York MLCA-MLHA-07-24 User Manual

MINISPLIT HIGH WALL
AIR CONDITIONER
Installation & Owner’s Manual
MODELS
MLCA-MLHA 07-24 MLCB-MLHB 07-24 MACC-MAHC 07-24
The units comply with one or more of the following marks - see unit for details.
J199.pmd 31/03/2005, 9:52 PM1
Please read this installation manual carefully before starting the installation. It will tell you necessary information.
CONTENTS
Safety Precautions ..................................................... 3
Part Names ................................................................. 4
Manual Operation ....................................................... 5
How the air conditioner works .................................. 5
Optimal operation ...................................................... 6
Preparation Before Installation ................................. 6
Installation Procedure ............................................... 8
Maintenance ............................................................. 15
Operation tips ........................................................... 16
Trouble Shooting Guide .......................................... 17
Technical Specification ........................................... 18
Declaration of conformity........................................ 22
Quality POLICY
We will continuously strive to satisfy our customers with consistent reli­ability in product, service and support through superior quality, service culture and distinctive technology.
J199.pmd 31/03/2005, 9:52 PM2
Set
Outdoor
Indoor
R22 (50 Hz) R22 (60 Hz) R407C (50 Hz) R410A (50 Hz)
MLCAxxFSAAAA MLCAxxFSAADA MLCBxxFSAAAA MACCxxFSAAA
MLHAxxFSAAAA MLHAxxFSAADA MLHBxxFSAAAA MAHCxxFSAAA
MLDAxxFS-AAA MLDAxxFS-ADA MLDBxxFS-AAA MADCxxFS-AAA
MLJAxxFS-AAA MLJAxxFS-ADA MLJBxxFS-AAA MAJCxxFS-AAA
MLEAxxFS-AAA MLEAxxFS-ADA MLEBxxFS-AAA MAECxxFS-AAA
MLKAxxFS-AAA MLKAxxFS-ADA MLKBxxFS-AAA MAKCxxFS-AAA
REQUIRED TOOLS
1.
Screw driver
2.
Hexagonal wrench
3.
Torque wrench
4.
Spanner
5.
Reamer
6.
Hole core drill
7.
Tape measure
8.
Thermometer
9.
10.
11.
12.
13.
14.
15.
Manifold gauge Gas leak detector Vacuum pump Pipe clamp Pipe cutter Flare tool set Electrical circuit tester
EXTENDED PARTS
1.
Refrigarant Pipe
Models
Liquid size 1/4 inch 1/4 inch 3/8 inch
Gas size 3/8 inch 1/2 inch 5/8 inch
2.
Pipe insulation material (Polyethylene foam 9 mm thick)
3.
Vinyl tape
4.
Putty
07-09 12-18 24
SAFETY PRECAUTIONS
• Please read this installation manual carefully before starting installation of the unit.
• This air conditioning system contains refrigerant under pressure, rotating parts and electrical connection which may be dangerous and can cause injury. Installation and maintenance of this air conditioning system should only be carried out by trained and qualified personnel.
• After unpacking, please check the unit carefully for possible damage.
• Before undertaking any work on the unit, make sure that the power supply has been disconnected.
WARNING & CAUTIONS
INSTALLATION
Do not store or unpack the unit in a wet area or expose to rain or water.
It may cause the unit to short circuit and may result electric shocks or fire.
Do not conduct installation in wet area or in the rain.
Do not install in a place where flammable gas may leak.
EN
It may cause fire.
This system is designed for domestic or residential use only.
It is a high risk to cause the electrical shocks.
J199.pmd 31/03/2005, 9:53 PM3
If used in certain environments, such as a manufacturing workplace, the equipment may not function efficiently.
ENGLISH
3
PART NAMES
INDOOR UNIT
1
2
7
4
8
5
C O O D R
Y H E A
T
M O D
E
O N
S
/O
W
F
F
I N
G
S L E
E P
T
I
A
D
R
IR
IR
E S
E
ET
C
T
LO
IO
CK
N
T IM
E
R
O
9
LE D
D ISP L
A
Y
TU
R BO
OUTDOOR UNIT
12
13
DISPLAY PANEL
INDOOR & OUTDOOR UNIT
1 Front panel
3
10
2 Air inlet 3 Air filter 4 Air outlet 5 Horizontal air flow grille 6 Vertical air flow louver 7 Display panel
6
Bio Filter
The perfection of MasterGold begins with the innovative Bio Screen for purifying air. This Bio Screen works in a twofold manner to give you the maximum effect of purification and dust elimination.
S
E T
A
T
U
E
T
M
O
P E R
A T
L
U
R E (C
)
F
A
N H I G
H
M
E D
L O
T
W
E M
P
F A
N S
P E E
D
M E R
O N
F F
11
DISPLAY PANEL
1 AUTO indicator
This indicator illuminates when the air conditioner is in AUTO operation.
2 DEFROST indicator (For Cooling & Heating models only)
This indicator illuminates when the air conditioner starts defrosting automatically or when the warm air control feature is activated in heating operation.
3 TEMPERATURE indicator
Displays the temperature settings when the air conditioner is operational.
4 OPERATION indicator
This indicator flashes after power is on and illuminates when the unit is in operation.
5 TIMER indicator
This indicator illuminates when TIMER is set ON/OFF.
8 Remote controller signal
receiver
9 Remote controller 0 Manual control button
- Connecting pipe, drain hose = Air inlet (side and rear) ~ Air outlet
4
Signal receptor
AUTOAUTO
DEFROSTDEFROST TIMERTIMER
1
22
3
ENGLISH
OPERATIONOPERATION
4
NOTE
All the pictures in this manual are for explanation purpose only. They may be slightly different from the air conditioner your purchased. The actual shape shall prevail.
OPERATING TEMPERATURE
5
Temperature
Mode
Room temperature
Outdoor temperature
CAUTIONS
1. If air conditioner is used outside of the above conditions, certain safety protection features may come into operation cause the unit to function abnormally.
2.
Room relative humidity less than 80%. If the air conditioner oper­ates in excess of this figure, the surface of the air conditioner may attract condensation. Please sets the vertical air flow louver to its maximum angle (Vertically to the floor), and set HIGH fan mode.
