York TCGD18, TCGD36 S21S2H, TCGD24 S21S2H, TCGD30 S21S2H, TCGD42 S21S2H Technical Manual

...
A
V A
w
TECHNICAL GUIDE
SPLIT-SYSTEM
IR CONDITIONERS 13 SEER – R-22 MODELS:
TCGD12 THRU 60 (1 THRU 5 NOMINAL TONS, 1 PHASE)
LISTED
Due to continuous product improvement, specifications are subject to change without notice.
isit us on the web at www.york.com dditional rating information can be found at
ww.ahridirectory.org
ISO 9001
Certified Quality
Management System
400034-YTG-B-0708
DESCRIPTION
The 13 SEER Series condensing unit is the outdoor part of a versatile system of air conditioning. It is designed to be cus­tom-matched with one of UPG’s complete line of evaporator sections, with each serving a specific function. Matching Air Handlers are available for upflow, downflow, or horizontal applications to provide a complete system. Electric Heaters are available, if required. Add-On coils are available fo r use with upflow, downflow, or horizontal furnaces and air han­dlers.
WARRANTY
Single Phase Units:
5-year limited parts warranty. 5-year limited compressor warranty.
FEATURES
QUALITY CONDENSER COILS - The coil is constructed of aluminum microchannel tubing and enhanced aluminum fins for increased efficiency and corrosion protection.
PROTECTED COMPRESSOR - The compressor is inter­nally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compressor if undesirable operating condi­tions occur. A liquid line filter-drier further protects the compressor.
DURABLE FINISH - The cabinet is made of pre-painted steel. The pre-treated galvanized steel provides a better paint to steel bond, which resists corrosion and rust creep. Special primer formulas and matted-textured finish insure less fading when exposed to sunlight.
LOWER INSTALLED COST - Installation time and costs are reduced by easy power and control wiring connec­tions. Available in sweat connect models only. The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping. The small base dimen­sion means less space is required on the ground or roof.
TOP DISCHARGE - The warm air from the top mounted fan is blown up away from the structure and any landscap­ing. This allows compact location on multi-unit applica­tions.
LOW OPERATING SOUND LEVEL - The upward air flow carries the normal operating noise away from the living area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil muffle the normal fan motor and compressor operating sounds.
LOW MAINTENANCE - Long life permanently lubricated motor-bearings need no annual servicing.
EASY SERVICE ACCESS - Fully exposed refrigerant con­nections, and a single panel covering the electrical con­trols make for easy servicing of the unit.
SECURED SERVICE VALVES - Secured re-usable ser- vice valves are provided on both the liquid and vapor sweat connections for ease of evacuating and charging.
U.L. and C.U.L. listed - approved for outdoor application.
Certified in accordance with the Unitary Small Equipment cer­tification program, which is based on ARI Standard 210/240.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
400034-YTG-B-0708
Physical and Electrical Data
MODEL
TCGD12
S21S2(H)
TCGD18
S21S2(H)
TCGD24
S21S2(H)
TCGD30
S21S2(H)
TCGD36
S21S2(H)
TCGD42
S21S2(H)
TCGD48
S21S2(H)
TCGD60
S21S2
Unit Supply Voltage 208-230V, 1φ, 60Hz Normal Voltage Range
1
187 to 252
Minimum Circuit Ampacity 6.2 9.5 11.3 14.0 18.2 19.9 22.7 33.5 Max. Overcurrent Device Amps Min. Overcurrent Device Amps
2
3
15 15 15 20 30 30 35 50 15 15 15 15 20 20 25 35
Compressor Type Rotary Rotary Rotary Recip Recip Recip Recip Scroll Compressor Amps
Rated Load 4.5 7.2 8.4 10.6 13.4 14.7 17.0 25.6
Locked Rotor 26.0 40.0 47.0 61.0 78.0 78.0 86.0 150.0 Crankcase Heater No No No No No No No No Fan Motor Amps Rated Load 0.50 0.50 0.80 0.80 1.4 1.5 1.5 1.5 Fan Diameter Inches 18 18 18 18 18 22 22 22
Rated HP 1/12 1/12 1/8 1/8 1/4 1/4 1/4 1/4 Fan Motor
Nominal RPM 1100 1100 1075 1075 1100 850 850 850
Nominal CFM 1350 1550 1850 1950 2400 3000 3000 3300
Face Area Sq. Ft. 8.1 9.7 9.7 11.3 12.1 16.5 16.5 19.75 Coil
Rows Deep 11111111
Fin / Inches 23 23 23 23 23 23 23 23 Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 Vapor Line Set OD (Field Installed) 5/8 5/8 3/4 3/4 3/4 7/8 7/8 1-1/8
Unit Charge (Lbs. - Oz.)
4
3 - 2 3 - 0 3 - 13 3 - 7 3 - 15 4 - 2 4 - 5 5 - 4
Charge Per Foot, Oz. 0.66 0.66 0.68 0.68 0.68 0.70 0.70 0.76 Operating Weight Lbs. 96 110 130 150 160 175 176 200
Models with “H” on the end of the model number have a factory installed start kits.
1.Rated in accordance with ARI Standard 110, utilization range “A”.
2.Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3.Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
C
A
2 Johnson Controls Unitary Products
All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.
Unit
Model
12 24 18 28
Dimensions
(Inches)
1
A
B C Liquid Vapor 23-1/2 23-1/2 23-1/2 23-1/2
24 28 23-1/2 23-1/2 30 32 23-1/2 23-1/2 36 34 23-1/2 23-1/2 42 34 29 29 48 34 29 29
B
60 40 29 29
1.Including Fan Guard.
2. Expander fitting required for 1-1/8” linset.
Refrigerant Connection
Service Valve Size
3/4”
3/8”
7/8”
2
7/8”
400034-YTG-B-0708
Additional R-22 Charge / Orifice Size for Various Matched Systems
Outdoor Unit
Required Orifice or TXV Factory R-22 Charge, lbs-oz 3 - 2 3 - 0 3 - 13 3 - 7 3 - 15 4 - 2 4 - 5 5 - 4
TCGD12
S21S2(H)
1,2
0.041 / 2A 0.052 / 2A 0.059 / 0.061 / 2A 0.065 / 2A 0.073 / 2A 0.081 / 2C 0.084 / 2C 0.096 / 2C
TCGD18
S21S2(H)
TCGD24
S21S2(H)
TCGD30
S21S2(H)
TCGD36
S21S2(H)
TCGD42
S21S2(H)
TCGD48
S21S2(H)
TCGD60
S21S2
Indoor Coil
FC/MC/PC/UC18A2A 0 0 ––––– FC/MC/PC/UC18B2A 0 0 ––––– FC/MC/PC/UC24A2A –0 ––––– FC/MC/PC/UC24B2A –0 ––––– FC/MC/PC32A2A –– +3 +4 –––– FC/MC/PC35B2A –– +3 +4 –––– FC/MC/PC35C2A –– +3 +4 –––– FC/MC/PC/UC36A2A –– 0 ––––– FC/MC/PC/UC36B2A –– 0 ––––– FC/MC/PC/UC36C2A –– 0 ––––– FC/MC/PC37A2A – +7 +12 +4 – FC/MC/PC43B2C –– ––0 –– FC/MC/PC43C2C –– ––0 –– FC/MC/PC/UC48C2C – +5 +2 – FC/MC/PC/UC48D2C – +5 +2 – FC/MC62D2C –– ––––0 HC18A2A 0 0 ––––– HC30A2A –– 0 ––––– HC36B2A –– +3 +4 –––– HC42C2C – +12 +4 0 – AHP18B2A 0 0 ––––– AHP24B2A –0 ––––– AHP30B2A –– +3 +4 –––– AHP36C2A – +12 +4 – AHP42C2C –– ––0 –– AHP/SHP60D2C –– –––0 – AV24B2A –+2 ––––– AV36C2A – +7 +12 +4 – AV/SV48D2C –– –––0 – FC/MC/PC/UC18A3X 41 + 0 52 + 0 ––––– FC/MC/PC/UC18B3X 41 + 0 52 + 0 ––––– FC/MC/PC/UC24A3X –52 + 2 ––––– FC/MC/PC/UC24B3X –52 + 2 ––––– FC/MC/PC32A3X –– 61 + 3 65 + 4 –––– FC/MC/PC35B3X –– 61 + 3 65 + 4 –––– FC/MC/PC35C3X ––61 + 3 65 + 4 –––– FC/MC/PC/UC36A3X –– 59 + 0 ––––– FC/MC/PC/UC36B3X –– 59 + 0 ––––– FC/MC/PC/UC36C3X –– 59 + 0 ––––– FC/MC/PC37A3X 61 + 7 65 + 12 73 + 4 – FC/MC/PC43B3X 61 + 7 65 + 12 73 + 4 81 + 0 – FC/MC/PC43C3X 61 + 7 65 + 12 73 + 4 81 + 0 – FC/MC/PC/UC48C3X 73 + 4 81 + 5 84 + 2 – FC/MC/PC/UC48D3X 73 + 4 81 + 5 84 + 2 – FC/MC62D3X –– ––––96 + 0 HC18A3X 41 + 0 52 + 0 ––––– HC30A3X –– 59 + 0 ––––– HC36B3X –– 61 + 365 + 4 –––– HC42C3X 61 + 7 65 + 12 73 + 4 81 + 0 – For Notes See Page 4.
