York DEX, DEX Affinity R410A Technical Guide

®
718434-YTG-A-0811
TECHNICAL GUIDE R-410A AFFINITY™ SERIES DEX MODELS 2 - 4 TON 60 Hertz

Description

These York® Affinitypackaged air conditioners are designed for outdoor installation. Only utility and duct connections are required at the point of installation.
Field-installed electric heater accessories are available to provide electric heat, if required.
Tested in accordance with:
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
718434-YTG-A-0811
Direct Drive Condenser
Fan Motor
Highly Efficient Enhanced Copper
Tube/Aluminum Fin
Indoor Coil
Highly Efficient Enhanced Copper Tube/Enhanced Aluminum Fin
OR Micro-Channel Aluminum Tube/Aluminum Fin Condenser
Decorative Protective
Coil Guard
Direct Drive Blower Motor With
Slide-Out Blower Assembly
Heavy Gauge
Removable Base Rails
High-Efficiency Compressor
Rigidly Mounted
Long-Lasting
Powder Paint Finish
Low Voltage
Terminal Block
High Voltage
Terminal Block
Back And Bottom
Return Air and Supply
Air Duct Opening

Table of Contents

Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Component Location

Cooling Only
2 Johnson Controls Unitary Products

Nomenclature

D 1 024 06
A
EX
Product Category
D = Single Package Air Conditioner
(Air Cooled)
Product Generation
1 = New or Current Design
Factory Installed Electric Heat
A = No Electric Heat Installed
Product Identifier
EX = R-410A 15 SEER
024 = 24,000 BTUH 030 = 30,000 BTUH 036 = 36,000 BTUH
Voltage Code
06 = 208/230-1-60 25 = 208/230-3-60 46 = 460-3-60
042 = 42,000 BTUH 048 = 48,000 BTUH
Nominal Cooling Capacity (MBH)
Cooling Only
718434-YTG-A-0811

Features and Benefits

Standard Features

Operating Efficiency - All air conditioners provide operating efficiencies of 15 SEER. All efficiencies exceed legislated minimum levels.
On Site Flexibility - All model sizes share a common, compact design cabinet in a single footprint. The installer has the flexibility of setting one curb and placing the proper tonnage unit on that curb after the internal load has been determined. Field convertible duct connections from side shot to down shot allows the installer to have greater flexibility with less inventory.
Lower Installation Cost - Installation time and costs are reduced by easy power and control wiring connections. The small base dimension means less space is required on the ground or roof, plus, the installer can fit this unit between the wheel wells of full size pick-up truck. All units are completely wired, charged with R-410A and tested prior to shipment. Unique test stations using a new state of the art computerized process system are used to insure product quality. Refrigerant charge and component part numbers are verified via computers at assembly. Vital run test statistics such as system pressure, motor currents, air velocity and temperature, unit vibration, and gas system safeties are monitored and recorded by the system to insure unit performance. Equal size, side supply and return duct connections allows easy hook-up of ducts to match low crawl spaces without transition pieces.
Utility Connections Made Easy - Electric utility knockouts are provided through the bottom as well as the side of the unit. Utility connections can be made quickly and with a minimum amount of field labor. A field supplied and field installed electrical disconnect switch must be installed.
Convertible Airflow Design - The bottom duct openings are covered when they leave the factory ready to be used for a side supply/side return application. If a bottom supply/bottom return application is desired, you simply remove the two panels from the bottom of the unit and place them in the side supply/side return duct openings. No panel cutting is required and no accessory panel is necessary. Convertible airflow design allows maximum field flexibility and minimum inventory.
Johnson Controls Unitary Products 3
Condensate Pan - A non-corrosive, long-lasting, water­tight pan is positioned below the evaporator coil to collect and drain all condensate. Less collection of stagnate condensate will build-up. The condensate pan conforms to ASHRAE 62-89 standards (Ventilation for Acceptable Indoor Air Quality).
Condensate Drain - The heavy duty, 3/4 inch NPTI copper connection is more durable over time. The connection is rigidly mounted to assure proper fit and leak tight seal.
Durable Finish - The cabinet is made of pre-painted steel. The pre-treated galvanized steel provides a better paint to steel bond, which resists corrosion and rust creep. Special primer formulas and matted-textured finish insure less fading when exposed to sunlight.
Full Perimeter Base Rails - The easily removable base rails provide a solid foundation for the entire unit and protects the unit during shipment. The rails provide fork lift access from all sides, and rigging holes are also provided so that an overhead crane can be used to place the units on a roof. On applications where the unit is placed on a pad, the base will keep the unit off the pad to deter corrosion. On applications where height is limited, the inch high base rails may be removed on location.
More Attractive Appearance - A single piece Water Shed top cover containing a top discharge condenser fan arrangement requires less square footage on installation and provides a wider variety of installations. The one piece design adds greater water integrity. Rounded corners with water drip edges add to the attractive appearance. The cabinet panels have a non-fibrous insulation that will not release insulation fibers into conditioned area.
Top Discharge - The top discharge condenser fan does not disrupt neighboring areas or dry-out vegetation surrounding the unit. The warm air from the top mounted fan is blown up away from the structure and any landscaping. This allows compact location on multi-unit applications.
Condenser Coil Grille - All models utilize a stamped “Louvered” design which provides superior impact protection against smaller objects during transit and after installation.
Low Operating Sound Level - The upward air flow carries the normal operating noise up and away from the living area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the
718434-YTG-A-0811
rippled fins of the condenser coil muffle the normal fan motor and compressor operating sounds. The unique formed base pan also aids in sound alterations with it's Super-Structure design. This design strategically places embossments in the pan for optimum strength and rigidity.
Fan System - All models operate over a wide range of design conditions with an electrically commutated fan motor. These units easily match all types of applications and provide greater on site flexibility to match comfort requirement. The cooling speed is factory set and can be field adjusted to a second speed. The heating speed is factory set but can be field adjusted. This allows maximum comfort conditions.
Simple Control Circuit - A low voltage printed circuit board contains a diagnostic indicator light and a low voltage terminal strip. An additional set of pin connectors is also provided to simplify the field interface of external controls. Mate-n-lock plug connectors are used. The electrical control box is not located in the compressor compartment. The controls are mounted on a Control-Tilt control panel to allow the access cover to be removed for trouble shooting and maintenance without affecting the normal system operating pressures. All wiring internal to the unit is color/number coded.
Protected Compressor - The compressor is internally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protect the compressor if undesirable operating conditions occur.
Pressure Switches - High pressure and low pressure/ loss of charge switches standard in all units. When abnormal conditions are sensed through the pressure switches, the unit will lock out preventing any further operation until reset or problem is corrected.
Exclusive Coil Design - Grooved copper tubes and enhanced aluminum fin construction improves heat transfer for maximum efficiency and durability.
Self Diagnostic Fan Control Module - Due to this se lf diagnostic control, less on site time is required to trouble shoot these units.
Low Maintenance - Long life, permanently lubricated condenser and evaporator fan motor bearings need no annual maintenance adding greater reliability to the unit. Blower assembly can be easily cleaned by the unique Slip- Track slide-out blower assembly.
Secured Service Access Ports - Protected, externally mounted, re-usable service access ports are provided on both the high and low lines for ease of evacuating and charging the system. No final field mounting required.
Easy Service Access - A large, single panel covers the electrical controls to make servicing easy. The blower compartment has an additional large panel with a built-in handle tab. Removing this panel will allow the blower assembly to slide-out for easy removal for maintenance and ease of trouble shooting.
Replacement Parts - The installer requires no special training to replace any of the components of these units and does not need to maintain an inventory of unique parts.
System Integration - Each unit has the internal ability to integrate an electronic air cleaner or humidifier to work in conjunction with the base unit.

