Page 1

SEALED COMBUSTION
DOWNFLOW GAS FURNACE
MODELS: DGAA, DGAH, DGPA, AND DGPH
For Installation In:
1, Manufactured (Mobile) Homes
2. RecreationaIVehicles & Park Models
3. Modular Homes & Buildings
IMPORTANT - Only individuals having proven expedence with this
type ofequipment shouldattempt to performset-up.
Proper furnace set-up and adjustment is the responsibility of the
retailer/homeowner and is not covered under warranty.
FURNACE START-UP CHECK LIST
Has roof jack crownbeen correctly installed?
Has furnace gas valve and burner orificebeen correctlycon-
vetted for Propane. gaswhere applicable?
Has furnace gas valve been de-rated for altitudesabove 2000
feet where applicable?
Is gas lineoutlet pressure properlyset for fuel type? (naturalgas
is 3.5" W.C.; Propane is 10"W.C.)
Is cross-overduct installed per home builderand UPG installa-
tion instructions?
Has furnace been operated througha complete heatingcycle?
Has the pilotflame been adjusted properly? (DGPH and DGPA
Models)
035-16328-002 Rav. C (0902)
Page 2

035-16328-002Rev.C(0902)
FURNACE SPECIFICATIONS
DGAA -- AUTOMATIC IGNITION -- WITH BUILT-IN COIL CABINET -- 4 TON - AIC READY
MODEL NO, Factor'/Equipped for use with Input/BTUH OutputJBTUH
DGAA056BDTA NATURAL GAS 56,000 45,000
DGAA07OBDTA NATURAL GAS 70,000 56,000
DGAAO77BDTA NATURAL GAS 77,000 62,000
DGAAO9OBDTA NATURAL GAS 90,000 72,000
DGPA -- STANDING PILOT -- WITH BUILT-IN COIL CABINET -- 3 TON - AIC READY
DGPA056ABTA NATURAL GAS 56,000 45,000
DGPA070ABTA NATURAL GAS 70,000 56,000
DGPA077ABTA NATURAL GAS 77,000 62,000
DGPA090ABTA NATURAL GAS 90,000 72,000
DGPH -- STANDING PILOT -- WITH BUILT-IN COIL CABINET -- 3 TON - NO AIC CONTROLS
DGPHO56ABTA NATURALGAS 56,000 45,000
DGPHO70ABTA NATURALGAS 79,000 66,000
DGPH077ABTA NATURALGAS 77,005 62,000
DGPH09OABTA NATURALGAS 90,000 72,000
DGAH -- AUTOMATIC IGNITION -- HEATING ONLY -- NO COIL CABINET
DGAH056BBSA
DGAHO77BBSA
Electdcal Power Supply
Thermostat Circuit
Nominal Anticipator Setting
I NATURALGASI 66,090I 45,006
Breaker or Fuse
Gas Valve Inlet
NATURAL GAS 77,000 62,000
ELECTRICAL SPECIFICATIONS
115 Volts - 60 Hz - 1 Phase
15 Arnp
24 Volt - 60 Hz - 40 VA
.50
1/2" NFPT
24-314"
DGAHSeries
FIGURE 1 : Furnace Dimensions
24-314"
19.1/2 °
19-1/2"
76"
5g=1/2"
DGPH, DGPA & DGAA Series
2 Unitary Products Group
Page 3

035-16328-002 Rev. C (0902)
GENERAL INFORMATION
NOTE: The words "Shall" or "Must" indicate a requirement
which is essential to satisfactory and safe product perfor-
mance.
The words "Should" or "May" indicate a recommendation
or advice which is not essential and not required but
which may be useful or helpful.
IMPORTANT - These instructions are primarily intended to
assist qualified individualsexperienced in the proper installa-
tion of heating and/or air conditioning appliances. Some local
codes require licensed installation service personnel for this
type of equipment. Read all instructions carefully before start-
ing the installation.
I_WARNING
I
Improper installation may damage equipment,
can create a shook hazard, and will void the war-
ran_
The furnace shall be installed so the electrical
components are protected from water
The furnace is not to be used for temporary heat-
ing of buildings or structures under construction.
Do not test the fuel system at more than 14
inches water column after fumace has been con-
nected to the fuel line. Such testing may void the
warren_ Any test run above 14 inches water col-
umn may damage the furnace control valve
which could cause an explosion, fire, or asphyxi-
ation.
INSTALLATION STANDARDS
CODECOMPLIANCE
The installer must comply with all local codes and regulations
which govern the installation of this appliance. Local codes
and regulations shall take precedent over these regulations
where applicable. In lieu of local codes, the appliance shall
be installed in accordance with one or more of the following
standards.
Manufactured homes in the U.S.A.:
1, Federal Manufactured Home Construction & Safety
Standard (HU.D. Title 24, Part 3280),
2. National Fuel Gas Code (ANSI-Z223,1, NFPA-54).
3. National ElectricalCode (NFPA 70).
Manufactured homes in Canada:
1, Natural Gas and Propane Installation Code (CAN/CSA
B149,1).
2. Canadian Electrical Code, Part 1 (CSA C22,1)
Recreational Vehicles in U.S.A.:
1. Standard on Recreational Vehicles (NFPA 1192, formerly
NFPA 501C).
2. National Electrical Code (NFPA 70).
Recreational Vehicles in Canada:
1,
Unit installationshall comply with current CSA standard
CAN/CGA-Z240.4.2 - Installation Requirements for Pro-
pane Appliances and Equipment in Recreational Vehi-
cles.
2. Unit electrical widng and grounding shall comply with
current CSA standard C22.2 No.148/CAN/CSA-Z240.6.2
- Electrical Requirements for recreational vehicles.
HIGH ALTITUDE INSTALLATION
For elevation above 2,000 feet, derate furnace input 4% for
each 1,000 feet of elevation above sea level. Derating is
accomplished by reducing the orifice size. See Derating
Chart for orifice size.
In Canada, for elevations from 2000 to 4500 feet derate by
reducing gas manifold pressure to 3.0" W.C. for natural gas
and 9.0" W.C. for LP gas.
IA CAUTIONj
• Never attempt to alter or modify thisfurnace orany
of its components.
• Never attempt torepair damaged or inoperable
components. Such action could cause unsafe opera-
tion, explosion, fire and/or asphyxiation.
• If a malfunction has occurred, or if you feel that the
furnace is not operating as it should, contact a quali-
fied service agency or gas utility for assistance.
MINIMUM FURNACE CLEARANCES
Access for servicing is an important factor in the location of
any furnace. A minimum of 24 inches should be provided in
front of the furnace for access to the heating elements and
controls. This access may be provided by a closet door or by
locating the furnace 24 inches from a facing wall or partition.
These furnaces are design certified for the following minimum
clearances from combustible material in alcove or closet
instanation
Table 1: MINIMUM CLEARANCES
CLOSET ALCOVE
BACK 0" 0"
SIDES 0" 0"
FRONT 6" 24"
TOP 2" 2"
ROOF JACK 0" 0"
DUCT 0" O"
Unitary Products Group 3
Page 4

