York GM8S Series, LM8S Series, LY8S Series, GY8S*UH Series, GM8S*UH Series User's Information, Maintenance And Service Manual

...
Page 1
USER’S INFORMATION,
EFFICIENCY RATING CERTIFIED
ISO 9001
Certified Quality
Management System
MAINTENANCE AND SERVICE MANUAL
HIGH EFFICIENCY TUBULAR HEAT EXCHANGER SERIES
MODELS:
GY8S*UH/GM8S*UH/GR8S/LY8S*UH/LM8S*UH/LF8*UH
CONTACT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
TABLE OF CONTENTS
USER’S INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTRUCTIONS FOR EXAMINING THE
FURNACE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
HOW YOUR GAS FURNACE WORKS . . . . . . . . . . . . . . . . . . . . . . 3
START-UP AND SHUTDOWN INSTRUCTIONS . . . . . . . . . . . . . . . 3
Read the Instructions Below Before Trying to Start the Furnace . . 3
Operating Instructions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
To Turn Off the Appliance: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
FURNACE USER MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . .4
Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Removing Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Blower Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Motor Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
SERVICE AND MAINTENANCE MANUAL . . . . . . . . . . . . . . . . . . . . 5
CONTACT INFORMATION
• Go to website at www.york.com click on “contact”, then click on “contact form” and follow the instructions.
• Contact us by mail:
York International
Consumer Relations
Norman, OK 73069
SAFETY SECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
FURNACE MAINTENANCE SECTION . . . . . . . . . . . . . . . . . . . . . . .5
FURNACE CLEANING SECTION . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Burner Removal/Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Cleaning the Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Continuous Blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Intermittent Blower - Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Heating Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Hot Surface Ignition System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
FURNACE CONTROL DIAGNOSTICS . . . . . . . . . . . . . . . . . . . . . . .7
DIAGNOSTIC FAULT CODE STORAGE AND RETRIEVAL . . . . . .8
REPLACEMENT PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
REPLACEMENT PART CONTACT INFORMATION . . . . . . . . . . . . .10
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
5005 York Drive
The manufacturer recommends that the user read all sec­tions of this manual and keep the manual for future refer­ence.
FIRE OR EXPLOSION HAZARD - Failure to follow safety
warnings exactly could result in serious injury, death, or prop­erty damage.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone (including cell phone) in your building.
• Leave the building immedia te l y.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire depart­ment.
— Installation and service must be performed by a quali-
fied installer, service agency or the gas supplier.
SECTION I: USER’S INFORMATION
SAFETY
1. The furnace area must be kept clear and free of combustible mate­rials, gasoline and other flammable vapors and liquids.
2. Insulating materials may be combustible. The furnace must be kept free and clear of insulating materials. The furnace area must be examined when installed in an attic or other insulated space or when insulation is added to be sure that the insulation material has been kept away from the furnace.
3. The furnace needs air for combustion in order to operate properly and safely. Do not block or obstruct air openings on the furnace, air openings to the area where the furnace is installed, or spaces around the furnace.
4. Follow the instructions exactly as shown on the OPERATING INSTRUCTION LABEL or the Start-up and Shutdown Instructions on Page 3 of this manual when lighting the furnace or turning the furnace off.
5. Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off the electrical supply.
6. Do not use this furnace if any part has been under water. A flood­damaged furnace is extremely dangerous. Attempts to use the fur­nace can result in fire or explosion. A qualified service agency should be contacted to inspect the furnace and replace all gas controls, control system parts, electrical parts that have been wet or the furnace if deemed necessary.
268893-UUM-A-0407
Page 2
268893-UUM-A-0407
PRESUURE SWITCH
SILICONE TUBE
INDUCER SHIELD
GAS VALVE
FLAME SENSOR
VENT PIPE
FLUE COLLAR
INDUCED DRAFT ASSEMBLY
INDUCED DRAFT
MOTOR ELECTRICAL JUNCTION BOX
LIMIT SWITCH
IGNITOR
MANIFOLD PIPE
SAFETY SHUTOFF SWITCH
CONTROL BOARD
FIGURE 1: Component Locations
7. NEVER . . .Store flammable materials of any kind near your fur­nace. Gasoline, solvents, and other volatile liquids should be stored only in approved containers outside your home. These materials vaporize easily and are extremely dangerous.
8. NEVER . . .Store cleaning materials near your furnace. Materials such as bleaches, detergents, powdered cleansers, etc., can cause corrosion of the heat exchangers.
9. NEVER . . . Use the area around your furnace as a storage area for items which could block the normal flow of air. This flow of air is required for ventilation of the various furnace components.
INSTRUCTIONS FOR EXAMINING THE FURNACE INSTALLATION
It is the owner’s responsibility to ensure that an annual inspection of the entire heating portion of the unit is made by a qualified service agency. Examine the furnace as outlined below in steps “1 - 6” before each heating season. Use Figure 3 for visual reference.
1. Examine the heat exchanger, vent pipe, combustion air passes gas, vent connectors and chimney to be sure they are clear and free of obstructions.
2. Examine the vent pipe making sure it is firmly in place, that it slopes slightly upward and is physically sound without holes and all of the connections are secure.
3. Examine the return-air duct connections to make sure they are physically sound, sealed to the furnace casing, and the ducts ter­minate outside the space containing the furnace.
4. Examine the furnace casing making sure the physical support is sound without sagging, cracks or gaps. Examine the furnace base making sure it is physically sound without cracks, gaps or sagging and has a good seal.