Field Installed Accessories

Economizer Down Discharge/Supply Kit - Modulating integrated economizer provides simultaneous operation between the mechanical cooling and economizer operation. Independent blade design insures proper control and less than 1% leak rate. Includes hood and mesh bird screen filter integrated into the hood, dry bulb sensor and relief damper. Separate field accessories of single enthalpy and dual enthalpy are also available. A built-in barometric relief of 25% is provided.
Single Enthalpy Sensor - Sensor replaces dry bulb sensor standard in economizer kit. Provides improved economizer operation by sensing the dry bulb temperature from outdoors plus the enthalpy content of the outdoor air.
Dual Enthalpy Sensor - Additional sensor to single enthalpy sensor. Sensor senses both the return air temperature dry bulb and humidity in conjunction with the single enthalpy to determine the most economical mix. Single Enthalpy sensor also required.
Hail Guard Kit - Kit contains protective grilles made of expanded aluminum with full perimeter frame. Sloped hoods are also included to assure maximum protection.
Filter/Frame Kit (Single Phase Only) - Kit contains the necessary hardware to field install return air filters into the base unit. Pre-cut filter racks and appropriate cleanable standard size filters are shipped in one kit. The filter rack is suitable for either 1" or 2" filters. (1" filter is supplied) This kit is available for single phase horizontal or vertical duct application only. Standard in all 3 Phase models.
Motorized Fresh Air Damper - Designed for duct mounted side supply/return and unit mounted down supply/return applications. Damper capable of providing 0% through 50% of outdoor air (field supplied). Closes on power loss, includes hood and screen assembly.
Rectangle To Round Adapters - Kit includes one supply and one return air rectangle to round duct adapter. Adapters are preformed and designed to fit over current duct openings on the base unit. Transition is from side square duct opening to 14" round duct opening.
Roof Curbs - NRCA approved curbs provide proper fit to base unit for rooftop installations. Curbs are designed to be assembled through hinge pins in each corner. Kit also provides seal strip to assure a water tight seal. 8 and 14 inch high roof curbs are available.
Manual Outdoor Damper - Provides 0% through 50% outdoor air capability (field adjustable). Designed for duct mounted side supply/return applications. Includes hood and screen assembly.
Wall Thermostat - The units are designed to operate with 24-volt electronic and electro-mechanical thermostats. All units can operate with single stage heat/single stage cool thermostats - with or without the economi z e r.
Low Ambient Kit - Kit provides necessary hardware to convert unit to operate in cooling cycle down to 0º F. Standard unit operation 45º F.
Transformer Kit - Kit provides necessary hardware to provide single phase models from factory furnished 40 VA transformer capability to 75 VA transformer capability. (Required on installations with economizer or motorized damper.)
4 Johnson Controls Unitary Products
718434-YTG-A-0811

Guide Specifications

General
Units shall be manufactured by Johnson Controls Unitary Products in an ISO 9001 certified facility. YORK’s Affinity™ package units give you the flexibility and choices you need in today’s market. These packaged air conditioners are designed for outdoor installation. Only utility and duct connections are required at the point of installation.
Description
Units shall be factory-assembled, single packaged, Electric Cooling units, designed for outdoor mounted installation. For SEER ratings, refer to technical literature. They shall have built in, equal size, field convertible duct connections for down discharge supply/return or horizontal discharge supply/return. The units shall be factory wired, piped, charged with R-410A Refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. All units shall be manufactured in a facility certified to ISO 9001 standards, and the cooling performance shall be rated in accordance with DOE and ARI test procedures. Units shall be CSA listed and classified to ANSI Z21.47/CAN/CSA 2.3 standards and UL 1995/CAN/CSA No. 236-M90 conditions.
Unit Cabinet
Unit cabinet shall be constructed of G-90, pre-paint textured steel, certified at 500 hours salt spray test per ASTM-B117 standards. The unit top shall be a single piece “Water Shed” design, with drip edges and no-seam corners to provide optimum water integrity. Unit shall have a rigidly mounted condenser coil guard to provide protection from objects and personnel after installation. Indoor blower section shall be insulated with up to 3/4” thick, aluminum, foil faced insulation, fastened to prevent insulation from entering the air stream. Cabinet panels shall be “large” size, easily removable for servicing and maintenance, with built-in lift handles. Unit shall be built on a formed, “Super-Structure” design base pan, with embossments at critical points to add strength, rigidity and aid in minimizing sound. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging, for truck access and proper sealing on roof curb applications. Base rails shall be removable, when required, to lower unit height. Filters shall be furnished and be accessible through a removable access door, sealed airtight. Units vertical discharge and return duct configuration shall be designed to fit between standard 24” O.C. beams without modification to building structure, duct work and base unit. Condensate pan shall be internally sloped and conform to ASHRAE 62-89 self-draining standards, with 3/4” NPTI copper, ridged mount connection.
Indoor (Evaporator) Fan Assembly
Fan shall be direct drive design. Fan wheel shall be double-inlet type with forward-curved blades, dynamically balanced to operate smoothly throughout the entire range of opera tion.
Airflow design shall be constant air volume. Bearings shall be sealed and permanently lubricated for longer life and no maintenance. Fan assembly shall be “Slip Track” (slide-out) design for easy removal and cleaning.
Outdoor (Condenser) Fan Assembly
The outdoor fan shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to corrosion resistant steel spider bracket and shall be statically balanced for smooth operation. The outdoor fan motor shall be totally enclosed with permanently lubricated bearings and internally protected against overload conditions.
Refrigerant Components
Compressors:
a. Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over temperature protection. The hermetic motor shall be suction gas cooled and have a voltage range of +/- 10% of the unit nameplate voltage.
b. Shall have internal isolation and sound muffling to
minimize vibration and noise, and be externally isolated on a dedicated, independent mounting.
Coils:
a. Evaporator coils shall have aluminum plate fins
mechanically bonded to seamless internally enhanced copper tubes with all joints brazed.
b. Evaporator coil shall be of the direct expansion, draw
through design.
c. Condenser coils shall have aluminum plate fins
mechanically bonded to seamless internally enhanced copper tubes with all joints brazed or Mircro-Channel aluminum tube, aluminum fins.
d. Condenser coil shall be draw through design.
Refrigerant Circuit and Refrigerant Safety Components shall include:
a. Independent fixed orifice expansion devices. b. Filter/strainer to eliminate any foreign matter.
Electric Heating Section (Field Install Accessory)
An electric heating section, with nickel chromium elements, shall be provided in a range of 5 thru 25 KW. The heating section shall have a primary limit control(s) (automatic reset) to prevent the heating element system from operating at an excessive temperature. The Heating Section assembly shall slide out of the unit for easy maintenance and service. Units with Electric Heating Sections shall be wired for a single point power supply with branch circuit fusing (where required).
Johnson Controls Unitary Products 5
718434-YTG-A-0811