035-16328-002Rev.C(0902)
RETURN AIR REQUIREMENTS
CLOSET INSTALLATIONS
Additional Requirements
Additionalrequirements for floor and ceiling returnsystem for
closet installed sealed combustion heating appliance are
given in the next paragraph.
Floor or Ceiling Return Air System
Listed in the next paragraph are the conditions to be met by
Manufactured Home Manufacturers to have U.L. acceptance
of in-floor or ceiling return air systems of closet installed
direct vent forced air heating appliances for Manufactured
Homes to be sold in the United States.
1. The return-air opening into the closet, regardless of loca-
tion, is to be sized not less than specified on the appli-
ance's rating plate.
2.
If the return-air opening is located in the floor of the
closet (versus the verticalfront or side wail), the opening
is to be provided with means to prevent its inadvertent
closureby a fiat object placad over the opening.
3.
The cross-sectional area ofthe return duct system (when
located in the floor or ceiling of the manufactured home)
leading into the closet is to be not less than that of the
opening specified on the appliance's rating plate.
4.
The total free area of openings in the floor or ceiling reg-
isters serving the return-air duct system is to be not less
than 150% of the size of the opening specified on the
appliance's rating plate. At least one such register is to
be located where likelihood of its being covered by car-
peting, boxes, and other objects is minimized.
5.
Materials located in the return duct system have a flame
spread classification of 200 or less.
6.
Non-combustiblepans having one-inch upturned flanges
are located beneath openings in the floor return duct
system.
7.
Wiring materials located in the return duct system con-
form to Article 300-22 (B&C) of the National Electrical
Code (NFPA-70).
8.
Gas piping is not run in or through the return duct sys-
tem.
9.
The negative pressure in the closet as determined by
test with the air-circulating fan operating at high heating
speed and the closet door closed is to be not more nega-
tive than minus 0.05-inch water column.
10.
For floor return systems, the manufactured home manu-
facturer or installer shallaffix a prominent marking onor
near the appliance where it is easily read when the
ctoset door isopen. The marking shall read:
_WARNING
HAZARD OF ASPHYXIATION, DO NOT COVER
OR RESTRICT FLOOR OPENING
AIR DISTRIBUTION SYSTEMS
For proper air distribution, the supply duct system shall be
designed so that the static pressure does not exceed the
listed static pressure rating on the furnace rating plate.
Three typicaldistdbution systems are illustratedin Figure 2.
Location, size and number of registers should be selected on
the basis of best air distribution and floor plan of the home.
The Air Temperature Rise is to be adjusted to obtain a tem-
perature dse within the range(s) specified on the furnace rat-
ing plate.
A
E
Singletrunkduct _ C
Dualtrunk duct with crossoverconnector
B*
Transitionduct
TransitionDuctwithBranches
Dualtrunk duct
Crossover
I
_r-..3
1.CrossoverDuctmust becentereddirectlyunder furnace.
2. Use12"DiameterRoundor insulatedFlex-ductonly.
3. TerminateFlex-duct(oppositefurnace) in the centerof the trunkduct.
4. Flex_uct matedalmust bepulledtight-- No Loopsor unnecessarydips-- Air Flowmay beimpeded.
FIGURE 2 : Air Distribution Systems
4 Unitary Products Group
Page 5

Return Air Grille Part No.
7900-287P/A * White
250 SQ. IN
MINIMUM
FREE AREA B
250 SQ. IN.
50 SQ LN FREE AREA
_ MINIMUM
FREE AREA
MINIMUM
FIGURE 3 : Closet To Door Clearance - 6" or Greater
250 SQ, IN
MINIMUM
t FREE AREA B
250 SQ. IN
MINIMUM
50 SQ IN.
MINIMUM
FREE AREA
FREE AREA
035-16328-002Rev.C(0902)
Furnace to Closet Door Clearance --
5 Inches or more
The closet door MUST have a minimum o1250 Square Inches
of free area inthe upper half of the door.
If opening for return airis located in the floor or sidewalls and
below the top of the furnace casing:
1. 6 inches minimum clearance must be provided on side
where return is located, and
2. 6 inches minimum clearance must be maintainedfrom the
Pont of furnace.
J_ i5_°_r _ac/_"t Return Air Closet Door Part No.
DOOR 7900-7771/C * White
Furnace to Closet Door Clearance --
Greater than 1 Inch and Up to 5 Inches
1. The closet door MUST have a minimum of 250 Square Inches
of free area in the upper half of the door and a minimum of
50 Square Inches of free area in the lower area ofthe door.
The lower closetdoor grille may be omitted if an undercut of
2-1/2 inches isprovided inthe door.
2. A fully Iouvered closet door MUST have a minimum of 250
Square Inches of free area in the upper half of the door.
As an optionto _e lower grill,
an undercut of 2-1/2" will provide
50 Square Inches of free area.
FIGURE 4 : Furnace To Closet Door Clearance - 1" To 6"
Furnace to Closet Door Clearance --
Less than 1 Inch
The closet door MUST have three return air gdlles. The
MINIMUM
FREE AREA
_i_ 250 SQ. IN
MINIMUM
50 SQ. IN.
FREE AREA
FIGURE 5 : Furnace To Closet Door Clearance - Less Than 1"
Unitary Products Group 5
total free area of the two upper grilles must be minimum
of 250 Square Inches. The total free area of the lower
gdlle MUST be a minimum of 50 Square Inches.
The grilles MUST BE ALIGNED directly opposite the
return air grille of the furnace door.
Page 6

035-16328-002Rev. C (0902)
ROOF JACK
AWARNING
Failure to follow aft venting instructions can result
in fire, asphyxiation, or explosion.
[AkCAUTION
Only use the appropriate roof jack. See Figures 6
& 7 for correct application.
Do not exceed the maximum height as deter-
mined from Figures 6 & 7. Installer should allow
an additional 1-1/2" travel before the flue pipe
assembly is fully extended against the built-in
stop. This provides an additional safeguard
against the flue assembly being pulled from the
roof jack during transportation or other stress
conditions.
EXISTING FURNACE REPLACEMENT
Ifthis furnace replaces an existing furnace, do the following:
f. If a 2nd roof, roof cop or addition has been made to the
existing roof of the home, remove the old roof jack com-
pletely! To avoid the possibility of an impropedy installed
pipe or gaps in the old roof jack, INSTALL A NEW ROOF
JACK. Your ceiling and roof height will determine the cor-
rect roof jack to use. Refer to the vent selection table, of
the furnace installation instructions.
2. After unpacking the roof jack, check the rain caps. Insure
they are not damaged, tilted or crooked. Do not twist,
crush or sit on the roof cape during installation. Damaged
roof cape will cause improper furnace operation. The fur-
nace will not heat properly and could result in explosion.
3. Before inserting the roof jack into the furnace top,
inspect the furnace flue and combustion air opening for
debris or insulation which might have fallen in during pre-
installation steps. Do not proceed unless all debris has
been cleaned out or removed.
4. After installing roof jack on furnace top collar, check to
make sure there is no gap in back or side between the
pipe collar and the furnace casing top.
5.
Use only the pipes provided with the roof jack assembly.
Do not add to or adapt other sheet metal pipes. Do not
cut, insert or add other pipes to this assembly.
6.
In no case should there be a gap between sections of
the flue pipe or the combustion air pipe. If necessary to
prevent excessive air leakage, the installer should seal
joints in the combustion air tube with aluminum type or
other suitable sealant.
NEW HOME INSTALLATION
Ifthis furnace is installedon a new home do the following:
1. Inspect the furnace top collars for signs of insulation or
ceiling debris which might have fallen in during cutting of
the ceiling and roof holes. Remove all debris before con-
tinuing.
2. After unpacking the roof jack, check the rain caps. Insure
they are not damaged, tilted or crooked. Do not twist,
crush or sit on the roof caps during installation. Damaged
roof cops will cause improper furnace operation. The fur-
nace willnot heat properly and could result inexplosion.
3. Before inserting the vent pipe into the furnace top,
inspect the furnace flue and combustion air opening for
debris or insulationwhich have fallen in during pre-instal-
lation steps. Do not proceed unless all debris have been
cleaned out or removed.
4.
After installing roof jack on furnace top collar, check to
make sure there is no gap in back or side between the
pipe collar end the furnace casing top. If necessary to
prevent excessive air leakage, the installer should seal
joints in the combustion air tube with aluminum type or
other suitable sealant.
INSTALLATION IN SNOW REGIONS
When the combustion air pipe inlet is covered or blocked with
snow, the furnace will not operate properly due to the
depleted combustion air supply.
Therefore, if the furnace will be located in regions where
snowaccumulation on the roof exceeds 7" or in H.U.D. Snow
Load Zones, a roof jack extension (Part No. 7680B6541) is
recommended.
LOCATING AND CUTTING ROOF JACK OPENING
To facilitate the proper installation of the roof jack, it is very
important that the roof jack opening in the ceiling and roof be
on the same vertical center line as the furnace flue collar. See
Figure 9.
Mark this location on ceiling and scribe a circle with a 5"
radius (10" diameter) around this mark. Cut opening for roof
jack through ceiling and roof. (If furnace was installed during
construction, cover furnace and flue opening to prevent
debris from entering flue when hole is cut for roof jack.)
INSTALLING ROOF JACK IN ROOF
(See Figure 6 & 7 for Dimensional requirements.)
Insert reef jack into opening inthe roof.
The roof jack should be secured to the furnace before roof
flange (flashing) is secured to the roof. This will insure a bet-
ter alignment of the flue pipe and furnace flue collar. Caulk
around and under roof flange to provide a water tight seal,
before secoring roof jack flashing to roof.
6 Unitary Products Group
Page 7

