York G8C, GF8 User Manual

Page 1
USER’S INFORMATION, MAINTENANCE AND
EFFICIENCY RATING CERTIFIED
SERVICE MANUAL
MODELS: G8C/ GF8 (Single Stage Multi-Position)
CONTACT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
TABLE OF CONTENTS
USER’S INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
DESCRIPTION (50-125 MBH INPUT MODELS) . . . . . . . . . . . . . . .2
DESCRIPTION (150 MBH INPUT MODELS) . . . . . . . . . . . . . . . . . . 2
INSTRUCTIONS FOR EXAMINING THE FURNACE
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
HOW YOUR GAS FURNACE WORKS . . . . . . . . . . . . . . . . . . . . . . 4
START-UP AND SHUTDOWN INSTRUCTIONS . . . . . . . . . . . . . . .4
Read the Instructions Below Before Trying to Start the Furnace . . 4
Operating Instructions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
To Turn Off the Appliance: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
FURNACE USER MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . .4
Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Removing Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Blower Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Motor Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
SERVICE AND MAINTENANCE MANUAL . . . . . . . . . . . . . . . . . . . . 6
CONTACT INFORMATION
• Go to website at www.york.com click on “contact”, then click on “contact form” and follow the instructions.
• Contact us by mail:
York International
Consumer Relations
Norman, OK 73069
SAFETY SECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
FURNACE MAINTENANCE SECTION . . . . . . . . . . . . . . . . . . . . . . .6
FURNACE CLEANING SECTION . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Burner Removal/Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Cleaning the Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Continuous Blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Intermittent Blower - Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Heating Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Hot Surface Ignition System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
FURNACE CONTROL DIAGNOSTICS . . . . . . . . . . . . . . . . . . . . . . .8
REPLACEMENT PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
FIELD INSTALLED ACCESSORIES - NON-ELECTRICAL . . . . . .11
REPLACEMENT PART CONTACT INFORMATION . . . . . . . . . . . . .11
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
LIMITED WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
5005 York Drive
This product was manufactured in a plant whose quality system is certified/registered as being in conformity with ISO 9001.
The manufacturer recommends that the user read all sec­tions of this manual and keep the manual for future refer­ence.
FIRE OR EXPLOSION HAZARD - Failure to follow safety
warnings exactly could result in serious injury, death, or prop­erty damage.
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone (including cell phone) in your building.
Leave the building immedia te l y.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire depart­ment.
Installation and service must be performed by a quali-
fied installer, service agency or the gas supplier.
SECTION I: USER’S INFORMATION
SAFETY
1. The furnace area must be kept clear and free of combustible mate­rials, gasoline and other flammable vapors and liquids.
2. Insulating materials may be combustible. The furnace must be kept free and clear of insulating materials. The furnace area must be examined when installed in an attic or other insulated space or when insulation is added to be sure that the insulation material has been kept away from the furnace.
3. The furnace needs air for combustion in order to operate properly and safely. Do not block or obstruct air openings on the furnace, air openings to the area where the furnace is installed, or spaces around the furnace.
4. Follow the instructions exactly as shown on the OPERATING INSTRUCTION LABEL or the Start-up and Shutdown Instructions on Page 4 of this manual when lighting the furnace or turning the furnace off.
5. Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off the electrical supply.
6. Do not use this furnace if any part has been under water. A flood­damaged furnace is extremely dangerous. Attempts to use the fur­nace can result in fire or explosion. A qualified service agency should be contacted to inspect the furnace and replace all gas controls, control system parts, electrical parts that have been wet or the furnace if deemed necessary.
035-19992-001 Rev. A (0404)
Page 2
035-19992-001 Rev. A (0404)
7. NEVERStore flammable materials of any kind near your fur-
nace. Gasoline, solvents, and other volatile liquids should be stored only in approved containers outside your home. These materials vaporize easily and are extremely dangerous.
8. NEVER
Store cleaning materials near your furnace. Materials
such as bleaches, detergents, powdered cleansers, etc., can cause corrosion of the heat exchangers.
9. NEVER
Use the area around your furnace as a storage area for
items which could block the normal flow of air. This flow of air is required for ventilation of the various furnace components.
FIRE OR EXPLOSION HAZARD This furnace is designed and approved for use with Nat-
ural Gas and (LP) Propane Gas ONLY. DO NOT BURN ANY LIQUID FUEL OR SOLID FUEL IN THIS FURNACE.
Burning any unapproved fuel will result in damage to the furnace heat exchanger, which could result in Fire, Per­sonal Injury, and/or Property Damage.
DESCRIPTION (50-125 MBH INPUT MODELS)
This furnace can be installed in the upflow, downflow, or horizontal left or right position. Figure 2 shows a typical model in the downflow posi­tion and Figure 1 shows a typical model in the upflow position. The fur­nace may also lie on either side in a horizontal position. The furnace is equipped with an induced-draft vent blower and atmospheric burners. Combustion air is taken from the space or area in which the furnace is installed and drawn into the burners through the louvers in the front panel. Flue gas is drawn from the heat exchanger by the vent blower and discharged through the flue pipe to the outside atmosphere.
This is a forced air furnace. The furnace circulating air blower draws cool air from the house, passes it over the hot furnace heat exchanger and circulates the warmed air through the ductwork to the house.
The furnace is equipped with the controls necessary for proper opera­tion. The various components referred to in this manual and on the fur­nace nameplate are identified in Figures 1, 2 & 3.
