York LEU360, LEU480, LEU600 Technical Manual

Page 1
550.13-TG2Y (1001)
g
g
g
y
y
TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 30, 40 & 50 TON LEU360, 480 & 600
PROVEN PERFORMANCE GENERAL
The LEU line is a flexible performer. LEU360 and 480 can be position in up to 12 different positi ons and suspended in various positions. The LEU600 can be position in up to 7 different arran will
ive you the power to condition large amounts of build-
space and the ability to conform to almost any situation.
in
ements and suspended also. The LEU line
FEATURING
• PART LOAD OPERATION
• EASE OF SERVICE
• NON-RECYCLING PUMPDOWN
• BASE SECTIONS (30 and 40 ton onl
• SUSPENSION PACKAGES
• HOT WATER COILS
• STEAM COILS (LEU360 onl
• WIDE RANGE OF BLOWER MOTORS
• A VARIETY OF DRIVE PACKAGES
)
)
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
Page 2
550.13-TG2Y (799)
TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
MODULAR DESIGN . . . . . . . . . . . . . . . . . . . . . . . . . 3
FACTORY-MOUNTED COMPONENTS . . . . . . . . . . 3
ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 20
EACH UNIT SHALL BE . . . . . . . . . . . . . . . . . . . . . . . . .20
EACH UNIT ENCLOSURE SHALL HAVE . . . . . . . . . . .20
THE DIMENSIONS OF EACH UNIT . . . . . . . . . . . . . . .20
THE BLOWER MOTOR SHALL . . . . . . . . . . . . . . . . . .20
THE EVAPORATOR COIL SHALL . . . . . . . . . . . . . . . .20
THE BLOWER WHEELS SHALL . . . . . . . . . . . . . . . . .20
LIST OF FIGURES
1 UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . .3
2 COIL CIRCUITING LIQUID LINE . . . . . . . . . . . . . . . . .8
3 UNIT DIMENSIONS - LEU360 & 480 . . . . . . . . . . . . . .9
4 UNIT DIMENSIONS - LEU600 . . . . . . . . . . . . . . . . . .10
5 HOT WATER COIL DIMENSIONS . . . . . . . . . . . . . . .10
6 STEAM COIL DIMENSIONS . . . . . . . . . . . . . . . . . . .11
7 BASE SECTION DIMENSIONS . . . . . . . . . . . . . . . . .11
8 BLOWER CURVE LEU360 . . . . . . . . . . . . . . . . . . . . .15
9 BLOWER CURVE LEU480 . . . . . . . . . . . . . . . . . . . . .17
10 BLOWER CURVE LEU600 . . . . . . . . . . . . . . . . . . . . .19
LIST OF TABLES
1 STATIC RESISTANCES FOR UNIT ACCESSORIES . 4
2 UNIT BLOWER MOTOR DATA . . . . . . . . . . . . . . . . . . 5
3 UNIT DRIVE DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 LEU600 OVERLOAD ELEMENTS . . . . . . . . . . . . . . . . 6
5 LEU600 STARTERS . . . . . . . . . . . . . . . . . . . . . . . . . . 6
6 HOT WATER COIL HEATING CAPACITIES. . . . . . . . 6
7 CAP CORRECTION & PRESS DROP VS GPM . . . . . 7
8 STEAM COIL CAP (LEU360 ONLY) . . . . . . . . . . . . . . 7
9 CORRECTION FACTOR FOR HIGH STEAM . . . . . . . 7
10 UNIT DIMENSIONS - LEU 360 & 480 . . . . . . . . . . . . . 9
11 HOT WATER COIL DIMENSIONS . . . . . . . . . . . . . . . 10
12 STEAM COIL DIMENSIONS . . . . . . . . . . . . . . . . . . . 11
13 BASE SECTIONS DIMENSIONS . . . . . . . . . . . . . . . . 11
14 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
15 ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . 13
16 L*EU360 SPLY AIR BLOWER PERF . . . . . . . . . . . . . 14
17 L*EU480 SPLY AIR BLOWER PERF . . . . . . . . . . . . . 16
18 L*EU600 SPLY AIR BLOWER PERF . . . . . . . . . . . . . 18
2 Unitary Products Group
Page 3
DESCRIPTION
y
g
y
y
y
y
g
g
y
g
g
y
y
y Sy
g
g
y
g
y
y
y
y y
y
y
g
g
g
y
g
g
g
g
y
g
g
y
g
g
y
550.13-TG2Y (1001)
Evaporator blower units are designed with two distinct mod­ules to provide max im um ap pli ca tio n fl ex ibi lit ton units are shipped as sin module mounted on top of the coil module, The blower mod­ule can be repositioned in the field to meet almost an lation requirement. Blower and coil modules for the 50 ton units are shipped separate ly to simplify handling. These mod­ules can be connected in the field with the same flexibilit the smaller units.