5. Examine the furnace casing for obvious signs of deterioration.
6. Examine the burner flames to make sure they are in good adjust­ment. Refer to the pictorial sketch shown in Figure 2 as a compari­son to the actual flame.
BLUE CONE PORTION OF FLAME SHOULD ENTER HEAT EXCHANGER TUBE
FIRE OR EXPLOSION HAZARD This furnace is designed and approved for use with Nat-
ural Gas and (LP) Propane Gas ONLY. DO NOT BURN ANY LIQUID FUEL OR SOLID FUEL IN THIS FURNACE.
Burning any unapproved fuel will result in damage to the furnace heat exchanger, which could result in Fire, Per­sonal Injury, and/or Property Damage.
EXAMINE ENTIRE
5
FURNACE CASING SHOWN IN ALL DRAWINGS
6
REMOVE PANEL TO EXAMINE BURNER FLAMES
3
EXAMINE RETURN AIR DUCT CONNECTION
EXAMINE EXTERNAL VENT PIPE
4
EXAMINE FURNACE CASING
FIGURE 2: Burner Flame Drawing
1
EXTERNAL HEAT EXCHANGER INTERNAL
VENT COMBUSTION AIR PIPE. MUST
REMOVE PANEL TO EXAMINE.
4
EXAMINE FURNACE CASING
6
REMOVE PANEL TO EXAMINE BURNER FLAMES
3
EXAMINE RETURN AIR DUCT CONNECTION (side or bottom)
FIGURE 3: Furnace Examination Checkpoints
2 Unitary Products Group
Page 3
268893-UUM-A-0407
HOW YOUR GAS FURNACE WORKS
Your furnace is a very easy appliance to take for granted. Season after season, it sits there in your home, keeping you warm and comfortable. For this reason, you may never have given much thought to the way your furnace operates. In order to get the safest and most efficient oper­ation from your furnace, you should understand how your furnace does its job.
When you set your thermostat to provide more heat in your home, you are starting the heating cycle of the furnace. First, the inducer motor starts to purge the heat exchanger of any remaining gases. Next, the hot surface ignitor glows and after a warm-up period the gas valve opens and ignition occurs. A short time later, the blower starts and dis­tributes the warm air throughout the home. When the temperature set­ting on your thermostat is reached, the gas valve closes, the main burners are turned off, and the blower continues to run until the remain­ing warm air in the system is distributed. When the blower stops, the heating cycle has ended.
START-UP AND SHUTDOWN INSTRUCTIONS
Read the Instructions Below Before Trying to Start the Furnace
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, and/or loss of life.
A. This appliance does not have a pilot. It is equipped with an ignition
device which automatically lights the burner. Do not try to light the burner by hand.
B. BEFORE OPERATING; smell all around the appliance area for
gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
C. Use only your hand to push the gas control switch to the “on” posi-
tion. Never use tools. If the switch will not operate by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Imme-
diately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control, which has been under water.
Operating Instructions:
1. STOP! Read the safety information above.
2. Set the thermostat to the lowest setting.
3. Turn off all electric power to the appliance.
4. Remove furnace door.
5. Move gas control switch to the “OFF” position. Do not force. See Figures 4 or 5.
6. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow “B” in the safety information above. If you don’t smell gas, go to next step.
7. Move gas control switch to the “ON” position. Do not force. See Figures 4 or 5.
8. Replace burner access panel.
9. Turn on all electric power to the appliance.
10. Set thermostat to the desired setting. Burner will light, which may take 30-60 seconds.
11. After three (3) trials for ignition, if the appliance will not operate fol­low the instructions, “TO TURN OFF THE APPLIANCE” and call your service technician or gas supplier.
To Turn Off the Appliance:
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be per­formed.
3. Remove burner access panel.
4. Move gas control switch to the “OFF” position. See Figures 4 or 5.
5. Replace burner access panel.
Should overheating occur, or the gas valve fail to shut off, turn the external manual gas valve in the gas supply line to the furnace to the “off” position and let the furnace cool off before shutting off the electrical power supply. Refer to Figure 6 or 7.
OUTLET PRESSURE PORT
INLET
WRENCH BOSS
INLET PRESSURE PORT
ON/OFF SWITCH (Shown in ON position)
OFF
ON
FIGURE 4: Gas Valve - All Except GR Models
INLET
WRENCH BOSS
SUPPLY PRESSURE TAP
ON/OFF SWITCH (shown in OFF position)
O
F
F
ON
MAIN REGULATOR ADJUSTMENT
FIGURE 5: Gas Valve - GR Models Only
EXTERNAL MANUAL SHUTOFF VALVE
TO GAS SUPPLY
DRIP LEG
GROUNDED JOINT UNION MAY BE INSTALLED INSIDE OR OUTSIDE UNIT.
FIGURE 6: Upflow Gas Piping
VENT PORT
OUTLET
MAIN REGULATOR ADJUSTMENT
ELECTRICAL CONNECTIONS
OUTLET
OUTLET (MANIFOLD) PRESSURE TAP
TO GAS SUPPLY
Unitary Products Group 3
Page 4
268893-UUM-A-0407
MANUAL SHUT-OFF VALV E
DRIP
GAS PIPE
GAS
LEG
GAS BURNERS
GAS VALVE
PIPE
DRIP LEG
MANUAL SHUT-OFF VALVE
FIGURE 7: Horizontal Gas Piping NOTE: The spring-loaded safety cut-off switch, mounted under the
blower deck will automatically cut off the electrical power supply to the furnace when the blower panel is removed. As a safety precaution, all electrical power and the gas supply to the furnace should be turned off before servicing.