Physical Data

DEX024-048 Physical Data

Component
Nominal Tonnage 2.0 2.5 3.0 3.5 4.0
ARI COOLING PERFORMANCE
Gross Capacity @ ARI A point (Btu) 23.5 29.2 36.8 44.5 50.8 ARI net capacity (Btu) 23.2 28.6 36.0 43.5 49.0 EER 12.3 12.3 12.3 12.3 12.3 SEER 15 15 15 15 15 Nominal CFM 800 1000 1150 1400 1600 System power (KW) 1.9 2.3 2.9 3.5 4.0 Refrigerant type R-410A R-410A R-410A R-410A R-410A Refrigerant charge (lb-oz) 5-0 8-0 8-0 7-8 10-0
DIMENSIONS (inches)
Length 49 1/8 49 1/8 49 1/8 49 1/8 49 1/8 Width 47 1/4 47 1/4 47 1/4 47 1/4 47 1/4 Height 33 1/2 33 1/2 33 1/2 41 1/2 41 1/2
OPERATING WT. (lbs.) 355 390 400 410 440
COMPRESSORS
Type Scroll 2-spd Scroll 2-spd Scroll 2-spd Scroll 2-spd Scroll 2-spd Quantity 1 1 1 1 1
CONDENSER COIL DATA
Face area (Sq. Ft.) 11.7 11.7 11.7 16.4 16.4 Rows 1 2 2 1 2 Fins per inch 20 20 20 20 20 Tube diameter (in.) 3/8 3/8 3/8 3/8 3/8 Circuitry Type Interlaced Interlaced Interlaced Interlaced Interlaced
EVAPORATOR COIL DATA
Face area (Sq. Ft.) 4.38 4.38 4.38 5.63 5.63 Rows 2 2 3 3 3 Fins per inch 15 15 15 16 16 Tube diameter 3/8 3/8 3/8 3/8 3/8 Circuitry Type Interlaced Interlaced Interlaced Interlaced Interlaced Refrigerant control TX Valve TX Valve TX Valve TX Valve TX Valve
CONDENSER FAN DATA
Fan diameter (Inch) 22 22 22 22 22 Type Prop. Prop. Prop. Prop. Prop. Drive type Direct Direct Direct Direct Direct No. speeds 1 1 1 1 1 Number of motors 1 1 1 1 1 Motor HP each 1/4 1/4 1/4 1/4 1/3 RPM 850 850 850 1100 1100 Nominal total CFM 1800 1800 2400 3000 3000
DIRECT DRIVE EVAP FAN DATA
Quantity 1 1 1 1 1 Fan Size (Inch) 10 x 8 10 x 8 10 x 8 11 x 10 11 x 10 Type Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal No. speeds 2 2 2 2 2 Motor HP each 1/2 1/2 1/2 3/4 3/4 RPM Variable Variable Variable Variable Variable Frame size 48 48 48 48 48
FILTERS
Quantity - Size 2 - 22 x 14 x 1 2 - 22 x 14 x 1 2 - 22 x 14 x 1 2 - 22 x 14 x 1 2 - 22 x 14 x 1
DEX024 DEX030 DEX036 DEX042 DEX048
Models
6 Johnson Controls Unitary Products

Unit Limitations

Size
(Tons)
024
(2.0)
030
(2.5)
036
(3.0)
042
(3.5)
048
(4.0)
718434-YTG-A-0811
Unit Limitations
Model Unit Voltage
DEX 208/230-1-60 187 252 115
DEX 208/230-1-60 187 252 115
208/230-1-60 187 252 115
DEX
DEX 208/230-1-60 187 252 115
DEX
208/230-3-60 187 252 115
460-3-60 432 504 115
208/230-1-60 187 252 115 208/230-3-60 187 252 115
460-3-60 432 504 115
Applied Voltage Outdoor DB Temp
Min Max Max (°F)
Johnson Controls Unitary Products 7
718434-YTG-A-0811

Capacity Performance

DEX024-048 Cooling Capacities

DEX024 (2.0 Ton)

Air on
Evaporator Coil
CFM
600
800
600
800
600
800
WB
(°F)
77 21.5 1.1 7.5 7.8 6.8 - - - 21.6 1.3 9.8 8.3 6.9 - - ­72 21.3 1.1 14.3 12.7 11.0 9.3 - - 20.7 1.3 14.8 12.8 10.8 8.9 - ­67 21.2 1.1 21.2 17.6 15.2 12.9 10.6 - 19.7 1.3 19.7 17.3 14.8 12.2 9.7 ­62 20.2 1.1 20.2 20.2 19.9 15.6 11.4 7.1 18.4 1.3 18.4 18.4 18.3 14.0 9.8 5.5 57 19.4 1.1 19.4 19.4 19.4 15.1 10.9 6.6 18.2 1.3 18.2 18.2 18.2 13.9 9.6 5.3 77 30.1 1.6 13.1 12.3 10.2 - - - 28.9 1.8 13.9 11.7 9.6 - - ­72 28.4 1.6 19.9 17.3 14.8 12.2 - - 26.9 1.8 19.4 16.8 14.1 11.4 - ­67 26.7 1.5 26.7 22.4 19.3 16.2 13.1 - 24.9 1.7 24.9 21.8 18.6 15.4 12.2 ­62 24.0 1.5 24.0 24.0 24.0 20.6 17.1 13.7 22.7 1.7 22.7 22.7 22.7 19.2 15.7 12.3 57 24.4 1.5 24.4 24.4 24.4 20.8 17.3 13.7 23.0 1.7 23.0 23.0 23.0 19.5 15.9 12.4
77 21.8 1.4 12.1 8.8 7.0 - - - 20.2 1.6 12.7 8.7 6.5 - - ­72 20.0 1.4 15.2 13.0 10.7 8.4 - - 18.4 1.6 14.7 12.4 10.1 7.8 - ­67 18.3 1.4 18.3 17.1 14.3 11.6 8.8 - 16.6 1.6 16.6 16.0 13.6 10.3 6.9 ­62 16.6 1.4 16.6 16.6 16.6 12.4 8.2 3.9 15.4 1.6 15.4 15.4 15.4 11.2 7.1 2.9 57 17.0 1.4 17.0 17.0 17.0 12.7 8.3 4.0 15.5 1.6 15.5 15.5 15.5 12.0 8.4 4.8 77 27.8 2.0 14.7 11.2 9.0 - - - 25.8 2.3 15.2 10.6 8.3 - - ­72 25.5 1.9 18.9 16.2 13.4 10.7 - - 23.6 2.2 18.3 15.5 12.7 9.9 - ­67 23.2 1.9 23.2 21.2 17.9 14.6 11.3 - 21.4 2.2 21.4 20.4 17.1 13.8 10.5 ­62 21.4 1.9 21.4 21.4 21.4 17.9 14.4 10.9 19.9 2.1 19.9 19.9 19.9 16.4 12.9 9.4 57 21.6 1.8 21.6 21.6 21.6 18.1 14.6 11.1 20.0 2.1 20.0 20.0 20.0 16.5 13.0 9.5
77 18.7 1.8 13.2 8.5 6.0 - - ­72 16.8 1.8 14.1 11.8 9.4 7.1 - ­67 15.0 1.8 15.0 15.0 12.9 9.0 5.1 ­62 14.2 1.8 14.2 14.2 14.2 10.1 6.0 1.9 57 14.1 1.8 14.1 14.1 14.1 11.3 8.4 5.6 77 23.7 2.5 15.7 10.1 7.6 - - ­72 21.7 2.4 17.6 14.8 11.9 9.1 - ­67 19.6 2.3 19.6 19.5 16.2 13.0 9.7 ­62 18.4 2.3 18.4 18.4 18.4 15.0 11.5 8.0 57 18.3 2.3 18.3 18.3 18.3 14.8 11.3 7.8
Net
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
115°F
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
Temperature of Air on Condenser Coil
Net
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
8 Johnson Controls Unitary Products

DEX030 (2.5 Ton)