The blower module includes the blower wheels and room for a field-mounted motor and drive. The coil module includes direct expansion coils, 1 in. throwawa noid valves for both capacit mal expansion valves, distributors and a condensate drain pan.
Every evaporator coil is pressurized with air to 325 psig and leak tested under water. After the headers are brazed onto the coil and the coil is installed in the unit, the coil is pressur­ized with a combination of refri
for pressu re t e sting and addit i onal l e ak t e sti ng. After the
psi coil is evacuated and deh holdin
charge of refrigerant-22 for storage and/or shipping.
Steam coils, hot water coils, base sections, suspension hard­ware, blower motors and drive packa field-installed accessories to provide additional application flexibilit
These evaporator blowers, combined with condensing units, provide These units are manufactured under ISO 9001 Qualit tem Certification.
.
ears of quiet, efficient and dependable operation.
le packages with the blower
reduction and pumpdown, ther-
erant-22 and nitrogen to 150
drated, it is pressurized with a
. The 30 and 40
instal-
as
filters, liquid line sole-
es are available as
Units ma can be arran ments. Each unit is available with a choice of blower motors, drive packages and other accessories to make them suitable for most applications.
be bottom-supported or ceiling-suspended and
ed to meet almost any space or duct r equire-
FACTORY-MOUNTED COMPONENTS
PART LOAD OPERATION These evaporator blowers have multiple coils with pre-piped distributors, expansion valves and solenoid valves. Field modifications are not required for part load operations. Capacit economical operation, but also maintains more even temper­ature and humidit
EASY SERVICE Serviceable expansion valves are provided on ever provide man required, it is not necessar
PUMPDOWN Evaporator blowers include a solenoid valve for non-rec in the conditioned space is satisfied, the refri pumped into the hi
unit. These superior valves are factory-installed to
levels in the conditioned space.
ears of trouble-free operation. If service is
cling pumpdown. When the cooling requirem ent
h side of the system.
reduction not only provides
to unbraze any joints.
ACCESSORIES
BASE SECTIONS (30 and 40 ton only) Base sections can used to elevate units above the floor. If desired, outdoor air may be introduced through these sections by cutting an access openin nection. These bases have a durable finish to match the
s-
evaporator blower unit. The certain applications.
to accommodate the outdoor air duct con-
may have to be insulated for
erant is
MODULAR DESIGN
These evaporator blo wers can be ar ranged for a variety of air dischar tion.
FIGURE 1 : UNIT INSTALLATION
The above illustration shows three of the common installation arran other possibilities.
Unitary Products Group 3
e patterns in either the horizontal or the vertical posi-
ements. Refer to the unit installation instructions for
SUSPENSION PACKAGES These accessories can be used to suspend horizontal units from above without interferin with access to the unit. They can also be used for elevating a floor-mounted unit (either horizontal or vertical) to provide additional hei sate drain connection. All suspension packa with vibration isolators.