3. Optimum performance will be achieved within these operating temperature.
Cooling
operation
17°C-32°C
Heating
operation
17°C-30°C
Drying
operation
17°C-32°C
18°C-43°C -7°C-24°C 18°C-43°C
J199.pmd 31/03/2005, 9:53 PM4
MANUAL OPERATION
Manual operation can be used temporarily in case you can not find the remote controller or its batteries are exhausted.
1 Open and lift the front panel up to an angle at which it remains
fixed with a clicking sound.
2 Press the button until the AUTO indicator is lit, the unit will work in
forced AUTO mode.
3 Close the panel firmly to its original position.
Panel
CAUTIONS
• Once you push the manual button, the operation mode is shifted in an order as: AUTO, COOL, OFF.
• Push the button twice, the unit will operate in forced COOL mode. This is used for testing purposes only . Third press will stop the operation and turn off the air conditioner operation.
• To restore the remote controller operation, use the remote controller directly.
Manual control button
AUTO / COOL
HOW THE AIR CONDITIONER WORKS
Set Temperature
Set Temperature
Room temperature
Press Sleep button
1
1
1 hour 1 hour
Cooling
Press Sleep button
1
1 hour 1 hour
Heating
Cooling
Fan only
Cooling
Fan only
set temperature
1
Time
Cooling
AUTOMATIC OPERATION
• When you set the air conditioner in AUTO mode, it will automatically select cooling, heating (cooling/heating models only), or fan only operation depending on what temperature you have selected and the room temperature.
• The air conditioner will control room temperature automatically around the temperature point set by you.
• If the AUTO mode is uncomfortable, you can select desired conditions manually.
SLEEP OPERATION
• When you push SLEEP button during cooling, heating (cooling only type without), or AUTO operation, the air conditioner will automatically increase (cooling) or decrease (heating) 1°C per hour. The set temperature will be steady 2 hours later.
• The fan speed will be automatically controlled.
DRYING OPERATION
• The dry mode will automatically select the drying operation based on the difference between the set temperature and the actual room temperature.
• The temperature is regulated while dehumidifying by repeating turning on and off of the cooling operation or fan only. The fan is low.
EN
DRYING operation
J199.pmd 31/03/2005, 9:53 PM5
ENGLISH
5
OPTIMAL OPERATION
To achieve optimal performance, Please note the following:
• Adjust the air flow direction correctly so that it is not directed on people.
• Adjust the temperature to achieve the highest comfort level. Do not adjust the unit to excessive temperature levels.
• Close doors and windows on COOL or HEAT modes, or performance may be reduced.
• Use TIMER ON button on the remote controller to select a time you want to start your air conditioner.
• Do not put any object near air inlet or air outlet, as the efficiency of the air conditioner may be reduced and the air conditioner may stop running.
• Clean the air filter periodically, otherwise cooling or heating performance may be reduced.
• Do not operate unit with horizontal louver in closed position.
PREPARATION BEFORE INSTALLATION
• Before doing any work, check the interior power supply cord and the main breaker capacity are sufficient and the installation area is sufficient and complies with the requirements.
• Check that the power supply available agrees with name plate voltage.
• Electrical work, wiring and cables must be in compliance with national and local wiring codes and standard.
• Do not use the extension cables. In the case extended cables are needed, use the terminal block.
SELECTION OF THE LOCATION
• Select a place which provides the space around the units as shown in the diagram below.
INDOOR UNIT OUTDOOR UNIT
Models
A 12cm 12cm 12cm 12cm 12cm
B 70cm 70cm 70cm 70cm 70cm
C 12cm 12cm 12cm 12cm 12cm
D 15cm 15cm 15cm 15cm 15cm
CAUTION
• Do not install in a place that cannot bear the weight of the unit.
07 09 12 18 24
Models
A 30cm 30cm 30cm 30cm 30cm
B 200cm 200cm 200cm 200cm 200cm
C 60cm 60cm 60cm 60cm 60cm
D 30cm 30cm 30cm 30cm 30cm
07 09 12 18 24
6
ENGLISH
J199.pmd 31/03/2005, 9:53 PM6
OUTDOOR UNIT PICTURES
MLDA-MLJA 07-09, MLDB-MLJB 07-09, MADC-MAJC 07
225
404
540
75
525
80
261
6082
5
250
88
700
458
88
33
35
60
MLDA-MLJA 12-18, MLDB-MLJB 12, MADC-MAJC 09-12
245
5
420
540
527
272
298
128
780
MLDB-MLJB 18
285
290
750
590
62
530 110
MLDA-MLJA 24, MLDB-MLJB 24, MADC-MAJC 18-24
694.5
351.2
843
301.5
135
560.1141.5
313
EN
10
266
48
548 115
45
90
335
235
125
ENGLISH
7
J199.pmd 31/03/2005, 9:53 PM7
PARTS INSTALLATION
Number
Name of part Q’ty 1 Installation plate 1 2 Clip anchor 8 3 Self-tapping screw A ST3.9X25 8
Liquid side
Connecting
4
pipe
assembly
Gas side
5 Remote controller 1 6 Self-tapping screw B ST3.9X10 2 7 Remote controller holder 1 8 Seal 1 9 Drain joint 1
NOTES
Except the above parts provided, the other parts needed during installation you must purchase.
CAUTIONS
• Ensure that the space around the left and right of the indoor unit is more than 12cm. The indoor unit should be installed allowing a minimum clear­ance of 15cm from the ceiling.
• Use a stud finder to locate studs to prevent unnecessary damage to the wall.
• A minimum pipe run of 3 metres is required to minimise vibration & excessive noise.
• The indoor unit should be installed on the wall at a height of
2.3 metres or more from the floor .
A, B and C directions should be free from obstructions.
NOTES
• This illustration is for explanation purposes only.
• Copper lines must be insulated independently.
ø 6.35 ø 9.53 (<12000Btu/h model) ø
12.7 (21000Btu/h model > Cooling capacity f 12000Btu/h model)
ø 16 (f21000Btu/h model)
Parts
you
must
purchase
1
2c
m minimum
5
Remote Controller
30c
m
minimu
A
m
00cm
2
B
3
2
15cm
m
in
i
m
um
1
12cm
minimum
A
ir F
ilter
Self-tapping screw B ST3.9X10
6
Remote Controller holer
60cm minimum
mum
i
n
mi
47
m
u
0cm minim
3
60
c
m
Loop the
m
connective
i
nim
u
m
cable.