Air on
Evaporator Coil
CFM
675
1000
675
1000
675
1000
WB
(°F)
77 29.5 1.3 14.1 12.0 9.9 - - - 27.9 1.5 13.4 11.3 9.2 - - ­72 27.2 1.3 18.6 16.2 13.7 11.3 - - 25.7 1.5 17.9 15.5 13.1 10.6 - ­67 25.0 1.3 23.0 20.3 17.5 14.8 12.0 - 23.5 1.5 22.5 19.7 16.9 14.1 11.3 ­62 22.8 1.4 22.8 22.8 21.4 17.3 13.3 9.2 21.5 1.5 21.5 21.5 20.7 16.5 12.4 8.3 57 20.1 1.4 20.1 20.1 20.3 15.8 11.2 6.6 20.0 1.5 20.0 20.0 20.2 15.8 11.4 7.0 77 37.4 2.1 16.7 14.7 12.0 - - - 37.2 2.3 17.4 14.7 12.0 - - ­72 36.3 2.1 24.7 21.5 18.3 15.1 - - 34.6 2.2 24.0 20.8 17.6 14.4 - ­67 35.3 2.1 32.7 28.3 24.5 20.8 17.0 - 32.0 2.2 30.7 26.9 23.2 19.4 15.7 ­62 31.0 1.9 31.0 31.0 28.8 24.8 20.7 16.6 29.2 2.1 29.2 29.2 28.0 23.9 19.8 15.7 57 30.5 1.9 30.5 30.5 30.5 26.3 22.1 17.9 28.9 2.1 28.9 28.9 28.8 24.7 20.5 16.3
77 26.3 1.7 12.6 10.6 8.6 - - - 24.3 2.0 12.7 9.3 7.8 - - ­72 24.2 1.7 17.3 14.8 12.4 10.0 - - 22.2 2.0 16.4 14.0 11.6 9.2 - ­67 22.0 1.7 21.9 19.1 16.2 13.4 10.6 - 20.2 2.0 20.1 18.7 15.4 12.1 8.8 ­62 20.2 1.7 20.2 20.2 20.0 15.7 11.5 7.3 18.3 2.0 18.3 18.3 18.3 14.1 10.0 5.8 57 19.9 1.7 19.9 19.9 20.2 15.9 11.6 7.4 18.3 2.0 18.3 18.3 18.6 14.9 11.1 7.4 77 37.1 2.7 18.1 14.7 12.0 - - - 34.0 2.9 17.7 13.6 10.9 - - ­72 32.9 2.5 23.4 20.1 16.9 13.7 - - 30.5 2.8 22.4 19.2 16.0 12.8 - ­67 28.6 2.3 28.6 25.5 21.8 18.0 14.3 - 27.1 2.7 27.1 24.8 21.1 17.4 13.6 ­62 27.5 2.4 27.5 27.5 27.1 23.0 18.9 14.8 25.6 2.7 25.6 25.6 25.4 21.3 17.3 13.2 57 27.3 2.4 27.3 27.3 27.2 23.1 18.9 14.8 25.5 2.7 25.5 25.5 25.4 21.3 17.2 13.1
77 22.3 2.2 12.8 8.1 7.1 - - ­72 20.3 2.2 15.5 13.2 10.8 8.5 - ­67 18.3 2.2 18.3 18.3 14.6 10.8 7.1 ­62 16.5 2.2 16.5 16.5 16.7 12.5 8.4 4.2 57 16.8 2.2 16.8 16.8 17.0 13.8 10.6 7.4 77 30.8 3.1 17.4 12.5 9.8 - - ­72 28.2 3.1 21.5 18.3 15.1 11.9 - ­67 25.6 3.0 25.6 24.1 20.4 16.7 12.9 ­62 23.8 2.9 23.8 23.8 23.7 19.7 15.6 11.5 57 23.7 2.9 23.7 23.7 23.7 19.6 15.5 11.4
Net
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
115°F
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
Temperature of Air on Condenser Coil
Net
Capacity
(MBh)
718434-YTG-A-0811
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Johnson Controls Unitary Products 9
718434-YTG-A-0811

DEX036 (3.0 Ton)

Air on
Evaporator Coil
CFM
800
1150
800
1150
800
1150
WB
(°F)
77 36.6 1.5 17.4 15.3 12.6 - - - 34.0 1.7 17.2 14.4 11.7 - - ­72 31.9 1.5 21.9 18.9 15.9 12.9 - - 30.1 1.7 21.6 18.5 15.4 12.3 - ­67 27.2 1.5 26.5 22.6 19.2 15.7 12.3 - 26.3 1.7 25.9 22.5 19.1 15.7 12.3 ­62 26.6 1.5 26.6 26.6 25.4 21.2 17.0 12.8 25.1 1.7 25.1 25.1 24.2 20.1 15.9 11.8 57 23.8 1.5 23.8 23.8 24.0 19.8 15.5 11.2 23.6 1.7 23.6 23.6 23.6 19.4 15.2 11.0 77 48.0 2.4 23.1 19.5 15.9 - - - 46.1 2.7 22.2 18.7 15.1 - - ­72 44.5 2.4 30.7 26.6 22.5 18.4 - - 42.3 2.7 29.7 25.6 21.5 17.5 - ­67 41.1 2.4 38.3 33.7 29.1 24.5 19.9 - 38.5 2.6 37.1 32.6 28.0 23.4 18.8 ­62 37.5 2.3 37.5 37.5 36.4 31.4 26.4 21.4 35.7 2.5 35.7 35.7 34.7 29.7 24.7 19.7 57 37.6 2.3 37.6 37.6 37.8 32.6 27.4 22.3 35.7 2.5 35.7 35.7 35.7 30.5 25.4 20.3
77 31.4 1.9 16.9 13.6 10.7 - - - 28.7 2.2 16.5 12.0 9.5 - - ­72 28.4 1.9 21.2 18.0 14.9 11.8 - - 26.1 2.2 20.0 16.9 13.9 10.8 - ­67 25.4 1.9 25.4 22.5 19.1 15.7 12.3 - 23.5 2.2 23.5 21.9 18.2 14.6 11.0 ­62 23.5 1.9 23.5 23.5 23.1 19.0 14.9 10.8 21.6 2.2 21.6 21.6 21.4 17.3 13.3 9.2 57 23.5 1.9 23.5 23.5 23.2 19.0 14.9 10.7 21.9 2.2 21.9 21.9 21.7 17.8 13.9 10.0 77 44.2 3.2 21.3 17.8 14.3 - - - 41.1 3.4 21.3 16.5 13.0 - - ­72 40.1 3.1 28.6 24.6 20.6 16.5 - - 37.4 3.3 27.5 23.5 19.4 15.4 - ­67 36.0 2.9 36.0 31.4 26.8 22.3 17.7 - 33.8 3.2 33.8 30.5 25.9 21.4 16.8 ­62 33.9 2.9 33.9 33.9 32.9 28.0 23.0 18.0 31.5 3.2 31.5 31.5 31.1 26.2 21.3 16.5 57 33.7 2.9 33.7 33.7 33.5 28.5 23.4 18.3 31.7 3.1 31.7 31.7 31.5 26.6 21.6 16.6
77 26.1 2.4 16.2 10.5 8.3 - - ­72 23.8 2.4 18.9 15.8 12.8 9.8 - ­67 21.6 2.4 21.6 21.2 17.3 13.5 9.6 ­62 19.8 2.4 19.8 19.8 19.8 15.7 11.6 7.6 57 20.3 2.4 20.3 20.3 20.1 16.5 12.9 9.3 77 38.0 3.8 21.2 15.2 11.7 - - ­72 34.8 3.8 26.4 22.4 18.3 14.3 - ­67 31.6 3.7 31.6 29.6 25.0 20.5 15.9 ­62 29.2 3.6 29.2 29.2 29.2 24.4 19.7 14.9 57 29.6 3.6 29.6 29.6 29.5 24.7 19.8 15.0
Net
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
115°F
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
Temperature of Air on Condenser Coil
Net
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
10 Johnson Controls Unitary Products

DEX042 (3.5 Ton)

