DUCTLESS SINGLE-SPLIT
AIR CONDITIONERS AND HEAT PUMPS
16 SEER – 1 PHASE
3/4 THRU 2 NOMINAL TONS
MODELS: DCMF/DHMF
Due to continuous product improvement, specifications
are subject to change without notice.
Visit us on the web at
www.upgnet.com
Additional rating information can be found at
www.ahridirectory.org
WARRANTY SUMMARY*
Standard 2-Years limited parts warranty.
Standard 6-Years limited compressor warranty.
TECHNICAL
GUIDE
TECHNICAL
GUIDE
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
923178-UTG-B-0114
DESCRIPTION
The Single-Split Series are ductless climate systems. They are
designed with a matching indoor unit for optimum performance and efficiency. These climate systems are supported with accessories and documents to serve specific functions.
FEATURES
Variable Frequency Rotary Compressor - Twin rotary in ve rte r co mpressor
on all models features high efficiency operation that modulates down to 15
Hz and as high as 120 Hz for red uced vibrat ion and qu iet opera tion. Brus hless DC motor uses powerful Neodymium magnets that are approximately
15-20 times stronger than ferrite magnets used in conventional AC compressors. The DC Inverter Control provides continuous operation, while adjusting
capacity according to room temp eratur e. Th e accur ate s ensing of co oling or
heating loads prevents frequen t changes in capacity and ensur es efficient,
economical operation.
Low Ambient Cooling Operation Down to 5 °F - This feature allows for a
space to be air-conditioned eve n in outdoor temperatures as low as 5 °F.
This cooling ability is important when de aling with server equipment rooms,
surveillance mechanical rooms, restaurant kitchens, fitness centers, and
more.
Load Variat io n Mana ge ment S ys tem - The outdoor coil thermistor continuously monitors the temperature and commun icates wit h the micro process or.
Depending on the temperature measured, the compressor will be allowed to
increase the frequency if nee ded to meet the load or reduce frequen cy as
the load is reduced.
High Pressure Discharge Temperature - The compressor discharge li ne
thermistor continuously monitors the temperature and communicates with
the microprocessor. Depending on the temperatur e me as u red, the compressor will be allowed to in crea se t he f r equen cy t o me et th e lo ad o r is fo rc ed to
run at the current or reduced f requency. If the temperature gets excessi vely
high, the compressor will be de-e nergized.
Defrost Control (Heat Pump Models) - Defrost cycle is automatically
enabled if there is a build-up of frost on the outdoor coil. Outdoor fan and
indoor blower operation is terminated during the defrost cycle. H1 is displayed on the indoor unit panel on the front cover during a defrost cycle.
Reversing Valve (Heat Pump Models) - 4-way inter change reversing valve
effects a rapid change in direction of refrigerant flow resulting in quick
changeover from cooling to h eating and vice vers a. Valve operates on system pressure differential betw e en outdoor unit and indoor unit.
R-410A Refrigerant - Unit is pre- charged with R410A refrigerant that uses
PVE refrigerant oil. Polyvinyl ether (PVE) is an innovative refrigerant oil specially formulated for hydrofluorocarbon (HFC) refrigeration systems. In addition to providing lubricati ng propert ies, it al so has a nu mber of othe r applied
advantages that help to increase the reliability of the refrigeration systems
where it is applied.
Refrigerant Line Connections, Service Valve - Outdoor units are designed
with easy service and mai nten an ce in mi n d. Ma in te nanc e p oi nts are loc at ed
behind easy-access panels, to m ake installation and s ervice a breeze for a
trained technician. Flare connection lines are located on side of unit cabinet.
Fully serviceable brass service valve prevents corrosion an d provide access
to refrigerant system. Shut -off valve that can be fully shut off while 2-way
suction/vapor valve (with service port) may be front seated to manage refrigerant charge while servicing system.
Air Deflection Louvers - Horizontal louvers default to the cooling or heating
position when the unit i s operating. Horizontal louvers can be set to a preset
oscillating range or fixed position from the wireless remote control. Full oscillating is the default settin g when button is pushed. Vertical louvers can be
manually adjusted to direct th e airflow for optimal comfort.
Indoor Coil Freeze Protectio n - The indoor coil thermistor monitors the coil
temperature continuously. Any time the coil tempera ture drops below 30°F,
the compressor and the outdoor fan (30 secon ds later) will be switched off
until the coil temperature r ises above 43°F and the compressor has been off
for a minimum of 3 minutes.
I FEEL Function - When I FEEL is activated, the system will sat isfy the coo ling or heating temperature setpoint where the remote control is located.
When I FEEL is deactivated, th e system will satisfy the cooling or heating
temperature setpoint where the indoor u nit is lo cated. This feature pr ovides
homeowners with optimum comfort whether the y are near or far from the
indoor unit.
