York DFAA, DFAH User Manual

HIGH EFFICIENCY SEALED COMBUSTION DRUM HEAT EXCHANGER SERIES
MODEL: DFAA/DFAH (Oil and Gas Conversion Burner/ Single Stage Downflow Only)
66 - 84 MBH INPUT (19.34 - 24.62 KW) INPUT
LIST OF SECTIONS
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
OIL PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
ELECTRICAL POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
VENT/COMBUSTION AIR SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . 14
LIST OF FIGURES
Label Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Air Distribution Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Closet To Door Clearance - 5” or Greater . . . . . . . . . . . . . . . . . . . . . . . . . 7
Furnace To Closet Door Clearance - 1” To 5” . . . . . . . . . . . . . . . . . . . . . . 7
Furnace To Closet Door Clearance - Less Than 1” . . . . . . . . . . . . . . . . . . 7
Duct Connector Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Recommended Floor Cut-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Duct Connector Depth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Duct Connector Screw Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Duct Connector Tab Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Anti-Backflow Damper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Installation of Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Floor Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Furnace Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Oil Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
One-Pipe System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Two-Pipe System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Solenoid Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Line Wiring Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Wiring for Heat Only Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Wiring for Electronic Heat-Cool Thermostat . . . . . . . . . . . . . . . . . . . . . . . 14
Wiring for Standard Heat-Cool Thermostat . . . . . . . . . . . . . . . . . . . . . . . 14
LIST OF TABLES
Unit Clearances to Combustibles . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Minimum Duct Sizing For Proper Airflow . . . . . . . . . . . . . . . . . . . . . . . 6
Round Duct Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
External Static Pressure Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Filter Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Burner Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Burner Rating at Elevation Above Sea Level, gph (l/m) . . . . . . . . . . .12
Ratings & Physical / Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Roof Jack Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Cad Cell Resistance When Sensing Flame . . . . . . . . . . . . . . . . . . . .22
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
WIRING DIAGRAM - OIL-FIRED FURNACE . . . . . . . . . . . . . . . . . . . .27
GAS GUN BURNER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
WIRING DIAGRAM - GAS CONVERSION BURNER . . . . . . . . . . . . . . 38
Wiring for Blend Air Accessory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Elbow Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Combustion Air Inlet Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Combustion Air Inlet Pipe Alternate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Flue Shield Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Roof Jack Attachment to Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Standard Roof Jack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Roof Jack With Removable Crowns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Installing Roof Jack Extension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Ceiling Ring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Home Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Electrode Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Oil Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Wiring Diagram for DFAA - Oil-Fired Furnace . . . . . . . . . . . . . . . . . . . . . 27
Wiring Diagram for DFAH - Oil Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Manual Shut-off Valve/Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Proper Piping Practice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Reading Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Electrode Orientation and Gap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Wiring Diagram for DFAA - Gas Conversion Burner . . . . . . . . . . . . . . . . . 38
Wiring Diagram for DFAH - Gas Gun . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Timings and Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Burner Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Filter Performance - Pressure Drop Inches W.C. and (kPa) . . . . . . . .24
Blower Performance CFM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Replacement Parts - Non Electrical . . . . . . . . . . . . . . . . . . . . . . . . . .26
Gas Line Piping Size and Length . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Length of Standard Pipe Threads in Inches (mm) . . . . . . . . . . . . . . .30
High Altitude Duration Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Gas Burner Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Inlet Gas Pressure Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Nominal Manifold Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
EFFICIENCY RATING CERTIFIED
Certified Quality
Management System
For Installation In:
1. Manufactured (Mobile) Homes
2. Recreational Vehicles & Park Models
3. Modular Homes & Buildings
ISO 9001
SECTION I: SAFETY
This is a safety alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION. DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or mo derate injury. alert against unsafe practices and hazards involving only property dam­age.
.
.
It is also used to
Improper installation may create a condition where the operation of the product could cause personal injury or property damage. Improper installation, adjustment, alteration, service or mainte­nance can cause injury or property damage. Refer to this manual for assistance or for additional information, consult a qualified con­tractor, installer or service agency.
This product must be installed in strict compliance with the installa­tion instructions and any applicable local, state, and national codes including, but not limited to building, electrical, and mechanical codes.
107272-UIM-B-1105
107272-UIM-B-1105
SPECIFIC SAFETY RULES AND PRECAUTIONS
1. U.S.....No. 1 or No. 2 heating oil only (ASTM D396),
CANADA.....No. 1 stove oil or No. 2 furnace oil only are ap proved
for use and can be burned in this furnace. Refer to the furnace rat­ing plate or SECTION IV of these instructions.
2. Install this furnace only in a location and position as specified in SECTION I of these instructions.
3. An oil-fired furnace for installation in a residential garage must be installed as specified in SECTION I of these instructions.
4. Combustion products must be discharged outdoors. The Roof Jack vent system is the only approved vent system that can be installed on this furnace. Install as specified in SECTION VI of these instructions.
FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious
injury, death or property damage. Read all instructions before proceeding. Follow all instructions com-
pletely. Failure to follow these instructions could result in equipment malfunction, causing severe personal injury, death, or substantial property damage.
5. Test for leaks in the oil line as specified in SECTION VIII of these instructions.
6. Always install the furnace to operate within the furnace’s intended temperature rise range. Only connect the furnace to a duct system which has an external static pressure within the allowable range, as specified on the furnace rating plate.
7. The return air duct system is not required by the furnace manufac­turer. This furnace utilizes a sealed combustion air and vent sys­tem referred to as a roof jack. The Roof Jack must be installed as specified in these instructions and must conform with state, local, or regional codes.
8. It is permitted to use the furnace for heating of buildings or struc­tures under construction. Installation must comply with all manu­facturer’s installation instructions including:
• Proper vent installation;
• Furnace operating under thermostatic control;
• Return air filter door must be sealed to the furnace;
• Air filters in place;
• Set furnace input rate and temperature rise per rating plate
marking;
• Means for providing outdoor air required for combustion;
• Return air temperature maintained between 55ºF (13ºC) and
80ºF (27ºC);
• The air filter must be replaced or thoroughly cleaned upon sub-
stantial completion of the construction process;
• Clean furnace, duct work and components upon substantial
completion of the construction process, and verify furnace operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer’s instructions.
The following requirements to be met:
a. Clean, outside combustion air is provided to the furnace to
minimize the impact of corrosive adhesives, sealants, and other construction materials. Drywall dust is a major concern during construction, which can be pulled into the combustion air path, leading to plugged heat exchangers, burners, and inducer assemblies.
b. Filter must be installed in the furnace as specified in the
installation instructions, and must be replaced or thoroughly cleaned prior to occupancy of the home. Again, drywall dust is the key issue, as that dust can be pulled into the circulating blower motor, plugging the motor vents, coating the rotors and stators, etc. which can lead to a potential fire hazard.
c. The temperature of the retu rn air to the furnace must not be
less than 55° F (13° C), with no evening setback or furnace shutdown, to prevent condensation in the primary heat exchangers.
d. The air temperature rise must be within the stated rise range
as indicated on the furnace rating plate, and the firing input rate must be set to the unit nameplate value.
e. The external static pressure of the air distribution system
ductwork must be set for heating operation to be at least 0.12 (.03 kPA) to 0.30 (0.7 kPA) inches water column, based on the input rate of the furnace, with the lower value for input rates at 66,000 btu/hr and the upper value for units with input rates at 84,000 btu/hr.
f. The furnace and ductwork should be thoroughly and com-
pletely cleaned prior to occupancy of the dwelling to insure the proper operation of the furnace and to avoid potential health concerns.
