The LEU line is a flexible performer. LEU360 and 480 can
be position in up to 12 different positi ons and suspended in
various positions. The LEU600 can be position in up to 7
different arran
will
ive you the power to condition large amounts of build-
space and the ability to conform to almost any situation.
in
ements and suspended also. The LEU line
FEATURING
•PART LOAD OPERATION
•EASE OF SERVICE
•NON-RECYCLING PUMPDOWN
•BASE SECTIONS (30 and 40 ton onl
•SUSPENSION PACKAGES
•HOT WATER COILS
•STEAM COILS (LEU360 onl
•WIDE RANGE OF BLOWER MOTORS
•A VARIETY OF DRIVE PACKAGES
)
)
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
Evaporator blower units are designed with two distinct modules to provide max im um ap pli ca tio n fl ex ibi lit
ton units are shipped as sin
module mounted on top of the coil module, The blower module can be repositioned in the field to meet almost an
lation requirement. Blower and coil modules for the 50 ton
units are shipped separate ly to simplify handling. These modules can be connected in the field with the same flexibilit
the smaller units.
The blower module includes the blower wheels and room for
a field-mounted motor and drive. The coil module includes
direct expansion coils, 1 in. throwawa
noid valves for both capacit
mal expansion valves, distributors and a condensate drain
pan.
Every evaporator coil is pressurized with air to 325 psig and
leak tested under water. After the headers are brazed onto
the coil and the coil is installed in the unit, the coil is pressurized with a combination of refri
for pressu re t e sting and addit i onal l e ak t e sti ng. After the
psi
coil is evacuated and deh
holdin
charge of refrigerant-22 for storage and/or shipping.
Steam coils, hot water coils, base sections, suspension hardware, blower motors and drive packa
field-installed accessories to provide additional application
flexibilit
These evaporator blowers, combined with condensing units,
provide
These units are manufactured under ISO 9001 Qualit
tem Certification.
.
ears of quiet, efficient and dependable operation.
le packages with the blower
reduction and pumpdown, ther-
erant-22 and nitrogen to 150
drated, it is pressurized with a
. The 30 and 40
instal-
as
filters, liquid line sole-
es are available as
Units ma
can be arran
ments. Each unit is available with a choice of blower motors,
drive packages and other accessories to make them suitable
for most applications.
be bottom-supported or ceiling-suspended and
ed to meet almost any space or duct r equire-
FACTORY-MOUNTED COMPONENTS
PART LOAD OPERATION These evaporator blowers have
multiple coils with pre-piped distributors, expansion valves
and solenoid valves. Field modifications are not required for
part load operations. Capacit
economical operation, but also maintains more even temperature and humidit
EASY SERVICE Serviceable expansion valves are provided
on ever
provide man
required, it is not necessar
PUMPDOWN Evaporator blowers include a solenoid valve
for non-rec
in the conditioned space is satisfied, the refri
pumped into the hi
unit. These superior valves are factory-installed to
levels in the conditioned space.
ears of trouble-free operation. If service is
cling pumpdown. When the cooling requirem ent
h side of the system.
reduction not only provides
to unbraze any joints.
ACCESSORIES
BASE SECTIONS (30 and 40 ton only) Base sections can
used to elevate units above the floor. If desired, outdoor air
may be introduced through these sections by cutting an
access openin
nection. These bases have a durable finish to match the
s-
evaporator blower unit. The
certain applications.
to accommodate the outdoor air duct con-
may have to be insulated for
erant is
MODULAR DESIGN
These evaporator blo wers can be ar ranged for a variety of air
dischar
tion.
FIGURE 1 : UNIT INSTALLATION
The above illustration shows three of the common installation
arran
other possibilities.
Unitary Products Group3
e patterns in either the horizontal or the vertical posi-
ements. Refer to the unit installation instructions for
SUSPENSION PACKAGES These accessories can be used
to suspend horizontal units from above without interferin
with access to the unit. They can also be used for elevating a
floor-mounted unit (either horizontal or vertical) to provide
additional hei
sate drain connection. All suspension packa
with vibration isolators.