C
INSTALLATION PROCEDURE
INDOOR UNIT
Fixing
• Place the installation guide pattern on the designated installation place and mark the hole position.
• Drill a hole and mount installation plate.
ø 65 mm
• After determining the pipe
hole position. Drill the hole at a slight downward slant towards the outdoor side.
Note: When installing
Indoor
the refrigerant pipes from others side. A hole must be place to allow fall towards the outdoor unit.
8
ENGLISH
.
.
.
.
.
..
....
.
..
.
..
.
..
.
.
.
.
.
..
.
.....
.
.
..
.
..
.....
.
....
.
.
Outdoor
.
.
..
.
.
..
...
...
.
.
..
.
.
...
.
.
.
.
.
..
.
..
..
...
...
.
.
....
.
.
.
..
.
..
.
.
.
.
.
...
..
.
..
.
Make 6 mm 4-6 holes, in the wall at the four corners of mouting plate (bracket) then insert appropriate mouting devices.
Install the mounting plate using 4-6 pieces of mounting screw securely at four corners and tighten the screw completely. Do not over tighten the screws and deform the back plate.
MODEL 07-12
Indoor unit outline
120mm or more to wall
Left refrigerant pipe hole 65
MODEL 18
120mm or more to wall
Left refrigerant pipe hole 65
293
Indoor unit outline
150mm or more to ceiling
750
( 12000Btu/h model)
150mm or more to ceiling
( 12000Btu/h model)
920
Installation plate
45
Installation plate
250
Right refrigerant pipe hole 65
120mm or more to wall
120mm or more to wall
Right refrigerant pipe hole 65
J199.pmd 31/03/2005, 9:53 PM8
MODEL 24
Above 120mm from
the wall
330
Pipe hole
Above 150mm from the ceiling
Hooked Part
432
95
58
50
115
465
Hooked Part
1080
Indoor Unit Outline
432
465
115
Hooked Part
108
22
95
Above 120mm from
5850
Pipe hole
CAUTION
Be careful when handling the sharp edge of the mounting plate.
the wall
Right
A
Right
B
D
C
Right
Right
E
Rear Bottom
Left
F
Wiring
• This indoor unit is ready for connection to the outdoor unit.
CAUTIONS
• Never modify the unit by removing any of the safety guards
or by passing any of the safety interlock swithces.
• Connect the interconnecting cable correctly and connect
the connecting cable to terminal as identified with their respective marking.
Do not damage the conductor core or inner insulation of power supply cables and do not deform or crush the cables.
Drain hose
• Drain hose is flexible and can be routed to suit various
piping arrangements. The drain line must include elbow trap (U bend). Connect a plastic condensate pipe with an internal diameter of 12 mm.
Piping
The auxiliary piping can be connected in the diections shown the above diagram. To connect in the D, E and
F
direction, pipes will need to be extended.
CAUTIONS
• Bend pipes carefully to avoid flattening or obstructing them if the pipes are bent incorrectly, the indoor unit may be unstable on the wall.
• Carefully arrange pipes so that pipes do not stick out of the rear plate of the indoor unit.
For right and right rear piping
Drain hose
Drain cap
Verification of condensate water drainage:
Fill the drain pan with water and observe evacuation.
EN
Note: Do not put the drain hose end into water.
The drain hose can be connected to the left or the right side.
For left and left rear piping
Drain hose
Drain cap
J199.pmd 31/03/2005, 9:53 PM9
ENGLISH
9
Indoor Unit Fixing
• Thread the indoor unit piping and cable through the hole.
• Hang the top of the unit onto the upper ridge of them in mounting plate.
• Make sure that the unit is correctly hung in place by sliding it to the left, then to the right.
• Press the bottom left and bottom right hand corners of the unit against the mounting plate until the fixing prongs click into place in the retainers provided to that effect.
Drainage line
Interconnection cable
OUTDOOR UNIT
Fixing and Piping
• Piping must be performed by qualified personnel according to good refrigeration systems practices.
• Piping materials and insulation materials must be of refrigerant quality.
• Select the pipe diameters according to the size of unit and cut the pipe to design length by using pipe cutter.
• Install the flare nuts and flare the end of the pipes.
• Check that no foreign bodies are inside the piping.
• Align the central of the connecting pipes and tighten the flare nut.
• Fix piping with pipe clamps and check that any pipe vibrations cannot be transmitted to the building structure.
NOTES
• Connect the pipe correctly.
• Do not apply the excessive torque.
• Use an appropriate bending tool to form curves and avoid over-tightening the refrigerant tubes.
• To prevent heat loss, the two lines must be insulated separately.
Maximum Piping Length
Unit size
7 9 12 18 24
(m) 10 10 10 15 15
MODELS
a
Condensate drainage line
Note: The condensate evacuation line should be taped to the
refrigerant lines with vinyl tape.
Vinyl tape
a) Access plate for the
condensate drainage pump detection (condensate pump is available as an accessory).
Refrigerant charge to be added per extra meter of piping length when more than 7.5 meters.
Unit size
7 9 12 18 24
g/m 15 15 15 40 40
MODELS
Refrigerant piping connections (FLARE connections)
To avoid alteration of unit capacities, check that piping lengths and changes in elevation are kept to a strict minimum.
Before connectiong the refrigerant lines, follow the procedures below (if pre-charged connection lines are not supplied):
- Select copper pipe diameters according to the size of
unit to be installed.
- Install the refrigeration lines, checking that no foreign
boodies get inside the piping.
- Install the flare connectors and flare the ends of the pipes.
- Evacuate the piping. This operation, which should last
at least 15 minutes if there are large piping lengths and
changes in elevation, should be followed by a leak test.
The suction line must have a 2% gradient up to the compressor on horizontal sections. Where piping lengths are unusually long and include a large number of oil traps, it may be necessary to adjust to compressor charge.
10
ENGLISH
J199.pmd 31/03/2005, 9:54 PM10
To this effect, when the piping has been evacuated, close the pressure gauge tap, note the value on the gauge, then wait for 15 minutes. If the needle moves, there is a leak in the system. Make the necessary adjustments or repairs and repeat this procedure until the needle no longer moves.
- Open the service valves and top up the refrigerant charge if necessary.