035-16328-002Rev. C (0902)
SWIVEL FLASHING
ADJUSTS FROM
0/12 TO 5/12 PITCH
4000-7101/C 4000-6101/A
4000-7121/C 4000-61211A
4900-7141/C 4000-6141/A
4900-7151/C 4000-6151/A
4900-7171/C 4009-6171/A
The 4084-7141 sd mens onally the same as 4000-7141/C and is avallab e on y In Canada.
2 ......
The 4084-7151 is dimensionally the same as 4000-7151/C and is available only in Canada.
FLUE
19 1/2"
GASES
CAULK
SLANT
FLASHING
3/12 PITCH
CAREFULLY CAULK ALL AROUND SWIVEL JOINT WITI-I • F_E S
SEALANT SUPPLIED By FURNACE MANUFACTURER, 1_ _ t
f _ _ _ I _- t COMBUSTION 19 1/2
DGAH FURNACES
INSTALLATION DIMENSIONS
"A"
ADJUSTABLE HEIGHT
7O"_ 79"
75" _ 86"
83"to 104"
90"_ 116"
127" _ 15T'
T.oEndo,U00e,Po.,ono,.oo,Jao,need ,oF
/. Not extend below the ceiling. _ __ _
DGPH, DGPA,& DGAAFURNACES
INSTALLATION DIMENSIONS
"B"
ADJUSTABLE HEIGHT
86" to 95"
91"to 102"
99"to 129"
106"to 132"
143" _ 173"
A B
59-1/2"
DGAH MODELS
, r -,iv ..... FLOOR _ 1 F
WARM AIR DUCT DUCT CONNECTOR DUCT CONNECTOR WARM AIR DUCT
FIGURE 6 : Standard Roof Jack
AND ROOF.
THIS ISTHE INSTALLER S RESPONSIBILITY = L_ __ __
76"
DGPH, DGPA,
DGAA, MODELS
/
Unitary Products Group 7
Page 8

035-16328-002Rev.C(0902)
I
SWIVEL FLASHING
ADJUSTS FROM
0/12 TO 5/12 PITCH
SLANT
FLASHING
3/12 PITCH
4000-8161/C I 4000-9161/A
4000-8181/C 4000-9181/A
AND ROOE
DGAH FURNACES
INSTALLATION DIMENSIONS
=A =
ADJUSTABLE HEIGHT
85" to 101"
99" to 129"
IMPORTANT
DGPH, DGPA, & DGAA FURNACES
INSTALLATION DIMENSIONS
"B"
ADJUSTABLE HEIGHT
101" to _17"
115" to 145"
CAULK
UNDER
FLASHING
ROOF
A
59-1/2"
DGAH MODELS
WARM AIR DUCT DUCT CONNECTOR
FIGURE 7 : Roof Jack With Removable Crowns
FLOOR
DGPH, DGPA,
DGAA, MODELS
DUCT CONNECTOR
B
76 II
WARM AIR DUCT
8 Unitary Products Group
Page 9

DUCT CONNECTORS
I .. - =
, , T. _
035-16328-002 Rev. C (0902)
I
DUCT CONNECTOR DIMENSIONS
DUCT CONNECTOR
PART NUMBER
7990-6011
7990-6021
7990-6041
7990-6061
7990-6071
7990-6081
7990_I01
7990-6121 I
FIGURE 8 : Duct Connector Dimensions
REARWALL
OFENCLOSURE CEILINGCUT-OUT
DUCT CONNECTOR
DEPTH
1"
2"
4-I/2"
6-1-2"
7-1/2"
8-1/2"
10-1/4"
12-!/4"
DUCT CONNECTOR DIMENSIONS
DUCT CONNECTOR
PART NUMBER
7990-6211
7990-6221
7990-6241
7990-6261
7990-6271
7990-6281
7990-6301
7990-6321
FLOORCUT-OUT
CONNECTOR
DUCTCONNECTOR FLOOR
L_ T
ouuuc
OPTIONAL GAS
SUPPLY DUCT
DUCT CONNECTOR
DEPTH
4-1/2"
6-1-2"
7-1/2"
8-1/2"
10-1/4"
I2-1/4"
s FLOOR
DEPTH JOIST
1"
2"
J
/
i ENTRANCE
-_ OFFURNACE
FUTUREREFRIGERANT
LINEENTRANCE
FIGURE 9 : Recommended Floor Cut-out
Unitary Products Group 9
20_ _ FLOOR
FIGURE 10 : Duct Connector Depth
Page 10

035-16328-002Rev. C (0902)
LOCATOR BRACKET
_ NAI L_,AFLEATHEAD SC REWS
FLOOR
SUPPLY DUCT
FIGUREtl : Duct Connector Screw Attachment
INSTALLATION OF SCREW A'B'ACHMENT DUCT
CONNECTOR
1,
Make floor cut out as shown in Figure 9.
2.
Determine the depth of the floor cavity from the surface
of the floor to the top of the supply air duct and select the
appropriate duct connector from the chart.
3.
Place locating bracket (supplied with the duct connector)
to the back edge of the flooropening. See Figure 11.
4.
Apply a water based duct sealant to the 1/2"supplyduct
attachment flange of the duct connector.
5.
Determine which of the four positions the duct connector
best centers over the supply duct and insert it through
the floor cutout.
6. When propedy aligned with the supply duct, secure the
duct connector to the floor with nails, flat head screws or
staples.
7. Use screws as required to secure the duct connector to
the supply duct.
8. Cut out the opening to the supplyduct. If sealant was not
used, the instaner should tape the mating flanges to pro-
vide s good air seal.
NOTE: Duct sealant and tape must be classified as
meeting HUD Standard 3280.715, U.L. Standard 181A.
If tape is used to provide a better air seal, it should be a type
approved by the applicable national or local codes.
NAILS, FLAT HEAD SCREWS
OR STAPLES
BEND TABS UNDER
OPENING TO
SECURE TO THE
SUPPLY DUCT
SUPPLY DUCT
FIGURE t2 : Duct Connector TabAttachment
INSTALLATION OF TAB ATTACHMENT DUCT
CONNECTORS
1. Make floor cut out as shown in Figure 9.
2. Determine the depth of the floor cavity from the surface
of the floor to the top of the supply air duct and select the
appropriate duct connector from the chart.
3. Place locating bracket (supplied with the duct connector)
to the rear of the floor area for the furnace. See Figure
12.
4. Determine which of the four positions the duct connector
best centers over the supply duct and insert it through
the floor cutout.
5. Mark cut-out location on the supplyduct and remove the
duct connector.
6. Cut out the opening to the supplyduct.
7. Bend tabs down through and back up under the supply
duct.
8. Secure the duct connector to the floor with nails, flat
head screws or staples.
The duct connector is designed for use on ducts down to 12"
in width. When using the connector on smaller width ducts,
there will not be sufficientclearance to bend the tabs on two
sides of the duct connector.
In such cases the tabs may be attached to the sides of the
duct by using sheet metal screws or other suitable fasteners.
Holes for sheet metal screws are provided inthree (3) tabs on
each side of the duct connector. If more than 3 tabs need to
be used to provide a more secure and air tight connection,
the remaining tabs can also be fastened to the duct with
screws after drilling the required screw holes.
10 Unitary Products Group
Page 11