3,4
Additional Charge, Oz
Johnson Controls Unitary Products 3
400034-YTG-B-0708
Additional R-22 Charge / Orifice Size for Various Matched Systems (Continued)
Outdoor Unit
Required Orifice or TXV
TCGD12
S21S2(H)
1,2
0.041 / 2A 0.052 / 2A 0.059 / 0.061 / 2A 0.065 / 2A 0.073 / 2A 0.081 / 2C 0.084 / 2C 0.096 / 2C
Factory R-22 Charge, lbs-oz 3 - 2 3 - 0 3 - 13 3 - 7 3 - 15 4 - 2 4 - 5 5 - 4
TCGD18
S21S2(H)
TCGD24
S21S2(H)
TCGD30
S21S2(H)
TCGD36
S21S2(H)
TCGD42
S21S2(H)
TCGD48
S21S2(H)
TCGD60
S21S2
Indoor Coil
3,4
Additional Charge, Oz
AHP18B3X 41 + 0 52 + 0 –––––
AHP24B3X –52 + 0 ––––– AHP30B3X ––61 + 3 65 + 4 –––– AHP36C3X 73 + 4 – AHP42C3X 73 + 4 81 + 0 – AHP/SHP60D3X – 84 + 0 – AV24B3X –52 + 2 ––––– AV36C3X 61 + 7 65 + 12 73 + 4 – AV/SV48D3X – 84 + 0
F4FP024
F4FP036
F4FP040
F5FP048
F5FP060
F4FV060
See Caution below
See Caution below
See Caution below
See Caution below
See Caution below
See Caution below
–52 + 0 ––––– –2A + 0 ––––– –– 61 + 1 ––––– ––2A + 2 ––––– –– – 65 + 0 –––– –– – 2A + 0 –––– – 73 + 0 81 + 5 84 + 2 – – 2A + 0 2C + 5 2C + 2 – –– –––84 + 0 – –– –––2C + 0 – –– –––84 + 0 – –– –––2C + 0
FOOTNOTES:
1. For applications requiring a TXV use 1TVM series kit.
2. Approved orifice shipped with outdoor unit.
3. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
4. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of inter­connecting line tubing.
2. Verify the TXV or orifice and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical Data Table.
4. For TXV match charge weight needs to be weighed in for specififc coil match and lineset length.
5. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator + adder for line set.
Models 12-48 require start kits for TXV matches. Models with “H” on the end of the model number have factory installed start kits. For models without an “H” refer to tech guide for kit number reference.
F*FP Air Handlers come with a factory installed R-22 TXV. Please note that some models may take a different TXV then what is factory installed. The proper TXV must be installed for system reliability and performance. Also note, TXV must be removed for orifice match.
4 Johnson Controls Unitary Products
400034-YTG-B-0708
COOLING CAPACITY - With Air Handler Coils
UNIT
MODEL
AIR HANDLER
MODEL W
COIL
MODEL
1
RATED
CFM
TOTAL SENS.
13 SEER AC WITH MA
TCGD18S21S2(H)
MA08B 17 FC/MC18B 600 18.0 12.6 13.00 11.00 MA08B 17 FC/MC24B 600 18.0 12.6 13.00 11.00 MA08B 17 FC/MC35B 800 24.0 17.2 13.00 11.00
TCGD24S21S2(H)
MA08B 17 FC/MC36B 800 24.0 17.2 13.00 11.00 MA08B 17 FC/MC43B 800 24.0 17.2 13.00 11.00
TCGD30S21S2(H)
TCGD36S21S2(H)
MA12B 17 FC/MC35B 1000 29.0 21.2 13.00 11.00 MA12B 17 FC/MC43B 1000 29.0 21.2 13.00 11.00 MA12B 17 FC/MC43B 1200 35.0 24.4 13.00 11.00 MA14D 24 FC/MC48D 1200 35.0 24.4 13.00 11.00 MA16C 21 FC/MC43C 1400 42.0 29.4 13.00 11.00
TCGD42S21S2(H)
MA14D 24 FC/MC48D 1400 42.0 29.4 13.00 11.00 MA16C 21 FC/MC48C 1400 42.0 29.4 13.00 11.00
TCGD48S21S2(H)
MA16C 21 FC/MC48C 1600 46.0 32.6 13.00 11.00 MA20D 24 FC/MC48D 1600 46.0 32.6 13.00 11.00
TCGD60S21S2 MA20D 24 FC/MC62D 1800 54.0 41.5 13.00 11.00
13 SEER AC WITH MV - VARIABLE SPEED
TCGD18S21S2(H)
MV12B 17 FC/MC18B 600 18.0 13.0 14.00 12.00 MV12B 17 FC/MC24B 600 18.0 13.0 14.00 12.00 MV12B 17 FC/MC36B 800 24.0 17.8 14.00 12.00
TCGD24S21S2(H)
MV12B 17 FC/MC35B 800 24.0 17.8 14.00 12.00 MV12B 17 FC/MC43B 800 24.0 17.8 14.00 12.00 MV12B 17 FC/MC35B 1000 30.0 21.8 14.00 12.00
TCGD30S21S2(H)
MV12B 17 FC/MC43B 1000 30.0 21.8 14.00 12.00 MV16C 21 FC/MC35C 1000 30.0 21.8 14.00 12.00 MV16C 21 FC/MC43C 1000 30.0 21.8 14.00 12.00 MV16C 21 FC/MC43C 1200 36.0 25.0 14.00 12.00
TCGD36S21S2(H)
MV16C 21 FC/MC48C 1200 36.0 25.2 14.00 12.00 MV20D 24 FC/MC48D 1200 36.0 25.2 14.00 12.00 MV12D 24 FC/MC48D 1135 35.0 25.2 14.00 12.00 MV16C 21 FC/MC43C 1400 42.0 30.0 14.00 12.00
TCGD42S21S2(H)
MV16C 21 FC/MC48C 1400 42.0 30.0 14.00 12.00 MV20D 24 FC/MC48D 1400 42.0 30.0 14.00 12.00
TCGD48S21S2(H)
MV16C 21 FC/MC48C 1600 45.0 33.2 13.50 11.00 MV20D 24 FC/MC48D 1600 46.0 33.0 13.50 11.00
TCGD60S21S2 MV20D 24 FC/MC62D 1800 55.0 41.5 13.50 11.00
13 SEER AC WITH AV / SV - / F*FV VARIABLE SPEED
TCGD18S21S2(H) AV24 17 – TCGD24S21S2(H) AV36 21 – TCGD30S21S2(H) AV36 21 – TCGD36S21S2(H) AV36 21 –
TCGD48S21S2(H)
AV/SV48 24 – F4FV060 24
565 18.0 13.1 14.00 12.00 765 24.0 17.9 14.00 12.00 1015 30.0 22.0 14.00 12.00 1270 35.0 25.0 14.00 12.00 1610 45.0 33.2 13.50 11.00 1600 45.0 33.2 13.50 11.00
For Notes See Page 6.
COOLING
NET MBH
SEER EER
Johnson Controls Unitary Products 5
400034-YTG-B-0708
COOLING CAPACITY - With Air Handler Coils (Continued)
UNIT
MODEL
AIR HANDLER
MODEL W
COIL
MODEL
1
RATED
CFM
TOTAL SENS.
13 SEER AC WITH AHP / SHP / F*FP
TCGD12S21S2(H) AHP18 17 –
AHP18 17
TCGD18S21S2(H)
AHP24 17
F4FP024 18
TCGD24S21S2(H)
AHP30 17
F4FP036 21.5
AHP30 17
TCGD30S21S2(H)
AHP36 21
F4FP040 21.5
TCGD36S21S2(H)
TCGD42S21S2(H)
AHP36 21
F5FP048 24
AHP42 21
F5FP048 24
AHP/SHP60 24
TCGD48S21S2(H)
F5FP048 24 – F5FP060 24
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210. Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow. EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.
