These completely assembled indoor units include a wellinsulated cabinet, a copper tube/aluminum fin coil, throw
away filters, a centrifugal blower,ablowermotor, an adjust
able V-belt drive, a blower motor contactor and a small
holding charge of an inert gas. They also include a filterdrier,anexpansion valveand adistributor that are only used
during the cooling cycle plus a check valve to provide the
proper flow of refrigerant through the coil during both the
cooling and heating cycles.
Supplementalresistanceheaters, a supplyair plenum, areturn
airgrille and abase are availableas accessories forfield instal
lation.
The units are shipped in the vertical position ready for field in
stallation. For horizontal installation, reverse the solid bottom
panel and the return air duct flange on the front of the unit.
REFERENCE
Thisinstruction coversthe installationof theindoor unit.For in
formationon theinstallation andoperation ofthe matchingout
door unit, refer to Form 035-15410-002.
Renewal Parts:
•
Refer to Parts Manual for complete listing of replacement
parts on this equipment.
All forms referenced in this instruction may be ordered from:
-
Installer should pay particular attention to the words: NOTE,
CAUTION and WARNING. Notes
make the installation easier. Cautions
equipment damage. Warnings
thatpersonal injuryand/orequipment damagemay resultifthe
installation procedure is not handled properly.
INSPECTION
As soon as a unit is received, it should be inspected for possi
ble damage during transit. If damage is evident, the extent of
thedamageshould benotedon the carrier'sfreightbill. Asepa
THIS PRODUCT MUSTBE INSTALLED IN STRICTCOMPLIANCE
WITH THE ENCLOSED INSTALLATION INSTRUCTIONS AND
ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES
-
INCLUDING, BUT NOT LIMITED TO, BUILDING, ELECTRICAL,
-
AND MECHANICAL CODES.
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION,
SERVICE OR MAINTENANCE CAN CAUSE INJURY OR
PROPERTY DAMAGE. REFER TO THIS MANUAL. FOR
ASSISTANCE OR ADDITIONAL INFORMATION, CONSULT A
QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS
SUPPLIER.
Standard Register
Toll Free Tel.: 877-318-9675
Toll Free Fax: 877-379-7920
rate request for inspection by the carrier's agent should be
made in writing.
LIMITATIONS
These units must be installed in accordance with all national
andlocal safety codes.Ifno localcodesapply,installationmust
conform with the appropriate national codes. Units are de
signedtomeetNational SafetyCodeStandards.Ifcomponents
are tobe added to aunit to meet localcodes, they are to be in
stalled at the dealer's and/or the customer's expense. See Ta
ble 2 for application limitations.
LOCATION
These indoor units are not designed for outdoor installation.
Theymustbe locatedwithinthe building structure,eitherinside
or outside the conditioned space.
The units should be located as close to the outdoor units as
practical and positioned to minimize bends in the refrigerant
piping.
Unitsbeinginstalledvertically orhorizontallycanbe setdirectly
on a floor or platform, or they can be supported by metal or
wooden beams.
Units being installed horizontally can be suspended from
above.Four 3/8" weld nutsare provided in the unit frame to accommodate hanger rods. Knockouts must be removed from
the unit panels to expose theseweld nuts. Refer to Figure1 for
their location and the individual load on each hanger rod.
WARNING: Be careful when attaching the hanger rods. Use a
washerwith a back-upnut oneachrod andtighten
down against the cabinet so they will not be al
lowed to turn or slip.
RIGGING AND HANDLING
Exercise care when moving the unit. Do not removeany pack
aging until the unit is near the place of installation.
-
The packaging consists of a bottom wooden skid that can be
liftedwitha forktruckfrom anydirection, a cardboardcontainer
thatcovers theentire unit, andstrapping thatsecures thecard
board container to the bottom skid.
These units can be rigged with slings under the bottom skid.
CAUTION: Spreader bars should be used to prevent the
slings from crushing the unit panels and frame.
Before rigging any unit,determine itsweight from Table 1. Bef
orerigging a unitforhorizontal installation, determineitscenter
of gravity from Figure 1, and make sure that its weight will be
distributed equally.
CLEARANCES
All unitsrequire certain minimum clearances for proper operation and service. Refer to Figure 12 for these clearances.
-
-
-
-
TABLE 1 - PHYSICAL DATA
DESCRIPTION
Rows Deep x Rows High3 x 244 x 32
Finned Length - inches45.545.5
Coil
Centrifugal Blower (Forward Curve)Diameter x Width - inches15 X 1515 X 15
Blower Motor
Filters (Throwaway)
Refrigerant-22 (Lbs.)
