York R-407C User Manual

Packaged Rooftop
Air Conditioning Units

FORM 100.50-EG1 (201)

R-407C OPTIMIZED
50 THROUGH 65 TONS
00406VIP
PAGE
Nomenclature .........................................................................................................3
Introduction .............................................................................................................4
Physical Data..........................................................................................................7
Application Data......................................................................................................9
Cooling Performance Data....................................................................................12
Fan Performance ..................................................................................................20
Electrical Data.......................................................................................................24
Controls ................................................................................................................26
Power Wiring ........................................................................................................31
Field Control Wiring ..............................................................................................34
General Arrangement Drawing .............................................................................35
Curb Layout Drawing ............................................................................................37
Mechanical Specifications.....................................................................................38
TABLES
1 Physical Data .............................................................................................7
2 Cooling Performance Data – 50 Ton Model..............................................12
3 Cooling Performance Data – 55 Ton Model..............................................14
4 Cooling Performance Data – 60 Ton Model..............................................16
5 Cooling Performance Data – 65 Ton Model..............................................18
6 50 Through 65 Ton Supply Fan Data........................................................20
7 50 Through 65 Ton Exhaust Fan Data......................................................21
8 Component Static Pressure Drops........................................................... 22
9 Compressors ........................................................................................... 24
10 Supply and Exhaust Fan Motor Electrical Data ........................................ 25
1 1 Condenser Fan Motors ............................................................................25
12 Controls and Convenience Outlet.............................................................25
2
YORK INTERNATIONAL
FIGURES
1 Packaged Rooftop Air Conditioning Unit .................................................. 4
2 Single-Point Power Supply Wiring.......................................................... 31
3 Single-Point Power Supply Wiring with Non-Fused Disconnect ............. 32
4 Dual-Point Power Supply Wiring ............................................................ 33
5 Field Control Wiring ............................................................................... 34
6 General Arrangement Drawing – Bottom Return, Bottom Supply ........... 35
7 General Arrangement Drawing – Rear Return, Left or Right Supply ...... 36
8 Curb Layout Drawing.............................................................................. 37
FORM 100.50-EG1
PAGE

NOMENCLATURE

BASIC MODEL NUMBER
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
BASE PRODUCT TYPE NOMINAL CAPACITY APPLICATION REFRIGERANT VOLTAGE DUCT LOCATIONS DESIGN SPECIAL Y050 B17BA
P055 28L S
: YORK : Packaged
Rooftop
A065 58 B
: Air-Cooled
L S
: Scroll
: 50-ton : 55-ton
060 4 6 R X
: 60-ton : 65-ton
: Cooling Only
C
: Constant Volume
C
: VAV, VFD
V
: VAV , VFD w/ Manual Bypass
B
: R-407C
: 200 / 3 / 60 : 230 / 3 / 60 : 460 / 3 / 60 : 575 / 3 / 60
: Bottom Supply : Left Supply : Right Supply : Bottom Return
F
: Front Return : Side Return
: Rev. Level A : Std. Product : Special
YORK INTERNATIONAL
3