Hot Heat Pump (cold air prevention) - In heating mode, the indoor fan wil l
be delayed from 1 to 3 minutes to allow refrigerant to warm up and avoid
cold blow. This may occur during:
• Initial start-up of a heating cycle
• Immediately after completion of an Auto mode operation
• Heating under extremely low indoor temperatures
Page 2
923178-UTG-B-0114
2Johnson Controls Unitary Products
Page 3
923178-UTG-B-0114
SPECIFICATIONS
AIR CONDITIONERS
Model (Indoor/Outdoor)
Function CoolingCoolingCoolingCooling
Rated Voltage 208/230208/230208/230208/230
Frequency (Hz)60Hz60Hz60Hz60Hz
Total Capacity (BTUH) (High/Standard/Low)11500/9000/380012500/12000/330021000/18000/450024000/22000/6400
Total Capacity (W) (High/Standard/Low)3370/2637/11143663/3516/9676155/5276/13197032/6446/1875
Rated Power Input (W) 882122416212200
Nominal Input Current (A)4.01 5.56 7.37 10.00
SEER16.0016.0016.0016.00
Air Flow Volume (CFM) (H/M/L)330/300/260/210340/300/260/210470/400/330/270590/440/300/200
Air Flow Volume (m3/h) (H/M/L)560/510/440/370580/520/440/370800/680/560/4601000/750/520/350
Dehumidifying Volume (cu.ft./h)0.0280.0490.0640.075
Dehumidifying Volume (l/h)0.801.401.802.13
EER10.29.811.110
Model of Indoor UnitDCMF09NWM42Q1DCMF12NWM42Q1DCMF18NWM42Q1DCMF24NWM42Q1
Fan Motor Speed (r/min) (SH/H/M/L)1300/1100/900/7001350/1150/950/7501400/1150/1000/8501450/1180/1000/850
Output of Fan Motor (w)15152036
Fan Motor Capacitor (uF)1.21.21.52.5
Fan Motor RLA (A)0.190.190.320.45
Fan Type-PieceCross-flow - 1Cross-flow - 1Cross-flow - 1Cross-flow - 1
Diameter-Length (inch)3.6 × 23.43.6 × 23.43.9 × 25.63.9 × 30.1
Diameter-Length (mm)92 × 59492 × 59598 × 65098 × 765
EvaporatorAluminum Fin-copper Tube Aluminum Fin-copper Tube Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Pipe Diameter (inch)Φ 0.276Φ 0.276Φ 0.276Φ 0.276
Pipe Diameter (mm)φ7φ7φ7φ7
Row-Fin Gap (inch) 2 - 0.0552 - 0.0552 - 0.0552 - 0.059
Row-Fin Gap (mm) 2-1.42-1.42-1.42-1.5
Coil length (L) x height (H) x coil width (W) (inch)24.0 × 11.6 × 0.924.0 x 11.6 × 0.925.9 × 12.0 × 1.030.1 × 13.5 × 1.0
Max Height Distance (ft)32.832.832.832.8
Max Height Distance (m)9.99.99.99.9
Max Length Distance (ft)49.2 49.2 82 82
Max Length Distance (m)14.914.924.924.9
624624624624
4.34.34.34.3
363363363363
2.52.52.52.5
4Johnson Controls Unitary Products
Page 5
923178-UTG-B-0114
HEAT PUMPS
Model (Indoor/Outdoor)
Function CoolingHeatingCoolingHeatingCoolingHeatingCoolingHeating
Rated Voltage 208/230208/230208/230208/230
Frequency (Hz)60Hz60Hz60Hz6 0Hz
Total Capacity (Btu/h) (High/Standard/Low)
Total Capacity (W) (High/Standard/Low)
Rated Power Input (W) 882799122410651621212322003118
Model of Outdoor UnitDHMF09CSM42Q1DHMF12CSM42Q1DHMF18CSM42Q1DHMF24CSM42Q1
Compressor Manufacturer/trademark GREEGREE MITSUBISHI SANYO
Compressor TypeInverter RotaryInverter RotaryInverter RotaryInverter Rotary
L.R.A. (A)16.5016.502741
Compressor RLA(A)6.226.2210.8611.38
Compressor Power Input (W)95095012451630
Throttling MethodCapillaryCapillaryCapillaryEXV
Working Temp Range (
Working Temp Range (°C)-15 ~ 46-10 ~ 24-15 ~ 46-10 ~ 24-15 ~ 46-10 ~ 24-15 ~ 46-10 ~ 24
Condenser Aluminum Fin-copper TubeAluminum Fin-copper TubeAluminum Fin-copper Tube Aluminum Fin-copper Tube
Pipe Diameter (inch)Φ 0.276Φ 0.276Φ 0.276Φ 0.276
Pipe Diameter (mm)φ7φ7φ7φ7
Rows-Fin Gap (inch)1 - 0.0552 - 0.0552 - 0.0552 - 0.055
Rows-Fin Gap (mm)1-1.42-1.42-1.42-1.4
