YORK® Sunline Plus™ units are convertible single package
air conditioners. The units were designed for light commercial
and commercial applications. They can easily be installed on
a roof curb, slab, roof jack or frame.
All units include:
•Powder Paint finish that meets ASTM-B-117 1000 hour
salt spray standards
•Permanently lubricated motors
•Bottom or side air discharge configuration capability
(field convertible)
•Manufactured under the quality standards of ISO9001
®
•Simplicity
•Copper tube/aluminum fin coils
•Easy access to all components
•Rigging holes in base rails for lifting
•Fork lift slots on three sides
•Single point power connection
•Complete factory package - tested, charged and wired
•CSA agency listing on all units
Control Board
WARRANTY
•Factory Limited Parts Warranty
•One-year parts warranty
•A Five-year parts warranty on the compressor and
electric heat elements.
•Ten-year parts warranty on the gas-fired heat
exchangers.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
A = Direct Drive
B = Direct Drive/Single Input Economizer
D = Direct Drive/Motorized Damper
N = Belt Drive
P = Belt Drive/Single Input Economizer
R = Belt Drive/Motorized Damper
Voltage
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
Product Style
A = Style A
These four digits will not be assigned until a quote is requested, or an order placed.
SS Drain Pan
CPC Controller, DFS, APS
Johnson Controller, DFS, APS
Honeywell Controller, DFS, APS
Novar Controller, DFS, APS
Simplicity IntelliComfort Controller
Simplicity IntelliComfort Controller w/ModLinc
2" Pleated filters
BAS Ready Economizer (2-10 V. D. C. Actuator without a Controller)
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
Product Generation
1 = First Generation
2 = Second Generation
Standard Cabinet
AA = None
AB = Phase Monitor
AC = Coil Guard
AD = Dirty Filter Switch
AE = Phase Monitor & Coil Guard
AF = Phase Monitor & Dirty Filter Switch
AG = Coil Guard & Dirty Filter Switch
AH = Phase Monitor, Coil Guard & Dirty Filter Switch
AS = Bottom Drain Connection
RC = Coil Guard & American Flag
TA = Technicoat Condenser Coil
TJ = Technicoat Evaporator Coil
TS = Technicoat Evaporator and Condenser Coil
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
Installation Options
A = No Options Installed
B=Option1
C=Option 2
D = Options 1 & 2
E=Option3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S=Option5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
All models are available with a wide variety of factorymounted options such as stainless steel heat exchangers,
electric heaters, phase monitor, convenience outlet, dirty filter
switch, disconnect switch, smoke detectors, and coil guard to
make them suitable for almost every application.
All units are self-contained and assembled on full perimeter
base rails with forklift holes on three sides and holes for overhead rigging. Every unit is completely piped, wired, charged
and tested at the factory to simplify the field installation and to
provide years of dependable operation.
All models (including those with an economizer) are suitable
for either bottom or horizontal duct connections. For bottom
duct, remove the sheet metal panels from the supply and
return air openings through the base of the unit. For horizontal duct, remove the supply and return air panels on the rear
of the unit.
All models are available with these “factory mounted” outdoor
air damper options:
•Single enthalpy economizer
•Motorized outdoor air damper
Supply air blowers are equipped with either a direct drive or a
belt drive that can be adjusted to meet the exact requirements of the job.
All compressors are equipped with internal pressure relief.
Every refrigerant circuit includes a liquid line filter-drier, a high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch to protect all system components.
®
•Simplicity
standardized a number of features previously available
only as options or by utilizing additional controls.
•Low Ambient - An integrated low-ambient control
•Anti-Short Cycle Protection - To aid compressor
•Fan Delays - Fan on and fan off delays are fully pro-
•Safety Monitoring - The control board monitors the
Controls - Simplicity® control boards have
allows all units to operate in the cooling mode down
to 0ºF outdoor ambient without additional assistance. Optionally , the control board can be programmed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti short cycle delay can be temporarily
overridden with the push of a button.
grammable and are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit
switch on gas heat units. The unit control board will
alarm on ignition failures, compressor lockouts and
repeated limit switch trips.
