295421-YTG-B-0707
DESCRIPTION
This fan coil unit provides the flexibility for installation in any
upflow or horizontal application. These versatile models may
be used for split-system cooling or heat pump operation.
Compact cabinets along with return air options in both the
upflow and horizontal positions allow this unit to fit into tight
spaces such as attics, crawl spaces, and closets.
NOTE: For matching condensing units and performance
data, refer to condenser technical guides.
TECHNICAL GUIDE
SINGLE PIECE AIR HANDLERS
FOR USE WITH SPLIT-SYSTEM
COOLING & HEAT PUMPS
HEAT PUMP MODELS:
F*FP
VARIABLE SPEED MODEL:
F*FV
FEATURES
CABINET -The compact and sturdy cabinet is protected with
a durable, attractive finish to prevent rust. The cabinet is also
insulated to prevent cabinet sweating. F*FP and F*FV models have 3/4 inch insulation.
BLOWERS - Blowers are sized to circulate air both quietly
and efficiently. The direct-drive, multi-speed motors provide a
selection of air volume to match any application. Motor
speeds may be selected via quick connect terminal at the
motor. Slide-out blower/motor assemblies provide for easy
servicing.
COILS - Using the latest in heat transfer technology, the rifled
tube coil/aluminum fin coils produce high performance ratings
and provide long lasting quality. The coils are capable of bottom return air in the upflow position, and right or left end
return air in the horizontal position.
FACTORY INSTALLED TXV - Air handler models F*FP and
F*FV have factory installed TXV metering device.
ELECTRIC HEATERS - Models providing up to 25kw of heat
are available as field installed accessories. Electric heaters
are available in both single and three phase.
EASY INSTALLATION - These fan coil units are designed to
provide the lowest total installation cost. Accessible color
coded control wiring, top and side power wiring knockouts,
easy to install drain connections and electric heaters all combine to minimize installed cost on every job.
CONTROL BOARD - The control board is equipped with low
voltage terminal strips for easy installation. The control board
is also equipped with plug-in receptacles for the auxiliary
heaters.
ISO 9001
Certified Quality
Management System
Due to continuous product improvement, specific a t ion s
are subject to change without notice.
isit us on the web at www.york.com
Additional rating information can be foun d at
www.ari.org/aridirectory.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
DIMENSIONS
295421-YTG-B-0707
SHIPPING BRACKET*
REMOVE PRIOR TO
INSTALLATION (2 SCREWS)
J
DRAIN CONNECTIONS
FOR HORIZONTAL
APPLICATIONS
4
VAPOR
OPENING
LIQUID
OPENING
D
2
DRAIN CONNECTIONS
FOR UPFLOW APPLICATIONS
10-3/8
ALL DIMENSIONS ARE IN INCHES. THEY ARE SUBJECT TO CHANGE
WITHOUT NOTICE. CERTIFIED DIMENSIONS WILL BE PROVIDED
F
K
C
B
FILTER
ACCESS
UPON REQUEST.
A
3/4
TOP VIEW (ALL MODELS)
=DRAIN PAN FOOTPRINT
MAX. FILTER LENGTH
(21 INCHES)
MAX. FILTER WIDTH
(B MINUS 1-1/2 INCHES)
3/4
E
REAR
BOTTOM VIEW
F
18-3/8
7-1/2
4-1/8
10-3/8
3/4
Refrigerant Connections
1
Line Size
Liquid Vapor
5/8
Model
ABC
Height Width Depth Power Control
F4FP024H06T2* 40-3/4 18
Dimensions
DEF
14-7/8 16-1/2
Wiring K.O.s
JK
F4FP030H06T2* 40-3/4 18 14-7/8 16-1/2 3/4
F4FP036H06T2* 40-3/4 21-1/2 18-3/8 20 3/4
12-1/8
7/8 (1/2)
1-3/8 (1)
F4FP040H06T2* 40-3/4 21-1/2 18-3/8 20 7/8
F4FP042H06T2* 40-3/4 21-1/2 18-3/8 20 7/8
F4FP045H06T2* 50-3/4 24
F5FP048H06T2* 50-3/4 24 20-7/8 22-1/2 7/8
F5FP060H06T2* 50-3/4 24 20-7/8 22-1/2 7/8
F4FV060H06T2* 50-3/4 24 20-7/8 22-1/2 7/8
1. Actual conduit size is shown in parenthesis.
2. All models only available with factory installed horizontal drain pan.
22
17-3/8
20-7/8 22-1/2
7/8 (1/2)
1-3/8(1)
1-23/32
(1-1/4)
7/8 (1/2) 3/8
7/8
2 Unitary Products Group
295421-YTG-B-0707
COIL TECHNICAL DATA
Coil
Slab Size
HW
Tube
Geometry
Tube
Dia.