035-16328-002Ray.C(0902)
LA,CAUTION]
FURNACE SEATED
AGAINST THE
LOCATOR BRACKET
SECUREFURNACE
\
FIGURE 13 : Installation of Furnace
TO FLOOR WITH
TWO NAILS OR
SCREWS.
INSTALLATION OF THE FURNACE
Remove the front panels and set the fumaca onto the
duct connector. Slide it back until the rear of the unit
engages the Iocator bracket.
2.
Secure the front of the furnace with two screws at the
mounting holes provided.
3.
Secure the top of the furnace to a structural member
using screw through the strap at the back of the furnace.
Strap may be moved to any of the holes located along
the top back of the furnace. Installer may provide an
equivalent method, such as screws through the casing
side.
The inner flue pipe must be present.
It is mandatory that the combustion air pipe and
flue pipe assembly be fully engaged. The com-
bustion air pipe MUST be securely fastened to
the furnace with a sheet metal screw in the hole
provided.
Use a 1/2" blunt or sharp end sheet metal screw
to fasten roof jack combustionair pipe to furnace
combustion air colla_ Screw hole is provided in
the pipe and collar Excessively long screws may
extend to flue pipe and puncture it. Screws are
not to exceed 1 1/2"in length.
NOTE: Combustion air tube and flue pipe are part of the
same assembly. Only the combustion air tube need be fas-
tened to the furnace.
1. Check to be certain that the flue pipe and combustion air
tube are present.
2.
Pull the telescoping flue tube and combustion air tube
assembly down from the roof jack. Slide the flue tube/
combustion air tube assembly down firmly over the fur-
nace flue outlet and combustion air cellar. Insure thatthe
back, side and front of combustionair tube collar is fully
engaged and is in contact with gasket, Fasten the com-
bustion air tube to the furnace combustion air collar
usinga 1/2 inchsheet metal screw. (Screw hole provided
in combustionair tube and fumaca combustionair collar.
See Figure 14.
COMBUSTION
It ismandatory that the combustion air and flue tube assembly
be fully engaged at back sides and front, and combustion air
SECURE STRAP
TO WALL_
FRONT OF
FURNACE
FIGURE 14 : Connecting Roof JAck to Furnace
Unitary Products Group 11
tube securely fastened to the fumace with a sheet metal screw
in the screw hole provided,
COMBUSTION
#8 OR #10 SCREW RECOMMENDED
Page 12

035-16328-092 Rev. C (0902)
CEILING RINGS
The coiling ring is to meet fire stop requirements. Accessory
Ceiling Ring (PIN 7660-2841) may be used, (See Figure 15)
or the manufactured home manufacturer or the installer may
use other approved methods to stop fire.
If required, three (3) sections of Accossory Ring may be used
as shown in Figure 15 to provide closer clearance around 3.
roof jack,
A B
FIGURE 15 : Ceiling Rings
ELECTRICAL WIRING
IlIACAUTIiQN
TO INSTALLER: Incoming power must be polar-
ized. Observe color coding.
AWARNING!
SHOCK HAZARD - DISCONNECT ELECTRI-
CAL POWER SUPPLY TO THE UNIT BEFORE
SERVICING TO AVOID THE POSSIBILITY OF
SHOCK INJURY OR DAMAGE TO THE EQUIP-
MENT
A separate 115 _/A.C. supplycircuitmust be used for the fur-
CONNECT THERMOSTAT WIRES
1. Insert24 voltwires throughthe small plastic bushing just
above the control panel.
2.
Connect the thermostat wires to the furnace low voltage
pigtails. See Figure17 (heating only) and Figure 18
(heating and cooling).
Connect low-voltage circuit to the wall thermostat pig-
tails.
NOTE: Five-conductorthermostat cable is recommended for
all installations to allow easy installation of an air conditioning
system at a later time.
Eighteen gauge thermostat wire is highly recommended.
Smaller gauge thermostatwire may be usedonly ifthe guide-
linebelow isfollowed.
THERMOSTAT WIRE
LENGTH (FURNACE TO
THERMOSTAT)
0 - 45 feet
0 - 70 feet
Do not use thermostat wire smaller than 22 gauge. Ifthermo-
stat wire smaller than 18 gauge is used, pay particular atten-
tion that the connections between the different wire sizes are
tight.
Operational problems may be caused by loose connections
or by the use of thermostat wire that is too small to carry the
required load. Any such problems are the responsibility of the
installer.
naco. The circuit shouldbe protected by a 15 amp fuse or cir-
cuit breaker.
THERMOSTAT
WlRE GAUGE
22
20
J
CONNECT POWER SUPPLY WIRES
1. Remove the field wiringcover.
2, Insert 115 volt wires through the large plastic bushing on
the left side of the furnace (See Figure 16). If conduit is
used it should be secured to the control box.
3.
Connect the "hot" wire to the BLACK pigtail lead, and the
"neutral" wire to the WHITE pigtail lead. Secure all con-
THIS SCREW DOES
NOT NEED TO BE
REMOVED IN ORDER
TO REMOVE THE
FIELD WIRING COVER.
(JUST LOOSEN).
NOTE:
Cover should
not be removed
except when
servicing the
controls.
nections with suitable wire nuts and wrap with electrical
tape.
4. Connect the "ground" wire to the grounding screw.
a
5. Reinstall the control panel cover and secure mounting
screw,
FIGURE 16 : Field Wiring
12 Unitary Products Group
Page 13

WALL THERMOSTAT
Avoid locations where the thermostat could be subject to
drafts from outside, or exposed to direct light from lamps,
sun, fireplaces, etc., or affected by air from a duct register
blowing directly on the thermostat.
The wall thermostat should be located 52 to 66 inches above
the floor. The preferred location is on an inside wall situated
in an area with good air circulation, and where the tempera-
ture will be reasonably representative of other living areas the
thermostat is controlling.
NOTE: In order to provide proper ventilation control when
using DGPH model furnaces with Coleman Blend
Air ventilation systems, it is required that a 4-wire
wall thermostat and Blower Relay Kit 7900-7761 be
installed,
BLEND AIR
CONTROL BOX
035-16328-002Rev. C (0902)
FURNACE
CONTROL
BOX
FIGUREt7 : Wiring for Heat Only Thermostat
E
;
FURNACE
CONTROL
BOX
WALL THERMOSTAT
FIGURE 18 : Wiring for Heat-Cool Thermostat
WHITE
Q
NOTFACTORYINSTALLED
Unitary Products Group 13
Page 14