9. In Canada refer to the Oil-fired Central Furnace Installation code, CANCSA B139 When installed in a Manufactured (Mobile) Home, combustion air shall not be supplied from occupied spaces.
10. The size of the unit should be based on an acceptable heat loss calculation for the structure. ACCA, Manual J or other approved methods may be used.
11. Manufactured (Mobile) Home and Modular Home Installation: This appliance must be installed in a (sealed combustion) configu­ration using a roof jack vent system. A roof jack is the only approved vent system that can be used to vent this appliance.
12. Modular Home Definition: Factory-built home constructed to the state, local, or regional code where the house will be located. The home is transported in one or more modules and joined at the home site.
13. Manufactured (Mobile) Home Definition: Factory-built home constructed, transported and installed under the federal building code administered by the U.S. Department of Housing and Urban Development (HUD Code), rather than to building codes at their destination. The house is built, transported and installed on a non­removable chassis.
14. This furnace is approved for installation in trailers or recreational vehicles.
SAFETY REQUIREMENTS
• Never attempt to alter or modify this furnace or any of its com­ponents.
• Never attempt to repair damaged or inoperable components. Such action could cause unsafe operation, explosion, fire and/ or asphyxiation.
• If a malfunction has occurred, or if you feel that the furnace is not operating as it should, contact a qualified service agency or oil supplier for assistance.
• A manufactured (mobile) home installation must conform with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, Federal Manufactured Home Construction & Safety Standard (H.U.D., Title 24, Part 3280) or when such stan­dard is not applicable, the standard for Manufactured Home Installations (Manufactured Home Sites, Communities, and Set­ups) NFPA 31 Installation of Oil-Burning Equipment, CAN/CSA B139 Installation Codes). This furnace has been certified to the latest edition of standard UL 727 Standard for Safety for Oil-Burn­ing Equipment, and for Oil-Fired Central Furnaces (Latest Edi­tion), CSA B140.10 (Latest Edition), and all local codes and ordinances.
• Refer to the unit rating plate for the furnace model number, and then see the dimensions page of these instructions for return air door dimensions in Figure 2. The filter(s) must be installed according to the instructions.
2 Unitary Products Group
107272-UIM-B-1105
• Provide clearances from combustible materials as listed under Furnace Locations and Clearances.
• Provide clearances for servicing, ensuring that service access is allowed for both the burners and blower.
• These models are ETL listed and ap proved for installation into a Modular Home or a Manufactured (Mobile) Home.
• Failure to carefully read and follow all instructions in this manual can result in furnace malfunction, death, personal injury and/or property damage.
• Furnaces for installation on combustible flooring shall not be installed directly on carpeting, tile or other combustible material other than wood flooring.
• Check the rating plate and power supply to be sure that the elec­trical characteristics match. All models use nominal 115 VAC, 1 Phase, 60-Hertz power supply. DO NOT CONNECT THIS APPLI­ANCE TO A 50 HZ POWER SUPPLY OR A VOLTAGE ABOVE 130 VOLTS.
• Furnace shall be installed so the electrical components are pro­tected from water.
• Installing and servicing heating equipment can be hazardous due to the electrical components and the oil fired components. Only trained and qualified personnel should install, repair, or service oil heating equipment. Untrained service personnel can perform basic maintenance functions such as cleaning and replacing the air filters. When working on heating equipment, observe precau­tions in the manuals and on the labels attached to the unit and other safety precautions that may apply.
NOTICE SPECIAL REQIREMENTS
This equipment must be installed, adjusted, and started only by a qualified service agency - an individual or agency, licensed and experienced with all codes and ordinances, who is responsible for the installation and adjustment of the equipment. The installation must comply with all local codes and ordinances and with the latest revision of the National Fire Protection Association Standard NFPA31 (or CSA B139).
These instructions cover minimum requirements and conform to exist­ing national standards and safety codes. In some instances these instructions exceed certain local codes and ordinances, especially those who have not kept up with changing Modular Home and Manu­factured (Mobile) Home construction practices. These instructions are required as a minimum for a safe installation.
COMBUSTION AIR QUALITY (LIST OF CONTAMINANTS)
The furnace will require OUTDOOR AIR for combustion when the fur­nace is located in any of the following environments.
• Restricted Environments
• Commercial buildings
• Buildings with indoor pools
• Laundry rooms
• Hobby or craft rooms
• Near chemical storage areas
• Chemical exposure
The furnace will require OUTDOOR AIR for combustion when the fur­nace is located in an area where the furnace is being exposed to the fol­lowing substances and / or chemicals.
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine based swimming pool chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as perchloroethylene)
• Printing inks, paint removers, varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for clothes dryers
• Masonry acid washing materials
When outdoor air is used for combustion, the combustion air intake duct system termination must be located external to the building and in an area where there will be no exposure to the substances listed above.
The furnace area must not be used as a broom closet or for any other storage purposes, as a fire hazard may be created. Never store items, such as the following, on, near or in contact with the furnace.
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning com­pounds; plastic items or
3. Containers, gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids or other volatile fluid.
4. Paint thinners and other painting compounds.
5. Paper bags, boxes or other paper products
Never operate the furnace with the blower door removed. To do so could result in serious personal injury and/or equipment damage.
INSPECTION
As soon as the furnace and/or accessories are received, it should be inspected for damage during transit. If damage is evident, the extent of the damage should be noted on the carrier’s freight bill. A separate request for inspection by the carrier’s agent should be made in writing. Also, before installation, the furnace and/or accessories should be checked for screws or bolts which have loosened in transit, or shipping and spacer brackets that need to be removed.
CONCEALED DAMAGE - If you discover damage to the burner or controls during unpacking, notify carrier at once and file the appro­priate claim.
WHEN CONTACTING BECKETT FOR SERVICE INFORMATION ­Please record the burner serial number (and have available when calling or writing). You will find the serial number on the Underwrit­ers Laboratories label, located on the left rear of the burner, or cover mounting plate. See Figure 1.
Unitary Products Group 3
107272-UIM-B-1105
General Model Information
Serial Number, Including Date Code
Rating Information
Approval Agency Symbols
Primary Group and Fuel Oil
Model "AFEVC"
Series Oil Burner
SERIAL NUMBER
020923-49038
Firing Rng:0.50-0.75 GPH
120V/60Hz 5.8A
R
OIL BURNER NO. PI-100001
R.W.BeckettCorp.
Elyria, Ohio
Made inthe U.S.A.
