York TCGD24S41S1, TCGD18S41S1H, TCGD30S41S1H, TCGD30S41S1, TCGD36S41S1H Technical Manual

...
Page 1
A
V A
w
TECHNICAL GUIDE
SPLIT-SYSTEM
IR CONDITIONERS 13 SEER – R-410A MODELS:
TCGD18 THRU 60 (1.5 THRU 5 NOMINAL TONS, 1 PHASE)
LISTED
Due to continuous product improvement, specifications are subject to change without notice.
isit us on the web at www.york.com dditional rating information can be found at
ww.ahridirectory.org
ISO 9001
Certified Quality
Management System
359315-YTG-B-0408
DESCRIPTION
The 13 SEER Series condensing unit is the outdoor part of a versatile system of air conditioning. It is designed to be cus­tom-matched with one of UPG’s complete line of evaporator sections, with each serving a specific function. Matching Air Handlers are available for upflow, downflow, or horizontal applications to provide a complete system. Electric Heaters are available, if required. Add-on coils are available for use with upflow, downflow, or horizontal furnaces and air han­dlers.
WARRANTY
Single Phase Units:
5-year limited parts warranty. 5-year limited compressor warranty.
FEATURES
QUALITY CONDENSER COILS - The coil is constructed of aluminum microchannel tubing and enhanced aluminum fins for increased efficiency and corrosion protection.
PROTECTED COMPRESSOR - The compressor is inter­nally protected against high pressure, temperature, and externally by a factory installed high pressure switch. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which pro­tects the compressor if undesirable operating conditions occur. A liquid line filter-drier further protects the compres­sor.
DURABLE FINISH - The cabinet is made of pre-painted steel. The pre-treated galvanized steel provides a better paint to steel bond, which resists corrosion and rust creep. Special primer formulas and matted-textured finish insure less fading when exposed to sunlight.
LOWER INSTALLED COST - Installation time and costs are reduced by easy power and control wiring connec­tions. Available in sweat connect models only. The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping. The small base dimen­sion means less space is required on the ground or roof.
TOP DISCHARGE - The warm air from the top mounted fan is blown up away from the structure and any landscap­ing. This allows compact location on multi-unit applica­tions.
LOW OPERATING SOUND LEVEL - The upward air flow carries the normal operating noise away from the living area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil muffle the normal fan motor and compressor operating sounds.
LOW MAINTENANCE - Long life permanently lubricated motor-bearings need no annual servicing.
EASY SERVICE ACCESS - Fully exposed refrigerant con­nections, and a single panel covering the electrical con­trols make for easy servicing of the unit.
SECURED SERVICE VALVES - Secured re-usable ser- vice valves are provided on both the liquid and vapor sweat connections for ease of evacuating and charging.
U.L. and C.U.L. listed - approved for outdoor application.
Certified in accordance with the Unitary Small Equipment cer­tification program, which is based on ARI Standard 210/240.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
Page 2
359315-YTG-B-0408
Physical and Electrical Data
MODEL
TCGD18
S41S1(H)
TCGD24
S41S1(H)
TCGD30
S41S1(H)
TCGD36
S41S1(H)
TCGD42
S41S1(H)
TCGD48
S41S1(H)
TCGD60
S41S1
Unit Supply Voltage 208-230V, 1φ, 60Hz Normal Voltage Range
1
187 to 252
Minimum Circuit Ampacity 10.0 12.4 14.7 17.9 21.5 21.1 34.3 Max. Overcurrent Device Amps Min. Overcurrent Device Amps
2
3
15 20 25 30 35 35 60 15 15 15 20 25 25 35
Compressor Type Rotary Recip Recip Recip Recip Recip Scroll Compressor Amps
Rated Load 7.6 9.3 10.6 13.1 16.0 15.7 26.2
Locked Rotor 40.0 43.0 54.0 74 84 84 150 Crankcase Heater No No No No No No No Fan Motor Amps Rated Load 0.5 0.8 1.4 1.5 1.5 1.5 1.5 Fan Diameter Inches 17.5 17.5 17.5 22 22 22 24
Rated HP 1/12 1/8 1/4 1/4 1/4 1/4 1/4 Fan Motor
Nominal RPM 1100 1075 1100 850 850 850 850
Nominal CFM 1400 1950 2050 3200 2950 2950 3600
Face Area Sq. Ft. 9.60 9.60 9.60 13.07 14.16 14.16 18.68 Coil
Rows Deep 1 1 1 1 1 1 1
Fin / Inches 23 23 23 23 23 23 23 Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8 3/8 3/8 3/8 Vapor Line Set OD (Field Installed) 5/8 3/4 3/4 3/4 7/8 7/8 7/8
Unit Charge (Lbs. - Oz.)
4
3 - 3 3 - 13 3 - 14 4 - 9 4 - 5 4 - 9 5 - 6
Charge Per Foot, Oz. 0.58 0.62 0.62 0.62 0.67 0.67 0.67 Operating Weight Lbs. 97 129 131 145 173 173 195
Models with “H” on the end of the model number have a factory installed start kits.
1.Rated in accordance with ARI Standard 110, utilization range “A”.
2.Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3.Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
C
A
2 Johnson Controls Unitary Products
All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.
Unit
Model
18 28
Dimensions
(Inches)
1
A
B C Liquid Vapor
23-1/2 23-1/2 24 28 23-1/2 23-1/2 30 28 23-1/2 23-1/2 36 28 29 29 42 30 29 29
60 32 33-5/8 33-5/8
B
1.Including Fan Guard.
Refrigerant Connection
Service Valve Size
3/4”
3/8”
7/8”48 30 29 29
Page 3
359315-YTG-B-0408
Additional R-410A Charge / Orifice Size for Various Matched Systems
Outdoor Unit
Required Orifice or TXV Factory Charge, lbs-oz 3 - 3 3 - 13 3 - 14 4 - 9 4 - 5 4 - 9 5 - 6
TCGD18
S41S1(H)
1,2
0.048 / 902 0.055 / 902 0.061 / 907 0.065 / 903 0.075 / 903 0.073 / 904 0.087 / 905
TCGD24
S41S1(H)
TCGD30
S41S1(H)
TCGD36
S41S1(H)
TCGD42
S41S1(H)
TCGD48
S41S1(H)
TCGD60
S41S1
Indoor Coil
FC/MC/PC/UC18A3X
FC/MC/PC/UC18B3X
FC/MC/PC32A3X
FC/MC/PC35B3X
FC/MC/PC35C3X
FC/MC/PC/UC36A3X
FC/MC/PC/UC36B3X
FC/MC/PC/UC36C3X
FC/MC/PC37A3X
FC/MC/PC43B3X
FC/MC/PC43C3X
FC/MC/PC/UC48C3X
FC/MC/PC/UC48D3X
FC/MC/PC/UC60D3X
FC/MC62D3X
HC18A3X
HC30A3X
HC36B3X
HC42C3X
HC60D3X
AHP18B3X
AHP30B3X
AHP36C3X
AHP42C3X
3,4
Additional Charge, Oz
48 + 0 ––––––
902 + 0 ––––––
48 + 0 ––––––
902 + 0 ––––––
–55 + 4 61 + 0 –––– – 902 + 4 907 + 0 –––– –55 + 4 61 + 0 –––– – 902 + 4 907 + 0 –––– –55 + 4 61 + 0 –––– – 902 + 4 907 + 0 –––– –55 + 0 ––––– – 902 + 0 ––––– –55 + 0 ––––– – 902 + 0 ––––– –55 + 0 ––––– – 902 + 0 ––––– – 55 + 4 61 + 2 65 + 0 – – 902 + 4 907 + 2 903 + 0 – – 55 + 4 61 + 2 65 + 0 75 + 0 – – 902 + 4 907 + 2 903 + 0 903 + 0 – – 55 + 4 61 + 2 65 + 0 75 + 0 – – 902 + 4 907 + 2 903 + 0 903 + 0 – – 65 + 8 75 + 2 73 + 4 – – 903 + 8 903 + 2 904 + 4 – – 65 + 8 75 + 2 73 + 4 – – 903 + 8 903 + 2 904 + 4 – –––––73 + 0 87 + 0 –––––904 + 0 905 + 0 ––––––87 + 4 ––––––905 + 4
48 + 0 ––––––
902 + 0 ––––––
–55 + 0 ––––– – 902 + 0 ––––– –55 + 4 61 + 0 –––– – 902 + 4 907 + 0 –––– – 55 + 4 61 + 2 65 + 0 75 + 0 – – 902 + 4 907 + 2 903 + 0 903 + 0 – ––––––87 + 0 ––––––905 + 0
48 + 0 ––––––
902 + 0 ––––––
–55 + 4 61 + 0 –––– – 902 + 4 907 + 0 –––– – 61 + 2 65 + 0 – – 907 + 2 903 + 0 – – 65 + 0 75 + 0 – – 903 + 0 903 + 0
Johnson Controls Unitary Products 3
Page 4
359315-YTG-B-0408
Additional R-410A Charge / Orifice Size for Various Matched Systems (Continued)
Outdoor Unit
Required Orifice or TXV
TCGD18
S41S1(H)
1,2
0.048 / 902 0.055 / 902 0.061 / 907 0.065 / 903 0.075 / 903 0.073 / 904 0.087 / 905
Factory Charge, lbs-oz 3 - 3 3 - 13 3 - 14 4 - 9 4 - 5 4 - 9 5 - 6
TCGD24
S41S1(H)
TCGD30
S41S1(H)
TCGD36
S41S1(H)
TCGD42
S41S1(H)
TCGD48
S41S1(H)
TCGD60
S41S1
Indoor Coil
3,4
AHP/SHP60D3X
AV36C3X
AV/SV48D3X
AV60D3X
F4FP024
F4FP036
F4FP040
F5FP048
F5FP060
F4FV060
See Caution below
See Caution below
See Caution below
See Caution below
See Caution below
See Caution below
–––––73 + 0 87 + 0 –––––904 + 0 905 + 0 55 + 4 61 + 2 65 + 0 – – 902 + 4 907 + 2 903 + 0 – –––––73 + 0 – –––––904 + 0 – ––––––87 + 0 ––––––905 + 0
48 + 0 ––––––
902 + 0 ––––––
–55 + 0 ––––– – 902 + 0 ––––– ––61 + 0 –––– – 907 + 0 –––– – 65 + 8 75 + 2 73 + 4 – – 903 + 8 903 + 2 904 + 4 – –––––73 + 0 87 + 0 –––––904 + 0 905 + 0 –––––73 + 0 87 + 0 –––––904 + 0 905 + 0
Additional Charge, Oz
FOOTNOTES:
1.For applications requiring a TXV use 1TVM900 series kit.