FURNACE USER MAINTENANCE
Before proceeding, be sure the area is well ventilated. Turn the thermostat OFF. If the blower is running, wait until it stops automatically. Turn OFF the gas and electrical power supplies to the furnace. Check all metal parts and surfaces to be sure they have cooled to room temperature before you begin.
Every time the filters are changed the following items should be visually inspected:
• Check combustion air and vent pipe for blockage or leakage.
• Check all components to be sure they are in good condition and that there are no obvious signs of deterioration.
• Check the drain lines to make sure there are no cracks or leaks.
• Check for dirt or lint on any surfaces or on components. Do not try to clean any of the surfaces or components. Cleaning of the fur­nace and its components must be done by a qualified service pro­fessional.
If during the inspection of your furnace, you find any of the following conditions:
• Excessive amounts of dust and lint on components.
• Damaged or deteriorated components or surfaces.
• Leaks or blockage in the vent pipe passages.
• Water on any surface inside or outside of the furnace.
Do not operate the furnace, call a certified dealer / servicing contractor to check and / or clean your furnace, or for more information if you have questions about the operation of your furnace.
If all components appear to be in good operating condition, replace the front panels. Turn ON the gas and electrical power supplies to the fur­nace, and set thermostat to the desired temperature.
Air Filters
Dirty filters greatly restrict the flow of air and may cause damage to the moving parts of the furnace. If the filters become clogged the heat exchangers and blower motor could overheat resulting in a potentially dangerous situation. The filters should be checked every 3 months. On new construction, check the filters every week for the first four weeks and every three weeks after that, especially if the indoor fan is running continuously. When replacing the filter(s) you must use filters that are the same size as those recommended in Table 1. Never operate your furnace without a suitable air filter.
Removing Filters
Internally Mounted Air Filters
Some upflow furnaces may have their filters located on the side or bot­tom of the furnace in a filter wire retainer located inside the blower com­partment. To check filters located in the blower compartment:
1. Remove the upper furnace door by lifting up. Pull out bottom of door and lower from furnace.
2. Remove the blower compartment panel by lifting up.
3. The filters will be located on the bottom or on one of the sides. To remove bottom-mounted or side mounted filter (s) on all furnaces, push the looped end of the filter retainer rod in, and then move the retainer rod away from the filter.
4. Reverse the procedure to reinstall filters.
POSITION WIRE RETAINER PROVIDED UNDER FLANGE
CLIPS
RIGHT SIDE INSTALLATION SHOWN
FIGURE 8: Internal Filter Retainer Externally Mounted Air Filters
The air filter should be located in a rack attached to the casing of the furnace or placed in the return air duct. You can gain access to the filter by pulling on the door or unscrewing the retaining screw, then slide the filter(s) out of its channel. Replace throw away filter(s) with the same size new filter(s). Throw away filter(s) may be replaced with cleanable filter(s) at this time. Cleanable filter(s) may be cleaned as described in the manufacturer instructions or as described below and then re­installed.
To replace the filter after cleaning you must do the following:
1. Slide filter into place.
2. Snap the door on or place the door in position and tighten the retaining screws, if provided.
3. Make sure the door is secure to the end of the filter rack.
TABLE 1:
Cabinet Size Side (in) Side (cm) Bottom (in) Bottom (cm)
Filter Sizes
A 16 x 25 40.6 x 63.5 14 x 25 35.6 x 63.5 A 16 x 25 40.6 x 63.5 14 x 25 35.6 x 63.5 A 16 x 25 40.6 x 63.5 14 x 25 35.6 x 63.5 B 16 x 25 40.6 x 63.5 16 x 25 40.6 x 63.5 C (2) 16 x 25 (2) 40.6 x 63.5 20 x 25 50.8 x 63.5 B 16 x 25 40.6 x 63.5 16 x 25 40.6 x 63.5 B 16 x 25 40.6 x 63.5 16 x 25 40.6 x 63.5 C (2) 16 x 25 (2) 40.6 x 63.5 20 x 25 50.8 x 63.5 C 16 x 25 40.6 x 63.5 20 x 25 50.8 x 63.5 C (2) 16 x 25 (2) 40.6 x 63.5 20 x 25 50.8 x 63.5 D (2) 16 x 25 (2) 40.6 x 63.5 22 x 25 55.9 x 63.5
How to Clean your Filter
High-velocity filters may be cleaned with a vacuum cleaner or washed with a garden hose. Be sure to shake off excess water and allow filter to completely dry before re-installing the filter.
FURNACE FRONT
4 Unitary Products Group
Page 5
268893-UUM-A-0407
Blower Care
Even with good filters properly in place, blower wheels and motors will become dust laden after long months of operation. The entire blower assembly should be inspected annually. If the motor and wheel are heavily coated with dust, they can be brushed and cleaned with a vac­uum cleaner. If the blower cannot be properly cleaned without removing it from the furnace, then this service must be performed by a qualified service agency.
Make sure you DO NOT move the clip on weight on the indoor fan wheel when cleaning the wheel. This weight is used to balance the wheel. Moving the weight will cause the fan wheel to vibrate.
Motor Lubrication
The motors in these furnaces are permanently lubricated, and do not require periodic oiling.
Every time the filters are changed, the following items should be visu­ally inspected:
• Check combustion air and vent pipe for blockage or leakage.
• Check all components to be sure they are in good condition and that there are no obvious signs of deterioration.
• Check the drain lines to make sure there are no cracks or leaks.