For usewith Group 1 or 2 primary safety controls&
#1 or#2 fuel oil
MP 1192 EVC201 R00
LISTED
MFR'S SETTINGS
AF36YHHS
ATC:
FIRING RNG:
0.5-1.10 GPH
F3
HEAD:
3-3/8U
STCPLT:
NOZZLE: 0.65 X 70A DLVNHLW
PUMP PRS: 100PSI
EVC201 R00
020923-49038
026-37357-000
DEPT.
Comm. ofMass. -
CS
I
A
L
B
F
U
E
P
T
Y
OFFICEOF
THESTATE
State FireMarshall
FIRE
MARSHAL
Approval #BEC-88-01 Approval July1, 1988
Accepted N.Y.C.MEA. 213-83-E
R. W. Beckett Manufacturer’s Settings
R. W. Beckett Specification Number and Revision
Can be Customized by Individual Specification
State and Local Approvals
RWB
ELYRIA
OHIOU.S.A.
MFR'SSETTINGS
Model"AF "
AF65XNATC:
SeriesOilBurner
FIRINGRNG:
0.75-1.35GPH
HEAD:
F3
SERIALNUMBER
STCPLT:
2-3/4U
1.0X80BDLVN
NOZZLE:
000405-62736
100PSI
PUMPPRS:
BJB3001R00
0.50-3.00GPH,120V/60HZ5.8A
000405-62736
4ULTESTSPEC
5ULTESTSPEC
R
LISTED
R
6ULTESTSPEC
7ULTESTSPEC
OILBURNER NO.PI-100001
8ULTESTSPEC
9ULTESTSPEC
R.W.BeckettCorp.
Elyria,Ohio
MadeintheU.S.A.
DEPT.
Comm.ofMass.-
CS
I
A
L
B
F
U
E
P
T
Y
OFFICEOF
THESTATE
StateFireMarshall
FIRE
ForusewithGroup1or 2
MARSHAL
Approval#BEC-88-01
primarysaftycontrols&
ApprovalJuly1,1988
#1or#2fueloil
AcceptedN.Y.C.MEA.213-83-E ApprovalJuly1,1988
MP1192BJB3001 R00
FIGURE 1: Label Location
CHECK CERTIFICATIONS / APPROVALS
• Underwriters Laboratories has certified this burner to comply with ANSI/UL 296 and has listed it for use with #1 or #2 fuel oil as specified in ASTM D396. Low sulfur #1 and #2 fuel oils reduce
2. Do not allow return air temperature to be below 55º F (13° C) for extended periods. To do so may cause condensation to occur in the main heat exchanger, leading to premature heat exchanger failure.
heat exchanger deposits with all burners compared to the stan­dard fuels. Reduced deposits may extend the service interval for cleaning and improve the efficiency of the appliance over time. Low sulfur fuels reduce particulate and oxides of nitrogen emis­sions as well. The Oil Heat Manufacturers’ Association recom­mends these fuels as the preferred fuels for this burner.
• State and local approvals are shown on burner rating label (See Figure 1).
• All oil burners must be installed in accordance with the regula­tions of the latest revision of the National Fire Protection Associa­tion Standard NFPA 31 and in complete accordance with all local codes and authorities having jurisdiction. Regulation of these authorities take precedence over the general instructions pro­vided in this installation manual.
FURNACE LOCATION AND CLEARANCES
The furnace shall be located using the following guidelines:
1. The furnace should be located where the roof jack can be installed without major modifications to the roof of the structure.
2. As centralized with the air distribution as possible.
3. Where there is access to fresh air particularly when the blend air accessory will be installed.
Installation in an ambient below 32ºF (0.0° C) could create a haz­ard, resulting in damage, injury or death.
3. If this furnace is installed in an unconditioned space and an extended power failure occurs, there will be potential damage to the internal components. Following a power failure situation, do not operate the unit until inspection and repairs are performed.
Clearances for access:
Ample clearances should be provided to permit easy access to the unit. The following minimum clearances are recommended:
1. Twenty-four (24) inches (61 cm) between the front of the furnace and an adjacent wall or another appliance, when access is required for servicing and cleaning.
2. Twenty-four (24) inches (61 cm) at the side where access is required for passage to the front when servicing or for inspection or replacement of flue/vent connections.
In all cases, accessibility clearances shall take precedence over clear­ances for combustible materials where accessibility clearances are greater.
4. Where it will not interfere with proper air circulation in the confined space.
5. Where the outdoor section of the roof jack will not be blocked or restricted. Refer to “VENT CLEARANCES” located in SECTION VI of these instructions. These minimum clearances must be main­tained throughout the installation.
6. Where the unit will be installed in a level position with no more than 1/4” (0.64 cm) slope side-to-side and front-to-back to provide a proper roof jack connection and seal.
Installation in freezing temperatures:
1. Furnace shall be installed in an area where ventilation facilities provide for safe limits of ambient temperature under normal oper­ating conditions. Ambient temperatures below 32º F (0º C) may
Check the rating plate and power supply to be sure that the electri­cal characteristics match. All models use nominal 115 VAC, 1 Phase 60Hz power supply.
Furnace shall be installed so the electrical components are pro­tected from water.
Installation in a residential garage:
1. An oil-fired furnace for installation in a residential garage must be installed so the burner(s) and the ignition source are located not less than 18 inches (46 cm) above the floor, and the furnace must be located or protected to avoid physical damage by vehicles.
result in the vent temperature falling below 260º F (127º C) at any point in the vent pipe. Vent temperatures below 260º F (127º C) will cause the flue products in the vent pipe to condense causing the vent pipe to deteriorate rapidly.
TABLE 1:
Unit Clearances to Combustibles
APPLICATION
TOP FRONT BACK SIDES
AIR INLET
PIPING
ROOF JACK
DUCT
1
In. (cm) In. (cm) In. (cm) In. (cm) In. (cm) In. (cm) In. (cm)
CLOSET 2 (5.08) 6 (15.24) 0 (0.0) 0 (0.0) 0 (0.0) 3 (7.62) 0 (0.0) 0 (0.0) ALCOVE 2 (5.08) 24 (60.96) 0 (0.0) 0 (0.0) 0 (0.0) 3 (7.62) 0 (0.0) 0 (0.0)
1. Approved Duct Connector must be used. Refer to Section II - Ductwork.
FLOOR/BOTTOM
4 Unitary Products Group
107272-UIM-B-1105
Inches
A
59-1/2”
B
C
D
E
F
G
A
DFAH Series
76”
C
24.3/4”
D
23”
E
19-1/2”
F
9-3/4”
G
12”
FIGURE 2: Dimensions
SECTION II: DUCTWORK
DUCTWORK GENERAL INFORMATION
The duct system’s design and installation must:
1. Handle an air volume appropriate for the served space and within the operating parameters of the furnace specifications.
2. Be installed in accordance with standards of NFPA (National Fire Protection Association) as outlined in NFPA pamphlets 90A and 90B (latest editions), in Canada CAN/CSA-B139, Installation Code for Oil-Burning Equipment, or applicable national, provincial, or state, and local fire and safety codes.
3. For Manufactured (Mobile) Home and Modular Home Return
Duct System Installations:
A return air duct and the return air plenum cannot be installed on this furnace. The return air is drawn through the louvers on the blower door. The vent system is a Sealed Combustion Direct Roof Jack Vent System. This is the ONLY vent system approved for use on this furnace.
