York SHP48, AHP18, 60 User Manual

TECHNICAL GUIDE
SINGLE PIECE AIR HANDLERS FOR USE WITH SPLIT -SYSTEM
COOLING & HEAT PUMPS
MODELS: AHP18 THRU 60 AND SHP48 THRU 60
255029-YTG-J-1007
DESCRIPTION
This fan coil line offers the ultimate in application flexibility. The AHP (non-variable speed motor) models can be ordered upflow only or as multi-position. The multi-position model can be installed in downflow, upflow, horizontal right or left without the need for additional field installed kits.
The SHP 48 & 60 models are upflow only models designed into a shorter cabinet than the AHP version, for those special applications where reduced height is required.
All UPG air handlers and coils utilize a TXV to provide our customers with the optimum performance and refrigerant control required for 13+ systems. Air handlers can be ordered with a R22 TXV factory installed that can be easily converted to R410A by changing the bolt-on TXV. Air handlers are also available with “Flex-coils” without a factory installed metering device. For added flexibility, an R22 or R410A TXV can be field installed to meet your refrigerant choice.
FEATURES
Thermal Expansion Valve - Provides the ultimate refrigerant
control required for today’s high efficient product. The UPG bolt-on TXV provides the added flexibility to co nvert the air handler to the required refrigerant. The UPG TXV is a true bolt-on which does not require brazing to replace or install.
MicroBlue
with the MicroBlue removal of condensate during the refrigeration cycle and reduce the possibility of water blow-off. The MicroBlue coating also reduces the growth of germ causing microbes for a healthier home environment.
Insulated Cabinet - All air handler cabinets are thermally insulated with 1” foil faced insulation (R-4.2) to prevent sweating. For applications in extreme humidity conditions an optional, field installed, external insulating wrap kit is also available.
Durable Finish Inside and Out - Air handler casings are made of pre-painted galvanized steel which provides a better paint to steel bond that resists corrosion and rust creep. All internal coil sheet metal parts are made of G90 pre-painted steel (i.e. triangular plates, top plates, horizontal supports etc). Coil header plates are not painted due to the brazing process during production. The coil header plates are treated after the brazing process with a corrosion resistant spray to reduce the probability of rust.
High Efficiency - 5 ton unit has high efficiency DC motor. New 4 HK Heat Kit - Installation friendly, easy service, more
robust, unique to new design.
TM
Coated Fins - All air handler coils are treated
TM
hydrophilic coating to enhance the
TM
ISO 9001
Certified Quality
Management System
Due to continuous product improvement, specifications are subject to change without notice.
isit us on the web at www.york.com
Additional rating information can be foun d at www.ari.org/aridirectory.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
DIMENSIONS
BLOWER COMPARTMENT
REFRIGERANT CONNECTIONS
J
D
DRAIN CONNECTIONS
FOR UPFLOW AND
DOWNFLOW
APPLICATIONS
255029-YTG-J-1007
10-3/8”
K
A
CIRCUIT BREAKER
PANEL
F
TOP OUTLET DIMENSIONS
1-1/2”
FILTER ACCESS
7-11/32”
18-9/32”
B
DRAIN PAN CONNECTIONS FOR HORIZONTALAPPLICATIONS
C
E
BOTTOM INLET
DIMENSIONS
DIMENSIONS
1
Models
Dimensions
AB C
DEF
Wiring Knockouts
JK
Height Width Depth Power Control Liquid Vapor
AHP18B**(N,H)21 46 17.5
12-3/8 13-29/32 14-19/32 AHP24B**(N,H)21 46 17.5 12-3/8 13-29/32 14-19/32 3/4” AHP30B**(N,H)21 46 17.5 12-3/8 13-29/32 14-19/32 3/4” AHP36C**(N,H)21 52 21 17-1/8 17-13/32 18-3/32 7/8” AHP42C**(N,H)21 52 21 17-1/8 17-13/32 18-3/32 7/8”
21.5
AHP48D**(N,H)21 57 24.5 22-1/8 20-29/32 21-19/32 7/8”
7/8” (1/2”) 1 3/8” (1”)
1 23/32” (1 1/4”)
7/8” (1/2”) 3/8”
SHP48D**N21 52 24.5 17-1/8 20-29/32 21-19/32 7/8
AHP60D**(N,H)21 57 24.5 22-1/8 20-29/32 21-19/32 7/8’
SHP60D**N21 52 24.5 17-1/8 20-29/32 21-19/32 7/8
1. Actual size (Conduit size).
Refrigerant
Connections
Line Size
COIL TECHNICAL DATA
Models Application
Refrig.