• Check for dirt or lint on any surfaces or on components. Do not try to clean any of the surfaces or components. Cleaning of the fur­nace and its components must be done by a qualified service pro­fessional.
If during the inspection of your furnace, you find any of the following conditions:
• Excessive amounts of dust and lint on components.
• Damaged or deteriorated components or surfaces.
• Leaks or blockage in the vent pipe passages.
• Water on any surface inside or outside of the furnace.
Do not operate the furnace, call a certified dealer / servicing contractor to check and / or clean your furnace, or for more information if you have questions about the operation of your furnace.
If all components appear to be in good operating condition, replace the front panels. Turn ON the gas and electrical power supplies to the fur­nace, and set thermostat to the desired temperature.
SECTION II: SERVICE AND MAIN TENANCE MANUAL
SAFETY SECTION
The following safety rules must be followed when servicing th e furnace.
ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in
dangerous operation, serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury, and death or property damage.
• Before servicing, disconnect all electrical power to the fur­nace.
• When servicing controls, label all wires prior to disconnect­ing. Reconnect wires correctly.
• Verify proper operation after servicing.
FURNACE MAINTENANCE SECTION
The furnace should be cleaned and adjusted by a certified dealer or qualified service contractor once a year or before the start of every heating season. The following items must be cleaned and serviced or replaced if there are signs of deterioration.
1. The vent terminal.
2. The furnace vent and combustion air intake passageways. Should it be necessary to service the vent/air intake system, the manufac­turer recommends this service be conducted by a qualified service agency. The operation of this appliance requires the reassembly and resealing of the vent/air intake system.
3. The furnace burners, ignitor and flame sensor.
4. The condensate collection and disposal system. If any disassem­bly of components containing flue or vent gases is required, a qualified service agency must perform the service.
FURNACE CLEANING SECTION
NOTE: The cleaning operations listed below must be performed only by
a qualified service agency.
Burner Removal/Cleaning
The main burners should be checked periodically for dirt accumulation. If cleaning is required, follow this procedure:
1. Turn off the electrical power to the unit.
2. Turn off the gas supply at the external manual shut-off valve and loosen the ground union joint.
3. Remove the upper access panel and remove the burner box cover.
4. Disconnect wires from flame sensor, rollout switch and HSI igniter. Remove igniter carefully, as it is easily broken.
5. Remove the screws that hold the burner box assembly to the vest panel and remove the assembly.
6. Remove burners from the burner assembly.
7. Burners may be cleaned by rinsing in hot water.
8. Reassemble the burners in the reverse order.
Cleaning the Heat Exchanger
Lower Heat Exchanger Access
1. Turn off the electrical power to the unit and turn off gas supply at the shutoff valve.
2. Remove the blower and burner compartment access doors. Dis­connect the gas supply piping at the union to permit removal of the entire burner and gas control assembly from the vestibule panel. Use the wrench boss on the gas valve when removing or installing this piping. See Figure 4 or 5.
3. Unplug the igniter from the wire harness. Disconnect sensor and rollout switch wires located on top of the air shield. Identify and note the location of all leads for ease of reinstallation. Also discon­nect the wires at the side rollout switches (upflow only) and the gas valve wires.
4. Remove the screws holding the burner assembly to the vestibule panel and remove this assembly. Handle the assembly carefully since it contains the igniter, which is fragile and easily broken. The lower portion of the heat exchanger will now be exposed. To clean the burner assembly, use a vacuum cleaner, or remove the burn­ers as outlined in burner cleaning, and clean in hot water.
Upper Heat Exchanger Access
1. Perform steps 1-4 above.
2. Disconnect vent piping from the vent motor assembly at the top panel on the furnace (upflow only). On downflow models, the vent pipe is secured to the vent motor outlet with a screw. Remove this screw before proceeding.
Unitary Products Group 5
Page 6
268893-UUM-A-0407
3. Unplug the vent motor wires and ground wire. Remove the pres­sure switch tubing at the top on the vent motor housing.
NOTE: It is recommended that replacement gaskets be available
before removing vent motor.
4. Remove six mounting screws that hold the vent motor to the restrictor plate. The surface is gasketed and the gasket can be reused if it is carefully removed. It is necessary to remove this assembly to gain access to the restrictor plate mounting holes. The assembly may be vacuumed if cleaning is necessary. If any vent assembly parts are damaged, replace with an entire new assembly (except for gaskets).
5. Remove the perimeter screws attaching the restrictor plate assem­bly to the vestibule panel. The surface is also gasketed. The assembly, including the flue baffle plate (rear) may be vacuumed or cleaned with hot water if necessary.
6. The upper portion of the heat exchanger is now accessible. With a long flexible wire brush, clean inside each tube at both the top and bottom. The brush must pass around the rear heat exchanger tubes. Vacuum loose scale and dirt from each tube.
7. Clean - Replace all components in reverse order. Re-gasket all surfaces which required a gasket. Reconnect all wiring. Reattach vent pipe and gas supply lines before restoring service to furnace. Restore electrical power, check gas supply piping for leaks, and then verify furnace operation.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and danger­ous operation. Verify proper operation after servicing.
SEQUENCE OF OPERATION
The following describes the sequence of operation of the furnace. Refer to Figure 1 for component location.
Continuous Blower
Cooling/heating thermostats have a fan switch that has an ON and AUTO position. In the ON position the thermostat circuit is completed between terminals R and G. The motor will operate on the speed tap wire that is connected to the “HI COOL” cooling terminal on the control board. To obtain a constant air circulation at lower flow rate, change the high-speed wire to either the medium speed wire or the low speed wire.