2.Approved orifice shipped with outdoor unit.
3.Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
4.PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of inter­connecting line tubing.
2. Verify the TXV or orifice and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical Data Table.
4. For TXV match charge weight needs to be weighed in for specififc coil match and lineset length.
5. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator + adder for line set.
Models 12-48 require start kits for TXV matches. Models with “H” on the end of the model number have factory installed start kits. For models without an “H” refer to tech guide for kit number reference.
F*FP Air Handlers come with a factory installed R-22 TXV which MUST BE CHANGED OUT to R-410A TXV or an orifice for proper opera­tion. If the TXV is not changed out system damage will occur.
4 Johnson Controls Unitary Products
Page 5
359315-YTG-B-0408
COOLING CAPACITY - With Air Handler Coils
UNIT
MODEL
TCGD18S41S1(H) MA08B 17 FC/MC18B 600 17.5 12.9 13.00 11.00
TCGD24S41S1(H)
TCGD30S41S1(H)
TCGD36S41S1(H)
TCGD42S41S1(H)
TCGD48S41S1(H)
TCGD60S41S1
TCGD18S41S1(H) MV12B 17 FC/MC18B 600 17.5 13.3 14.00 12.50
TCGD24S41S1(H)
TCGD30S41S1(H)
TCGD36S41S1(H)
TCGD42S41S1(H)
TCGD48S41S1(H)
TCGD60S41S1
TCGD24S41S1(H) AV36 21 – 765 24.0 17.4 14.00 12.00 TCGD30S41S1(H) AV36 21 – 1015 30.0 21.8 14.00 12.00 TCGD36S41S1(H) AV36 21 – 1270 35.0 25.2 14.00 12.00
TCGD48S41S1(H)
TCGD60S41S1
For Notes See Page 6.
AIR HANDLER
MODEL W
MA08B 17 FC/MC36B 800 24.0 16.7 13.00 11.00 MA08B 17 FC/MC35B 800 24.0 16.7 13.00 11.00 MA08B 17 FC/MC43B 800 24.0 16.7 13.00 11.00 MA12B 17 FC/MC35B 1000 29.0 21.0 13.00 11.00 MA12B 17 FC/MC43B 1000 29.0 21.0 13.00 11.00 MA12B 17 FC/MC43B 1200 35.0 24.8 13.00 11.00 MA14D 24 FC/MC48D 1200 35.0 24.8 13.00 11.00 MA16C 21 FC/MC43C 1400 42.0 29.2 13.00 11.00 MA14D 24 FC/MC48D 1400 42.0 29.2 13.00 11.00 MA16C 21 FC/MC48C 1400 42.0 29.2 13.00 11.00 MA16C 21 FC/MC48C 1600 48.0 34.4 13.00 11.00 MA20D 24 FC/MC48D 1600 48.0 34.4 13.00 11.00 MA16C 21 FC60C 1600 48.0 34.4 13.00 11.00 MA20D 24 FC/MC60D 1600 48.0 34.4 13.00 11.00 MA20D 24 FC/MC60D 1800 57.0 38.5 13.00 11.00 MA20D 24 FC/MC62D 1800 57.0 38.5 13.00 11.00
13 SEER AC WITH MV - VARIABLE SPEED
MV12B 17 FC/MC36B 800 24.0 17.4 14.00 12.00 MV12B 17 FC/MC35B 800 24.0 17.4 14.00 12.00 MV12B 17 FC/MC43B 800 24.0 17.3 14.00 12.00 MV12B 17 FC/MC35B 1000 29.0 21.6 14.00 12.00 MV16C 21 FC/MC35C 1000 30.0 21.6 14.00 12.00 MV12B 17 FC/MC43B 1000 29.0 21.6 14.00 12.00 MV16C 21 FC/MC43C 1000 30.0 21.6 14.00 12.00 MV16C 21 FC/MC43C 1200 36.0 25.4 14.00 12.00 MV16C 21 FC/MC48C 1200 36.0 25.4 14.00 12.00 MV20D 24 FC/MC48D 1200 36.0 25.6 14.00 12.00 MV12D 24 FC/MC48D 1135 35.0 25.4 14.00 12.00 MV16C 21 FC/MC43C 1400 42.0 30.0 13.50 12.00 MV16C 21 FC/MC48C 1400 42.0 30.0 13.50 12.00 MV20D 24 FC/MC48D 1400 42.0 30.0 14.00 12.00 MV16C 21 FC/MC48C 1600 48.0 35.0 13.50 12.00 MV20D 24 FC/MC48D 1600 48.0 35.0 13.50 12.00 MV20D 24 FC/MC60D 1600 48.0 35.0 13.50 12.00 MV20D 24 FC/MC60D 1800 57.0 38.5 13.00 11.00 MV20D 24 FC/MC62D 1800 57.0 38.5 13.00 11.00
13 SEER AC WITH AV / SV / F*FV - VARIABLE SPEED
AV/SV48 24 1610 48.0 35.0 13.50 12.00 AV/SV60 24 1655 48.0 35.0 13.50 12.00 F4FV060 24 1600 48.0 34.4 14.00 11.50 AV/SV60 24 1765 58.0 39.0 13.50 11.00 F4FV060 24 1780 57.0 38.5 13.50 11.00
COIL
1
MODEL
13 SEER AC WITH MA
RATED
CFM
TOTAL SENS.
COOLING
NET MBH
SEER EER
Johnson Controls Unitary Products 5
Page 6
359315-YTG-B-0408
COOLING CAPACITY - With Air Handler Coils (Continued)
UNIT
MODEL
AIR HANDLER
MODEL W
COIL
MODEL
1
RATED
CFM
TOTAL SENS.