Conn. Types
AHP18B3X(N,H)21 AHP18B2A(N,H)21 AHP24B3X(N,H)21 AHP24B2A(N,H)21 AHP30B3X(N,H)21 AHP30B2A(N,H)21 AHP36C3X(N,H)21 AHP36C2A(N,H)21 AHP42C3X(N,H)21 AHP42C2C(N,H)21
Cooling /
Heat Pump
Sweat
AHP48D3X(N,H)21 AHP48D2C(N,H)21
SHP48D3XN21 5.83 3 11 SHP48D2CN21 5.83 3 11 2C
AHP60D3X(N,H)21 AHP60D2C(N,H)21
SHP60D3XN21 5.83 3 11 SHP60D2CN21 5.83 3 11 2C
Note: H models are available with a factory installed horizontal drain pan.
Face Area
(Sq. Ft.)
3.40 2 14
3.40 2 14 2A
3.89 2 14
3.89 2 14 2A
3.89 3 12
3.89 3 12 2A
4.86 3 12
4.86 3 12 2A
4.86 3 12
4.86 3 12 2C
5.83 3 11
5.83 3 11 2C
Rows
Deep
Fin
Per In.
Coil Size
(2) 14 x 17.5
(2) 16 x 17.5
(2) 16 x 17.5
(2) 20 x 17.5
(2) 20 x 17.5
(2) 24 x 17.5
Tube
Geometry
Tube
Dia.
Fin
Type
1 x 0.866 3/8 Enhanced
(2) 24 x 17.5
5.83 3 11
5.83 3 11 2C
(2) 24 x 17.5
(2) 24 x 17.5
3/4”
TXV
None
None
None
None
None
None
None
None
None
2 Unitary Products Group
255029-YTG-J-1007
COOLING CAPACITY
Models Rated CFM
AHP18B2A(N,H)21 650
AHP24B2A(N,H)21 800
AHP30B2A(N,H)21 1050
AHP36C2A(N,H)21 1200
AHP42C2C(N,H)21 1400
AHP48D2C(N,H)21
SHP48D2CN21
AHP60D2C(N,H)21
SHP60D2CN21
1600
1850
Entering Air °F
(Dry / Wet Bulb)
FULL-CASED “A” TYPE MULTI-POSITION
85/72 24.5 22.3 19.9 17.3 80/67 22.6 20.3 18.0 15.6 75/62 18.5 16.4 14.2 12.0 70/57 15.0 13.1 10.9 8.5 85/72 35.0 31.8 28.4 24.7 80/67 32.2 29.1 25.7 22.3 75/62 26.4 23.4 21.0 17.1 70/57 21.4 18.6 20.2 12.1 85/72 41.5 37.8 33.7 29.5 80/67 36.2 32.4 28.6 24.5 75/62 29.1 25.3 24.0 19.2 70/57 24.1 21.5 18.7 15.8 85/72 51.3 46.7 41.7 36.8 80/67 41.1 36.3 31.8 27.1 75/62 32.1 27.0 29.4 21.9 70/57 27.6 25.4 23.5 18.3 85/72 88.4 76.0 63.3 50.0 80/67 70.8 59.4 48.4 37.0 75/62 55.2 43.9 35.8 29.9 70/57 47.4 41.5 32.37 25.24 85/72 100.5 86.4 72.0 56.8 80/67 80.4 67.5 55.0 42.1 75/62 62.7 49.9 40.7 34.0 70/57 53.9 47.2 36.81 28.71 85/72 119.9 101.0 82.0 62.2 80/67 96.0 79.2 62.6 45.8 75/62 74.8 58.6 46.2 37.0 70/57 64.3 55.4 43.2 33.7
MBH@ Evaporator Temperature and Corresponding Pressure °F / PSIG
35 / 61.5 40 / 68.5 45 / 76.0 50 / 84.0
Unitary Products Group 3
255029-YTG-J-1007
ACCESSORIES
Refer to Price Manual for specific model numbers. TXV Kits - TXV kits are available for “Flex-coil” applications
and converting R22 to R410A or as a service replacement. All kits are bolt-on and require no brazing to install.