Intermittent Blower - Cooling
Cooling/heating thermostats have a fan switch that has an ON and AUTO position. In the AUTO position the thermostat circuit is completed between terminals R and G when there is a call for cooling. The motor will operate on the speed tap wire that is connected to the “HI COOL” cooling terminal on the control board. The fan off setting is fixed at 60 seconds to improve cooling efficiency.
Heating Cycle
When the thermostat switch is set on HEA T and the fan is set on AUT O, and there is a call for heat, a circuit is completed between terminals R and W of the thermostat. When the proper amount of combustion air is being provided, the pressure switch will close, the ignition control pro­vides a 17-second warm-up period, the gas valve then opens, the gas starts to flow, ignition occurs and the flame sensor begins its sensing function. The blower motor will energize 30 seconds after the gas valve opens, if a flame is detected. Normal furnace operation will continue until the thermostat circuit between R and W is opened, which causes the ignition system and gas valve to de-energize and the burner flames to be extinguished. The vent motor will operate for 15 seconds and the blower motor will operate for the amount of time set by the fan-off delay jumper located on the control board. See Figure 8. The heating cycle is complete, and ready for the start of the next heating cycle.
TWIN
FAN OFF ADJUSTMENT JUMPER
Y/Y2
W
R
G
C
120
180
90
60
BLOWER
OFF
DELAY
FIGURE 9: Furnace Control Board If the flame is not detected within 7 seconds of the gas valve opening,
the gas valve is shut off and a retry operation begins. If the flame is lost for 2 seconds during the 10-second stabilization period, the gas valve is shut off and a retry operation begins. During a retry operation, the vent motor starts a 15 second inter-purge and the ignitor warm-up time is extended to 27 seconds. If the flame is established for more than 10 seconds after ignition during a retry, the control will clear the ignition attempt (retry) counter. If three retries occur during a call for heat, the furnace will shut down for one hour. If at the end of the one hour shut down there is a call for heat, the furnace will initiate a normal start cycle. If the problem has not been corrected the furnace will again lockout after three retries.
YELLOW-MED. LOW
RED-LOW BLACK-HI
BLUE-MED. HI
HUM
PAR K
PARK
HI COOL
HEAT
EAC-H
L1
XFMR
NEUTRALS
A momentary loss of gas supply, flame blowout, or a faulty flame probe circuit will result in a disruption in the flame and be sensed within 1.0 seconds. The gas valve will de-energize and the control will begin a recycle operation. A normal ignition sequence will begin after a 15 sec­ond inter-purge. If during the five recycles the gas supply does not return, or the fault condition is not corrected the ignition control will lock­out for 60 minutes.
During burner operation, a momentary loss of power for 50 milliseconds or longer will de-energize the gas valve. When the power is restored, the gas valve will remain de-energized and the ignition sequence will immediately restart.
6 Unitary Products Group
Page 7
268893-UUM-A-0407
Hot Surface Ignition System
HOT SURFACE IGNITION SYSTEM Do not attempt to light this furnace by hand (with a match or any other means). There may be a potential shock hazard from the components of the hot surface ignition system. The furnace can only be lit automatically by its hot surface ignition system.
TROUBLESHOOTING
The following visual checks should be made before troubleshooting:
1. Check to see that the power to the furnace and the ignition control module is ON.
2. The manual shut-off valves in the gas line to the furnace must be open.
3. Make sure all wiring connections are secure.
4. Review the sequence of operation. Start the system by setting the thermostat above the room temperature. Observe the system’s response. Then use the troubleshooting section in this manual to check the system’s operation.
Never bypass any safety control to allow furnace opera­tion. To do so will allow furnace to operate under poten­tially hazardous conditions.
Do not try to repair controls. Replace defective controls with UPG Source 1 Parts.
Never adjust pressure switch to allow furnace operation.
FURNACE CONTROL DIAGNOSTICS
The furnace has built-in, self-diagnostic capability. If a system problem occurs, a blinking LED shows a fault code. The LED can flash red, green or amber to indicate various conditions. It is located behind a clear view port in the blower compartment door.
The control continuously monitors its own operation and the operation of the system. If a failure occurs, the LED will indicate the failure code. If the failure is internal to the control, the light will stay on continuously. In this case, the entire control should be replaced, as the control is not field repairable.
Flash sequence codes 1 through 11 are as follows: LED will turn “on” for 1/4 second and “off” for 1/4 second. This pattern will be repeated the number of times equal to the code. For example, six “on” flashes equals a number 6 fault code. All flash code sequences are broken by a 2 sec­ond “off” period.
SLOW GREEN FLASH: Normal operation. SLOW AMBER FLASH: Normal operation with call for heat. RAPID RED FLASH: Twinning error, incorrect 24V phasing. Check
twinning wiring. RAPID AMBER FLASH: Flame sense current is below 1.5 microamps.
Check and clean flame sensor. Check for proper gas flow. Verify that current is greater than 1.5 microamps at flame current test pad.
4 AMBER FLASHES: The control board is recie ving a “Y” signal from the thermostat without a “G” signal, indicating improper thermostat wir­ing.
1 RED FLASH: This indicates that flame was sensed when there was not a call for heat. With this fault code the control will turn on both the inducer motor and supply air blower. A gas valve that leaks through or is slow closing would typically cause this fault.
2 RED FLASHES: This indicates that the normally open pressure switch contacts are stuck in the closed position. The control confirms these contacts are open at the beginning of each heat cycle. This would indicate a faulty pressure switch or miswiring.