Coil length (l) x height (H) x
coil width (L) (inch)
Coil length (l) x height (H) x
coil width (L) (mm)
Fan Motor Speed (rpm) 880±20880±20690690
Output of Fan Motor (W)21216060
Fan Motor RLA(A)0.250.250.620.62
Fan Motor Capacito r ( uF)2233.5
Fuse (A)15A15A25A25A
Air Flow Volume of Outdoor Unit (CFM)94494418871887
Air Flow Volume of Outdoor Unit (m
Fan Type-PieceAxial-flow-1Axial-flow-1Axial-flow-1Axial-flow-1
Fan Diameter (inch)14.614.620.520.5
Max Height Distance (ft)32.832.832.832.8
Max Height Distance (m)9.99.99.99.9
Max Length Distance (ft)49.2 49.2 82 82
Max Length Distance (m)14.914.924.924.9
Condition
Indoor:DB 68°F
Indoor air flow: Super High
Pipe length:24.6ft
Current(A)
Current(A)
09K 12K
Compressor Frequency(Hz)
Compressor Frequency(Hz)
18K
Cooling
Heating
0
1
2
3
4
5
6
7
8
9
10
020406080
100120
Condition
F°6.08 BD:roodnI
WB66.2
°F
Indoor air flow: Super High
Pipe length:24.6ft
Compressor Frequency(Hz)
0
2
4
6
8
10
12
020406080100 120
Condition
Indoor:DB 68°F
Indoor air flow: Super High
Pipe length:24.6ft
Compressor Frequency(Hz)
Current(A)
Current(A)
923178-UTG-B-0114
Johnson Controls Unitary Products7
Page 8
923178-UTG-B-0114
Cooling
Heating
24K
0
2
4
6
8
10
12
14
0204060
0
2
4
6
8
10
12
14
020406080100120
Conditio
n
F°6.08 BD:roodnI
WB66.2
°F
Indoor air flow: Super High
Pipe length:24.6ft
Condition
Indoor:DB 68°F
Indoor air flow: Super High
Pipe length:24.6ft
Compressor Frequency(Hz)
Compressor Frequency(Hz)
09K 12K
Heating
Cooling
50
60
70
80
90
100
110
Capacity ratio(%)
Condition
Indoor air flow: Super High
Pipe length:
24.6ft
Outdoor temp. (°F)
0
20
40
60
80
100
120
510152025 3035404550
Capacity ratio(%)
Condition
Indoor air flow: Super High
Pipe length:
24.6ft
Outdoor temp. (°F)
Indoor:DB 68°F
Indoor:DB 80.6°F
WB66.2
°F
9095100105110115
18K 24K
<Cooling><Heating>
95100105110
5101520253035404550
100
105
95
90
85
80
75
70
65
60
55
50
Outdoor temp. (˚F)
110
100
90
80
70
60
50
40
Outdoor temp. (˚F)
Capacity ratio (%)
Conditions
Indoor: Indoor air flow: High Pipe length:
24.6ft
90
Capacity ratio (%)
DB 80.6°F
WB66.2
°F
Condition
Indoor:DB 68°F
Indoor air flow: Super High
Pipe length:24.6ft
PRODUCT CAPACITY VARIATION RATIO
8Johnson Controls Unitary Products
Page 9
OPERATION DATA
Indoor side noise when blowing
Outdoor side noise
60
60
6080100
50
50
40
40
40
30
30
20
20
20
10
0
0
Indoor Fan Motor Rotating Speed
Noice/dB(A)
Noice/dB(A)
low
Middle
HighSuper High
Compressor frequency/Hz
09K12K09K12K
09K 12K
Indoor side noise when blowing
Outdoor side noise
18K
24K
60
60
6080100
50
50
40
40
40
30
30
20
20
20
10
0
0
Indoor Fan Motor Rotating Speed
Noice/dB(A)
low
Middle
HighSuper High
Compressor frequency/Hz
18 24K
18K 24K
Noice/dB(A)
Temperature Condition (°F)
Indoor OutdoorP (MPa)T1 (°F) T2 (°F)
80/66.995/7509K0.9 to 1.153.6 to 57.2158 to 104Super HighHigh73
80/66.995/7512K0.9 to 1.153.6 to 57.2158 to 104Super HighHigh71
80/66.995/7518K0.9 to 1.153.6 to 57.2176 to 104Super HighHigh75
80/66.995/7524K0.9 to 1.153.6 to 57.2176 to 104Super HighHigh89
70/6046.9/4309K2.5 to 2.7158 to 9535.6 to 39.2Super HighHigh76
70/6046.9/4312K2.5 to 2.7158 to 9535.6 to 39.2Super HighHigh76
70/6046.9/4318K2.2 to 2.4 158 to 10433.8 to 41.0 Super HighHigh90
70/6046.9/4324K2.2 to 2.4 158 to 10433.8 to 41.0 Super HighHigh87
Notes:
Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent. (Thermistor thermometer).