4. Complete a path for heated or cooled air to circulate through the air conditioning and heating equipment and from the conditioned space.
5. Consideration should be given to the heating capacity required and also to the air quantity (CFM) required. These factors can be determined by calculating the heat loss and heat gain of the home or structure. If these calculations are not performed and the fur­nace is over-sized, the following may result: a. Short cycling of the furnace. b. Wide temperature fluctuations from the thermostat setting.
c. Reduced overall operating efficiency of the furnace.
On DFAA furnaces, the cooling coil must be installed in the bottom of the casing. DFAH furnaces must have the cooling coil installed downstream of the furnace. Cooled air may not be passed over the heat exchanger.
C
c.m.
151.0
193.0
62.9
58.4
49.5
24.8
30.5
D
E
F
G
B
DFAA Series
When the furnace is used in conjunction with a cooling coil, the coil must be installed parallel with, or in the supply air side of the furnace to avoid condensation in the primary heat exchanger. When a parallel flow arrangement is used, dampers or other means used to control airflow must be adequate to prevent chilled air from entering the furnace. If manually operated, the damper must be equipped with means to pre­vent the furnace or the air conditioner from operating unless the damper is in full heat or cool position.
The duct system must be properly sized to obtain the correct airflow for the furnace size that is being installed. Refer to Table 8 and the furnace rating plate for the correct rise range and Table 4 for static pressures.
If the ducts are undersized, the result will be high duct static pres­sures and/or high temperature rises which can result in a heat exchanger OVERHEATING CONDITION. This condition can result in premature heat exchanger failure, which can result in personal injury, property damage, or death.
HAZARD OF ASPHYXIATION, DO NOT COVER OR RESTRICT FLOOR OPENING.
The duct system is a very important part of the installation. If the duct system is improperly sized, the furnace will not operate properly.
The ducts attached to the furnace duct connector should be of sufficient size so that the furnace operates at the specified external static pres­sure and within the air temperature rise specified on the nameplate.
IMPORTANT: Fabricate and install an inspection door in the plenum base below the unit to allow an annual inspection of the heat exchang­ers. The inspection door can be fabricated by following method.
1. Cut a rectangular opening in the plenum base.
2. A Sheet metal plate can be made that completely covers the open­ing in the base.
3. The plate must be secured with screws.
4. This plate must be sealed to prevent leaks.
Table 2 is a guide for determining whether the rectangular duct system that the furnace is being connected to, is of sufficient size for proper fur­nace operation.
Unitary Products Group 5
107272-UIM-B-1105
Use the example below to help you in calculating the duct area to deter­mine whether the ducts have sufficient area so that the furnace oper­ates at the specified external static pressure and within the air temperature rise specified on the nameplate.
Example: The furnace input is 80,000 BTUH, (23.4 kW) 1,200 CFM
3
(34.0 m in x 14 in (20.3 cm x 35.6 cm) rectangular ducts attached to the plenum and there are two 7 inch (722 cm
1. Take 8 in x 14 in (20.3 cm x 35.6 cm), which equals 112 inch
). The recommended duct area is 280 inch2 (1, there are two 8
2
) round ducts attached to the furnace.
(35.6 cm x 2), which equals 224 inch
2
(1445 cm2) then go to round
2
X 2
2. The square inch area for 7 inch (17.8 cm) round pipe is 38.4, mul­tiply by 2 for two round ducts which equals 76.8 inch
2
3. Then take the 224 inch add it to the 76.8 inch inch of duct attached to the furnace plenum is 300.8 inch
2
cm
). This exceeds the recommended 280 inch2 (1,806 cm2) of
(1445 cm2) from the rectangular duct and
2
(495 cm2) of round duct. The total square
2
(495 cm2).
2
(1,940
duct.
In this example, the duct system attached to the plenum has a sufficient area so that the furnace operates at the specified external static pres­sure and within the air temperature rise specified on the nameplate.
duct size located in Table 3.
TABLE 2:
Minimum Duct Sizing For Proper Airflow
Input Airflow
Return
1
Rectangular
2
Round
2
Supply
3
Rectangular
2
Round
2
BTU/H (kW) CFM(m³) In² (cm²) in. x in.(cm x cm) in. (cm) dia In² (cm²) in. x in. (cm x cm) in. (cm) dia. 66000 (19.34) 1,050 (29.73) 280 (711) 14 x 20 (35.6 x 50.8) 18(45.7) 216(549) 12 x 18 (30.5 x 45.7) 16 (40.6) 84000 (24.62) 1,250 (35.40) 360 (914) 18 x 20 (45.7 x 50.8) 22(55.8) 280(711) 14 x 20 (35.6 x 50.8) 18 (45.7)
NOTE: This chart does not replace proper duct sizing calculations or take into account static pressure drop for run length and fittings. Watch out for the temperature rise and static pressures.
3
1. Maximum return air velocity in rigid duct @ 700 feet per minute (19.82 m
2. Example return main trunk duct minimum dimensions.
3. Maximum supply air velocity in rigid duct @ 900 feet per minute (25.49 m
TABLE 3:
Round Duct Size
Round Duct Size Calculated Area For Each Round Duct Size
Inches (cm)
Sq. Inch (cm
2
) 5 (13) 19.8 (126) 6 (15) 28.2 (182) 7 (18) 38.4 (248) 8 (20) 50.2 (324) 9 (23) 63.6 (410)
10 (25) 78.5 (506) 11 (28) 95.0 (613) 12 (30) 113.1 (730) 13 (33) 132.7 (856) 14 (36) 153.9 (993)
1. The Air Temperature Rise is determined by subtracting the Return Air Temperature Reading from the Supply Air Temperature Read­ing.
2. The External Static Pressure is determined by the Supply Duct Static Pressure reading.
TABLES 2 and 3 are to be used as a guide only to help the installer determine if the duct sizes are large enough to obtain the proper air flow (CFM) through the furnace. TABLES 2 and 3 ARE NOT to be used to design ductwork for the building where the furnace is being installed. There are several variables associated with proper duct sizing that are not included in the tables. To properly design the ductwork for the build­ing, Refer to the ASHRAE Fundamentals Handbook, Chapter on “DUCT DESIGN” or a company that specializes in Residential and Mod­ular Home duct designs.
/ minute).
3
/ minute).
DUCKWORK INSTALLATION
Air Distribution Systems
For proper air distribution, the supply duct system shall be designed so that the static pressure does not exceed the listed static pressure rating on the furnace rating plate.
Three typical distribution systems are illustrated in Figure 3. Location, size and number of registers should be selected on the basis
of best air distribution and floor plan of the home. The Air Temperature Rise is to be adjusted to obtain a temperature rise
within the range(s) specified on the furnace rating plate.
DUCT DESIGN - CANADA
Supply duct design shall be in accordance with the latest HRA Digest, the ASHRAE Handbook Fundamentals, or other good engineering prin­ciples.
