York F3EH090 User Manual

INSTALLATION MANUAL
SPLIT-SYSTEM HEAT PUMPS
INDOOR UNITS
Supersedes: 515.41-N2Y (692)/035-09651-000 035-09651-001-A-0304
MODELS F3EH090 & F4EH120
(50 and 60 Hz)
GENERAL
These completely assembled indoor units include a well­insulated cabinet, a copper tube/aluminum fin coil, throw away filters, a centrifugal blower,ablowermotor, an adjust able V-belt drive, a blower motor contactor and a small holding charge of an inert gas. They also include a filter­drier,anexpansion valveand adistributor that are only used during the cooling cycle plus a check valve to provide the proper flow of refrigerant through the coil during both the cooling and heating cycles.
Supplementalresistanceheaters, a supplyair plenum, areturn airgrille and abase are availableas accessories forfield instal lation.
The units are shipped in the vertical position ready for field in stallation. For horizontal installation, reverse the solid bottom panel and the return air duct flange on the front of the unit.
REFERENCE
Thisinstruction coversthe installationof theindoor unit.For in formationon theinstallation andoperation ofthe matchingout door unit, refer to Form 035-15410-002.
Renewal Parts:
Refer to Parts Manual for complete listing of replacement parts on this equipment.
All forms referenced in this instruction may be ordered from:
-
­Installer should pay particular attention to the words: NOTE,
CAUTION and WARNING. Notes make the installation easier. Cautions equipment damage. Warnings thatpersonal injuryand/orequipment damagemay resultifthe installation procedure is not handled properly.
INSPECTION
­As soon as a unit is received, it should be inspected for possi
ble damage during transit. If damage is evident, the extent of
­thedamageshould benotedon the carrier'sfreightbill. Asepa
THIS PRODUCT MUSTBE INSTALLED IN STRICTCOMPLIANCE WITH THE ENCLOSED INSTALLATION INSTRUCTIONS AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES
-
INCLUDING, BUT NOT LIMITED TO, BUILDING, ELECTRICAL,
-
AND MECHANICAL CODES.
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE. REFER TO THIS MANUAL. FOR ASSISTANCE OR ADDITIONAL INFORMATION, CONSULT A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER.
Standard Register Toll Free Tel.: 877-318-9675 Toll Free Fax: 877-379-7920
are intended to clarify or
are given to prevent
are given to alert the installer
CAUTION
WARNING
-
-
GENERAL REFERENCE INSPECTION NOMENCLATURE
.............................................................................
.............................................................................
.............................................................................
......................................................................
INSTALLATION
LIMITATIONS LOCATION RIGGING CLEARANCES VERTICAL/HORIZONTALINSTALLATION DUCT CONNECTIONS REFRIGERANT MAINS DRAIN CONNECTION SUPPLYAIR BLOWER ADJUSTMENT POWER AND CONTROL WIRING
.............................................................................
.............................................................................
.............................................................................
...........................................................................
..............................................................
..............................................................
...............................................................
.....................................
.............................................
TABLE OF CONTENTS
1 1
................................
1 2
3 3 3 3 5 5 6 6 7 9
Figure
No.
035-09651-001-A-0304
FIGURES
Description Page 1 Unit Suspension Mounting 2 Vertical & Horizontal Application 3 Electric Heater Accessory 4 Supply Air Plenum Accessory 5 Base Accessory 6 Return Air Grille Accessory 7 Recommended Drain Piping 8 Motor Mounting Assembly 9 Hole Locations for Pressure Drop
10 Pressure Drop vs Supply Air CFM 11 Field Wiring 12 Unit Dimensions & Clearances
...................................................
..........................................................
...................................
....................................
..............................
..................................
................................
....................................
............................
..........................
........................
.......................
4 5 5 5 5 6 6 7 8
8 10 11
Refer to the matching outdoor unit installation instruction (Form 035-15410-002) for the operating sequence of the entire system.
MAINTENANCE
INDOOR COIL DRAIN PAN FILTERS LUBRICATION
BELTS ............................................................................. 12
............................................................................
.............................................................................
.............................................................................
............................................................................
12 12 12 12
TABLES
Table
No.
1 Physical Data 2 Application Data 3 Blower Motor Pulley Adjustment 4 Blower Performance (60Hz Units) 5 Blower Performance (50 Hz Units) 6 Accessory Static Resistance
7 Blower Motor & Drive Data................................... 9
8 Electrical Data...................................................... 9
Description Page
.......................................................
...................................................
..........................
........................
.......................
................................
3 4 7 8 8 9
PRODUCT NOMENCLATURE
PRODUCT CATEGORY
F = Split-System Heat Pump
Indoor
Unit
PRODUCT GENERATION
3 = 3rd Generation 4 = 4th Generation
PRODUCT IDENTIFIER
2 Unitary Products Group
F 3 E H 3 39 A
EH = Indoor Unit
0 0
NOMINAL COOLING
CAPACITY
090 = 7-1/2 Ton 120 = 10 Ton
VOLTAGE CODE
33 = 208/230/460-3-60 50 = 380/415-3-50
FACTORYINSTALLED HEAT
A = Not Applicable
035-09651-001-A-0304
INSTALLATION
rate request for inspection by the carrier's agent should be made in writing.