13 SEER AC WITH AHP / SHP / F*FP
TCGD18S41S1(H)
TCGD24S41S1(H)
AHP18 17 – 650 17.5 12.9 13.00 11.00
F4FP024 18 600 17.5 12.9 13.00 11.00
AHP30 17 – 795 24.0 16.8 13.00 11.00
F4FP036 21.5 800 24.0 16.7 13.00 11.00
AHP30 17 – 1015 29.0 21.0 13.00 11.00
TCGD30S41S1(H)
AHP36 21 – 1040 29.0 21.0 13.00 11.00
F4FP040 18 1050 29.0 21.0 13.00 11.00
AHP36 21 – 1235 35.0 24.8 13.00 11.00
TCGD36S41S1(H)
AHP42 21 – 1255 35.0 24.8 13.00 11.00
F5FP048 24 1235 35.0 24.8 13.00 11.00
TCGD42S41S1(H)
AHP42 21 – 1485 41.0 29.2 13.00 11.00
F5FP048 24 1455 41.0 29.2 13.00 11.00
AHP/SHP48 24 1675 48.0 34.4 13.00 11.00
TCGD48S41S1(H)
AHP/SHP60 24 1600 48.0 35.0 13.50 11.00
F5FP048 24 1600 48.0 34.4 13.00 11.00 F5FP060 24 1600 48.0 34.4 13.00 11.00
TCGD60S41S1
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210. Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow. EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.
AHP/SHP60 24 1850 57.0 38.5 13.00 11.00
F5FP060 24 1900 57.0 38.5 13.00 11.00
COOLING
NET MBH
SEER EER
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
— = Not applicable.
6 Johnson Controls Unitary Products
Page 7
COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils
FURNACE**
UNIT MODEL
TCGD18S41S1(H)
TCGD24S41S1(H)
TCGD30S41S1(H)
TCGD36S41S1(H)
TCGD42S41S1(H)
TCGD48S41S1(H)
TCGD60S41S1
1. Requires a 2FD06700224 Blower Time Delay unless a standard furnace is equipped with one. ** Refer to Quick Selection Chart for specific furnace match-up.
CFM RANGE
(Min.-max.)
450 - 750 14,17 FC/MC/PC18 600 17.5 12.9 13.00 11.00 450 - 750 14 HC18 600 17.5 12.9 13.00 11.00
450 - 750 14,17 UC18 600 17.5 12.9 13.00 11.00 600 - 1000 14 FC/MC/PC32 800 24.0 16.7 13.00 11.00 600 - 1000 17,21 FC/MC/PC35 800 24.0 16.7 13.00 11.00 600 - 1000 14,17,21 FC/MC/PC36 800 24.0 16.7 13.00 11.00 600 - 1000 14 FC/MC/PC37 800 24.0 16.7 13.00 11.00 600 - 1000 17,21 FC/MC/PC43 800 24.0 16.7 13.00 11.00 600 - 1000 14 HC30 800 24.0 16.7 13.00 11.00 600 - 1000 17 HC36 800 24.0 16.7 13.00 11.00 600 - 1000 21 HC42 800 24.0 16.7 13.00 11.00 600 - 1000 14,17,21 UC36 800 24.0 16.7 13.00 11.00 800 - 1200 14 FC/MC/PC32 1000 29.0 21.0 13.00 11.00 800 - 1200 17,21 FC/MC/PC35 1000 29.0 21.0 13.00 11.00 800 - 1200 14 FC/MC/PC37 1000 29.0 21.0 13.00 11.00 800 - 1200 17,21 FC/MC/PC43 1000 29.0 21.0 13.00 11.00 800 - 1200 17 HC36 1000 29.0 21.0 13.00 11.00 800 - 1200 21 HC42 1000 29.0 21.0 13.00 11.00
1000 - 1400 14 FC/MC/PC37 1200 35.0 24.8 13.00 11.00 1000 - 1400 17,21 FC/MC/PC43 1200 35.0 24.8 13.00 11.00 1000 - 1400 21,24 FC/MC/PC48 1200 35.0 24.8 13.00 11.00 1000 - 1400 21 HC42 1200 35.0 24.8 13.00 11.00 1000 - 1400 21,24 UC48 1200 35.0 24.8 13.00 11.00 1200 - 1600 17,21 FC/MC/PC43 1400 42.0 29.2 13.00 11.00 1200 - 1600 21,24 FC/MC/PC48 1400 42.0 29.2 13.00 11.00 1200 - 1600 21 HC42 1400 42.0 29.2 13.00 11.00 1200 - 1600 21,24 UC48 1400 42.0 29.2 13.00 11.00 1400 - 1800 21,24 FC/MC/PC48 1600 48.0 34.4 13.00 11.00 1400 - 1800 21,24 FC/MC/PC60 1600 48.0 34.4 13.00 11.00 1400 - 1800 24 HC60 1600 48.0 34.4 13.00 11.00 1400 - 1800 21,24 UC48 1600 48.0 34.4 13.00 11.00 1400 - 1800 21,24 UC60 1600 48.0 34.4 13.00 11.00 1600 - 2000 21,24 FC/MC/PC60 1800 57.0 38.5 13.00 11.00 1600 - 2000 24 FC/MC62 1800 57.0 38.5 13.00 11.00 1600 - 2000 24 HC60 1800 57.0 38.5 13.00 11.00 1600 - 2000 21,24 UC60 1800 57.0 38.5 13.00 11.00
W
COIL
MODEL
RATED
CFM
TOTAL SENS.
COOLING
NET MBH
359315-YTG-B-0408
1
SEER
EER
Johnson Controls Unitary Products 7
Page 8
359315-YTG-B-0408
COOLING CAPACITY - With Variable Speed Furnaces
UNIT MODEL
TCGD18S41S1(H)
TCGD24S41S1(H)
TCGD30S41S1(H)
TCGD36S41S1(H)
For Notes See Page 9.
VARIABLE SPEED FURNACE MODEL
13 SEER AC WITH VARIABLE SPEED FURNACES
PV8*A12 FC/MC/PC18A 14 600 17.5 13.4 14.00 12.50 PV9*A12 FC/MC/PC18A 14 625 17.5 13.3 14.00 12.50
P(C,V)9*B12 FC/MC/PC18B 17 620 17.5 13.3 14.00 12.50
PV8*A12 HC18 14 600 17.5 13.4 14.00 12.50 PV9*A12 HC18 14 625 17.5 13.3 14.00 12.50 PV8*A12 FC/MC/PC32A 14 750 24.0 17.3 14.00 12.00 PV9*A12 FC/MC/PC32A 14 800 24.0 17.1 13.50 12.00
P(C,V)9*B12 FC/MC/PC35B 17 820 24.0 17.2 14.00 12.00
PV8*A12 FC/MC/PC36A 14 750 24.0 17.3 14.00 12.00 PV9*A12 FC/MC/PC36A 14 800 24.0 17.2 14.00 12.00
P(C,V)9*B12 FC/MC/PC36B 17 820 24.0 17.2 14.00 12.00
PV8*A12 FC/MC/PC37A 14 750 24.0 17.2 14.00 12.00 PV9*A12 FC/MC/PC37A 14 800 24.0 17.2 14.00 12.00
P(C,V)9*B12 FC/MC/PC43B 17 820 24.0 17.2 14.00 12.00
PV8*A12 HC30 14 750 24.0 17.3 14.00 12.00 PV9*A12 HC30 14 800 24.0 17.1 13.50 12.00
P(C,V)9*B12 HC36 17 820 24.0 17.2 14.00 12.00
PV8*A12 FC/MC/PC32A 14 975 29.0 21.6 14.00 12.00 PV9*A12 FC/MC/PC32A 14 1000 29.0 21.4 13.50 12.00 PV8*B16 FC/MC/PC35B 17 1050 29.0 21.6 14.00 12.00
P(C,V)9*B12 FC/MC/PC35B 17 975 29.0 21.6 14.00 12.00
PV8*C16 FC/MC/PC35C 21 1000 30.0 21.8 14.00 12.00
PV8*C20 FC/MC/PC35C 21 1120 29.0 21.4 13.50 11.00 P(C,V)9*C16 FC/MC/PC35C 21 1010 29.0 21.6 14.00 12.00 P(C,V)9*C20 FC/MC/PC35C 21 1045 29.0 21.6 14.00 12.00
PV8*A12 FC/MC/PC37A 14 975 29.0 21.6 14.00 12.00 PV9*A12 FC/MC/PC37A 14 1000 30.0 21.4 13.50 12.00 PV8*B16 FC/MC/PC43B 17 1050 29.0 21.6 14.00 12.00
P(C,V)9*B12 FC/MC/PC43B 17 975 29.0 21.6 14.00 12.00
PV8*C16 FC/MC/PC43C 21 1000 30.0 21.8 14.00 12.00
PV8*C20 FC/MC/PC43C 21 1120 29.0 21.4 13.50 11.00 P(C,V)9*C16 FC/MC/PC43C 21 1010 29.0 21.6 14.00 12.00 P(C,V)9*C20 FC/MC/PC43C 21 1045 29.0 21.6 14.00 12.00
PV8*B16 HC36 17 1050 29.0 21.6 14.00 12.00
P(C,V)9*B12 HC36 17 975 29.0 21.6 14.00 12.00
PV8*C16 HC42 21 1000 30.0 21.8 14.00 12.00
PV8*C20 HC42 21 1120 29.0 21.4 13.50 11.00 P(C,V)9*C16 HC42 21 1010 29.0 21.6 14.00 12.00 P(C,V)9*C20 HC42 21 1045 29.0 21.6 14.00 12.00
PV8*A12 FC/MC/PC37A 14 1185 35.0 25.0 13.00 12.00 PV9*A12 FC/MC/PC37A 14 1200 35.0 25.0 13.00 11.00 PV8*B16 FC/MC/PC43B 17 1200 35.0 25.2 13.50 12.00
P(C,V)9*B12 FC/MC/PC43B 17 1185 35.0 25.2 13.50 12.00
PV8*C16 FC/MC/PC43C 21 1200 35.0 25.4 14.00 12.00
PV8*C20 FC/MC/PC43C 21 1200 35.0 25.2 13.50 12.00 P(C,V)9*C16 FC/MC/PC43C 21 1175 35.0 25.2 13.50 12.00 P(C,V)9*C20 FC/MC/PC43C 21 1195 35.0 25.2 13.50 12.00
PV8*C16 FC/MC/PC48C 21 1200 36.0 25.4 14.00 12.00
COIL
MODEL
1
COOLING
W
RATED
CFM
Net MBH
TOTAL SENS.