Introduction

FIG. 1 – PACKAGED ROOFTOP AIR CONDITIONING UNIT

00406VIP

FEATURES/BENEFITS

Ecological and Economical Design
• First packaged R TU with 407C optimized design
Cooling and Heating – Superior operating perfor­mance provides lower operating costs. Smaller steps of cooling capacity provide tighter control of building environment and occupant comfort while optimizing energy efficiency .
Indoor Air Quality (IAQ) – Outside air economiz­ers provide energy savings in free cooling mode, and can provide a healthier and more comfortable building environment by introducing fresh outside air into the building as needed. Indoor Air Quality (IAQ) requirements for building ventilation and comfort are controlled through the microprocessor control panel. Optional air flow measurement provides an accu­rate means of tracking air quality and alerting the occupants or building owner to unhealthy situations.
High-Efficiency Motors – High-ef ficiency motors are available for optimum energy efficiency. All motors used on the eco2 packaged rooftop air conditioner meet U.S. EP ACT 1992 minimum requirements.
Indoor Air Quality (IAQ)
Double-sloped stainless steel drain pan – This double-sloped inclined stainless steel drain pan fa­cilitates removal of evaporator condensate. Sloped
in two directions conforming to ASHRAE 62n, this drain pan swiftly minimizes any condensate within the unit. Best of all, the drain pan is accessible for periodic cleaning required by IAQ standards.
Smart ventilation – YORK maintains the leader­ship role in IAQ products with adaptive ventilation control. The OptiLogicTM controls provide continu­ous monitoring of air quality and take action by open­ing the outside air dampers, bringing in the right amount of fresh air before air impurities reach un­comfortable or even dangerous levels.
Air flow measurement – Precise measurement of ventilation air flow is possible using an air flow measurement station which can be installed in the economizer section. Proper ventilation air flow is required to ensure sufficient fresh air is in the build­ing. A myriad of air flow measurement options are available from minimum air flow to high-accuracy full air flow capabilities. The complete system is designed as an integrated component of the OptiLogicTM control system to ensure optimum sys­tem performance.
Double-wall construction – Rigid double-wall construction throughout provides ease of clean­ing and protects against insulation fiber entrain­ment in the breathable air. Double-wall construc­tion also helps improve the acoustical character­istics of the air handling unit.
4
YORK INTERNATIONAL
FORM 100.50-EG1
Enhanced filtration – The Eco2 unit gives design­ers the flexibility to meet various IAQ requirements with a full range of rigid and throwaway filters at various efficiency levels.
Reliable Scroll Compressor Technology
Reliable, efficient, trouble-free operation is the true mea­sure of a packaged rooftop’s value. That’s why YORK Eco2 Packaged Rooftop Air Conditioners use estab­lished scroll-compressor technology to deliver depend­able, economical performance in a wide range of appli­cations. With the Eco2 Packaged Rooftop, you get the latest generation of compressor enhancements added to the scroll’s inherent strengths. The simplicity of a hermetic scroll compressor allows the use of fewer moving parts to minimize breakdown. YORK also em­ploys the latest sealing technology to avoid metal-to­metal contact. Axial sealing is accomplished with float­ing tip seals, while radial sealing utilizes a microcushion of oil. The result: a maintenance-free compressor pro­viding minimum wear and maximum runtime.
A scroll compressor operates with two scroll members— a fixed scroll and an identical orbiting scroll turned 180 degrees, like two hands curled and interlocked together. As the orbiting scroll oscillates against the fixed scroll, it traps and compresses suction gas inside involute pockets. As the orbiting scroll moves, the gas is com­pressed into the central area, where it is discharged as compressed gas. High efficiency is achieved through a precisely controlled orbit and the use of advanced scroll geometry . There is no wasted motion. All rotating parts are statically and dynamically balanced to ensure opti­mal performance over the long haul.