Installation
Minimum thickness 6 mm
Heat pump (discharge)
Heat pump
Liquid
Cooling
Cooling
(suction)
Cooling
(suction)
Heat pump (discharge)
GAS
Heat pump
Liquid
Cooling
Low pressure
Outdoor unit
High pressure
Manifold
Liquid valve
Pressure tap
Gas line
Liquid line
Gas valve
Indoor unit
R22/R407C/R410A
This unit is shipped complete with a charge of R22/R407C/R 410A refrigerant that will be sufficient for an interconnecting piping length of 5 meters.
EN
COLD AREA RECOMMENDATION
- Outdoor heat pump unit : install the unit at least 10 cm above ground level to facilitate drainage of defrost water and prevent accumulation of ice. In effect, defrost water can cause accumulation of ice under the unit during subfreezing outdoor temperatures.
- In areas with heavy snowfall it is best to install the unit on wall supports.
- In some regions. It is necessary to heat the bottom of the condensate drainage pan and the condensate drainage piping to avoid ice formation, and resulting ice build-up in the fan compartment (heater strip must be at least 25 w/m).
OK
ENGLISH
11
J199.pmd 31/03/2005, 9:54 PM11
Wiring
Prepare the power source for exclusive with the air conditioner. The supply voltage must comply with the rated voltage of the air conditioner: The plug socket shall be accessible after installation.
Remark: All the wiring must be based on the wiring nameplate which is shown on the model.
CAUTIONS
Perform the wiring with sufficient capacity. Installation places legally require a short circuit isolator to be attached to
prevent electrical shock. Do not extend the power cable code by cutting.
Power voltage should be in the range of 90%~110% of rated voltage.
The plug of the air conditioner takes a grounding leg, and clients should use a grounding socket so that the air
conditioner can be grounded efficiently. If the power cord is damaged, replacement should be conducted by qualified technician or a serviceman.
Note Remark per EMC Directive 89/336/EEC
NOTE
To prevent flicker impressions during the start of the compressor (technical process), following installation conditions do apply.
1. The power connection for the air conditioner has to be done at the main power distribution.
The distribution has to be of an low impedance, normally the required impedance reaches at a 32 A fusing point.
2. No other equipment has to be connected with this power line.
3. For detailed installation acceptance, please refer to your contract with the power supplier if restrictions do apply for
products like washing machines, air conditioner or electrical ovens.
4. For power details of the air conditioner, refer to the rating plate of the product.
5. For any question, contact your local dealer.
CAUTIONS
Cautions
Never modify the unit by removing any of the safety guards or by bypassing any of the safety interlock swithces.
Connect the connecting cable correctly and connect the connecting cable to terminal as identified with their respective marks.
Do not scratch the conductive core & inner insulator of power supply cables and do not deform or smash on the surface of cables.
Electrical Connections
All electrical wiring and connections must comply with local codes and standards. Power supply cord and interconnection cord used must not be lighter than Polychloroprene sheeted cord (245 IEC 57 or H05RN-F). Disconnecting device must have a contact separation of at least 3 mm.
Models : 07-18 (Cooling only)
Power supply
220-240V/1Ph/50Hz
220-230V/1Ph/60Hz
LN 1
1
2(N)
2(N)
Indoor
Outdoor
Models : 24 (Cooling only / Cooling and Heating)
1
2(N)
S
Indoor
Outdoor
S
Power supply
220-240V/1Ph/50Hz
220-230V/1Ph/60Hz
LN
1
2(N)
Models : 07-18 (Cooling and Heating)
Power supply
220-240V/1Ph/50Hz
220-230V/1Ph/60Hz
LN 12(N) 34
2(N) 34
1
Indoor
Outdoor
For correct installation, a proper ground connection must be made for unit.
12
ENGLISH
J199.pmd 31/03/2005, 9:54 PM12
Wiring Connection
e
Models : 07-18
Indoor
Terminal block of indoor unit
Outdoor
Terminal block of outdoor unit
1 2(N) 3 4
Cord clamp
To outdoor unit To outdoor unit
Cooling only type
1 2(N) 3 4
Cooling & heating type Cooling only type Cooling & heating type
Models : 24
Indoor
Terminal block of indoor unit
S
1 2 (N)
Cooling only type / cooling & heating type
1 2(N)
Wire-holding
board
1 2(N) 3 4
Outdoor
T
Terminal block of outdoor unit
1 2(N) S L N
Cooling only type / cooling & heating type
Terminal block of Outdoor unit
1
2(N)
3 4 5 6 7 8
Cord clamp
Cooling & heating type
EN
J199.pmd 31/03/2005, 9:54 PM13
ENGLISH
13
Electrical Work
Switch and
Fuse rating
7000-9000 Btu/h
12000 Btu/h
18000 Btu/h
24000 Btu/h
Power SourceModel
220-240V ~ 50Hz
220-230V ~ 60Hz
220-240V ~ 50Hz
220-230V ~ 60Hz
220-240V ~ 50Hz
220-230V ~ 60Hz
220-240V ~ 50Hz
220-230V ~ 60Hz
NOTE
The supply volyage must be consistent with the rate voltage of the air conditioner.
Defrosting operation (Available for heating only)
1.
Condition to start defrosting: Units will switch to defrosting mode when either of the following conditions is met.
a. Unit has been running under T3<0ºC for 40
minutes and T3<-3ºC for 3 minutes.
T3 (°C)
2
1
0 5 10 15 20 25 30 35 40 45 50
0
-1
-2
-3
-4
-5
Starting Defrosting Mode under condition a.
Time Elapsed (min)
40 min
Heating mode Defrosting mode
3 min
b. Unit has been running at high temperature
protection mode* for 90 minute. (*High temperature protection mode: when coil temperature of indoor unit reaches 55°C, outdoor unit will turn off external unit fan but still keep compressor running).
2. Condition to stop defrosting: Units will switch back to heating mode when either of the following conditions is met.
a. Unit has been running at defrosting mode for 10
minutes.
b. T3>20
ºC
Remark: T3 is coil temperature of outdoor units.
10A
16A
25A
32A
Wiring size
ff
f 1.0 mm
ff
ff
f 1.5 mm
ff
ff
f 2.5 mm
ff
2
2
2
14
ENGLISH
J199.pmd 31/03/2005, 9:54 PM14
MAINTENANCE
Household
Drain
Cleaner
No
WARNING
It is necessary to stop the air conditioner and disconnect the power supply before cleaning.
Cleaning the indoor unit and remote controller
Tinenr
h
Filter Handle
CAUTION
Use a dry cloth to wipe the indoor unit and remote controller.