Connecting piping condition: 24.6 ft.
P: pressure of air pipe connected to the indoor and outdoor units (g as valve side),
T1: Inlet and outlet temperature for evaporator,
T2: Inlet and outlet temperature for condenser.
Model name
Standard
Pressure
Heat Exchanger
Pipe Temperature
COOLING
HEATING
Indoor Fan
Mode
Outdoor Fan
Mode
SOUND DATA
923178-UTG-B-0114
Compressor
Frequency (Hz)
Johnson Controls Unitary Products9
Page 10
923178-UTG-B-0114
5.021.6
3.7
09K 12K
7.221.3
5.5
18K
7.6
27.05.1
24K
A
C
B
B
A
C
G
D
E
F
PRODUCT CONSTUCTION VIEW & DIMENSIONS
Indoor Unit Dimensions
Model SizeABC
09K
12K27 lbs (12 kg)27 lbs (12 kg)
18K34.1 (866)8.5 (216)12.0 (305)35 lbs (16 kg)35 lbs (16 kg)
24K39.7 (1008)8.7 (221)12.4 (315)44 lbs (20 kg)44 lbs (20 kg)
30.3 (770)7.9 (201)11.1 (282)
Unit Gross Weight
Air ConditionerHeat Pump
25 lbs (11.5 kg)25 lbs (11.5 kg)
Outdoor Unit Dimensions
Model SizeABCDEFG
09K
12K77 lbs (35 kg)77 lbs (35 kg)
18K
24K123 lbs (56 kg)126 lbs (57 kg)
SymbolPart NameSymbolColor SymbolSymbolColor Symbol
C1CBB61BNBROWNWHWHITE
C2CBB65BUBLUEYEYELLOW
SATOVERLOADBKBLACKRDRED
COMPCOMPRESSOROGORANGEYEGNYELLOW GREEN
PROTECTIVE EARTHWHWHITE//
Electrical Wiring
09K & 12K Outdoor Air Conditioners
Johnson Controls Unitary Products13
Page 14
923178-UTG-B-0114
09K & 12K Indoor Air Conditioners
18K & 24K Outdoor Air Conditioners
14Johnson Controls Unitary Products
Page 15
923178-UTG-B-0114
18K & 24K Indoor Air Conditioners
09K & 12K Outdoor Heat Pumps
Johnson Controls Unitary Products15
Page 16
923178-UTG-B-0114
09K & 12K Indoor Heat Pumps
18K & 24K Outdoor Heat Pumps
16Johnson Controls Unitary Products
Page 17
18K
24K
Start cooling
Stop cooling
sorserpmoC
Original working state
Run
Stop
Outdoor fan
Indoor fan
T
preset
T
preset
+3.6
T
amb.
Preset fan speed
6 minutes
6 minutes
3 minutes
ºF
923178-UTG-B-0114
18K & 24K Indoor Heat Pumps
DESCRIPTION OF EACH CONTROL
OPERATION
Temperature & Current Parameters
• Indoor preset temperature (T
• Indoor ambient temperature (T
• Evaporator coil temperature (T
• Condenser coil temperature (T
• Defrost compensation temperature (T
• Outdoor ambient temperature (T
• Measured temperature of outdoor condensing coil under
cooling mode and measured temperature of indoor evaporator coil under heating mode (T
• Indoor ambient temperature (T
Basic Functions
Once energized, the compressor should never be restarted
within less than 3 minutes. In a situation where memory function is available when energized for the first time, if the compressor is at stop before de-energized, it will re-start without a
3-minute lag. If it has been in operation before de- energized,
the compressor will start with a 3-minute lag. Once started, the
compressor will not be stopped within 6 minutes regardless of
changes in room temperature.
Cooling Mode
1. Cooling Mode Operation
• When T
amb
T
fan, outdoor fan and the compressor will operate simultaneously. The indoor fan will run at preset speed.
• When T
amb
T
outdoor fan will stop with a time lag of 60 seconds, and the
indoor fan will run at preset speed.
• When T
preset
remain at its previous state.