Air on
Evaporator Coil
CFM
925
1400
925
1400
925
1400
WB
(°F)
77 40.2 1.9 21.0 17.4 13.7 - - - 37.3 2.2 19.2 15.7 12.2 - - ­72 37.1 1.9 26.3 22.4 18.5 14.7 - - 34.5 2.1 24.8 20.9 17.1 13.3 - ­67 34.0 1.9 31.6 27.5 23.3 19.2 15.1 - 31.6 2.1 30.3 26.2 22.1 18.0 13.8 ­62 30.5 1.9 30.5 30.5 27.7 23.2 18.8 14.3 28.1 2.1 28.1 28.1 26.5 22.0 17.6 13.2 57 29.4 1.8 29.4 29.4 29.4 24.8 20.1 15.5 27.5 2.1 27.5 27.5 27.5 22.9 18.3 13.7 77 61.7 3.4 29.1 24.8 20.4 - - - 56.7 3.3 27.2 22.8 18.4 - - ­72 55.5 3.1 37.9 32.7 27.6 22.4 - - 51.6 3.3 36.1 31.0 25.8 20.7 - ­67 49.4 3.1 46.7 40.7 34.7 28.8 22.8 - 46.5 3.3 45.0 39.1 33.3 27.5 21.7 ­62 44.5 3.0 44.5 44.5 42.4 36.2 30.1 23.9 41.8 3.2 41.8 41.8 40.8 34.6 28.4 22.3 57 46.0 2.9 46.0 46.0 45.5 39.2 32.8 26.4 42.9 3.1 42.9 42.9 42.7 36.4 30.1 23.8
77 34.4 2.4 17.5 14.0 10.6 - - - 31.7 2.6 17.7 12.8 9.6 - - ­72 31.8 2.3 23.3 19.5 15.7 11.9 - - 29.0 2.6 21.9 18.3 14.6 10.9 - ­67 29.2 2.3 29.1 24.9 20.8 16.7 12.6 - 26.3 2.6 26.2 23.8 19.6 15.5 11.4 ­62 25.7 2.4 25.7 25.7 25.3 20.9 16.5 12.1 23.5 2.6 23.5 23.5 23.3 18.9 14.5 10.1 57 25.6 2.4 25.6 25.6 25.6 21.0 16.5 11.9 23.6 2.7 23.6 23.6 23.5 19.1 14.7 10.4 77 51.7 3.8 25.3 20.8 16.3 - - - 47.4 4.1 24.9 18.7 14.5 - - ­72 47.6 3.7 34.3 29.2 24.1 19.0 - - 43.5 4.0 32.2 27.3 22.4 17.5 - ­67 43.5 3.5 43.3 37.6 31.9 26.2 20.5 - 39.5 3.9 39.4 35.9 30.3 24.7 19.1 ­62 39.2 3.5 39.2 39.2 39.2 33.0 26.8 20.7 36.2 3.8 36.2 36.2 36.2 30.1 24.0 17.9 57 39.8 3.5 39.8 39.8 39.8 33.6 27.4 21.2 36.7 3.8 36.7 36.7 36.8 30.7 24.6 18.5
77 28.9 2.9 17.9 11.5 8.6 - - ­72 26.2 2.9 20.6 17.1 13.5 9.9 - ­67 23.4 2.9 23.4 22.6 18.4 14.3 10.1 ­62 21.3 2.9 21.3 21.3 21.3 16.9 12.6 8.2 57 21.5 2.9 21.5 21.5 21.4 17.2 13.0 8.8 77 43.2 4.5 24.6 16.5 12.6 - - ­72 39.4 4.4 30.1 25.4 20.7 16.0 - ­67 35.6 4.3 35.6 34.2 28.7 23.3 17.8 ­62 33.2 4.2 33.2 33.2 33.3 27.2 21.2 15.2 57 33.6 4.2 33.6 33.6 33.8 27.8 21.9 15.9
Net
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
115°F
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
Temperature of Air on Condenser Coil
Net
Capacity
(MBh)
718434-YTG-A-0811
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Johnson Controls Unitary Products 11
718434-YTG-A-0811

DEX048 (4.0 Ton)

Air on
Evaporator Coil
CFM
1050
1600
1050
1600
1050
1600
WB
(°F)
77 47.3 2.2 23.6 19.9 16.0 - - - 44.7 2.4 22.6 18.6 14.6 - - ­72 43.7 2.1 30.5 26.1 21.8 17.5 - - 41.1 2.4 29.4 25.0 20.6 16.2 - ­67 40.1 2.1 37.3 32.3 27.6 22.9 18.1 - 37.5 2.4 36.1 31.4 26.6 21.8 17.0 ­62 35.9 2.1 35.9 35.9 33.2 28.9 24.6 20.3 33.8 2.4 33.8 33.8 32.1 27.7 23.3 18.9 57 35.5 2.1 35.5 35.5 35.5 30.9 26.3 21.6 33.4 2.4 33.4 33.4 33.4 28.8 24.2 19.7 77 66.0 3.6 30.9 26.5 21.0 - - - 62.1 3.8 29.9 24.5 19.1 - - ­72 61.0 3.5 42.4 36.3 30.1 24.0 - - 57.3 3.7 40.7 34.6 28.5 22.3 - ­67 56.0 3.4 53.9 46.0 39.2 32.4 25.7 - 52.5 3.6 51.5 44.7 37.9 31.1 24.3 ­62 51.7 3.3 51.7 51.7 48.9 41.6 34.2 26.8 48.7 3.5 48.7 48.7 47.2 39.8 32.4 24.9 57 50.8 3.2 50.8 50.8 50.7 43.0 35.4 27.7 47.8 3.5 47.8 47.8 47.7 40.2 32.6 25.1
77 42.1 2.7 21.6 17.3 13.2 - - - 38.2 3.1 22.1 16.4 12.0 - - ­72 38.5 2.7 28.3 23.8 19.4 14.9 - - 35.1 3.0 27.0 22.6 18.2 13.7 - ­67 35.0 2.7 35.0 30.4 25.6 20.7 15.9 - 31.9 3.0 31.9 28.8 24.3 19.8 15.3 ­62 31.8 2.7 31.8 31.8 30.9 26.4 22.0 17.5 29.1 3.0 29.1 29.1 28.7 24.2 19.7 15.3 57 31.3 2.7 31.3 31.3 31.3 26.8 22.2 17.7 29.0 3.0 29.0 29.0 29.0 24.2 19.4 14.6 77 58.1 4.2 29.0 22.5 17.1 - - - 53.4 4.5 30.3 21.0 15.7 - - ­72 53.6 4.1 39.0 32.9 26.8 20.7 - - 49.0 4.4 37.5 31.4 25.3 19.3 - ­67 49.0 4.0 49.0 43.4 36.5 29.7 22.9 - 44.6 4.3 44.6 41.8 34.9 28.1 21.2 ­62 45.6 3.9 45.6 45.6 45.5 38.0 30.5 23.0 41.6 4.2 41.6 41.6 41.6 34.1 26.6 19.2 57 44.9 3.9 44.9 44.9 44.8 37.4 29.9 22.4 41.4 4.2 41.4 41.4 41.3 34.0 26.7 19.3
77 34.3 3.4 22.6 15.4 10.8 - - ­72 31.6 3.4 25.7 21.3 16.9 12.6 - ­67 28.9 3.3 28.9 27.2 23.1 18.9 14.7 ­62 26.4 3.3 26.4 26.4 26.4 22.0 17.5 13.0 57 26.7 3.3 26.7 26.7 26.7 21.6 16.5 11.4 77 48.7 4.9 31.7 19.6 14.4 - - ­72 44.4 4.8 36.0 29.9 23.8 17.8 - ­67 40.2 4.8 40.2 40.2 33.3 26.4 19.5 ­62 37.7 4.6 37.7 37.7 37.7 30.2 22.8 15.3 57 37.9 4.6 37.9 37.9 37.9 30.6 23.4 16.2
Net
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
95°F 105°F
115°F
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
Temperature of Air on Condenser Coil
Net
Capacity
(MBh)
Total
1
Input
2
(kW)
Sensible Capacity (MBh)
12 Johnson Controls Unitary Products