2
SEER EER
8 Johnson Controls Unitary Products
Page 9
COOLING CAP ACITY - With Variable Speed Furnaces (Continued)
UNIT MODEL
TCGD36S41S1(H)
TCGD42S41S1(H)
TCGD48S41S1(H)
TCGD60S41S1
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. Variable speed furnaces have B.O.D (Blower on Delay) standard.
VARIABLE SPEED FURNACE MODEL
13 SEER AC WITH VARIABLE SPEED FURNACES
PV8*C20 FC/MC/PC48C 21 1200 35.0 25.2 13.50 12.00 P(C,V)9*C16 FC/MC/PC48C 21 1175 35.0 25.4 14.00 12.00 P(C,V)9*C20 FC/MC/PC48C 21 1195 35.0 25.2 14.00 12.00 P(C,V)9*D20 FC/MC/PC48D 24 1220 35.0 25.4 14.00 12.00
PV8*C16 HC42 21 1200 36.0 25.4 14.00 12.00
PV8*C20 HC42 21 1200 35.0 25.2 13.50 12.00 P(C,V)9*C16 HC42 21 1175 35.0 25.2 14.00 12.00 P(C,V)9*C20 HC42 21 1195 35.0 25.2 13.50 12.00
PV8*B16 FC/MC/PC43B 17 1400 42.0 29.6 13.00 12.00
PV8*C20 FC/MC/PC43C 21 1400 42.0 29.8 13.50 12.00 P(C,V)9*C16 FC/MC/PC43C 21 1415 42.0 29.6 13.00 11.00 P(C,V)9*C20 FC/MC/PC43C 21 1370 42.0 29.8 13.50 12.00
PV8*C16 FC/MC/PC48C 21 1400 42.0 29.6 13.50 12.00
PV8*C20 FC/MC/PC48C 21 1400 42.0 29.8 13.50 12.00 P(C,V)9*C16 FC/MC/PC48C 21 1415 42.0 29.6 13.00 11.00 P(C,V)9*C20 FC/MC/PC48C 21 1370 42.0 29.8 13.50 12.00 P(C,V)9*D20 FC/MC/PC48D 24 1360 42.0 30.0 13.50 12.00
PV8*C16 HC42 21 1400 42.0 29.6 13.00 12.00
PV8*C20 HC42 21 1400 42.0 29.8 13.50 12.00 P(C,V)9*C16 HC42 21 1415 42.0 29.6 13.00 11.00 P(C,V)9*C20 HC42 21 1370 42.0 29.8 13.50 12.00
PV8*C16 FC/MC/PC48C 21 1500 47.0 34.6 13.00 11.00
PV8*C20 FC/MC/PC48C 21 1610 48.0 34.6 13.00 11.00 P(C,V)9*C16 FC/MC/PC48C 21 1600 48.0 34.4 13.00 11.00 P(C,V)9*C20 FC/MC/PC48C 21 1580 48.0 34.6 13.00 11.00 P(C,V)9*D20 FC/MC/PC48D 24 1560 48.0 35.0 13.00 12.00
PV8*C16 FC/PC60C 21 1500 48.0 34.6 13.00 11.00
PV8*C20 FC/PC60C 21 1610 48.0 34.6 13.00 11.00 P(C,V)9*C16 FC/PC60C 21 1600 48.0 34.4 13.00 11.00 P(C,V)9*C20 FC/PC60C 21 1580 48.0 34.6 13.00 11.00 P(C,V)9*D20 FC/MC/PC60D 24 1560 48.0 35.0 13.00 12.00
PV8*C20 FC/PC60C 21 1730 57.0 38.0 13.00 11.00 P(C,V)9*C20 FC/PC60C 21 1650 56.0 39.0 13.00 11.00 P(C,V)9*D20 FC/MC/PC60D 24 1620 56.0 39.0 13.00 11.00
PV8*C20 FC/MC62D 21 1730 57.0 38.0 13.00 11.00 P(C,V)9*C20 FC/MC62D 21 1650 56.0 39.0 13.00 11.00 P(C,V)9*D20 FC/MC62D 24 1620 56.0 39.0 13.00 11.00
COIL
MODEL
1
W
RATED
CFM
Net MBH
TOTAL SENS.
2
359315-YTG-B-0408
COOLING
SEER EER
Johnson Controls Unitary Products 9
Page 10
359315-YTG-B-0408
ACCESSORIES
Refer to Price Manual for specific model numbers. HARD START KIT - Required when using TXV indoor coil.
Also, provides increased starting torque for areas with low voltage.
Model Source 1 Kit numbers
18 S1-2SA06708606 24 S1-2SA06721706 30 S1-2SA06705906 36 S1-2SA06708906 42 S1-2SA06708806 48 S1-2SA06708806 60 S1-2SA06707906
OFF CYCLE TIMER DELAY - Provides a 5-minute off cycle to prevent rapid recycling of the compressor.
TYPICAL INSTALLATION
MINIMUM 18” SERVICE
60” OVERHEAD CLEARANCE
ACCESS CLEARANCE ON ONE SIDE
ROOM THERMOSTATS - A wide selection of compatible thermosets are available to provide optimum performance and features for any installation.
1H/1C, manual changeover electronic non-programmable thermostat.
1H/1C, auto/manual changeover, electronic programmable, deluxe 7-day, thermostat.
1H/1C, auto/manual changeover, electronic programmable. * For the most current accessory information, refer to the
price book or consult factory.
SOUND POWER RATINGS*
UNIT MODEL (dBA)
18 75 24 76 30 76 36 76 42 76 48 77 60 TBD
* Rated in accordance with ARI 270-95 Standards.
THERMOSTAT
WEATHERPROOF DISCONNECT SWITCH
NEC CLASS 1 WIRING
6” CLEARANCE AROUND PERIMETER
NOTE:
ALL OUTDOOR WIRING MUST BE WEATHERPROOF.
TYPICAL FIELD WIRING
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
POWER WIRING
208/230-1-60
CONTACTOR TERMINALS
GND.
LUG
CONDENSING UNIT
ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.
COIL
24 VOLT CONTROL WIRING MINIMUM 18 GA. WIRE (NEC CLASS 2)
TO FURNACE OR AIR HANDLER TERMINAL BLOCK
NEC CLASS 2 WIRING
TO INDOOR COIL
CONTROL ACCESS PANEL
FURNACE OR AIR HANDLER TERMINAL BLOCK
CYRGW
SEAL OPENING(S) WITH PERMAGUM OR EQUIVALENT
R
Y
ROOM THERMOSTAT
GW
POWER WIRING CONTROL WIRING FACTORY WIRING
*
TERMINAL W IS ONLY REQUIRED ON SYSTEMS WITH HEAT.