HOT WATER COILS Drainable water coils are available for
field installation between the blower and the coil modules of
both horizontal and vertical units. Since their casin
the dimensions and the finish of the basic units, the
an inte
of their casin
that have been mechanicall
Both headers are located on the same end of the coil. Coils
are leak-tested at 325 psi
connections are capped for st ora
STEAM COILS (LEU360 onl
the LEU360 for installation between the blower and coil mod-
ht for the installation of a trap at the conden-
es can be used
s match
become
ral part of the unit afte r installation. The co ils s lid e o ut
s for easy installation. Coils have copper tubes
expanded into aluminum fins.
under water and dried befor e the ir
e and shipping.
) A steam coil is available on
Page 4
550.13-TG2Y (799)
g
g
g
g
y
g
g
y
y
g
y
g
y
y
g
g
y
y
ules of both horizontal and vertical units. Since the casin
matches the dimensions and the finish of the basic unit, it
becomes an inte
slides out of the casin
the casin
copper tubes that h ave been m echa nical l
ral part of the unit after installation. The coil
s for easy installation and is pitched in
s to facilitate condensate drainage. The coil has
expanded into aluminum fins. Both headers are located on the same end of the
coil. The coil is leak-tested at 325 psi
connections are capped for stora
and dried before the
e and shipping.
DRIVE P ACKAGES Diff erent size pul le
able for each unit to provide a blower RPM ran
almost an
s can be adjusted to provide the proper blower RPM. All
le
drive packa
ratin
of the bl ower m otor. Two-groove pulleys and two belts
are provided on ever
above.
STARTERS AND HEATER ELEMENTS (50 ton onl
BLOWER MOTORS Different HP motors are available for
each unit to meet almost an
motors are UL approved, have permanentl
s and are field-mo unt ed within the ins ulate d cabi net of
bearin
air delivery requirement. All
lubricated ball
blower mot ors that are av ailable for t he 50 ton uni ts do not
have inher ent prot ect ion a nd re qui re e xte rnal moto r ov erl oad
protection.
the units to minimize the transmission of sound to the surrounding space. All motors have inherent protection except
those available for the 50 ton unit. Motors for 50 ton units
require a starter and overload elements
TABLE 1: STATIC RESISTANCES FOR UNIT ACCESSORIES
UNIT MODELACCESSORYCFM
10,00011,00012,00013,00014,000
LEU360
LEU480
LEU600
Hot Water Coil0.080.090.100.120.14
Steam Coil0.170.200.230.270.31
12,80014,40016,00017,60019,200
Hot Water Coil0.110.130.150.170.20
16,00018,00020,00022,00024,000
Hot Water Coil0.150.180.210.240.28
s and belts are avai l-
e to meet
air delivery requirement. Variable pitch motor pul-
es are rated at least 25% above the nominal HP
drive package rated at 5 HP and
) The
4Unitary Products Group
Page 5
TABLE 2: UNIT BLOWER MOTOR DATA
UNIT
MODEL
HP
5
2LR04605023
2LR04605032230/460
2LR04607523
LEU360
7-1/2
2LR04607532230/460
2LP04610033
10
2LR04610032230/460
2LR04607523
7-1/2
2LR04607532230/460
LEU480
2LP04610033
10
2LR04610032230/460
2LP04610017
10
LEU600
2LP04610032230/460
2LP04615017
15
2LP04615032230/460
1.
All motors are 1750 RPM and have a 1.15 service factor. All motors have inherent protection and permanently lubricated ball bearings, except the motors for
the LEU600. These motors require external protection
(starter with overloads and periodic lubrication). All
motors have a solid base.
BLOWER MOTOR DATA
MODEL
#
FRAME
SIZE
184
213
215
213
215
215
254
1
V
OLTAGE
(3PH-60HZ)
208
208
200/208
208
200/208
200
200
550.13-TG2Y (1001)
TABLE 3: UNIT DRIVE DATA
UNIT
MODEL
LEU360
LEU480
LEU600
1.
The drive package includes a bushing for the blower pulley.