A cloth dampened with cold water may be used on the indoor unit if
it is very dirty.
The front panel of the indoor unit can be removed and cleaned with water. Then wipe it with a dry cloth.
Do not use a chemically treated cloth or duster to clean the unit.
Do not use benzine, thinner, polishing powder, or similar solvents for
cleaning. These may cause the plastic surface to crack or deform.
Cleaning the air filter
A clogged air filter reduces the cooling efficiency of this unit. Please clean
the filter once every 2 weeks.
Lift the indoor unit panel up to an angle until it stops with a clicking sound.
1.
2. Take hold of the handle of the air filter and lift it up slightly to take it out from the filter holder, then pull it downwards.
3. Remove the AIR FILTER from the indoor unit.
Clean the AIR FILTER once two weeks.
Clean the AIR FILTER with a vacuum cleaner or water, then dry it up
in cool place.
4. Remove the Electrostatic Filter from its support frame as shown in the Figure on the left (Not applicable to the units without electrostatic filter).
Do not touch this Electrostatic Filter within 10 minutes after opening the inlet grille, it may cause an electric shock.
Clean the Electrostatic Filter with mild detergent or water and dry in
the sunlight for two hours.
Before re-install the Electrostatic Filter, check whether the corona line
or support frame is damaged or not.
5. Install the AIR FILTER back into position.
6. Insert the upper portion of the AIR FILTER back into the unit taking care that the left and right edges line up correctly and place filter into position.
Maintenance
If you plan to idle the unit for a long time, perform the following: (1) Operate the fan for about half a day to dry the inside of the unit. (2) Stop the air conditioner and disconnect power.
Remove the batteries from the remote controller.
(3) The outdoor unit requires periodic maintenance and cleaning. Do not
attempt to do this yourself. Contact your dealer or servicer.
Checks before operation
Check that the wiring is not broken off or disconnected.
Check that the air filter is installed.
Check if the air outlet or inlet is blocked after the air conditioner has not
been used for a long time.
EN
J199.pmd 31/03/2005, 9:54 PM15
CAUTION
Do not touch the metal parts of the unit when removing the filter. Injuries can occur when handling sharp metal edges.
Do not use water to clean inside the air conditioner. Exposure to water can destroy the insulation, leading to possible electric shock.
When cleaning the unit, first make sure that the power and circuit breaker are turned off.
ENGLISH
15
OPERATION TIPS
The following events may occur during normal operation.
1. Protection of the air conditioner.
Compressor protection
The compressor cant restart for 3 minutes after it stops. Anti-cold air (Cooling and heating models only)
The unit is designed not to blow cold air on HEAT mode, when the indoor heat exchanger is in one of the following three situations and the set temperature has not been reached. A) When heating has just starting. B) Defrosting. C) Low temperature heating.
The indoor or outdoor fan stop running when defrosting (Cooling and heating models only). Defrosting (Cooling and heating models only)
Frost may be generated on the outdoor unit during heat cycle when outdoor temperature is low and humidity is high resulting in lower heating efficiency of the air conditioner.
During this condition air conditioner will stop heating operation and start defrosting automatically.
The time to defrost may vary from 4 to 10 minutes according to the outdoor temperature and the amount of frost
buildup on the outdoor unit.
2. A white mist coming out from the indoor unit.
A white mist may generate due to a large temperature difference between air inlet and air outlet on COOL mode in an indoor environment that has a high relative humidity.
A white mist may generate due to moisture generated from defrosting process when the air conditioner restarts in HEAT mode operation after defrosting.
3. Low noise of the air conditioner.
You may hear a low hissing sound when the compressor is running or has just stopped running. This sound is the sound of the refrigerant flowing or coming to a stop.
You can also hear a low squeak sound when the compressor is running or has just stopped running. This is caused by heat expansion and cold contraction of the plastic parts in the unit when the temperature is changing.
A noise may be heard due to louver restoring to its original position when power is first turned on.
4. Dust in blown out from the indoor unit.
This is a normal condition when the air conditioner has not been used for a long time or during first use of the unit.
5. A peculiar smell come out from the indoor unit.
This is caused by the indoor unit giving off smells permeated from building material, from furniture, or smoke.
6. The air conditioner turns to FAN only mode from COOL or HEAT (for cooling and heating models only) mode.
When indoor temperature reaches the temperature setting on air conditioner, the compressor will stop automatically, and the air conditioner turns to FAN only mode. The compressor will start again when the indoor temperature rises on COOL mode or falls on HEAT mode (for cooling and heating models only) to the set point.
7. Dripping water may generate on the surface of the indoor unit when cooling in a high relatively humidity (relative
humidity higher than 80%). Adjust the horizontal louver to the maximum air outlet position and select HIGH fan speed.
8. Heating mode (For cooling and heating models only)
The air conditioner draws in heat from the outdoor unit and releases it via the indoor unit during heating operation. When the outdoor temperature falls, heat drawn in by the air conditioner decreases accordingly. At the same time, heat loading of the air conditioner increases due to larger difference between indoor and outdoor temperature. If a comfortable temperature cant be achieved by the air conditioner, we suggest you use a supplementary heating device.
9. Auto-restart function
Power failure during operation will stop the unit completely. For the unit without Auto-restart feature, when the power restores, the OPERATION indicator on the indoor unit starts flashing. To restart the operation, push the ON/OFF button on the remote controller. For the unit with Auto-restart feature, when the power restores, the unit restarts automatically with all the previous settings preserved by the memory function.
10.
Lightning or a car wireless telephone operating nearby may cause the unit to malfunction.
Disconnect the unit with power and then re-connect the unit with power again. Push the ON/OFF button on the remote controller to restart operation.
16
ENGLISH
J199.pmd 31/03/2005, 9:54 PM16
TROUBLE SHOOTING GUIDE
Problem Probable cause Remedy
A. The air conditioner does not run. 1. Power failure. 1. Wait for power resume.
2. Fuse blown or circuit breaker 2. Replace the fuse or reset the open. breaker.
3. Voltage is too low. 3. Find the cause and fix it.
4. Faulty contactor or relay. 4. Replace the faulty component.
5. Electrical connections loose. 5. Retighten the connection.
6. Thermostat adjustment too low 6. Check thermostat setting. (in heating mode) or too high (in cooling mode).
7. Faulty capacitor. 7. Find the cause then replace
capacitor.