NOTE: Refer to HRA Digest Residential Air System Design Manual, Sections 5 and 6, the requirements of which are summarized as fol­lows:
1. The kilowatt output of each duct register shall not exceed 2.35 kW.
2. The furnace output should not be more than 20% greater than the calculated heat loss of the home. If a larger furnace is used, the duct system shall be capable of the increased air volumes neces-
sary to maintain a maximum air temperature rise of 50 air passes over the furnace heat exchanger.
3. At least one warm air supply outlet shall be provided in each room.
4. When rooms are located adjacent to the exterior walls, warm air outlets shall be located so as to bathe at least one exterior wall and, where practical, a window area with warm air, except for bath­rooms or kitchens where this might not be practical.
o
C as the
5. Where practical, outlets shall be provided near the exterior doors of the home.
The supply air temperature MUST NEVER exceed the Maximum Supply Air Temperature, specified on the nameplate.
Operating the furnace above the maximum supply air temperature will cause the heat exchanger to overheat, causing premature heat exchanger failure. Improper duct sizing, dirty air filters, incorrect oil pump pressure, incorrect oil orifice and/or a faulty limit switch can
CLEARANCE REQUIREMENTS - CANADA
Supply air ducts from warm air furnaces having a specified minimum plenum clearance shall maintain this clearance from combustible mate­rial for at least the distance specified in CSA Standards CAN/CSA B139, B14.0, B140.10.
cause the furnace to operate above the maximum supply air tem­perature. Refer to SECTIONS II, III and VIII for additional informa­tion on correcting the problem.
6 Unitary Products Group
A
Single trunk duct
Dual trunk duct with crossover connector
B*
1
Transition Duct with Branches
C
Transition duct
107272-UIM-B-1105
Dual trunk duct
1. Crossover Duct must be centered directly under furnace.
2. Use 12” (30.5 cm) Diameter Round or insulated Flex-duct only.
3. Terminate Flex-duct (opposite furnace) in the center of the trunk duct.
4. Flex-duct material must be pulled tight — No Loops or unnecessary dips — Air Flow may be impeded.
Crossover
4
FIGURE 3: Air Distribution Systems
Return Air Grille Part No. 7900-287P/A * White
A
22
250 IN. (161 cm ) MINIMUM FREE AREA
22
50 IN. (322 cm ) MINIMUM FREE AREA
FIGURE 4: Closet To Door Clearance - 5” or Greater
2
Branches
3
Furnace to Closet Door Clearance —
B
22
250 IN. (161 cm ) MINIMUM FREE AREA
5 Inches (12.7 cm) or more
The closet door have a minimum of of free area in the upper half of the door. If opening for return air is located in the floor or sidewalls and below the top of the furnace casing:
6 inches (15.2 cm) minimum clearance must be provided on side
1. where return is located, and 6 inches (15.2 cm) minimum clearance must be maintained from
2. the front of furnace.
CLOSET
FURNACE
DOOR
MUST 250 Inches (1613 cm )
5 in (12.7 cm) or greater * Closet to Door Clearance
Return Air Closet Door Part No. 7900-7771/C* White
22
22
250 IN. (161 cm ) MINIMUM FREE AREA
22
50 IN. (322 cm ) MINIMUM FREE AREA
As an option to the lower grill, an undercut of 2-1/2" will provide
50 inches (322 cm ) of free area.
22
FIGURE 5: Furnace To Closet Door Clearance - 1” To 5”
250 IN. (161 cm ) MINIMUM FREE AREA
50 IN. (322 cm ) MINIMUM FREE AREA
B
250 IN. (161cm ) MINIMUM FREE AREA
22
22
Furnace to Closet Door Clearance — Greater than 1 Inch (2.54 cm) and Up to 5 (12.7 cm) Inches
1.
The closet door have a minimum of (1613 cm f free area in the upper half of the door and a minimum of (322 cm ) of free area in the lower area of the door. omitted if an undercut of 2-1/2 inches (16.1 cm) is provided in the door.
2.
A fully louvered closet door have a minimum of
250 Inches
22
Furnace to Closet Door Clearance — Less than 1 Inch (2.54 cm)
MUST 250 Inches
The lower closet door grille may be
22
(1613 cm )
MUST
of free area in the upper half of the door.
The closet door MUST have three return air grilles. The total free area of the two upper grilles must be minimum of (1613 cm ) . The total free area of the lower grille MUST be a minimum of .
The grilles MUST BE ALIGNED directly opposite the return air grille of the furnace door.
250 Inches
22
50 Inches
22
50 Inches (322 cm )
)o
22
22
FIGURE 6: Furnace To Closet Door Clearance - Less Than 1”
Unitary Products Group 7
107272-UIM-B-1105
DUCT CONNECTORS
18-3/4 (47.6 cm)
2-3/8 (6.0 cm)
14 (35.6 cm)
13
(33.0 cm)
(27.9 cm
11
DUCT CONNECTOR DIMENSIONS
DUCT CONNECTOR
PART NUMBER
7990-6011 7990-6021 7990-6041 7990-6061 7990-6071 7990-6081 7990-6101 7990-6121
FIGURE 7: Duct Connector Dimensions
Rear Wall
2-3/4 (7.0 cm)
Min.
9-7/8
(25.1 cm
of Enclosure
2-3/8
(6.0 cm)
12
(30.5 cm)
18-3/4
(47.6 cm)
4-3/8 (11.1 cm)
DUCT CONNECTOR
DEPTH
1” (2.5 cm) 2” (5.7 cm)
4-1/2” (11.4 cm 6-1-2” (16.5 cm) 7-1/2” (19.0 cm) 8-1/2” (21.6 cm)
10-1/4” (26.0 cm) 12-1/4” (21.1 cm)
Ceiling Cut-Out For Roof Jack
Floor Cut-Out For Duct Connector
SEE CHART
Furnace Outline
2-3/8 (6.0 cm)
DUCT CONNECTOR DIMENSIONS
DUCT CONNECTOR
PART NUMBER
7990-6211 7990-6221 7990-6241 7990-6261 7990-6271 7990-6281 7990-6301 7990-6321
18-3/4 (47.6 cm)
14 (35.6 cm)
13
(33.0 cm)
11
(27.9 cm
Locator Bracket
2-3/8
(6.0 cm)
12
(30.5 cm)
18-3/4
(47.6 cm)
4-3/8 (11.1 cm)
DUCT CONNECTOR
DEPTH
1” (2.5 cm) 2” (5.7 cm)
4-1/2” (11.4 cm 6-1-2” (16.5 cm) 7-1/2” (19.0 cm) 8-1/2” (21.6 cm)
10-1/4” (26.0 cm) 12-1/4” (21.1 cm)
Nails, Flat Head Screws or Staples
Screws
SEE CHART
Floor
23-1/4 (59.1 cm)
20-1/2 (52.1 cm)
2-1/8 (5.4 cm)
1
1-3/8
(3.5 cm)
Future Refrigerant Line Entrance
15
(38.1 cm)
6-3/8
(16.2 cm)
9-3/4
24.8 cm)
15
(38.1 cm)
20
(50.8 cm)
(8.3 cm)
FIGURE 8: Recommended Floor Cut-out
Duct Connector
Depth
Supply Duct
FIGURE 9: Duct Connector Depth
3-1/4
Floor
1-1/8 (2.9 cm)
Floor
Optional Gas or Electric Entrance
Front Panel of Furnace
Floor Joist
Supply Duct
FIGURE 10: Duct Connector Screw Attachment
INSTALLATION OF SCREW ATTACHMENT DUCT CONNECTOR
1. Make floor cut out as shown in Figure 8.
2. Determine the depth of the floor cavity from the surface of the floor to the top of the supply air duct and select the appropriate duct connector from the chart.