Non-Combustible Bases - A combustible floor base acces­sory is available, if required by local codes, when the air han­dler is installed in the downflow position on a combustible material.
Electric Heaters - 4HK models shown under electrical data include sequential operation and temperature dual limit switches for safe, efficient operation. Circuit breakers are pro­vided where shown.
External Insulating Wrap Kit - Provides a vinyl covered thermal insulation wrap, providing additional thermal insula­tion protection to prevent sweating in applications where extreme high humidity is present. Air Handler cover (or wrap) has Velcro edges for easy installation and access.
LIMITATIONS
These units must be wired and installed in accordance with all national and local safety codes.
Voltage limits are as follows:
Air Handler
Voltage
208/230-1-60 06 187-253 220/240-1-50 93 198-264
1. Rated in accordance with ARI Standard 110, utilization range “A”.
Voltage
code
Airflow must be within the minimum and maximum limits approved for electric heat, evaporator coils and outdoor units.
Entering Air Temperature Limits
Wet Bulb Temp.°F Dry Bulb Temp. °F
Min. Max. Min. Max.
57 72 65 95
1
Normal Operating
Voltage Range
AIR FLOW DATA - 60 Hz MODELS
Models
AHP18B**(N,H)21
AHP24B**(N,H)21
AHP30B**(N,H)21
AHP36C**(N,H)21
AHP42C**(N,H)21
AHP48D**(N,H)21
SHP48D**N21
AHP60D**(N,H)21
SHP60D**N21
1. Includes return air filter and coil.
All Air handler units are UL Listed up to 0 .50" w.c. external static pressure, including air filter, wet coil, and largest KW size heater, unless otherwise noted.
Blower
Motor
Speed
High 1142 1096 1053 997 925
Medium 677 652 634 615 572
Low 442 427 395 361 289 High 1084 1038 985 935 856
Medium 840 807 767 693 610
Low 654 614 548 483 420 High 1244 1184 1138 1079 1004
Medium 956 913 868 815 748
Low 941 904 862 806 731 High 1719 1650 1572 1482 1386
Medium 1119 1097 1062 1019 935
Low 929 910 877 825 760 High 1719 1650 1572 1482 1386
Medium 1119 1097 1062 1019 935
Low 929 910 877 825 760 High 1941 1818 1675 1532 1269
Medium 1594 1474 1409 1260 1021
Low 1241 1204 1128 1014 819
High / #1 2126 2093 2074 2048 1991
Medium High / #2 1863 1842 1804 1800 1758
Medium / #3 1642 1603 1593 1568 1523
Medium Low / #4 1482 1468 1427 1370 1324
Low / #5 1268 1220 1169 1118 1070
0.10 0.20 0.30 0.40 0.50
1
@ External Static Pressure - IWC
CFM
208 Volt
0.60 0.70 0.80 0.90 1.00
828 721 210 N/A N/A 486 295 120 N/A N/A 209 114 N/A N/A N/A 762 665 602 484 333 550 485 387 323 221 349 302 218 179 130 903 841 674 580 457 663 574 487 384 N/A 643 566 480 361 226
1273 1108 925 785 644
827 743 637 479 337 685 616 508 372 221
1273 1108 925 785 644
827 743 637 479 337 685 616 508 372 221 870 703 362 146 N/A 802 524 215 144 N/A
659 385 165 N/A N/A 1941 1801 1569 1461 1366 1730 1662 1503 1383 1306 1471 1410 1334 1307 1216 1274 1233 1196 1153 1099 1037 982.5 949.1 891.9 831
4 Unitary Products Group
Loading...
+ 8 hidden pages