Balanced components and precision machining also ensure that smooth compression occurs in all involute pockets simultaneously . When compression forces are equally distributed over the entire scroll surface, equal forces in opposing directions cancel one another, mini­mizing any imbalance. Consequently, compression is smooth, continuous, and quiet. Vibration isolators on each compressor handle normal vibration. For extra quiet operation, acoustic sound blankets for each com­pressor are available as options.
Serviceability
OptiLogicTM – fully-integrated factory-packaged controls are standard on every unit and include a display unit with a 4x20 character LCD display. OptiLogic
TM
continually monitors all control setpoints and configurations. If a unit or control component, or sensor fails, the controller notifies the user of a problem. If desired, YORK service can provide re­mote monitoring and automatically schedule a ser­vice technician to make the repair and maintain your comfort.
Access doors – full-sized access doors provide easy access into the unit for routine maintenance and inspection.
Suction & discharge service valves – oversized service valves to provide isolation and quick recla­mation and charging of system refrigerant are avail­able to minimize downtime and simplify the service and repair task.
VFD Fan Motor Control with Manual Bypass – Optional manual VFD bypass reduces time required for troubleshooting, commissioning and system balancing.
Convenience Outlet – for maintenance tasks re­quiring power tools, an optional 1 10V GFCI power supply can power lights, drills or any other power hand tool needed.
Filter Maintenance Alarm – An optional filter main­tenance alarm indicates when a filter becomes dirty and requires replacement or cleaning.
Install with Ease and Safety
Factory run-tested – Each unit is subjected to a series of quality assurance checks as well as an automated quality control process before being run­tested. Fans and drives are balanced at the factory during testing. The factory run-test ensures safe, proper operation when the unit is installed and re­duces installation and commissioning time.
Single-point power connection – Single-point power connection reduces installation time by pro­viding a single point for incoming power, including
YORK INTERNATIONAL
5
Introduction
the optional convenience outlet. All incoming power is connected in one location, reducing the cost of field-supplied and installed power wiring.
Factory-mounted and wired controls – All con­trol points within the unit are factory-installed, wired and tested. The OptiLogic nicate with BACNet IP.
Non-fused disconnect – A factory-installed non­fused disconnect switch simplifies unit installation and serviceability by reducing installed labor costs. The disconnect switch is interlocked with the power cabinet ensuring that all power to the unit has been disconnected before servicing.
Design Flexibility
Low Ambient Operation – Head-pressure control is accomplished via a VFD motor controller rather than an inefficient and noisy condenser fan damper. By varying the speed of the condenser fan, better control and quieter operation is obtained during the colder months. Low ambient controls are available
TM
controls can commu-
on all systems offering higher rooftop cooling ca­pacity than competitive units.
Hot Gas Bypass – Optional on constant volume units, hot gas bypass reduces the cycling of compressors which helps prolong the life of the equipment.
Supply Air Openings – Side supply connections are available on select configurations, offering more flexibility for duct layout and improving sound trans­mission characteristics.
Compressor Sound Blankets – For applications in sound-sensitive areas, compressor sound blan­kets are available to reduce sound emitted from the rooftop unit.
Fan Spring Isolators – One-inch spring isolation is used to prevent vibration transmission from the rooftop unit’s supply fan to the building. Two-inch spring isolation is also available.
Harsh Environments – A variety of coil coating and materials are available as well as hail guards to pro­tect coils from weather damage. Seismic and hurri­cane duty curbs and fan restraints are available.
6
YORK INTERNATIONAL
FORM 100.50-EG1