3 RED FLASHES: This indicates the normally open pressure switch contact did not close after the inducer was energized. This could be caused by a number of problems: faulty inducer, blocked vent pipe, bro­ken pressure switch hose or faulty pressure switch.
4 RED FLASHES: This indicates that a primary or auxiliary limit switch has opened its normally closed contacts. With this fault code the control will operate the supply air blower and inducer. This condition may be caused by: dirty filter, improperly sized duct system, incorrect blower speed setting, incorrect firing rate or faulty blower motor.
5 RED FLASHES: This fault is indicated if the normally closed contacts in the rollout switch opens. The rollout control is manually reset. If it has opened, check for proper combustion air, proper inducer operation, and primary heat exchanger failure or burner problem. Be sure to reset the switch and cycle power (24 VAC) to the control after correcting the fail­ure condition.
6 RED FLASHES: This indicates that after the unit was operating, the pressure switch opened 4 times during the call for heat. If the main blower is in a “Delay on” mode, it will complete it, and any subsequent delay off period. The furnace will lock out for one hour and then restart.
7 RED FLASHES: This fault code indicates that the flame could not be established. This no-light condition occurred 3 times (2 retries) during the call for heat before locking out. Low gas pressure, faulty gas valve, dirty or faulty flame sensor, faulty hot surface ignitor or burner problem may cause this. The furnace will lock out for one hour and then restart.
8 RED FLASHES: This fault is indicated if the flame is lost 5 times (4 recycles) during the heating cycle. This could be caused by low gas pressure, dirty or faulty flame sensor or faulty gas valve. The furnace will lock out for one hour and then restart.
9 RED FLASHES: Indicates reversed line voltage polarity or grounding problem. Both heating and cooling operations will be affected. Check polarity at furnace and branch. Check furnace grounding. Check that flame probe is not shorted to chassis.
10 RED FLASHES: Gas flow with no call for heat. Check gas valve and gas valve wiring.
11 RED FLA SHES: This indicates that a primary or auxiliary limit switch has opened its normally-closed contacts and has remained open for more than five minutes. This condition is usually caused by a failed blower motor or blower wheel. Cycle power (24 VAC) to the control to reset the hard lockout condition after correcting the failure condition. 12 RED FLASHES: This code indicates an open igniter circuit, which could be caused by a disconnected or loose wire or by a cracked or bro­ken igniter.
STEADY ON RED: Control failure. Replace control board. 60-MINUTE AUTOMATIC RESET FROM LOCKOUT: This control
includes a “watchdog” type circuit that will reset from a lockout condition after 60 minutes. Operational faults 6,7,8 will be reset. This provides protection to an unoccupied structure if a temporary condition exists causing a furnace malfunction. An example would be a low incoming gas supply pressure preventing unit operation. When the gas pressure is restored, at some point the “watchdog” would restart the unit and pro­vide heat for the house.
NOTE: If a flame is detected the control flashes the LED for 1/8 of a second and then enters a flame stabilization period.
IGNITION CONTROL
Normal flame sense current is approximately
3.7 microamps DC (µa)
Low flame signal warning starts at 1.5 microamps.
Low flame signal control lockout point is
0.1 microamps DC (µa)
Unitary Products Group 7
Page 8
268893-UUM-A-0407
DIAGNOSTIC FAULT CODE STORAGE AND RETRIEVAL
The control in this furnace is equipped with memory that will store up to five error codes to allow a service technician to diagnose problems more easily. This memory will be retained even if power to the furnace is lost. This feature should only be used by a qualified service tech-
nician.
The control stores up to five separate error codes. If more than five error codes have occurred since the last reset, only the five most recent will be retained. The furnace control board has a button, labeled "LAST ERROR" that is used to retrieve error codes. This function will only work if there are no active thermostat signals. So any call for heating, cooling or continuous fan must be terminated before attempting to retrieve error codes.
Thermostat Calling for Heat
(Seconds)
THERMOSTAT
INDUCER
IGNITOR
MAIN VALVE
HUMIDIFIER
ELECTRONIC AIR CLEANER
CIRCULATING BLOWER
OFF
OFF
OFF
OFF
OFF
OFF
OFF
0
2
ON
ON
ON
17 22
ON
Fan on Delay 30 Seconds
OFF
To retrieve the error codes, push the LAST ERROR button. The LED on the control will then flash the error codes that are in memory, starting with the most recent. There will be a two-second pause between each flash code. After the error codes have all been displayed, the LED will resume the normal slow green flash after a five second pause. To repeat the series of error codes, push the button again.
If there are no error codes in memory, the LED will flash two green flashes. To clear the memory, push the LAST ERROR button and hold it for more than five seconds. The LED will flash three green flashes when the memory has been cleared, then will resume the normal slow green flash after a five-second pause.
