York 292443-XTG-D-0508 User Manual

®
292443-XTG-D-0508

FLEXIBLE LIGHT COMMERCIAL UNIT

GENERAL

TECHNICAL GUIDE AFFINITY™ SERIES EXPORT ONLY SINGLE PACKAGE GAS/ELECTRIC AIR COOLED AIR CONDITIONERS
2.5 THROUGH 5 NOMINAL TON
8.6 - 9.2 EER
York® Affinity™ Series packaged units are designed to han­dle applications ranging from residential to light commercial and any in between. The Affinity™ is a unit that gives you the flexibility and choices you need in today’s market.

FEATURING

COOLING/GAS HEATING UNITS (NATURAL GAS OR PROPANE)
LOW PROFILE
QUIET OPERATION
COMMON FOOTPRINT
OPTIONAL SLIDE IN MOTORIZED DAMPERS
OPTIONAL SLIDE IN ECONOMIZERS
OPTIONAL PROP ANE CONVERSION KIT
OPTIONAL HIGH ALTITUDE CONVERSION KIT (NATURAL GAS/PROPANE)
FULL PERIMETER BASE RAILS
BOTTOM AND SIDE UTILITY CONNECTIONS
ISO 9001
Certified Quality
Management System
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
292443-XTG-D-0508

TABLE OF CONTENTS

DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
STANDARD FEATURES/BENEFITS . . . . . . . . . . . . 3
FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . . 4
TYPICAL WIRING DIAGRAM NOTES . . . . . . . . . . 24
MECHANICAL SPECIFICATIONS . . . . . . . . . . . . . 24

LIST OF FIGURES

Fig. # Pg. #
1 PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . .2
2 UNIT COMPONENT LOCATI ON . . . . . . . . . . . . . . . . .5
3 TYPICAL FIELD CONTROL WIRING DIAGRAM . . . 14
4 TYPICAL FIELD POWER WIRING DIAGRAM . . . . .15
5 UNIT DIMENSIONS - FRONT . . . . . . . . . . . . . . . . . .16
6 UNIT DIMENSIONS - FRONT & BOTTOM . . . . . . . .17
7 UNIT DIMENSIONS - BACK & BOTTOM . . . . . . . . .17
8 TYPICAL SLAB ON GROUND INSTALLATION . . . . 18
9 TYPICAL ROOF CURB INSTALLATION . . . . . . . . . . 18
10 TYPICAL DUCT APPLICATIONS . . . . . . . . . . . . . . . 19
11 UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . . . . .19
12 ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . . . . .20
13 ROOF CURB CROSS SECTION . . . . . . . . . . . . . . . .20
14 TYPICAL WIRING DIAGRAM DNA 030 THRU 060
(208/230-1-60 POWER SUPPLY) . . . . . . . . . . . . . . .21
15 TYPICAL WIRING DIAGRAM DNA 036, 042, 048,
060 (208/230-3-60 POWER SUPPLY) . . . . . . . . . . . .22
16 TYPICAL WIRING DIAGRAM DNA 036, 042, 048,
060 (460-3-60 POWER SUPPLY) . . . . . . . . . . . . . . .23
17 TYPICAL WIRING DIAGRAM LEGEND . . . . . . . . . .24

LIST OF TABLES

Tbl. # Pg. #
1 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 RATINGS COOLING/GAS HEATING . . . . . . . . . . . . . 7
3 DNA030 COOLING CAPACITIES - 2-1/2 TON . . . . . . 8
4 DNA036 COOLING CAPACITIES - 3 TON . . . . . . . . . 9
5 DNA042 COOLING CAPACITIES - 3-1/2 TON . . . . . 10
6 DNA048 COOLING CAPACITIES - 4 TON . . . . . . . . 11
7 DNA060 COOLING CAPACITIES - 5 TON . . . . . . . . 12
8 SIDE SUPPLY AIR BLOWER PERFORMANCE . . . . 13
9 BOTTOM SUPPLY AIR BLOWER
PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
10 ADDITIONAL STATIC PRESSURE RESISTANCE
2-1/2 - 3-1/2 TON (DNA030 - 042) . . . . . . . . . . . . . . . 14
11 ADDITIONAL STATIC PRESSURE RESISTANCE
4 - 5 TON (DNA048 - 060) . . . . . . . . . . . . . . . . . . . . . 14
12 ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . 15
13 UNIT DIMENSIONS FRONT . . . . . . . . . . . . . . . . . . . 16
14 UNIT MINIMUM CLEARANCES . . . . . . . . . . . . . . . . 16
15 UNIT WEIGHTS AND CENTER OF GRAVITY . . . . . 19
3
0 6 0 63 0 6
FACTORY
INSTALLED GAS HEAT
VOL TAGE CODE
06 = 208/230-1-60 25 = 208/230-3-60 46 = 460-3-60
NOMINAL GAS HEATING
OUTPUT CAPACITY
036 = 36,000 BTUH 056 = 56,000 BTUH 065 = 65,000 BTUH 072 = 72,000 BTUH 090 = 90,000 BTUH 110 = 110,000 BTUH
PRODUCT CATEGORY
D = Single Package Air Conditioner
PRODUCT GENERATION
2 = 2nd Generation 3 = 3rd Generation 4 = 4th Generation
PRODUCT IDENTIFIER
NA = 10 SEER Gas Heat/Electric
D 2 N A N
NOMINAL COOLING
CAPACITY (MBH)
030 = 30,000 BTUH 036 = 36,000 BTUH 042 = 42,000 BTUH 060 = 60,000 BUTH
N = Natural Gas Heat Installed
FIGURE 1 - PRODUCT NOMENCLATURE
2 Johnson Controls Unitary Products
292443-XTG-D-0508

DESCRIPTION

These packaged cooling/heating air conditioners are designed for outdoor installation. Only utility and duct con­nections are required at the point of installation.
The gas-fired heaters have aluminized steel tubular heat exchangers and spark to pilot ignition. They are available in natural gas with field conversion to propane.