Physical Data

T ABLE 1 – PHYSICAL DATA

MODEL SIZE 50 55 60 65 GENERAL DATA
Length (Inches) 336 336 336 336 Width (Inches) 92 92 92 92 Height (Inches) 82 82 82 82
Operating Weights (Lbs.) (base unit, no options)
Cooling Only (Rigging & Refrigerant) 8,080 8,290 8,530 8,740
Rigging Weights (Lbs.) (base unit, no options)
Cooling Only 8,010 8,210 8,440 8,640
Option Weights (Lbs.)
Power Exhaust (Blower, motor, fan skid & mod damper) 647 647 647 647 Power Exhaust (Blower, motor, fan skid, VFD & baro damper) 654 654 6 54 654 100% AMS (Measurement Station & Mounting) 110 110 110 110 25/75% AMS (Measurement Station & Mounting) 130 130 130 130 Min. AMS (Measurement Station & Mounting) 40 40 40 40 Barometric only 36 36 36 36 Condenser Hail Guard 32 32 32 32 Copper Condenser Coils 617 617 793 793 Copper Evaporator Coils 262 320 400 500
Roof Curb Weights (Lbs.)
14" Full Perimeter Roof Curb 787 787 787 787 14" Open Condenser Roof Curb 555 555 555 555
Compressor Data
Quantity / Size (Nominal Tons ) 4/13 4/13 4/15 4/15 Type Scroll Scroll Scroll Scroll Capacity Steps (%) 25, 50, 75, 100 25, 50, 75, 100 25, 50, 75, 100 25, 50, 75, 100
Supply Fan and Drive
Quantity 1111 Type FC FC FC FC Size 25-22 25-22 25-22 25-22 Motor Size Range (min. to max. HP) 7.5-40 7.5-40 7.5-40 7.5-40 Air Flow Range (min. to max. cfm) 10000-22500 12000-24000 14000-27000 14000-27000 Static Pressure Range (min. to max. ESP) 0-4" 0-4" 0-4" 0-4"
Exhaust Fan
Quantity 2222 Type FC FC FC FC Size 15-15 15-15 15-15 15-15 Motor Size Range (min. to max. HP) 5-20 5-20 5-20 5-20 Air Flow Range (min. to max. cfm) 0-20000 0-20000 0-20000 0-20000 Static Pressure Range (min. to max. ESP) 0-1" 0-1" 0-1" 0-1"
Evaporator Coil
Size (square feet) 48.8 48.8 48.8 48.8 Number of rows/fins per inch 3/8 4/8 4/12 5/10 Tube Diameter/Surface 1/2"/enhanced 1/2"/enhanced 1/2"/enhanced 1/2"/enhanced
Condenser Coil (Aluminum Fins)
Size (square feet) 121.3 121.3 121.3 121.3 Number of rows/fins per inch 3/14 3/14 3/18 3/18 Tube Diameter 3/8" 3/8" 3/8" 3/8"
Condenser Coil (Copper Fins – Opt)
Size (square feet) 121.3 121.3 121.3 121.3 Number of rows/fins per inch 3/14 3/14 3/18 3/18 Tube Diameter 3/8" 3/8" 3/8" 3/8"
YORK INTERNATIONAL
7
Physical Data
(continued)
T ABLE 1 – PHYSICAL DATA (Cont’d)
MODEL SIZE 50 55 60 65 GENERAL DATA Condenser Fans
Quantity 4444 Type Prop. Prop. Prop. Prop. Diameter (inches) 36 36 36 36
Filters – 2" throwaway
Quantity 8 12 8 12 8 12 8 12 Size (length x width) (in.) 25x16 25x20 25x16 25x20 25x16 25x20 25x16 25x20 Total Filter Face Area (square feet) 63.9 63.9 63.9 63.9
Filters – 2" cleanable
Quantity 8 12 8 12 8 12 8 12 Size (length x width) (in.) 25x16 25x20 25x16 25x20 25x16 25x20 25x16 25x20 Total Filter Face Area (square feet) 63.9 63.9 63.9 63.9
Filters – 2" pleated (30% efficient)
Quantity 8 12 8 12 8 12 8 12 Size (length x width) (in.) 25x16 25x20 25x16 25x20 25x16 25x20 25x16 25x20 Total Filter Face Area (square feet) 63.9 63.9 63.9 63.9
Filters – 12" rigid 65%, 2" 30% prefilter
Quantity 149149149149 Size (length x width) (in.) 16x20 25x16 25x20 16x20 25x16 25x20 16x20 25x16 25x20 16x20 25x16 25x20 Total Filter Face Area (square feet) 44.6 44.6 44.6 44.6
Filters – 12" rigid 95%, 2" 30% prefilter
Quantity 149149149149 Size (length x width) (in.) 16x20 25x16 25x20 16x20 25x16 25x20 16x20 25x16 25x20 16x20 25x16 25x200 Total Filter Face Area (square feet) 44.6 44.6 44.6 44.6
Filters – 2" carbon (30% efficient)
Quantity 8 12 8 12 8 12 8 12 Size (length x width) (in.) 25x16 25x20 25x16 25x20 25x16 25x20 25x16 25x20 Total Filter Face Area (square feet) 63.9 63.9 63.9 63.9
Refrigerant HFC-407C HFC-407C HFC-407C HFC-407C Minimum OA Temp. for Mech. Clg. (°F) 45 45 45 45 Low Ambient Option Min. OA Temp. (°F) 0000
8
YORK INTERNATIONAL