Fin. Type
1 x .886 3/8 Enhanced
Models Application
F4FP024H06T2A A/C & HP
Refrigerant
Connection
Type
Face
Area
(Sq. Ft.)
Deep
Rows
Fins
Per
Inch
3.40 2 14 14 17.5
F4FP024H06T2B A/C & HP 3.40 2 14 14 17.5 TXV-2B
F4FP030H06T2A A/C & HP 3.89 2 14 16 17.5 TXV-2A
F4FP036H06T2A A/C & HP 3.40 3 12 14 17.5
F4FP040H06T2A A/C & HP 3.89 3 11 16 17.5 TXV-2A
F4FP040H06T2C A/C & HP 3.89 3 11 16 17.5 TXV-2C
F4FP042H06T2A A/C & HP 3.89 3 11 16 17.5
Sweat
F4FP042H06T2C A/C & HP 3.89 3 11 16 17.5 TXV-2C
F4FP045H06T2C A/C & HP 5.83 3 12 24 17.5 TXV-2C
F5FP048H06T2C A/C & HP 5.35 3 12 22 17.5
F5FP060H06T2C A/C & HP 5.83 3 12 24 17.5 TXV-2C
F4FV060H06T2C A/C & HP 5.83 3 12 24 17.5
COOLING CAPACITY
Blower
Model
Rated
CFM
F4FP024H06T2* 830
F4FP030H06T2* 1050
F4FP036H06T2* 1250
F4FP040H06T2* 1050
F4FP042H06T2* 1400
F4FP045H06T2* 1400
F5FP048H06T2* 1600
F5FP060H06T2* 1850
4FV060H06T2*
F
1980
Entering
Air °F
(Dry / Wet Bulb)
Upflow / Horizontal Positions Only
85 / 72
80 / 67
75 / 62
70 / 57
85 / 72
80 / 67
75 / 62
70 / 57
85 / 72
80 / 67
75 / 62
70 / 57
85 / 72
80 / 67
75 / 62
70 / 57
85 / 72
80 / 67
75 / 62
70 / 57
85 / 72
80 / 67
75 / 62
70 / 57
85 / 72
80 / 67
75 / 62
70 / 57
85 / 72
80 / 67
75 / 62
70 / 57
85 / 72
80 / 67
75 / 62
70 / 57
MBH @ Evaporator Temperature and Corresponding Pressure °F /
PSIG
35 / 61.5 40 / 68.5 45 / 76.0 50 / 84.0
36.3
33.4
27.4
22.2
41.5
36.2
29.1
24.1
53.4
42.8
33.4
28.7
55.3
44.2
34.5
29.6
88.4
70.8
55.2
47.4
92.7
74.2
57.8
49.7
100.5
80.4
62.7
53.9
119.9
96.0
74.8
64.3
122.0
98.1
76.9
66.4
33.0
30.2
24.3
19.3
37.8
32.4
25.3
21.5
48.6
37.8
28.1
26.5
47.5
37.1
27.5
26.0
76.0
59.4
43.9
41.5
78.1
61.3
45.3
42.8
86.4
67.5
49.9
47.2
101.0
79.2
58.6
55.4
103.1
81.3
60.7
57.5
29.5
26.7
21.0
16.2
33.7
28.6
24.0
18.7
43.4
33.1
30.6
24.5
39.6
30.2
22.4
22.4
63.3
48.4
35.8
35.8
63.4
48.4
35.7
35.7
72.0
55.0
40.7
40.7
82.0
62.6
46.2
46.2
84.1
64.7
50.3
48.3
Metering
Device
TXV-2A
TXV-2A
TXV-2A
TXV-2C
TXV-2C
25.6
23.1
17.7
12.6
29.5
24.5
19.2
15.8
38.3
28.2
22.8
22.8
31.2
23.1
18.7
18.7
50.0
37.0
29.9
29.9
48.1
35.4
28.6
28.6
56.8
42.1
34.0
34.0
62.2
45.8
37.0
37.0
64.3
47.9
39.1
39.1
Unitary Products Group 3
295421-YTG-B-0707
ACCESSORIES
Refer to Price Manual for specific model numbers.
