035-17392-000 REV. A (0401)
SUPPLEMENTAL INSTALLATION INSTRUCTIONS
MODEL H4CE180A40 (380V-3-60 Hz Electrical Supply)
SPLIT-SYSTEM CONDENSING UNITS (EXPORT)
Scope
This installation Instruction Supplement provides information specific to Model H4CE180A40. For all other
information regarding the installation and operation of this unit, refer to Installation Instruction Form 035-17384-000.
Approvals
As unit is for Export, it is not certified by ETL or CGA.
TABLE 3: Electrical Data
Model
Voltage
HCE
180 40 380-3-60 16.7 123 16.7 123 1.0 EA. 2.5 EA. 42.6 50
Code
Power
Supply
RLA LRA RLA LRA
Compressor Condensing Fan
Sys. #1 Sys. #2
HP FLA (See Notes)
Minimum Circuit Ampacity
Maximum Fuse Size.
Amps (See Note 2)
NOTES:1. Condenser Fan Motors are supplied by one (1) autotransformer (p/n 025-32756-000) used to elevate
380 volt supply to 475 volt. Full load Amp rating at 460-3-60 supply is 2.4 amp rating at 380 volt supply
terminals of autotransformer is 2.6.
2. Dual Element time delay type fuses or HACR circuit breakers. Refer to NEC/NFPA No. 70,
Articles 440-11 & 12 for information on disconnect size.
®
Subject to change without notice. Printed in U.S.A. 035-17392-000 REV. A (0401)
Copyright © by Unitary Products Group2000. Allrights reserved. Supersedes: 035-17318-000 Rev.A (10/00)