Due to continuous product improvement, specifications
are subject to change without notice.
Visit us on the web at www.york.com
Additional rating information can be found at
www.ahridirectory.org
246819-BTG-H-0208
DESCRIPTION
The 13 SEER series heat pumps are designed for use with a
variety of UPG evaporator sections to suit any application
need. A full line of matching Add-On Coils are available for
use with upflow, downflow or horizontal furnaces. Matching
Air Handlers are also available for upflow, downflow or horizontal installation to provide a complete system. Electric heat
may be installed in air handlers. All units are factory charged
to assure easy installation.
WARRANTY
Single Phase Units:
5-year limited parts warranty.
5-year limited compressor warranty.
Three Phase Units:
1-year limited parts warranty.
5-year limited compressor warranty.
FEATURES
• DURABLE CONSTRUCTION - The outdoor unit is constructed of pre-painted steel that offers tough protection
against corrosion and resists fading when exposed to sunlight. Drain holes are incorporated into the base pan to permit free drainage of moisture.
• QUALITY COILS - The coil is constructed of enhanced
copper tube and aluminum fins.
• COIL PROTECTION - Coils are protected from damage by
a polymer mesh applied between the coil face, and a PVC
coated steel coil guard.
• PROTECTED COMPRESSOR - The hermetic compressor
is internally protected against high pressure and temperature by the simultaneous operation of a high pressure relief
valve and temperature sensors which stop the compressor
if operating temperatures go too high. Both protectors
reset automatically. A discharge line solid core filter drier
further protects the compressor.
• Complete System Control – These heat pumps utilize
the unique microprocessor defrost control system to provide optimal comfort and to monitor the overall system for
reliable operation. The defrost control system continuously
monitors the space environment to maintain optimum efficiency. It initiates defrost only when necessary to further
reduce heating costs and improve reliability. In the event
improper operating conditions occur, the control will automatically shut the system down to extend the life of the
heat pump. Rapid cycling is prevented by use of an internal anti-recycle timer.
• LOW OPERATING SOUND LEVEL - The compressor is
mounted on rubber isolators to reduce operating sounds.
The slow moving condenser fan keeps air turbulence and
sound to a low level.
• EASY ACCESS - Removable panel affords accessibility to
the electrical box.
• FULLY CHARGED AND FACTORY WIRED - to simply
installation and reduce labor costs. Only power supply and
control wiring and refrigerant lines must be connected. All
models are sweat connect with reusable service valves.
• Factory tested - to verify system operation and control
functioning before shipment.
• U.L. and C.U.L. listed - approved for outdoor application.
Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
246819-BTG-H-0208
Physical and Electrical Data - 1 Phase
MODEL
Unit Supply Voltage208-230V, 1φ, 60Hz
Normal Voltage Range
Minimum Circuit Ampacity9.915.016.919.825.032.737.8
Max. Overcurrent Device Amps
Min. Overcurrent Device Amps
Compressor Type
Compressor
Amps
Crankcase HeaterYesYesYesYesYesNoNo
Fan Motor Amps Rated Load0.51.51.51.51.51.51.5
Fan Diameter Inches22222222222424
Fan Motor
Coil
Liquid Line Set OD (Field Installed)3/83/83/83/83/83/83/8
Vapor Line Set OD (Field Installed)3/43/47/87/87/87/81-1/8
Unit Charge (Lbs. - Oz.)
Charge Per Foot, Oz.0.680.680.700.700.700.700.76
Operating Weight Lbs.172184196208208250294
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. All scrolls listed with a superscript “D” are Danfoss scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.
5. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15
feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
Rated HP1/151/41/41/41/41/41/4
Nominal RPM850850850850850850850
Nominal CFM2,0003,2503,4503,5003,5003,4003,500
Face Area Sq. Ft.15.7218.3420.9623.5823.5824.0027.00
Rows Deep1111122
Fin / Inches22222222221818
Fan Motor AmpsRated Load1.51.51.51.51.50.70.70.70.70.7
Fan Diameter Inches22222224242222222424
Fan Motor
Coil
Liquid Line Set OD (Field Installed)3/83/83/83/83/83/83/83/83/83/8
Vapor Line Set OD (Field Installed)7/87/87/87/81-1/87/87/87/87/81-1/8
Unit Charge (Lbs. - Oz.)
Charge Per Foot, Oz.0.700.700.700.700.760.700.700.700.700.78
Operating Weight Lbs.196208208250294196208208250294
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than
15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value. If line exceeds 25
feet, you may refer to publications software 036-68001-001 for proper line sizing.
Rated HP1/41/41/41/41/41/41/41/41/41/4
Nominal RPM850850850850850850850850850850
Nominal CFM3450350035003400350034503500350034003500
Face Area Sq. Ft.20.9623.5823.5824.0027.0020.9623.5823.5824.0027.00
Rows Deep1112211122
Fin / Inches22222218182222221818
1. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of inter-connecting line tubing.
2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210/240.
Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power
input in watt-hours during the same period.
F*FV06024–180054.039.713.2511.00
AHP/SHP6024–180055.039.713.0011.00
F*FV06024–180053.539.313.2511.00
AHP/SHP6024–180054.539.313.0011.00
COOLING
NET MBH
SEEREER
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
— = Not Applicable.
Go towww.ari.org/aridirectory for the latest additional mat ches.
8Unitary Products Group
COOLING CAPACITY - Upflow, Downflow, and Horizontal Furnaces and Coils
FURNACE**
UNIT MODEL
EABD-F018S
EABD-F024S
EABD-F030S
EABD-(T,W)030S
EABD-F036S
EABD-(T,W)036S
EABD-F042S
EABD-(T,W)042S
EABD-F048S
EABD-(T,W)048S
EABD-F060S
EABD-(T,W)060S
1. Requires a 2FD06700224 Blower Time Delay unless a standard furnace is equipped with one.
** Refer to Quick Selection Chart for specific furnace match-up.