In cooling mode, the four-way valve will be de-energized and
temperature can be set within a range from 61 to 86°F. If the
compressor stops running, the indoor fan and the swing device
will operate at original state.
Johnson Controls Unitary Products17
, cooling mode is activated. The indoor
preset
- 3.6,°F the compressor will stop, the
preset
- 3.6°F < T
amb
)
preset
.)
amb
)
evap
outdoor pipe
outdoor amb
tube
indoor amb)
)
compensation
).
. < T
+ 1.8°F, the unit will
preset
)
)
2. Protection – Cooling Mode
• Antifreeze protection - In cooling and dehumidification
mode, antifreeze protection is activated 6 minutes after the
compressor has started if one of followings occur:
T
35.6 °F, the compressor will operate at reduced
evap
frequency.
T
30.2 °F is detected for a duration of 3 minutes,
evap
the compressor will stop and after 60 seconds, the outdoor fan will stop. In cooling mode, the indoor fan and the
swing motor will remain at the original state.
T
42.8 °F and the compressor has remained in
evap.
OFF mode for at least 3 minutes, the compressor will
resume its original operation state.
• Total current up and freq uency down protection if the followings occur:
I
16A, the compressor frequency will start to
total
increase
I
17A, the compressor frequency will not increase
total
18A, the compressor will run at reduced frequency
I
total
20A, the compressor will immediately stop and the
I
total
outdoor fan will stop after 60 seconds
Page 18
923178-UTG-B-0114
Dehumidification Mode
1. Dehumidification Mode Operation
• When T
amb
> T
+ 1.8 °F, cooling and dehumidification
preset
mode will be activated. The compressor and th e outdoor
fan will operate while the indoor fan runs at low speed.
• When T
preset
- 3.6 °F T
amb
T
+ 1.8°F, the compres-
preset
sor remains at its original operation state.
• When T
amb
. < T
- 3.6°F, the compressor will stop, the
preset
outdoor fan will stop after 60 seconds and the indoor fan
will operate at low speed.
2. Protection – Dehumidification Mode
Protection is the same as that under cooling mode section.
Heating Mode
1. Heating Mode Operation
• When T
amb
. T
+ 3.6°F, heating mode is activated.
preset
The four-way valve, the compressor and the outdoor fan
will operate simultaneously. The indoor fan will run at preset speed defined under “cold air prevention”.
• When T
amb
. T
+ 9°F, the compressor will stop, the
preset
outdoor fan will stop after 60 seconds, and the indoor fan
will continue to run at low speed for 60 seconds more.
• When T
preset
+ 3.6°F<T
amb
.<T
+ 9°F, the unit will
preset
maintain its original operating status.
In heating mode, the four-way valve is energized an d temperature can be set within a range of 61 - 86°F. The heating symbol
and preset temperature are displayed on the indoor unit display.
2. Defrost Mode Operation
When the system has been running continuously in heating
mode for more than 45 minutes, or an accumulated heating
time of more than 90 minutes, and one of the following conditions are present, the unit will enter defrost mode after 3 minutes.
•T
outdoor amb.
• 28.4°F≤T
• 23°F≤T
• 14°F≤T
•T
outdoor amb.
outdoor amb.
door amb
outdoor amb.
≥ 41°F, T
outdoor amb.
-5.4°F);
<14°F, T
outdoor pipe
<28.4°F, T
<23°F, T
outdoor pipe-Tcompensation
≤28.4°F;
outdoor pipe
outdoor pipe
≤17.6°F;
- T
compensation
≤ (T
outdoor amb.
≤ (T
out-
5.4°F)
NOTE:
After defrost mode is energized for the first time, T
0°F. After the first time, T
densing coil temperature T
•T
outdoor pipe
•T
outdoor pipe
>35.6°F, T
≤35.6°F, T
compensation
outdoor pipe
compensation
compensation
is determined by the con of the last defrost cycle.
= 0°F;
= 5.4°F
compensation
When in defrost mode the following will occur in the order
described:
a. The indoor fan and compressor stop running
b. The outdoor fan will stop running after 60 seconds.
c. 30seconds later, the four-way valve will close.
d. After 30 seconds, the compressor’s frequency is
increased to defrost frequency.
e. When the compressor has operated in defrost mode for
10 minutes, or T
outdoor pipe
≥ 50°F, the compressor will
adjust to 46Hz.
f. After 30 seconds, the compressor will stop.
g. After another 30 seconds, the four-way valve will open.
h. After 60 seconds, the compressor and the outdoor unit fan
will start running. The indoor fan will run under preset cold
air prevention conditions. H1 will be displayed on the
indoor unit display. Defrost frequency is 70Hz.