FURNACE CONTROL
BLOWER DOOR SWITCH
ROLL-OUT SWITCHES
BURNERS
HOT SURFACE IGNITOR
GAS VALV E
PRESSURE SWITCH
VENT
VENT PIPE TRANSITION
3” DIAMETER VENT PIPE
ROLL-OUT SWITCH
VENT BLOWER
FIGURE 2: Component Locations - Downflow (50 - 125 MBH Models)
DESCRIPTION (150 MBH INPUT MODELS)
This furnace can be installed in the upflow or horizontal left or right posi­tion. Figure 3 shows the 150 MBH input model. The furnace may also lie on either side in a horizontal position. This furnace is not approved to be installed in a downflow application. The furnace is equipped with an induced-draft vent blower and atmospheric burners. Combustion air is taken from the space or area in which the furnace is installed and drawn into the burners through the louvers in the front panel. Flue gas is drawn from the heat exchanger by the vent blower and discharged through the flue pipe to the outside atmosphere.
This is a forced air furnace. The furnace circulating air blower draws cool air from the house, passes it over the hot furnace heat exchanger and circulates the warmed air through the ductwork to the house.
The furnace is equipped with the controls necessary for proper opera­tion. The various components referred to in this manual and on the fur­nace nameplate are identified in Figure 3.
PRESSURE SWITCH
GAS VALV E
HOT SURFACE IGNITOR
BURNERS
BLOWER DOOR SWITCH
FURNACE CONTROL
VENT BLOWER
DIRT LEG
ROLL-OUT SWITCH
PRESSURE SWITCH
GAS VALV E
HOT SURFACE IGNITOR
BURNERS
ROLL-OUT SWITCHES
BLOWER DOOR SWITCH
FURNACE CONTROL
VENT BLOWER
ROLL-OUT SWITCH
ROLL-OUT SWITCHES
FIGURE 3: Component Locations - Upflow (150 MBH Models)
FIGURE 1: Component Locations - Upflow (50 - 125 MBH Models)
2 Unitary Products Group
Page 3
035-19992-001 Rev. A (0404)
INSTRUCTIONS FOR EXAMINING THE FURNACE INSTALLATION
It is the owner’s responsibility to ensure that an annual inspection of the entire heating portion of the unit is made by a qualified service agency. Examine the furnace as outlined below in steps “1 - 6” before each heating season. Use Figures 5 & 6 for visual reference.
1. Examine the heat exchanger, vent/combustion air piping, vent connectors and chimney to be sure they are clear and free of obstructions.
2. Examine the vent pipe making sure it is firmly in place, that it slopes slightly upward and is physically sound without holes and all of the connections are secure.
3. Examine the return-air duct connections to make sure they are physically sound, sealed to the furnace casing, and the ducts ter­minate outside the space containing the furnace.
4. Examine the furnace casing making sure the physical support is sound without sagging, cracks or gaps. Examine the furnace base making sure it is physically sound without cracks, gaps or sagging and has a good seal.
EXAMINE ENTIRE
5
FURNACE CASING SHOWN IN ALL DRAWINGS
6
REMOVE PANEL TO EXAMINE BURNER FLAMES
4
EXAMINE FURNACE CASING
EXAMINE EXTERNAL VENT PIPE
5. Examine the furnace casing for obvious signs of deterioration.
6. Examine the burner flames to make sure they are in good adjust­ment. Refer to the pictorial sketch shown in Figure 4 as a compar­ison to the actual flame.
BLUE CONE PORTION OF FLAME SHOULD ENTER HEAT EXCHANGER TUBE
FIGURE 4: Burner Flame Drawing
1
EXTERNAL HEAT EXCHANGER INTERNAL
VENT COMBUSTION AIR PIPE. MUST
REMOVE PANEL TO EXAMINE.
6
REMOVE PANEL TO EXAMINE BURNER FLAMES
4
EXAMINE FURNACE CASING
3
EXAMINE RETURN AIR DUCT CONNECTION
FIGURE 5: Furnace Examination Checkpoints - Upflow
3
EXAMINE RETURN AIR DUCT CONNECTION
4
EXAMINE FURNACE CASING
EXAMINE EXTERNAL VENT PIPE
5
EXAMINE ENTIRE FURNACE CASING SHOWN IN ALL DRAWINGS
6
REMOVE PANEL TO EXAMINE BURNER FLAMES
FIGURE 6: Furnace Examination Checkpoints - Downflow
3
EXAMINE RETURN AIR DUCT CONNECTION
1
EXTERNAL HEAT EXCHANGER INTERNAL
VENT COMBUSTION AIR PIPE. MUST
REMOVE PANEL TO EXAMINE.
6
REMOVE PANEL TO EXAMINE BURNER FLAMES
3
EXAMINE RETURN AIR DUCT CONNECTION
4
EXAMINE FURNACE CASING
Unitary Products Group 3
Page 4
035-19992-001 Rev. A (0404)
HOW YOUR GAS FURNACE WORKS
Your furnace is a very easy appliance to take for granted. Season after season, it sits there in your home, keeping you warm and comfortable. For this reason, you may never have given much thought to the way your furnace operates. In order to get the safest and most efficient oper­ation from your furnace, you should understand how your furnace does its job.
When you set your thermostat to provide more heat in your home, you are starting the heating cycle of the furnace. First, the inducer motor starts to purge the heat exchanger of any remaining gases. Next, the hot surface ignitor glows and after a warm-up period the gas valve opens and ignition occurs. A short time later, the blower starts and dis­tributes the warm air throughout the home. When the temperature set­ting on your thermostat is reached, the gas valve closes, the main burners are turned off, and the blower continues to run until the remain­ing warm air in the system is distributed. When the blower stops, the heating cycle has ended.