450 12.0 8.9 13.00 11.00 650 18.0 12.6 13.00 11.00 650 18.0 12.6 13.00 11.00 600 18.0 12.6 1300 11.00 795 24.0 17.3 13.00 11.00 860 24.0 17.3 13.00 11.00 1015 29.0 21.2 13.00 11.00 1015 29.0 21.2 13.00 11.00 1000 29.0 21.2 13.00 11.00 1235 35.0 24.4 13.00 11.00 1235 35.0 24.4 13.00 11.00 1485 42.0 29.4 13.00 11.00 1455 42.0 29.4 13.00 11.00 1600 46.0 33.0 13.00 11.00 1690 46.0 33.0 13.00 11.00 1680 46.0 33.0 13.00 11.00
COOLING
NET MBH
SEER EER
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
— = Not applicable.
CONDENSER ONLY DAT A
Air Temp on Condenser
Model
TCGD12S21S2(H)
SH 11 / SC 13 @
95 OD Temp
TCGD18S21S2(H)
SH 11 / SC 10 @
95 OD Temp
TCGD24S21S2(H)
SH 10 / SC 12 @
95 OD Temp
TCGD30S21S2(H)
SH 12 / SC 10 @
95 OD Temp
TCGD36S21S2(H)
SH 10 / SC 11 @
95 OD Temp
TCGD42S21S2(H) SH 10 / SC 9 @ 95
OD Temp
TCGD48S21S2(H)
SH 10 / SC 12 @
95 OD Temp
TCGD60S21S2
SH 10 / SC 9 @ 95
OD Temp
Suct. T/P @ Compr.
75° F 95° F 115° F
Temp. PSIG MBH KW MBH KW MBH KW
40 68.6 11.81 0.73 8.15 0.85 5.29 1.01 45 76.1 12.65 0.73 10.15 0.86 7.21 1.02 50 84.1 13.55 0.74 12.29 0.87 9.26 1.04 40 68.6 17.53 1.07 15.03 1.29 11.98 1.57 45 76.1 18.63 1.07 17.25 1.30 14.07 1.59 50 84.1 19.80 1.08 19.61 1.31 16.30 1.61 40 68.6 22.88 1.42 19.07 1.70 13.99 2.02 45 76.1 24.93 1.44 22.25 1.72 17.25 2.07 50 84.1 27.12 1.47 25.63 1.75 20.72 2.12 40 68.6 28.77 1.75 23.85 2.01 17.06 2.21 45 76.1 30.28 1.80 26.56 2.07 19.76 2.31 50 84.1 31.89 1.86 29.45 2.13 22.64 2.40 40 68.6 31.46 2.16 18.41 2.37 13.42 2.78 45 76.1 36.54 2.20 25.84 2.47 18.88 2.85 50 84.1 41.95 2.24 33.77 2.58 24.71 2.91 40 68.6 40.44 2.46 28.86 2.83 21.78 3.21 45 76.1 45.28 2.52 36.10 2.91 27.55 3.30 50 84.1 50.44 2.59 43.82 3.00 33.70 3.41 40 68.6 42.04 2.70 26.14 3.03 21.19 3.49 45 76.1 46.86 2.77 35.10 3.16 27.59 3.60 50 84.1 52.00 2.85 44.65 3.30 34.43 3.73 40 68.6 52.76 3.40 46.38 4.04 36.26 5.08 45 76.1 59.98 3.41 53.35 4.14 42.46 5.15 50 84.1 67.69 3.41 60.79 4.25 49.07 5.22
6 Johnson Controls Unitary Products
400034-YTG-B-0708
COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils
FURNACE**
UNIT MODEL
TCGD12S21S2(H)
TCGD18S21S2(H)
TCGD24S21S2(H)
TCGD30S21S2(H)
TCGD36S21S2(H)
TCGD42S21S2(H)
TCGD48S21S2(H)
TCGD60S21S2 1600 - 2000 24 FC/MC62 2000 55.0 41.0 13.00 11.00
1. Requires a 2FD06700224 Blower Time Delay unless a standard furnace is equipped with one. ** Refer to Quick Selection Chart for specific furnace match-up.
CFM RANGE
(Min.-max.)
450 - 750 14,17 FC/MC/PC18 450 12.0 9.1 13.00 11.00 450 - 750 14 HC18 450 12.0 9.1 13.00 11.00 450 - 750 14,17 UC18 450 12.0 9.1 13.00 11.00 450 - 750 14,17 FC/MC/PC18 600 18.0 12.6 13.00 11.00 450 - 750 14,17 FC/MC/PC24 600 18.0 12.6 13.00 11.00 450 - 750 14 HC18 600 18.0 12.6 13.00 11.00 450 - 750 14,17 UC18 600 18.0 12.6 13.00 11.00
450 - 750 14,17 UC24 600 18.0 12.6 13.00 11.00 600 - 1000 14 FC/MC/PC32 800 24.0 17.2 13.00 11.00 600 - 1000 17,21 FC/MC/PC35 800 24.0 17.2 13.00 11.00 600 - 1000 14,17,21 FC/MC/PC36 800 24.0 17.2 13.00 11.00 600 - 1000 14 FC/MC/PC37 800 24.0 17.2 13.00 11.00 600 - 1000 17,21 FC/MC/PC43 800 24.0 17.2 13.00 11.00 600 - 1000 14 HC30 800 24.0 17.2 13.00 11.00 600 - 1000 17 HC36 800 24.0 17.2 13.00 11.00 600 - 1000 21 HC42 800 24.0 17.2 13.00 11.00 600 - 1000 14,17,21 UC36 800 24.0 17.2 13.00 11.00 800 - 1200 14 FC/MC/PC32 1000 29.0 21.2 13.00 11.00 800 - 1200 17,21 FC/MC/PC35 1000 29.0 21.2 13.00 11.00 800 - 1200 14 FC/MC/PC37 1000 29.0 21.2 13.00 11.00 800 - 1200 17,21 FC/MC/PC43 1000 29.0 21.2 13.00 11.00 800 - 1200 17 HC36 1000 29.0 21.2 13.00 11.00 800 - 1200 21 HC42 1000 29.0 21.2 13.00 11.00
1000 - 1400 14 FC/MC/PC37 1200 35.0 24.4 13.00 11.00 1000 - 1400 17,21 FC/MC/PC43 1200 35.0 24.4 13.00 11.00 1000 - 1400 21,24 FC/MC/PC48 1200 35.0 24.4 13.00 11.00 1000 - 1400 21 HC42 1200 35.0 24.4 13.00 11.00 1000 - 1400 21,24 UC48 1200 35.0 24.4 13.00 11.00 1200 - 1600 17,21 FC/MC/PC43 1400 42.0 29.4 13.00 11.00 1200 - 1600 21,24 FC/MC/PC48 1400 42.0 29.4 13.00 11.00 1200 - 1600 21 HC42 1400 42.0 29.4 13.00 11.00 1200 - 1600 21,24 UC48 1400 42.0 29.4 13.00 11.00 1400 - 1800 21,24 FC/MC/PC48 1550 46.0 32.6 13.00 11.00 1400 - 1800 21,24 UC48 1550 46.0 32.6 13.00 11.00
W
COIL
MODEL
RATED
CFM
TOTAL SENS.
COOLING
NET MBH
SEER
1
EER
Johnson Controls Unitary Products 7
400034-YTG-B-0708
1
COOLING CAPACITY - With Variable Speed Furnaces
UNIT MODEL
TCGD18S21S2(H)
TCGD24S21S2(H)
TCGD30S21S2(H)
For Notes See Page 8.
