and furnace is calling when control is moved to for heat. If unit still doesn’t operate, “Test/Reset” position.) consult a heating contractor.
Humidifier won’t shut off. Turn dial to “Off”. If unit continues to
operate, consult a heating contractor.
Test mode. System operation is checked by setting the
knob to “Test/Reset”. Make certain furnace blower is operating and furnace is calling for heat. Humidifier will operate for one minute.
3. Turn the control dial setting to the “Off” position. Then, slowly turn the dial clockwise until you hear the solenoid valve “click on”. Next, slowly turn the dial counterclockwise until you hear the solenoid valve “click off”. At this point, make note of the dial setting.
4. Locate your dial setting on Table 2. Follow the dial setting to the right until it intersects with the current outdoor temperature. This is the relative humidity in your home under existing conditions.
As an example, if the outdoor temperature is 20˚F and, following step 3, the humidifier turns off at “5” on the dial range, then the relative humidity in your home is 35%.
5. Return the thermostat and control to their original settings.
The Automatic Humidifier Control will accurately control
the humidity in your home to a maximum of 45% RH and a minimum of 10% RH. The values of outdoor temperature and dial settings may fall in between or outside of the listed values in Table 2. In these cases, you can only approximate your home’s actual indoor relative humidity.
(Table 2) % Relative Humidity Guide
Outdoor Temperature (˚F)
-10 0 10203040
1 101010152025
2 101015202530
3 101520253035
4 152025303540
520253035 40 45
6 25 3035404545
7 30 3540454545
Dial Setting
Relative Humidity (%)
(Figure A)
- 1 - - 2 - - 3 -
90-1054
Loading...