DESCRIPTION
The 13 SEER Series condensing unit is the outdoor part of a
versatile system of air conditioning. It is designed to be custom-matched with one of UPG’s complete line of evaporator
sections, with each serving a specific function. Matching Air
Handlers are available for upflow, downflow, or horizontal
applications to provide a complete system. Electric Heaters
are available, if required. Add-on coils are available for use
with upflow, downflow, or horizontal furnaces and air handlers.
WARRANTY
Single Phase Units:
5-year limited parts warranty.
5-year limited compressor warranty.
FEATURES
• QUALITY CONDENSER COILS - The coil is constructed
of aluminum microchannel tubing and enhanced aluminum
fins for increased efficiency and corrosion protection.
• PROTECTED COMPRESSOR - The compressor is internally protected against high pressure, temperature, and
externally by a factory installed high pressure switch. This
is accomplished by the simultaneous operation of high
pressure relief valve and a temperature sensor which protects the compressor if undesirable operating conditions
occur. A liquid line filter-drier further protects the compressor.
• DURABLE FINISH - The cabinet is made of pre-painted
steel. The pre-treated galvanized steel provides a better
paint to steel bond, which resists corrosion and rust creep.
Special primer formulas and matted-textured finish insure
less fading when exposed to sunlight.
• LOWER INSTALLED COST - Installation time and costs
are reduced by easy power and control wiring connections. Available in sweat connect models only. The unit
contains enough refrigerant for matching indoor coils and
15 feet of interconnecting piping. The small base dimension means less space is required on the ground or roof.
• TOP DISCHARGE - The warm air from the top mounted
fan is blown up away from the structure and any landscaping. This allows compact location on multi-unit applications.
• LOW OPERATING SOUND LEVEL - The upward air flow
carries the normal operating noise away from the living
area. The rigid top panel effectively isolates any motor
sound. Isolator mounted compressor and the rippled fins
of the condenser coil muffle the normal fan motor and
compressor operating sounds.
• LOW MAINTENANCE - Long life permanently lubricated
motor-bearings need no annual servicing.
• EASY SERVICE ACCESS - Fully exposed refrigerant connections, and a single panel covering the electrical controls make for easy servicing of the unit.
• SECURED SERVICE VALVES - Secured re-usable ser-
vice valves are provided on both the liquid and vapor
sweat connections for ease of evacuating and charging.
• U.L. and C.U.L. listed - approved for outdoor application.
Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
Page 2
359315-YTG-B-0408
Physical and Electrical Data
MODEL
TCGD18
S41S1(H)
TCGD24
S41S1(H)
TCGD30
S41S1(H)
TCGD36
S41S1(H)
TCGD42
S41S1(H)
TCGD48
S41S1(H)
TCGD60
S41S1
Unit Supply Voltage208-230V, 1φ, 60Hz
Normal Voltage Range
Compressor Type RotaryRecipRecipRecipRecipRecipScroll
Compressor Amps
Rated Load7.6 9.3 10.6 13.1 16.0 15.7 26.2
Locked Rotor 40.0 43.0 54.0 74 84 84 150
Crankcase HeaterNo No No No No No No
Fan Motor Amps Rated Load0.5 0.8 1.4 1.5 1.5 1.5 1.5
Fan Diameter Inches17.5 17.5 17.5 22 22 22 24
Rated HP1/12 1/8 1/4 1/4 1/4 1/4 1/4
Fan Motor
Nominal RPM1100 1075 1100 850 850 850 850
Nominal CFM 1400 1950 2050 3200 2950 2950 3600
Face Area Sq. Ft.9.60 9.60 9.60 13.07 14.16 14.16 18.68
Coil
Rows Deep 1 1 1 1 1 1 1
Fin / Inches23 23 23 23 23 23 23
Liquid Line Set OD (Field Installed)3/8 3/8 3/8 3/8 3/8 3/8 3/8
Vapor Line Set OD (Field Installed)5/8 3/4 3/4 3/4 7/8 7/8 7/8
Models with “H” on the end of the model number have a factory installed start kits.
1.Rated in accordance with ARI Standard 110, utilization range “A”.