HOT WATER COILS Drainable water coils are available for field installation between the blower and the coil modules of both horizontal and vertical units. Since their casin the dimensions and the finish of the basic units, the an inte of their casin that have been mechanicall Both headers are located on the same end of the coil. Coils are leak-tested at 325 psi connections are capped for st ora
STEAM COILS (LEU360 onl the LEU360 for installation between the blower and coil mod-
ht for the installation of a trap at the conden-
es can be used
s match
become
ral part of the unit afte r installation. The co ils s lid e o ut
s for easy installation. Coils have copper tubes
expanded into aluminum fins.
under water and dried befor e the ir
e and shipping.
) A steam coil is available on
Page 4
550.13-TG2Y (799)
g
g
g
g
y
g
g
y
y
g
y
g
y
y
g
g
y
y
ules of both horizontal and vertical units. Since the casin matches the dimensions and the finish of the basic unit, it becomes an inte slides out of the casin the casin copper tubes that h ave been m echa nical l
ral part of the unit after installation. The coil
s for easy installation and is pitched in
s to facilitate condensate drainage. The coil has
expanded into alu­minum fins. Both headers are located on the same end of the coil. The coil is leak-tested at 325 psi connections are capped for stora
and dried before the
e and shipping.
DRIVE P ACKAGES Diff erent size pul le able for each unit to provide a blower RPM ran almost an
s can be adjusted to provide the proper blower RPM. All
le drive packa ratin
of the bl ower m otor. Two-groove pulleys and two belts are provided on ever above.
STARTERS AND HEATER ELEMENTS (50 ton onl
BLOWER MOTORS Different HP motors are available for each unit to meet almost an motors are UL approved, have permanentl
s and are field-mo unt ed within the ins ulate d cabi net of
bearin
air delivery requirement. All
lubricated ball
blower mot ors that are av ailable for t he 50 ton uni ts do not have inher ent prot ect ion a nd re qui re e xte rnal moto r ov erl oad protection.
the units to minimize the transmission of sound to the sur­rounding space. All motors have inherent protection except those available for the 50 ton unit. Motors for 50 ton units require a starter and overload elements
TABLE 1: STATIC RESISTANCES FOR UNIT ACCESSORIES
UNIT MODEL ACCESSORY CFM
10,000 11,000 12,000 13,000 14,000
LEU360
LEU480
LEU600
Hot Water Coil 0.08 0.09 0.10 0.12 0.14 Steam Coil 0.17 0.20 0.23 0.27 0.31
12,800 14,400 16,000 17,600 19,200
Hot Water Coil 0.11 0.13 0.15 0.17 0.20
16,000 18,000 20,000 22,000 24,000
Hot Water Coil 0.15 0.18 0.21 0.24 0.28
s and belts are avai l-
e to meet
air delivery requirement. Variable pitch motor pul-
es are rated at least 25% above the nominal HP
drive package rated at 5 HP and
) The
4 Unitary Products Group
Page 5
TABLE 2: UNIT BLOWER MOTOR DATA
UNIT
MODEL
HP
5
2LR04605023 2LR04605032 230/460 2LR04607523
LEU360
7-1/2
2LR04607532 230/460 2LP04610033
10
2LR04610032 230/460 2LR04607523
7-1/2
2LR04607532 230/460
LEU480
2LP04610033
10
2LR04610032 230/460 2LP04610017
10
LEU600
2LP04610032 230/460 2LP04615017
15
2LP04615032 230/460
1.
All motors are 1750 RPM and have a 1.15 service fac­tor. All motors have inherent protection and perma­nently lubricated ball bearings, except the motors for the LEU600. These motors require external protection (starter with overloads and periodic lubrication). All motors have a solid base.
BLOWER MOTOR DATA
MODEL
#
FRAME
SIZE
184
213
215
213
215
215
254
1
V
OLTAGE
(3PH-60HZ)
208
208
200/208
208
200/208
200
200
550.13-TG2Y (1001)
TABLE 3: UNIT DRIVE DATA
UNIT
MODEL
LEU360
LEU480
LEU600
1.
