This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury
CAUTION indicated a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to alert
against unsafe practices and hazards involving only property damage.
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual
for assistance or additional information, consult a qualified installer
or service agency.
This product must be installed in strict compliance with the
enclosed installation instructions and any applicable local, state,
and national codes including, but not limited to building, electrical,
and mechanical codes.
The furnace area must not be used as a broom closet or for any
other storage purposes, as a fire hazard may be created. Never
store items such as the following on, near or in contact with the furnace.
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum
cleaners or other cleaning tools.
2. Soap powders, bleaches, waxes or other Cleaning compounds; plastic items or containers; gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids or other volatile fluid.
3. Paint thinners and other painting compounds.
4. Paper bags, boxes or other paper products
Never operate the furnace with the blower door removed. To do so
could result in serious personal injury and/or equipment damage.
841890-UIM-B-0612
Page 2
841890-UIM-B-0612
Coil Access
Panel
Suction Line
Connection
Liquid Line
Connection
Alternate Drain Location
Label
Location
Drain Location
Horizontal Application
(on MC Coils Only)
Primary Drain
Secondary Drain
Bottom Door Panel
Label Location
Coil Access
Panel
Primary Drain
Secondary Drain
Bottom Door Panel
Alternate Drain Locations
Suction Line
Connection
Liquid Line
Connection
20 3/8”
(Opening)
B
C
3/4” Flange
A
21 1/2”
BOTTOM
OPENING
DIMENSIONS
D
20 1/4”
SECTION II: GENERAL INFORMATION
This instruction covers the installation of the following coils with 80+ or
90+ AFUE furnaces or MA/MX/MV air moving systems.
The coils have sweat connect fittings. All coils are shipped with a low
psi nitrogen holding charge.
FIGURE 1: Component Location - Coil MC & FC
INSPECTION
As soon as a coil is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage
should be noted on the carrier’s delivery receipt. A separate request for
inspection by the carrier’s agent should be made in writing. See Local
Distributor for more information. Check drain pan for cracks or breakage.
FIGURE 2: Component Location - Coil PC
CLEARANCES
DURING INSTALLATION
Clearance must be provided for:
1.Refrigerant piping and connections
2.Maintenance and servicing access - including cleaning the coil
3.Condensate drain line
4.Filter removal / change
5.Removal of coil assembly
TABLE 1: Dimensions
- MC Coils
1. All dimensions are in inches.
2. Refrigerant line sizes may require larger lines for extended line lengths. See York bulletin #690.01-AD1V for details.
These coils should be installed in accordance with all national and local
safety codes.
TABLE 4:
60, 62, 64
Coil Air Flow Limits
Coil
Size
181-1/2525675
24
30, 32
35
36, 37
42
43
48
Outdoor Unit
Tons
1-1/2525675
2700900
2700900
2-1/28751125
2-1/28751125
310501200
2-1/28751125
310501350
310501350
3-1/212251575
310501350
3-1/212251575
310501350
3-1/212251575
414001800
416001800
517502250
CFM Limits
MinimumMaximum
FIGURE 3: TXV Bulb Installation
SECTION III: COIL METERING DEVICES
An orifice or a TXV to be installed in the field. Refer to installation manual with TXV kit. It is recommended to install the orifice or TXV kit prior
to installation of coil in cabinet and brazing line sets.
Consult the outdoor installation guide for outdoor units that require an
orifice as a metering device for the indoor coil. The orifice and the
Schraeder core are supplied with the outdoor unit. Install Schraeder
core in the suction line Schraeder body and cap with the supplied plastic cap.
TXV METERING DEVICE
Please refer to Technical Guide to verify which TXV is installed in this
coil and that this is a valid system match for the AC or HP unit installed.
The temperature sensing bulb is attached to the coil suction header
line.
For models that have factory installed TXV’s, take caution not to
apply high temperatures to the TXV assembly or equalizer line
while brazing.
FIGURE 4: Proper Bulb Location
COIL UNDER PRESSURE.
