Due to continuous product improvement,
specifications are subject to change without notice.
Visit us on the web at:
www.upgnet.com and www.york.com
Additional rating information can be found at:
www.ahridirectory.org
WARRANTY
Standard 5-year limited parts warranty.
Extended 10-year limited parts warranty when product is
registered online within 90 days of purchase for replacement or closing for new home construction.
ISO 9001
Certified Quality
Management System
697887-YTG-H-0514
DESCRIPTION
The AHE Air Handler line offers the ultimate in comfort, sound
and application flexibility. This unit may be used for upflow, down-
flow, horizontal right, or horizontal lef t applications.
required to install this deluxe product.
All JCI Unitary Products air handlers and coils use a TXV to pro-
vide our customers with the optimum performance and refrigerant control. Air handlers are shipped with “Flex-coils” without a
factory installed metering device. For added flexibility, an R-22
or R-410A TXV or orifice can be field installed to meet your
refrigerant choice.
No special kits are
FEATURE
Thermal Expansion Valve - Provides the ultimate refrigerant
control required for today’s high efficient product. The UPG bolton TXV provides easy installation to convert the air handler to
the required refrigerant, which is a true bolt-on design that does
not require brazing to replace or install.
Insulated Cabinet - All air handler cabinets are thermally insulated with 3/4” foil faced insulation to prevent sweating.
Factory Sealed - Achieves 2% or less total airflow leakage rate
at duct blaster field test conditions for system airflow verification.
Durable Finish Inside and Out - Air handler casings are made
of pre-painted galvanized steel which provides a better paint to
steel bond that resists corrosion and rust creep. All internal coil
sheet metal parts are made of G60 galvanized or prepainted
G30 galvanized.
Filters - All models have internal filter racks provided for use
with 1” thick standard size filters.
Electric Heat Kits - 6HK series of field installed electric heat
kits are available for installation friendly and easy service applications.
High Efficiency Blowers - All models use high efficiency
brushless DC motors to provide cooling SEER rating enhancement.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
Page 2
697887-YTG-H-0514
J
D
Blower
Compartment
Service
Disconnect
Panel
Drain Pan Connections
for Horizontal Applications
Refrigerant
Connections
Drain Connections
for Upflow
Applications
7-11/32”
B
A
K
C
1-1/2”
Top Outlet
Dimensions
Filter
Access
20-5/16”
E
Bottom Inlet
Dimensions
13”
F
A024-001
DIMENSIONS & DUCT CONNECTION DIMENSIONS
Dimensions
1
Models
AHE18B/AHE22B/AHE24B/
AHE30B (1CJZ7/6ELE6)
AHE34C/AHE36C (1CKA2/
6ELE9)
AHE42D/AHE48D/AHE60D
(1CKA3/6ELF0/6ELF1)
1. All dimensions are in inches.
2. Actual size (conduit size).
COIL TECHNICAL DATA
ModelsApplication
AHE18B3XH21
AHE22B3XH21
AHE24B3XH21
AHE30B3XH21
AHE34C3XH21
AHE36C3XH21
AHE42D3XH21
AHE48D3XH21
AHE60D3XH21
Dimensions
ABC
DEF
Wiring Knockouts
2
JK
Refrigerant
Connections
Line Size
HeightWidthDepthPowerControlLiquidVapor
4617 1/2
16 1/213-29/3216 1/2
7/8 (1/2)
522121 1/217-13/3220
21 1/2
1-3/8(1)
7/8 (1/2)3/8
1-23/32 (1-1/4)
5724 1/22620-29/3223-1/27/8
Cooling /
Heat Pump
Cooling /
Heat Pump
Cooling /
Heat Pump
Cooling /
Heat Pump
Cooling /
Heat Pump
Cooling /
Heat Pump
Cooling /
Heat Pump
Cooling /
Heat Pump
Cooling /
Heat Pump
Refrig.