START-UP AND SHUTDOWN INSTRUCTIONS
Read the Instructions Below Before Trying to Start the Furnace
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, and/or loss of life.
A. This appliance does not have a pilot. It is equipped with an ignition
device which automatically lights the burner. Do not try to light the burner by hand.
B. BEFORE OPERATING; smell all around the appliance area for
gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
C. Use only your hand to push the gas control switch to the “on” posi-
tion. Never use tools. If the switch will not operate by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Imme-
diately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control, which has been under water.
Operating Instructions:
1. STOP! Read the safety information above.
2. Set the thermostat to the lowest setting.
3. Turn off all electric power to the appliance.
4. Remove burner door.
5. Move gas control switch to the “OFF” position. Do not force.
6. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow “B” in the safety information above. If you don’t smell gas, go to next step.
7. Move gas control switch to the “ON” position. Do not force.
8. Replace burner door.
9. Turn on all electric power to the appliance.
10. Set thermostat to the desired setting. Burner will light, which may take 30-60 seconds.
11. After three (3) trials for ignition, if the appliance will not operate fol­low the instructions, “TO TURN OFF THE APPLIANCE” and call your service technician or gas supplier.
To Turn Off the Appliance:
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be per­formed.
3. Remove burner access panel.
4. Move gas control switch to the “OFF” position.
5. Replace burner access panel.
Should overheating occur, or the gas valve fail to shut off, turn the external manual gas valve in the gas supply line to the furnace to the “off” position and let the furnace cool off before shutting off the electrical power supply. Refer to Figure 8.
OUTLET PRESSURE PORT
INLET
WRENCH BOSS
INLET PRESSURE PORT
OFF
ON
ON/OFF SWITCH (Shown in ON position)
VENT PORT
OUTLET
MAIN REGULATOR ADJUSTMENT
FIGURE 7: Gas Valve - White Rodgers
EXTERNAL MANUAL SHUTOFF VALVE
TO GAS SUPPLY
DRIP LEG
TO GAS SUPPLY
GROUNDED JOINT UNION MAY BE INSTALLED INSIDE OR OUTSIDE UNIT.
FIGURE 8: Gas Piping NOTE: The spring-loaded safety cut-off switch, mounted under the
blower deck will automatically cut off the electrical power supply to the furnace when the blower panel is removed. As a safety precaution, all electrical power and the gas supply to the furnace should be turned off before servicing.
FURNACE USER MAINTENANCE
Before proceeding, be sure the area is well ventilated. Turn the thermostat OFF. If the blower is running, wait until it stops automatically. Turn OFF the gas and electrical power supplies to the furnace. Check all metal parts and surfaces to be sure they have cooled to room temperature before you begin.
Every time the filters are changed the following items should be visually inspected:
• Check combustion air and vent pipe for blockage or leakage.
• Check all components to be sure they are in good condition and that there are no obvious signs of deterioration.
• Check the drain lines to make sure there are no cracks or leaks.
• Check for dirt or lint on any surfaces or on components. Do not try to clean any of the surfaces or components. Cleaning of the fur­nace and its components must be done by a qualified service pro­fessional.
4 Unitary Products Group
Page 5
035-19992-001 Rev. A (0404)
If, during the inspection of your furnace, you find any of the following conditions:
• Excessive amounts of dust and lint on components.
• Damaged or deteriorated components or surfaces.
• Leaks or blockage in the vent pipe passages.
• Water on any surface inside or outside of the furnace.
Do not operate the furnace, call a certified dealer / servicing contractor to check and / or clean your furnace, or for more information if you have questions about the operation of your furnace.
If all components appear to be in good operating condition, replace the front panels. Turn ON the gas and electrical power supplies to the fur­nace, and set thermostat to the desired temperature.
Air Filters
Dirty filters greatly restrict the flow of air and may cause damage to the moving parts of the furnace. If the filters become clogged the heat exchangers and blower motor could overheat resulting in a potentially dangerous situation.
The filters should be checked every 3 months. On new construction, check the filters every week for the first four weeks and every three weeks after that, especially if the indoor fan is running continuously. When replacing the filter(s) you must use filters that are the same size as those recommended in Table 1. Use the following procedure to determine the filter size. Never operate your furnace without a suitable air filter.
1. Measure the furnace width. Use the following measurements to determine the cabinet size.
• A 17-1/2” wide cabinet is a “B” cabinet.
• A 21” wide cabinet is a “C” cabinet.
• A 24-1/2” wide cabinet is a “D” cabinet.
2. Locate the cabinet size on Table 1, then determine whether you have a bottom, side or top return using the following method.
a. If the return air filters are on the left or right side of the fur-
nace it is a side return. Refer to Figure 11.
b. If the air filter is on the bottom of the furnace then you have a
bottom return. Refer to Figure 12 or for horizontal applica­tions refer to Figure 9.
c. If the air filters are on the bottom an d the side of the furnace
then you have a bottom and side return. You must replace both air filters. Brackets with the number two (2) before the fil­ter size requires 2 filters. Refer to Figures 11 & 12.
d. If the air filters are on both sides of the furnace then you have
a (2) sided return. You must replace both air filters.
e. If the air filters are in the return air plenum, above the furnace
then you have a top return (Downflow Furnace). Refer to Fig­ure 10.
3. After you determine the cabinet size and what return configuration you have, look up the recommended filter size from Table 1. You must replace the air filters with the same size as recommended.