Application Data

FORM 100.50-EG1

LOCATION

Of the many factors that can affect the acoustical char­acteristics of a rooftop installation, one of the most im­portant is the unit location. Ideally , the rooftop unit should be installed away from sound-sensitive areas, such as conference rooms, auditoriums and executive offices. Possible locations could be above storage areas, hall­ways, mechanical or utility rooms, or bathrooms.
The eco door installation. When selecting a site for installation, be guided by the following conditions:
• Unit must be installed on a level surface.
• For the outdoor location of the unit, select a place
• Also avoid locations beneath windows or between
• Optional condenser coil protection should be used
2
air conditioning units are designed for out-
having a minimum sun exposure and an adequate supply of fresh air for the condenser.
structures.
for seashore locations or other harsh environments.
Spreader bars must be used to prevent damage to the unit casing. All lifting lugs must be used when lifting the rooftop unit.
Care must be taken to keep the unit in the upright posi­tion during rigging and to prevent damage to the water­tight seams in the unit casing. Avoid unnecessary jar­ring or rough handling.
Ground Level Locations
It is important that the units be installed on a substan­tial base that will not settle, causing strain on the refrig­erant lines and sheet metal and resulting in possible leaks. A one-piece concrete slab with footers extended below the frost line is highly recommended. Addition­ally, the slab should not be tied to the main building foundation as noises may be transmitted into the build­ing structure.
For ground level installations, precautions should be taken to protect the unit from tampering by, or injury to, unauthorized persons. Erecting a fence around the unit is another common practice.
• The unit should be installed on a roof that is struc­turally strong enough to support the weight of the unit with a minimum of deflection. Extreme caution should be taken when the unit is mounted on a wood structured roof. It is recommended that the unit(s) be installed not more than 15 feet from a main sup­port beam to provide proper structural support and to minimize the transmission of sound and vibra­tion. Ideally , the center of gravity should be located over a structural support or building column.
• Location of unit(s) should also be away from build­ing flue stacks or exhaust ventilators to prevent pos­sible reintroduction of contaminated air through the outside air intakes.
• Be sure the supporting structures will not obstruct the duct, gas or wiring connections.
• Proper service clearance space of 6-feet around the perimeter of the unit and 12-feet to any adja­cent units is required to eliminate cross contami­nation of exhaust and outdoor air, and for mainte­nance tasks such as coil pull and cleaning. No ob­structions should be above the condensing unit section.

ECONOMIZER

The economizer section is used for ventilation of the conditioned space to maintain indoor air quality, and also to reduce energy consumption by using outdoor air cooling in lieu of mechanical cooling. If outdoor air is appropriate for cooling, but not sufficient for the cool­ing demand, mechanical cooling will stage on as nec­essary until the cooling load is met.
Comparative enthalpy operation is the most accurate and efficient means of economizer operation. The OptiLogic control monitors the return and outside air energy con­tent, and selects the lower of the two for operation.

V AV SUPPLY AIR PRESSURE CONTROL

Traditional packaged rooftop systems use inlet guide vanes (IGVs) f or du ct st atic pre ssur e con trol. These con­trol supply duct pressure by modulating dampers (intro­ducing losses and inef ficiencies) on the intlet of the fan, open and closed. V ariable frequency drives (VFDs) of­fer superior fan speed control and quieter, energy ef fi­cient operation.
TM

RIGGING

Proper rigging and handling of the equipment is man­datory during unloading and setting it into position to retain warranty status.
YORK INTERNATIONAL
IGV inefficiency can be compared to the operation of a car. Modulating air flow with an IGV is like pressing on the gas to drive the car, but modulating the speed of the car by simultaneously pressing on the brake. VFD modu­lation is speed modulation by using just the gas pedal.
9
Application Data
(continued)
For VAV applications, the YORK eco2 unit uses a VFD to modulate fan speed and maintain a constant duct static pressure. VFDs offer superior control over the operation of the unit at part load, and offer the addi­tional benefits of quieter and more efficient operation when compared to IGV.

HARSH ENVIRONMENTS – CONDENSER AND EV APORATOR COIL PROTECTION

For harsh environmental conditions such as seashore applications, YORK offers three types of coil protec­tion: copper fin material, black fin and T echnicoat coat­ings. YORK recommends that for corrosive environ­ments that copper fins be used to protect the evapora­tor and/or condenser coils. In areas where chemicals that can corrode copper are present, such as ammo­nia, YORK recommends that the black fin or T echnicoat coating be used for maximum protection.
Copper Fin Condenser Coil
Copper fins can be used instead of aluminum for addi­tional corrosion protection, however it is not suitable for areas that are subject to acid rain or exposed to ammonia.
Pre-Coated Condenser Fins
Black fin coating (yellow fin for evaporator fins) is pre­coated application epoxy on aluminum fin stock to guard from corrosive agents and insulate against galvanic po­tential. It is used for mild seashore or industrial loca­tions. This can provide corrosion resistance comparable to copper fin coils in typical seashore locations.
Post-Coated Condenser Fins
T echnicoat (a post-coated application of epoxy) can be used for seashore and other corrosive applications with the exception of strong alkalides, oxidizers, wet bro­mide, chlorine and fluorine in concentrations greater than 100 ppm.
Any of the above suitable options should be selected based on the particular project design parameters and related environmental factors. The application should be further reviewed and approved by the consulting en­gineer or owner based on their knowledge of the job site conditions.