Airflow Performance

Side Duct Application

DEX024-048

Size
(Tons)
Model Mode
024
(2.0)
030
(2.5)
036
(3.0)
042
(3.5)
048
(4.0)
DEX
DEX
DEX
DEX
DEX
Low
Cool
High
Heat
Low
Cool
High
Heat
Low
Cool
High
Heat
Low
Cool
High
Heat
Low
Cool
High
Heat
718434-YTG-A-0811
Thermostat
Input
Y1 COOL-A 600 57 74 91 108 126 143 161 179 197 Y1 COOL-B 450 39 54 69 84 100 117 134 152 171 Y1 COOL-C 525 47 63 79 95 112 129 146 164 182
Y1 COOL-D 675 71 88 106 124 142 161 179 198 216 Y1+Y2 COOL-A 800 99 117 137 156 176 196 217 237 258 Y1+Y2 COOL-B 600 57 74 91 108 126 143 161 179 197 Y1+Y2 COOL-C 700 76 94 112 130 148 167 186 205 224 Y1+Y2 COOL-D 900 126 146 166 187 208 231 253 277 300
W1 HEAT-A80099117137156----­W1 HEAT-B7208098116135----­W1 HEAT-C880120140160180-----
Y1 COOL-A 670 61 78 95 113 130 148 166 184 201
Y1 COOL-B 620 54 70 87 104 121 138 156 173 191
Y1 COOL-C 720 70 88 106 124 142 160 178 197 215
Y1 COOL-D 770 81 99 118 136 155 174 193 213 232 Y1+Y2 COOL-A 1000 159 179 200 222 246 270 296 323 350 Y1+Y2 COOL-B 925 129 148 169 190 211 233 256 280 304 Y1+Y2 COOL-C 1075 194 214 236 260 285 312 341 371 403 Y1+Y2 COOL-D 1150 233 254 277 302 330 360 392 427 463
W1 HEAT-A1000159179200222----­W1 HEAT-B900120139159180----­W1 HEAT-C1100206227249274----­W1 HEAT-D1000159179200222-----
Y1 COOL-A 900 120 139 159 180 201 222 244 267 291
Y1 COOL-B 750 76 94 113 131 150 168 187 206 225
Y1 COOL-C 830 97 116 135 155 174 194 215 236 256
Y1 COOL-D 980 150 170 191 213 236 260 285 311 337 Y1+Y2 COOL-A 1200 261 283 306 333 362 394 429 467 507 Y1+Y2 COOL-B 1000 159 179 200 222 246 270 296 323 350 Y1+Y2 COOL-C 1100 206 227 249 274 300 328 357 389 422 Y1+Y2 COOL-D 1300 325 346 372 401 434 471 511 556 604
W1 HEAT-A1200261283306333----­W1 HEAT-B1080196217239263----­W1 HEAT-C1275308330355383----­W1 HEAT-D1200261283306333-----
Y1 COOL-A 920 139 166 195 224 255 286 319 352 386
Y1 COOL-B 790 100 124 149 176 205 235 266 299 333
Y1 COOL-C 850 117 143 170 198 227 257 289 322 356
Y1 COOL-D 980 159 188 218 249 281 313 346 379 414 Y1+Y2 COOL-A 1400 338 383 426 468 509 549 589 627 664 Y1+Y2 COOL-B 1200 245 281 318 354 390 426 462 497 533 Y1+Y2 COOL-C 1300 290 330 370 409 447 485 523 560 596 Y1+Y2 COOL-D 1500 391 439 486 532 576 618 660 700 739
W1 HEAT-A1225256293330367----­W1 HEAT-B1100203237270304----­W1 HEAT-C1350314356397438----­W1 HEAT-D1225256293330367-----
Y1 COOL-A 1050 184 216 248 280 313 346 380 414 449
Y1 COOL-B 920 139 166 195 224 255 286 319 352 386
Y1 COOL-C 980 159 188 218 249 281 313 346 379 414
Y1 COOL-D 1120 211 245 279 313 348 382 417 452 486 Y1+Y2 COOL-A 1600 448 500 551 600 647 693 736 779 819 Y1+Y2 COOL-B 1400 338 383 426 468 509 549 589 627 664 Y1+Y2 COOL-C 1500 391 439 486 532 576 618 660 700 739 Y1+Y2 COOL-D 1700 508 565 620 672 723 772 818 863 905
W1 HEAT-A 1600 448 500 551 600 647 - - - ­W1 HEAT-B 1440 359 405 449 493 535 - - - ­W1 HEAT-C 1760 546 606 663 718 771 - - - ­W1 HEAT-D 1600 448 500 551 600 647 - - - -
Speed
Tap
CFM
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Watts Watts Watts Watts Watts Watts Watts Watts Watts
External Static Pressure (Inch Water Gauge)
Johnson Controls Unitary Products 13
718434-YTG-A-0811

Bottom Duct Application

DEX024-048

Size
(Tons)
Model Mode
024
(2.0)
030
(2.5)
036
(3.0)
042
(3.5)
048
(4.0)
DEX
DEX
DEX
DEX
DEX
Low
Cool
High
Heat
Low
Cool
High
Heat
Low
Cool
High
Heat
Low
Cool
High
Heat
Low
Cool
High
Heat
Thermostat
Input
Y1 COOL-A 600 57 74 91 108 126 143 161 179 197
Y1 COOL-B 450 39 54 69 84 100 117 134 152 171
Y1 COOL-C 525 47 63 79 95 112 129 146 164 182
Y1 COOL-D 675 71 88 106 124 142 161 179 198 216 Y1+Y2 COOL-A 800 99 117 137 156 176 196 217 237 258 Y1+Y2 COOL-B 600 57 74 91 108 126 143 161 179 197 Y1+Y2 COOL-C 700 76 94 112 130 148 167 186 205 224 Y1+Y2 COOL-D 900 126 146 166 187 208 231 253 277 300
W1 HEAT-A80099117137156----­W1 HEAT-B7208098116135----­W1 HEAT-C880120140160180-----
Y1 COOL-A 670 61 78 95 113 130 148 166 184 201
Y1 COOL-B 620 54 70 87 104 121 138 156 173 191
Y1 COOL-C 720 70 88 106 124 142 160 178 197 215
Y1 COOL-D 770 81 99 118 136 155 174 193 213 232 Y1+Y2 COOL-A 1000 159 179 200 222 246 270 296 323 350 Y1+Y2 COOL-B 925 129 148 169 190 211 233 256 280 304 Y1+Y2 COOL-C 1075 194 214 236 260 285 312 341 371 403 Y1+Y2 COOL-D 1150 233 254 277 302 330 360 392 427 463
W1 HEAT-A1000159179200222----­W1 HEAT-B900120139159180----­W1 HEAT-C1100206227249274----­W1 HEAT-D1000159179200222-----
Y1 COOL-A 900 120 139 159 180 201 222 244 267 291
Y1 COOL-B 750 76 94 113 131 150 168 187 206 225
Y1 COOL-C 830 97 116 135 155 174 194 215 236 256
Y1 COOL-D 980 150 170 191 213 236 260 285 311 337 Y1+Y2 COOL-A 1200 261 283 306 333 362 394 429 467 507 Y1+Y2 COOL-B 1000 159 179 200 222 246 270 296 323 350 Y1+Y2 COOL-C 1100 206 227 249 274 300 328 357 389 422 Y1+Y2 COOL-D 1300 325 346 372 401 434 471 511 556 604
W1 HEAT-A1200261283306333----­W1 HEAT-B1080196217239263----­W1 HEAT-C1275308330355383----­W1 HEAT-D1200261283306333-----
Y1 COOL-A 920 139 166 195 224 255 286 319 352 386
Y1 COOL-B 790 100 124 149 176 205 235 266 299 333
Y1 COOL-C 850 117 143 170 198 227 257 289 322 356
Y1 COOL-D 980 159 188 218 249 281 313 346 379 414 Y1+Y2 COOL-A 1400 338 383 426 468 509 549 589 627 664 Y1+Y2 COOL-B 1200 245 281 318 354 390 426 462 497 533 Y1+Y2 COOL-C 1300 290 330 370 409 447 485 523 560 596 Y1+Y2 COOL-D 1500 391 439 486 532 576 618 660 700 739
W1 HEAT-A1225256293330367----­W1 HEAT-B1100203237270304----­W1 HEAT-C1350314356397438----­W1 HEAT-D1225256293330367-----
Y1 COOL-A 1050 184 216 248 280 313 346 380 414 449
Y1 COOL-B 920 139 166 195 224 255 286 319 352 386
Y1 COOL-C 980 159 188 218 249 281 313 346 379 414
Y1 COOL-D 1120 211 245 279 313 348 382 417 452 486 Y1+Y2 COOL-A 1600 448 500 551 600 647 693 736 779 819 Y1+Y2 COOL-B 1400 338 383 426 468 509 549 589 627 664 Y1+Y2 COOL-C 1500 391 439 486 532 576 618 660 700 739 Y1+Y2 COOL-D 1700 508 565 620 672 723 772 818 863 905
W1 HEAT-A 1600 448 500 551 600 647 - - - ­W1 HEAT-B 1440 359 405 449 493 535 - - - ­W1 HEAT-C 1760 546 606 663 718 771 - - - ­W1 HEAT-D 1600 448 500 551 600 647 - - - -
Speed
Tap
CFM
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Watts Watts Watts Watts Watts Watts Watts Watts Watts
External Static Pressure (Inch Water Gauge)
14 Johnson Controls Unitary Products
718434-YTG-A-0811

