These compact units (31-1/2" high) employ induced combustion, reliable electronic ignition and high heat transfer heat
exchangers. The units may be factory shipped for upflow/horizontal application and converted for downflow application.
These units may also be factory shipped for downflow application and converted for upflow/horizontal applications
Note: The 150 MBH input model is upflow/horizontal only and
may not be converted to the downflow position.
These furnaces are designed for residential installation in a
basement, closet, alcove, attic, or garage. All units are factory
assembled, wired and tested to assure safe dependable and
economical installation and operation.
These units are Category I listed and may be common vented
with another gas appliance as allowed by the National Fuel
Gas Code.
1. 4-position models may be factory configured as upflow (MU) or downflow (MD).
2. 3-position 150 MBH model available only in upflow/horizontal (UH) configuration.
4. Dimensions “B”, “C”, “D”, and “E” are with duct flanges turned up. “F”, “G”, “H”, & “J” are with flanges flat.
3. All models are supplied with 3” (7.62 cm) vent connections. An installer supplied transition to 4” (10.16 cm) or 5” (12.7 cm) must be used where necessary.
G8C05012(MU,MD)B12501601/27.010 x 81514112
G8C07512(MU,MD)B12751651/27.010 x 81514118
G8C07516(MU,MD)C12751601/210.410 x 101514129
G8C10016(MU,MD)C121001701/210.410 x 101514135
G8C10020(MU,MD)D11100165110.3(2)10 x 61514149
G8C12520(MU,MD)D11125170110.3(2)10 x 61514155
G8C15020UHD11150170110.3(2)10 x 61514165
Nominal external static pressure is 0.50” w.c. at furnace outlet ahead of cooling coils.
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
/min) require either return from two sides or one side plus bottom
0.10.20.30.40.50.60.70.8
BOTTOM/END RETURN
External Static Pressure, Inches WC - CFM
3
/min).
RETURN AIR AND FILTERS
The return air ducts to the furnace must have a total cross
sectional area of not less than two square inches per 1000
BTUH of furnace input rating for heating operation. If air con-
ditioning is to be inst alled with th e furnace, or if it may be
added at a later time, larger return air ducts may be
required, depending on the capacity of the air conditioner and the airflow required.
For applications requiring more than 1800 CFM, it
is required to use the bottom return, both side
returns or one side plus the bottom return.
• Single side return is not approved on 5 Ton models.
• 18” minimum height for return air box for bottom
return only on Heating only applications with furnace in the upflow configuration.
• 24” minimum height for return air box for bottom
return only on A/C applications with furnace in
the upflow configuration.
FILTER PERFORMANCE
The airflow capacity data published in the “Blower Performance” table listed above represents blower performance
WITHOUT filters. To determine the approximate blower performance of the system, apply the filter drop value for the filter being used or select an appropriate value from the “Filter
Performance” table shown.
The filter pressure drop values in the “Filter Performance”
table shown are typical values for the type of filter listed and
should only be used as a guideline. Actual pressure drop ratings for each filter type vary between filter manufacturers.
Unitary Products Group5
Page 6
270844-YTG-A-0407
RECOMMENDED FILTER SIZE
UPFLOW
Side
Return
Models
InputAir Flow
MBHCFMin.in.
Cabinet
Size
G8C05012(MU,MD)B12501200B25 x 1625 x 16
G8C07512(MU,MD)B12751200B25 x 1625 x 16
G8C07516(MU,MD)C12751600C25 x 1625 x 20
G8C10016(MU,MD)C121001600C25 x 1625 x 20
G8C10020(MU,MD)D111002000D(2) 25 x 1624 x 24
G8C12520(MU,MD)D111252000D(2) 25 x 1624 x 24
G8C15020UHD111502000D(2) 25 x 1624 x 24
DOWNFLOW
Top Return (Downflow)
Cleanable Air Filters
Models
InputAir Flow
MBHCFMin.in.