Conn. Types
Sweat3.4214(2) 14 x 17.51 x 0.8663/8Enhanced
Sweat3.9214(2) 16 x 17.51 x 0.8663/8Enhanced
Sweat3.9312(2) 16 x 17.51 x 0.8663/8Enhanced
Sweat3.9312(2) 16 x 17.51 x 0.8663/8Enhanced
Sweat3.9312(2) 16 x 17.51 x 0.8663/8Enhanced
Sweat4.9312(2) 20 x 17.51 x 0.8663/8Enhanced
Sweat5.4312(2) 22 x 17.51 x 0.8663/8Enhanced
Sweat5.8311(2) 24 x 17.51 x 0.8663/8Enhanced
Sweat6.8312(2) 28 x 17.51 x 0.8663/8Enhanced
Face Area
(Sq. Ft.)
Rows
Deep
Fins
Per In.
Coil Size
Tube
Geometry
Tube
Dia.
Fin
Type
3/4
2Johnson Controls Unitary Products
Page 3
COOLING CAPACITY
Models
AHE18B
AHE22B
AHE24B
AHE30B
AHE34C
Continuation and notes on next page.
1
Rated CFM
610
850
585
795
985
585
795
985
585
795
985
730
855
1000
1190
Entering Air
2
Dry/Wet Bulb (°F)
697887-YTG-H-0514
MBH@ Evap. Temp. and Corresponding R-410A Pressure (°F/PSIG)
KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT
For a power distribution voltage that is different than the provided nominal voltage, multiply the kW and MBH d ata from the table by
the conversion factor in the following table.
DISTRIBUTION POWERNOMINAL VOLTAGECONVERSION FACTOR
220V240V0.84
ELECTRICAL DATA - COOLING ONLY
Models
AHE18B / AHE22B /
AHE24B / AHE30B
Motor FLA
1
2.83.51514
AHE34C / AHE36C / AHE42D4.15.11514
AHE48D / AHE60D6.07.51514
1. FLA = Full Load Amps
2. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
3. 75C, copper wire only. If wire other than non-plated, 75C ambient, copper wire is used, consult applicable tables of the NEC and local codes.
ELECTRICAL HEAT: MINIMUM FAN SPEED
Heater Kit Models
2,3
Nom. kW
@240V
1
AHE18B
6HK(0,1)65002062.4kWMed Low #2 Med Low #2Low #1Med #3Low #1Med Low #2 Med Low #2
6HK(0,1)65005064.8kWMed Low #2 Med Low #2 Med Low #2 Med Low #2Med #3Med #3Med Low #2
6HK(0,1)65008067.7kWMed High #4 Med High #4Med #3Med #3Med #3Med #3Med Low #2
6HK(0,1)6501006
6HK06501025
9.6kWMed High #4 Med High #4 Med High #4 Med High #4 Med High #4 Med High #4Med #3
6HK(1,2)650130612.5kW-Med High #4 Med High #4 Med High #4 Med High #4 Med High #4Med #3
6HK(1,2)6501506
6HK06501525
6HK(1,2)6501806
6HK06501825
6HK(1,2)6502006
6HK16502025
6HK(1,2)6502506
6HK16502525
1. The referenced letter in this table is for the heat jumper tap.
2. (0,1) - 0 = no circuit breaker OR 1 = with circuit breaker.
3. (1,2) - 1 = with circuit breaker, no breaker jumpe r bar OR 2 = with circuit breaker & breaker jumper bar .
14.4kW-High #5High #5Med High #4 Med High #4 Med High #4Med #3
17.3kW---High #5High #5High #5Med High #4
19.2kW---High #5High #5High #5High #5
24kW------High #5
Minimum Circuit
Ampacity
AHE22B
AHE24B
AHE30B
MOP
Air Handler Models
AHE34C
AHE36C
2
Minimum Wire Size (AWG)
AHE42DAHE48DAHE60D
3
Johnson Controls Unitary Products5
Page 6
697887-YTG-H-0514
ELECTRIC HEAT PERFORMANCE DATA: 208/230-1-60 & 208/230-3-60
3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
4. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.
Field Wiring
3
MOP.
Min Wire Size (AWG)
ELECTRICAL DATA FOR MULTI-SOURCE POWER SUPPLY: 208/230-1-60
1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
2. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.
3. 1st Circuit includes the blower motor amps.