The drive package includes a bushing for the blower pulley.
MODEL#B
LOWER
RPM
1LD0415 636-795 4.0-5.0 1-1/8 11 1-3/16 2 63.3 A62 1LD0407 668-827 4.2-5.2 1-3/8 11.0 1-3/16 2 63.3 A62 1LD0408 827-986 5.2-6.2 1-3/8 11.0 1-3/16 2 59.7 A59 1LD0409 607-776 4.3-5.5 1-3/8 12.4 1-3/16 2 85.1 B84 1LD0410 776-917 5.5-6.5 1-3/8 12.4 1-3/16 2 86.8 B85 1LD0411 692-833 4.9-5.9 1-3/8 12.4 1-3/16 2 78.6 B78
1LD0412 762-931 5.4-6.6 1-5/8 12.4 1LD0415 636-795 4.0-5.0 1-1/8 11
DRIVE DATA BELT DRIVE
MOTOR PULLEY BLOWER PULLEY
PITCH DIA. BORE PITCH DIA. BORE
1-3/16 1-3/16
QTY
1
1
PITCH
LENGTH
2 76.8 B75 2 63.3 A62
DESIGNATION
Unitary Products Group 5
Page 6
550.13-TG2Y (799)
TABLE 4: 2LP* MOTOR OVERLOAD ELEMENTS
VOLTAGE MO TOR HP KIT # 200 V
230 V 460 V
200 V 230 V 460 V
OLTS OLTS OLTS
OLTS OLTS OLTS
10 HP Motor
15 HP Motor
2MP04701600 2MP04701400 2MP04701300
2MP04701500 2MP04701700 2MP04701200
TABLE 5: 2LP* MOTOR STARTERS
MOTOR HP @ VOLTAGE KIT NUMBER
10HP motor @ 200 volts or 15 HP motor @ 200 or 230 volts
10HP motor @ 230 or 460 volts or 15 HP motor @ 460 volts
2MS04700100
(60 AMP)
2MS04700200
(30 AMP)
DO NOT OPERATE THE SUPPLY AIR BLOWER MOTOR ABOVE ITS NOMINAL HP RATING WHEN A UNIT IS EQUIPPED WITH A HOT WATER COIL ACCESSORY. DO NOT USE STEAM IN HOT WATER Coils.
DO NOT OPERATE THE SUPPLY AIR BLOWER ABOVE ITS NOMINAL HP RATING WHEN A UNIT IS EQUIPPED WITH A STEAM COIL ACCESSORY.
ALTHOUGH THESE COILS ARE SUITABLE OF A MUCH HIGHER PRESSURE, STEAM ABOVE 25 PSIG PROVIDES TOO MUCH HEAT THAT COULD DAMAGE THE BLOWER MOTOR.
TABLE 6: HOT WATER COIL HEATING CAPACITIES1.
HOT WATER
COIL MODEL
1HW0406
1HW0407
1.
These capacities do not include any blower motor heat.
Temperature Water Drop (°F) = (2 x MBH)/GPM
NOTE:
UNIT
MODEL
LEU360 50
LEU480 75
LEU600 75
GPM CFM
8,000 236 304 372 440 508 10,000 265 341 416 492 568 12,000 291 374 457 540 623 14,000 315 405 495 585 675 12,800 348 447 547 646 746 16,000 389 500 611 722 833 19,200 425 547 668 790 911 16,000 389 500 611 722 833 20,000 436 561 686 810 935 24,000 473 610 746 882 1,019
ENTERING WATER TEMPERATURE MINUS ENTRY AIR TEMPERATURE, °F.
70 90 110 130 150
6 Unitary Products Group
Page 7
TABLE 7: CAPACITY CORRECTION AND
PRESSURE DROP VS GPM
HOT WATER
COIL MODEL
1HW0406
1HW0407
1.
For pressure drop in feet (water), multiply these values by 2.31.