Unit Weight (lbs.)
Accessory Operating Weights (Lbs.)
1
All of these 1750 RPM motors have a solid base, a 56 frame, a 1.15 service factor, inherent protection & permanently lubricated ball bearings. Refer to page 6 for additional motor & drive data.
2
Refer to Form 035-15410-002 for system charge.
Unitary Products Group3
1
2
Face Area - square feet7.610.1
Tube (Copper) OD - inches3/83/8
Fins (Aluminum) per inch1313
Nominal Rating - HP1-1/22
Quantity Per Unit - 16" x 25" x 1"44
Total Face Area - square feet11.111.1
Pumpdown Capacity12.022.0
Shipping405440
Operating365400
10 KW6363
Electric Heaters
Supply Air Plenum102102
Base6060
Return Air Grille1515
16 KW6666
26 KW7171
36 KW7474
UNIT MODEL
F3EH090F4EH120
Page 4
TABLE 2 - APPLICATION DATA
Model
Power
Supply
Voltage Variation
Min.Max.Min.Max.Min.Max.Min.Max.
1
208/230-3-60187252
F3EH090
380/415-3-50342456
208/230-3-60187252
F4EH120
1
Utilization Range “A” in accordance with ARI Standard 110.
2
The system may operate below 50°F for a short period of time when warming up the conditioned space after a long shutdown.
380/415-3-50342456
Supply Air CFM
24003600577250
32004800577250
035-09651-001-A-0304
Entering Air Temperatures, °F
Cooling - wbHeating - db
2
2
80460-3-60414506
80460-3-60414506
FIG. 1 - UNIT SUSPENSION MOUNTING
(Horizontal Application)
Based on a Standard Blower Motor
ModelAccessory
Center of Gravity
Dimensions, In.
Weight
Distribution, Lbs.
ABW1W2W3W4Total
Basic Unit Only25-5/823-1/4991047983365
F3EH090
Unit with Electric Heat30-3/423-3/89015072121433
Unit with Plenum35-1/823-1/27118658152467
Unit with Electric Heat & Plenum3823-5/86223251190535
Basic Unit Only24-1/823-1/41161069385400
F4EH120
Unit with Electric Heat29-1/423-3/810315584126468
Unit with Plenum33-3/823-1/28819070154502
Unit with Electric Heat & Plenum36-5/823-5/87623663195570
NOTE: Unit weights (with electric heat accessory) are based on an average heater weight of 68 lbs.
4Unitary Products Group
Page 5
035-09651-001-A-0304
WARNING: Do notpermit overhanging structures or shrubs to
obstruct air discharge.
Additional height may be required for snow clearance if winter
operation is expected.
Thereturn airduct flangeis factory-mountedon thefront ofthe
unit, but it can bereversed with the solid bottom panel forhori
zontal applications.
A supply air plenum (Fig. 4), a base (Fig. 5) and a return air
grille (Fig. 6) are available as field-installed accessories, and
one ofthe following respective instructions will be packed with
each.
-
FIG. 2 - VERTICAL AND HORIZONTAL APPLICATIONS
VERTICAL / HORIZONTAL INSTALLATION
Theseindoor units are shipped forvertical installationwith ver
tical air discharge as shown in Figure 2(A) but may be con
verted for horizontal installation as shown in Figure 2(B) by
interchanging the solid bottom panel and the return air duct
flange.
-
-
DUCT CONNECTIONS
Design and install all ducts in accordance with all national
and/or local codes.
Ducts should be sized no smaller than the duct flanges on the
unitor theelectric heater(if used).Refer tothe unitdimensions
(Fig. 12) and the heater detail (Fig. 3) for these sizes. Refer to
Form035-16602-002 for installationinstructionson theelectric
heater.
Useflexible fiber glass or plasticcloth collarsor other nonflam
-
mable material at the unit duct connections to minimize the
transmission of noise and vibration.
Insulate all ductwork running through unconditioned areas to
prevent moisture condensation and to provide more economi
cal operation.
Unitary Products Group5
-
FIG. 5 - BASE ACCESSORY
(For Vertical Arrangement Shown)
Page 6
FIG. 6 - RETURN AIR GRILLE ACCESSORY
(Vertical Arrangement Shown)
Form 035-16650-001 – Supply Air Plenum
Form 035-16621-001 – Return Air Grille
Form 035-16632-001 – Base
035-09651-001-A-0304
INSTALLING REFRIGERANT MAINS
WARNING: Provisions for recovering refrigerant releases
must be available during allphases of installation,
leak testing and charging. Do NOT release refrig
erant into the atmosphere.