3
2nd 3rd
2
4
Johnson Controls Unitary Products7
Page 8
697887-YTG-H-0514
UPFLOW
HORIZONTAL RIGHT
HORIZONTAL LEFT
HEAT
HEAT
HEAT
DOWNFLOW
HEAT
ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY - 208/230-3-60
1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
2. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.
3. The 20kW and 25kW heater models (6HK16502025 and 6HK16502525) come with circuit breakers st andard. Si ngle source power MCA and MOP r equirement s are
given here only for reference if used with field installed single point power modification.
1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
2. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.
Refer to Price Manual for specific model numbers where not
shown.
TXV Kits - TXV kits are available for “Flex-coil” applications and
converting R-22 to R-410A or as a service replac ement. All ki ts
are bolt-on and require no brazing to install.
Electric Heaters - 6HK models shown under electrical data
include sequential operation and temperature dual limit
switches for safe, efficient operation. Circuit breakers are provided where shown.
1st
2
3
2nd
8Johnson Controls Unitary Products
Page 9
697887-YTG-H-0514
LIMITATIONS
These units must be wired and installed in accordance with all
national and local safety codes.
Voltage limits are as follows:
Air Handler VoltageVoltage code
208/230-1-6006187-253
1. Rated in accordance with ARI Standard 110, utilization range “A”.
Normal Operating
Voltage Range
Airflow must be within the minimum and maximum limits
approved for electric heat, evaporator coils and outdoor units.
AIR FLOW DATA (CFM)
Models
AHE18B
AHE22B
AHE24B
AHE30B
AHE34C
AHE36C
AHE42D
AHE48D
AHE60D
1. Air handler units have been tested to UL 1995 / CSA 22.2 st andards up to 0.30" wc. external static pressure.
Dry coil conditions only, tested without filters.
For optimal performance, external static pressures of 0.2" to 0.5" are recommended. Applications above 0.6" are not recommended.
Airflow data shown is from testing performed at 230V. AHE units use a X13 motor, and there is minimal variation of airflow at other distribution voltage values. The
above data can be used for airflow at other distribution voltages.
1
Blower
Motor Speed
High #5107510411003970930885842
Med High #4895845808767709647561
Med #3663618557490348267192
Med Low #26294683561971756823
Low #16294683561971756823
High #511561120109310561014951862
Med High #4102198795291887 3836787
Med #3829789754698654585532
Med Low #2681621575496435336262
Low #159850343734025920374
High #51471142913871337128912331172
Med High #413011248119811471008999927
Med #310971044972906815748680
Med Low #2943868768689617566520
Low #1869668515424365287NA
High #51465141513601307124611831118
Med High #412601204114210751008946876
Med #310881022939862782721626
Med Low #2998810717630562493444
Low #1903707411323265152NA
High #51632158915421494144613911335
Med High #4143013901346129412381168960
Med #31238119811451082993908805
Med Low #211181020947851734666563
Low #1998772477418349NANA
High #51861182317871750170816661620
Med High #41674164015991562151614721432
Med #31442140513581311126211971108
Med Low #212571220116311031031942864
Low #111531031967867764718633
High #52091205320161975193719061869
Med High #41903186818321791174817031660
Med #31634159815621516146814221350
Med Low #21447140413611318125711641092
Low #11268120311481073978907839
0.100.200.300.400.500.600.70
External Static Pressure (in. wc.)
1
Johnson Controls Unitary Products9
Page 10
697887-YTG-H-0514
TYPICAL THERMOSTAT CONNECTION
10Johnson Controls Unitary Products
Page 11
697887-YTG-H-0514
A001-001
NOTICE
WIRING FOR BLOWER MOTOR
MAY REQUIRE FIELD ADJUSTMENT,
DEPENDING ON MATCHUP OF
SYSTEM UNITS. REFER TO
THE AIR FLOW DATA (CFM) TABLE IN
THE TECHNICAL GUIDE FOR DETAILS.
BLK -SPD (Y1 / W1)
TYPICAL THERMOSTAT WIRING FOR 2-STAGE HEAT PUMP WITH ECM BLOWER MOTOR