DESCRIPTION
The 13 SEER Series condensing unit is the outdoor part of a versatile system of air conditioning. It is designed to be custom- matched
with one of UPG’s complete line of evaporator sections, each
designed to serve a specific function.
WARRANTY
5-year limited parts warranty.
5-year limited compressor warranty.
FEATURES
•QUALITY CONDENSER COILS - The coil is constructed of
aluminum microchannel tubing and enhanced aluminum fins for
increased efficiency and corrosion protection.
•COIL PROTECTION - Coils are protected from damage by a
polymer mesh applied between the coil face, and a coated steel coil
guard.
•PROTECTED COMPRESSOR - Compressors are internally
protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve
and a temperature sensor which protects the compressor if undesirable operating conditions occur. A liquid line filter-drier further protects the compressor.
•DURABLE FINISH - The cabinet is made of pre-painted steel.
The pre-treated flat galvanized steel provides a better paint-to-steel
bond, which resists corrosion and rust creep. Special primer formulas
and matted champagne finish insure less fading when exposed to
sunlight.
•LOWER INSTALLED COST - Installation time and costs are
reduced by easy power and control wiring connections. The small
base dimension means less space is required on the ground or roof.
•TOP DISCHARGE - The warm air from the top mounted fan is
blown away from the structure and any landscaping. This allows
compact location on multi-unit applications.
•LOW OPERATING SOUND LEVEL - The upward air flow car-
ries the normal operating noise away from the living area. The rigid
top panel effectively isolates any motor sound. Isolator mounted
compressor and the condenser coil muffle the normal fan motor and
compressor operating sounds.
•LOW MAINTENANCE - Long life permanently lubricated motor-
bearings need no annual servicing.
•EASY SERVICE ACCESS - Fully exposed refrigerant connec-
tions and a single panel covering the electrical controls make for
easy servicing of the unit.
•SECURED SERVICE VALVES - Secured re-usable service
valves are provided on both the liquid and vapor sweat connections
for ease of evacuating and charging.
•U.L. AND C.U.L. LISTED - Approved for outdoor application.
Certified in accordance with the Unitary Small Equipment certification
program, which is based on ARI Standard 210/240.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
Unit Supply Voltage208 - 230V, 1 Phase, 60Hz
Minimum Circuit Ampacity8.99.512.014.518.2
Maximum Overprotection Device
Rated Load Amps6.77.28.91113.5
Compressor
Dimensions
Fan & Motor
OD Coil
Connection OD
Line Set OD
RefrigerantR-22R-22R-22R-22R-22
Unit Charge (lbs - oz)
2
Charge Per Foot - oz0.660.660.660.680.68
1. Dual element fuses or HACR circuit breaker.
2. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15
subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
1. Systems matched with furnace or air handlers not equipped with blower-off delays may re quire blower Time Delay Kit #6918A5011
2. These orifices are factory mounted in the flow device of each indoor coil
3. A TXV kit must be used with these coils to obtain system perf ormance (2A, 2B, and 2C indicate 1TVM series)
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for th e condenser, the smallest evaporator and for 15 feet of interconnecting line
tubing.
2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tub i ng greater than 15 feet at the rate specified in the table above.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator + adder
for line set.
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210.
Cooling MBH based on 80ºF entering air temperature, 50% RH, and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95ºF outdoor ambient divided by the total electric power in watt-hours at those conditions
SEER (Seasonal Energy Efficiency Ratio) is the t ot al coolin g ou tput in B UT’s during a normal annual usage period for cooli ng d i vided by t he total electric power
input in watt-hours during the same period.
1. G4FD coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. Single phase units require single phase 2HK heaters.
COOLING
NET MBH
TOTALSENS.
SEEREER
.
Unitary Products Group5
Page 6
246814-YTG-D-0606
COOLING CAPACITY - Upflow, Downflow, & Horizontal Furnaces and Coils
FURNACE**
UNIT MODEL
AY012MA321
AY018MA321
AY024MA321
AY030MA321
AY036MA321
1. Requires a 2FD Blower Time Delay unless a standard furnace is equipped with one.
2. TXV = Use 1TVM2* kit on non-factory installed TXV coils.
** Refer to Quick Selection Chart for specific furnace match-up.
Refer to Price Manual for specific model numbers.
OFF CYCLE TIMER DELAY - Provides a 5-minute off cycle to prevent rapid recycling of the compressor.
ROOM THERMOST ATS - A wide selection of compatible thermosets
are available to provide optimum performance and features for any
installation.
1H/1C, manual change-over electronic non-programmable therm
stat.
1H/1C, auto/manual changeover, electronic programmable, deluxe
7-day, thermostat.
1H/1C, auto/manual changeover, electronic programmable.
MATCHING INDOOR COMPONENTS
FC
FULL CASED
UPFLOW
MC
MULTI-POSITION
(UPFLOW, HORIZONTAL
AND DOWNFLOW)
* For the most current accessory information, refer to the price book
or consult factory.
SOUND POWER RATINGS*
UNIT MODEL(dBA)
01274
01872
02475
03075
03676
*Rated in accordance with ARI 270-95 Standards.