•Nuisance Trip Protection- To prevent nuisance
trouble calls, the control board uses a “three strikes,
you’re out” philosophy. The high and low-pressure
switches and the freezestats must trip three times
within two hours before the unit control board will
lock out the compressor.
•On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
All units have long lasting powder paint cabinets with 1000
hour salt spray test approval under ASTM-B117 procedures.
All models are CSA listed.
•Warranty - All models include a one-year limited parts
warranty on the complete unit. Compressors and electric
heater elements carry a five-year warranty. Gas heat
exchangers carry a 10-year parts warranty.
•Gas Heat Operation - All single phase models with gas
heat have minimum annual fuel utilization efficiency
(AFUE) of 80%. All three phase models with gas heat
have minimum steady state efficiency of 80%. Each section includes a durable heat exchanger with aluminized
steel or optional stainless steel tubes, a redundant gas
valve, spark ignition, power venting, an ignition module for
100% shut-off and all of the safety controls required to
meet the latest ANSI standards.
The gas supply piping can be routed into the heating
compartment through a hole in the base pan of the unit
or through a knockout in the piping panel on the front of
the unit.
•Electric Heat Operation - All electric heat models are
wired for a single power source and include a bank of
nickel chromium elements mounted at the discharge of
the supply air blower to provide a high velocity and uniform distribution of air across the heating elements.
Every element is fully protected against excessive temperature by thermal limit switches.
The power supply wiring can be routed into the control
box through a threaded pipe connection (field supplied)
in the base pan of the unit or through a knockout in the
wiring panel on the side of the unit.
•BAS Controls - Y ork’ s Sunline™ series uni ts of fer factory
mounted BAS controls such as Simplicity
fort™, Novar, Honeywell , Johnson, and CPC.
®
INTELLI-Com-
4Unitary Products Group
Page 5
254599-YTG-C-0807
FIGURE 1 - UNIT CUTAWAY
FACTORY-INSTALLED OPTIONS
•SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•PHENOLIC COATED EVAPORATOR AND CON-DENSER COILS - Special coating process that utilizes
Technicoat 10-1
immersion of the complete coil for maximum protection.
TM
processes. Coating is applied by total
•ELECTRIC HEATERS - Wired for single point power
supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent
operation at excessive temperatures.
•FILTER OPTIONS - Standard units are shipped with 1”
throw-away filters installed. 2” pleated filters are offered
as a factory installed option.
•CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or the
unit may be ordered with a “non-powered” convenience
outlet that can be wired in the field.
•DISCONNECT SWITCH - For gas heat units and cooling
units with electric heat, a HACR breaker sized to the unit
is provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
•BAS - Building Automation System Controls
Simplicity
Simplicity
®
INTELLI-Comfort™ CONTROL - The York®
®
INTELLI-Comfort™ control is factory
installed. It includes a supply air sensor, a return air sensor, and an outside air sensor . There are provisions for a
field installed dirty filter indicator switch, an air-proving
switch, an Outside Air Humidity sensor, a Return Air
Humidity sensor, an Inside IAQ sensor, and an Outside
Air IAQ sensor. Construction mode operation, 365-day
real time clock with 7 day programming plus holiday
Unitary Products Group5
Page 6
254599-YTG-C-0807
scheduling is built-in. Two different modes of demand
ventilation are achieved through the INTELLI-Comfort™
using CO2 sensors. It uses an inside CO2 sensor to perform Demand Ventilation. It can also use an Outside
CO2 sensor to perform Differential Demand Ventilation.
It uses a Patented Comfort Ventilation algorithm to provide comfortable ventilation air temperature. The patented economizer-loading algorithm will protect the
equipment when harsh operating conditions exist.
Humidity in the occupied space or return duct can be
monitored and controlled via humidity sensors and the
on-board connection for hot gas re-heat system. It uses
the INTELLI-Start™ algorithm to maximize energy savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the
Occupied Time Period to begin. The Simplicity
®
INTELLI-Comfort™ balances space temperature, ventilation air temperature, CO2 and humidity for ultimate
comfort.