Removing Filters
Externally Mounted Air Filters
The air filter is in a rack that is attached to the casing of the furnace or placed in the return air duct. Figures 9, 10, 11 & 12 indicate possible external air filter box locations.
AIR FILTER RACK
ACCESS DOOR
FILTER
FURNACE
RACK
18” MIN
AIR FLOW
FIGURE 9: External Air Filter Rack - Horizontal Left Position
AIR FLOW
DUCTWORK
NOTE: FILTER ACCESS THROUGH DUCTWORK MUST BE PROVIDED FOR REMOVAL AND CLEANING
FILTER RACK (factory supplied with some furnaces)
RACK AND FILTERS SECURED INSIDE BLOWER SECTION FOR SHIPMENT
CASING SIZE
16-1/4” 22-1/4” 26-1/4”
FILTERS
FILTER RACK
CROSS SECTION A-A
(with Plenum and filters)
DIMENSION FH
12-3/4”
11”
8-1/4”
BRANCH DUCTS
FH
FIGURE 10: Downflow Filter
AIR FILTER RACK ACCESS DOOR
DUCT
RIGHT SIDE FILTER RACK
AIR FLOW
AIR FLOW
AIR FILTER RACK ACCESS DOOR
DUCT
LEFT SIDE FILTER RACK
FURNACE
FIGURE 11: External Air Filter Rack - Left & Right Side Position
FURNACE
AIR FILTER RACK
ACCESS DOOR
AIR FLOW
BOTTOM FILTER RACK
DUCT
FIGURE 12: External Air Filter Rack - Bottom Position
Unitary Products Group 5
Page 6
035-19992-001 Rev. A (0404)
To remove the filter you must do the following:
1. Before proceeding, be sure the area is well ventilated. Follow instruction “To turn off the appliance”. Check all metal parts and surfaces to be sure they have cooled to room temperature before you begin.
2. Remove the door by removing the retaining screw(s), if provided.
3. Remove the air filter by pulling on it. The air filter will slide out of the rack.
4. Replace throw away filter(s)) with the same size new filter(s). Throw away filter(s)) may be replaced with cleanable filter(s) at this time. Cleanable filter(s) may be cleaned as described in the manufacturer instructions or as described in these instructions.
To replace the filter after cleaning you must do the following:
5. Slide filter into place. If the filter has been cleaned, make sure it is dry before re-installing it.
6. Replace the door or cover panel and tighten the retaining screws, if provided.
7. Make sure the door is secure to the end of the filter rack and sealed to prevent leaks.
8. Follow the Operating Instructions to place the furnace back in operation.
TABLE 1:
Filter Sizes
Make sure you DO NOT move the clip on weight on the indoor fan wheel when cleaning the wheel. This weight is used to balance the wheel. Moving the weight will cause the fan wheel to vibrate.
Motor Lubrication
The motors in these furnaces are permanently lubricated, and do not require periodic oiling.
SECTION II: SERVICE AND MAINTENANCE MANUAL
SAFETY SECTION
This section has been designed to assist a qualified service agency in performing service and maintenance on this appliance. The homeown­ers and/or end user must never attempt to perform any service or main­tenance on the appliance especially when it involves the removal or adjustment of any parts and/or components.
The following safety rules must be followed when servicing the furnace.
Cabinet
Size
B 25 x 16 64 x 41 24 x 15 61 x 38 B 25 x 16 64 x 41 24 x 15 61 x 38 C 25 x 16 64 x 41 24 x 15 61 x 38 C 25 x 16 64 x 41 24 x 15 61 x 38 D (2) 25 x 16 (2) 64 x 41 24 x 21 61 x 53 D (2) 25 x 16 (2) 64 x 41 24 x 21 61 x 53 D (2) 25 x 16 (2) 64 x 41 24 x 21 61 x 53
Cabinet
Size
B 14 x 20 (2) 25 x 51 (2) 10 x 20 (2) 25 x 51 B 14 x 20 (2) 25 x 51 (2) 10 x 20 (2) 25 x 51 C 16 x 20 (2) 41 x 51 (2) 16 x 20 (2) 41 x 51 C 16 x 20 (2) 41 x 51 (2) 16 x 20 (2) 41 x 51 D 20 x 20 (2) 51 x 51 (2) 20 x 20 (2) 51 x 51 D 20 x 20 (2) 51 x 51 (2) 20 x 20 (2) 51 x 51 D N/A N/A N/A N/A
Side Return Bottom/End Return
in. cm in. cm
Top Return (Downflow)
Cleanable Air Filters
in. cm in. cm
Top Return (Downflow)
Disposable Air Filters
How to Clean your Filter
High-velocity filters may be cleaned with a vacuum cleaner or washed with a garden hose. Be sure to shake off excess water and allow filter to completely dry before re-installing the filter.
Blower Care
Even with good filters properly in place, blower wheels and motors will become dust laden after long months of operation. The entire blower assembly should be inspected annually. If the motor and wheel are heavily coated with dust, they can be brushed and cleaned with a vac­uum cleaner. If the blower cannot be properly cleaned without removing it from the furnace, then call a qualified service agency. Only a qualified service agency can perform this service.
ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in
dangerous operation, serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury, and death or property damage.
• Before servicing, disconnect all electrical power to the fur­nace.
• When servicing controls, label all wires prior to discon­necting. Reconnect wires correctly.
• Verify proper operation after servicing.
FURNACE MAINTENANCE SECTION
The furnace should be cleaned and adjusted by a certified dealer or qualified service contractor once a year or before the start of every heating season. The following items must be cleaned and serviced or replaced if there are signs of deterioration.