GPM
25 0.4 0.79 50 1.0 1.00 75 1.8 1.04
100 3.4 1.07
50 1.0 0.95
75 1.5 1.00 100 2.4 1.03 125 3.5 1.05
PRESSURE
DROP
PS
1
I
550.13-TG2Y (1001)
CAPACITY
CORRECTIO
N
FACTOR
TABLE 8: STEAM COIL CAPACITY1 (LEU360 only), MBH @ 2psig
STEAM COIL
MODEL
1NF0454
1.
These capacities do not include any blower motor heat.
2.
Multiply these capacities by the factors in Table 9 to correct for higher steam pressure.
UNIT
MODEL
LEU360
CFM
8,000 535 483 432 380 10,000 592 535 478 422 12,000 642 580 518 456 14,000 687 621 555 489
DRY BULB TEMPERATURE OF AIR ENTERING COIL, °F
10 30 50 70
TABLE 9: CORRECTION FACTOR FOR HIGH STEAM
Steam Pressure, psig 5 10 15 20 25
Capacity correction factor 1.05 1.12 1.19 1.25 1.30
NOTE: Steam rate = (lbs/Hr.) = 1.025 x MBH
2
Unitary Products Group 7
Page 8
550.13-TG2Y (799)
FIGURE 2 : COIL CIRCUITING LIQUID LINE
8 Unitary Products Group
Page 9
550.13-TG2Y (1001)
FIGURE 3 : UNIT DIMENSIONS - LEU360 & 480
TABLE 10: UNIT DIMENSIONS - LEU 360 & 480
MODEL A B C D E F G H J K M N P
LEU360 LEU480
100-1/8 95-5/8 33-1/4 36-5/8 73-1/4 2-1/2 18-7/8 16-1/2 15-13/16 21-7/8 22-9/16 1 2-1/8 103-1/8 98- 5/8 40-5/8 44 88 2-1/2 18-7/8 23-7/8 20-11/16 21-7/8 20-11/16 1-1/8 1-5/8
Unitary Products Group 9
Page 10
550.13-TG2Y (799)
FIGURE 4 : UNIT DIMENSIONS - LEU600
FIGURE 5 : HOT WATER COIL DIMENSIONS
TABLE 11: HOT WATER COIL DIMENSIONS
COIL
MODEL
1HW0406
UNIT
MODEL
LEU360 100-1/8 37-7/8 6-3/4 3-7/8 1-3/8 1-3/8
ABCDEF
DIMENSIONS
TABLE 11: HOT WATER COIL DIMENSIONS
COIL
MODEL
1HW0407
UNIT
MODEL
LEU480 LEU600
ABCDEF
103-1/8 45-1/4 6 -1/2 4 1-5/8 1-5/8
DIMENSIONS
10 Unitary Products Group
Page 11
FIGURE 6 : STEAM COIL DIMENSIONS
550.13-TG2Y (1001)
TABLE 12: STEAM COIL DIMENSIONS
COIL
MODEL
1NF0454
1.
UNIT
MODEL
LEU360 100-1/8 37- 7/8 4-3/8 18-3/8 1-1/2 2 2-1/2
Coils are field-installed between the evaporator coil and the blower section of the unit.
ABCDEFG
DIMENSIONS
1
FIGURE 7 : BASE SECTION DIMENSIONS
TABLE 13: BASE SECTIONS DIMENSIONS
BASE
MODEL
1BS0406 1BS0407
1.
Ventilation air can be brought into the unit through the base section providing the base section is fully insu­lated in the field.