10HP motor @ 200 volts
or
15 HP motor @ 200 or 230 volts
10HP motor @ 230 or 460 volts
or
15 HP motor @ 460 volts
2MS04700100
(60 AMP)
2MS04700200
(30 AMP)
DO NOT OPERATE THE SUPPLY AIR BLOWER
MOTOR ABOVE ITS NOMINAL HP RATING
WHEN A UNIT IS EQUIPPED WITH A HOT
WATER COIL ACCESSORY. DO NOT USE
STEAM IN HOT WATER Coils.
DO NOT OPERATE THE SUPPLY AIR BLOWER
ABOVE ITS NOMINAL HP RATING WHEN A
UNIT IS EQUIPPED WITH A STEAM COIL
ACCESSORY.
ALTHOUGH THESE COILS ARE SUITABLE OF
A MUCH HIGHER PRESSURE, STEAM ABOVE
25 PSIG PROVIDES TOO MUCH HEAT THAT
COULD DAMAGE THE BLOWER MOTOR.
TABLE 6: HOT WATER COIL HEATING CAPACITIES1.
HOT WATER
COIL MODEL
1HW0406
1HW0407
1.
These capacities do not include any blower motor heat.
Unit resistance is based on a wet evaporator coil and clean filters.
2.
Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to
the blower motor and drive table and the accessory static resistance table for additional information.
3.
Motors can be selected to operate into the service factor because they are located in the moving air stream, upstream of any heating device. units with steam or hot water coils are the only exception. On these units, the BHP must not exceed the nominal HP
rating of the motor.
Unit resistance is based on a wet evaporator coil and clean filters.
2.
Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to the
blower motor and drive table and the accessory static resistance table for additional information.
Unit resistance is based on a wet evaporator coil and clean filters.
2.
Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to the
blower motor and drive table and the accessory static resistance table for additional information.
3.
Motors can be selected to operate into the service factor because they are located in the moving air stream, upstream of any heating device. Units with steam or hot water coils are the only exception. On theses units, the BHP must not exceed the nominal HP
rating of the motor.
4.
Min. speed for drive accessory 1LD0411.
5.
Min. speed for drive accessory 1LD0412.
6.
Max. speed for drive accessory 1LD0411
7.
Max. speed for drive accessory 1LD0412.
1
BHP
2
W
K
18Unitary Products Group
Page 19
550.13-TG2Y (1001)
FIGURE 10 : BLOWER CURVE LEU600
Unitary Products Group19
Page 20
yrig
GUIDE SPECIFICATIONS
y
g
gaug
g
y
g
y
g
y
y
g
EACH UNIT SHALL BE:
•Covered by a 1-year limited parts warranty on the com-
plete unit.
•In current production with published literature available
to check performance, limitations, specific ations, power
requirements, dimensions, operation and appearance,
and
•Equipped with a V-belt drive that:
a.Is rated at least 25% above the required HP.
b.Will permit the blower RPM to be adjusted to meet
the exact CFM requirement of the s
stem.
EACH UNIT ENCLOSURE SHALL HAVE:
•A steel angle frame to provide the rigid support required
for shippin
•Exterior panels of 18
enamel to provide a lon
•Removable panels to provide ea s
components for maintenance and service, and,
•A filter rack with 1” filters.
, rigging and years of dependable operation.
e steel, finished with baked
lasting quality appearance
access to the intern al
THE DIMENSIONS OF EACH UNIT SHALL NOT
EXCEED THOSE SPECIFIED.
THE BLOWER MOTOR SHALL:
•Be mounted within the insulated cabinet to minimize the
transmission of sound to the surroundin
•Have a service factor of 1.15
space, and
THE EVAPORATOR COIL SHA LL:
•Consist of copper tubes arranged in staggered rows,
mechanicall
•Be draw-throu
•Include factor
and solenoid valves for both capacit
pumpdown.
expanded into aluminum fins,
h, and
-mounted distributors, expansion valves
reduction and
THE BLOWER WHEELS SHALL
•Be dynamically balanced to mini mize the l evels of sound
and vibration
enerated by the unit
Subject to change without notice. Printed in U.S.A.