8. Incorrect wiring, terminal loose. 8. Check and retighten.
9. Pressure switch tripped. 9. Find the cause before reset.
B. The outdoor fan runs but the 1. Motor winding cut or grounded. 1. Check the wiring and the compressor will not start. compressor winding resistance.
2. Faulty capacitor. 2. Find the cause then replace
capacitor.
C. There is insufficient heating or 1. There is a gas leak. 1. Remove charge, repair, evacuate cooling. and recharge.
2. Liquid and gas line insulated 2. Insulate them separately. together.
3. The room was probably very hot 3. Wait while unit has enough time to (cool) when you started the cool the room. system.
The compressor runs continuously.
D.
E. The compressor starts but shuts 1. Too much or too little refrigerant. 1. Remove charge, evacuate and down quickly. recharge.
F. Clicking sound is heard from In heating or cooling operation any In heating or cooling operation any
the air conditioner. plastic parts may expand or shrink plastic parts may expand or shrink due
1. Thermostat adjustment too low 1. Check thermostat setting. (in heating mode) or too high (in cooling mode).
2. Faulty fan. 2. Check condenser air circulation.
3. Refrigerant charge too low, leak. 3. Find leak, repair and recharge.
4. Air or incondensables in 4. Remove charge, evacuate and refrigerant circuit. recharge.
2. Faulty compressor. 2. Determine the cause and replace
compressor.
3. Air or incondensables in 3. Remove charge, evacuate and refrigerant circuit. recharge.
4. Changeover valve damaged or 4. Replace it. blocked open (heat pump unit).
due to a sudden temperature change in this event, a clicking sound may event, a clicking sound may occur. occur.
to a sudden temperature change in this
EN
J199.pmd 31/03/2005, 9:54 PM17
ENGLISH
17
TECHNICAL SPECIFICATION
Technical Specifications : Master Gold R22 - 50 Hz
Indoor
Unit
Models
Power Supply
Power Consumption KW Running Current A Refrigerant Type Refrigerant Charge
Noise level
Power Supply
Air flow m Input Power W
Fan
Running Current A
Indoor Unit
Dimension Width mm
Weight kg System Operation Control
Power Supply
Compressor
Dimension Width mm
Outdoor Unit
Weight kg
Type Pipe Suction inch
Piping
Size Liquid inch
Outdoor
Indoor Outdoor
Height mm
Depth mm
Qty Compressor Type Height mm
Depth mm
MLEA07 MLKA07 MLEA09 MLKA09 MLEA12 MLKA12 MLEA18 MLKA18 MLEA24 MLKA24
Unit
MLDA07 MLJA07 MLDA09 MLJA09 MLDA12 MLJA12 MLDA18 MLJA18 MLDA24 MLJA24
V/Ph/Hz
Ph
gr
dB(A)
V/Ph/Hz
Ph
3
/h
V/Ph/Hz
Ph
111 11
0.8 0.8 1.01 1.01 1.35 1.35 1.96 1.96 2.8 2.8
3.5 3.5 4.6 4.6 6.0 6.0 9.4 9.4 12.5 12.5
530 570 580 800 850 900 1130 1400 1450 1900
35/32/30 35/32/30 37/34/32 37/34/32 37/32/28 37/32/28 42/40/38 42/40/38 45/42/39 45/42/39
49 49 50 50 54 54 56 56 55 55
1 111 1 11 1 11
400 400 450 450 580 580 800 800 1080 1080
39.5 39.5 39.5 39.5 38.5 38.5 53 53 65 65
0.17 0.17 0.17 0.17 0.17 0.17 0.24 0.24 0.29 0.29
250 250 250 250 265 265 292 292 330 330
710 710 710 710 790 790 920 920 1080 1080
190 190 190 190 195 195 225 225 225 225
8 8 8 8 9 9 13 13 17 17
1 111 1 11 1 11
1 111 1 11 1 11
535 535 535 535 540 540 590 590 695 695
700 700 700 700 780 780 780 780 845 845
235 235 235 235 250 250 250 250 335 335
25.5 26 26.5 28.5 34 35 37 40 56 60
3/8 3/8 3/8 3/8 1/2 1/2 1/2 1/2 5/8 5/8
1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 3/8 3/8
MLEA-MLKA
MLDA-MLJA
220-240/1/50
R22
220-240/1/50
Wireless Control with LCD Display
220-240/1/50
Rotary
Flare + Nut
Remark: The above design and specifications are subject to change without prior notice for product improvement.
18
ENGLISH
J199.pmd 31/03/2005, 9:54 PM18
TECHNICAL SPECIFICATION
Technical Specifications : Master Gold R22 - 60 Hz
Indoor
Unit
Models
Power Supply
Power Consumption KW Running Current A Refrigerant Type Refrigerant Charge
Noise level
Power Supply
Indoor Unit
Dimension Width mm
Weight kg System Operation Control
Power Supply
Compressor
Dimension Width mm
Outdoor Unit
Weight kg
Indoor Outdoor
Air flow m Input Power W
Fan
Running Current A
Height mm
Depth mm
Qty Compressor Type Height mm
Depth mm
Type Pipe Suction inch
Piping
Size Liquid inch
MLEA07 MLKA07 MLEA09 MLKA09 MLEA12 MLKA12 MLEA18 MLKA18 MLEA24 MLKA24
Outdoor
Unit
MLDA07 MLJA07 MLDA09 MLJA09 MLDA12 MLJA12 MLDA18 MLJA18 MLDA24 MLJA24
V/Ph/Hz
Ph
gr
dB(A)
V/Ph/Hz
Ph
3
/h
V/Ph/Hz
Ph
111 11
0.71 0.71 0.95 0.95 1.21 1.21 1.95 1.95 2.67 2.67
3.2 3.2 4.5 4.5 5.5 5.5 8.9 8.9 12.1 12.1
530 590 630 650 780 1050 1180 1450 1450 1900
35/32/30 35/32/30 35/32/30 35/32/30 37/32/28 37/32/28 42/40/38 42/40/38 48/45/42 48/45/42
52 52 52 53 56 56 56 56 58 58
11111
400 400 400 400 580 580 800 800 1080 1080
31 31 31 31 31 31 53 53 150 150
0.14 0.14 0.14 0.14 0.14 0.14 0.24 0.24 0.68 0.68
250 250 250 250 265 265 292 292 330 330
710 710 710 710 790 790 920 920 1080 1080
190 190 190 190 195 195 225 225 225 225
8.5 8.5 8.5 8.5 9.0 9.0 13 13 17 17
111 11
1111111111
535 535 535 535 540 540 540 540 695 695
700 700 700 700 780 780 780 780 845 845
235 235 235 235 250 250 250 250 335 335
27 28 32 30 34 36 37 40 58 60
3/8 3/8 3/8 3/8 1/2 1/2 1/2 1/2 5/8 5/8
1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 3/8 3/8
MLEA-MLKA
MLDA-MLJA
220-230/1/60
R22
220-230/1/60
Wireless Control with LCD Display
220-230/1/60
EN
Rotary
Flare + Nut
Remark: The above design and specifications are subject to change without prior notice for product improvement.