3. Protection – Heating Mode
• Cold air prevention (Hot Heat Pump) - In heating mode,
after the compressor is energized the indoor fan is delayed
under these conditions to prevent discharging cold air:
When T
T
tube
indoor amb.
≤104°F, the indoor fan will not run. The indoor fan
<75°F if:
will start running at low speed after 2 minutes.
Within 2 minutes, if T
>104°F, the indoor fan will start
tube
running at low speed.
After 1minute of operation at low speed, the indoor fan
will run at preset speed.
Within 1-minute of low speed operation or 2-minute
non-operation, if T
>108°F, the fan will run at present
tube
speed.
When T
T
tube
indoor amb.
≤108°F, the indoor fan will run at low speed. After
≥75°F if:
one minute of operation, the indoor fan wil l run at preset speed.
Within one-minute of low speed operation, if
T
>104°F, the indoor fan will run at preset speed.
tube
Total current up and frequency down protection occurs:
When I
When I
≤16A, compressor frequency can increase
total
≥17A, compressor frequency is not allowed
total
to increase
When I
≥18A, the compressor runs at reduced fre-
total
quency
When I
≥20A, the compressor stops running and the
total
outdoor fan stops running after 60 seconds.
Fan Mode
In this mode, the indoor fan will run at preset speed. The compressor, the outdoor fan and the four-way valve will not be running.
1. In fan mode, temperature can be set within a range of 61 -
-
86°F.
AUTO Mode
1. AUTO Mode Operation
=
In AUTO mode, the default cooling setpoint temperature T
is 77°F and the default heating setpoint temperature T
68°F. Once activated, the following will occur under these con-
ditions:
• When T
• When 71.6°F< T
fan icon is displayed on the indoor unit display.
• When T
• When T
mode. The preset temperature is 77°F;
• When T
the outdoor fan stops running after 1 minute, and the indoor
fan continues to run at a preset speed.
• When T
tinues to run normally.
• When T
•T
amb.≥Tpreset
door fan stops running after 1 minute, and the indoor fan
continues to run for about 30 seconds before it stops.
≤71.6°F, heating mode is activated.
amb.
<78.8°F, fan mode is activated and the
amb.
≥78.8°F, cooling mode is activated.
amb.
amb.≥Tpreset
amb. ≤Tpreset
preset
amb.≤Tpreset
+1.8°F, the system runs in cooling
-1.8°F, the compressor stops running,
-1.8°F< T
amb.
< T
+1.8°F, the system con-
preset
+3.6°F, heating mode is activated.
+9°F, the compressor stops running, the out-
preset
preset
is
18Johnson Controls Unitary Products
Page 19
923178-UTG-B-0114
• When T
preset
+3.6°F< T
amb.
< T
+41°F, the system con-
preset
tinues to run normally
• When 71.6°F<T
<78.8°F, the system continues to run
amb.
normally.
2. Protection – Auto Mode
• When the system is running in cooling mode, the protections described in “Protection - Cooling Mode” apply.
• When the system is running in heating mode, the protections described in “Protection – Heating Mode” apply.
• When the ambient temperature changes, operation mode
will switch back and forth. Once the compressor is ene rgized, it will keep running for a minimum of 6 minutes.
COMMON PROTECTION FUNCTIONS AND
FAULT DISPLAY UNDER COOL, HEAT, DRY
AND AUTO MODES
1. Overload Protection
• Cooling Overload
When T
When T
allowed to increase.
When T
quency.
When T
the indoor fan will continue to run at preset speed.
Heating Overload
When T
When T
allowed to increase.
When T
quency.
≤ 126⁰F, the system operates normally.
tube
≥ 131⁰F, compressor frequency is not
tube
≥ 136⁰F, compressor will run at reduced fre-
tube
≥ 144⁰F, compressor is de-energized and
tube
≤ 126⁰F, the system operates normally.
tube
≥ 131⁰F, compressor frequency is not
tube
≥ 136⁰F, compressor will run at reduced fre-
tube
When T
≥ 144⁰F, compressor is de-energized and
tube
the indoor fan will continue to run for about 30 seconds
and stops.
2. High Discharge Temperature Compressor Protection
• When compressor discharge temperature is ≥ 208 ⁰F, compressor frequency is not allowed to increase.
• When compressor discharge temperature is ≥ 217 ⁰F, compressor will run at reduced frequency.
• When compressor discharge temperature is ≥ 230 ⁰F, t he
compressor will stop.
• When compressor discharge temperature is ≤ 194 ⁰F and
the compressor has been idle for at least 3 minutes, it will
resume its operation.
3. Communication Fault
If the system fails to receive communication signals for more
than 3 minutes, its operation will stop.
4. Module Protection
• Under module protection mode, the compressor will stop.