PC
1/2 CASED
UPFLOW
HC
FULL CASED
HORIZONTAL
G4FD*
MULTI-POSITION
(UPFLOW, HORIZONTAL
AND DOWNFLOW)
UC
1/2 CASED
UPFLOW
G4FA*
FULL CASED
UPFLOW
Unitary Products Group9
Page 10
246814-YTG-D-0606
TYPICAL INSTALLATION
48” OVERHEAD
CLEARANCE
MINIMUM 24” SERVICE ACCESS
CLEARANCE ON ONE SIDE
WEATHERPROOF
DISCONNECT
SWITCH
THERMOSTAT
NEC CLASS 1 WIRING
12” CLEARANCE
AROUND PERIMETER
NOTE:ALL OUTDOOR WIRING
MUST BE WEATHERPROOF.
TYPICAL FIELD WIRING
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
POWER WIRING
208/230-1-60
GND.
LUG
CONTROL ACCESS PANEL
24 VOLT CONTROL WIRING
MINIMUM 18 GA. WIRE
(NEC CLASS 2)
*
TERMINAL W IS ONLY
REQUIRED ON SYSTEMS
WITH HEAT.
TO FURNACE OR
AIR HANDLER
TERMINAL BLOCK
NEC CLASS 2 WIRING
TO INDOOR COIL
SEAL OPENING(S) WITH
PERMAGUM OR EQUIVALENT
POWER WIRING
CONTROL WIRING
FACTORY WIRING
FURNACE OR AIR HANDLER TERMINAL BLOCK
CYRGW
CONTACTOR
TERMINALS
COIL
CONDENSING UNIT
ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.
YRGW
ROOM THERMOSTAT
*
10Unitary Products Group
Page 11
246814-YTG-D-0606
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
INDOOR COIL MODEL NO.
CONDENSER
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
125
ID CFM
ID DB (°F)808075808080807580808080758080
ID WB (°F)576262677257626267725762626772
T .C.10.514.013.415.116.613.915.615.317.418.917.317.217.219.621.1
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
T .C.16.318.518.620.322.117.819.119.120.822.519.319.719.721.222.9
S.C.15.414.012.312.1 9.8 17.015.813.813.410.918.617.715.314.812.1
KW1.21.21.21.21.21.21.21.21.21.21.21.21.21.21.2
T .C.15.917.517.619.321.317.318.218.219.921.718.618.818.920.422.1
S.C.15.013.411.711.69.516.515.313.313.110.617.917.214.914.611.8
KW1.31.31.31.31.31.31.31.31.31.31.31.31.31.31.3
T .C.15.616.616.618.320.516.717.217.318.920.917.917.918.119.621.2
S.C.14.712.911.111.19.316.014.712.812.710.317.316.614.414.411.4
KW1.51.51.51.51.51.51.51.51.51.51.51.51.51.51.5
T .C.15.215.615.617.319.716.216.316.418.020.017.217.017.318.720.4
S.C.14.312.310.510.69.115.514.212.312.410.016.616.114.014.211.0
KW1.61.61.61.61.61.61.61.61.61.61.61.61.61.61.6
T .C.13.914.614.716.318.615.115.315.417.018.916.315.916.117.619.3
S.C.13.011.810.010.28.614.213.411.611.99.615.415.013.313.710.7
KW1.81.81.81.81.81.81.81.81.81.81.81.81.81.81.8
T .C.12.713.713.715.317.514.014.314.415.917.815.314.915.016.618.2
S.C.11.811.29.59.78.213.012.511.111.49.214.313.812.613.210.3
KW1.91.91.92.02.02.02.02.02.02.02.02.02.02.02.0
T .C.11.412.812.814.416.412.913.313.314.916.714.413.913.815.517.1
S.C.10.510.79.09.27.711.811.710.511.08.913.212.711.912.710.0
KW2.12.12.12.22.22.12.12.12.22.22.22.22.22.22.2
AY018MA321
G2FD024S17
450600750
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
T .C.27.230.029.532.735.728.730.430.133.035.730.130.730.633.435.6
S.C.25.624.420.720.516.427.126.723.022.617.828.629.025.424.719.2
KW1.91.91.91.92.01.91.91.91.92.01.91.91.92.02.0
T .C.26.628.828.431.434.328.029.228.831.634.329.329.629.331.834.3
S.C.25.123.720.020.015.916.425.822.122.117.227.828.024.224.118.5
KW2.12.12.12.22.22.12.12.22.22.22.22.22.22.22.2
T .C.26.127.627.230.132.927.228.127.630.233.028.428.528.030.333.0
S.C.24.522.919.219.515.525.725.021.121.516.627.027.123.023.617.8
KW2.32.42.42.42.42.42.42.42.42.42.42.42.42.42.4
T .C.25.526.426.128.931.526.526.926.428.831.627.527.426.628.731.7
S.C.23.922.218.519.015.025.024.220.221.016.026.226.121.823.017.1
KW2.62.62.62.62.62.62.62.62.62.72.62.62.62.62.7
T .C.24.625.325.027.530.225.525.825.327.530.226.426.325.527.530.1
S.C.23.021.818.118.414.624.123.419.820.515.725.125.021.622.616.8
KW2.82.82.82.92.92.82.92.82.92.92.92.92.92.93.0
T .C.23.724.224.026.328.924.524.724.226.328.825.325.124.426.328.6
S.C.22.221.417.617.914.323.222.619.520.115.424.123.921.422.216.4
KW3.13.13.13.13.23.13.13.13.23.23.23.23.23.23.2
T .C.22.823.223.025.027.723.523.623.225.127.424.323.923.425.127.1
S.C.21.421.017.217.414.022.321.919.219.615.023.122.821.321.816.1
KW3.33.33.33.43.53.43.43.43.43.53.43.43.43.43.5
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
AY030MA321
G2FD036S17
80010001200
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
246814-YTG-D-0606
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.