Relieve pressure by depressing schrader stem. Coil may have factory installed TXV or may require orifice or TXV to be added. See
outdoor unit documentation for correct orifice or TXV to be used.
Refer to coil nameplate for orifice or TXV identification for this unit.
The coil should be open to the air for no more than 2 minutes to
keep moisture and contaminates from entering the system. If the
coil cannot be brazed into the refrigeration system in that time, the
ends should be temporarily closed or plugged. For a short term
delay, use masking tape over the ends of the copper tubing to close
the tube to the air. For a longer term delay, use plugs or caps.
There is no need to purge the coil if this procedure is followed.
4
Page 5
SECTION IV: COIL INSTALLATION
UPFLOW
DOWNFLOW
Furnace
Furnace
NOTICE
Alternate
Flange Location
Factory
Flange
Location
FIGURE 5: Vertical Applications
FURNACE ASSEMBLY - MC & FC
These coils are factory shipped for installation in either upflow or downflow applications with a minor conversion.
For Upflow Application:
1.Position the coil casing over or under the furnace opening as
shown in Figure 5 after configuring coil flanges as required see
“Coil Flange” section below and refer to Figure 7.
2.Slide up the sides and back flange and tight the 6 screws that hold
them. Refer to Figure 6.
3.Unscrew the front flange and move it to the top to align it to the
rest of the flanges allowing to screw it back to the brace using the
2 holes in the bottom of the front flange. Refer to Figure 6.
4.Place the ductwork over the coil casing flange and secure.See
sections on "Refrigerant L ine Connections" and "Condensate
Drain Connections". One mounting plate is provided with the coils.
For Downflow Application:
1.Position the coil casing over or under the furnace opening as
shown in Figure 5 after configuring coil flanges as required see
“Coil Flange” section below and refer to Figure 7.
2.Remove all 8 screws from flangs and position them at the bottom
of the casing for the alternate position. Refer to Figure 7.
3.Place the ductwork over the coil casing flange and secure.See
sections on "Refrigerant Line Connections" and "Condensate
Drain Connections". One mounting plate is provided with the coils
841890-UIM-B-0612
FIGURE 6: Coil Flange Placement
When installing this coil with an oil furnace, a minimum of six inches
clearance should be maintained from the top of the heat exchanger.
COIL FLANGE - FOR DOWNFLO W AND HORIZONT AL
LEFT KIT INSTALLATION
The coils include removable flanges to allow proper fit up with furnaces
or two-piece air handlers having various inlet and outlet flange configurations. The two flanges are attached to the top of the coil in the factory
during production. If the installation requires the flanges to be moved to
the bottom of the coil, remove the screws attaching the flanges to the
top of the coil casing. Next, install the flanges to the bottom of the coil
casing using the same screws. Refer to Figure 7.
The additional holes in the upper area of the flanges may be used to
attach the coil to the furnace or two-piece air handler. This is done by
installing field-supplied screws through the flanges into the inside of the
furnace or two-piece air handler casing.
The front flange is also designed so that it can be rotated 180 degrees
and re-installed. In this mounting configuration the front flange will
extend further to the front of the coil casing to accommodate furnaces
or two-piece air handlers that have a greater front-to-back dimension
than the coils.
FIGURE 7: Coil Flange
5
Page 6
841890-UIM-B-0612
Furnace
Furnace
NOTICE
NOTICE
Flexible Duct
Collar
DO NOT Drill or
Screw this Flange
Field
Fabricated
Ductwork
Upflow Coil
Upflow Furnace
Secondary Drain
Primary Drain
D
C
(Min.)
Alternate
Drain Location
FURNACE ASSEMBLY - (MC ONLY)
MC coils are supplied ready to be installed in a horizontal position. A
horizontal pan is factory installed. MC coils should be installed in all horizontal applications with the horizontal drain pan side down.
FIGURE 8: Horizontal Right Application
For horizontal left hand applications no conversion is required to an MC
coil when used with a downflow/horizontal furnace. A mounting plate,
supplied with every coil should always be installed on the side designated as top side. See Figure 8 & 9.