VARIABLE SPEED
FURNACE MODEL
13 SEER AC WITH VARIABLE SPEED FURNACES
PV8*A12 FC/MC/PC18A 14 600 18.0 13.0 14.00 12.00 PV9*A12 FC/MC/PC18A 14 600 18.0 12.9 14.00 12.00
P(C,V)9*B12 FC/MC/PC18B 17 600 18.0 13.0 14.00 12.00
PV8*A12 FC/MC/PC24A 14 600 18.0 13.0 14.00 12.00 PV9*A12 FC/MC/PC24A 14 600 18.0 12.9 14.00 12.00
P(C,V)9*B12 FC/MC/PC24B 17 600 18.0 13.0 14.00 12.00
PV8*A12 HC18 14 600 18.0 13.0 14.00 12.00 PV9*A12 HC18 14 600 18.0 12.9 14.00 12.00 PV8*A12 FC/MC/PC32A 14 800 24.0 17.7 14.00 12.00 PV9*A12 FC/MC/PC32A 14 800 24.0 17.7 14.00 12.00
P(C,V)9*B12 FC/MC/PC35B 17 800 24.0 17.7 14.00 12.00
PV8*A12 FC/MC/PC36A 14 800 24.0 17.7 14.00 12.00 PV9*A12 FC/MC/PC36A 14 800 24.0 17.7 14.00 12.00
P(C,V)9*B12 FC/MC/PC36B 17 800 24.0 17.7 14.00 12.00
PV8*A12 FC/MC/PC37A 14 800 24.0 17.7 14.00 12.00 PV9*A12 FC/MC/PC37A 14 800 24.0 17.7 14.00 12.00
P(C,V)9*B12 FC/MC/PC43B 17 800 24.0 17.7 14.00 12.00
PV8*A12 HC30 14 800 24.0 17.7 14.00 12.00 PV9*A12 HC30 14 800 24.0 17.7 14.00 12.00
P(C,V)9*B12 HC36 17 800 24.0 17.7 14.00 12.00
PV8*A12 FC/MC/PC32A 14 1000 30.0 21.8 14.00 12.00 PV9*A12 FC/MC/PC32A 14 1000 30.0 21.8 14.00 12.00 PV8*B16 FC/MC/PC35B 17 1000 30.0 21.8 14.00 12.00 PV8*C16 FC/MC/PC35C 21 1000 30.0 21.8 14.00 12.00 PV8*C20 FC/MC/PC35C 21 1000 30.0 22.0 14.00 12.00
P(C,V)9*B12 FC/MC/PC35B 17 1000 30.0 21.6 14.00 12.00
PV8*A12 FC/MC/PC37A 14 1000 30.0 21.8 14.00 12.00 PV9*A12 FC/MC/PC37A 14 1000 30.0 21.8 14.00 12.00 PV8*B16 FC/MC/PC43B 17 1000 30.0 21.8 14.00 12.00 PV8*C16 FC/MC/PC43C 21 1000 30.0 21.8 14.00 12.00 PV8*C20 FC/MC/PC43C 21 1000 30.0 22.0 14.00 12.00
P(C,V)9*B12 FC/MC/PC43B 17 1000 30.0 21.6 14.00 12.00
PV8*B16 HC36 17 1000 30.0 21.8 14.00 12.00
P(C,V)9*B12 HC36 17 1000 30.0 21.6 14.00 12.00
PV8*C16 HC42 21 1000 30.0 22.0 14.00 12.00 PV8*C20 HC42 21 1000 30.0 22.0 14.00 12.00
P(C,V)9*C16 HC42 21 1000 30.0 22.0 14.00 12.00
COIL
MODEL
1
COOLING
W
RATED
CFM
Net MBH
TOTAL SENS.
2
SEER EER
8 Johnson Controls Unitary Products
COOLING CAP ACITY - With Variable Speed Furnaces (Continued)
UNIT MODEL
TCGD36S21S2(H)
TCGD42S21S2(H)
TCGD48S21S2(H)
TCGD60S21S2
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. Variable speed furnaces have B.O.D (Blower on Delay) standard.
VARIABLE SPEED FURNACE MODEL
13 SEER AC WITH VARIABLE SPEED FURNACES
PV8*A12 FC/MC/PC37A 14 1200 35.2 25.0 14.00 12.00 PV9*A12 FC/MC/PC37A 14 1200 35.2 25.0 14.00 12.00 PV8*B16 FC/MC/PC43B 17 1200 35.4 25.0 14.00 12.00 PV8*C16 FC/MC/PC43C 21 1200 35.4 25.0 14.00 12.00
PV8*C20 FC/MC/PC43C 21 1200 35.6 25.0 14.00 12.00 P(C,V)9*B12 FC/MC/PC43B 17 1200 35.2 24.8 13.50 11.00 P(C,V)9*C16 FC/MC/PC43C 21 1200 35.4 25.0 13.50 11.00 P(C,V)9*C20 FC/MC/PC43C 21 1200 35.4 25.0 14.00 12.00
PV8*C16 FC/MC/PC48C 21 1200 35.6 25.0 14.00 12.00
PV8*C20 FC/MC/PC48C 21 1200 35.6 25.0 14.00 12.00 P(C,V)9*C16 FC/MC/PC48C 21 1200 35.4 25.0 14.00 12.00 P(C,V)9*C20 FC/MC/PC48C 21 1200 35.4 25.0 14.00 12.00 P(C,V)9*D20 FC/MC/PC48D 24 1200 35.4 25.0 14.00 12.00
PV8*C16 HC42 21 1200 36.0 25.0 14.00 12.00
PV8*C20 HC42 21 1200 36.0 25.0 14.00 12.00 P(C,V)9*C16 HC42 21 1200 35.0 25.0 14.00 12.00 P(C,V)9*C20 HC42 21 1200 35.0 25.0 14.00 12.00
PV8*C20 FC/MC/PC43C 21 1400 41.0 29.8 13.50 11.00
PV8*C16 FC/MC/PC48C 21 1400 42.0 29.8 13.50 11.00
PV8*C20 FC/MC/PC48C 21 1400 41.0 30.0 13.50 11.00 P(C,V)9*C16 FC/MC/PC48C 21 1400 42.0 29.8 13.50 11.00 P(C,V)9*C20 FC/MC/PC48C 21 1400 42.0 29.8 13.50 11.00 P(C,V)9*D20 FC/MC/PC48D 24 1400 42.0 29.8 13.50 11.00
PV8*C16 HC42 21 1400 42.0 29.8 13.50 11.00
PV8*C20 HC42 21 1400 41.0 30.0 13.50 11.00 P(C,V)9*C16 HC42 21 1400 42.0 29.6 13.50 11.00 P(C,V)9*C20 HC42 21 1400 41.0 29.8 13.50 11.00
PV8*C16 FC/MC/PC48C 21 1500 46.0 32.8 13.25 11.00
PV8*C20 FC/MC/PC48C 21 1600 46.0 32.8 13.30 11.00 P(C,V)9*C16 FC/MC/PC48C 21 1600 46.0 32.6 13.10 11.00 P(C,V)9*C20 FC/MC/PC48C 21 1600 46.0 32.8 13.10 11.00 P(C,V)9*D20 FC/MC/PC48D 24 1600 46.0 32.8 13.35 11.00
P V8*C20 FC/MC62D 21 1730 54.0 41.5 13.15 11.00 P(C,V)9*C20 FC/MC62D 21 1620 54.0 41.5 13.15 11.00 P(C,V)9*D20 FC/MC62D 24 1620 54.0 42.0 13.40 11.00
COIL
MODEL
1
W
RATED
CFM
Net MBH
TOTAL SENS.
2
400034-YTG-B-0708
COOLING
SEER EER
Johnson Controls Unitary Products 9
400034-YTG-B-0708
ACCESSORIES
Refer to Price Manual for specific model numbers. HARD START KIT - Required when using TXV indoor coil.
Also, provides increased starting torque for areas with low voltage.
Model Source 1 Kit numbers
12 S1-2SA06708606 18 S1-2SA06708606 24 S1-2SA06708706 30 S1-2SA06705906 36 S1-2SA06708106 42 S1-2SA06708106 48 S1-2SA06708806
OFF CYCLE TIMER DELAY - Provides a 5-minute off cycle to prevent rapid recycling of the compressor.
ROOM THERMOSTATS - A wide selection of compatible thermosets are available to provide optimum performance and features for any installation.
TYPICAL INSTALLATION
MINIMUM 18” SERVICE
60” OVERHEAD CLEARANCE
ACCESS CLEARANCE ON ONE SIDE
1H/1C, manual changeover electronic non-programmable thermostat.
1H/1C, auto/manual changeover, electronic programmable, deluxe 7-day, thermostat.
1H/1C, auto/manual changeover, electronic programmable. * For the most current accessory information, refer to the
price book or consult factory.
SOUND POWER RATINGS*
UNIT MODEL (dBA)
12 72 18 75 24 76 30 75 36 76 42 75 48 76 60 78
* Rated in accordance with ARI 270-95 Standards.
THERMOSTAT
WEATHERPROOF DISCONNECT SWITCH
NEC CLASS 1 WIRING
6” CLEARANCE AROUND PERIMETER
NOTE:
ALL OUTDOOR WIRING MUST BE WEATHERPROOF.
TYPICAL FIELD WIRING
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
POWER WIRING
208/230-1-60
CONTACTOR
GND.
LUG
TERMINALS
CONDENSING UNIT
ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.
COIL
24 VOLT CONTROL WIRING MINIMUM 18 GA. WIRE (NEC CLASS 2)
TO FURNACE OR AIR HANDLER TERMINAL BLOCK
NEC CLASS 2 WIRING
TO INDOOR COIL
CONTROL ACCESS PANEL
FURNACE OR AIR HANDLER TERMINAL BLOCK
CYRGW
SEAL OPENING(S) WITH PERMAGUM OR EQUIVALENT
R
Y
GW
ROOM THERMOSTAT
POWER WIRING CONTROL WIRING FACTORY WIRING
*
TERMINAL W IS ONLY REQUIRED ON SYSTEMS WITH HEAT.