ENGLISH
J199.pmd 31/03/2005, 9:54 PM19
19
TECHNICAL SPECIFICATION
Technical Specifications : Master Gold R407C - 50 Hz
Indoor
Unit
Models
Power Supply
Power Consumption KW Running Current A Refrigerant Type Refrigerant Charge
Noise level
Power Supply
Air flow m Input Power W
Fan
Running Current A
Indoor Unit
Dimension Width mm
Weight kg System Operation Control
Power Supply
Compressor
Dimension Width mm
Outdoor Unit
Weight kg
Type Pipe Suction inch
Piping
Size Liquid inch
Outdoor
V/Ph/Hz
Indoor Outdoor
V/Ph/Hz
Height mm
Depth mm
V/Ph/Hz
Qty Compressor Type Height mm
Depth mm
MLEB07 MLKB07 MLEB09 MLKB09 MLEB12 MLKB12 MLEB18 MLKB18 MLEB24 MLKB24
Unit
MLDB07 MLJB07 MLDB09 MLJB09 MLDB12 MLJB12 MLDB18 MLJB18 MLDB24 MLJB24
Ph
gr
dB(A)
Ph
3
Ph
/h
111 11
0.78 0.78 1 1 1.35 1.35 1.96 1.96 2.73 2.73
3.5 3.5 4.4 4.4 6.0 6.0 9.4 9.4 12.5 12.5
680 700 820 850 900 1200 1400 1400 1950 2050
35/32/30 35/32/30 37/34/32 37/34/32 37/32/28 37/32/28 42/40/38 42/40/38 45/42/39 45/42/39
49 49 50 50 54 52 56 56 55 55
111 11
400 400 450 450 580 580 800 800 1080 1080
39.5 39.5 39.5 39.5 44 44 53 53 65 65
0.17 0.17 0.17 0.17 0.2 0.2 0.26 0.26 0.37 0.37
250 250 250 250 265 265 292 292 330 330
710 710 710 710 790 790 920 920 1080 1080
190 190 190 190 195 195 225 225 225 225
8 8 8 8 9 9 13 13 17 17
111 11
1 111 1 11 1 11
535 535 535 535 540 540 590 590 695 695
700 700 700 700 780 780 760 760 845 845
235 235 235 235 250 250 285 285 335 335
25.5 26 27.5 28.5 34 36 42 43 61 62
3/8 3/8 3/8 3/8 1/2 1/2 1/2 1/2 5/8 5/8
1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 3/8 3/8
MLEB-MLKB
MLDB-MLJB
220-240/1/50
R407C
220-240/1/50
Wireless Control with LCD Display
220-240/1/50
Rotary
Flare + Nut
Remark: The above design and specifications are subject to change without prior notice for product improvement.
20
ENGLISH
J199.pmd 31/03/2005, 9:54 PM20
TECHNICAL SPECIFICATION
Technical Specifications : Master Gold R410A - 50 Hz
Indoor
Unit
Models
Power Supply
Power Consumption KW Running Current A Refrigerant Type Refrigerant Charge
Noise level
Power Supply
Indoor Unit
Dimension Width mm
Weight kg System Operation Control
Power Supply
Compressor
Dimension Width mm
Outdoor Unit
Weight kg
Indoor Outdoor
Air flow m Input Power W
Fan
Running Current A
Height mm
Depth mm
Qty Compressor Type Height mm
Depth mm
Type Pipe Suction inch
Piping
Size Liquid inch
MAEC07 MAKC07 MAEC09 MAKC09 MAEC12 MAKC12 MAEC18 MAKC18 MAEC24 MAKC24
Outdoor
Unit
MADC07 MAJC07 MADC09 MAJC09 MADC12 MAJC12 MADC18 MAJC18 MADC24 MAJC24
V/Ph/Hz
Ph
gr
dB(A)
V/Ph/Hz
Ph
3
/h
V/Ph/Hz
Ph
111 11
0.64 0.64 0.82 0.82 1.12 1.12 1.72 1.72 2.53 2.53
2.8 2.8 3.6 3.6 5.0 5.0 7.8 7.8 11.2 11.2
800 820 900 920 1050 1080 1690 1740 1900 1950
35/32/30 35/32/30 37/34/31 37/34/31 40/37/34 40/37/34 42/39/37 42/39/37 45/42/39 45/42/39
49 49 50 50 50 50 52 52 55 55
111 11
450 450 500 500 580 600 850 850 1080 1080
36.5 36.5 39.5 39.5 44 44 53 53 65 65
0.17 0.17 0.17 0.17 0.2 0.2 0.26 0.26 0.37 0.37
250 250 250 250 265 265 292 292 330 330
710 710 710 710 790 790 920 920 1080 1080
190 190 190 190 193 193 225 225 225 225
8 8 8 8 9 9 13 13 17 17
111 11
1 111 1 11 1 11
535 535 540 540 540 540 695 695 695 695
700 700 780 780 780 780 845 845 845 845
235 235 250 250 250 250 335 335 335 335
31 32 36 37 37 38 52 52 59 60
3/8 3/8 3/8 3/8 1/2 1/2 1/2 1/2 5/8 5/8
1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 3/8 3/8
MAEC-MAKC
MADC-MAJC
220-240/1/50
R410A
220-240/1/50
Wireless Control with LCD Display
220-240/1/50
EN
Rotary
Flare + Nut
Remark: The above design and specifications are subject to change without prior notice for product improvement.