Additional Static Resistance

Size
(Tons)
024
(2.0)
030
(2.5)
036
(3.0)
042
(3.5)
048
(4.0)
Model CFM Wet Indoor Coil Economizer
500 0.01 0.00 0.01 0.02 600 0.01 0.00 0.02 0.03 700 0.01 0.00 0.02 0.03
DEX
DEX
DEX
DEX
DEX
800 0.01 0.01 0.02 0.03
900 0.01 0.01 0.02 0.04 1000 0.02 0.01 0.02 0.04 1100 0.03 0.01 0.03 0.05 1200 0.04 0.02 0.03 0.06
700 0.01 0.00 0.02 0.03
800 0.01 0.01 0.02 0.03
900 0.01 0.01 0.02 0.04 1000 0.02 0.01 0.02 0.04 1100 0.03 0.01 0.03 0.05 1200 0.04 0.02 0.03 0.06 1300 0.07 0.03 0.17 -
700 0.01 0.00 0.02 0.03
800 0.01 0.01 0.02 0.03
900 0.01 0.01 0.02 0.04 1000 0.02 0.01 0.02 0.04 1100 0.03 0.01 0.03 0.05 1200 0.04 0.02 0.03 0.06 1300 0.04 0.03 0.03 0.07 1400 0.04 0.04 0.03 0.08 1100 0.03 0.01 0.03 0.05 1200 0.04 0.02 0.03 0.06 1300 0.04 0.03 0.03 0.07 1400 0.04 0.04 0.03 0.08 1500 0.05 0.05 0.04 0.09 1600 0.06 0.06 0.05 0.10 1100 0.03 0.01 0.03 0.05 1200 0.04 0.02 0.03 0.06 1300 0.04 0.03 0.03 0.07 1400 0.04 0.04 0.03 0.08 1500 0.04 0.05 0.04 0.09 1600 0.04 0.06 0.05 0.10 1700 0.05 0.07 0.05 0.11 1800 0.05 0.07 0.06 0.11 1900 0.06 0.08 0.06 0.11 2000 0.07 0.08 0.07 0.12
1. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
1
Filter/Frame Kit Electric Heat
Johnson Controls Unitary Products 15
718434-YTG-A-0811

Electric Heat Minimum Supply Air

Size
(Tons)
024
(2.0)
030
(2.5)
036
(3.0)
042
(3.5)
048
(4.0)
Model Voltage
DEX 208/230-1-60 630 630 800 - - ­DEX 208/230-1-60 630 630 800 800 - -
DEX
DEX 208/230-1-60 1225 1225 1225 1225 - -
DEX

Indoor Blower Specifications

Size
(Tons)
024
(2.0)
030
(2.5)
036
(3.0)
042
(3.5)
048
(4.0)
Model
HP RPM Eff. SF Frame
DEX 1/2 Variable 0.8 1.0 48
DEX 1/2 Variable 0.8 1.0 48
DEX 1/2 Variable 0.8 1.0 48
DEX 3/4 Variable 0.8 1.0 48
DEX 3/4 Variable 0.8 1.0 48
Minimum Supply Air (CFM)
Heater kW
5.0 7.5 10.0 15.0 20.0 25.0
208/230-1-60 1070 1070 1070 1070 - ­208/230-3-60 1070 1070 1070 1070 - -
460-3-60 1070 1070 1070 1070 - -
208/230-1-60 - - 1200 1430 1430 1430 208/230-3-60 - - 1200 1430 1430 1430
460-3-60 - - 1200 1430 1430 1430
Motor

Electric Heat Multipliers

Voltage
Nominal Applied
240
208 0.75 230 0.92
480 460 0.92
1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat capacity for heaters applied at lower voltages.
kW Capacity Multipliers

Sound Performance

Outdoor Sound Power Levels

Size
(Tons)
024
(2.0)
030
(2.5)
036
(3.0)
042
(3.5)
048
(4.0)
Model
Sound Rating
dB (A)
DEX 73 61.5 64.5 68.5 66.5 62 60 54
DEX 77 60 62.5 64.5 75.5 62.5 59.5 58.5
DEX 78 63 65 76 73 64.5 62.5 60
DEX 76 67.5 68.5 69.5 69 66 63.5 60
DEX 79 71.5 69.5 71.5 75.5 68 67 62
1
1. Rated in accordance with ARI 270 standard.
125 250 500 1000 2000 4000 8000
Octave Band Centerline Frequency (Hz)
1
16 Johnson Controls Unitary Products

Electrical Data

DEX024-048 Cooling Only With/Without Electric Heat

Size
(Tons)
024
(2.0)
030
(2.5)
036
(3.0)
042
(3.5)
048
(4.0)
Volt
208/230-1-60 10.2 52 16 1.2 4.3
208/230-1-60 14.1 70 22 1.2 4.3
208/230-1-60 16.6 82 26 1.2 4.3
208/230-3-60 11.1 58 17 1.2 4.3
460-3-60 4.5 29 7 0.8 4.3
208/230-1-60 16.6 96 26 1.4 6.8
208/230-1-60 21.1 96 33 1.7 6.8
208/230-3-60 13.4 88 21 1.7 6.8
460-3-60 6.4 41 10 1.0 6.8
Compressors
(each)
RLA LRA MCC FLA FLA Model kW Stages Amps
OD Fan
Motors
(each)
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
Supply Blower
Motor
None - - - 18.3 25 2NH04500506 3.8/5 1 18.1/20.8 27.9 / 31.4 30 / 35 2NH04500706 5.6/7.5 2 27.1/31.3 39.2 / 44.4 40 / 45 2NH04501006 7.5/10 2 36.1/41.7 50.5 / 57.5 60 / 60
None - - - 23.1 30 2NH04500506 3.8/5 1 18.1/20.8 27.9 / 31.4 35 / 35 2NH04500706 5.6/7.5 2 27.1/31.3 39.2 / 44.4 40 / 45 2NH04501006 7.5/10 2 36.1/41.7 50.5 / 57.5 60 / 60 2NH04501506 11.3/15 2 54.2/62.5 73.1 / 83.5 80 / 90
None - - - 26.3 35 2NH04500506 3.8/5 1 18.1/20.8 27.9 / 31.4 35 / 40 2NH04500706 5.6/7.5 2 27.1/31.3 39.2 / 44.4 40 / 45 2NH04501006 7.5/10 2 36.1/41.7 50.5 / 57.5 60 / 60 2NH04501506 11.3/15 2 54.2/62.5 73.1 / 83.5 80 / 90
None - - - 19.4 25 2NH04501025 7.5/10 1 20.8/24.1 31.4 / 35.4 35 / 40 2NH04501525 11.3/15 1 31.3/36.1 44.5 / 50.5 45 / 60
None - - - 10.7 15 2NH04501046 10 1 12 20.4 25 2NH04501546 15 1 18 27.9 30
None - - - 29 35 2NH04500506 3.8/5 1 18.1/20.8 31.1 / 34.5 40 / 45 2NH04500706 5.6/7.5 2 27.1/31.3 42.4 / 47.6 45 / 50 2NH04501006 7.5/10 2 36.1/41.7 53.6 / 60.6 60 / 70 2NH04501506 11.3/15 2 54.2/62.5 76.2 / 86.6 80 / 90
None - - - 34.9 45 2NH04501006 7.5/10 2 36.1/41.7 53.6 / 60.6 60 / 70 2NH04501506 11.3/15 2 54.2/62.5 76.2 / 86.6 80 / 90 2NH04502006 15/20 2 72.2/83.3 98.8 / 112.7 100 / 125 2NH04502506 18.8/25 2 90.3/104.2 121.3 / 138.7 125 / 150
None - - - 25.3 35 2NH04501025 7.5/10 1 20.8/24.1 34.6 / 38.6 35 / 40 2NH04501525 11.3/15 1 31.3/36.1 47.6 / 53.6 50 / 60 2NH04502025 15/20 2 41.7/48.1 60.6 / 68.6 70 / 70 2NH04502525 18.8/25 2 52.1/60.1 73.7 / 83.7 80 / 90
None - - - 15.9 20 2NH04501046 10 1 12 23.5 25 2NH04501546 15 1 18 31.1 35 2NH04502046 20 2 24.1 38.6 40 2NH04502546 25 2 30.1 46.1 50
Electric Heat Optio n
MCA
(Amps)
1
Max Fuse2/
Breaker
Size
(Amps)
718434-YTG-A-0811
3
Johnson Controls Unitary Products 17
718434-YTG-A-0811