1. The vent terminal screen (if applicable).
2. The furnace vent and combustion air intake passageways. Should it be necessary to service the vent/air intake system, the manufac­turer recommends this service be conducted by a qualified service agency. The operation of this appliance requires the reassembly and resealing of the vent/air intake system.
3. The furnace burners, ignitor and flame sensor.
FURNACE CLEANING SECTION
NOTE: The cleaning operations listed below must be performed only by
a qualified service agency.
Burner Removal/Cleaning
The main burners should be checked periodically for dirt accumulation. If cleaning is required, follow this procedure:
1. Turn off the electrical power to the unit.
2. Turn off the gas supply at the external manual shut-off valve and loosen the ground union joint.
3. Remove the upper access panel.
6 Unitary Products Group
Page 7
035-19992-001 Rev. A (0404)
4. Disconnect wires from flame sensor, rollout switch and HSI ignitor. Remove ignitor carefully, as it is easily broken.
5. Remove the screws that hold the burner box assembly to the vest panel and remove the assembly.
6. Remove burners from the burner assembly.
7. Rinsing in hot water may clean burners.
8. Reassemble in the reverse order.
Cleaning the Heat Exchanger
NOTE: It is recommended that replacement gaskets be available
before removing vent motor.
Lower Heat Exchanger Access
1. Turn off the electrical power to the unit and turn off gas supply at the shutoff valve.
2. Remove the blower and burner compartment access doors. Dis­connect the gas supply piping at the union to permit removal of the entire burner and gas control assembly from the vestibule panel. Use the wrench boss on the gas valve when removing or installing this piping.
3. Unplug the ignitor from the wire harness. Disconnect sensor and rollout switch wires located on top of the air shield. Identify and note the location of all leads for ease of reinstallation. Also discon­nect the wires at the side rollout switches (upflow only) and the gas valve wires.
4. Remove the screws holding the burner assembly to the vestibule panel and remove this assembly. Handle the assembly carefully since it contains the ignitor, which is fragile and easily broken. The lower portion of the heat exchanger will now be exposed. With a long flexible wire brush, clean inside of each heat exchanger at both the top and bottom. The brush must pass around the rear heat exchanger to remove any soot and scale. Vacuum loose soot, scale and dirt from each heat exchanger.
5. After cleaning is complete, replace all components in reverse order. Re-gasket all surfaces which required a gasket. Reconnect all wiring. Reattach vent pipe and gas supply lines before restoring service to furnace. Restore electrical power, check gas supply pip­ing for leaks, and then verify furnace operation.
Upper Heat Exchanger Access
1. Perform steps 1 - 4 in cleaning the heat exchanger.
2. Unplug the vent motor wires and ground wire. Remove the pres­sure switch tubing at the tap on the vent motor housing.
3. Disconnect vent piping from the vent motor assembly.
4. Remove the screws that secure the vent motor assembly to the flue box and remove the vent motor assembly. The surface is also gasketed so be extra careful not to tear the gasket.
5. Remove the screws from the flue box that secure the flue box to the vestibule panel and remove the flue box. The surface is also gasketed so be extra careful not to tear the gasket.
6. The upper portion of the heat exchanger is now accessible. With a long flexible wire brush, clean inside of each heat exchanger at both the top and bottom. The brush must pass around the rear heat exchanger to remove any soot and scale. Vacuum loose soot, scale and dirt from each heat exchanger.
7. After cleaning is complete, replace all components in reverse order. Re-gasket all surfaces which required a gasket. Reconnect all wiring. Reattach vent pipe and gas supply lines before restoring service to furnace. Restore electrical power, check gas supply pip­ing for leaks and then verify furnace operation.
Upper Heat Exchanger Access for furnaces converted to Down­flow
1. Perform steps 1 - 4 in cleaning the heat exchanger.
2. Unplug the vent motor wires and ground wire. Remove the pres­sure switch tubing at the tap on the vent motor housing.
3. Disconnect vent piping from the vent motor assembly and remove the flue pipe that extends through the blower access compartment.
4. Remove the screws that secure the vent motor assembly to the flue box and remove the vent motor assembly. The surface is also gasketed so be extra careful not tear the gasket. The assembly may be brushed and vacuumed to remove soot and scale.
5. Follow Steps 4-7 in “Upper heat exchanger access”.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and danger­ous operation. Verify proper operation after servicing.
SEQUENCE OF OPERATION
The following describes the sequence of operation of the furnace. Refer to Figure 1 for component location.
Continuous Blower
Cooling/heating thermostats have a fan switch that has an ON and AUTO position. In the ON position the thermostat circuit is completed between terminals R and G. The motor will operate on the speed tap wire that is connected to the cooling terminal on the control board. To obtain a constant air circulation at lower flow rate, change the high­speed wire to either the medium speed wire or the low speed wire.
Intermittent Blower - Cooling
Cooling/heating thermostats have a fan switch that has an ON and AUTO position. In the AUTO position the thermostat circuit is completed between terminals R and G when there is a call for cooling. The motor will operate on the speed tap wire that is connected to the cooling termi­nal on the control board. The fan off setting is fixed at 60 seconds for SEER enhancement.
Heating Cycle
When the thermostat switch is set on HEAT and the fan is set on AUTO, and there is a call for heat, a circuit is completed between terminals R and W of the thermostat. When the proper amount of combustion air is being provided, the pressure switch will close, the ignition control pro­vides a 17-second warm-up period, the gas valve then opens, the gas starts to flow, ignition occurs and the flame sensor begins its sensing function. The blower motor will energize 30 seconds after the gas valve opens, if a flame is detected. Normal furnace operation will continue until the thermostat circuit between R and W is opened, which causes the ignition system and gas valve to de-energize and the burner flames to be extinguished. The vent motor will operate for 15 seconds and the blower motor will operate for the amount of time set by the fan-off delay jumper located on the control board. See Figure 7. The heating cycle is complete, and ready for the start of the next heating cycle.