*
10 Johnson Controls Unitary Products
400034-YTG-B-0708
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. TCGD12S21S2(H) INDOOR COIL MODEL NO. FC/MC/PC18
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE I NDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
HC18 1.00 1.00 1.00 – UC18 1.00 1.00 1.00 AHP18 0.98 0.97 0.98
IDCFM 450 600 750
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 11.3 11.9 12.1 13.1 14.1 11.7 12.4 12.3 13.2 14.1 12.1 12.9 12.6 13.2 14.1
S.C. 11.1 10.2 9.1 9.0 7.2 11.5 11.0 9.6 9.2 7.4 11.9 11.8 10.0 9.5 7.5
KW 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 T.C. 11.1 11.7 11.7 12.9 13.8 11.6 12.2 12.0 13.0 13.8 12.0 12.7 12.3 13.1 13.9 S.C. 10.9 10.4 9.1 9.0 7.2 11.4 11.2 9.6 9.4 7.4 11.8 11.9 10.1 9.8 7.7
KW 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 T.C. 10.9 11.6 11.4 12.6 13.5 11.4 12.1 11.7 12.8 13.6 11.9 12.6 11.9 13.0 13.7 S.C. 10.7 10.6 9.0 9.0 7.1 11.2 11.3 9.6 9.6 7.5 11.7 12.1 10.3 10.1 7.8
KW 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 T.C. 10.7 11.5 11.1 12.3 13.2 11.2 12.0 11.3 12.6 13.3 11.7 12.4 11.6 12.8 13.4 S.C. 10.5 10.8 9.0 9.0 7.1 11.0 11.5 9.7 9.7 7.5 11.5 12.2 10.4 10.4 7.9
KW 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 T.C. 10.0 10.9 10.2 11.5 12.5 10.6 11.4 10.5 11.8 12.7 11.1 11.9 10.9 12.0 12.9 S.C. 9.8 10.3 8.6 8.8 6.9 10.4 10.9 9.2 9.5 7.3 11.0 11.5 9.9 10.2 7.8
KW 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 T.C. 9.3 10.3 9.3 10.7 11.9 9.9 10.9 9.7 11.0 12.2 10.5 11.4 10.1 11.3 12.4 S.C. 9.2 9.9 8.2 8.6 6.7 9.8 10.3 8.8 9.3 7.2 10.4 10.8 9.4 10.0 7.6
KW 1.1 1.0 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 T.C. 8.6 9.7 8.4 9.9 11.2 9.3 10.3 8.9 10.2 11.6 9.9 10.9 9.4 10.5 11.9 S.C. 8.5 9.4 7.8 8.4 6.5 9.2 9.8 8.4 9.1 7.0 9.8 10.1 8.9 9.8 7.5
KW 1.1 1.1 1.1 1.2 1.2 1.2 1.1 1.1 1.2 1.2 1.2 1.2 1.1 1.2 1.2
Johnson Controls Unitary Products 11
400034-YTG-B-0708
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. TCGD18S21S2(H) INDOOR COIL MODEL NO. FC/MC/PC18
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
FC/MC/PC/UC24 1.00 1.00 1.00 – HC18 1.00 1.00 1.00 – UC18 1.00 1.00 1.00 AHP18 1.00 1.00 1.00 AHP24 1.00 1.00 1.00 AV24 1.00 1.03 0.91 F4FP024 1.00 1.00 1.00 MA08B FC/MC18B 1.00 1.00 1.00 MA08B FC/MC24B 1.00 1.00 1.00 MV12B FC/MC18B 1.00 1.03 0.91 MV12B FC/MC24B 1.00 1.03 0.91
IDCFM 450 600 750
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 15.4 17.1 16.7 18.1 18.0 16.2 17.6 17.2 18.2 18.0 17.0 18.2 17.6 18.3 18.0
S.C. 15.2 13.4 11.4 11.3 8.6 16.0 14.7 12.6 12.0 9.0 16.8 16.0 13.8 12.7 9.5
KW 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 T.C. 14.9 16.6 16.3 17.7 18.0 15.9 17.3 16.8 17.9 18.1 16.9 18.0 17.3 18.2 18.2
S.C. 14.7 13.4 11.3 11.1 8.5 15.7 14.9 12.7 12.1 9.2 16.7 16.4 14.1 13.1 9.8
KW 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 T.C. 14.4 16.1 15.8 17.3 18.0 15.6 17.0 16.3 17.7 18.2 16.8 17.8 16.9 18.1 18.4
S.C. 14.3 13.5 11.2 11.0 8.5 15.5 15.2 12.8 12.3 9.3 16.6 16.9 14.4 13.6 10.2
KW 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 T.C. 13.9 15.7 15.4 16.8 17.9 15.3 16.6 15.9 17.4 18.2 16.7 17.5 16.5 18.0 18.5
S.C. 13.8 13.5 11.1 10.8 8.5 15.2 15.4 12.9 12.4 9.5 16.5 17.3 14.7 14.0 10.5
KW 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 T.C. 13.2 14.6 14.2 15.9 17.2 14.6 15.7 14.9 16.5 17.5 16.0 16.8 15.5 17.1 17.8
S.C. 13.1 13.1 10.6 10.6 8.3 14.4 14.8 12.4 12.3 9.3 15.8 16.4 14.2 13.9 10.4
KW 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 T.C. 12.5 13.6 13.1 15.0 16.5 13.9 14.9 13.8 15.6 16.8 15.2 16.2 14.6 16.2 17.2
S.C. 12.4 12.6 10.1 10.3 8.1 13.7 14.1 11.9 12.1 9.2 15.1 15.7 13.7 13.8 10.2
KW 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 T.C. 11.8 12.6 12.0 14.2 15.7 13.2 14.1 12.8 14.8 16.1 14.5 15.5 13.6 15.3 16.5
S.C. 11.7 12.2 9.6 10.1 7.9 13.0 13.5 11.5 11.9 9.0 14.4 14.9 13.3 13.8 10.1
KW 1.7 1.7 1.7 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
Variable Speed Furnace
PV8*A12 FC/MC/PC18A 1.00 1.03 0.91 PV9*A12 FC/MC/PC18A 1.00 1.02 0.91 P(C,V)9*B12 FC/MC/PC18B 1.00 1.03 0.91 PV8*A12 FC/MC/PC24A 1.00 1.03 0.91 PV9*A12 FC/MC/PC24A 1.00 1.02 0.91 P(C,V)9*B12 FC/MC/PC24B 1.00 1.03 0.91 PV8*A12 HC18 1.00 1.03 0.91 PV9*A12 HC18 1.00 1.02 0.91
Coil T.C. S.C. KW
12 Johnson Controls Unitary Products
400034-YTG-B-0708
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. TCGD24S21S2(H) INDOOR COIL MODEL NO. FC/MC/PC36
CONDENSING
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE I NDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
FC/MC/PC32 1.00 1.00 1.00 – FC/MC/PC35 1.00 1.00 1.00 – FC/MC/PC37 1.00 1.00 1.00 – FC/MC/PC43 1.00 1.00 1.00 – HC30 1.00 1.00 1.00 – HC36 1.00 1.00 1.00 – HC42 1.00 1.00 1.00 – UC36 1.00 1.00 1.00 AHP30 1.00 1.00 1.00 AV36 1.00 1.04 0.88 F4FP036 1.00 1.00 1.00 MA08B FC/MC35B 1.00 1.00 1.00 MA08B FC/MC36B 1.00 1.00 1.00 MA08B FC/MC43B 1.00 1.00 1.00 MV12B FC/MC36B 1.00 1.03 0.88 MV12B FC/MC43B 1.00 1.03 0.88 MV12B FC/MC35B 1.00 1.03 0.88
