REPAIR PART KIT INSTALLATION INSTRUCTIONS
REPLACEMENT DEMAND DEFROST CONTROL BOARD – S1-33101975102
FOR USE WITH MODELS: 12, 13 & 14 SEER HEAT PUMPS
1. Power off unit totally - 240V & 24V.
2. Carefully record positions and colors of wiring removed.
3. Remove old defrost circuit board.
4. Install replacement circuit board - utilizing same placement, mounting & screws.
HEATER LIMIT SWITCH (Not on all Units)
START RELAY (Not on all Units)
DUAL RUN/FAN CAPACITOR
START CAPACITOR (Not on all Units)
GROUND LUG
REVERSIBLE HIGH VOLTAGE CONDUIT PLATE
CONTACTOR
DEFROST CONTROL BOARD
LOW VOLTAGE BOX
“FINGERED” BUSHING
5. Refer to unit Installation Manual or Table 1 below - and set the Demand Defrost Curve Selection Jumper to the proper position. For the new jumper setting to take effect - all 24V power to the board must be removed and reapplied.
6. Complete the installation and power up the unit, re-apply­ing both 240V & 24V.
DEMAND DEFROST CURVE SELECTION JUMPER
X/L
R
C
Y
O
W
W1/66
X/L
R
C
Y
O
W
W1/66
P 1 2
3 4
REV
VALV E
TEST
PRESSURE
SWITCH
COIL
M
AMBIENT
COIL G
AMBG
COND
HIGH VOLTAGE
FAN
FIGURE 1: Outdoor Unit Control Box FIGURE 2: Demand Defrost Control Module
DEFROST CURVE SELECTION
When the control board is replaced, the jumper MUST be placed in a numbered position. Select the proper jumper posi­tion from Table1. If the jumper is missing or in the P po si-
tion, the replacement control will not energize the compressor.
The control will display the active defrost curve using the X/L terminal when the heat pump is operating in a defrost cycle that has been forced using the TEST inputs. For instance, the X/L output will be energized with two flashes when defrost curve 2 is active. The control only reads the jumper input when the Y and W thermostat inputs are de-energized.
When the jumper position is changed, the control will not act upon the jumper changes until the thermostat calls are de-ener­gized or power (24 VAC) to the control is cycled.
T ABLE 1: Defrost Initiate Curves
Defrost Curve Selection
Jumper Position
1234
14 Seer 2, 3, 4 Ton 2.5, 3.5 Ton None None
All Other Models All None None None
Subject to change without notice. Printed in U.S.A. 035-21270-001-A-0906 Copyright © by York International Corp. 2006. All rights reserved. Supersedes: Nothing