*
10 Johnson Controls Unitary Products
Page 11
359315-YTG-B-0408
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. TCGD18S41S1(H) INDOOR COIL MODEL NO. FC/MC/PC18
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE I NDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
HC18 1.00 1.00 1.00 – UC18 1.00 1.00 1.00 AHP18 1.00 1.00 1.00 MV12B FC/MC18B 1.02 1.03 0.89 MA08B FC/MC18B 1.00 1.00 1.00 F4FP024 1.00 1.00 1.00
IDCFM 450 600 750
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 15.7 17.8 17.7 19.3 19.9 16.9 18.4 18.0 19.5 20.2 18.0 18.9 18.4 19.6 20.4
S.C. 16.0 13.8 12.1 12.0 9.3 17.3 15.9 13.5 13.0 9.8 18.5 17.9 14.9 13.9 10.4
KW 1.0 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9
T.C. 15.0 16.8 16.6 18.4 19.2 16.2 17.5 17.1 18.6 19.4 17.4 18.2 17.5 18.8 19.6
S.C. 15.3 13.6 11.7 11.6 8.9 16.6 15.6 13.2 12.8 9.6 17.9 17.6 14.7 13.9 10.3
KW 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1
T.C. 14.2 15.8 15.6 17.4 18.5 15.5 16.6 16.1 17.7 18.6 16.8 17.4 16.7 18.1 18.8
S.C. 14.5 13.4 11.2 11.2 8.6 15.9 15.3 12.8 12.6 9.4 17.2 17.2 14.4 13.9 10.1
KW 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
T.C. 13.5 14.8 14.6 16.4 17.7 14.8 15.7 15.2 17.5 17.9 16.1 16.6 15.8 17.3 18.0
S.C. 13.8 13.1 10.8 10.7 8.2 15.2 15.0 12.5 12.4 9.1 16.6 16.9 14.2 14.0 10.0
KW 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
T.C. 12.6 13.7 13.2 15.1 16.5 13.8 14.6 13.8 15.5 16.7 15.0 15.5 14.4 16.0 16.8
S.C. 12.8 12.5 10.2 10.3 7.9 14.1 14.1 11.8 11.9 8.8 15.4 15.7 13.4 13.6 9.8
KW 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
T.C. 11.6 12.6 11.8 13.8 15.4 12.7 13.5 12.5 14.2 15.5 13.8 14.5 13.1 14.6 15.6
S.C. 11.9 11.9 9.6 9.8 7.6 13.1 13.2 11.2 11.6 8.6 14.3 14.6 12.7 13.3 9.6
KW 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
T.C. 10.7 11.4 10.5 12.5 14.2 11.7 12.4 11.2 12.9 14.3 12.7 13.4 11.8 13.3 14.4
S.C. 11.0 11.2 9.0 9.4 7.3 12.1 12.3 10.5 11.2 8.3 13.1 13.5 12.0 12.9 9.4
KW 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
Variable Speed Furnace
PV8*A12 FC/MC/PC18A 1.02 1.03 0.89 PV9*A12 FC/MC/PC18A 1.01 1.03 0.88 P(C,V)9*B12 FC/MC/PC18B 1.02 1.03 0.89 PV8*A12 HC18 1.02 1.03 0.89 PV9*A12 HC18 1.01 1.03 0.88
Coil T.C. S.C. KW
Johnson Controls Unitary Products 11
Page 12
359315-YTG-B-0408
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. TCGD24S41S1(H) INDOOR COIL MODEL NO. FC/MC/PC36
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
FC/MC/PC32 1.00 1.00 1.00 – FC/MC/PC35 1.00 1.00 1.00 – FC/MC/PC37 1.00 1.00 1.00 – FC/MC/PC43 1.00 1.00 1.00 – HC30 1.00 1.00 1.00 – HC36 1.00 1.00 1.00 – HC42 1.00 1.00 1.00 – UC36 1.00 1.00 1.00 AHP30 1.00 1.00 1.00 AV36 1.00 1.04 0.91 MV12B FC/MC36B 1.00 1.04 0.91 MA08B FC/MC36B 1.00 1.00 1.00 MV12B FC/MC35B 1.00 1.04 0.91 MA08B FC/MC35B 1.00 1.00 1.00 MV12B FC/MC43B 1.00 1.03 0.91 MA08B FC/MC43B 1.00 1.00 1.00 F4FP36 1.00 1.00 1.00
IDCFM 600 800 1000
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 22.0 27.4 27.3 29.1 30.3 24.3 28.8 28.6 30.4 31.7 26.6 30.1 29.8 31.8 33.2
S.C. 22.0 19.9 17.3 17.0 13.8 24.2 22.9 19.6 18.8 14.8 26.4 26.0 22.0 20.6 15.7
KW 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 T.C. 20.5 25.3 25.1 27.4 29.3 23.0 26.9 26.6 28.9 30.7 25.5 28.4 28.0 30.4 32.2
S.C. 20.5 19.3 16.4 16.5 13.4 22.8 22.1 18.8 18.4 14.4 25.1 24.9 21.3 20.3 15.5
KW 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 T.C. 19.0 23.2 23.0 25.8 28.3 21.7 25.0 24.6 27.4 29.7 24.4 26.7 26.1 28.9 31.2
S.C. 19.0 18.6 15.6 15.9 12.9 21.4 21.2 18.1 18.0 14.1 23.9 23.7 20.5 20.0 15.3
KW 1.7 1.7 1.7 1.7 1.8 1.7 1.7 1.7 1.8 1.8 1.7 1.7 1.7 1.8 1.8 T.C. 17.5 21.1 20.8 23.8 27.2 20.4 23.1 22.5 24.0 28.7 23.3 25.0 24.3 27.5 30.1
S.C. 17.5 18.0 14.7 15.4 12.4 20.0 20.3 17.3 16.8 13.7 22.6 22.6 19.8 19.7 15.1
KW 1.8 1.8 1.8 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.0 T.C. 16.2 19.0 18.4 21.7 24.8 18.7 21.0 20.2 23.3 26.3 21.3 22.9 22.0 24.9 27.7
S.C. 16.1 16.6 13.7 14.4 11.6 18.4 18.6 15.9 16.6 13.0 20.6 20.6 18.2 18.8 14.5
KW 2.0 2.0 2.0 2.0 2.1 2.0 2.0 2.0 2.0 2.1 2.0 2.0 2.0 2.1 2.1 T.C. 14.8 17.0 16.1 19.3 22.5 17.1 18.9 17.9 20.8 23.9 19.4 20.9 19.7 22.3 25.4
S.C. 14.8 15.3 12.7 13.5 10.8 16.8 17.0 14.6 15.7 12.4 18.7 18.7 16.5 17.8 13.9
KW 2.1 2.1 2.1 2.1 2.2 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.1 2.2 2.3 T.C. 13.5 14.9 13.8 16.8 20.1 15.5 16.9 15.6 18.3 21.6 17.5 18.9 17.4 19.8 23.1
S.C. 13.5 13.9 11.7 12.5 10.1 15.1 15.4 13.3 14.7 11.7 16.8 16.8 14.9 16.9 13.3
KW 2.2 2.2 2.2 2.3 2.4 2.3 2.3 2.2 2.3 2.4 2.3 2.3 2.3 2.3 2.4
Variable Speed Furnace
PV8*A12 FC/MC/PC32A 1.00 1.03 0.91 PV9*A12 FC/MC/PC32A 1.00 1.02 0.91 P(C,V)9*B12 FC/MC/PC35B 1.00 1.02 0.91 PV8*A12 FC/MC/PC36A 1.00 1.03 0.91 PV9*A12 FC/MC/PC36A 1.00 1.02 0.91 P(C,V)9*B12 FC/MC/PC36B 1.00 1.02 0.91 PV8*A12 FC/MC/PC37A 1.00 1.03 0.91 PV9*A12 FC/MC/PC37A 1.00 1.02 0.91 P(C,V)9*B12 FC/MC/PC43B 1.00 1.02 0.91 PV8*A12 HC30 1.00 1.03 0.91 PV9*A12 HC30 1.00 1.02 0.91 P(C,V)9*B12 HC36 1.00 1.02 0.91