VERTICAL SUSPENSION KIT - The suspension kit is
designed to be used with all sizes of fan coil units whenever
the application requires vertical suspension of the unit.
ELECTRIC HEATERS - Models shown under Electrical Data
include sequencers and temperature dual limit switches for
safe, efficient operation. Circuit breakers are provided where
shown.
BOLT-ON THERMAL EXPANSION VALVE - TXV kits are
available for enhanced efficiency. These fan coil units have
factory installed TXV’s.
LIMITATIONS
These units must be wired and installed in accordance with
all national and local safety codes. Voltage limits are as follows:
Normal Operating voltage Range
1. Utilization range “A” in accordance with ARI Std. 110.
1
Air flow must be within the minimum and maximum limits
approved for electric heat, evaporator coils and outdoor units:
Entering Air Temperature Limits
Wet Bulb Temp. ºF Dry Bulb Temp. ºF
Min. Max. Min. Max.
57 72 65 95
187-253
EXTENDED AIRFLOW DATA1 FOR 230 VOLT - HEAT PUMP MODELS
Models
F4FP024H06T2*
F4FP030H06T2*
F4FP036H06T2*
F4FP040H06T2*
F4FP042H06T2*
F4FP045H06T2*
F5FP048H06T2*
F5FP060H06T2*
F4FV060H06T2*
NOTE: Air flow data shown above 0.50” W.C. external static pressure is for REFERENCE ONLY. Maximum allowable external static when electric heat is used is
limited to 0.50” W.C. Maximum allowable external static pressure may also be limited by minimum CFM requirements for proper Heat Pump operation.
1. Includes Return Air Filter and Largest Electric Heater.
All F*FP series air handler units are UL Listed up to 0.50" w.c. external static pressure, including air filter, wet coil, and largest KW size heater.
Blower Motor
Speed
High 950 910 865 835 775
Med 845 815 785 745 705
Low 650 630 605 575 540
High 1,270 1,210 1,150 1,085 1,015
Med 1,050 1,040 995 930 855
Low 855 820 780 735 680
High - 1,310 1,250 1,175 1,120
Med 1,200 1,150 1,100 1,040 985
Low 1,060 1,015 970 925 860
High 1,270 1,210 1,150 1,085 1,015
Med 1,050 1,040 995 930 855
Low 855 820 780 735 680
High - 1,575 1,500 1,420 1,350
Med 1,460 1,395 1,330 1,260 1,190
Low 1,250 1,200 1,155 1,100 1,050
High 1,575 1,535 1,475 1,390 1,310
Med High 1,375 1,315 1,255 1,185 1,110
Med Low 1,210 1,160 1,110 1,050 980
Low 1,035 990 940 890 825
High 2223 2158 2090 2029 1929
Med High 1948 1904 1801 1815 1777
Med 1741 1690 1649 1606 1564
Med Low 1499 1454 1415 1370 1328
Low 1286 1233 1177 1142 1092
High 2195 2145 2070 2008 1920
Med High 1938 1899 1873 1824 1791
Med 1726 1681 1641 1607 1560
Med Low 1525 1483 1441 1383 1356
Low 1306 1254 1204 1160 1114
High 2,285 2,195 2,105 2,015 1,950
Med. 2,125 2,020 1,910 1,805 1,705
Low 1,655 1,605 1,550 1,500 1,450
0.10 0.20 0.30 0.40 0.50
CFM @ External Static Pressure - IWC
230 Volt
0.60 0.70 0.80 0.90 1.00
730 662 590 502 400
654 594 524 439 344
508 450 383 285 158
946 862 769 645 502
804 714 624 494 364
624 550 447 333 190
1,053 983 894 779 645
933 879 795 711 587
809 740 661 572 453
946 802 769 645 502
804 714 624 494 364
624 550 447 333 190
1,273 1,192 1,102 996 871
1,125 1,052 960 842 695
1,001 931 851 751 631