Unitary Products Group 11
UNIT
MODEL
LEU360 100-1/8 37-7/8 LEU480 103-1/8 45-1/4
DIMENSIONS
AB
1
Page 12
550.13-TG2Y (799)
TABLE 14: PHYSICAL DATA
DESCRIPTION
Rows Deep X Rows High 4 x 32 4 x 40 4 x 50 Finned Length, inches 93 96 96
EVAPORATOR
COIL
CENTRIFUGAL
BLOWERS (2 PER UNIT)
FILTERS (THROWAWAY)
OPERATING CHARGE
(R
EFRIGERANT
- 22)
DRAINABLE HOT WATER
COIL ACCESSORY
NON-FREEZE, STEA M
DISTRIBUTING COIL
ACCESSORY
COMPONENT WEIGHT
Face Area, feet Tube (copper) OD, inches 1/2 1/2 1/2 Fins (Aluminum) per 1 inch 12 12 12
Diameter X Width, inches (Forward Curved) 18 x 18 18 x 18 20 x 18
Size and Quantity Per Model, inches
Total Face Area / feet System 1 18 12 14
LBS
System 2 - 12 19 Tube (copper) OD, inches 1/2 1/2 1/2 Rows Deep 2 2 2 Fins (Aluminum) per 1 inch 12 12 8
Face Area, feet Connections (Supply & Return), inches 13/8 OD (copper) 1-5/8 OD (copper) Tube (copper) OD, inches 1 (Outside) 5/8 (in.) Rows Deep 1 Fins (Aluminum) per 1 inch 8
Face Area, feet Connection, (Brass)
Inches (NPTE) Basic Unit (Less Motor & Drive) 690 1170 1500
Shipping Weight (lbs) 990 1170 Operating Weight (lbs) 1115 1310
Accessories
Blower Motor (1750 RPM)
MODEL
LEU360 LEU480 LEU600
2
26.0 33.4 41.7
16 x 25 x 1 - - 6 20 x 20 x 1 - 12 ­20 x 22-1/4 x 1 - 3 ­20 x 25 x 1 10 - 3 25 x 25 x 1 - - 6
2
2
2
34.7 42.6 53.1
21.2 27.2 27.2
N/A
18.2
Inlet 2 Outlet 1-1/2
Hot Water Coil 150 190 190
Steam Coil 160 - -
Supply Air Plenum 125 - -
Return Air Grille 25 - -
120 (5HP) - -
150 (7.5HP) 150 (7.5HP) 150 (7.5HP)
180 (10HP) 180 (10HP) 180 (10HP)
12 Unitary Products Group
Page 13
TABLE 15: ELECTRICAL DATA
MODELS
LEU
360
230/460-3-60
480
230/460-3-60
600
230/460-3-60
1.
Based on an 80% power factor and on a 3% voltage drop.
2.
Dual element, time delay fuses.
3.
For additional motor data, refer to blower motor and drive table.
MOTOR NAMEPLATE DATA MAX. WIRE
POWER SUPPLY
208-3-60
208-3-60
200-3-60
@230V
@460V
@230V
@460V
@230V
@460V
550.13-TG2Y (1001)
MAX. FUSE
2
(A
SIZE
MPS
)
HP
3
FLA
LENGTH
1
(FT.)
5 13.6 135 25 30
7-1/2 21.0 135 35 60
10 25.0 175 40 60
5 13.4 150 25 30
7-1/2 21.0 150 35 60
10 25.0 195 40 60
5 6.7 385 12 30
7-1/2 10.5 245 20 30
10 12.5 320 20 30
7-1/2 21.0 135 35 60
10 25.0 175 40 60
7-1/2 21.0 150 35 60
10 25.0 195 40 60
7-1/2 10.5 245 20 30
10 12.5 320 20 30 10 34.4 190 60 60 15 46.0 215 70 100 10 28.6 170 50 60 15 42.0 180 70 100 10 14.3 285 25 30 15 21.0 300 35 60
MIN. DISC.