Coil T.C. S.C. KW
12 Johnson Controls Unitary Products
Page 13
359315-YTG-B-0408
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. TCGD30S41S1(H) INDOOR COIL MODEL NO. FC/MC/PC35
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE I NDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
IDCFM 800 1000 1200
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 28.4 31.4 30.8 33.1 34.4 29.8 31.8 31.4 33.4 34.5 31.2 32.3 32.1 33.7 34.7
S.C. 28.8 25.8 21.7 21.2 16.0 30.4 28.2 23.6 22.6 17.1 31.9 30.7 25.4 24.0 18.1
KW 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
T.C. 26.4 28.8 28.2 30.9 32.6 27.9 29.7 28.9 31.4 32.8 29.5 30.5 29.6 31.8 32.9
S.C. 26.9 24.7 20.5 20.3 15.4 28.5 27.1 22.6 22.0 16.4 30.2 29.5 24.6 23.7 17.5
KW 1.8 1.8 1.8 1.9 1.9 1.8 1.8 1.8 1.9 1.9 1.9 1.9 1.9 1.9 1.9
T.C. 24.4 26.3 25.6 28.8 30.9 26.0 27.5 26.4 29.3 31.0 27.7 28.7 27.1 29.8 31.2
S.C. 24.9 23.6 19.4 19.4 14.7 26.6 26.0 21.6 21.4 15.8 28.4 28.4 23.9 23.4 16.8
KW 2.0 2.0 2.0 2.0 2.1 2.0 2.0 2.0 2.0 2.1 2.0 2.0 2.0 2.1 2.1
T.C. 22.4 23.8 23.0 26.7 29.1 24.2 25.3 23.8 29.0 29.3 26.0 26.9 24.7 27.9 29.4
S.C. 22.9 22.5 18.2 18.5 14.1 24.8 24.9 20.7 21.2 15.1 26.7 27.3 23.1 23.1 16.2
KW 2.1 2.1 2.1 2.2 2.3 2.2 2.2 2.2 2.2 2.3 2.2 2.2 2.2 2.2 2.3
T.C. 20.5 21.8 20.4 23.7 26.3 22.0 23.1 21.3 24.3 26.4 23.6 24.5 22.1 24.8 26.4
S.C. 21.0 20.7 17.1 17.4 13.2 22.6 22.7 19.1 19.7 14.3 24.3 24.7 21.0 22.0 15.4
KW 2.3 2.3 2.3 2.4 2.4 2.4 2.4 2.3 2.4 2.5 2.4 2.4 2.3 2.4 2.5
T.C. 18.6 19.8 17.9 20.9 23.5 19.9 21.0 18.8 21.4 23.5 21.2 22.2 19.6 21.8 23.6
S.C. 19.1 18.9 15.9 16.4 12.3 20.5 20.5 17.5 18.6 13.5 22.0 22.2 19.1 20.9 14.7
KW 2.5 2.5 2.4 2.5 2.6 2.5 2.5 2.5 2.5 2.6 2.6 2.6 2.5 2.6 2.6
T.C. 16.8 17.9 15.4 18.1 20.7 17.8 18.9 16.2 18.5 20.7 18.9 19.9 17.1 18.8 20.7
S.C. 17.3 17.2 14.8 15.3 11.4 18.4 18.4 16.0 17.6 12.6 19.6 19.6 17.1 19.8 13.9
KW 2.7 2.7 2.6 2.7 2.8 2.7 2.7 2.6 2.7 2.8 2.7 2.7 2.7 2.7 2.8
Air Handler Coil T.C. S.C. KW
FC/MC/PC35 1.00 1.00 1.00 – FC/MC/PC37 1.00 1.00 1.00 – FC/MC/PC43 1.00 1.00 1.00 – HC36 1.00 1.00 1.00 – HC42 1.00 1.00 1.00 AHP30 1.00 1.00 1.00 AHP36 1.00 1.00 1.00 AV36 1.02 1.03 0.93 MV12B FC/MC35B 1.01 1.02 0.92 MV16C FC/MC35C 1.02 1.02 0.93 MA12B FC/MC35B 1.00 1.00 1.00 MV12B FC/MC43B 1.01 1.02 0.92 MV16C FC/MC43C 1.02 1.02 0.93 MA12B FC/MC43B 1.00 1.00 1.00 F4FP040 1.00 1.00 1.00
Variable Speed Furnace
PV8*A12 FC/MC/PC32A 1.01 1.02 0.92 PV9*A12 FC/MC/PC32A 1.00 1.01 0.91 PV8*B16 FC/MC/PC35B 1.01 1.02 0.92 P(C,V)9*B12 FC/MC/PC35B 1.00 1.01 0.91 PV8*C16 FC/MC/PC35C 1.01 1.02 0.92 PV8*C20 FC/MC/PC35C 1.01 1.02 0.92 P(C,V)9*C16 FC/MC/PC35C 1.01 1.02 0.92 P(C,V)9*C20 FC/MC/PC35C 1.00 1.01 0.91 PV8*A12 FC/MC/PC37A 1.01 1.02 0.92 PV9*A12 FC/MC/PC37A 1.00 1.01 0.91 PV8*B16 FC/MC/PC43B 1.01 1.02 0.92 PV8*C16 FC/MC/PC43C 1.02 1.03 0.93 PV8*C20 FC/MC/PC43C 1.00 1.01 1.00 P(C,V)9*B12 FC/MC/PC43B 1.01 1.02 0.92 P(C,V)9*C16 FC/MC/PC43C 1.01 1.02 0.92 P(C,V)9*C20 FC/MC/PC43C 1.01 1.02 0.92 PV8*B16 HC36 1.01 1.02 0.92 P(C,V)9*B12 HC36 1.01 1.02 0.92 PV8*C16 HC42 1.02 1.03 0.93 PV8*C20 HC42 1.00 1.01 1.00 P(C,V)9*C16 HC42 1.01 1.02 0.92 P(C,V)9*C20 HC42 1.01 1.02 0.92
Coil T.C. S.C. KW
Johnson Controls Unitary Products 13
Page 14
359315-YTG-B-0408
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. TCGD36S41S1(H) INDOOR COIL MODEL NO. FC/MC/PC43
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
FC/MC/PC43 1.00 1.00 1.00 – FC/MC/PC48 1.00 1.00 1.00 – HC42 1.00 1.00 1.00 – UC48 1.00 1.00 1.00 AHP36 1.00 1.00 1.00 AHP42 1.00 1.00 1.00 AV36 1.01 1.01 0.92 MV16C FC/MC43C 1.01 1.02 0.92 MA12B FC/MC43B 1.00 1.00 1.00 MV16C FC/MC48C 1.01 1.02 0.92 MV20D FC/MC48D 1.01 1.03 0.92 MA14D FC/MC48D 1.00 1.00 1.00 MV12D FC/MC48D 1.01 1.02 0.92 F5FP048 1.00 1.00 1.00
IDCFM 1000 1200 1400
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 34.7 36.1 35.2 37.4 37.3 33.8 35.5 34.8 37.0 37.5 32.9 34.9 34.4 36.6 37.6
S.C. 34.3 33.0 27.6 25.5 18.4 33.3 31.0 26.2 24.6 18.0 32.3 29.1 24.7 23.6 17.7
KW 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 2.0 1.9 2.0 2.0 T.C. 33.6 34.7 33.6 35.9 36.6 32.6 33.9 33.2 35.5 36.6 31.5 33.2 32.7 35.1 36.6
S.C. 33.3 32.5 27.5 25.6 18.6 32.1 30.6 25.8 24.5 18.0 31.0 28.7 24.2 23.3 17.5
KW 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.2 2.2 2.2 2.2 T.C. 32.4 33.2 32.0 34.4 35.8 31.3 32.3 31.5 34.1 35.7 30.2 31.5 31.0 33.7 35.5
S.C. 32.2 32.0 27.3 25.8 18.8 30.9 30.2 25.5 24.3 18.0 29.6 28.3 23.7 22.9 17.3
KW 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.4 2.4 2.4 2.4 T.C. 31.3 31.7 30.4 33.0 35.0 30.1 30.7 29.9 35.0 34.8 28.9 29.8 29.4 32.2 34.5
S.C. 31.1 31.5 27.2 26.0 19.0 29.7 29.7 25.2 24.9 18.0 28.3 27.9 23.2 22.5 17.1