035-16328-002 Rev. C (0902)
WIRING DIAGRAMS
If" B!OWER
MOTOR
BLK
MANUAL RESET
LIMIT SWITCH
_c_ w
LN
02
03
-c 4
05
06
07
°11
4 8
ORG ____ __Z
WHT
3 AMP FUSE
GND.
SCREW
24V SEC.
120V PRI.
I INE
TRANSFORMER
SWITCH
ORG (_
o
AUTO
RESET
ORG LIMIT
SWITCH
FAN
GRY
E
NEU. ., WHT
..... .
W R
WALL "lit.... L
THERMOSTAT
FIGURE 19 : Wiring Diagram for DGPH056, DGPH070, DGPH077
NOTE: in order to provide proper ventilationcontrolwhen using DGPH model furnaces with Coleman BlendAir ventilation sys-
tems, it is required that a 4,-v,'irewallthermostat and Blower Relay Kit 7900-7761 beinstalled.
14 Unitary Products Group
LI " BLK
_. GND.
TO EARTH GND. Q SCREW
SYSTEM GAS
SWITCH CONTROL
Page 15

COMBUSTION
BLOWER
RELAY
035-16328-002 Rev. C (0902)
o2
o3
-o 4
o5
o6
o7
WHT
MANUAL RESET
LIMIT SWITCI
[_ WHT
i
:{_]_ RED
I, W'
i
WALL qt @ GNO.
THERMOSTAT TO EARTH GND. SCREW
O1
_8
3 AMP FUSE
NEU, WHT SWITCH
ORG
TRANSFORMER
WHT
BLU
BRN
_/ o 1
LI BLK
iv. BLK _3
GND.
SCREW
LOAD
24V SEC.
120V PRI.
ORG
WHT
SYSTEM
FAN
SWITCH
AUTO RESET
LIMITSWITCH
PRESSURE
SWITCH _
GAS
CONTROL
FIGURE 20 : Wiring Diagram for DGPH090
NOTE: In order to provideproper ventilationcontrolwhen using DGPH modelfurnaces with Coleman Blend Air ventilationsys-
tems, it is required that a 4-wire wall thermostat and BlowerRelay Kit 7900-7761 be installed,
Unitary Products Group 15
Page 16

035-16328-002 Rev. C (0902)
! I
BLOWER
MOTORI_
BLK
MANUAL
t
I BLEND-AIR
I CONTROL BOX
[ (IF EQUIPPED
i
, , . i
i
i
i
, i
[_]i BLK
i' LUl
b r
• 1 AIC
• J CONTACTORI
, L ...... J
RESET
i
{ LIMIT
] SWITCH
I
GRN
WHT
RED
i CONDENSING
I UNIT
2°_w_ .,vAc
WALL "lit
THERMOSTAT
K
4 I
s :_g
6
7
9
{_i
TO EARTH GND.
ORG
WHT
3 AMP FUSE
NEU. _ WHT
i'_
LI _ BLK
!
€ BLOWER
RELAY
l
TRANSFORMER
GRY
LOAD
24V SEC.
-
I LINE
E
Q GND.
SCREW
ORG
ORG
..._ s°c%w
>-
BRN
BLU
WHT
SYSTEM
SWITCH
BLK Oo_3
FAN
SWITCH
©
AUTO
RESET
LIMIT
SWITCH
GAS
CONTROL
FIGURE21 :Wiring Diagram for DGPA056, DGPA070, DGPA077
16 UnitaryProducts Group
Page 17

035-16328-002 Rev. C (0902)
BLOWER
MOTOR
WHT
BLEND AIR !
CONTROL BOX I LIMIT
(IF EQUIPPED) I SWITCH
_}_ GRN
I
Z
MANUAL
RESET
i_ WriT
i_ RED
' I_ BLK
, F
-I AJC l
I CONDENSING I
I UNIT I
W, -J' L .......
CONTACTOR I
G°°°:]wR ,,,VAt
WA,, "lit L
THERMOSTAT
ORG
_2 _,
_5
)6
'1
81
2N
RED
3 AMP FUSE
NEU. WHT
LI BLK
:J
TO EARTH GND,
/ ORG
COMBUSTION
BLOWER
RELAY
GRY m
A/C
BLOWER :).
RELAY EW
TRANSFORMEEp120V24VLOADSE(pR I
_,._
GND.
_ SCREW
ORG
BLK
IT O _
/
WHT
©
AUTO RESET
LIMIT SWITCH
PRESSURE _
SWITCH
SYSTEM SWI_
°°_ 3 GAS
FAN
SWITCH
CONTROL
zl.-
oo
m_
FIGURE22 : Wiring Diagram for DGPA090
Unitary Products Group 17
Page 18

035-16328-002Rev.C(0902)
UPPER
I LIMIT SWITCH
BLU
CRY
ORG
LIMIT
Q OWER
SWITCH
WALL
THERMOSTAT
TO A]C
CONDENSING
UNIT (if equipped) ............
ERL_ WHT
BLOW RED
MOTOR
I I
__,J
I TO EARTH GROUND
I
115
VAC L1
NEUTRAL
RED
BLK
m O
o o
BLK I
RED
WHT
o
ca L o; WHT
GROUND
SCRI
.... _A D-_
BRN
BRN
X
o
TRANSFORMER VAC
7
SYSTEM
SWITCH
BLK
BLK
BLK
WHT
WHT
i
YEL
©
COMBUSTION AIR
SWITCH
Or-o
O_w
;i3mc
5
Z
i c---..--
I GAS
IVALVE
_----.--
INCOMING POWER MUST BE POLARIZED.
OBSERVE COLOR CODING.
HOT SURFACE
IGNITOR
FIGURE23 : Wiring Diagram for DGAA and DGAH Models
18 Unitary ProductsGroup
Page 19

