GAS-FIRED
CONDENSING / HIGH EFFICIENCY
DOWNFLOW/HORIZONTAL
TWO STAGE FURNACES
NATURAL GAS
60 - 120 MBH INPUT
EFFICIENCY
RATING
CERTIFIED
ISO 9001
Certified Quality
Management System
Due to continuous product improvement,
specifications are subject to change without notice.
Visit us on the web at www.york.com for the most
up-to-date technical information.
Additional rating information can be found at
www.gamanet.org.
246782-YTG-B-0407
DESCRIPTION
These Category IV, highly efficient, compact, condensing
type furnaces are designed for residential and commercial
installations in a basement, closet, alcove, recreation room or
garage where the ambient temperature is above 32°F, or
higher. They may be either side wall or thru-roof vented using
approved plastic type combustion air and vent piping. All
units are factory assembled, wired and tested to assure
dependable and economical installation and operation.
WARRANTY
Lifetime limited warranty on both heat exchangers to the original purchaser; a 20-year limited warranty from original installation date to subsequent purchaser.
10-year warranty on commercial applications.
5-year limited parts warranty.
FEATURES
• Two stage heating operation includes:
- Two stage gas valve
- Two stage inducer operation
• Provides increased comfort level & very quiet unit operation.
• Adjustable delay timer allows two stage operation with single stage thermostat.
• Compact, easy to install, ideal height 40" cabinet.
• Blower-off delay for cooling SEER improvement.
• Easy to connect power/control wiring.
• Built-in, high level self diagnostics with fault code display.
• Low unit amp requirement for easy replacement application.
• Integrated control module for reliable, economical operation.
• May be installed as either two-pipe (sealed combustion) or
single pipe vent (using indoor combustion air).
• Top intake & vent connection allows installation in narrow
locations.
• Electronic Hot Surface Ignition saves fuel cost with
increased dependability and reliability.
• Induced combustion system with inshot main burners for
quiet, efficient operation.
• No special vent termination kit required.
• 100% shut off main gas valve for extra safety.
• PSC - four speed, direct drive motor with large, quiet
blower.
• 24V, 40 VA control transformer and blower relay supplied
for add-on cooling.
MBH°FHPAmpsIn.Lbs.
PT9B12N060DH1160 / 391651/27.011 x 82014136
PT9B12N080DH1180 / 521651/27.011 x 82014143
PT9C16N080DH1180 / 521653/410.211 x 102014159
PT9C20N100DH11100 / 65165112.711 x 112012164
PT9D20N120DH11120 / 78165112.711 x 112012182
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest editio n) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.
* Wire size and overcurrent protection must comply with the National Electric Code.
NOTES:
1. For altitudes above 2000 ft. reduce capacity 4% for each 1000 ft. above sea level.
2. Wire size based on copper conductors, 60°C, 3% voltage drop.
3. Continuous return air temperature must not be below 55°F.
4. All filters must be high velocity cleanable type.
Rise
2Unitary Products Group
Page 3
BLOWER PERFORMANCE CFM
Models
PT9B12N060DH11
PT9B12N080DH11
PT9C16N080DH11
PT9C20N100DH11
PT9D20N120DH11
NOTES:
1. Airflow expressed in standard cubic feet per minute.
2. Motor voltage at 115 V.
Speed
Tap
High1687165216311595155715111456138213131211
Medium High11931183117311621142111510761036982950
Medium Low933933921911902872825793771712
Low752745731718698652602580536496
High1686165816231572153414651391130512021091
Medium High12571223121812031177114210941026939874
Medium Low977982976955934899843791738686
Low775777757733698663627584549490
High2071202619811935186417961713162515321401
Medium High1583159015691554153215021457140913271221
Medium Low1256127512751288127512651232118711261023
Low937939936945942936912874810726
High2404232022252138203419241816169215591422
Medium High2018195518831815175016701586149713941246
Medium Low162615811531148814181363129112251123964
Low1336129112491205115510911018951884759
High2520243223532251215220421947181517011525
Medium High2018197919451911186317791705159914931353
Medium Low158615451501145714071351128712161081926
Low132112661213116311111071987864763700
246782-YTG-B-0407
AIRFLOW WITH TOP RETURN - WITHOUT FILTERS
EXTERNAL STATIC PRESSURE, INCHES W.C.