SWITCH SIZE
(A
MPS
)
Unitary Products Group 13
Page 14
550.13-TG2Y (799)
TABLE 16: L*EU360 SUPPLY AIR BLOWER PERFORMANCE
1
CFM
RPM
SP
2
BHP
3
W
K
SP
2
BHP
3
W
K
SP
2
BHP
3
W
K
SP
2
BHP
3
W
K
10,000 11,000 12,000 13,000 14,000
600
635
700
775
800
875
900
970 1000
0.48 2.8 2.4 0.35 3.3 2.9 0.20 3.9 3.4 0.03 4.5 3.9 ———
4
0.62 3.1 2.7 0.49 3.7 3.2 0.35 4.3 3.7 0.19 4.9 4.2 0.03 5.5 4.7
5
0.87 3.8 3.3 0.76 4.4 3.8 0.63 5.0 4.3 0.49 5.6 4.8 0.34 6.3 5.4
6
1.21 4.7 4.1 1.11 5.3 4.6 0.99 5.9 5.1 0.86 6.5 5.6 0.72 7.2 6.2
7
1.30 4.9 4.2 1.20 5.5 4.8 1.08 6.2 5.4 0.95 6.9 6.0 0.81 7.6 6.6
8
1.64 5.9 5.1 1.54 6.5 5.6 1.43 7.1 6.1 1.32 7.8 6.7 1.20 8.6 7.4
1.75 6.2 5.4 1.66 6.8 5.9 1.55 7.4 6.4 1.44 8.1 7.0 1.33 8.9 7.7
9
2.10 7.2 6.2 2.00 7.8 6.7 1.90 8.5 7.3 1.81 9.2 7.9 1.71 10.0 8.6
2.25 7.6 6.6 2.15 8.2 7.1 2.06 8.8 7.6 1.97 9.5 8.2 1.88 10.4 9.0
1.
Unit resistance is based on a wet evaporator coil and clean filters.
2.
Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to the blower motor and drive table and the accessory static resistance table for additional information.
3.
Motors can be selected to operate into the service factor because they are located in the moving air stream, upstream of any heat­ing device. units with steam or hot water coils are the only exception. On these units, the BHP must not exceed the nominal HP rating of the motor.
4.
Min. speed for drive accessory 1LD0415.
5.
Min. speed for drive accessory 1LD0414
6.
Min. speed for drive accessory 1LD0408
7.
Max. speed for drive accessory 1LD0415
8.
Max. speed for drive accessory 1LD0414
9.
Max. speed for drive accessory 1LD0406
SP
2
BHP
3
W
K
14 Unitary Products Group
Page 15
550.13-TG2Y (1001)
FIGURE 8 : BLOWER CURVE LEU360
Unitary Products Group 15
Page 16
550.13-TG2Y (799)
TABLE 17: L*EU480 SUPPLY AIR BLOWER PERFORMANCE
CFM
RPM
SP
1
BHP
2
W
K
SP
1
BHP
2
W
K
SP
1
BHP
2
W
K
SP
1
BHP
2
W
K
SP
1
12,800 14,400 16, 000 17,600 19,200
600
640
700
775
800 900
915
0.31 4.3 3.7 0.13 5.1 4.4 —————————
3
0.49 4.8 4.1 0.31 5.6 4.8 0.15 6.3 5.4 ——————
0.76 5.5 4.7 0.59 6.4 5.5 0.42 7.2 6.2 0.24 8.1 7.0 0.03 9.2 7.9
4 5
1.10 6.5 5.6 0.96 7.4 6.4 0.80 8.4 7.2 0.63 9.4 8.1 0.42 10.4 9.0
1.22 6.8 5.9 1.08 7.8 6.7 0.93 8.8 7.6 0.76 9.8 8.4 0.55 10.8 9.3
1.76 8.1 7.0 1.64 9.3 8.0 1.50 10.5 9.0 ——————
6
1.84 8.3 7.2 1.72 9.5 8.2 1.58 10.7 9.2 ——————
1.
Unit resistance is based on a wet evaporator coil and clean filters.
2.
Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to the blower motor and drive table and the accessory static resistance table for additional information.
3.
Min. speed for drive accessory 1LD0409.
4.
Min. speed for drive accessory 1LD0410.
5.
Max. speed for drive accessory 1LD0409.
6.
Max. speed for drive accessory 1LD0410.