GAS PIPING
INSTALLATION AND CHECKING OF GAS LINE
Gas Supply piping must be sized in accordance with the rec-
ommendations contained in National Fuel Gas Code (ANSI-
Z223.1, NFPA-54) unless local codes or regulations state oth-
erwise.
Matedals used and pipe sizing for U.S. manufactured homes
must comply with requirements contained in Manufactured
Homes Al19.1, Recreational Vehicles Al19.2 and H.U.D.
Title 24, Section 3280.705 and any local or state codes.
NOTE: The gas line inlet on the gas valve is 1/2-14 N.ET
The gas line may be installed through the furnace floor or fur-
nace side to the gas valve.
F& CAUTION
To install gas line and to connect it to the gas
valve, care must be taken to hold gas valve firmly
to prevent misalignment of the bumer orifice, or
to damage gas valve which could result in
improper heating, explosion, fire or asphyxiation.
DO NOT USE EXCESSIVE PIPE SEALANT ON
PIPE JOINTS. Pipe sealant, metal chips or other
foreign material that could be deposited in the
inlet of the gas valve, when gas pipe is installed
or carried through the gas piping into the gas
valve inlet after installation, may cause the gas
valve to malfunction and could result in possible
improper heating, explosion, fire or asphyxiation.
Also, pipe sealant must be resistant to Propane
gas.
Where regulations require, a main shut-off valve
shaft be installed externally of furnace casing.
After piping has been installed, turn gas on and
check aft connections with a leak detector or
soap solution.
Never use open flame to test for gas leaks as
fire or explosion could occur.
Do not test the fuel system at more than 14" HZC.
after furnace has been connected to fuel line.
Such testing could void the warranty. Any test run
above 14" WC. may damage furnace control
valve which could cause an explosion, fire or
asphyxiation.
I CAUTION!
If the gas input to the furnace is too great
because of excessive gas pressure, wrong size
orifice, high altitude, etc., the burnerflame will be
sooty and may produce carbon monoxide, which
could result in unsafe operation, explosion, and/
or fire or asphyxiation.
A dirt leg may be required by some local cedes to trap mois-
ture and contaminations.
035-16328-002 Rev. C (0902)
For natural gas operation, the furnace is designed for 7" W.C.
inlet gas pressure. Pressure to main burner is then reduced
to 3 1/2" W.C.
For Propane gas operation, the furnace is designed for 11"
W.C. inlet gas pressure. Pressure to main burner is then
reduced to 10" W.C.
IMPORTANT - When converting gas valve from or to Pro-
pane gas, it will be necessary to change main burner orifice
to prevent an underfired or overfired condition. See label
inside lower furnace door for complete instructions.
Pilot Adjustment
On models equipped with standing pilot ignition, the pilot
should be adjusted so that the flame is approximately 1" in
height (500 BTU / hr.). This will allow proper burner ignition
without excessive fuel usage. The pilot adjustment screw is
located on the top of the gas valve.
Observing Burner Operation
1,
Observe burner to make sure it ignites. Observe color of
flame. On natural gas the flame will burn blue with appre-
ciably yellow tips. On Propane gas a yellow flame may
be expected. If flame is not the proper color call a quali-
fied service technician for service.
2,
Let furnace heat until blower cycles on.
3.
Turn thermostat down.
4.
Observe burner to make sure it shuts off.
5.
Let the furnace cool and blower cycle off.
kWARNING]
Should overheating occur, or the gas supply fail
to shut off, shut off the manual gas valve to the
furnace and allow bomer to run until furnace
cools down and blower shuts off before shutting
off the electdcal supply.
If any abnormalities are observed when checking for correct
operation, such as burner failing to ignite or to turn off, sooty
flame, etc., call your nearest authorized service technician as
shown in the Service Center List included in the home owner
envelope with the furnace.
If Furnace Fails to Operate Properly
1.
Check setting of thermostat - and position of HEAT/
COOL switch if air conditioning is installed. If a set-back
type thermostat is employed be sure that the thermostat
is in the correct operating mode.
2.
Check to see that electrical power is ON.
3.
Check to see that the knob or switch on the gas control
valve is in the full ON position.
4.
Make sure filters are clean, return gdfies are not
obstructed, and supply registers are open.
5.
Be sure that furnace flue piping is open and unob-
structed.
If the cause for the failure to operate is not obvious, do not
attempt to service the furnace yourself. Call a qualified ser-
vice agency or your gas supplier.
Unitary Products Group 19
Page 20

035-16328-002Rev.C(0902)
FINAL PROCEDURE
INSTALL FURNACE DOORS
Install the lower door first by slidingthe bottom of the door
down until the tabs on the casing base engage the slots in the
bottom door end cap. Then push the top of the lower door in
until the door clips snap into place. Install the upper door in a
similarmanner, first engaging the slots inthe top of the upper
door on the tabs on the casing top. Then snap the bottom of
the upper door into place against the casing.
FINISH AND TRIM
Alcove and Closet Installations may now be finished and
trimmed as necessary.
/ AUTOMATIC
DAMPER
FURNACE AND AIR CONDITIONER
INSTALLATIONS
Ifan air conditioner is installed which does not use the blower
for air distribution and operates completely independent of
the furnace, the thermostat system must have an interlock to
prevent the furnace and air conditioner from operating at the
same time. This interlock system usually contains a heat-cool
switch which must be turned to either HEAT or COOL to acti-
vate either heating or cooling operation, or a positive OFF
switch on the cooling thermostat.
When used in connection with a cooling unit the furnace shall
be installed parallel with or on the upstream side of the cool-
ing unit to avoid condensation inthe heat exchanger.
For installations with a parallel flow arrangement, the furnace
must be equipped with a damper to prevent cold air from
being discharged up around the heat exchanger. Cold air
causes condensation inside the exchanger and can cause it
to rust out which can allow products of combustion to be cir-
culated into the living area by the furnace blower resulting in
possible asphyxiation. An air flow activated automatic
damper, PIN 7900-6771, is available from furnace manufac-
turer. See Figure 24.
NOTE: See label on coil panel for conversion and lighting
instructions. Obtain a temperature rise within the ranges
specified on the name plate.
FURNACE
BASE
DUCT
CONNECTOR
NOTE: FOR BEST AIR DELIVERY INSTALL DAMPER
WITH BLADES PARALLEL TO SUPPLY DUCT.
FIGURE 24 : Anti-Backflow Damper
20 Unitary Products Group
Page 21

035-16328-002Rev. C (0902)
HIGH ALTITUDE DERATION CHART
NATURAL GAS
Elevation
Sea Level
2,000
3,000
4,000
5,000
6,000
7,000
8,000
9,000
10,000
Elevation Orifice Ddll Pa_ # Odfice Ddll Pad# Orifice Drill Odfice Ddll
Sea Level 0.082 48 9951--0821 0.093 42 9951-0931 0.098 40 9951_-0981 0.106 36 9951-1061
2,000 0.081 46 9951--0811 0.093 42 9951-0931 0.096 41 9981-0961 0.104 37 9951--1041
3,000 0.078 47 9951--0781 0.089 43 9951-0891 0.093 42 9951-0931 0.101 38 9951--1011
4,000 0.078 47 9951--0781 0.089 43 9951--0891 0.093 42 9951--0931 0.101 38 9951-1011
5,000 0.078 47 9951--0781 0.089 43 995%-0891 0.093 42 9951--0931 0.099 39 9981--0991
6,000 0.076 48 9981--0761 0.086 44 9951--0861 0089 43 9951--0891 0.098 40 9951--0981
7,000 0.076 48 9951--0761 0.086 44 9951--0861 0.089 43 9951--0891 0.096 41 9951-0961
8,000 0,073 49 9951--0731 0.082 45 9951--0821 0.086 44 9951--0861 0.096 41 9951-0961
9,000 0.073 49 9951--0731 0.081 46 9951-0511 8.086 44 9951--0881 0.093 42 9951--0931
10,000 0.070 50 9951--0731 0.078 47 9951--0781 0.082 48 9951-6821 0.059 43 9981-0891
Table shows 4% Input Reduction per 1,000 feet Elevation. For Canadian high altitude (2000 - 4500 feet), reduce gas
Reference Source: NFPA No. 54, ANSI Z 223.1, National manifold pressure to 3.0" W.C. for natural gas, 9,0"
Fuel Gas Code. W.C. for Propane gas.
56,000--lnput
Odfice Drill
Dia. Size
0.136 29 9951-1361
0.136 29 9981--1361
0.128 30 9981--1281
0.128 30 9951--1281
0.128 30 9951-1281
0.128 30 9951-1281
0.129 31 9951--1291
0.120 31 9951-1201
0.120 31 9951_-1201
0.116 32 9951--1161
56,000--Input 70,000--Input 77,000--Input 90,000--Input
Dia. Size Dia. Size Dia. Size Pa_ # Dia. Size Pa_ #
Pa_ #
70,000--Input
Odfce Dnll
Dia. Size
0,154 23 9951--1541
0.149 25 9951--1491
0,149 25 9951--1491
0,147 26 9951-1471
0,144 27 9951-1441
0.144 27 9951-1441
0.140 28 9951--1401
0.136 29 9951--1361
0.136 29 9951--1361
0.128 30 9951--1281
Pa_ #
PROPANE GAS
77,000--Input 90,000--Input
Odfice Ddll Odfice Ddll
Dia Size Dia. Size
0.161 20 9951--1611 0.180 15 9951-1801
0.157 22 9951-1571 0.177 16 9951--1771
0.157 22 9951-1571 0.173 17 9951--1731
0.154 23 9951=1541 0.173 17 9951--1731
0.152 24 9951-1521 0.169 18 9951--1691
0.149 25 9951--1491 0.166 19 9981--1661
0.147 26 9951--1471 0.161 20 9951-1611
0.144 27 9951--1441 0.161 20 9951--1611
0.140 28 9951--1401 0.157 22 9951-1571
0.136 29 9951--1361 0.152 24 9951-1521
Pa_ # Pa_ #
Unitary Products Group 21
Page 22