LIMITATIONS
These units must be installed in accordance with all national andlocal safety codes.Ifno localcodesapply,installationmust conform with the appropriate national codes. Units are de signedtomeetNational SafetyCodeStandards.Ifcomponents are tobe added to aunit to meet localcodes, they are to be in stalled at the dealer's and/or the customer's expense. See Ta ble 2 for application limitations.
LOCATION
These indoor units are not designed for outdoor installation. Theymustbe locatedwithinthe building structure,eitherinside or outside the conditioned space.
The units should be located as close to the outdoor units as practical and positioned to minimize bends in the refrigerant piping.
Unitsbeinginstalledvertically orhorizontallycanbe setdirectly on a floor or platform, or they can be supported by metal or wooden beams.
Units being installed horizontally can be suspended from above.Four 3/8" weld nutsare provided in the unit frame to ac­commodate hanger rods. Knockouts must be removed from the unit panels to expose theseweld nuts. Refer to Figure1 for their location and the individual load on each hanger rod.
WARNING: Be careful when attaching the hanger rods. Use a
washerwith a back-upnut oneachrod andtighten down against the cabinet so they will not be al lowed to turn or slip.
RIGGING AND HANDLING
­Exercise care when moving the unit. Do not removeany pack
aging until the unit is near the place of installation.
-
­The packaging consists of a bottom wooden skid that can be
liftedwitha forktruckfrom anydirection, a cardboardcontainer thatcovers theentire unit, andstrapping thatsecures thecard board container to the bottom skid.
These units can be rigged with slings under the bottom skid.
CAUTION: Spreader bars should be used to prevent the
slings from crushing the unit panels and frame.
Before rigging any unit,determine itsweight from Table 1. Bef orerigging a unitforhorizontal installation, determineitscenter of gravity from Figure 1, and make sure that its weight will be distributed equally.
CLEARANCES
All unitsrequire certain minimum clearances for proper opera­tion and service. Refer to Figure 12 for these clearances.
-
-
-
-
TABLE 1 - PHYSICAL DATA
DESCRIPTION
Rows Deep x Rows High 3 x 24 4 x 32 Finned Length - inches 45.5 45.5
Coil
Centrifugal Blower (Forward Curve) Diameter x Width - inches 15 X 15 15 X 15 Blower Motor
Filters (Throwaway) Refrigerant-22 (Lbs.) Unit Weight (lbs.)
Accessory Operating Weights (Lbs.)
1
All of these 1750 RPM motors have a solid base, a 56 frame, a 1.15 service factor, inherent protection & permanently lubricated ball bearings. Refer to page 6 for additional motor & drive data.
2
Refer to Form 035-15410-002 for system charge.
Unitary Products Group 3
1
2
Face Area - square feet 7.6 10.1 Tube (Copper) OD - inches 3/8 3/8 Fins (Aluminum) per inch 13 13
Nominal Rating - HP 1-1/2 2 Quantity Per Unit - 16" x 25" x 1" 4 4 Total Face Area - square feet 11.1 11.1 Pumpdown Capacity 12.0 22.0 Shipping 405 440 Operating 365 400
10 KW 63 63
Electric Heaters
Supply Air Plenum 102 102 Base 60 60 Return Air Grille 15 15
16 KW 66 66 26 KW 71 71 36 KW 74 74
UNIT MODEL
F3EH090 F4EH120
TABLE 2 - APPLICATION DATA
Model
Power
Supply
Voltage Variation Min. Max. Min. Max. Min. Max. Min. Max.
1
208/230-3-60 187 252
F3EH090
380/415-3-50 342 456 208/230-3-60 187 252
F4EH120
1
Utilization Range “A” in accordance with ARI Standard 110.
2
The system may operate below 50°F for a short period of time when warming up the conditioned space after a long shutdown.
380/415-3-50 342 456
Supply Air CFM
2400 3600 57 72 50
3200 4800 57 72 50
035-09651-001-A-0304
Entering Air Temperatures, °F
Cooling - wb Heating - db
2
2
80460-3-60 414 506
80460-3-60 414 506
FIG. 1 - UNIT SUSPENSION MOUNTING
(Horizontal Application)
Based on a Standard Blower Motor
Model Accessory
Center of Gravity
Dimensions, In.
Weight
Distribution, Lbs.
A B W1 W2 W3 W4 Total
Basic Unit Only 25-5/8 23-1/4 99 104 79 83 365
F3EH090
Unit with Electric Heat 30-3/4 23-3/8 90 150 72 121 433 Unit with Plenum 35-1/8 23-1/2 71 186 58 152 467 Unit with Electric Heat & Plenum 38 23-5/8 62 232 51 190 535 Basic Unit Only 24-1/8 23-1/4 116 106 93 85 400
F4EH120
Unit with Electric Heat 29-1/4 23-3/8 103 155 84 126 468 Unit with Plenum 33-3/8 23-1/2 88 190 70 154 502 Unit with Electric Heat & Plenum 36-5/8 23-5/8 76 236 63 195 570
NOTE: Unit weights (with electric heat accessory) are based on an average heater weight of 68 lbs.
4 Unitary Products Group
Loading...
+ 8 hidden pages