BHP
2
W
K
16 Unitary Products Group
Page 17
550.13-TG2Y (1001)
FIGURE 9 : BLOWER CURVE LEU480
Unitary Products Group 17
Page 18
550.13-TG2Y (799)
TABLE 18: L*EU600 SUPPLY AIR BLOWER PERFORMANCE
1
CFM
RPM
SP
2
BHP
3
W
K
SP
1
BHP
2
W
K
SP
1
BHP
2
W
K
SP
1
BHP
2
W
K
SP
16,000 18,000 20, 000 22,000 24,000
600
660
700
760
800
900
930
0.92 6.0 5.2 0.72 7.2 6.2 0.50 8.4 7.2 0.25 9.7 8.4 ———
4
1.27 7.3 6.3 1.09 8.5 7.3 0.88 9.8 8.5 0.62 11.2 9.7 0.33 12.7 11.0
1.50 8.2 7.1 1.34 9.4 8.1 1.13 10.7 9.2 0.87 12.2 10.5 0.59 13.7 11.8
5
1.86 9.5 8.2 1.72 10.8 9.3 1.53 12.3 10.6 1.28 13.8 11.9 1.00 15.6 13.5
6
2.10 10.4 9.0 1.98 11.8 10.2 1.79 13.3 11.5 1.55 14.9 12.9 1.28 16.9 14.6
2.70 12.8 11.0 2.62 14.5 12.5 2.50 16.0 13.8 ——————
7
2.88 13.5 11.6 2.81 15.3 13.2 —————————
1.
Unit resistance is based on a wet evaporator coil and clean filters.
2.
Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to the blower motor and drive table and the accessory static resistance table for additional information.
3.
Motors can be selected to operate into the service factor because they are located in the moving air stream, upstream of any heat­ing device. Units with steam or hot water coils are the only exception. On theses units, the BHP must not exceed the nominal HP rating of the motor.
4.
Min. speed for drive accessory 1LD0411.
5.
Min. speed for drive accessory 1LD0412.
6.
Max. speed for drive accessory 1LD0411
7.
Max. speed for drive accessory 1LD0412.
1
BHP
2
W
K
18 Unitary Products Group
Page 19
550.13-TG2Y (1001)
FIGURE 10 : BLOWER CURVE LEU600
Unitary Products Group 19
Page 20
yrig
GUIDE SPECIFICATIONS
y
g
gaug
g
y
g
y
g
y
y
g
EACH UNIT SHALL BE:
• Covered by a 1-year limited parts warranty on the com- plete unit.
• In current production with published literature available to check performance, limitations, specific ations, power requirements, dimensions, operation and appearance, and
• Equipped with a V-belt drive that: a. Is rated at least 25% above the required HP.
b. Will permit the blower RPM to be adjusted to meet
the exact CFM requirement of the s
stem.
EACH UNIT ENCLOSURE SHALL HAVE:
• A steel angle frame to provide the rigid support required for shippin
• Exterior panels of 18 enamel to provide a lon
• Removable panels to provide ea s components for maintenance and service, and,
• A filter rack with 1” filters.
, rigging and years of dependable operation.
e steel, finished with baked
lasting quality appearance
access to the intern al
THE DIMENSIONS OF EACH UNIT SHALL NOT EXCEED THOSE SPECIFIED.
THE BLOWER MOTOR SHALL:
• Be mounted within the insulated cabinet to minimize the transmission of sound to the surroundin
• Have a service factor of 1.15
space, and
THE EVAPORATOR COIL SHA LL:
• Consist of copper tubes arranged in staggered rows, mechanicall
• Be draw-throu
• Include factor
and solenoid valves for both capacit pumpdown.
expanded into aluminum fins,
h, and
-mounted distributors, expansion valves reduction and
THE BLOWER WHEELS SHALL
• Be dynamically balanced to mini mize the l evels of sound and vibration
enerated by the unit
Subject to change without notice. Printed in U.S.A. Cop