BUILDING EXHAUST SYSTEMS

Building exhaust systems are often necessary when economizers are used to bring in outdoor air. Without proper building exhaust, the building may become over­pressurized. The exhaust system maintains the proper building pressure by expelling the appropriate amount of air from the building. Exhaust systems are typically designed to exhaust approximately 10% less air than what is entering the building. This provides a slight posi­tive pressure on the building.
100% modulating exhaust with building static pressure sensing and control
The 100% exhaust system can be configured with ei­ther control actuated dampers or VFDs for modulating control. The unit controller monitors the building pres­sure using a differential pressure transducer and main­tains the required building static pressure by modulat­ing the exhaust control. If the building has other means of exhaust or building pressure is not important, on/off or barometric control may be used.
100% modulating exhaust with fan on/off control
The 100% exhaust system can be configured for on/off operation eliminating the expense of the damper ac­tuators or VFDs. This exhaust system can be controlled by either the outside air damper position, or a building static pressure sensor.
Barometric exhaust
Barometric exhaust can be used when smaller amounts of air at low static pressure variations within the build­ing or other means of building exhaust are employed. Barometric exhaust is commonly used where there are only small fluctuations in building pressure or where building static pressure control is not necessary .

ROOF CURB

Optional 14-inch full-perimeter or open condenser roof curbs can be provided if necessary for mounting to the building roof. These curbs come disassembled and require installation in the field. For bottom supply and return duct openings, the curbs have matching con­nections to ease installation. A pipe chase that matches the rooftop unit is also included in the curb footprint for through-the-curb utility connections.
10
YORK INTERNATIONAL
FORM 100.50-EG1
The curb should be located according to the location recommendations above, and properly sealed to pre­vent moisture and air leakage into and out of the duct system. Flexible collars should be used when connect­ing the duct work to prevent unit noise transmission and vibration into the building.
Duct work should be supported independently of the unit.

ACOUSTICAL CONSIDERA TIONS

The eco
2
unit is designed for lower sound levels than competitive units by using flexible fan connections, fan spring isolators, double-wall construction, and lower speed and horsepower fans. For VAV applications, VFDs are used instead of inlet guide vanes. Additional sound attenuation can be obtained using compressor sound blankets and field-supplied sound attenuators when necessary .
Even with these equipment design features, the acous­tical characteristics of the entire installation must never be overlooked. Additional steps for the acoustical char­acteristics of a rooftop installation should be addressed during the design phase of a project to avoid costly al­terations after the installation of the equipment. During the design phase of a project, the designing engineer should consider, at a minimum, the impact of the equip­ment location, rooftop installation, building structure, and duct work.