FIGURE 9: Horizontal Left Application
FURNACE ASSEMBLY - PC
These upflow coils are designed for installation on top of upflow furnaces only.
If the coil is used with a furnace of a different size, use a 45° transition
to allow proper air distribution through the coil.
1.Position the coil casing over the furnace opening as shown in Figure 10.
2.Place the ductwork over the coil casing flange and secure.
3.Check for air leakage between the furnace and coil casing and
seal appropriately.
Do not drill any holes or drive any screws into the front duct
flange on the coil in order to prevent damaging coil tubing (see
Figure 12).
FIGURE 10: Upflow Coil Installation
TABLE 5:
Dimension “C” should be at least 2/3 of dimension “D”. See Figure 12.
Coil Projection Dimensions - PC Coils
COIL SIZEDIMENSION “C” INCH
PC183-1/2
PC244-1/2
PC30, PC32, PC354-1/2
PC42, PC43, PC36, PC375-1/2
PC486-1/2
PC609
CRITICAL COIL PROJECTION
The coil assembly must be located in the duct such that a minimum distance is maintained between the top of the coil and the top of the duct.
Refer to Table 6.
SECTION V: DUCT CONNECTIONS
Air supply and return may be handled in one of several ways best
suited to the installation. Upflow, horizontal or downflow applications
may be used.
The vast majority of problems encountered with combination heating
and cooling systems can be linked to improperly designed or installed
duct systems. It is therefore highly important to the success of an installation that the duct system be properly designed and installed.
Use flexible duct collars to minimize the transmission of vibration/noise
into the conditioned space.
When installing this coil with an oil furnace, a minimum of six inches
clearance should be maintained from the top of the heat exchanger.
Refer to the heat pump add-on control instruction before installing
an add-on heat pump coil.
6
Use 1/2" screws to connect ductwork to unit. If pilot holes are
drilled, drill only through field duct and unit flange.
Page 7
841890-UIM-B-0612
NOTICE
NOTICE
Condensate
Deflector
S-Clips (3)
Vertical Drain Pan
NOTICE
S-Clips on Horizontal Pan
Feeder
Tubes
Condensate
Deflector
Condensate
Deflector
S-Clip
Drain Pan
Wall
Where return air duct is short, or where sound may to be a problem,
sound absorbing glass fiber should be used inside the duct. Insulation
of duct work is a must where it runs through an unheated space during
the heating season or through an uncooled space during the cooling
season. The use of a vapor barrier is recommended to prevent absorption of moisture from the surrounding air into the insulation. The supply
air duct should be properly sized by use of a transition to match unit
opening. All ducts should be suspended using flexible hangers and
never fastened directly to the structure. Duct work should be fabricated
and installed in accordance with local and/or national codes. This
includes the standards of the National Fire Protection Association for
Installation of Air-Conditioning and Ventilating Systems, NFPA No. 90B.
Equipment should never be operated without filters.
SECTION VI: CONDENSATE DRAIN
CONNECTIONS
All drain lines should be pitched away from unit drain pan and should be
no smaller than the coil drain connection.
Route the drain line so that it doesn’t interfere with accessibility to the
coil, furnace, air handling system or filter and will not be exposed to
freezing temperatures.
Instruct the owner that the evaporator coil drain pan should be
inspected and cleaned regularly to prevent odors and assure proper
drainage.
SUCTION FEEDER TUBECONDENSATE DEFLECTOR
Upflow or Downflow
No action required. See Figure 11.
FIGURE 11: Condensate Deflector on Vertical Drain Pan
Horizontal Left or Right
Use an appropriate tool to pry out water deflector with two or three sclips from the vertical drain pan. See Figure 11. Relocate the deflector
with s-clips on the Horizontal Drain Pan lined up to the coil support
bracket. See Figure 12. This positions the deflector below the feeder
tubes to channel the condensate to the drain pan.