The units are evacuated and dehydrated at the factory and
shipped with a holding charge of aninert gas suchas Nitrogen
or Helium. The vapor and liquid connections are sealed with
copper discs.
If the unit has already lost its holding charge, it should be leak
tested and the necessary repairs should be made. If the unit
has maintained its holding charge, you can assume that it has
no leaks and proceed with the installation.
The temperature required to make or break a brazed joint is
sufficientlyhightocauseoxidation of thecopperunlessaninert
atmosphere is provided.
Many service problems can be avoided by taking adequate
precautions to provide an internally clean and dry system and
by using procedures and materials that conform with established standards.
Useharddrawn copper tubingwherenoappreciable amountof
bending around pipes or other obstructions is necessary. Use
long radius ells wherever possible with one exception - small
radius ells for any traps in a vapor riser.If soft copper is used,
care should be taken toavoid sharp bends whichmay cause a
restriction.
Fiber glass insulation and a sealing material such as perma
gum should be packed around refrigerant lines where they
penetrate a wall to reduce vibration and to retain some flexibil
ity.
Support all refrigerant lines at minimum intervals with suitable
hangers, brackets or clamps.
Braze all copper to copper joints with Sil-Fos 5 or equivalent
brazing material. DO NOT USE SOFT SOLDER.
Drilla small holethrough thediscsto preventanyinternal pres
surefrom blowing themoff and to allowthe flow of dry nitrogen
through the connections when unbrazing the closures.
The liquid and vapor connections must be piped outside the
unit. Refer to the unit drawing for the locations and the dimensions of these connections.
Before brazing the refrigerant lines to these connections, remove the short panel from the unit frame and slide the grommets onto the refrigerant lines. After the brazed joints have
cooled, slide the grommets back into place and secure the
panel to the unit frame.
NOTE: Thesecoilscan only bepipedfromonesideof the unit.
DRAIN CONNECTION
The drain line MUSTbe trapped becausethe coil islocated on
the negative side of the supply air blower,and it must be pro
tected from freezing temperatures.
-
-
Never braze or solder the liquid and vapor lines together. The
completevaporline should beinsulatedwithminimum 1/2" AR
-
MAFLEX or equivalent.
If it is desirable to tape or wire these lines together for support
purposes, they must be completely insulated, one from the
other.
Refer to the installation instruction (Form 035-15410-002) for
the matching outdoor unit for piping limitations, line sizes, and
other design considerations.
6Unitary Products Group
FIG. 7 - RECOMMENDED DRAIN PIPING
Page 7
035-09651-001-A-0304
A7/8" OD drain connection extends through right hand side of
cabinet. Refer to Fig. 7 for recommended drain piping.
The drain connection is located on the sameside of theunit as
therefrigerantconnections. The lineshouldbe insulated where
moisturedrippagewillbe objectionable orcausedamagetothe
area.
The 3" dimension must equal or exceed the negative static
pressure developed by the supply air blower. If it does not, the
condensate will not drain properly and may overflow the drain
pan. The trap must be at least 2-1/2" deep to maintain a water
seal under all operating conditions, especially during blower
start-up.
NOTE: The unit may have to be raised off the floor to allow
The RPM of the supply air blower will depend on the required
CFM,theunitaccessories andthestaticresistancesofboth the
supply and the return air duct systems. With this information,
the RPM for the supply air blower can be determined from the
blower performance in Table 4.
Knowing the required blower RPM and the blower motor HP,
the setting (turns open) for the supply air motor pulley can be
determined from Table 3.
Each motor pulley has:
1. Athreaded barrel with two flats (or notched recesses) 180
degrees apart.
2. A movable flange with one set screw.
After the movable flange has been rotated to the proper
number of “turns open”, the set screw should be tightened
againsttheflat on thebarreltolock the movableflangeinplace.
If the pulley includesa locking collar, thelocking collar mustbe
loosened to adjust the setting of the movable flange.
Note the following:
1. The supply air CFM mustbe within the limitations shown in
Table 2.
2. All pulleys can be adjusted in half turn increments.
3. The tension on the belt should be adjusted for a deflection
of 3/16 of an inch per footof belt spanwith an applied force
of 2 to 3 pounds. This adjustment is made by moving the
blowermotor mounting plate.Refer toFigure8. Turningthe
adjustment bolt (B) moves the motor mounting plate up or
down.
Unitary Products Group7
Twohex nuts (A) have to be loosened to move the mount
ingplate and retightenedafter the mountingplate hasbeen
moved to the proper position.