®
•Simplicity
INTELLI-Comfort™ with MOD LINK CON-
TROL - The York® Simplicity® INTELLI-Comfort™ with
Mod Link control is factory installed. It includes all the
features of the INTELLI-Comfort™ control with an additional control to translate communications from MODBUS to the BACnet MSTP protocol.
•Novar® BAS CONTROL - The Novar® ETC-3 building
automation system controller is factory installed.
Includes supply air sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
•JOHNSON CONTROLS BAS CONTROL - The Johnson
Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor,
return air sensor, dirty filter indicator switch, and air proving switch.
•CPC BAS CONTROL - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
•HONEYWELL BAS CONTROL - The Honeywell
W7750C building automation system controller is factory
installed. Includes air supply sensor, return air sensor,
dirty filter indicator switch, and air proving switch.
•SMOKE DETECTORS - (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.
Factory installed Smoke D etecto rs in the return air,
may be subjected to freezing temperatures during
“off” times due to outside air infiltration. These
smoke detectors have an operational limit of 32°F
to 131°F. Smoke detectors installed in areas that
could be outside those limitations will have to be
moved to prevent having false alarms.
•COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
•STAINLESS STEEL HEAT EXCHANGER - For applica-
tions in corrosive environments, this option provides a
full stainless steel heat exchanger assembly.
•STAINLESS STEEL DRAIN PAN - An optional rust-
proof stainless steel drain pan is available to provide
years of trouble-free operation in corrosive environments.
•BOTTOM DRAIN CONNECTION - An optional bottom
drain connection is available for inside the curb connections for applications in cold environments to reduce
freezing drain lines.
•PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-ofphase condition.
•DIRTY FILTER SWITCH - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
•HINGED FILTER DOOR/“TOOLLESS” BLOWER AND ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.
NOTE:Knobs are shipped inside the unit to prevent ship-
ping damage. These must be field installed for
tool-less operation.
6Unitary Products Group
Page 7
254599-YTG-C-0807
FIELD-INSTALLED ACCESSORIES
•SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•ELECTRIC HEA T ERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent
operation at excessive temperatures.
•ROOF CURBS - Eight and fourteen-inch high roof curbs
provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association
(NRCA) and are shipped knocked-down for field assembly.
Roof curbs are designed to fit inside the base rails of the
unit and include both a wood nailing strip and duct
hanger supports.
•HIGH ALTITUDE NATURAL GAS - Burner orifices and
pilot orifices are provided for proper furnace operation at
altitudes up to 6,000 feet.
•PROPANE - Burner orifices, pilot orifices and gas valve
parts are provided to convert a natural gas furnace to
propane.
•HIGH ALTITUDE PROPANE - Burner orifices and pilot
orifices are provided for proper furnace operation at alti-
tudes up to 6,000 feet. This accessory supplements the
basic propane conversion kit.
•LOW NOX KIT- Required to reduce the emission of
nitrogen oxides below 40 nanograms per joule.
•POWER EXHAUST - Our single input economizer
options are available with power exhaust. Whenever the
outdoor air intake dampers are opened for free cooling,
the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation.
The power exhaust option can only be used on bottom duct configurations.
•BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.
•ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.
•BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.
•FLUE EXHAUST EXTENSION KIT - In locations with
wind or weather conditions which may interfere with
proper exhausting of furnace combustion products, this
kit can be installed to prevent the flue exhaust from
entering nearby fresh air intakes.
•CO
•COIL GUARD - Customers can purchase a coil guard kit
•HAIL GUARD - Hail guard kit is available to prevent unit
•GAS PIPING KIT - This kit supplies all necessary fittings
SENSOR - Senses CO2 levels and automatically
2
overrides the economizer when levels rise above the
present limits.
to protect the condenser coil from damage. This is not a
hail guard kit.
from hail damage. This is a sloped hood that fits above
the coil.
and shut off valve.
Unitary Products Group7
Page 8
254599-YTG-C-0807
TABLE 1: SOUND POWER RATING
UNIT
SIZE
CFM
ESPBLOWER
IWGSPEEDKW631252505001,0002,0004,0008,000
1
-12
SOUND POWER (db 10
Octave Band Centerline Frequency (Hz)
Watts)
SWL
dB(A)
dB(A)
@
10Ft.
0722,2000.3HIGH1.3587877770726560557744
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.