035-16328-002Rev.C(0902)
REPAIR PARTS LIST
DGAA056BDTA DGPA056ABTA
DGAA070BDTA DGPA070ABTA
DGAA077BDTA DGPA077ABTA
DGAA090BDTA DGPA090ABTA
_ _HEAT/COOLHEATONLY __'_
DGAH056BBSA DGPH056ABTA
DGAH077BBSA DGPH070ABTA
DGPH077ABTA
DGPH09OABTA
i DGAA,DGAH
L DGP_ DGPH
®
[] /
3--"
"4
DGAA, DGAH DGPA, DGPH
I
CONTROL BOX DETAIL
22 Unitary Products Group
Page 23

035-16328-002Rev. C (0902)
DGAA
ITEM DESCRIPTION DGAA056BDTA DGAA070BDTA DGAA077BDTA DGAA09OBDTA
Switch, Pressure 024-27666-000 024-27666-000 024-27666-000 024-27666-000
2 Tubing Silicone (2' Req'd) 028-11957-000 028-11957-000 028-11957-000 028-11957-000
LimitSwitch, Manual(Upper) 025-35358-000 026-35358-000 025-35356-000 025-35358-009
4 Assembly, Booster (w/Motor) 373-19801-820 373-19801-820 373-19801-820 373-19801-820
Control Board, Integrated 031-01932-000 031-01932-000 031-01932-000 031-01932-000
6 Valve, Gas 7990-328P 7990-328P 7990-328P 7990-326P
7 Bracket, Valve 073-19801.664 073-19801-064 073-19801-064 073-19601-064
8 Thermostat (Heat/Cool) Accessory (See Page 6)
9 Exchanger, Heat (w/Gaskets) 373-19804-651 373-19805-651 373-19806-651 373-19806-650
10 Sensor, Flame 025-35354-000 025-35354-000 025-35354-000 025-35354-000
Switch, System 7681-3301 7681-3301 7681-3301 7681-3301
Transformer (115-24V, 40 VA) 2940A3541 2940A3541 2940A3541 2946A3541
Switch, Limit 025-35380-000 625-35380-000 025-35381-090 025-35381-000
14 Burner Assembly, Auto Ignition 373-19801-403 373-19801-403 373-16801-403 373-19801-403
Includes items 10 & 15)
15 Ignitor, Hot Surface 1474-052P 1474-052P 1474-052P 1474-052P
16 Filter (2 Req'd) (16x20x1) 1214-2511 1214-2511 1214-2511 1214-2511
17 Panel, Door (Upper) Accessory (See Page 6)
18 Panel, Door (Lower, Tall) 373-19801-740 373-19801-740 373-19801-740 373-19801-740
Motor (See note 2) 1468-220P _468-220P 1468-220P 1468-220P
29 Assembly, Motor Mount (See Note 3) 373-19606-190 373-19806-100 373-19806-100 373-19806-100
21 Plug, Connector 025-21192-000 025-21192-000 025-21192-000 025-21192-000
Capacitor, Run (See Note 3) 024-20063-000 024-20063-006 024-20063-000 024-20063-000
23 Wheel, Blower 1472-2761 1472-2761 1472-2761 1472-2761
Relay, Fan .........
26 Relay, Booster ...........
Switch, Fan ........
27 Thermocouple ...........
28 Burner, Pilot ...........
29 Tube, Pilot .......
30* Diagram, VVidng 036-15289-001 035-15289-001 035-15289-601 035-15289-001
NOTE: *Not Shown
New replacement parts shown in bold face type at the first pdnting of parts list dated 9/02.
Ma_or components and suggested stocking items are shown with shaded ilem number
"<=Across from row indicates a change in that row.
--- Not applicable to specified model.
2. For Sedal Numbers lower then 001207164- Replacement DGAA motors also require Motor Mount
Assembly 373-19806-100 if replaced motor has integral, flex-arm motor mount.
3 DGAA wffh 5-Ton Blowers are provided as an accessory item and are nat standard equipment from
the faatony. See Page 6
Unitary Products Group 23
Page 24

035-16328-002 Rev. C (0902)
DGAH
ITEM DESCRIPTION
Switch, Pressure
2 Tubing Silicone (2' Req'd)
LimitSwitch,Manual(Upper)
4 Assembly, Booster (w/Motor)
Control Board, Integrated
6 Valve, Gas
7 Bracket, Valve
8 Thermostat (Heat/Cool)
9 Exchanger, Heat (w/Gasketa)
19 Sensor, Flame
_ Switch, System
Transformer (115-24V, 40 VA)
Switch, Limit
14 Burner Assembly, Auto Ignition
Includes iternss 10 & 15)
15 Ignitor, Hot Surface
16 Filter (2 Req'd) (16x20×1)
17 Panel, Door (Upper)
18 Panel, Door (Lower, Short)
Motor (See Note 3)
29 Assembly, Motor Mount
21 Plug, Connector
Capacitor, Run
23 Wheel, Blower
Relay, Fan
25 ! Relay, Booster
Switch, Fan
27 Thermocouple
28 Burner, Pilot
29 Tube, Pilot
30* Diagram, Vvldng
NOTE: *Not Shown
New replacement parts shown in bold face type at the first printing of parts list dated 9/02.
Major components and suggested stocking items are shownwith shaded item number,
"<=Across from row indicates a change in that row
-- Not applicable to specified model.
DGAH056BBSA
024-27666-000
028-11957-000
025-35358-000
373-19801-820
031-01932-006
7990-328P
073-19891-064
AP._essory (See
373-19804-651
625-35354-000
7661-3301
2946A3541
025-35380-090
373-19891_-93
1474-952P
1214-2511
DGAH077BBSA
024-27666-600
028-11957-000
025-35358-009
373-19601420
031-61932-069
7999-328P
073-19801-064
Page 6)
373-19806-651
025-35354-000
7681-3391
2940A3541
925-35381-900
373-19861-493
1474-052P
1214-2511
Accessory(See Page 6)
373-19801-790 373-19801-790
024-31948-009 924-31948-900
025-21192-000 025-21192-000
1472-2761 1472-2761
035-15289-901 035-15269-901
3. DGAH with 5-Ton Blowers are provided as an accessory item and are notstandard equipment from
the factory. See page 6.
24 Unitary Products Group
Page 25