Unitary Products Group 7
Page 8
035-19992-001 Rev. A (0404)
COOL
HEAT
PARK
PARK
LINE
XM
FAN OFF ADJUSTMENT SWITCHES
120
60
90
180
FIGURE 13: Typical Heat/Cool Speed Tap Connections If the flame is not detected within 2 seconds of the gas valve opening,
the gas valve is shut off and a retry operation begins. If the flame is lost for 2 seconds during the 10-second stabilization period, the gas valve is shut off and a retry operation begins. During a retry operation, the vent motor starts a 15 second inter-purge and the ignitor warm-up time is extended to 27 seconds. If the flame is established for more than 10 seconds after ignition during a retry, the control will clear the ignition attempt (retry) counter. If three retries occur during a call for heat, the furnace will shut down for one hour. If at the end of the one hour shut down there is a call for heat, the furnace will initiate a normal start cycle. If the problem has not been corrected the furnace will again lockout after three retries.
A momentary loss of gas supply, flame blowout, or a faulty flame probe circuit will result in a disruption in the flame and be sensed within 1.0 seconds. The gas valve will de-energize and the control will begin a recycle operation. A normal ignition sequence will begin after a 15 sec­ond inter-purge. If during the five recycles the gas supply does not return, or the fault condition is not corrected the ignition control will lock­out for 60 minutes.
During burner operation, a momentary loss of power for 50 milliseconds or longer will de-energize the gas valve. When the power is restored, the gas valve will remain de-energized and the ignition sequence will immediately restart.
Hot Surface Ignition System
HOT SURFACE IGNITION SYSTEM Do not attempt to light this furnace by hand (with a
match or any other means). There may be a potential shock hazard from the components of the hot surface ignition system. The furnace can only be lit automatically by its hot surface ignition system.
TROUBLESHOOTING
The following visual checks should be made before troubleshooting:
1. Check to see that the power to the furnace and the ignition control module is ON.
2. The manual shut-off valves in the gas line to the furnace must be open.
3. Make sure all wiring connections are secure.
4. Review the sequence of operation. Start the system by setting the thermostat above the room temperature. Observe the system’s response. Then use the troubleshooting section in this manual to check the system’s operation.
FURNACE CONTROL DIAGNOSTICS
The furnace has built-in, self-diagnostic capability. If a system problem occurs, a blinking red LED shows a fault code. It is located behind a clear view port in the blower compartment door. DO NOT remove the furnace blower compartment panel OR turn off furnace power, as either action will clear the control’s memory of the fault.
The control continuously monitors its own operation and the operation of the system. If a failure occurs, the LED will indicate the failure code. If the failure is internal to the control, the light will stay on continuously. In this case, the entire control should be replaced, as the control is not field repairable.
Flash sequence codes 1 through 11 are as follows: LED will turn “on” for one second and “off” for one second. This pattern will be repeated the number of times equal to the code. For example, six “on” flashes equals a number 6 fault code. All flash code sequences are broken by a 2 sec­ond “off” period.
Never bypass pressure switch to allow furnace opera­tion. To do so will allow furnace to operate under poten­tially hazardous conditions.
Do not try to repair controls. Replace defective con trols with UPG Source 1 Parts.
Never adjust pressure switch to allow furnace operation.
CONTINUOUS FLASH: This indicates that flame was sensed when there was not a call for heat. With this fault code the control will turn on both the inducer motor and supply air blower.
CAUSE: A gas valve that leaks through or is slow closing would typically cause this fault.
2 FLASH: This indicates that the normally open pressure switch con­tacts are stuck in the closed position. The control confirms these con­tacts are open at the beginning of each heat cycle.
CAUSE: This would indicate a faulty pressure switch or miswiring.
3 FLASH: This indicates the normally open pressure switch contact did
not close at the beginning of the heat cycle.
CAUSE: This could be caused by a number of problems, faulty inducer, blocked vent pipe, broken pressure switch hose or faulty
pressure switch.
4 FLASH: This indicates that a primary or auxiliary limit switch has opened its normally closed contacts. With this fault code the control will operate the supply air blower and inducer.
CAUSE: This condition may be caused by: dirty filter, improperly sized duct system, incorrect blower speed setting, incorrect firing rate or faulty blower motor.
5 FLASH: This fault is indicated if the normally closed contacts in the rollout switch opens. The rollout control is manually reset.
CAUSE: If it has opened, check for proper combustion air, proper inducer operation, primary heat exchanger failure or burner prob­lem. Be sure to reset the switch after correcting the failure condi­tion.
8 Unitary Products Group
Page 9
035-19992-001 Rev. A (0404)
6 FLASH: This indicates that after the unit was operating, the pressure switch opened 4 times during the call for heat. If the main blower is in a "Delay on" mode it will complete it, and any subsequent delay off period. The induced draft motor continues to operate until the pressure switch re-closes or a call for heat is removed.
7 FLASH: This fault code indicates that the flame could not be estab­lished. This no-light condition occurred 3 times (2 retries) during the call for heat before locking out.
CAUSE: This may be caused by low gas pressure, faulty gas valve, faulty hot surface ignitor or burner problem.
8 FLASH: This fault is indicated if the flame is lost 5 times (5 recycles) during the heating cycle.
CAUSE: This could be caused by low gas pressure or faulty gas valve.