2. At a distance of 10 feet from the blower.
TABLE 2: CAPACITY RATINGS - (ARI 210/240)
MODELMBH
DF072
1. 80/67°F Indoor and 95°F outdoor.
2. EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power
70.510.4
1
EER
TABLE 3: GAS HEAT RATINGS
2
MODEL
DF072N08
DF072N10
1. All units are single-stage heating.
MBH
INPUT
100
125
1
MBH
OUTPUT
80
100
AFUE
(%)
80.5
80.3
TEMP
RISE ºF
25 - 55
35 - 65
input in watts, expressed in Btuh per watt (Btuh/watt).
1. These ratings include the compre ssor and t he con denser fan motors but not the supply air blower motor. The total condenser fan
motor power input is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
2. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER
PERFORMANCE Table, multiply this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity
of the unit.
Nominal Rating
Temperature of Air on Condenser Coil
Gross
Capacity
(MBh)
Power
Input
(kW)
Gross Sensible Capacity (MBh)
8075706568
95°F
Unitary Products Group9
Page 10
TABLE 6: SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE) - SIDE DUCT APPLICATION
1. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for resistance values on applications other than gas / electric units with side duct airflows.
1. All motors have solid bases and are inherently protected. these motors ca n be select ed t o operat e into t heir service f acto r be cause t hey ar e located
in the moving air, upstrea m of any heating device.
MOTOR
HP FRAME
ADJUSTABLE MOTOR PULLEYFIXED BLOWER PULLEY
DESIG-
NATION
OUTSIDE
DIA.
(IN.)
PITCH
DIA.
(IN.)
BORE
(IN.)
DESIG-
NATION
OUTSIDE
DIA.
(IN.)
PITCH
DIA.
(IN.)
BORE
(IN.)
DESIG-
NATION
BELT
(NOTCHED)
PITCH
LENGTH
(IN.)
QTY.
10Unitary Products Group
Page 11
254599-YTG-C-0807
TABLE 8: SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE) - SIDE DUCT APPLICATION
Unit
Tonnage
2
6
Motor
Speed
0.20.30.40.50.6
CFMWattsCFMWattsCFMWattsCFMWattsCFMWatts
Available External Static Pressure - IWG
Hi22568832258931224795022239642182979
Med/Hi21457712127784211980820898262051844
Med20206371999656198567519476961910715
Med/Low----------
Low----------
1
Unit
Tonnage
Motor
Speed
Available External Static Pressure - IWG
0.70.80.91.0
CFMWattsCFMWattsCFMWattsCFMWatts
1
Hi2125971204494019588981864854
Med/Hi2014859196586118968431801806
2
6
Med187673018327401793756--
Med/Low--------
Low--------
1. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESIST ANCES
Table for resistance values.
2. Side Duct application (230 Volts)
TABLE 9: STATIC RESISTANCES
RESISTANCE, IWG
DESCRIPTION
ECONOMIZER
ELECTRIC
HEATERS
BOTTOM DUCT CONNECTIONS
1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.
2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.
3. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
TABLE 11: ELECTRICAL DATA - DF072 BELT DRIVE W/O POWERED CONV. OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
RLA
EACH
LRA
EACH
OD FAN
MOTOR
FLA
208-3-6020.7156.02.35.20.0
230-3-6020.7156.02.35.20.0
DF072
(6.0)
460-3-6010.075.01.32.60.0
575-3-608.254.01.32.00.0
1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block
accessories 2FB04700825 and 2FB04700846 are available for field installation.
TABLE 12: ELECTRICAL DATA - DF072 DIRECT DRIVE W/O POWERED CONV. OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
RLA
EACH
LRA
EACH
OD FAN
MOTOR
FLA
208-3-6020.7156.02.310.60.0
DF072
(6.0)
230-3-6020.7156.02.310.60.0
1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block
accessories 2FB04700825 and 2FB04700846 are available for field installation.