4. All pulleys are factory aligned.
5. All supply air motor pulleys are factory set 3 “turns open”.
After thesupply air blower motoris operating, adjust the resis
tances in both the supply and the return duct systems to bal
ancethe air distributionthroughout theconditioned space. The
job specifications may require that this balancing be done by
someone other than the equipment installer.
Tocheckthe supply airCFMafter the initialbalancinghas been
completed:
1. Drill two 5/16 inch holes in the side panel as shown in Figure 9.
2. Insert atleast 6" of 1/4 inch tubing into each of these holes
for sufficient penetration into the air flow on both sides of
the indoor coil.
NOTE: The tubes must be inserted and heldin a position
perpendicular tothe air flow so thatvelocity pres
sure will not affect the static pressure readings.
3. Usingan inclined manometer,determinethepressuredrop
across a dry indoor coil. Since moisture on the coil may
varygreatly,measuringthe pressuredrop acrossa wet coil
underfield conditions would be inaccurate. To assure a dry
coil, the heat pump system should be de-activated while
the test is being run.
4. Knowing the pressure drop across a dry coil, the actual
CFM through the unit can be determined from the curve in
Figure 10.
Ifthe CFM is above orbelow thespecified value, the supply air
motor pulley may have to be readjusted. After one hour of op
eration,checkthebeltand pulleys fortightnessandalignment.
WARNING: Failure to properly adjust the total system CFM
can result in extensive blower damage.
Afterreadings havebeen obtained,remove thetubes and seal
up the drilled holes in the side panel. Dot plugs (5/16" - P/N
029-13880-000) are available through normal parts ordering
procedures.
NOTE: Shut down the heat pump system before taking any
Unit resistance is based on a wet indoor coil and clean filters.
2
Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to the Tables 6 & 7 for the resistance of these accessories and for
additional motor and drive data .
3
Motors can be selected to operate into the service factor because they are located in the moving air stream, upstream of any heating device.
RPM range for the standard drive components.
Exceeds the BHP limitations of the standard blower motor.
8Unitary Products Group
Page 9
035-09651-001-A-0304
TABLE 6 - ACCESSORY STATIC RESISTANCE (IWG)
(To be included with Duct System Static Resistance)
Supply Air Plenum0.050.060.070.080.10
Return Air Grille0.050.060.070.080.10
TABLE 7 - BLOWER MOTOR AND DRIVE DATA
ModelMotor HP*Blower RPM
60 Hz
50 Hz
*These factory-mounted motors are wired for a 460V power supply. Refer to the wiring diagram inside the motor terminal box when reconnecting the motor leads for a
To determine the total circuit length, add the following distances:
1 - Outdoor Unit to Indoor Unit ___________
2 - Indoor Unit to Thermostat ____________
3 - Thermostat to Indoor Unit ____________
4 - Indoor Unit to Outdoor Unit ___________
5 - Outdoor Unit to Elec. Heater __________
CONTROL WIRE SIZING
Wire Size
Total Circuit Length __________
Maximum Total
Circuit Length
(Feet)
Unitary Products Group9
Page 10
POWER AND CONTROL WIRING
Install electrical wiring in accordance with the latest National
Electrical Code (NFPA Standard No. 70) and/or local regula
tions. The unit should be grounded in accordance with these
codes.
Routethe powerwiresinto theunit throughthe1-3/8” knockout
in the rear panel, and connect them to the terminals on blower
motor contactor 10M. Route the control wires into the unit
throughthe 7/8"hole inthe rear panel,and connectthem to the
terminals on block 4TB. Refer to the unit drawing in Fig. 12 for
the locations of these knockouts.
If the unit includes an electric heat accessory, route the power
wires intoheater control box in lieu of the unit. Referto electric
location of all disconnect switches and the thermostat. Teach him how to start and stop the unit, how to adjust temperature
settings within the limitations of the system, how the defrost cycle is controlled and how the anti-cycle timer operates.
MAINTENANCE
INDOOR COIL
Do not allow dirt to accumulate on the indoor coil or other parts
of the supply/return air circuit. Clean as often as necessary to
assure good system performance. Use a brush, vacuum
cleaner attachment or other suitable means.
If the coil becomes extremely dirty,it may be necessary to use
anindustrialgrade detergent andahoseto clean thefinnedsur
faces.This isrecommended to preventany lossin capacity and
efficiency.
DRAIN PAN
The condensate drain pan should be inspected regularly to as
sure proper drainage.
FILTERS
The filters must be replaced as often as necessary to assure
good air flow and filtering action. Clean filters will prevent any
loss in capacity and efficiency.
Refer to the unit drawing in Fig. 12 for the location of the filter
access panel.