SELECTION PROCEDURE

Given:
Required total cooling capacity of 600 mbh and sen­sible cooling capacity of 450 mbh with evaporator en­tering air conditions of 83°F dry bulb and 67°F wet bulb. Design ambient temperature is 95°F dry bulb. Supply air requirements are 17500 cfm of air at 2.25 IWG ex­ternal static pressure. Power supply is 460V/3ph/60Hz
and the unit requires a modulating economizer, 2-inch pleated filters, bottom supply and bottom return air open­ings and is constant volume.
Select Unit:
1. Determine the internal static pressure drop of the cabinet by referencing Table 8.
Wet evaporator coil 0.54 Bottom supply opening 0.14 Bottom return opening 0.13 2-inch pleated filters 0.10 Economizer openings 0.24 Modulating economizer dampers 0.31
T otal 1.46 IWG
2. Determine the total static pressure by adding the internal to the external static pressure.
TSP = 1.46 IWG + 2.25 IWG
= 3.71 IWG total static pressure
3. Determine the BHP of the supply fan from Table 6 using the supply air flow and total static pressure. From the table, we interpolate to get 15.1 BHP . As­suming a drive loss of 3% and a motor efficiency of 90%, we can calculate the heat rejection of the sup­ply fan motor as:
(2545 x 15.1)/(0.90 x (1-0.03)) = 44.0 mbh
Required Cooling Capacities:
Total = 600 + 44.0 = 644 mbh Sensible = 450 + 44.0 = 494 mbh
4. Required total and sensible capacities are 644 mbh and 494 mbh, respectively. Using the Cooling Per­formance Data starting with Tables 2, locate the table with the correct ambient air temperature. Next, trace the 83°F entering air dry bulb temperature to match the 17,500 cfm and 67°F entering wet bulb temperature condition. The resulting conditions are, from the table, 645 mbh total cooling capacity and 497 mbh sensible cooling capacity . Thus, a 50-ton unit is selected.
YORK INTERNATIONAL
11
Cooling Performance Data –
50 Ton Model

T ABLE 2 – COOLING PERFORMANCE DATA – 50 TON MODEL

85° AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
CFM
10000 67 653 548 646 500 635 454 637 416 632 377 626 343
14000 67 665 581 656 523 647 474 647 431 643 388 637 349
17500 67 684 634 672 558 666 505 663 454 660 406 653 359
20000 67 705 695 689 597 686 540 680 479 679 425 672 370
22500 67 715 715 697 616 696 557 689 492 688 435 680 376
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
ENTERING 90 86 83 80 77 74
WB (°F) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
72 700 477 700 431 695 387 692 353 691 311 ——
62 640 640 608 608 590 583 582 562 569 514 574 455 72 711 500 708 445 705 399 701 360 699 316 ——
62 654 654 625 625 606 606 594 547 583 498 585 439 72 729 536 721 467 719 418 715 370 712 324 ——
62 680 680 652 652 632 625 612 550 606 497 603 438 72 749 576 736 492 736 439 732 382 726 333 ——
62 710 710 682 682 661 661 633 582 631 523 622 467 72 758 595 742 504 743 449 739 388 732 338 ——
62 715 715 696 610 674 549 643 486 643 429 631 370
95° AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
CFM
10000 67 628 536 630 494 615 445 616 404 609 383 605 331
14000 67 642 569 638 515 627 465 625 419 619 382 615 338
17500 67 665 625 651 547 645 497 640 443 635 382 630 348
20000 67 691 691 665 582 665 532 656 470 653 382 647 360
22500 67 703 703 672 599 674 549 664 483 661 382 655 366
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
ENTERING 90 86 83 80 77 74
WB (°F) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
72 673 468 673 416 669 375 667 340 664 301 ——
62 618 618 590 590 569 513 571 481 562 435 562 390 72 684 491 682 432 678 388 676 348 673 306 ——
62 635 635 607 607 586 541 580 500 572 453 571 407 72 701 526 696 458 693 407 690 360 686 315 ——
62 661 661 634 634 612 587 594 531 588 481 586 433 72 720 565 712 486 709 429 705 373 701 325 ——
62 691 691 663 663 641 641 609 565 606 511 602 462 72 729 584 720 500 717 439 712 380 708 329 ——
62 704 704 675 658 655 629 617 556 614 488 610 447
12
YORK INTERNATIONAL
FORM 100.50-EG1
T ABLE 2 – COOLING PERFORMANCE DATA – 50 TON MODEL (CONTD)
105° AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
CFM
10000 6 7 590 513 596 478 589 434 591 390 593 354 589 318
14000 6 7 609 550 608 501 600 454 600 406 601 366 597 326
17500 6 7 638 607 625 537 618 485 615 432 613 384 609 337
20000 6 7 670 670 645 577 638 520 631 461 626 404 623 350
22500 6 7 686 695 654 596 647 537 639 475 632 414 629 356
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
ENTERING 90 86 83 80 77 74
WB (°F) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
72 649 464 650 409 645 365 644 330 644 290 ——
62 597 597 573 573 536 498 549 460 544 429 542 384 72 658 483 658 424 653 378 651 338 650 295 ——
62 614 614 589 589 556 527 557 483 553 446 550 397 72 673 512 670 447 667 397 663 350 661 303 ——
62 641 641 614 614 587 571 570 520 567 472 563 419 72 689 545 684 472 682 419 677 364 672 311 ——
62 670 670 642 642 621 621 584 561 582 500 576 443 72 696 560 690 485 690 430 683 371 678 315 ——
62 684 684 655 655 637 644 591 580 590 514 583 455
115° AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
CFM
10000 6 7 494 424 524 387 514 349 515 313 514 281 518 254
14000 6 7 548 509 545 449 541 406 539 359 536 317 537 276
17500 6 7 577 555 557 481 555 435 552 383 548 336 547 288
20000 6 7 609 609 570 517 571 468 566 410 562 357 558 301
22500 6 7 624 624 576 534 579 484 572 423 568 367 563 307
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
ENTERING 90 86 83 80 77 74
WB (°F) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
72 563 368 562 318 567 286 558 258 563 233 ——
62 498 498 501 501 442 424 458 349 467 343 467 306 72 592 432 588 370 589 325 585 286 583 246 ——
62 550 550 533 533 498 488 494 434 491 395 489 349 72 608 465 603 397 600 346 600 300 594 253 ——
62 578 578 550 550 527 522 513 478 504 422 500 371 72 625 503 618 427 613 368 616 316 606 261 ——
62 609 609 568 568 560 560 534 528 518 452 513 396 72 633 520 626 441 619 379 623 324 611 265 ——
62 624 624 577 577 575 578 544 548 525 467 520 408
YORK INTERNATIONAL
13
Cooling Performance Data –
55 Ton Model