Cabinet
Size
G8C05012(MU,MD)B12501200B14 x 20(2) 10 x 20
G8C07512(MU,MD)B12751200B14 x 20(2) 14 x 20
G8C07516(MU,MD)C12751600C16 x 20(2) 16 x 20
G8C10016(MU,MD)C121001600C16 x 20(2) 16 x 20
G8C10020(MU,MD)D111002000D20 x 20(2) 20 x 20
G8C12520(MU,MD)D111252000D20 x 20(2) 20 x 20
G8C15020UHD111502000DN/AN/A
NOTES:
1. Air velocity through throwaway type filters may not exceed 300 feet per minute. All velocities over this require the use of high velocity filters.
2. Air flows above 1800 CFM require either return from two sides or one side plus bottom.
Bottom/End
Return
Top Return (Downflow)
Disposable Air Filters
FILTER PERFORMANCE - PRESSURE DROP INCHES W.C. AND (KPA)
APPLYING FILTER PRESSURE DROP T O
DETERMINE SYSTEM AIRFLOW
To determine the approximate airflow of the unit with a filter in
place, follow the steps below:
1.Select the filter type.
2.Select the number of return air openings or calculate the
return opening size in square inches to determine the
proper filter pressure drop.
3.Determine the External System Static Pressure (ESP)
without the filter.
4.Select a filter pressure drop from the table based upon
the number of return air openings or return air opening
size and add to the ESP from Step 3 to determine the
total system static.
5.If total system static matches a ESP value in the airflow
table (i.e. 0.20 w.c., 0.60 w.c., etc.,) the system airflow
corresponds to the intersection of the ESP column and
Model/Blower Speed row.
6.If the total system static falls between ESP values in the
table (i.e. 0.58 w.c., 0.75 w.c., etc.), the static pressure
may be rounded to the nearest value in the table determining the airflow using Step 5 or calculate the airflow by
Example: For a 75,000 BTUH furnace with 2 return openings
and operating on high-speed blower, it is found that total system static is 0.38” w.c. To determine the system airflow, complete the following steps:
Obtain the airflow values at 0.30 w.c. & 0.40 w.c. ESP.
Airflow @ 0.30”: 1408 CFM
Airflow @ 0.40”: 1343 CFM
Subtract the airflow @ 0.30 w.c. from the airflow @ 0.40 w.c.
to obtain airflow difference.
1343 - 1408 = -65 CFM
Subtract the total system static from 0.30 w.c. and divide this
difference by the difference in ESP values in the table, 0.40
w.c. - 0.30 w.c., to obtain a percentage.
(0.38 - 0.30) / (0.40 - 0.30) = 0.8
Multiply percentage by airflow difference to obtain airflow
reduction.
(0.8) X (-65) = -52
Subtract airflow reduction value to airflow @ 0.30 w.c. to
obtain actual airflow @ 0.38 in. w.c. ESP.
1408 - 52 = 1356
1. Special floor base or air conditioning coil required for use on combustible floor.
2. Line contact only permitted between lines formed by the intersection of the rear panel and side panel (top in horizontal position) of
the furnace jacket and building joists, studs or framing.
*
Cabinet clearance is "0", vent clearance is required.
120001CombustibleYesYesYesNo
120011CombustibleNoYesYes
12 0 0 01
Right
Side
Flue
Floor /
Bottom
1" (See Note
1" (See Note
ClosetAlcoveAttic
1
YesYesYesNo
)
)
YesYesYesNo
Line
Contact
Yes(See Note
Yes(See Note
2
)
2
)
ACCESSORIES
Propane Conversion Kit (Standard) – 1NP0366
This accessory conversion kit may be used to convert natural
gas units for propane (LP) operation at altitudes 0-2,000 ft.
Conversion must be made by qualified distributor or dealer
personnel.
Propane Conversion Kit (High Altitude) – 1PS0467
This accessory conversion kit may be used to convert natural
gas units for propane (LP) operation at altitudes from 2,000 to
8,000 ft. Conversion must be made by qualified distributor or
dealer personnel.
Natural Gas Conversion Kit (High Altitude) – 1PS0466
This accessory conversion kit may be used to convert natural
gas units for high altitude operation at altitudes from 2,000 to
8,000 ft. Conversion must be made by qualified distributor or
dealer personnel.
Unitary Products Group7
Combustible Floor Base
This accessory is used for downflow applications on combustible surfaces.