• If the compressor remains idle for at least 3 minutes, it will
resume its operation.
• If module protection occurs six consecutive times, the compressor will not be allowed to start again.
5. Overload Protection
• If the overload temperature is over 239 ⁰F, the compressor
will stop and the outdoor fan will stop after 30 seconds.
• If the overload temperature drops below 203 ⁰F, t h e c om pressor overload protection is reset.
• If voltage on the DC bus is below 150V or over 420V, the
compressor will stop and the outdoor fan will stop after 30
seconds.
• When voltage on the DC bus returns to its normal value
and the compressor has been idle for at least 3 minutes,
the compressor will resume its operation.
6. Temperature Sensors Faults.
Designation of SensorsFaults
Indoor ambient temperatureThe sensor is detected to be open-circuited or short-circuited for a continuous 30 seconds.
Indoor tube temperatureThe sensor is detected to be open-circuited or short-circuited for a continuous 30 seconds.
Outdoor ambient temperature The sensor is detected to be open-circuited or short-circuited for a continuous 30 seconds.
Outdoor tube temperature
Exhaust
Overload
The sensor is detected to be open-circuited or short-circuited for a continuous 30 seconds and no detection is
performed within 10 minutes after defrost begins.
After the compressor has operated for 3minutes, the sensor is detected to be open-circuited or short-circuited for a
continuous 30 seconds.
After the compressor has operated for 3minutes, the sensor is detected to be open-circuited or short-circuited for a
continuous 30 seconds.
Johnson Controls Unitary Products19
Page 20
923178-UTG-B-0114
RESISTANCE TABLES
Resistance Table of Ambient Temperature Sensor for Indoor and Outdoor Units (15K)
Remove 2 screws fixing display,
and then remove the filter.
Removal Procedure of Indoor Unit
Be sure to wait for a minimum of 10 minutes after turning off all power supplies before disassembly.
STEPSPROCEDURES
1. Before disassembly of the unit
923178-UTG-B-0114
2. Remove filter
3. Remove display
Johnson Controls Unitary Products23
Page 24
923178-UTG-B-0114
horizontal louver
Remove the axial bush on the
horizontal louver, and then
remove the horizontal louver.
Screw
Top cover of electric box
a. Remove screws fixing the
top cover of electric box.
b. Remove the top cover of
electric box.
STEPSPROCEDURES
Pull the clasps at both sides slightly,
4. Remove panel
5. Remove horizontal louver
and then remove the panel.
Panel
Clasp
6. Remove top cover of electric box
24Johnson Controls Unitary Products
Page 25
STEPSPROCEDURES
Screw Cap
Screw
Front Case
a. Remove the screw caps on front case.
b. Remove screws connecting
the front case.
c. Remove the front case.
screw
Remove earthing screws, and
then remove the earthing wire.
Clasp
Clasp
electric box cover
a. Loosen clasps at the left side of
electric box.
b. Loosen clasps on the right side of
electric box.
c. Remove electric box cover.
7. Remove front case
923178-UTG-B-0114
8. Remove earthing wire
9. Remove electric box cover
Johnson Controls Unitary Products25
Page 26
923178-UTG-B-0114
STEPSPROCEDURES
10. Remove temperature sensor
11. Remove electric box
Pull out the indoor temperature sensor.
a. Pull out 6 sockets on PCB board.
b. Pull out two screws on electric box.
temperature sensor
Screw
Electric
Box
c. Remove the electric box.
Water Tray
12. Remove water tray
13. Remove connection pipe between
indoor and outdoor units
Pull the water tray upwards,
and then remove the water tray.
Separate the connection pipe
between indoor and outdoor units.
Connection position for indoor and
outdoor units' connection pipe
26Johnson Controls Unitary Products
Page 27
STEPSPROCEDURES
Pipe-Stopping Plate
Screw
Remove two screws on pipe-stopping
plate for indoor unit, and then remove
the pipe-stopping
Screw
Damping
Board
Remove 2 screws on
damping board, and then
remove the damping board.
Screw
Evaporator
a. Remove screws between
evaporator and bottom case.
b. Turn over the indoor unit
and adjust the pipe line to
the position as shown by
the broken line.
c. Lift up the evaporator, and
then remove the evaporator.
Screw
Remove 2 screws on fixing
plate of motor, and then
remove the fixing pate of
motor.
14. Remove pipe-stopping plate
15. Remove damping board
923178-UTG-B-0114
16. Remove evaporator
17. Remove the fixing plate of motor
Johnson Controls Unitary Products27
Page 28
923178-UTG-B-0114
STEPSPROCEDURES
a. Remove screws fixing cross
flow blade and motor.