KW 2.6 2.6 2.6 2.6 2.7 2.6 2.6 2.6 2.6 2.7 2.5 2.6 2.6 2.6 2.6 T.C. 27.9 28.8 27.2 29.8 32.5 27.0 27.8 26.6 29.4 32.2 26.0 26.9 25.9 29.0 31.9
S.C. 28.7 28.9 25.0 25.0 18.4 27.3 27.2 23.2 23.2 17.3 25.8 25.6 21.5 21.4 16.2
KW 2.8 2.8 2.8 2.8 2.9 2.8 2.8 2.8 2.8 2.9 2.7 2.8 2.7 2.8 2.9 T.C. 24.6 26.0 24.2 26.8 30.1 23.9 25.1 23.4 26.3 29.8 23.3 24.1 22.6 25.9 29.5
S.C. 26.3 26.3 22.8 24.1 17.8 24.9 24.8 21.3 22.2 16.6 23.5 23.3 19.8 20.3 15.4
KW 3.0 3.0 3.0 3.0 3.1 3.0 3.0 2.9 3.0 3.1 2.9 2.9 2.9 3.0 3.1 T.C. 21.3 23.2 21.1 23.7 27.6 20.9 22.3 20.2 23.2 27.3 20.5 21.3 19.3 22.7 27.0
S.C. 23.9 23.8 20.6 23.2 17.2 22.5 22.4 19.4 21.2 15.9 21.1 21.0 18.2 19.2 14.6
KW 3.2 3.2 3.2 3.2 3.4 3.2 3.2 3.1 3.2 3.3 3.1 3.1 3.1 3.2 3.3
Variable Speed Furnace
PV8*A12 FC/MC/PC37A 1.00 1.00 0.91 PV9*A12 FC/MC/PC37A 1.00 1.00 1.00 PV8*B16 FC/MC/PC43B 1.01 1.01 0.92 PV8*C16 FC/MC/PC43C 1.01 1.02 0.92 PV8*C20 FC/MC/PC43C 1.01 1.01 0.92 P(C,V)9*B12 FC/MC/PC43B 1.00 1.01 0.91 P(C,V)9*C16 FC/MC/PC43C 1.01 1.01 0.92 P(C,V)9*C20 FC/MC/PC43C 1.01 1.01 0.92 PV8*C16 FC/MC/PC48C 1.01 1.02 0.92 PV8*C20 FC/MC/PC48C 1.01 1.01 0.92 P(C,V)9*C16 FC/MC/PC48C 1.01 1.02 0.92 P(C,V)9*C20 FC/MC/PC48C 1.01 1.01 0.92 P(C,V)9*D20 FC/MC/PC48D 1.01 1.02 0.92 PV8*C16 HC42 1.01 1.02 0.92 PV8*C20 HC42 1.01 1.01 0.92 P(C,V)9*C16 HC42 1.01 1.01 0.92 P(C,V)9*C20 HC42 1.01 1.01 0.92
Coil T.C. S.C. KW
14 Johnson Controls Unitary Products
Page 15
359315-YTG-B-0408
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. TCGD42S41S1(H) INDOOR COIL MODEL NO. FC/MC/PC43
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE I NDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
FC/MC/PC48 1.00 1.00 1.00 – HC42 1.00 1.00 1.00 – UC48 1.00 1.00 1.00 AHP42 0.97 1.00 0.97 MV16C FC/MC43C 1.00 1.02 0.91 MA16C FC/MC43C 1.00 1.00 1.00 MV16C FC/MC48C 1.00 1.02 0.91 MV20D FC/MC48D 1.00 1.02 0.91 MA14D FC/MC48D 1.00 1.00 1.00 MA16C FC/MC48C 1.00 1.00 1.00 F5FP048 1.00 1.00 1.00
IDCFM 1200 1400 1600
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 44.4 45.5 43.6 47.0 48.5 45.9 46.5 45.0 48.5 49.8 47.5 47.5 46.5 50.1 51.1
S.C. 41.5 35.6 29.7 28.7 21.5 42.9 37.5 31.4 30.2 22.9 44.4 39.4 33.2 31.7 24.3
KW 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6 2.5 2.5 2.5 2.5 2.6
T.C. 42.3 42.9 41.2 45.1 46.6 44.2 44.3 42.7 46.6 47.9 46.0 45.7 44.2 48.1 49.1
S.C. 39.4 35.2 29.2 28.5 21.3 41.1 37.4 31.1 30.1 22.4 42.9 39.7 33.0 31.8 23.6
KW 2.7 2.7 2.7 2.8 2.8 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.9
T.C. 40.2 40.3 38.9 43.3 44.6 42.4 42.1 40.4 44.7 45.9 44.6 43.9 41.9 46.0 47.2
S.C. 37.2 34.7 28.7 28.2 21.2 39.3 37.3 30.8 30.0 22.0 41.5 40.0 32.9 31.8 22.9
KW 3.0 3.0 3.0 3.0 3.1 3.0 3.0 3.0 3.1 3.1 3.0 3.0 3.0 3.1 3.1
T.C. 38.2 37.7 36.5 41.5 42.7 40.7 39.9 38.0 42.0 44.0 43.2 42.1 39.6 43.9 45.3
S.C. 35.0 34.3 28.1 28.0 21.0 37.5 37.3 30.5 29.4 21.6 40.0 40.3 32.8 31.9 22.2
KW 3.2 3.2 3.2 3.3 3.4 3.3 3.3 3.3 3.3 3.4 3.3 3.3 3.3 3.4 3.4
T.C. 35.3 34.7 32.8 37.4 38.7 37.5 36.7 34.2 38.6 39.8 39.8 38.8 35.6 39.8 40.9
S.C. 32.3 32.1 26.5 26.4 19.6 34.5 34.5 28.8 28.4 20.4 36.7 37.0 31.1 30.5 21.2
KW 3.5 3.5 3.5 3.6 3.7 3.5 3.5 3.5 3.6 3.7 3.6 3.6 3.5 3.6 3.7
T.C. 32.4 31.7 29.2 33.4 34.8 34.5 33.6 30.5 34.6 35.7 36.5 35.5 31.8 35.7 36.7
S.C. 29.7 30.0 25.0 24.9 18.2 31.6 31.9 27.2 27.0 19.3 33.5 33.8 29.4 29.1 20.3
KW 3.7 3.7 3.7 3.8 4.0 3.8 3.8 3.7 3.8 4.0 3.8 3.8 3.7 3.9 4.0
T.C. 29.6 28.8 25.6 29.4 30.9 31.4 30.5 26.8 30.5 31.7 33.2 32.2 28.0 31.7 32.5
S.C. 27.1 27.9 23.5 23.4 16.8 28.7 29.3 25.6 25.6 18.1 30.2 30.6 27.6 27.8 19.4
KW 4.0 4.0 3.9 4.0 4.2 4.0 4.0 4.0 4.1 4.3 4.1 4.1 4.0 4.1 4.3
Variable Speed Furnace
PV8*B16 FC/MC/PC43B 1.00 1.01 0.91 PV8*C20 FC/MC/PC43C 1.00 1.02 0.91 P(C,V)9*C16 FC/MC/PC43C 1.00 1.01 1.00 P(C,V)9*C20 FC/MC/PC43C 1.00 1.02 0.91 PV8*C16 FC/MC/PC48C 1.00 1.01 0.91 PV8*C20 FC/MC/PC48C 1.00 1.02 0.91 P(C,V)9*C16 FC/MC/PC48C 1.00 1.01 1.00 P(C,V)9*C20 FC/MC/PC48C 1.00 1.02 0.91 P(C,V)9*D20 FC/MC/PC48D 1.00 1.02 0.91 PV8*C16 HC42 1.00 1.01 0.91 PV8*C20 HC42 1.00 1.02 0.91 P(C,V)9*C16 HC42 1.00 1.01 1.00 P(C,V)9*C20 HC42 1.00 1.02 0.91
Coil T.C. S.C. KW
Johnson Controls Unitary Products 15
Page 16
359315-YTG-B-0408
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. TCGD48S41S1(H) INDOOR COIL MODEL NO. FC/MC/PC48
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
FC/MC/PC60 1.00 1.00 1.00 – HC60 1.00 1.00 1.00 – UC48 1.00 1.00 1.00 – UC60 1.00 1.00 1.00 AHP/SHP48 1.00 1.00 1.00 AHP/SHP60 1.00 1.01 1.00 AV/SV48 1.00 1.01 0.91 AV/SV60 1.00 1.01 0.91 MV16C FC/MC48C 1.00 1.01 0.91 MV20D FC/MC48D 1.00 1.01 0.91 MA16C FC/MC48C 1.00 1.00 1.00 MA20D FC/MC48D 1.00 1.00 1.00 MV20D FC/MC60D 1.00 1.01 0.91 MA16C FC60C 1.00 1.00 1.00 MA20D FC/MC60D 1.00 1.00 1.00 F5FP048 1.00 1.00 1.00 F5FP060 1.00 1.00 1.00 F4FV060 1.00 1.01 0.95