035-16328-002Rev.C(0902)
DGPA
ITEM DESCRIPTION DGPA086ABTA DGPA070ABTA DGPA077ABTA DGPA090ABTA
Switch, Pressure ....... 024-27666-000
2 Tubing Silicone (2' Req'd) ........ 028-11957-000
LimitSwitch,Manual(Upper) 025-35358-000 025-35358-000 025-35358_000 025-35358-000
4 Assembly, Booster (w/Motor) ........ 373-19601-820
Control Board, Integrated ..........
6 Valve, Gas 7956-336P 7956-336P 7956-336P 7956-336P
7 Bracket,Valve 073-19801-064 073-19601-064 073-19801-064 073-19801-064
8 Thermostat (Heat/Cool) Accessory (See Page 6)
9 Exchanger, Heat (w/Gaskets) 373-19804-651 373-19805-651 373-19806451 373-19806-650
10 Sensor, Flame ..........
Switch, System 7681-3301 7681-3301 7681-3301 7681-3301
Transformer (115-24V, 46 VA) 2940A3541 2940A3541 2946A3541 2940A3541
Switch, Limit 025-35380-000 025-35380-069 025-35381-000 925-35381-000
14 Standing Pilot, Burner Assembly 373-19801-401 373-19801-401 373-19801-401 373-19801*402
Includes items10 & 15)
15 Ignitor, Hot Surface ........
16 Filter (2 Req'd) (16x20xl) 1214-2511 1214-2511 1214-2511 1214-2511
17 Panel, Door (Upper) Accessory (See Page 6)
18 Panel, Door(Lower, Tall) 373-19801-740 373-19801-746 373-19801-740 373-19801-740
Motor (See Note 3) 024-31948-000 024-31948-000 024-31948-000 024-31949-900
20 Assembly, Motor Mount ..........
21 Plug, Connector 028-21192-000 025-21192_000 028-21192-000 025-21192-000
Capacitor, Run ..... 024-20045-000
23 Wheel, Blower 1472-2761 1472-2761 1472-2761 1472-2761
Relay, Fan 3110-3301 3116-3301 3119-3391 3110-3301
25 Relay, Booster ....... 3110-3301
Switch, Fan 7975-3281 7975-3281 7975-3281 7975-3281
27 Thermocouple 7945-3481 7945-3481 7945-3481 7945-3481
28 Burner, Pilot 9680-0141 9880-0141 9880-0141 9880-0141
29 Tube, Pilot 029-22188-600 029-22188-000 029-22168-006 029-22188-960
30* Diagram, tA_dng 035-15287-001 035-15287-001 035-15287-001 035-15288-001
NOTE: *Not Shown
New replacement pa_s shown in bold face type at the first pdnting of parts list dated 9/02
Major components and suggested stocking items are shownwith shaded item numbe_
"<" Across from row indicates a change in that row.
-- Not applicable to specJfiedmodel.
3. DGPA with 4 or S-Ton Blowers are provided as an accessory item and are notstandard equipment
from the factory See Page 6
Unitary Products Group 25
Page 26

035-16328-002Rev.C(0902)
DGPH
ITEM DESCRIPTION
Switch, Pressure
2 Tubing Silicone (2' Req'd}
LimitSwitch,Manual(Upper)
4 Assembly, Booster (w/Motor)
Control Board, Integrated
6 Valve, Gas
7 Bracket, Valve
8 Thermostat (Heat Only)
9 Exchanger, Heat (w/Gaskets)
10 !Sensor, Flame
Switch, System
Transformer (115-24V, 40 VA)
Switch, Limit
14 Standing Pilot, Burner Assembly
Includes items 10 & 15)
15 Ignitor, Hot Surface
16 Filter (2 Req'd) (16x2Ox1)
17 Panel, Door (Upper)
18 Panel, Door (Lower, Tall)
Motor (See Note 3)
20 Assembly, Motor Mount
21 Plug, Connector
Capacitor, Run
23 Wheel, Blower
Relay, Fan
25 Relay, Booster
26 Switch, Fan
27 Thermocouple
28 Burner, Pilot
29 Tube, Pilot
30 Diagram, Wiring
DGPH056ABTA
025-35358-000
7956-336P
073-19801-064
373-19504451
7970-3331
2940A3541
025-35380-000
373-19801401
1214-2511
373-19801-740
024-31948-000
025-21192-000
1472-2761
7975-3281
7945-3481
9880-0141
029-22188-000
035-15285-001
DGPH070ABTA DGPH077ABT/
025-35358-000 025-35358-000
7956-336P 7956-336P
073-19801-064 073-19801-064
Accessory (See Page 6)
373-19805_651 373-19806451
--- n_
7970-3331 7970-3331
2940A3541 2940A3541
025-35380-000 025-35381-000
373-19801-401 373-19801401
1214-2511 1214-2511
Accessory(See Page 6)
373-19801-740 373-19801-740
024-31948-000 024-31948-000
--- _.
025-21192-000 025-21192-000
__=
1472-2761 1472-2761
7975-3281 7975-3281
7945-3481 7945-3481
9880-0141 9880-0141
029*22185-000 029-22188-000
035-15285-001 035-15285-001
DGPH090ABTA
024-27666-000
028-11957-000
025-35358-000
373-19801-820
7956-336P
073-19801-064
373-19806-650
7970-3331
2940A3541
025-35381-000
373-19801-402
1214-2511
373-19801-740
024-31949-000
025-21192-000
024-20045-000
1472-2761
3110-3301
7975-3281
7945-3481
9880-0141
029-22188-900
035-15286-001
NOTE: *Not Shown
New replacement parts shown in bold face type at the first printing of parts list dated 9/02.
Major components and suggested stocking items are shown with shaded item numpen
"<=Across from row indimate$ a change in that row.
-- Not applicable to specified model.
3. DGPH with 4 or 5-Ton Blowers are provided as an accessory item and are not standard equipment
from the factory. See page 6.
26 Unitary Products Group
Page 27

035-16328-002 Rev. C (0902)
BURNER ORIFICE CHART (Normal Altitude Only 4)
MODEL 056 070 077 090
NATURAL GAS 9951-1361 9951-1541 9951-1611 9951-1801
LP GAS 9951-0821 9951-0931 9951-0981 9951-1061
NOTES
4, Contact Customer Service for installations at altitudes over 2000 feet above sea level.
=<=Across from row indicates a change in that row.
ACCESSORY PARTS LIST
DESCRIPTION DGAA DGAH DGPA DGPH
Thermostat (Heat/Cool) 025-38251-000 026-38261-000 025-38251-000 ---
Thermostat (Heat Only) ...... 028-38252-000
Door Panel (Upper) 373-19802-010 373-19802-010 373-19802-010 373-19802-010
4-Ton Blower Ass' Motor ..... 1468-220 1468-220
7900-7741/A Run Capacitor (7.5 MFD) -- -- 024-32020-000 024-32020-000
Motor Mount ..... 373-19806-100 373-19806-100
Blower Wheel .... 1472-2761 1472-2781
5-Ton BlowerAss' Motor 024-31975-000 024-31975-000 024-31975-000 024-31975-000
7900-7751 Run Capacitor (20 MFD) 024-20051-000 024-20051-000 024-20051-000 024-20051-000
Motor Mount 373-19802-930 373-19802-930 373-19802-930 373-19802-930
Blower Wheel 1472-2761 1472-2761 1472-2761 1472-2761
<
<
UnitaryProducts Group 27
Page 28

NOTES
Subject to change without notice. Printed in U.S.A.
Copyright © by York Intemational Corp. 2002. All rights reserved.
Supersedes: 0035-16328-002 Rev. B (1001)
035-16328-002 Rev. C (0902)
Unitary P.O. Wichita
Products Box KS
Group 19014 67204-9014