Thermostat Satisfied
52
ON
OFF
ON
OFF
ON
OFF
0
OFF
15 Sec. Post Purge
OFF
OFF
60, 90, 120, 180 SEC. Selectable Fan Off Delay
OFF
OFF
OFF
OFF
FIGURE 10: Furnace Control Event Schedule
8 Unitary Products Group
Page 9
SECTION III: REPLACEMENT PARTS LIST
268893-UUM-A-0407
43
29
8 23 12
7 17
19
21 13 1
16
15
26
40
28
2
11
4
6,20
24
22 9
10
5
31
3
30
39
25
37
27
12A
11
19
12
24
TABLE 2:
7
Field Installed Accessories - Non Electrical
36
MODEL NO. DESCRIPTION USED WITH
1NP0347 PROPANE (LP) CONVERSION KIT ALL MODELS 1PS0301 1PS0302 80 MBH 1PS0311 100, 115, 130 MBH 1SR0302 SIDE RETURN FILTER KIT 1” FILTER ALL MODELS 1SR0200 SIDE RETURN FILTER KIT 1-4” FILTER ALL MODELS 1BR0114 BOTTOM RETURN FILTER KIT 1” FILTER 14-1/2” CABINETS 1BR0214 BOTTOM RETURN FILTER KIT 1-4” FILTER 14-1/2” CABINETS 1BR0117 BOTTOM RETURN FILTER KIT 1” FILTER 17-1/2” CABINETS 1BR0217 BOTTOM RETURN FILTER KIT 1-4” FILTER 17-1/2” CABINETS 1BR0121 BOTTOM RETURN FILTER KIT 1” FILTER 21” CABINETS 1BR0221 BOTTOM RETURN FILTER KIT 1-4” FILTER 21” CABINETS 1BR0124 BOTTOM RETURN FILTER KIT 1” FILTER 24-1/2” CABINETS 1BR0224 BOTTOM RETURN FILTER KIT 1-4” FILTER 24-1/2” CABINETS 1HF0801 INTERNAL FILTER KIT WITH 1” FIBER FILTER ALL MODELS
HIGH ALTITUDE PRESSURE SWITCH KIT
(Does Not Include Orifices)
35
40, 60 MBH
Unitary Products Group 9
Page 10
268893-UUM-A-0407
ITEM DESCRIPTION
MOTOR
MOTOR,DIRECT DRIVE BLOWER
1 2 MOTOR,VENTOR ASS’Y
ELECTRICAL
3 CAPACITOR 4 CONTROL, HIGH LIMIT 5 CONTROL, FURACE 6IGNITER 7 SENSOR, FLAME 8 SWITCH, AIR PRESSURE [1LP]
9 SWITCH, DOOR [SW] 10 TRANSFORMER 11 VALVE, GAS 12 CONTROL, LIMIT (Top)
CONTROL, LIMIT (Side, 2 Req’d)
12A
CONTROL, AUX LIMIT (2 Req’d)
13
14* FUSE
AIR MOVING
15 HOUSING, BLOWER 16 WHEEL, BLOWER
16A PANEL, FILLER WRAP
FABRICATED PARTS
17 SHIELD, SECONDARY AIR
18* BAFFLE, FLUE
19 BURNER, MAIN GAS 20 BRACKET, IGNITER 21 DECK, BLOWER (Rear) 22 DECK, FRONT 23 HEAT EXCHANGER ASS’Y 24 MANIFOLD, GAS
(Primary)
ITEM DESCRIPTION
25 PANEL, VEST ACCESS (Burner) 26 PAN, BASE 27 PANEL, BLOWER ACCESS 28 PANEL, TOP 29 WRAPPER, INSULATED 30 CHANNEL, TOE PLATE
31 BASE FRAME, SIDE (2 Req’d) 32* PLATE, RESTRICTOR 33* SHIELD, INDUCER
34 BRACKET, ROLL-OUT SWITCH
MISCELLANEOUS
35* FILTER 36* RACK, FILTER
37 PLUG HOLE WINDOW CLEAR-.875”
38 ORIFICE, BURNER
(Natural #45)
39 HANDLE, DOOR
40 COLLAR, FLUE 41* GROMMET, 1/2” DIA. 42* GASKET, RESTRICTOR PLATE
43 TUBING, SILICONE 44* SPRING, DOOR 45* WIRING DIAGRAM 46* WIRING HARNESS 47* FERRULE 48* GROMMET 49* BEZEL/LOGO 50* MOTOR MOUNT 51* LO-NOX SCREEN 52* GASKET KIT, INDUCER MOTOR
NOTE: *Not Shown
Major components and suggested stocking items are shown with shaded item number.
REPLACEMENT PART CONTACT INFORMATION
This is a generic parts list. To request a complete parts list, refer to the contact information below:
• Visit our website at www.source1parts.com for the following information:
1. Search for a part or browse the catalog.
2. Find a dealer or distributor.
3. Customer Service contact information. a. Click on the “Brand Links” button
b. Click on the “Customer Service” button
• You can contact us by mail. Just send a written request to:
York International
Consumer Relations
5005 York Drive
Norman, OK 73069
10 Unitary Products Group
Page 11
SECTION IV: WIRING DIAGRAM
268893-UUM-A-0407
FIGURE 11: Wiring Diagram
Unitary Products Group 11
Page 12
Limited Warranty
UPG warrants this product to be free from d efects in facto ry workmanshi p and material under nor mal use and ser vice and will , at its op tion, repair or replace any parts that prove to have such defects accordin g to the ter ms out lined on this warran ty. This warranty covers only the eq uip ment described by the Product Model Number and Serial Number listed on the Warranty Registration Card. UPG warrants the primary heat excha ngers i n th e produ ct t o be fr ee fro m def ects in fa ctory w orkma nship a nd mat erial under norma l u se and servi ce and will at its option, repair or furnish a repl acement heat exchanger, either new or reconditio ned, that meets the intended fit, us e and function of the origina l heat exchanger for any heat exchange r furnishe d by UPG whic h proves to h ave such de fects within the du ration of wa rranty cove rage. Alterna tively, UPG may, at its option, extend a replacement allowance to be appl ied toward the purchas e of a new furnace or packa ged unit marketed by UPG. The exact amount of th e allowance will be determined at the discret ion of UPG, based upon current market conditions, but i n no ca se shall this al lowanc e ex ceed thir ty (30) perc ent of the original consumer purchase price of the furnace, excluding such items as ductwork, wiring, piping and installation costs. UPG shall have no responsibility hereunder for installation, sh ipping, handling or other charges except as specifically pro vided herein. For your benefit and protect ion, re turn the Warranty Re gistration Card to UPG promptly after installation. This will initiat e the warr anty per iod and a llow us to contact you, should it become necessary. In the absence of a recorded Warranty Registration Card, the warranty period will begin upon product shipment from UPG.