TABLE 13: ELECTRICAL DATA - DF072 BEL T DRIVE W/POWERED CONV. OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
RLA
EACH
LRA
EACH
OD FAN
MOTOR
FLA
208-3-6020.7156.02.35.210.0
230-3-6020.7156.02.35.210.0
DF072
(6.0)
460-3-6010.075.01.32.65.0
575-3-608.254.01.32.04.0
1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block
accessories 2FB04700825 and 2FB04700846 are available for field installation.
TABLE 14: ELECTRICAL DATA - DF072 DIRECT DRIVE W/POWERED CONV. OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
RLA
EACH
LRA
EACH
OD FAN
MOTOR
FLA
208-3-6020.7156.02.310.610.0
DF072
(6.0)
230-3-6020.7156.02.310.610.0
1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block
accessories 2FB04700825 and 2FB04700846 are available for field installation.
SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.
4
RH
RC
Y
W
G
R
Y1
W1
C
G
ADD
JUMPER
THERMOSTAT
1
TERMINALS
UNIT TERMINAL
STRIP TB1
24 VOLT
TRANSFORMER
1
ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET07701024 (INCLUDES SUBBASE).
TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT
2TH04700224.
COOLING / HEATING (ELECTRONIC THERMOSTAT)
SINGLE STAGE
TYPICAL POWER WIRING
REFER TO THE ELECTRICAL DATA
TABLES TO SIZE THE DISCONNECT
SWITCH, OVERCURRENT PROTECTION AND WIRING.
TYPICAL CONTROL WIRING
COOLING ONLY (24 VOLT THERMOSTAT)
THERMOSTAT
TERMINALS
RV
YC
GF
1
24 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER
ON SECOND STAGE COOLING, USE THE THERMOSTAT 2TH0401224.
COOLING / HEATING (ELECTRONIC THERMOSTAT)
1
UNIT TERMINAL
STRIP TB1
R
Y1
Y2
G
C
MULTI STAGE
24 VOLT
TRANSFORMER
COOLING / HEATING (24 VOLT THERMOSTAT)
THERMOSTAT
1
TERMINALS
ADD
RH
JUMPER
1
24 VOLT THERMOSTAT 2ET07701024. TO CONTROLTHE ECONOMIZER ON THE SECOND
STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF
HEAT, USE THERMOSTAT 2TH0471024.
RC
Y
W
G
UNIT TERMINAL
STRIP TB1
R
Y1
Y2
W1
W2
G
C
24 VOLT
TRANSFORMER
3
ELECTRIC HEATER OR 2 STAGE GAS HEAT.
FIGURE 2 - TYPICAL FIELD POWER & CONTROL WIRING
SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE
REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR
P6 ON UNITS WITH ECONOMIZER. TERMINALS A1 ANDA2 PROVIDE A RELAY
OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE
THERMOSTAT SWITCHES TO THE SET-BACK POSITION.
Unitary Products Group15
Page 16
254599-YTG-C-0807
FIGURE 3 - UNIT DIMENSIONS (6 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW
FIGURE 4 - UNIT DIMENSIONS (6 TON COOLING/GAS HEAT) FRONT VIEW
16Unitary Products Group
Page 17
254599-YTG-C-0807
FIGURE 5 - UNIT WITH ECONOMIZER RAINHOOD
DETAIL “A”
DETAIL “B”
FIGURE 6 - UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD
Unitary Products Group17
Page 18
FIGURE 7 - UNIT DIMENSIONS (REAR VIEW)
254599-YTG-C-0807
FILTER
ACCESS
BLOWER MOTOR
ACCESS
DOT PLUGS
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
MOUNTING BRACKET
FOR DICONNECT SWITCH
(Shipped attached to the
blower housing inside
the blower compartment)
DISCONNECT SWITCH LOCATION
AND MOTOR ACCESS PANEL FOR
UNIT WITH “BELT-DRIVE” OPTION
A,B
WIRING ENTRY
(See Detail “B”)
CONTROL BOX
ACCESS
FIGURE 8 - DISCONNECT/BLOWER ACCESS
LOCATION
TABLE 18: UTILITIES ENTRY
HOLEOPENING SIZE (DIA.)USED FOR
A
B
C
D
1
7/8” KO
2” KO
1
Control Wiring
Power Wiring
1-5/8” KOGas Piping (Front)
1-1/2” KO
Gas Piping (Bottom)
1. Opening in the bottom to the unit can be located by the
side in the insulation.