ENGLISH
J199.pmd 31/03/2005, 9:54 PM21
21
DECLARACIÓN DE CONFORMIDAD
DECLARATION OF CONFORMITY
DECLARATION OF CONFORMITY
Type of Equipment Brand Name Type Designation
Application of Council Directive (s)
The following harmonized standards have been applied: Standard (s)
EN 60335-2-40/A1:2000 EN 60335-2-40/A1:2000 EN 55014-1:2000/A2:2002 EN 55014-2:1997/A1:2001 EN 55022:1998/A1:2000 EN 61000-3-2:2000 EN 61000-3-3:1995/A1:2001 EN 61000-3-11:2000 EN 60825 EN 60335-1:1994+A11:1995+A1, A12:1996+A13, A14:1998+A15, A2:2000+A16:2001 EN 60335-2-40:1997+A1:2000 EN 55014-1:1993+A1:1997/A2:1999 EN 55104-2:1997 EN 61000-3-2:1995/A1:1998/A2:1998 EN 61000-3-2:1995/A14:2000 EN 61000-3-3:1995 EN 60335-2-40:2003 EN 50366:2003
The product complies with the harmonized European safety standards and harmonized EMC standards listed above.
We have internal production control system that ensures compliance between the manufacturer products and the technical documentation.
The product is CE mark.
We declare under our sold responsibility that the equipment follows the provisions Of the Directives stated above.
Authorized Representative:
Air Conditioners YORK HAEA-HADA07/09/12FS, HAEB-HADB07/09/12FS, HAEC-HADC07/09/12FS, HAKA-HAJA07/09/12FS, HAKB-HAJB07/09/12FS, HAKC-HAJC07/09/12FS, HEEB-HEDB07/09/12/18/24/30FS, HEKB-HEJB07/09/12/18/21/24/30FS, HLEA-HLDA07/09/12/18/24FS, HLCA-HLHA24/28/FS, HMEA09MC/MD/ME, HMDA18MC, HMDA21MD, HMDA27ME, HMKB09MC/MD/ME/MF, HMKB12MD/MF, HMJB18MC, HMJB21MD, HMJB27ME, HMJB30MF, HRKB09AB/AG/AH, HRKB12AG, HRJB18AB, HRJB21AG, HRJB27AH, HRKA09AB, HRJA18AB, HSKB-HSJB07/09/12/18/24FS, HTEA-HTDA18/21/24/30FS, HVKA-HVJA09/12/21/24AS, HVKC-HVJC07/09/12DS, HVKC-HVJC18AS, PECA09/12FD, PECB09/12/14FS, PESA09/12FD, PESB09/12/14FS, PLCA09FC/FD, PLCB09FC/FD, PLSA09FC/FD, PLSB09FC/FD MACC-MAHC07/09/12/18/24FS, MECB-MEHB07/09/12/18/24FS, MLCA-MLHA07/09/12/18/24FS, MLCB-MLHB07/09/12/18/24FS EMC Directive 89/336/EEC, Low Voltage Directive 73/23/EEC and Machine Safety Directive: MSD 98/37/CE
CM Choi Shipping Manager
YORK International (Northern Asia) Ltd.
15/F., Tower II, World Trade Square, 123 Hoi Bun Road, Kwun Tong, Kowloon, Hong Kong Telephone: (852) 2331 9286 Fax: (852) 2331 9840 Technical Service Division: Telephone: (852) 2331 9286 Fax: (852) 2304 0068
INSTALLATION, REMOVAL AND DISPOSALINSTALLATION, REMOVAL AND DISPOSAL
INSTALLATION, REMOVAL AND DISPOSAL
INSTALLATION, REMOVAL AND DISPOSALINSTALLATION, REMOVAL AND DISPOSAL
This product contains refrigerant under pressure, rotating parts, and electrical connections which may be a danger and cause injury!This product contains refrigerant under pressure, rotating parts, and electrical connections which may be a danger and cause injury!
This product contains refrigerant under pressure, rotating parts, and electrical connections which may be a danger and cause injury!
This product contains refrigerant under pressure, rotating parts, and electrical connections which may be a danger and cause injury!This product contains refrigerant under pressure, rotating parts, and electrical connections which may be a danger and cause injury!
All work must only be carried out by competent persons using suitable protective clothing and safety precautions.All work must only be carried out by competent persons using suitable protective clothing and safety precautions.
All work must only be carried out by competent persons using suitable protective clothing and safety precautions.
All work must only be carried out by competent persons using suitable protective clothing and safety precautions.All work must only be carried out by competent persons using suitable protective clothing and safety precautions.
Read the ManualRead the Manual
Read the Manual
Read the ManualRead the Manual
1.1.
1.
Isolate all sources of electrical supply to the unit including any control system supplies switched by the unit. Ensure that all points of electrical and
1.1. gas isolation are secured in the OFF position. connection refer to unit installation instructions.
2.2.
2. Remove all refrigerant from each system of the unit into a suitable container using a refrigerant reclaim or recovery unit. This refrigerant may then
2.2. be reused, if appropriate, or returned to the manufacturer for disposal. Where appropriate, drain the refrigerant oil from each system into a suitable container and dispose of according to local laws and regulations governing disposal of oily wastes.
3.3.
3. Packaged unit can generally be removed in one piece after disconnection as above. Any fixing down bolts should be removed and then unit lifted
3.3. from position using the points provided and equipment of adequate lifting capacity. Reference MUST be made to the unit installation instructions for unit weight and correct methods of lifting. Note that any residual or spilt refrigerant oil should be mopped up and disposed of as described above.
4.4.
4. After removal from position the unit parts may be disposed of according to local laws and regulations.
4.4.
The supply cables and gas pipework may then be disconnected and removed. For points of
Risk of electric shockRisk of electric shock
Risk of electric shock
Risk of electric shockRisk of electric shock
Under No circumstances should refrigerant be vented to atmosphere.Under No circumstances should refrigerant be vented to atmosphere.
Under No circumstances should refrigerant be vented to atmosphere.
Under No circumstances should refrigerant be vented to atmosphere.Under No circumstances should refrigerant be vented to atmosphere.
Unit is remotely controlled andUnit is remotely controlled and
Unit is remotely controlled and
Unit is remotely controlled andUnit is remotely controlled and
may start without warningmay start without warning
may start without warning
may start without warningmay start without warning
YORK® International Corporation
J199.pmd 31/03/2005, 9:54 PM22
Loading...