IDCFM 600 800 1000
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 21.5 24.0 23.5 25.4 26.2 22.7 24.9 24.2 25.8 26.4 23.9 25.8 24.9 26.2 26.7 S.C. 21.3 19.0 16.1 15.7 12.2 22.5 21.5 17.8 17.3 12.9 23.7 24.1 19.5 18.9 13.6
KW 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 T.C. 20.6 23.0 22.5 24.7 26.0 22.1 24.1 23.3 25.3 26.3 23.5 25.2 24.1 25.8 26.6 S.C. 20.4 18.7 15.7 15.5 12.1 21.9 21.4 17.6 17.3 13.0 23.3 24.0 19.5 19.1 13.9
KW 1.4 1.4 1.4 1.4 1.5 1.4 1.4 1.4 1.5 1.5 1.4 1.4 1.4 1.5 1.5 T.C. 19.7 22.0 21.4 23.9 25.7 21.4 23.3 22.4 24.7 26.1 23.2 24.7 23.3 25.5 26.5 S.C. 19.5 18.3 15.3 15.3 12.0 21.2 21.2 17.5 17.3 13.1 22.9 24.0 19.6 19.4 14.2
KW 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 T.C. 18.8 21.0 20.4 23.2 25.5 20.8 22.5 21.4 24.2 26.0 22.8 24.1 22.5 25.2 26.4 S.C. 18.6 18.0 14.9 15.1 11.9 20.6 21.0 17.3 17.3 13.2 22.6 24.0 19.7 19.6 14.5
KW 1.7 1.7 1.7 1.7 1.8 1.7 1.7 1.7 1.8 1.8 1.8 1.7 1.7 1.8 1.8 T.C. 17.9 19.5 18.8 21.7 24.0 19.8 21.2 19.9 22.6 24.5 21.7 22.9 21.0 23.6 25.0 S.C. 17.8 17.4 14.2 14.6 11.5 19.7 19.9 16.6 16.9 12.9 21.6 22.5 19.1 19.2 14.4
KW 1.9 1.9 1.9 1.9 2.0 1.9 1.9 1.9 2.0 2.0 2.0 2.0 1.9 2.0 2.0 T.C. 17.1 18.2 17.3 20.2 22.5 18.9 20.0 18.4 21.1 23.1 20.8 21.8 19.5 22.0 23.6 S.C. 16.9 16.7 13.5 14.0 11.1 18.8 18.9 16.0 16.4 12.6 20.6 21.0 18.5 18.8 14.2
KW 2.1 2.1 2.1 2.1 2.2 2.1 2.1 2.1 2.1 2.2 2.2 2.2 2.1 2.2 2.2
Variable Speed Furnace
PV8*A12 FC/MC/PC32A 1.00 1.02 0.88 PV9*A12 FC/MC/PC32A 1.00 1.02 0.88 P(C,V)9*B12 FC/MC/PC35B 1.00 1.02 0.88 PV8*A12 FC/MC/PC36A 1.00 1.02 0.88 PV9*A12 FC/MC/PC36A 1.00 1.02 0.88 P(C,V)9*B12 FC/MC/PC36B 1.00 1.02 0.88 PV8*A12 FC/MC/PC37A 1.00 1.02 0.88 PV9*A12 FC/MC/PC37A 1.00 1.02 0.88 P(C,V)9*B12 FC/MC/PC43B 1.00 1.02 0.88 PV8*A12 HC30 1.00 1.02 0.88 PV9*A12 HC30 1.00 1.02 0.88 P(C,V)9*B12 HC36 1.00 1.02 0.88
Coil T.C. S.C. KW
Johnson Controls Unitary Products 13
400034-YTG-B-0708
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. TCGD30S21S2(H) INDOOR COIL MODEL NO. FC/MC/PC35
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
IDCFM 800 1000 1200
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 27.8 29.9 29.6 30.6 31.8 29.2 30.1 29.7 30.8 31.8 30.6 30.4 29.8 31.1 31.8
S.C. 27.2 24.5 20.5 19.0 14.8 28.2 26.1 21.6 20.0 15.4 29.1 27.7 22.6 21.0 15.9
KW 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.7 T.C. 26.2 28.2 27.9 29.7 31.2 28.0 28.9 28.2 30.0 31.2 29.9 29.5 28.6 30.3 31.2
S.C. 25.7 23.9 20.0 19.1 14.9 27.0 25.8 21.5 20.5 15.7 28.3 27.6 22.9 21.8 16.5
KW 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 T.C. 24.6 26.5 26.1 28.8 30.5 26.9 27.6 26.7 29.2 30.6 29.2 28.6 27.3 29.5 30.6
S.C. 24.1 23.3 19.4 19.2 14.9 25.8 25.4 21.4 20.9 16.0 27.4 27.5 23.3 22.7 17.1
KW 1.9 1.9 1.9 2.0 2.0 1.9 1.9 1.9 2.0 2.0 2.0 2.0 1.9 2.0 2.0 T.C. 23.0 24.9 24.4 28.0 29.8 25.7 26.3 25.3 28.4 29.9 28.4 27.7 26.1 28.7 30.0
S.C. 22.6 22.8 18.9 19.3 15.0 24.6 25.1 21.3 21.4 16.3 26.6 27.5 23.7 23.5 17.7
KW 2.1 2.1 2.1 2.1 2.2 2.1 2.1 2.1 2.1 2.2 2.1 2.1 2.1 2.1 2.2 T.C. 21.5 23.1 22.1 25.6 27.7 24.1 24.5 23.0 26.0 28.0 26.6 26.0 23.9 26.4 28.3
S.C. 21.2 21.3 17.9 18.5 14.3 23.0 23.4 20.0 20.6 15.8 24.8 25.5 22.1 22.7 17.2
KW 2.3 2.3 2.2 2.3 2.4 2.3 2.3 2.3 2.3 2.4 2.3 2.3 2.3 2.3 2.4 T.C. 20.1 21.4 19.8 23.2 25.5 22.5 22.9 20.8 23.7 26.0 24.9 24.3 21.8 24.1 26.5
S.C. 19.8 19.9 16.9 17.7 13.7 21.4 21.8 18.7 19.8 15.2 23.1 23.6 20.6 22.0 16.8
KW 2.4 2.4 2.4 2.5 2.5 2.5 2.5 2.4 2.5 2.6 2.5 2.5 2.5 2.5 2.6 T.C. 18.7 19.7 17.6 20.9 23.4 20.9 21.2 18.6 21.4 24.1 23.1 22.7 19.7 21.9 24.8
S.C. 18.4 18.6 15.9 16.8 13.1 19.9 20.1 17.5 19.0 14.7 21.4 21.7 19.1 21.3 16.4
KW 2.6 2.6 2.5 2.6 2.7 2.6 2.6 2.6 2.7 2.7 2.7 2.7 2.6 2.7 2.8
Air Handler Coil T.C. S.C. KW
FC/MC/PC32 1.00 1.00 1.00 – FC/MC/PC37 1.00 1.00 1.00 – FC/MC/PC43 1.00 1.00 1.00 – HC36 1.00 1.00 1.00 – HC42 1.00 1.00 1.00 AHP30 1.00 1.00 1.00 AHP36 1.00 1.00 1.00 AV36 1.02 1.03 0.89 F4FP040 1.00 1.00 1.00 MA12B FC/MC35B 1.00 1.00 1.00 MA12B FC/MC43B 1.00 1.00 1.00 MV12B FC/MC43B 1.02 1.02 0.89 MV16C FC/MC43C 1.02 1.02 0.89 MV12B FC/MC35B 1.02 1.02 0.89 MV16C FC/MC35C 1.02 1.02 0.89
Variable Speed Furnace
PV8*A12 FC/MC/PC32A 1.00 1.00 0.91 PV9*A12 FC/MC/PC32A 1.00 1.00 0.91 PV8*B16 FC/MC/PC35B 1.02 1.02 0.89 PV8*C16 FC/MC/PC35C 1.02 1.02 0.89 PV8*C20 FC/MC/PC35B 1.02 1.03 0.89 P(C,V)9*B12 FC/MC/PC35C 1.02 1.01 0.89 PV9*A12 FC/MC/PC35A 1.00 1.00 0.91 PV8*A12 FC/MC/PC37A 1.02 1.02 0.89 PV9*A12 FC/MC/PC37A 1.02 1.02 0.89 PV8*B16 FC/MC/PC43B 1.02 1.02 0.89 PV8*C16 FC/MC/PC43C 1.02 1.02 0.89 PV8*C20 FC/MC/PC43C 1.02 1.03 0.89 P(C,V)9*B12 FC/MC/PC43B 1.02 1.01 0.89 P(C,V)9*C16 FC/MC/PC43C 1.02 1.01 0.89 P(C,V)9*C20 FC/MC/PC43C 1.02 1.01 0.89 PV8*B16 HC36 1.02 1.02 0.89 P(C,V)9*B12 HC36 1.02 1.01 0.89 PV8*C16 HC42 1.02 1.03 0.89 PV8*C20 HC42 1.02 1.03 0.89 P(C,V)9*C16 HC42 1.02 1.01 0.89 P(C,V)9*C20 HC42 1.02 1.01 0.89
Coil T.C. S.C. KW
14 Johnson Controls Unitary Products
400034-YTG-B-0708