3. Place locating bracket (supplied with the duct connector) to the back edge of the floor opening. See Figure 10.
4. Apply a water based duct sealant to the 1/2 in (1.3 cm) supply duct attachment flange of the duct connector.
5. Determine which of the four positions the duct connector best cen­ters over the supply duct and insert it through the floor cut-out.
6. When properly aligned with the supply duct, secure the duct con­nector to the floor with nails, flat head screws or staples.
7. Use screws as required to secure the duct connector to the supply duct.
8. Cut out the opening to the supply duct. If sealant was not used, the installer should tape the mating flanges to provide a good air seal.
NOTE: Duct sealant and tape must be classified as meeting HUD Stan­dard 3280.715, U.L. Standard 181A.
If tape is used to provide a better air seal, it should be a type approved by the applicable national or local codes.
8 Unitary Products Group
107272-UIM-B-1105
Locator Bracket
Nails, Flat Head Screws or Staples
Bend Tabs Under Duct Opening to Secure to the Supply Duct
Floor
Supply Duct
FIGURE 11: Duct Connector Tab Attachment
INSTALLATION OF TAB ATTACHMENT DUCT CONNECTORS
1. Make floor cut out as shown in Figure 8.
2. Determine the depth of the floor cavity from the surface of the floor to the top of the supply air duct and select the appropriate duct connector from the chart.
3. Place locating bracket (supplied with the duct connector) to the rear of the floor area for the furnace. See Figure 11.
4. Determine which of the four positions the duct connector best cen­ters over the supply duct and insert it through the floor cut-out.
5. Mark cut-out location on the supply duct and remove the duct con­nector.
6. Cut out the opening to the supply duct.
7. Bend tabs down through and back up under the supply duct.
8. Secure the duct connector to the floor with nails, flat head screws or staples.
The duct connector is designed for use on ducts down to 12 in (30.5 cm) width. When using the connector on smaller width ducts, there will not be sufficient clearance to bend the tabs on two sides of the duct connector. In such cases the tabs may be attached to the sides of the duct by using sheet metal screws or other suitable fasteners. Holes for sheet metal screws are provided in three (3) tabs on each side of the duct connector. If more than 3 tabs need to be used to provide a more secure and air tight connection, the remaining tabs can also be fas­tened to the duct with screws after drilling the required screw hole.
TABLE 4:
External Static Pressure Range
Input Output
Nominal
Air Flow
Ext. Static Pressure
1
Minimum Maximum
MBH kW MBH kW CFM cmm In.W.C kPa In.W.C kPa
66000 19.34 53000 15.55 1050 29.73 .12 .03 .30 .07 84000 24.62 67000 19.63 1250 35.40 .12 .03 .30 .07
1. Std. Blower-High Speed-No Coil.
IMPORTANT: The air temperature rise should be taken only after the furnace has been operating for at least 15 minutes. Temperatures should be taken 6" (15.2 cm) past the first bend from the furnace in the supply duct. The return air temperature must be taken at the return air louvered door. Return static pressures can be taken by pushing probe through the air filter on the louvered door.
Furnace and Air Conditioner Installations
If an air conditioner is installed which does not use the blower for air dis­tribution and operates completely independent of the furnace, the ther­mostat system must have an interlock to prevent the furnace and air conditioner from operating at the same time. This interlock system usu ­ally contains a heat-cool switch which must be turned to either HEAT or COOL to activate either heating or cooling operation, or a positive OFF switch on the cooling thermostat. When used in connection with a cooling unit the furnace shall be installed parallel with or on the upstream side of the cooling unit to avoid condensation in the heat exchanger.
For installations with a parallel flow arrangement, the furnace must be equipped with a damper to prevent cold air from being discharged up around the heat exchanger. Cold air causes condensation inside the exchanger and can cause it to rust out which can allow products of combustion to be circulated into the living area by the furnace blower resulting in possible asphyxiation. An air flow activated automatic damper, is available from furnace manufacturer. See Figure 12.
NOTE: See label on coil panel for conversion and lighting instructions. Obtain a temperature rise within the ranges specified on the name plate.
All installations must have a filter installed.
Automatic Damper
Supply Duct
Furnace Base
NOTE: FOR BEST AIR DELIVERY INSTALL DAMPER
WITH BLADES PARALLEL TO SUPPLY DUCT.
Opening
Duct Connector
FIGURE 12: Anti-Backflow Damper
INSTALLATION OF THE FURNACE
1. Remove the front panels and set the furnace onto the duct con­nector. Slide it back until the rear of the unit engages the locator bracket.
2. Secure the front of the furnace with two screws at the mounting holes provided. See Figure 13.
Furnace Seated Against the Locator Bracket
Secure Furnace to Floor with Two Nails or Screws.
FIGURE 13: Installation of Furnace
3. Secure the top of the furnace to a structural member using screw through the strap at the back of the furnace. Strap may be moved to any of the holes located along the top back of the furnace. Installer may provide an equivalent method, such as screws through the casing side.
Unitary Products Group 9
107272-UIM-B-1105
DFAH Furnaces:
If a matching cooling coil is used, it may be placed directly on the fur­nace outlet and sealed to prevent leakage. Follow the coil instructions for installing the supply plenum. On all installations without a coil, a removable access panel is recommended in the outlet duct such that smoke or reflected light would be observable inside the casing to indi­cate the presence of leaks in the heat exchanger. This access cover shall be attached in such a manner as to prevent leaks.
RETURN AIR REQUIREMENTS
Closet Installations
Additional Requirements
Additional requirements for floor and ceiling return system for closet installed sealed combustion heating appliances are given in the next paragraph.
Floor or Ceiling Return Air System
Listed in the next paragraph are the conditions to be met by Manufac­tured Home Manufacturers to have U.L. acceptance of in-floor or ceiling return air systems of closet installed direct vent forced air heating appli­ances for Manufactured Homes to be sold in the United States.
1. The return air opening into the closet, regardless of location, is to be sized not less than 16” X 24” (40.6 cm x 101.6 cm).
2. If the return air opening is located on the floor of the closet (versus the vertical front or side wall), the opening is to be provided with means to prevent its inadvertent closure by a flat object placed over the opening.
3. The cross sectional area of the return duct system (when located in the floor or ceiling of the manufactured home) leading into the closet is to be not less than 16” X 24” (40.6 cm x 101.6 cm).
4. At least one register is to be located where likelihood of its being covered by carpeting, boxes, and other objects is minimized.