18. Remove cross flow blade and motor
Blade
Motor
19. Remove cushion rubber
b. Remove the motor sub-assy.
c. Separate two cross flow blade.
a. Remove the cushion rubber
on cross flow blade.
Cushion Rubber
b. Remove the cushion rubber
from the base.
28Johnson Controls Unitary Products
Page 29
Removal Procedure of Outdoor Unit
a. Use the screwdriver to remove
the screws connecting the top
panel and panel and side panels.
Remove the top panel. Loosen the
screws fixing the valve cover and
then remove the valve cover.
Top Panel
Valve Cover
b. Loosen the screws connecting the front
side panel and mask and chassis.
Remove the front side panel.
Front Side Plate
Twist off the screws connecting the grille
and panel, and then remove the grille.
Grille
Twist off the screws connecting the panel,
chassis and motor support with screwd-river,
and then remove the panel.
Panel
Be sure to wait for a minimum of 10 minutes after turning off all power supplies before disassembly.
STEPSPROCEDURES
1. Remove top cover and front side plate
923178-UTG-B-0114
2. Remove grille
3. Remove panel
Johnson Controls Unitary Products29
Page 30
923178-UTG-B-0114
STEPSPROCEDURES
Twist off the screws fixing the guard grille
4. Remove guard grille
and then remove the guard grille.
Twist off the screws fixing the handle
5. Remove handle
and then remove the handle.
Guard Grille
Handle
6. Remove right side plate
7. Remove electric box
Right
Side Plate
Twist off the screws connecting the right
side plate and chassis, valve support and
condenser, and then remove the right
side plate.
Electric Box
Cover
a. Twist off the screws on electric box
cover with screwdriver, and then
remove the electric box cover.
30Johnson Controls Unitary Products
Page 31
STEPSPROCEDURES
b. Twist off the screws on electric box,
cut off the tieline with scissors or pliers,
pull out the wiring terminal, pull it upwards
to remove the electric box.
Electric Box
Electric Box 1
c. Twist off the screws between electric box 1
and left side plate with screwdriver,
pull it upwards to remove the electric box 1.
Left Side Plate
Twist off the screws connecting the
left side plate and chassis with
screwdriver, and then remove the
left side plate.
Axial Flow Blade
Twist off the nuts on blade
with wrench and then remove
the axial flow blade.
7. Remove electric box (Continued)
923178-UTG-B-0114
8. Remove left side plate
9. Remove axial flow blade
Johnson Controls Unitary Products31
Page 32
923178-UTG-B-0114
STEPSPROCEDURES
a. Twist off the tapping screws fixing the
motor, pull out the pin of leading wire
for motor and then remove the motor.
Motor
10. Remove motor and motor support
11. Remove 4-way valve
Motor
Support
b. Twist off the tapping screws fixing the
motor support, pull it upwards and
then remove the motor support.
4-Way Valve
Unsolder the pipeline between
compressor, condenser, gas and
liquid valve, and then remove the
4-way valve. (note: release all
refrigerant before unsoldering).
Twist off the 2 bolts fixing the
valve sub-assy. Unsolder the
soldering joint between gas valve
and air-return pipe and then
remove the gas valve.
(note: when unsoldering
12. Remove gas valve and liquid valve
the soldering joint, wrap the
gas valve with wet cloth
completely to avoid the damage
to valve, and release all
Gas
Valve
refrigerant completely at first).
Unsolder the soldering joint
between liquid valve and connection
pipe of liquid valve, and then remove the liquid valve.
Liquid Valve
32Johnson Controls Unitary Products
Page 33
STEPSPROCEDURES
Compressor
Twist off the 3 foot nuts on
compressor and then remove
the compressor.
Isolation
Sheet
Twist off the screws connecting
isolation sheet and end plate of
condenser and chassis, and then
remove the isolation sheet.
Support Plate
of Condenser
Twist off the screws connecting
the support plate of condenser
and condenser with screwdriver,
and then remove the support
plate of condenser.
Condenser
Chassis
Pull it upwards to separate
the chassis and condenser.
13. Remove compressor
14. Remove isolation sheet
923178-UTG-B-0114
15. Remove support plate of condenser
16. Remove chassis and condenser
Johnson Controls Unitary Products33
Page 34
ACCESSORIES
PART NUMBERDESCRIPTION
OTHER ACCESSORIES
S1-DL30510050Remote Control
S1-DL26150003Remote Control Holder
S1-230-MB14WBLOCK,MOUNTING,MINISPLIT,14",PK OF 2(M6)
S1-230-MB17WBLOCK,MOUNTING,MINISPLIT,17",PK OF 2(M6)
S1-230-MB36WBLOCK,MOUNTING,MINISPLIT,36",PK OF 2(M6)