2. Do not remove the 2” knockout ring.
TABLE 19: MINIMUM CLEARANCES
LOCATION
Front
Rear
36” (With Economizer or Fixed Air/
Left Side (Filter Access)
Right Side (Cond. Coil)
Below Unit
Above Unit
1
2
1. Units may be installed on combustible floors made
from wood or class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet.
CLEARANCE
24” (Cooling/Electric Heat)
32” (Gas Heat)
12” (Less Economizer)
Motorized Damper)
24” (Less Economizer)
36” (With Economizer)
24”
0”
72” (For
Condenser Air Discharge)
Side
2
Bottom
Side
Bottom
18Unitary Products Group
Page 19
254599-YTG-C-0807
FIGURE 9 - TYPICAL APPLICATIONS
Unitary Products Group19
Page 20
254599-YTG-C-0807
447/
8
A
BACK OF UNIT
821/
4
D
X
APPROXIMATE
CENTER OF GRAVITY
FRONT OF UNIT
C
B
CONDENSER COIL
Y
END OF UNIT
FIGURE 10 - FOUR AND SIX POINT LOADING
TABLE 20: DF 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility.
TM
York's Sunline Plus
units. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or
set on steel beams above a finished roof. Cooling only, cooling
with gas heat and cooling with electric heat models are available
with a wide variety of factory-mounted options and field-installed
accessories to make them suitable for almost every application.
All units are self-contained and assembled on full perimeter
base rails with holes in the four corners for overhead rigging.
Every unit is completely piped, wired, charged and tested at the
factory to simplify the field installation and to provide years of
dependable operation. All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with power exhaust are suitable for bottom duct
connections only. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of
the unit. For horizontal duct, remove the supply and return air
panels on the rear of the unit.
All compressors include crankcase heaters and all compressors have internal pressure relief. Every refrigerant circuit
includes a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch.The unit control circuit includes a
75 VA transformer, a 24-volt circuit breaker and a relay board
units are convertible single package
with a compressor lockout circuit, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify
the interface of additional field controls. All units have long
lasting powder paint cabinets with 1000 hour salt spray test
approval under ASTMB117 procedures. All models are CSA
listed. All models include a 1-year limited warranty on the
complete unit. Compressors and electric heater elements
carry a 5-year warranty. Aluminized steel and Stainless steel
tubular heat exchangers carry a 10-year warranty.
DESCRIPTION
Units shall be factory-assembled, single packaged, Electric
Cooling/Gas Heat, Electric Cooling/Optional Electric Heat
and designed for outdoor mounted installation.
The 6 ton unit is rated at 10.4 EER. They shall have built-in
field convertible duct connections for down discharge supply/
return or horizontal discharge supply/return, and be available
with factory installed options or field installed accessories. The
units shall be factory wired, piped, charged with R-22 refrigerant and factory tested prior to shipment. All unit wiring shall be
both numbered and color coded. All units the cooling performance shall be rated in accordance with DOE and ARI test
procedures. Units shall be CSA listed, classified to ANSI
Z21.47, UL 1995/CSA No. 236 standards.
UNIT CABINET
Unit cabinet shall be constructed of G90 galvanized steel,
with exterior surfaces coated with a non-chalking, powdered
paint finish, certified at 1000 hours salt spray test per
ASTMB117 standards. Indoor blower section shall be
Unitary Products Group21
Page 22
254599-YTG-C-0807
insulated with a minimum 1/2” thick insulation, coated on the
airside. Aluminum foil faced insulation shall be used in the
furnace compartment and be fastened with ridged fasteners
to prevent insulation from entering the air stream. Cabinet
panels shall be “large” size, easily removable for servicing
and maintenance. Full perimeter base rails shall be provided
to assure reliable transit of equipment, overhead rigging and
proper sealing on roof curb applications. Disposable 1" filters
shall be furnished and be accessible through a removable
access door, sealed airtight. Units filter track shall be
designed to accommodate either 1” or 2” filters. Fan
performance measuring ports shall be provided on the
outside of the cabinet to allow accurate air measurements of
evaporator fan performance without removing panels or
creating air by-pass of the coils. Condensate pan shall be
internally sloped and conform to ASHRAE 62-89 self-draining
standards. Condensate connection shall be a minimum of 3/
4” I.D. female and be a ridged mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
The indoor fan shall be direct drive, multi-speed, or a factory
installed belt drive assembly that includes an adjustable pitch
motor pulley. Job site selected brake horsepower (B.H.P.)