1,245 1,147 1,030 897 735
1,040 944 848 732 606
921 844 737 640 533
770 698 616 524 432
1861 1788 1679 1594 1501
1741 1681 1618 1539 1453
1516 1476 1436 1387 1353
1269 1228 1191 1132 1093
1039 987 960 888 842
1852 1754 1663 1570 1462
1724 1679 1603 1521 1420
1517 1485 1433 1402 1349
1291 1253 1208 1169 1123
1061 1008 980 914 876
1,845 1,770 1,685 1,590 1,485
1,597 1,491 1,386 1,280 1,175
1,398 1,326 1,245 1,153 1,052
4 Unitary Products Group
295421-YTG-B-0707
EXTENDED AIR FLOW DATA1 FOR 208 VOLT - HEAT PUMP MODELS
Models
F4FP024H06T2*
F4FP030H06T2*
F4FP036H06T2*
F4FP040H06T2*
F4FP042H06T2*
F4FP045H06T2*
F5FP048H06T2*
F5FP060H06T2*
F4FV060H06T2*
NOTE: Air flow data shown above 0.50” W.C. external static pressure is for REFERENCE ONLY. Maximum allowable external static when electric heat is used is
limited to 0.50” W.C. Maximum allowable external static pressure may also be limited by minimum CFM requirements for proper Heat Pump operation.
1. Includes Return Air Filter and Largest Electric Heater.
All F*FP series air handler units are UL Listed up to 0.50" w.c. external static pressure, including air filter, wet coil, and largest KW size heater.
Blower Motor
Speed
High 855 819 779 752 698
Med. 760 733 706 670 634
Low 585 567 545 518 486
High 1143 1089 1035 977 914
Med. 941 936 895 837 770
Low 770 738 702 662 612
High 1235 1179 1125 1058 1008
Med. 1080 1035 990 936 887
Low 954 914 873 833 774
High 1143 1089 1035 977 914
Med. 941 936 895 837 770
Low 770 738 702 662 612
High 1400 1418 1350 1278 1215
Med. 1314 1266 1197 1135 1071
Low 1125 1080 1040 990 945
High 1418 1382 1328 1251 1179
Med-high 1238 1184 1130 1067 999
Med-low 1089 1044 999 945 882
Low 932 891 846 801 743
High 2209 2140 2093 2000 1939
Med High 1945 1906 1871 1819 1784
Med 1739 1690 1640 1602 1559
Med Low 1506 1464 1415 1369 1325
Low 1301 1248 1197 1151 1095
High 2134 2124 2052 1979 1861
Med High 1916 1875 1838 1777 1744
Med 1716 1671 1613 1569 1523
Med Low 1494 1435 1390 1341 1284
Low 1276 1223 1168 1115 1068
High 2057 1976 1895 1814 1728
Med. 1913 1818 1719 1625 1535
Low 1490 1445 1395 1350 1305
0.10 0.20 0.30 0.40 0.50
CFM @ External Static Pressure - IWC
208 Volt
0.60 0.70 0.80 0.90 1.00
657 596 531 452 360
589 535 472 395 310
457 405 344 257 142
851 776 692 581 451
724 643 562 445 328
561 495 402 300 171
947 885 804 701 580
840 791 716 640 528
728 666 595 515 408
851 776 692 581 451
724 643 562 445 328
561 495 402 300 171
1145 1073 991 897 784
1012 947 864 758 625
901 838 766 676 568
1120 1032 927 807 661
936 850 763 659 545
829 760 663 576 480
693 628 554 472 389
1864 1746 1724 1655 1587
1741 1667 1640 1595 1550
1516 1470 1431 1387 1343
1283 1238 1193 1139 1100
1054 1005 958 909 860
1756 1639 1597 1512 1427
1671 1594 1584 1537 1490
1475 1429 1384 1337 1290
1241 1194 1139 1087 1036
1009 965 902 847 792
1661 1593 1517 1431 1337
1437 1342 1247 1152 1057
1258 1194 1120 1038 946
APPLICA TION FACTORS-RELATED CFM VS. ACTUAL CFM
% Of Rated Airflow 80% 90% RATED CFM 110% 120%
Capacity Factor 0.96 0.98 1.00 1.02 1.03
Unitary Products Group 5