5. Materials located in the return duct system have a flame spread classification of 200 or less.
6. Non-combustible pans having 1” (2.5 cm) upturned flanges are located beneath openings in the floor return duct system.
7. Wiring materials located in the return duct system conform to Arti­cle 300-22 (B&C) of the National Electrical Code (NFPA-70).
8. Fuel piping is not run in or through the return duct system.
9. The negative pressure in the closet as determined by test with the air circulating fan operating at high heating speed and the closet door closed is to be not more negative than minus 0.05 inches (1.2 kPa) water column.
10. For floor return systems, the manufactured home manufacturer or installer shall affix a prominent marking on or near the appliance where it is easily read when the closet door is open. The marking shall read:
HAZARD OF ASPHYXIATION, DO NOT COVER OR RESTRICT FLOOR OPENING.
BLEND AIR INSTALLATIONS
If a blend air ventilation system is installed, the 5” (12.7 cm) diameter knockout in the top cover must be removed. The blend air damper is to be placed on the top cover and secured with screws as shown in Figure
14. The power wires for the Blend Air Damper are inserted through the
7/8” (2.22 cm) hole in the top cover. The wires to the Blend Air Damper will be connected as shown in Figure 24. Refer to the Blend Air Installa­tion Manual to complete the installation.
Blend Air Flex Duct
Blend Air Damper
WARM AIR DUCT
DUCT CONNECTOR
Floor
FIGURE 14: Floor Installation
SECTION III: FILTERS
FILTER INSTALLATION
All applications require the use of a filter. A standard air filter is located in the return filter rack on the louvered door. The air filter(s) must be replaced with air filter(s) that are the same size and same type. Replacement filter size is shown in Table 5.
Downflow Filters:
There are two types of downflow filter racks.
1. FURNACE FILTER RACK: A return filter rack is with two standard throwaway type filters are supplied on all models. The return filter rack is located on the inside of the louvered door. This type of filter rack is designed for two standard air filters only. Pleated Media or Washable Filters cannot be used in this filter rack because they cause too much pressure drop causing a reduction in airflow.
2. EXTERNAL RETURN FILTER GRILLE: The second type is an external return air filter grille that can only be used in applica- tions where the furnace is installed in a closet. This type of fil­ter grille is typically installed in a closet door or wall with the filters located within 12" (30.5 cm) of the return air opening of the fur­nace. There must be a minimum clearance of 6" (15.2 cm) between the front of the furnace and the closet door and/or the fur­nace and the filter grille to prevent the return air flow from being obstructed. Refer to Table 1 Unit Clearances to Combustibles.
a. If the standard throwaway filter are used the external filter
grille must have a minimum area of 540 in² (3483 cm²) which would equal a 15" X 36" (38.1 cm x 91.4 cm) filter grille.
b. If the Pleated Media or Washable Filters are used the exter-
nal filter grille must have a minimum area of 684 in² (4413 cm²) which would equal a 18" X 38" (38.1 cm x 91.4 cm) filter grille. The increased area is to reduce the pressure drop across the air filter.
c. Consideration should be given when locating the return filter
grille for maintenance.
d. Any filter that has a large pressure drop should be checked to
be sure the pressure drop caused by the air filter will not pre­vent the furnace from operating within the rise range, speci­fied on the rating plate and in Table 8. If the furnace does not operate within the specified rise range then a larger air filter or an air filter that has a lower pressure drop must be installed.
TABLE 5:
66 / 53 (19.34 / 15.53) 1050 (29.73) (2) 14 x 20 (35.56 x 50.8) 84 / 67 (24.62 / 19.64) 1250 (35.40) (2) 14 x 20 (35.56 x 50.8)
Filter Sizes
Input / Output
BTU/H (kW)
(m
CFM
3
/mm)
Top Return
Filter In. (cm)
10 Unitary Products Group
107272-UIM-B-1105
IMPORTANT: Air velocity through throwaway type filters must not exceed 300 feet per minute (1.52 m/m).
.
All installations must have a filter installed.
Air Filters Can Be Found On The Inside Of This Access Panel
FIGURE 15: Furnace Air Filters
.
SECTION IV: OIL PIPING
OIL SAFETY
IMPORTANT INFORMATION: Long or oversized inlet lines may require the pump to operate dry during initial bleeding period. In such cases, the priming may be assisted by injecting fuel oil in the pump gearset. Under lift conditions, lines and fittings must be air tight. To assure this, “Pipe Dope” may be applied to both the used and unused inlet and both return fittings. DO NOT USE TEFLON TAPE! DO NOT USE COM­PRESSION FITTINGS!
VACUUM CHECK: A vacuum gauge may be installed in either of the 1/ 4” NPT inlet ports. The Beckett CleanCut pump should be used where the vacuum does not exceed 6” hg. (20.3 kPa) single pipe and 12” hg. (40.6 kPa) two pipe. Remember, running vacuum is the total of all pres­sure drops (P) in the system from tank to inlet of pump.
PRESSURE CHECK: When a pressure check is made, use either the BLEED PORT OR NOZZLE PORT.
CUTOFF CHECK: To check cut-off pressure, dead head a pressure gauge in nozzle port. Run burner for short period of time. Shut burner off. The pressure will drop and hold above zero
.
Pressurized or gravity feed installations must not exceed 3 P.S.I.
20.7 kPa) on inlet line or return line at the pump per NFPA 31. A pressure greater than 10 P.S.I. (69.0 kPa) may cause damage to the shaft seal.
TABLE 6:
Furnace Model Burner Spec ATC Head
DFAA084BBTA DFAH084BBSA
DFAA066BBTA DFAH066BBSA
Burner Specifications
EVC - 201 AF36YHHS F3
EVC - 202 AF36YHHS F3
Static Plate Nozzle Pump Pressure Air Boot Setting
3-3/8 U 0.65 x 70° A
Delavan
3-3/8 U 0.50 x 70° A
Delavan
100 psi
(689.5 kPa)
100 psi
(689.5 kPa)
4.0
3.0
The burner fuel unit is shipped without the bypass plug installed. You must install this plug on two-pipe oil systems. DO NOT install the plug in the fuel unit if connected to a one-pipe oil system. Fail­ure to comply could cause fuel unit seal failure, oil leakage, and potential fire and injury hazard.
Fuel Supply Level With or Above Burner
The burner may be equipped with a single-stage fuel unit for these installations. Connect the fuel supply to the burner with a single supply line if you want a one-pipe system (making sure the bypass plug is NOT installed in the fuel unit). Manual venting of the fuel unit is required on initial start-up. If connecting a two-pipe fuel supply, install the fuel unit bypass plug.
The oil supply inlet pressure to the fuel unit cannot exceed 3 psi. (20.7 kPa) Install a pressure-limiting device in accordance with NFPA 31.
Fuel Supply Below the Level of the Burner
When the fuel supply is below the level of the burner, a two-pipe fuel supply system is required. Depending on the fuel line diameter and hor­izontal and vertical length, the installation may also require a two-stage pump. Consult the fuel unit manufacturer’s literature for lift and vacuum capability.