2.Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3.Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15
feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
All dimensions are in inches. They are subject to change
without notice. Certified dimensions will be provided upon
1.For applications requiring a TXV use 1TVM900 series kit.
2.Approved orifice shipped with outdoor unit.
3.Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit
2FD06700224.
4.PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of interconnecting line tubing.
2. Verify the TXV or orifice and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical
Data Table.
4. For TXV match charge weight needs to be weighed in for specififc coil match and lineset length.
5. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for
evaporator + adder for line set.
Models 12-48 require start kits for TXV matches. Models with “H” on the end of the model number have factory installed start kits.
For models without an “H” refer to tech guide for kit number reference.
F*FP Air Handlers come with a factory installed R-22 TXV which MUST BE CHANGED OUT to R-410A TXV or an orifice for proper operation. If the TXV is not changed out system damage will occur.
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210.
Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power
input in watt-hours during the same period.
AHP/SHP60 24 –1850 57.0 38.5 13.00 11.00
F5FP060 24 –1900 57.0 38.5 13.00 11.00
COOLING
NET MBH
SEEREER
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
— = Not applicable.
6Johnson Controls Unitary Products
Page 7
COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils
FURNACE**
UNIT MODEL
TCGD18S41S1(H)
TCGD24S41S1(H)
TCGD30S41S1(H)
TCGD36S41S1(H)
TCGD42S41S1(H)
TCGD48S41S1(H)
TCGD60S41S1
1. Requires a 2FD06700224 Blower Time Delay unless a standard furnace is equipped with one.
** Refer to Quick Selection Chart for specific furnace match-up.
1H/1C, auto/manual changeover, electronic programmable.
* For the most current accessory information, refer to the
price book or consult factory.
SOUND POWER RATINGS*
UNIT MODEL(dBA)
1875
2476
3076
3676
4276
4877
60TBD
* Rated in accordance with ARI 270-95 Standards.
THERMOSTAT
WEATHERPROOF
DISCONNECT
SWITCH
NEC CLASS 1 WIRING
6” CLEARANCE
AROUND PERIMETER
NOTE:
ALL OUTDOOR WIRING
MUST BE WEATHERPROOF.
TYPICAL FIELD WIRING
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
POWER WIRING
208/230-1-60
CONTACTOR
TERMINALS
GND.
LUG
CONDENSING UNIT
ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.
COIL
24 VOLT CONTROL WIRING
MINIMUM 18 GA. WIRE
(NEC CLASS 2)
TO FURNACE OR
AIR HANDLER
TERMINAL BLOCK
NEC CLASS 2 WIRING
TO INDOOR COIL
CONTROL
ACCESS
PANEL
FURNACE OR AIR HANDLER TERMINAL BLOCK
CYRGW
SEAL OPENING(S) WITH
PERMAGUM OR EQUIVALENT
R
Y
ROOM THERMOSTAT
GW
POWER WIRING
CONTROL WIRING
FACTORY WIRING
*
TERMINAL W IS ONLY
REQUIRED ON SYSTEMS
WITH HEAT.
*
10Johnson Controls Unitary Products
Page 11
359315-YTG-B-0408
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.TCGD18S41S1(H)
INDOOR COIL MODEL NO.FC/MC/PC18
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE I NDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
AIR CONDITIONER MODEL NO.TCGD24S41S1(H)
INDOOR COIL MODEL NO.FC/MC/PC36
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
AIR CONDITIONER MODEL NO.TCGD30S41S1(H)
INDOOR COIL MODEL NO.FC/MC/PC35
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE I NDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
AIR CONDITIONER MODEL NO.TCGD36S41S1(H)
INDOOR COIL MODEL NO.FC/MC/PC43
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
AIR CONDITIONER MODEL NO.TCGD42S41S1(H)
INDOOR COIL MODEL NO.FC/MC/PC43
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE I NDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
AIR CONDITIONER MODEL NO.TCGD48S41S1(H)
INDOOR COIL MODEL NO.FC/MC/PC48
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
AIR CONDITIONER MODEL NO.TCGD60S41S1(H)
INDOOR COIL MODEL NO.FC/MC/PC60
CONDENSING
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
NOTE: ALL CAPACITIES INCLUDE I NDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.