This warranty extends only to the ori ginal cons umer purch aser and is non-tra nsferable. For this w arranty to apply, the product must be installed acc ording to UPG recommendations and specif icati ons, and i n ac cordanc e wit h all local , state, and n ation al code s; a nd the prod uct must not be removed from its place of original installation. The warran ty period for repair or replacement parts provided h ereunder shall not extend beyond the w arranty period stated on this war­ranty
HEAT EXCHANGER
FURNACE TYPE
Original Owner Subsequent Owner
80% GY8S / GM8S / GR8S / LY8S / LM8S / LF8S
UPG strongly recommends regular peri odic pre vent a tive mainte nan ce on t his e quip ment. Th e pe rson most familia r wi th th e equ ipmen t in your HVAC system is a UPG dealer. The UPG dealer can ensure your maintenance program meets the conditions of the "UPG Warranty", maximize the efficiency of the equipment, and service your unit within th e mandated guidelines with regard to unlawful discharge of refrigerants into the atmosphere. This warranty applies only to products installed in the United States and Canada.
20 N/A 10 5
Non-Residential
Applications
EXCLUSIONS
This warranty does not cover any:
1. Shipping, labor, or material charges.
2. Damages resulting from transportation, installation, or servicing.
3. Damages resu lting from accident , abuse, fire, flood, alteration, or acts of God (tamper ing, altering, defac ing or removing th e product serial numbe r will serve to void this warranty).
4. Damages resulting from use of the product in a corrosive atmosphere.
5. Damages resulting from inadequacy or interruption of electrical service or fuel supply, improper voltage conditions, blown fuses, or other like damages.
6. Cleaning or replacement of filters.
7. Damages resulting from failure to properly and regularly clean air and/or water side of condenser and evaporator.
8. Damages resul ting f rom: (I ) freez ing of conden ser water or cond ensate; (II) in adequ ate or interr upte d water sup ply; (I II) use of corrosive water; (IV) foul­ing or restriction of the water ci rcuit by foreign material or like c auses.
9. Damages resulting from operation with inadequate supply of air or water.
10. Damages resulting from use of components or accessories not approved by UPG (vent dampers, etc.).
11. Increase in fuel or electric cost.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABIL­ITY AND FITNESS FOR A PARTICULAR PURPOSE.
SOME STATES DO NOT ALLOW THE DISCLAIMER OF IMPLIED WARRANTY, SO THAT THE ABOVE DISCLAIMER MAY NOT APPLY TO YOU. SOME STATES ALLOW ONLY A PARTIAL LIMIT ATION ON IMPLIED WARRANTIES TO LIMIT THE DURA TION OF IMPLIED W ARRANTIES TO THE DURA-
TION OF THE EXPRESS WARRANTY. IN SUCH STATES, THE DURATION OF IMPLIED WARRANTIES IS HEREBY EXPRESSLY LIMITED TO THE DURA­TION OF THE EXPRESS WARRANTY ON THE FACE HEREOF.
IN NO EVENT, WHETHER AS A RESULT OF BREACH OF WARRANTY OR CONTRACT, TORT (INCLUDING NEGLIGENCE) STRICT LIABILITY OR OTH­ERWISE, SHALL UPG BE LIABLE FOR SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, INCLUDING BUT NOT LIMITED TO LOSS OF USE OF THE EQUIPMENT OR ASSOCIATED EQUIPMENT , LOST REVENUES OR PROFITS, COST OF SUBSTITUTE EQUIPMENT OR COST OF FUEL OR ELEC­TRICITY. THE ABOVE LIMITATIONS SHALL INURE TO THE BENEFIT OF UPG'S SUPPLIERS AND SUBCONTRACTORS. THE ABOVE L IMITATION ON CONSEQUENTIAL DAMAGES SHALL NOT APPLY TO INJURIES TO PERSONS IN THE CASE OF CONSUMER GOODS.
SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF LIABILITY FOR CONSEQUENTIAL OR INCIDENT AL DAMAGES, OR FOR STRICT LIABILITY IN TORT, SO THAT THE ABOVE EXCLUSIONS AND LIMITATIONS MAY NOT APPLY TO YOU.
UPG DOES NOT ASSUME, OR AUTHORIZE ANY OTHER PERSON TO ASSUME FOR UPG , ANY OTHER LIABILITY FOR THE SALE OF THIS PRODUCT . THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE. For Owner's Information:
PARTSResidential Applications
PRODUCT MODEL. NO. ____________________ INSTALLATION DATE ______________________________ UNIT SERIAL NO. _________________________ INSTALLING DEALER ______________________________
Subject to change without notice. Printed in U.S.A. 268893-UUM-A-0407 Copyright © by York International Corp. 2007. All rights reserved. Supersedes: 166747-UUM-C-0706
Unitary 5005 Norman Products York OK Group Drive 73069
Loading...