IDCFM 1400 1600 1800
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 49.7 51.4 50.6 55.8 54.6 52.0 53.1 51.9 56.4 55.4 54.4 54.7 53.2 56.9 56.3
S.C. 47.2 43.1 35.9 36.0 26.1 49.2 45.9 38.2 37.4 27.6 51.2 48.7 40.4 38.8 29.0
KW 2.7 2.8 2.8 2.8 2.8 2.7 2.8 2.8 2.8 2.8 2.7 2.8 2.8 2.8 2.9 T.C. 47.5 48.6 47.7 52.9 52.4 49.8 50.3 48.9 53.6 53.1 52.0 52.1 50.2 54.3 53.8
S.C. 44.9 42.0 35.0 34.9 25.4 47.0 44.8 37.1 36.5 26.8 49.0 47.6 39.3 38.2 28.1
KW 3.0 3.0 3.0 3.1 3.1 3.0 3.0 3.0 3.1 3.2 3.0 3.0 3.0 3.1 3.2 T.C. 45.4 45.8 44.8 49.9 50.2 47.5 47.6 46.0 50.8 50.8 49.7 49.4 47.1 51.7 51.4
S.C. 42.7 41.0 34.0 33.8 24.8 44.7 43.7 36.1 35.7 26.0 46.8 46.5 38.2 37.6 27.2
KW 3.2 3.3 3.3 3.4 3.4 3.3 3.3 3.3 3.4 3.5 3.3 3.3 3.3 3.4 3.5 T.C. 43.2 42.9 42.0 47.0 47.9 45.3 44.9 43.1 48.0 48.4 47.4 46.8 44.1 49.1 48.9
S.C. 40.4 39.9 33.0 32.7 24.1 42.4 42.6 35.1 34.6 25.2 44.5 45.4 37.1 37.0 26.3
KW 3.5 3.5 3.5 3.6 3.7 3.6 3.6 3.5 3.7 3.8 3.6 3.6 3.6 3.7 3.8 T.C. 39.8 39.4 37.3 42.4 43.6 41.6 41.1 38.4 43.4 44.0 43.5 42.9 39.5 44.4 44.5
S.C. 37.1 37.0 30.9 30.9 22.9 38.9 39.3 32.9 33.0 23.9 40.8 41.5 34.9 35.1 25.0
KW 3.8 3.8 3.8 3.9 4.0 3.9 3.9 3.8 3.9 4.1 3.9 3.9 3.8 4.0 4.1 T.C. 36.5 35.9 32.7 38.0 39.3 38.1 37.5 33.9 38.9 39.8 39.7 39.1 35.1 39.8 40.2
S.C. 33.9 34.2 28.9 29.2 21.6 35.5 36.0 30.9 31.3 22.7 37.2 37.7 32.8 33.3 23.8
KW 4.1 4.1 4.0 4.2 4.3 4.1 4.1 4.1 4.2 4.4 4.2 4.2 4.1 4.2 4.4 T.C. 33.1 32.4 28.1 33.5 35.1 34.5 33.8 29.4 34.4 35.5 35.9 35.3 30.6 35.2 36.0
S.C. 30.7 31.4 26.9 27.5 20.4 32.1 32.7 28.8 29.6 21.5 33.5 34.0 30.7 31.6 22.5
KW 4.4 4.4 4.3 4.4 4.6 4.4 4.4 4.3 4.5 4.7 4.5 4.5 4.4 4.5 4.7
Variable Speed Furnace
PV8*C16 FC/MC/PC48C 0.97 1.00 0.97 PV8*C20 FC/MC/PC48C 1.00 1.00 1.00 P(C,V)9*C16 FC/MC/PC48C 1.00 1.00 1.00 P(C,V)9*C20 FC/MC/PC48C 1.00 1.00 1.00 P(C,V)9*D20 FC/MC/PC48D 1.00 1.01 0.91 PV8*C16 FC/PC60C 1.00 1.00 1.00 PV8*C20 FC/PC60C 1.00 1.00 1.00 P(C,V)9*C16 FC/PC60C 1.00 1.00 1.00 P(C,V)9*C20 FC/PC60C 1.00 1.00 1.00 P(C,V)9*D20 FC/MC/PC60D 1.00 1.01 0.91
Coil T.C. S.C. KW
16 Johnson Controls Unitary Products
Page 17
359315-YTG-B-0408
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. TCGD60S41S1(H) INDOOR COIL MODEL NO. FC/MC/PC60
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE I NDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
FC/MC62 1.00 1.00 1.00 – HC60 1.00 1.00 1.00 – UC60 1.00 1.00 1.00 AHP/SHP60 1.00 1.00 1.00 AV/SV60 1.00 1.01 1.00 MV20D FC/MC60D 1.00 1.01 1.00 MA20D FC/MC60D 1.00 1.00 1.00 MV20D FC/MC62D 1.00 1.01 1.00 MA20D FC/MC62D 1.00 1.00 1.00 F5FP060 1.00 1.00 1.00 F4FV060 1.00 1.01 1.00
IDCFM 1400 1600 1800
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 55.8 63.8 62.1 65.2 71.9 60.3 65.7 62.8 66.7 69.8 64.8 67.5 63.5 68.2 67.8
S.C. 54.7 51.6 41.4 41.1 34.1 58.4 54.2 43.9 42.6 31.9 62.1 56.8 46.5 44.2 29.6
KW 3.0 3.0 3.0 3.1 3.1 3.0 3.0 3.0 3.1 3.1 3.0 3.1 3.0 3.1 3.1
T.C. 56.9 61.1 58.9 62.7 69.7 59.2 63.0 59.9 64.3 67.9 61.4 64.9 61.0 65.9 66.0
S.C. 53.9 50.4 40.5 40.0 33.5 55.8 53.1 43.1 41.8 31.5 57.7 55.7 45.6 43.6 29.5
KW 3.4 3.5 3.5 3.5 3.6 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5
T.C. 58.0 58.4 55.7 60.3 67.6 58.0 60.4 57.1 61.9 65.9 58.1 62.4 58.5 63.6 64.1
S.C. 53.2 49.3 39.7 39.0 32.9 53.3 52.0 42.2 41.0 31.2 53.4 54.7 44.8 42.9 29.4
KW 3.9 3.9 3.9 3.9 4.0 3.9 3.9 3.9 3.9 4.0 3.9 3.9 3.9 3.9 4.0
T.C. 59.1 55.7 52.5 56.9 65.5 56.9 57.8 54.3 57.0 63.9 54.7 59.8 56.0 61.2 62.2
S.C. 52.4 48.1 38.8 37.9 32.3 50.7 50.9 41.4 38.8 30.8 49.0 53.6 43.9 42.3 29.4
KW 4.3 4.3 4.3 4.4 4.5 4.3 4.3 4.3 4.4 4.4 4.3 4.3 4.3 4.4 4.4
T.C. 56.4 52.2 48.8 54.0 60.1 54.0 54.3 50.5 55.7 59.7 51.6 56.3 52.2 57.4 59.4
S.C. 49.7 45.9 37.5 36.5 29.7 47.9 48.3 40.0 38.7 29.4 46.2 50.6 42.5 40.9 29.0
KW 4.9 4.9 4.9 4.9 5.0 4.9 4.9 4.9 5.0 5.0 4.9 4.9 4.9 5.0 5.0
T.C. 53.8 48.8 45.2 50.2 54.8 51.2 50.9 46.8 51.9 55.7 48.7 53.0 48.5 53.6 56.6
S.C. 47.1 43.8 36.2 35.0 27.3 45.3 45.7 38.6 37.3 27.9 43.5 47.7 41.1 39.6 28.6
KW 5.5 5.4 5.4 5.5 5.6 5.5 5.5 5.4 5.5 5.6 5.4 5.5 5.4 5.5 5.6
T.C. 51.2 45.4 41.6 46.5 49.4 48.5 47.5 43.2 48.2 51.6 45.7 49.7 44.8 49.8 53.8
S.C. 44.5 41.7 34.9 33.6 24.9 42.6 43.2 37.3 35.9 26.5 40.7 44.7 39.7 38.3 28.2
KW 6.1 6.0 5.9 6.1 6.2 6.0 6.0 6.0 6.1 6.2 6.0 6.0 6.0 6.1 6.2
Variable Speed Furnace
PV8*C20 FC/PC/UC60C 1.00 1.00 1.00 P(C,V)9*C20 FC/PC/UC60C 1.00 1.00 1.00 P(C,V)9*D20 FC/MC/PC/UC60D 1.00 1.00 1.00 PV8*C20 FC/MC62D 1.00 1.00 1.00 P(C,V)9*C20 FC/MC62D 1.00 1.00 1.00 P(C,V)9*D20 FC/MC62D 1.00 1.00 1.00
Coil T.C. S.C. KW
Johnson Controls Unitary Products 17
Page 18
NOTES
Subject to change without notice. Printed in U.S.A. 359315-YTG-B-0408 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 359315-YTG-A-0208
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
Loading...