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. TCGD36S21S2(H) INDOOR COIL MODEL NO. FC/MC/PC43
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE I NDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
FC/MC/PC37A 1.00 1.00 1.00 – FC/MC/PC/UC48 1.00 1.00 1.00 – HC42 1.00 1.00 1.00 AHP36 1.00 1.00 1.00 AV36 1.01 1.02 0.92 F5FP048 1.00 1.00 1.00 MA12B FC/MC43B 1.00 1.00 1.00 MA14D FC/MC48D 1.00 1.00 1.00 MV16C FC/MC43C 1.01 1.02 0.92 MV16C FC/MC48C 1.01 1.03 0.92 MV20D FC/MC48D 1.01 1.03 0.92 MV12D FC/MC48D 1.01 1.03 0.92
IDCFM 1000 1200 1400
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 35.6 36.1 34.4 37.6 38.5 37.2 37.4 35.5 38.5 38.9 38.9 38.6 36.7 39.4 39.2 S.C. 32.9 29.4 24.0 23.3 17.9 34.4 31.7 25.4 24.7 18.3 35.9 34.0 26.7 26.2 18.7
KW 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
T.C. 33.6 34.4 32.7 36.1 37.2 36.0 36.0 34.0 37.1 37.6 38.3 37.6 35.2 38.2 38.0 S.C. 31.2 29.0 23.6 23.0 17.5 33.1 31.4 25.3 24.8 18.1 35.0 33.9 27.0 26.5 18.7
KW 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.3
T.C. 31.6 32.6 31.1 34.6 35.9 34.7 34.6 32.4 35.8 36.3 37.8 36.6 33.7 37.0 36.8 S.C. 29.6 28.6 23.2 22.8 17.1 31.9 31.2 25.3 24.8 17.9 34.2 33.8 27.3 26.8 18.7
KW 2.3 2.3 2.3 2.4 2.5 2.4 2.4 2.4 2.4 2.5 2.4 2.4 2.4 2.4 2.5
T.C. 29.7 30.9 29.4 33.1 34.5 33.4 33.2 30.8 34.4 35.1 37.2 35.6 32.3 35.8 35.6 S.C. 27.9 28.2 22.8 22.5 16.6 30.6 30.9 25.2 24.8 17.7 33.3 33.7 27.6 27.1 18.7
KW 2.5 2.5 2.5 2.6 2.7 2.5 2.5 2.5 2.6 2.7 2.6 2.6 2.5 2.6 2.7 T.C. 28.0 28.6 26.6 30.1 31.4 30.9 30.7 27.9 31.4 32.0 33.9 32.8 29.2 32.6 32.5 S.C. 25.9 26.3 21.6 21.5 15.6 28.2 28.6 23.8 23.7 16.7 30.4 30.9 26.0 25.9 17.8
KW 2.7 2.7 2.7 2.8 2.9 2.7 2.7 2.7 2.8 2.9 2.8 2.8 2.7 2.8 2.9 T.C. 26.3 26.4 23.9 27.3 28.4 28.6 28.3 25.1 28.5 28.9 30.8 30.1 26.3 29.6 29.5 S.C. 24.0 24.5 20.4 20.4 14.6 25.8 26.3 22.4 22.5 15.8 27.6 28.2 24.4 24.6 17.0
KW 2.9 2.9 2.9 3.0 3.1 2.9 2.9 2.9 3.0 3.1 3.0 3.0 2.9 3.0 3.1 T.C. 24.7 24.2 21.2 24.5 25.3 26.2 25.8 22.3 25.5 25.9 27.6 27.4 23.4 26.6 26.5 S.C. 22.1 22.7 19.3 19.4 13.5 23.4 24.1 21.1 21.4 14.9 24.8 25.5 22.8 23.4 16.2
KW 3.1 3.1 3.1 3.1 3.2 3.1 3.1 3.1 3.2 3.3 3.2 3.2 3.1 3.2 3.3
Variable Speed Furnace
PV8*A12 FC/MC/PC37A 1.01 1.02 0.92 PV9*A12 FC/MC/PC37A 1.01 1.02 0.92 PV8*B16 FC/MC/PC43B 1.01 1.02 0.92 PV8*C16 FC/MC/PC43C 1.01 1.02 0.92 PV8*C20 FC/MC/PC43C 1.01 1.02 0.92 P(C,V)9*B12 FC/MC/PC43B 1.00 1.01 0.91 P(C,V)9*C16 FC/MC/PC43C 1.01 1.02 0.92 P(C,V)9*C20 FC/MC/PC43C 1.01 1.02 0.92 PV8*C16 FC/MC/PC48C 1.01 1.02 0.92 PV8*C20 FC/MC/PC48C 1.01 1.02 0.92 P(C,V)9*C16 FC/MC/PC48C 1.01 1.02 0.92 P(C,V)9*C20 FC/MC/PC48C 1.01 1.02 0.92 P(C,V)9*D20 FC/MC/PC48D 1.01 1.02 0.92 PV8*C16 HC42 1.01 1.02 0.92 PV8*C20 HC42 1.01 1.02 0.92 P(C,V)9*C16 HC42 1.01 1.02 0.88 P(C,V)9*C20 HC42 1.01 1.02 0.92
Coil T.C. S.C. KW
Johnson Controls Unitary Products 15
400034-YTG-B-0708
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. TCGD42S21S2(H) INDOOR COIL MODEL NO. FC/MC/PC43
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
FC/MC/PC/UC48 1.00 1.00 1.00 – HC42 1.00 1.00 1.00 AHP42 1.00 1.00 1.00 F5FP048 1.00 1.00 1.00 MA16C FC/MC43C 1.00 1.00 1.00 MA14D FC/MC48D 1.00 1.00 1.00 MA16C FC/MC48C 1.00 1.00 1.00 MV16C FC/MC43C 1.01 1.02 0.88 MV16C FC/MC48C 1.01 1.02 0.88 MV20D FC/MC48D 1.01 1.02 0.88
IDCFM 1200 1400 1600
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 39.7 42.3 41.6 45.1 46.3 41.4 43.5 42.3 45.7 46.7 43.1 44.7 43.0 46.2 47.0
S.C. 38.2 34.5 28.8 27.9 21.2 39.3 36.8 30.2 29.0 21.5 40.4 39.0 31.6 30.0 21.9
KW 2.2 2.3 2.2 2.3 2.3 2.2 2.3 2.3 2.3 2.3 2.2 2.3 2.3 2.3 2.3 T.C. 38.1 40.6 39.7 43.7 45.1 40.1 42.0 40.5 44.4 45.5 42.0 43.4 41.3 45.2 45.9
S.C. 36.8 34.3 28.4 27.9 21.0 38.0 36.5 30.0 29.2 21.6 39.3 38.7 31.7 30.6 22.1
KW 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6 T.C. 36.5 38.9 37.7 42.3 43.9 38.7 40.5 38.6 43.2 44.4 40.9 42.0 39.5 44.1 44.9
S.C. 35.4 34.1 27.9 27.8 20.8 36.8 36.3 29.8 29.5 21.6 38.2 38.5 31.7 31.2 22.4
KW 2.7 2.7 2.7 2.7 2.8 2.7 2.7 2.7 2.8 2.8 2.7 2.7 2.7 2.8 2.8 T.C. 35.0 37.2 35.8 40.9 42.7 37.4 39.0 36.8 42.0 43.3 39.8 40.7 37.8 43.1 43.8
S.C. 33.9 33.8 27.4 27.7 20.7 35.5 36.0 29.6 29.8 21.6 37.1 38.2 31.8 31.8 22.6
KW 2.9 2.9 2.9 3.0 3.1 2.9 2.9 2.9 3.0 3.1 3.0 3.0 3.0 3.0 3.1 T.C. 33.7 34.8 32.6 38.0 39.5 35.6 36.4 33.7 38.9 40.1 37.5 38.0 34.8 39.8 40.7
S.C. 31.9 31.9 26.1 26.5 19.4 33.2 33.7 28.2 28.5 20.6 34.6 35.5 30.3 30.6 21.7
KW 3.2 3.2 3.2 3.2 3.3 3.2 3.2 3.2 3.2 3.3 3.2 3.2 3.2 3.3 3.3 T.C. 32.4 32.5 29.5 35.1 36.5 33.8 33.9 30.7 35.9 37.1 35.1 35.4 31.8 36.6 37.7
S.C. 29.9 30.0 24.8 25.3 18.2 31.0 31.5 26.8 27.3 19.5 32.1 33.0 28.8 29.4 20.8
KW 3.4 3.4 3.4 3.5 3.6 3.4 3.4 3.4 3.5 3.6 3.5 3.5 3.4 3.5 3.6 T.C. 31.1 30.1 26.4 32.3 33.4 32.0 31.4 27.6 32.8 34.0 32.8 32.8 28.9 33.4 34.7
S.C. 27.9 28.1 23.5 24.1 17.0 28.8 29.2 25.4 26.1 18.5 29.7 30.4 27.4 28.2 20.0
KW 3.7 3.6 3.6 3.7 3.8 3.7 3.7 3.6 3.7 3.8 3.7 3.7 3.7 3.7 3.9
Variable Speed Furnace