Fuel Line Installation
• Continuous lengths of heavy wall copper tubing are recom­mended. Always use flare fittings. Never use compression fit- tings.
• Always install fittings in accessible locations. Fuel lines should not run against the appliance or the ceiling joists (to avoid vibra­tion noise).
CONNECT FUEL LINES
Carefully follow the fuel unit manufacturer’s literature and the latest edi­tion of NFPA 31 for oil supply system specifications. If this information is unavailable, use the following basic guidelines.
Never use Teflon tape on any fuel fitting. Tape fragments can lodge in fuel line components and the fuel unit, damaging the equipment and preventing proper operation.
Fuel Line Valve and Filter
Install two high quality shut-off valves in accessible locations on the oil supply line. Locate one close to the tank and the other close to the
Fuel units with automatic bypass do not require a bypass plug.
burner, upstream of the filter.
Some states require these valves to be fusible-handle design for
Burners equipped with a Beckett CleanCut pump must have a con­trol system that provides a valve-on delay (prepurge).
protection in the event of fire. We recommend this as good industry practice for all installations.
Install a generous capacity filter inside the building between the fuel tank shut-off valve and the burner, locating both the filter and the valve close to the burner for ease of servicing. The filter should be rated for 50 microns 50 micrometers) or less.
Unitary Products Group 11
107272-UIM-B-1105
NOTICE SPECIAL REQUIREMENTS
This equipment must be installed, adjusted, and started only by a qualified service technician, an individual or agency, licensed and experienced with all codes and ordinances, who is responsible for the installation and adjustment of the equipment. The installation must comply with all local codes and ordinances and with the National Fire Protection Standard for Liquid Fuel Equipment, NFPA 31 (or in Canada the installation must comply with CSA B139).
This pump must be used with a control system that provides a valve on delay (pre-purge).
This furnace is designed to operate on #1 FUEL-OIL or #2 FUEL­OIL ONLY. Do Not burn any other fuel in this furnace. Burning any fuel except #1 FUEL-OIL or #2 FUEL-OIL in this furnace can cause premature heat exchanger burnout, high levels of carbon monox­ide, excessive sooting, a fire hazard, personal injury, property dam­age, and/or death.
In Canada, the furnace is designed to operate on #1 STOVE OIL or #2 FURNACE OIL ONLY.
THE EFFECT OF ELEVATION ON OIL BURNER FIRING
The elevation of the installation of a modern high-speed flame retention oil burner affects the performance of the burner. Allowance for elevation must be taken into consideration when choosing an oil burner and oper­ating it above 2000 ft. (610m).
It is especially important in high elevation installations to adjust air set­tings to match the burner nozzle firing rate. As elevation increases above sea level, the ambient air contains less oxygen. Because there is less available oxygen per cubic foot of air, the burner must deliver a greater volume flow (cfm) of air to provide the proper amount of oxygen for the amount of oil being burned. This is the reason that an increase in the burner air setting may be required.
It is also important in high elevation installations to consider the maxi­mum firing rate of the burner, so that the heat input as required by the application is maintained. Regardless of elevation, the oil burner has a maximum volume flow of air that it can deliver. As a result, the maxi­mum firing rate of the oil burner decreases as the elevation increases, because the combustion air contains less oxygen. An increase in the size of a fixed-type retention head, or even the use of an oil burner with a higher maximum firing rate may be necessary.
The effect of elevation up to 2000 ft. (610 m) is minimal, so no re-rate is necessary up to 2000 ft. (610 m) elevation. Above 2000 ft. (610 m), for every 1000 ft. (305 m) above sea level (including the first 2000 ft. (610 m), there is a 1.84% rate reduction of the burner. To assist you, we have included the following chart and some examples: Refer to Table 7.
The pressure regulator on the fuel pump must not be adjusted in excess of 100 PSIG (689 kPa).
Pressures exceeding 100 PSIG (689 kPa) may cause an overheat­ing condition which can lead to premature heat exchanger failure, resulting in a fire or explosion, or cause damage to the furnace of some of its components that will result in property damage and loss of life. Refer to Figure 16 for Pressure Regulator Location.
TABLE 7:
(Above Sea Level)
Burner Rating at Elevation Above Sea Level, gph (l/m)
Elevation
Nozzle Size
0.50 1.892706 0.65 2.460518
ft m gph l/h gph l/h
500 152 0.50 1.89 0.65 2.46 1,000 305 0.50 1.89 0.65 2.46 1,500 457 0.50 1.89 0.65 2.46 2,000 610 0.50 1.89 0.65 2.46 2,500 762 0.49 1.86 0.65 2.46 3,000 914 0.48 1.82 0.64 2.42 3,500 1,067 0.48 1.82 0.64 2.42 4,000 1,219 0.47 1.79 0.63 2.37 4,500 1,372 0.47 1.79 0.63 2.37 5,000 1,527 0.46 1.76 0.61 2.33 5,500 1,676 0.46 1.76 0.61 2.33 6,000 1,829 0.46 1.72 0.60 2.28 6,500 1,981 0.46 1.72 0.60 2.28 7,000 2,134 0.45 1.69 0.59 2.24 7,500 2,286 0.45 1.69 0.59 2.24 8,000 2,438 0.44 1.66 0.58 2.20 9,000 2,743 0.43 1.63 0.57 2.16
10,000 3,048 0.42 1.60 0.56 2.12
Note: All examples are for 7000 ft. elevation.
1.84% x 7 (for 7000 ft.) = 12.9% 100% - 12.9% = 87.1%
ft = feet m = meters gph = gallons per hour l/h = liters per hour
EXAMPLE 1:
Re-Rating of the Maximum Firing Rate for Burners @ 7000 ft.
Burner
Model
Maximum Firing
Rate of Burner
@ Sea Level
Elevation
X
Re-rate Factor
@ 7000 ft.
=
Adjusted
Maximum
Firing Rate
AFG 3.00 gph (11.4 L/h) X 87.1% = 2.61 gph (9.83 Lh)
AF 3.00 gph (11.4 L/h) X 87.1% = 2.61 gph (9.83 Lh)
.
Nozzle Port 3/16 Flare Fittting
USEONLY WITH VALVE ONDELAY
4GPH 100-150 P SI 3450 RPM
NO.2 & LIGHTERFUEL
3GPH 150-200 P SI 3450 RPM
INLET
Inlet Port 1/4 NPTF (0.64 cm)
Beckett
CLEANCUT
A2EA-6520
NO.2FUEL
MadebyS untec
ExclusivelyforBe ckett
By Pass Solenoid Valve
INLET
BY-PASS
Cordset
Bleed & Gauge Port
Return Port Install 1/16” by Pass Pipe Plug For Two-Pipe System Only (Use 5/32” Allen Wrench)
Inlet Port 1/4 NPTF
Pressure Adjustment Screw
FIGURE 16: Oil Pump
INSTALLATION AND CHECKING OF OIL PIPING
Location and installation of oil tanks and oil piping must comply with local codes and regulations. In absence of such codes, follow NFPA 31: Standard Floor Installation of Oil Burner Equipment.
12 Unitary Products Group
Loading...
+ 28 hidden pages