9 FLASH: Indicates reversed line voltage polarity. Both heating and cooling operations will be affected. Check polarity at furnace and branch.
11 FLASH: This fault will be indicated if the rollout jumper wire connec­tion soldered into the board is broken. If this fault occurs the co ntrol will have to be replaced.
STEADY ON: This fault occurs if the gas valve is energized when there is no call for heat. If this happens the induced draft motor is energized and will remain energized for 5 seconds or until the fault clears itself at which point the induced draft motor de-energizes.
CAUSE: This failure is counted as a recycle. Check the gas valve and control for proper operation.
60-MINUTE AUTOMATIC RESET FROM LOCKOUT: This control includes a "watchdog" type circuit that will reset from a lockout condition after 60 minutes. Operational faults 1,6,7,8 and Steady On will be reset. This provides protection to an unoccupied structure if a temporary con­dition exists causing a furnace malfunction. An example would be a low incoming gas supply pressure preventing unit operation. When the gas pressure is restored, at some point the "watchdog" would restart the unit and provide heat for the house.
IGNITION CONTROL
Normal flame sense current is approximately
3.7 microamps DC (µa)
Low flame signal control lockout point is
0.9 microamps DC (µa)
FIGURE 14: Furnace Control Event Schedule
Unitary Products Group 9
Page 10
035-19992-001 Rev. A (0404)
OFF
ON
SECTION III: REPLACEMENT PARTS LIST
5
29
11
7
8
7
26
1
4
6
4
21
21
9
10
12
13
26
11
2
24
32
23
15
13
21
26
15
15 19
18
17
20
31
F
F
O
N
O
27
22
28
ITEM DESCRIPTION
1 Casing, Top Cap 2 Heat Exchanger Assembly
3* Gasket, Vent Blower
4Blower, Vent 5 Tube, Pressure 6 Switch, Pressure 7 Switch, Roll Out (3 Req’d) 8 Rod, Sensor 9 Ignitor
10 Bracket, Ignitor
Switch, Limit (Open 140 Deg.)
11
Switch, Limit (Open 155 Deg.) 12 Switch, Door 13 Control, Integrated
14* Harness, Wire
15 Transformer (40VA)
Capacitor (7.5MFD, 370V) 16
Capacitor (10MFD, 370V) 17 Wheel, Blower 18 Motor, Blower
NOTE: *Not Shown
Major components and suggested stocking items are shown with shaded item number.
33
ITEM DESCRIPTION
19 Mount, 1-PC. Motor 20 Motor Mounts, Rubber (3 Req’d) 21 Valve, Gas
Orifice, Gas (Natural-0-2,000 Ft.) Orifice, Gas (LP-0-2,000 Ft.) Orifice, Gas
22
(Natural-High Altitude-2,000-5,000 Ft.)
Orifice, Gas (Natural-High Altitude-5,000-7,000 Ft.)
Orifice, Gas (LP-High Altitude-2,000-7,000 Ft.) 23 Burner 24 Panel, Door 25 Casing, Bottom Cap 26 Transition, 3” 27 Blower Assembly 28 Burner Assembly 29 Clip, Door Latch (2 per pkg.)
30* Diagram, Wiring
31 Spacer (Ferrule) (3 Req’d) 32 Wrapper, Casing 33 Manifold, Gas
10 Unitary Products Group
Page 11
FIELD INSTALLED ACCESSORIES - NON-ELECTRICAL
Field Installed Accessories-Non-Electrical
Part Number Description Used With
1FB0318 1FB0319 7516,10016 1FB0320 10020,125 1BR0312 1BR0316 7516,10016 1BR0320 10020,125,150 1NP0366 Conversion Kit-Natural Gas to LP Gas
2802-321P Vent Pipe Extension
Combustible Floor Sub-Base
Bottom Filter Rack
REPLACEMENT PART CONTACT INFORMATION
This is a generic parts list. To request a complete parts list, refer to the contact information below:
• Visit our website at www.source1parts.com for the following information:
1. Search for a part or browse the catalog.
2. Find a dealer or distributor.
3. Customer Service contact information. a. Click on the “Brand Links” button
b. Click on the “Customer Service” button
• You can contact us by mail. Just send a written request to:
York International
Consumer Relations
5005 York Drive
Norman, OK 73069
035-19992-001 Rev. A (0404)
50, 7512
50,7512
All Models1NP0367 Conversion Kit- Natural Gas to LP Gas- High Altitude
Unitary Products Group 11
Page 12
035-19992-001 Rev. A (0404)
SECTION IV: WIRING DIAGRAM
FIGURE 15: Wiring Diagram
12 Unitary Products Group
Page 13
NOTES
035-19992-001 Rev. A (0404)
Unitary Products Group 13
Page 14
035-19992-001 Rev. A (0404)
NOTES
14 Unitary Products Group
Page 15
NOTES
035-19992-001 Rev. A (0404)
Unitary Products Group 15
Page 16
Limited Warranty
UPG warrants this product to be free from defects in factory workmanship and material under normal use and service and will, at its option, repair or replace any parts that prove to have such def ects acco rding to th e ter ms out lined on t his warr ant y. This warranty covers only t he eq uipme nt de scribe d by the Prod uct Model Number and Serial Number listed on t he Warranty Registration Card . UPG warrants the primary heat exchangers in the product to be free from defects in factory workmanship and material under normal use and service and will at its option, repair or furnish a replaceme nt heat exchanger, either new or reconditioned, that meets the intended fit, use and function of the original heat exchanger for any heat exchanger furnished by UPG which proves to have such defects within the duration of warranty coverage. Alternatively, UPG may, at its option, extend a replacement all owance to be applied toward th e purchase of a new furnace or packag ed unit marketed by UPG. The exact amount of the allowance will be determined at the discretion of UPG, based upon current market conditions, but in no case shall this allowance exceed thirty (30) percent of the original consumer pu rchase pr ice o f the fu rnace, exclu ding suc h items as du ctwork, w iring, piping and ins tallation costs. U PG shall have no responsibility hereunder for installation, shipping, handling or other charges except as specifically provided herein. For your benefit and protection, return the Warranty Registration Card to UPG promptly after installation. This will initiate the warranty period and allow us to contact you, should it beco me necessary. In the ab se n ce of a recorded Warranty Registrati on Ca rd , th e warranty period will begin upon product shipment from UPG.