When the coil is installed in an attic or above a finished ceiling, an
auxiliary drain pan must be provided under the coil as is specified
by most local building codes.
Coils should be installed level or pitched slightly toward the drain end.
Suggested pitch should not exceed 1/4-inch per foot of coil.
If the coil is provided with a secondary drain it should be piped to a location that will give the occupant a visual warning that the primary drain is
clogged. If the secondary drain is not used it must be capped.
Avoid Double Trapping.
Threaded drain connections should be hand tightened, plus
no more than 1 turn.
DO NOT
sealant may cause damage and premature failure of the drain pan.
use T e flonTM tape, “pipe dope”, or other sealants. The use of a
If the coil is installed in a draw-thru application (modular air handler), it is recommended to trap the primary and secondary drain
line. If the secondary drain line is not used, it must be capped.
The condensate deflector should be installed in the s-clip section
which is inside the drain pan edge. See Figure 13.
FIGURE 12: Condensate Deflector on Horizontal Drain Pan Edge
FIGURE 13: S-Clip Installation
7
Page 8
841890-UIM-B-0612
NOTICE
NOTICE
SECTION VII: REFRIGERANT LINE
CONNECTION
Coil is under inert gas pressure. Relieve pressure from coil by
removing rubber plug or by depressing schrader core.
Dry nitrogen should always be supplied through the tubing while it
is being brazed, because the temperature required is high enough
to cause oxidation of the copper unless an inert atmosphere is provided. The flow of dry nitrogen should continue until the joint has
cooled. Always use a pressure regulator and safety valve to insure
that only low pressure dry nitrogen is introduced into the tubing.
Only a small flow is necessary to displace air and prevent oxidation.
Connect lines as follows:
Route the refrigerant lines to the coil in a manner that will not
obstruct service access to the coil, air handling system, furnace flue
or filter.
1.Suction and liquid line connections are made outside the cabinet.
Leave the tubing connection panel attached to the cabinet with the
tubes protruding through it. Coil access panel should be removed
for brazing. The lines are expanded to receive the field line set
tubes.
2.Cut the end of the suction tube using a tube cutter. Place the tube
cutter as close as possible to the end of the tube to allow more
space for the connection and brazing of the suction line.
3.Remove the heat shield from the Customer Packet, soak in water,
and install over coil tubing to prevent overheating of cabinet.
4.Wrap a water soaked rag around the coil connection tubes inside
the cabinet to avoid damaging the TXV bulb.
5.Remove grommets where tubes exit the cabinet to prevent burning
them during brazing.
6.Purge refrigerant lines with dry nitrogen.
7.Braze the suction and liquid lines.
8.Remove the heat shield.
9.Re-attach the grommets to the lines carefully to prevent air leakage.
10. Attach the coil access panel to the cabinet.
Refer to Outdoor unit Installation Manual for evacuation, leak check and
charging instructions.
Lines should be sound isolated by using appropriate hangers or strapping.
All evaporator coil connections are copper-to-copper and should be
brazed with a phosphorous-copper alloy material such as Silfos-5 or
equivalent. DO NOT use soft solder.
SECTION VIII: COIL CLEANING
If the coil needs to be cleaned, it should be washed with Calgon CalClean (mix one part CalClean to seven parts water). Allow solution to
remain on coil for 30 minutes before rinsing with clean water. Solution
should not be permitted to come in contact with painted surfaces.
SECTION IX: AIR SYSTEM ADJUSTMENT
To check the CFM, measure the static pressure drop across the coil
using a portable manometer and static pressure tips. To prepare coil for
static pressure drop measurements - the system should have been
recently operational in cooling mode.
Table 7 below has WET coil data. Run system for approximately 15
minutes in cooling mode prior to taking measurements.
Drill 2 holes, one 3" after the coil (before any elbows in the ductwork)
and one 3” before the coil. Insert the pressure tips and read the pressure drop from the manometer. See Table 5 to determine the air flow,
and make the necessary adjustments to keep the CFM within the air
flow limitations of the coil.