York SAPHIR CER20, SAPHIR CEL20, SAPHIR CER30, SAPHIR CML00, SAPHIR CMR00 Specifications

...
WATER SYSTEMS
Fan Coil Unit SAPHIR (2 & 4 pipe system)
A complete range from 0.8 kW up to 3.5 kW
Features
• Inner frame, made of galvanized steel and lined with self­extinguishing thermal insulation material.
• Centrifugal fan deck independent of the inner frame with two aluminium impellers and galvanized steel scrolls, dynamically balanced; it includes the insulated condensate tray.
• 3 speed single phase motor, with permanently connected capacitor and thermal protection for the windings.
• Terminal board for the electric connections, tted into a plastic box (ABS), mounted on the left side of the inner structure and easily removable.
• Outer casing, made of white (RAL 9001) ABS plastic (YSF and YSW models).
• Panel frontage made of sheet steel and painted with epoxy powders, of the same colour of the casing (YSF and YSW models).
• Air intake group (YSF and YSW models) and air delivery grilles (model YSW), both made of heat-resistant ABS plastic.
• Protection grill on the air delivery, made of heat-resistant ABS plastic (YSF and YSW models).
• Feet set (only YSF model), made of the same material and colour of the casing.
• Foldaway lter, easily removable, consisting of either an ABS plastic structure (YSW model) or a metallic structure (all other models), with a lter element made of polypropylene.
CSL00 (Built in) CSR00 (Wall mounted)
Fan speed selector
CML00 (Built in) CMR00 (Wall mounted)
Thermostat with manual fan speed and S/W change over
CEL00 (Built in) CER00 (Wall mounted)
Thermostat with manual fan speed and automatic change over
CEL20 (Built in) CER20 (Wall mounted)
Thermostat with auto. fan speed and automatic change over
CEL30 (Built in) CER30 (Wall mounted)
Thermostat with auto. fan speed and automatic change over for modulating valve
E-COM-H0703
Fan Coil Unit SAPHIR
0.8 to 3.5 kW
(1) Room temperature 27°C d.b., 19ºC w.b. - Water temperature 7/12 °C (2) Room temperature 20°C - Water inlet temperature: 50°C (3) Room temperature 20°C - Water inlet temperature: 70/60°C (4) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,3 s. * Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397
Technical features
Model 130 140 230 240
Total cooling capacity [kW]
(1)
max 1.50 2.00 2.87 3.52
med 1.14 1.54 2.39 3.00
min 0.83 1.13 1.86 2.29
Sensible cooling capacity [kW]
(1)
max 1.16 1.58 2.16 2.70
med 0.86 1.19 1.78 2.27
min 0.62 0.85 1.37 1.70
Water flow in cooling [l/h]
(1)
max 282 342 493 605
med 197 264 410 515
min 143 197 319 394
Pressure drop in cooling [kPa]
(1)
max 1.9 2.9 7.0 10.1
med 0.9 1.7 5.1 7.6
min 0.5 0.9 3.2 4.7
Heating capacity 2 pipes [kW]
(2)
max 1.98 2.79 3.83 4.82
med 1.49 2.07 3.21 4.05
min 1.09 1.48 2.50 3.07
Water flow in heating 2 pipes [l/h] *
(2)
max 282 342 493 605
med 197 264 410 515
min 143 197 319 394
Pressure drop in heating 2 pipes [kPa]
(2)
max 1.6 2.4 5.8 8.4
med 0.7 1.4 4.2 6.3
min 0.4 0.7 2.7 3.9
Heating capacity 2 pipes [kW]
(3)
max 3.81 5.10 6.56 8.21
med 2.84 3.91 5.44 6.89
min 2.09 2.83 4.23 5.20
Water flow in heating 2 pipes [l/h]
(3)
max 333 450 574 718
med 248 342 476 602
min 183 247 370 455
Pressure drop in heating 2 pipes [kPa]
(3)
max 2.1 4.1 7.2 10.7
med 1.1 2.3 5.1 7.8
min 0.6 1.1 3.3 4.7
Heating capacity 4 pipes [kW]
(3)
max 1.94 2.36 3.28 3.73
med 1.59 1.97 2.92 3.38
min 1.25 1.59 2.48 2.84
Water flow in heating 4 pipes [l/h]
(3)
max 170 206 287 326
med 139 172 256 296
min 109 139 217 248
Pressure drop in heating 4 pipes [kPa]
(3)
max 2.2 3.3 10.4 13.2
med 1.5 2.3 8.5 11.0
min 0.9 1.5 6.3 8.0
Air flow [m3/h]
max 275 390 425 550
med 201 288 330 460
min 125 190 246 325
Sound power level [dB(A)]
max 44 53 48 55
med 36 45 43 50
min 28 35 35 41
Sound pressure level [dB(A)]
(4)
max 35 44 39 46
med 27 36 34 41
min 19 26 26 32
Power supply [V-ph-Hz]
230 - 1- 50
Power input [W]
max 31 42 61 63
Absorbed current [W]
max 0.14 0.20 0.29 0.28
Water content (2 pipes) [l]
0.96 0.96 1.40 1.40