0.10.20.30.40.50.60.70.80.91.0
CFMCFMCFMCFMCFMCFMCFMCFMCFMCFM
Unitary Products Group3
Page 4
246782-YTG-B-0407
FILTER PERFORMANCE
The airflow capacity data published in the “Blower Performance” table listed above represents blower performance
WITHOUT filters. To determine the approximate blower performance of the system, apply the filter drop value for the filter being used or select an appropriate value from the “Filter
Performance” table shown.
NOTE: The filter pressure drop values in the “Filter Performance” table shown are typical values for the type of filter
listed and should only be used as a guideline. Actual pressure drop ratings for each filter type vary between filter manufacturer.
RECOMMENDED FILTER SIZES
Input
BTU/H
601200B(2) 14 x 20
801200B(2) 14 x 20
801600C(2) 14 x 20
1002000C(2) 14 x 20
1202000D(2) 14 x 20
NOTES:
1. Air velocity through throwaway type filters may not exceed 300
feet per minute. All velocities over this require the use of high
velocity filters.
CFM
Cabinet
Size
Top Return
Filter in
APPLYING FILTER PRESSURE DROP TO
DETERMINE SYSTEM AIRFLOW
To determine the approximate airflow of the unit with a filter in
place, follow the steps below:
1.Select the filter type.
2.Determine the External System Static Pressure (ESP)
without the filter.
3.Select a filter pressure drop from the table based upon
the number of return air openings or return air opening
size and add to the ESP from Step 3 to determine the
total system static.
4.If total system static matches a ESP value in the airflow
table (i.e. 0.20, 0.60, etc,) the system airflow corresponds to the intersection of the ESP column and Model/
Blower Speed row.
5.If the total system static falls between ESP values in the
table (i.e. 0.58, 0.75, etc.), the static pressure may be
rounded to the nearest value in the table determining the
airflow using Step 5 or calculate the airflow by using the
following example.
Example: For a 120,000 Btuh furnace operating on high
speed blower, it is found that total system static is 0.58" w.c.
To determine the system airflow, complete the following
steps:
* Combustible floor base or air conditioning coil required for use on combustible floor.
TopFrontRearLeft Side Right SideFlueFloor/Bottom
In.In.In.In.In.In.In.
*
1
ClosetAlcoveAttic
YesYesYesNA
Line
Contact
2
Yes
4Unitary Products Group
Page 5
246782-YTG-B-0407
Y/Y2
Cool
For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document available online at www.upgnet.com
in the Product Catalog Section.
1NP0347 - All units
This accessory conversion kit may be used to convert natural
gas units for propane (LP) operation. Conversions must be
made by qualified distributor or dealer personnel.
CONCENTRIC VENT TERMINATION -
1CT0302 (2")
1CT0303 (3")
For use through rooftop, sidewall. Allows combustion air to
enter and exhaust to exit through single common hole. Eliminates unslightly elbows for a cleaner installation.
SIDEWALL VENT TERMINATION KIT -
1HT0901 (3")
1HT0902 (2")
For use on sidewall, two-pipe installations only. Provide a
more attractive termination for locations where the terminal is
visable on the side of the home.
1TK0917 - 17-1/2” Furnace
1TK0921 - 21” Furnace
1TK0924 - 24-1/2” Furnace
These kits are required in downflow application when using
G*F* series coils. These kits are not required with MC/FC
series coils, but please ensure that the coil and furn ace are
secured and that there are no air leaks.
CONDENSATE NEUTRALIZER KIT - 1NK0301
Neutralizer cartidge has a 1/2" plastic tube fittings for installation in the drain line. Calcium carbonate refill media is also
avaiable from the Source 1 Parts (p/n 026-30228-000).
HIGH ALTITUDE PRESSURE SWITCHES -
For installation where the altitude is less than 8,000 feet it is
not required that the pressure switch be changed. For altitudes above 8,000 feet see kits below. Conversion must be
made by qualified distributor or dealer personnel.