shall not exceed the motors nameplate horsepower rating,
plus the service factor. Units shall be designed not to operate
above service factor. Fan wheel shall be double-inlet type
with forward-curved blades, dynamically balanced to operate
smoothly throughout the entire range of operation. Airflow
design shall be constant air volume. Bearings shall be sealed
and permanently lubricated for longer life and no maintenance.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fan shall be of the direct-driven propeller type,
discharge air vertically, have aluminum blades riveted to a
corrosion resistant steel spider bracket and shall be dynamically balanced for smooth operation. The outdoor fan motor
shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and
staged independently.
REFRIGERANT COMPONENTS
Compressor:
a.Shall be internally protected with internal high-pres-
sure relief and over temperature protection.
b.Shall have internal spring isolation and sound muf-
fling to minimize vibration and noise, and be externally isolated on a dedicated, independent
mounting.
Coils:
a.Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless
internally enhanced copper tubes with all joints
brazed. Special Phenolic coating shall be available
as a factory option.
b.Evaporator and Condenser coils shall be of the
direct expansion, draw-thru, design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a.Thermal expansion devices (TXV’s).
• DF072 uses a fixed orifice distributor.
b.Filter drier/strainer to eliminate any moisture or for-
eign matter.
c.Accessible service gage connections on both suc-
tion and liquid lines to charge, evacuate, and measure refrigerant pressure during any necessary
servicing or troubleshooting without losing charge.
d.The refrigeration system shall provide at least 15°F
of sub-cooling at design conditions.
UNIT CONTROLS
a.Unit shall be complete with self-contained low-volt-
age control circuit protected by a resetable circuit
breaker on the 24-volt transformer side.
b.Unit shall incorporate a lockout circuit which pro-
vides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor.
c.Loss-of-charge/Low-pressure switch.
d.High-pressure switch.
e.Freeze-protection thermostat, evaporator coil.
f.If any of the above safety devices trip, a LED (light-
emitting diode) indicator shall flash a diagnostic
code that indicates which safety switch has tripped.
g.Unit shall incorporate “AUTO RESET” compressor
over temperature, over current protection.
h.Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for
easy hook-up.
i.Unit control board shall have on-board diagnostics
and fault code display.
j.Standard controls shall include anti-short cycle and
low voltage protection, and permit cooling operation
down to 0°F.
k.Control board shall monitor each refrigerant safety
switch independently.
l.Control board shall retain last 5 fault codes in non
volatile memory, which will not be lost in the event of
a power loss.
GAS HEATING SECTION (SINGLE OR 2 STAGE)
Shall be designed with induced draft combustion with post
purge logic, energy saving direct spark ignition, and redun-
nt main gas valve. Venter wheel shall be constructed of
da
stainless steel for corrosion resistance. The heat exchanger
shall be of the tubular type, constructed of T1-40 aluminized
22Unitary Products Group
Page 23
254599-YTG-C-0807
steel for corrosion resistance and allowing minimum mixed
air entering temperature of 25°F. Burners shall be of the
inshot type, constructed of aluminum coated steel and contain air mixture adjustments. All gas piping shall enter the unit
cabinet at a single location through either the side or curb,
without any field modifications. Integrated control boards
shall provide timed control of evaporator fan functioning and
burner ignition. Heating section shall be provided with the following minimum protection:
a.Primary and auxiliary high-temperature limit switches.
b.Induced draft motor speed sensor.
c.Flame roll out switch.
d.Flame proving controls.
e.If any of the above safety devices trip, a LED (light-
emitting diode) indicator shall flash a diagnostic
code that indicates which safety switch has tripped.