PV8*C20 FC/MC/PC43C 0.98 1.01 0.89 PV8*C16 FC/MC/PC48C 1.00 1.01 0.91 PV8*C20 FC/MC/PC48C 0.98 1.02 0.89 P(C,V)9*C16 FC/MC/PC48C 1.00 1.01 0.91 P(C,V)9*C20 FC/MC/PC48C 1.00 1.01 0.91 P(C,V)9*D20 FC/MC/PC48D 1.00 1.01 0.91 PV8*C16 HC42 1.00 1.01 0.91 PV8*C20 HC42 0.98 1.02 0.89 P(C,V)9*C16 HC42 1.00 1.00 0.91 P(C,V)9*C20 HC42 0.98 1.01 0.89
Coil T.C. S.C. KW
16 Johnson Controls Unitary Products
400034-YTG-B-0708
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. TCGD48S21S2(H) INDOOR COIL MODEL NO. FC/MC/PC48
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE I NDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
UC48 1.00 1.00 1.00 AHP/SHP60 1.00 1.01 1.00 AV/SV48 0.98 1.01 0.89 F5FP048 1.00 1.00 1.00 F5FP060 1.00 1.00 1.00 F4FV060 0.98 1.01 0.89 MA16C FC/MC48C 1.00 1.00 1.00 MA20D FC/MC48D 1.00 1.00 1.00 MV16C FC/MC48C 0.98 1.01 0.89 MV20D FC/MC48D 1.00 1.01 0.91
IDCFM 1400 1600 1800
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 48.0 48.3 46.7 49.9 49.6 49.2 49.1 47.2 50.1 50.1 50.3 49.9 47.6 50.4 50.6 S.C. 44.6 41.2 33.8 31.6 23.5 45.9 43.6 35.3 32.6 24.3 47.3 46.0 36.9 33.7 25.1
KW 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.6
T.C. 45.5 45.5 43.7 47.8 48.4 46.8 46.5 44.3 48.4 49.0 48.1 47.6 45.0 49.0 49.5 S.C. 42.2 40.0 32.7 31.3 23.3 43.7 42.3 34.5 32.8 24.2 45.2 44.7 36.3 34.2 25.1
KW 2.7 2.7 2.7 2.8 2.8 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.9
T.C. 43.0 42.6 40.6 45.6 47.3 44.5 44.0 41.5 46.6 47.8 45.9 45.4 42.4 47.6 48.3 S.C. 39.9 38.8 31.7 31.0 23.1 41.5 41.1 33.7 32.9 24.1 43.1 43.4 35.6 34.8 25.1
KW 3.0 3.0 3.0 3.1 3.1 3.0 3.0 3.0 3.1 3.1 3.0 3.0 3.0 3.1 3.2
T.C. 40.5 39.8 37.6 43.5 46.1 42.1 41.5 38.7 44.8 46.7 43.7 43.1 39.7 46.2 47.2 S.C. 37.5 37.5 30.7 30.7 22.9 39.3 39.8 32.8 33.0 24.0 41.0 42.1 34.9 35.4 25.1
KW 3.2 3.2 3.2 3.3 3.4 3.2 3.2 3.2 3.3 3.4 3.3 3.3 3.3 3.4 3.5 T.C. 37.7 36.8 34.1 40.1 42.6 39.2 38.3 35.1 41.2 43.1 40.6 39.8 36.2 42.4 43.5 S.C. 34.8 35.0 29.1 29.4 21.4 36.3 36.9 30.9 31.7 22.7 37.9 38.8 32.7 33.9 23.9
KW 3.5 3.5 3.5 3.6 3.7 3.5 3.5 3.5 3.6 3.7 3.6 3.6 3.5 3.6 3.7 T.C. 35.0 33.9 30.7 36.8 39.2 36.3 35.3 31.7 37.8 39.6 37.5 36.6 32.7 38.7 40.0 S.C. 32.1 32.5 27.4 28.1 20.0 33.5 34.1 29.0 30.3 21.4 34.9 35.6 30.6 32.6 22.7
KW 3.7 3.8 3.7 3.8 4.0 3.8 3.8 3.7 3.8 4.0 3.8 3.8 3.8 3.9 4.0 T.C. 32.3 31.0 27.4 33.5 35.8 33.4 32.2 28.3 34.3 36.1 34.5 33.5 29.3 35.0 36.5 S.C. 29.5 30.0 25.8 26.8 18.6 30.7 31.2 27.1 29.0 20.1 31.9 32.5 28.4 31.2 21.5
KW 4.0 4.0 4.0 4.1 4.2 4.0 4.1 4.0 4.1 4.2 4.1 4.1 4.0 4.1 4.3
Variable Speed Furnace
PV8*C16 FC/MC/PC48C 1.00 1.00 0.91 PV8*C20 FC/MC/PC48C 1.00 1.00 0.91 P(C,V)9*C16 FC/MC/PC48C 1.00 1.00 1.00 P(C,V)9*C20 FC/MC/PC48C 1.00 1.00 1.00 P(C,V)9*D20 FC/MC/PC48D 1.00 1.00 0.91
Coil T.C. S.C. KW
Johnson Controls Unitary Products 17
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. TCGD60S21S2 INDOOR COIL MODEL NO. FC/MC62
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler Coil T.C. S.C. KW
MA20D FC/MC62D 1.00 1.01 1.00 MV20D FC/MC62D 1.00 1.01 1.00
IDCFM 1750 2000 2250
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 57.5 58.5 57.1 62.2 60.7 59.2 60.1 58.2 63.4 62.8 61.0 61.6 59.3 64.5 64.9
S.C. 54.4 51.6 42.7 41.3 29.2 55.9 54.9 45.2 43.3 30.4 57.3 58.1 47.6 45.4 31.6
KW 2.9 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.1 3.0 3.0 3.0 3.0 3.1 T.C. 55.4 56.6 54.6 60.1 59.4 57.4 58.3 55.7 61.2 60.1 59.4 60.0 56.8 62.3 60.8
S.C. 52.4 50.5 41.7 40.7 28.8 53.9 53.4 44.2 43.0 30.0 55.5 56.2 46.7 45.3 31.2
KW 3.3 3.3 3.3 3.4 3.5 3.4 3.4 3.4 3.4 3.5 3.4 3.4 3.4 3.4 3.5 T.C. 53.3 54.7 52.1 58.0 58.1 55.5 56.6 53.1 59.0 57.3 57.7 58.4 54.2 60.1 56.6
S.C. 50.3 49.4 40.6 40.1 28.4 52.0 51.9 43.2 42.6 29.6 53.7 54.4 45.8 45.1 30.8
KW 3.7 3.7 3.7 3.8 3.9 3.8 3.8 3.7 3.8 3.9 3.8 3.8 3.8 3.8 3.9 T.C. 51.3 52.7 49.6 56.0 56.7 53.7 54.8 50.6 56.9 54.6 56.1 56.9 51.6 57.8 52.5
S.C. 48.2 48.3 39.5 39.6 28.0 50.0 50.4 42.2 42.3 29.2 51.8 52.6 44.9 45.0 30.4
KW 4.1 4.1 4.1 4.2 4.3 4.2 4.1 4.1 4.2 4.3 4.2 4.2 4.2 4.3 4.4 T.C. 49.1 49.5 45.8 51.8 52.6 51.3 51.4 46.8 52.7 50.5 53.6 53.2 47.8 53.6 48.4
S.C. 45.2 45.4 37.8 38.0 26.8 46.9 47.3 40.3 40.6 28.1 48.5 49.2 42.8 43.3 29.4
KW 4.6 4.6 4.6 4.7 4.9 4.7 4.7 4.7 4.7 4.9 4.7 4.7 4.7 4.8 4.9 T.C. 47.1 46.4 42.2 47.8 48.5 49.1 48.1 43.2 48.7 46.5 51.1 49.7 44.2 49.5 44.5
S.C. 42.3 42.6 36.2 36.4 25.8 43.8 44.3 38.5 39.0 27.1 45.3 45.9 40.7 41.6 28.5
KW 5.2 5.2 5.1 5.2 5.4 5.2 5.2 5.2 5.3 5.4 5.2 5.2 5.2 5.3 5.4 T.C. 45.0 43.3 38.6 43.8 44.5 46.9 44.8 39.6 44.6 42.5 48.7 46.2 40.5 45.4 40.6
S.C. 39.4 39.9 34.5 34.9 24.7 40.8 41.2 36.6 37.4 26.1 42.1 42.6 38.7 40.0 27.5
KW 5.7 5.7 5.6 5.7 5.9 5.7 5.7 5.7 5.8 5.9 5.7 5.7 5.7 5.8 5.9
Variable Speed Furnace
PV8*C20 FC/MC62D 1.00 1.01 1.00 P(C,V)9*C20 FC/MC62D 0.98 1.01 0.98 P(C,V)9*D20 FC/MC62D 1.00 1.02 1.00
Coil T.C. S.C. KW
Subject to change without notice. Printed in U.S.A. 400034-YTG-B-0708 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 400034-YTG-A-0408
Johnson Controls Unitary Products