T ABLE 3 – COOLING PERFORMANCE DATA – 55 TON MODEL

85° AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
CFM
12000 67 677 564 651 511 641 463 642 423 637 382 631 346
16000 67 693 598 661 535 653 484 652 438 649 394 642 353
19250 67 728 677 684 586 680 530 675 472 673 419 666 367
22000 67 750 713 695 613 694 554 688 490 687 433 679 375
24000 67 758 720 701 625 701 565 693 497 692 439 685 378
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
ENTERING 90 86 83 80 77 74
WB (°F) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
72 732 488 704 437 700 393 696 356 695 313 ——
62 660 648 616 616 598 598 588 564 576 515 579 456 72 743 512 712 452 709 405 706 363 703 319 ——
62 680 661 634 634 615 587 600 531 591 481 591 421 72 767 564 731 485 731 433 727 378 722 331 ——
62 725 701 673 673 652 652 627 572 624 515 616 458 72 781 592 741 502 742 448 738 387 731 337 ——
62 750 713 694 613 672 554 642 490 641 433 630 375 72 786 604 746 510 747 454 743 390 736 340 ——
62 760 720 701 602 681 534 648 473 649 416 636 357
95° AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
CFM
12000 67 651 554 634 504 621 454 621 411 613 382 610 334
16000 67 668 585 643 525 633 476 630 427 624 382 620 341
19250 67 707 671 661 572 659 521 651 462 647 382 642 357
22000 67 728 701 671 597 673 546 663 481 660 382 654 365
24000 67 737 709 675 607 678 556 667 489 665 382 659 369
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
ENTERING 90 86 83 80 77 74
WB (°F) CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC CAP SHC
72 706 479 678 424 673 381 671 344 668 303 ——
62 641 626 598 598 577 527 575 490 567 444 566 398 72 716 502 687 441 683 394 680 352 677 309 ——
62 661 644 616 616 594 554 585 511 577 462 576 415 72 738 554 708 478 704 422 700 369 696 322 ——
62 705 682 654 654 633 625 605 555 600 502 598 453 72 751 581 719 497 715 438 7 11 379 707 328 ——
62 730 703 675 675 653 653 616 578 613 524 609 473 72 756 593 723 506 720 444 715 383 711 331 ——
62 740 709 675 607 662 556 620 489 618 382 614 369
14
YORK INTERNATIONAL
Loading...
+ 30 hidden pages