ELECTRIC HEA T ING SECTION
An electric heating section, with nickel chromium elem en ts,
shall be provided in a range of 5 thru 3 0 KW , offering two
stages of capacity - 16 KW and above on 208/230 volt he aters
and 20 KW and above on 460 and 575 volt heaters. The heating section shall have a primary limit control(s) and automatic
reset to prevent the heating element system from operating at
an excessive temperature. The heating se ctio n assembly
shall slide out of the unit for easy maintenance and servi ce.
Units with Electric Heating shall be wired for a single point
power supply with branch circuit fusing (where required).
UNIT OPERATING CHARACTERISTICS
a.Unit shall be capable of starting and running at 125°F
outdoor temperature, exceeding maximum load criteria of ARI Standard 210/240. The compressor, with
standard controls, shall be capable of operation down
to 0°F outdoor temperature. Unit shall be provided
with fan time delay to prevent cold air delivery before
heat exchanger warms up (Gas heat only).
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory
provided location and be capable of side or bottom entry, to
minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
control wiring.
STANDARD LIMITED WARRANTIES
•Compressor 5 Years
•Heat Exchanger 10 Years
•Electric Heat Element 5 Years
•Other Parts 1 Year
OPTIONAL OUTDOOR AIR (Shall be made available by
either/or):
•ELECTRONIC ENTHALPY AUTOMATIC ECONO-MIZER- Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring
return damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return
air damper assembly to take in CFM of outdoor air to
meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer operation, a mixed-air temperature control shall
modulate the outdoor and return air damper assembly to
prevent the supply air temperature from dropping below
55°F. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy
control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood
that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully
close on power loss.
•MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air
dampers are positioned by a 2-position, spring-return
damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when
dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor damper
assembly to take in the design CFM of outdoor air to
meet the ventilation requirements of the conditioned
space during normal operation. Whenever the indoor fan
motor is energized, the dampers open up to one of two
pre-selected positions - regardless of the outdoor air
enthalpy. Dampers return to the fully closed position
when the indoor fan motor is de-energized. Dampers
shall fully close on power loss.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
•ROOF CURB - 14"and 8” high, full perimeter curb with
wood nailer (shipped knocked-down).
•BAROMETRIC RELIEF DAMPER - Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
t.
the uni
•PROPANE CONVERSION KIT - Contains new orifices
and gas valve parts to convert from natural to L.P. gas.
One per unit required.
•HIGH ALTITUDE - NATURAL GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude.
•HIGH ALTITUDE - PROPANE GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude. Must be used with propane conversion kit.
•LOW NOX - Required to reduce the emission of nitrogen
oxides below 40 nanograms per joule.
Unitary Products Group23
Page 24
•GAS PIPING - Contains 1/2” pipe nipples, fittings and
gas cock (including panel assess gaskets) required for
bottom gas supply connection with external shut off.
•POWER EXHAUST OPTION - To work in conjunction
with economizers.
•ELECTRIC HEATERS
•ECONOMIZER/MOTORIZED DAMPER RAIN HOOD Contains all hood panels and the hardware for assembling.
•MANUAL OUTDOOR AIR DAMPER
•COIL GUARD KIT - Guard for cooling coil.
•HAIL GUARD
•FLUE EXHAUST EXTENSION
OTHER FACTORY INSTALLED OPTIONS
•POWER EXHAUST OPTION - To work in conjunction
with economizers.
•STAINLESS STEEL HEAT EXCHANGER
•ST A INLES S STEEL DRAIN PAN
•BOTTOM DRAIN CONNECTION
•TECHNICOAT PHENOLIC COATED CONDENSER
AND EVAPORATOR COIL
•ELECTRONIC SINGLE ENTHALPY ECONOMIZER
•DIRTY FILTER SWITCH
•PHASE MONITOR
•COIL GUARD
•POWERED GFI CONVENIENCE OUTLET
•NON-POWERED GFI CONVENIENCE OUTLET
•BAS CONTROLS (Simplicity
®
INTELLI- Comfort™,
CPC, JOHNSON, HONEYWELL, NOVAR)
•BAS READY ECONOMIZER (2 - 10 V. D. C.
ACTUATOR WITHOUT A CONTROLLER)
•HINGED FILTER DOOR ACCESS AND TOOLESS
ACCESS PANELS