Typical Wiring Diagrams

Typical DEX024, 048 Cooling Only 208/230-1-60 volt Wiring Diagram

18 Johnson Controls Unitary Products

Typical DEX036, 048 Cooling Only 208/230-3-60 volt Wiring Diagram

718434-YTG-A-0811
Johnson Controls Unitary Products 19
718434-YTG-A-0811

Typical DEX036, 048 Cooling Only 460-3-60 volt Wiring Diagram

20 Johnson Controls Unitary Products

Weights and Dimensions

X
CENTER OF
GRAVITY
49-1/8
FRONT
OF
UNIT
Y
47-1/4
"D"
"C"
"B"
"A"
Unit 4 Point Load Weight
718434-YTG-A-0811
Size
(Tons)
024
(2.0)
030
(2.5)
036
(3.0)
042
(3.5)
048
(4.0)
Model
DEX 360 355 22.25 25 96 84 81 93
DEX 395 390 22.25 25 106 92 89 102
DEX 405 400 22.25 25 109 95 92 105
DEX 415 410 22.25 25 111 97 94 108
DEX 445 440 22.25 25 120 104 101 115
Weight (lbs.) Center of Gravity 4 Point Load Location (lbs.)
Shipping Operating X Y A B C D

Unit Accessory Weights

Unit Accessory Model
Add Economizer All 45 40
Add Electric Heat
1. Weight given is for the maximum heater size available (25 kW).
1
All 13 12
Shipping Operating
Weight (lbs.)
Johnson Controls Unitary Products 21
718434-YTG-A-0811
FRONT
(OVERALL)
(OVERALL)
(OVERALL)
COMPRESSOR SERVICE
ACCESS COMPARTMENT
PANEL
REFRIGERANT
CONNECTIONS
ELECTRICAL/FILTER
SERVICE ACCESS
COMPARTMENT PANEL
HIGH VOLTAGE CONN.
1-23/64" DIA. KNOCKOUT
UNIT CONDENSATE
CONNECTION 3/4" NPTF
(TRAP REQUIRED)
SIDE RETURN
AIR OPENING
SIDE SUPPLY AIR OPENING
LOW VOLTAGE CONN.
7/8" DIA. KNOCKOUT
HIGH VOLTAGE CONN.
1-31/32" DIA. KNOCKOUT
HIGH VOLTAGE CONN.
7/8" DIA. KNOCKOUT
“A”
3-3/4
1-1/2
2-1/2
2-3/8
4-1/2
49-1/8
28-1/4
28-1/4
47-1/4
17-1/4
17-1/4
22-1/4
22-1/4

Cooling Only Unit Dimensions

Cooling Only Unit Dimensions

Unit Size
024, 030, 036 33-1/2
042, 048 41-1/2

Cooling Only Unit Clearances

Direction
1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air discharge outlet.
2. Units may be installed on combustable floors made from wood or class A, B or C roof covering materials.
3. Minimum Clearance of 1inch all sides of supply air duct for the first 3 foot of duct for 20 & 25 kW., zero inches there after. For all other heaters, zero inch clearance all sides for entire length of duct.
Note: For units applied with a roof curb, the minimum clearance may be reduced from 1 inch to 1/2 inch between combustible roof curb material and this supply air duct.
Dimensions
“A”
Distance
1
Top Front 12 Left 24 Rear 0 Bottom
(in.)
36 Right 24
Direction
2 3
Distance
(in.)
0
22 Johnson Controls Unitary Products

Unit Dimensions Front and Bottom

6
19-1/4
11-7/8
8-7/8
FRONT
GAS SUPPLY 1-5/8"
DIA. KNOCKOUT (1/2"
NPTF CONNECTION)
LOW VOLTAGE
CONN. 7/8" DIA.
KNOCKOUT
4-5/8
26-3/4
CONDENSATE
DRAIN 3/4" NPTF
HIGH VOLTAGE
CONN. 1-3/32"
DIA. KNOCKOUT
LOW VOLTAGE
CONN. 7/8" DIA.
KNOCKOUT
HIGH VOLTAGE
CONN. 1-31/32" x 7/8"
KNOCKOUT
22-1/2
43-1/2
40-1/2
4
14-1/2
28-3/8
14-1/2
BACK
3-3/8
SIDE RETURN AIR OPENING
14-1/2
4-1/4
3-1/2
15
1-3/4
1-3/4
BOTTOM RETURN
AIR OPENING
15
28-9/16
15
1-3/4
BOTTOM SUPPLY
AIR OPENING
*CONDENSER
COIL
SIDE SUPPLY
AIR OPENING
718434-YTG-A-0811

Unit Dimensions Back and Bottom

Johnson Controls Unitary Products 23
718434-YTG-A-0811
ROOF CURB
INSTALLATION
REAR DUCT
ROOF CURB
INSTALLATION
BOTTOM DUCT
SLAB ON GROUND
INSTALLATION
TO POWER SUPPLY
SUPPLY AIR
DUCT
RETURN AIR
DUCT
FIELD SUPPLIED
DISCONNECT SWITCH
LOCATED TO REAR OF UNIT
CONTROL WIRING
TO INDOOR
THERMOSTAT

Unit Typical Duct Applications

Unit Typical Slab on Ground Installation

24 Johnson Controls Unitary Products

Unit Typical Roof Curb Installation

SUPPLY AIR
DUCT
RETURN AIR
DUCT
CONTROL WIRING
TO INDOOR THERMOSTAT
TO POWER SUPPLY
FIELD SUPPLIED
DISCONNECT SWITCH
MOUNTED ON UNIT
1
RECOMMENDED
DUCT SIZE
17-1/8" x 21-1/2"
RECOMMENDED
DUCT SIZE
17-1/2" x 16-3/4"
OPENING FOR
RETURN AIR DUCT
OPENING FOR
SUPPLY AIR DUCT
42-2/3
40-3/4
17-5/8
17-1/4
43-1/4
22
45-1/8
3-1/2
14
718434-YTG-A-0811

Unit Accessory Dimensions

Roof Curb

1
1. 8” Roof Curb also available.
Johnson Controls Unitary Products 25

Roof Curb Cross Section

1"
UNIT BASE RAIL
COUNTERFLASHING
CANT STRIP
INSULATION AND ROOFING MATERIAL
ROOF DECK AND ROOFING MATERIAL
INSULATION
CURB FRAME
14"
8" MIN. ABOVE FINISHED ROOF
WOOD NAILER
UNIT BASE
3/4" x 1" WIDE GASKETING FOR CURB FRAME
AND ALL DUCT SUPPORT SURFACES
\
Subject to change without notice. Printed in U.S.A. 718434-YTG-A-0811 Copyright © 2011 by Johnson Controls, Inc. All rights reserved. Supersedes: 294604-YTG-H-0711
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069