This warranty extends only to the original consumer purchaser and is non-transferable. For this warranty to apply, the product must be installed according to UPG recommendations and specifica tions , and in acc ordance with all l ocal, state, an d natio nal codes; and the pr oduct mus t not be removed f rom its plac e of original installation. The warranty period for repair or replacement parts provided hereunder shall not extend beyond the warranty period stated on this warranty
HEAT EXCHANGER
FURNACE TYPE
Original Owner Subsequent Owner
80% G8C / GF8
UPG strongly recommends regular periodic preventative maintenance on this equipment. The person most familiar with the equipment in your HVAC system is a UPG dealer. The UPG dealer can ensure your maintenance program meets the conditions of the "UPG Warranty", maximize the efficiency of the equipment, and service your unit within the mandated guidelines with regard to unlawful discharge of refrigerants into the atmosphere. This warranty applies only to products installed in the United States and Canada.
20 N/A 10 5
Non-Residential
Applications
EXCLUSIONS
This warranty does not cover any:
1. Shipping, labor, or material charges.
2. Damages resulting from transportation, installation, or servicing.
3. Damages re sulting from ac cident, abuse, fir e, flood, alterat ion, or acts of God (tampe ring, altering, defacing or removi ng the produc t serial number will serve to void this warranty).
4. Damages resulting from use of the product in a corrosive atmosphere.
5. Damages resulting from inadequacy or interruption of electrical service or fuel supply, improper voltage conditions, blown fuses, or other like damages.
6. Cleaning or replacement of filters.
7. Damages resulting from failure to properly and regularly clean air and/or water side of condenser and evaporator.
8. Damages resulting from: (I) freezing of condenser water or condensate; (II) inadequate or interrupted water supply; (III) use of corrosive water; (IV) fouling or restriction of the water circuit by foreign material or like causes.
9. Damages resulting from operation with inadequate supply of air or water.
10. Damages resulting from use of components or accessories not approved by UPG (ve n t damp er s, etc.).
11. Increase in fuel or electric cost.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABIL­ITY AND FITNESS FOR A PARTICULAR PURPOSE.
SOME STATES DO NOT ALLOW THE DISCLAIMER OF IMPLIED WARRANTY, SO THAT THE ABOVE DISCLAIMER MAY NOT APPLY TO YOU. SOME STATES ALLOW ONLY A PARTIAL LIMITATION ON IMPLIED WARRANTIES TO LIMIT THE DURATION OF IMPLIED WARRANTIES TO THE DURA-
TION OF THE EXPRESS WARRANTY. IN SUCH STATES, THE DURATION OF IMPLIED W ARRANTIES IS HEREBY EXPRESSLY LIMITED TO THE DURA­TION OF THE EXPRESS WARRANTY ON THE FACE HEREOF.
IN NO EVENT, WHETHER AS A RESULT OF BREACH OF WARRANTY OR CONTRACT, TORT (INCLUDING NEGLIGENCE) STRICT LIABILITY OR OTH­ERWISE, SHALL UPG BE LIABLE FOR SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, INCLUDING BUT NOT LIMITED TO LOSS OF USE OF THE EQUIPMENT OR ASSOCIATED EQUIPMENT, LOST REVENUES OR PROFITS, COST OF SUBSTITUTE EQUIPMENT OR COST OF FUEL OR ELEC­TRICITY. THE ABOVE LIMITATIONS SHALL INURE TO THE BENEFIT OF UPG'S SUPPLIERS AND SUBCONTRAC TORS. THE ABOVE LIMITATION ON CONSEQUENTIAL DAMAGES SHALL NOT APPLY TO INJURIES TO PERSONS IN THE CASE OF CONSUMER GOODS.
SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITA TION OF LIABILITY FOR CONSEQUENTIAL OR INCIDENT AL DAMAGES, OR FOR STRICT LIABILITY IN TORT, SO THAT THE ABOVE EXCLUSIONS AND LIMITATIONS MAY NOT APPLY TO YOU.
UPG DOES NOT ASSUME, OR AUTHORIZE ANY OTHER PERSON TO ASSUME FOR UPG, ANY OTHER LIABILITY FOR THE SALE OF THIS PRODUCT . THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE. For Owner's Information:
PARTSResidential Applications
PRODUCT MODEL. NO. ____________________ INSTALLATION DATE ______________________________ UNIT SERIAL NO. _________________________ INSTALLING DEALER ______________________________
Subject to change without notice. Printed in U.S.A. 035-19992-001 Rev. A (0404) Copyright © by York International Corp. 2004. All rights reserved. Supersedes: 035-15243-005 Rev. B (0902)
Unitary 5005 Norman Products York OK Group Drive 73069
Loading...