STANDARD FEATURES/BENEFITS

OPERATING EFFICIENCY - All units provide high operating
efficiencies and have a minimum AFUE of 80% and EERs of
8.6 to 9.2. All efficiencies exceed legislated minimum levels. ON SITE FLEXIBILITY - All model sizes share a common,
compact design cabinet in a single footprint. The installer has the flexibility of setting one curb and placing the proper ton­nage unit on that curb after the internal load has been deter­mined. Field convertible duct connections from side shot to down shot allows the installer to have greater flexibility with less inventory.
LOWER INSTALLATION COST - Installation time and costs are reduced by easy power and control wiring connections. The small base dimension means less space is required on the ground or roof, plus, the installer can fit this unit between the wheel wells of full size pick-up truck. All models are well under 500 pounds.
All units are completely wired, charged with R-22 and tested prior to shipment. Unique test stations using a new state of the art computerized process system are used to insure prod­uct quality. Refrigerant charge, and component part numbers are verified via computers at assembly. Vital run test statistics such as system pressure, motor currents, air velocity and temperature, unit vibration, and gas system safeties are mon­itored and recorded by the system to insure unit perfor­mance.
Equal size, side supply and return duct connections allows easy hook-up of ducts to match low crawl spaces without transition pieces.
UTILITY CONNECTIONS MADE EASY - Gas and electric utility knockouts are provided through the bottom as well as the side of the unit. Utility connections can be made quickly and with a minimum amount of field labor. A field supplied and field installed electrical disconnect switch must be installed.
CONVERTIBLE AIRFLOW DESIGN - The bottom duct open­ings are covered when they leave the factory ready to be used for a side supply / side return application. If a bottom supply / bottom return application is desired, you simply remove the two panels from the bottom of the unit and place them in the side supply / side return duct openings. No panel cutting is required and no accessory panel is necessary. Convertible airflow design allows maximum field flexibility and minimum inventory.
CONDENSATE PAN - A non-corrosive, long-lasting, water­tight pan is positioned below the evaporator coil to collect and drain all condensate. Less collection of stagnate condensate will build-up. The condensate pan conforms to ASHRAE 62­89 standards (Ventilation for Acceptable Indoor Air Quality).
CONDENSATE DRAIN - The heavy duty, 3/4 inch NPTI cop­per connection is more tolerable during installation and is more durable over time. The connection is rigidly mounted to assure proper fit and leak tight seal.
DURABLE FINISH - With a heavy duty cabinet made of pow­der-painted, galvanized steel the neutral color blends into surrounding areas. The powdered paint, provides a better paint to steel bond, which resists corrosion and rust creep. The special primer formulas and glossy finish insure less fad­ing when exposed to sunlight and offers a more attractive on site appearance. This paint finish meets ASTM-B117 stan­dards for 1000 hours salt spray rating. The highest in the industry.
FULL PERIMETER BASE RAILS - The easily removable base rails provide a solid foundation for the entire unit and protects the unit during shipment. The rails provide fork lift access from all sides, and rigging holes are also provided so that an overhead crane can be used to place the units on a roof. On applications where the unit is placed on a pad, the base will keep the unit off the pad to deter corrosion. On applications where height is limited, the inch high base rails may be removed on location.
MORE ATTRACTIVE APPEARANCE - A single piece Water Shed top cover containing a top discharge condenser fan arrangement requires less square footage on installation and provides a wider variety of installations. The one piece design adds greater water integrity. Rounded corners with water drip edges add to the attractive appearance. The cabinet panels have a non-fibrous insulation that will not release insulation fibers into conditioned area.
TOP DISCHARGE - The top discharge condenser fan does not disrupt neighboring areas or does this dry-out vegetation surrounding the unit. The warm air from the top mounted fan is blown up away from the structure and any landscaping. This allows compact location on multi-unit applications.
CONDENSER COIL GRILLE
rigidly mounted condenser coil grille provides protection from objects after installation and provides protection duri ng transi t.
LOW OPERATING SOUND LEVEL - The upward air flow carries the normal operating noise up and away from the liv­ing area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil muffle the normal fan motor and compres­sor operating sounds. The unique formed base pan also aids in sound alterations with it's Super-Structure design. This design strategically places embossments in the pan for opti­mum strength and rigidity.
- A multi-piece totally enclosed,
Johnson Controls Unitary Products 3
292443-XTG-D-0508
FAN SYSTEM - All models operate over a wide range of design conditions with a 3-speed direct-drive fan motor. These units easily match all types of applications and pro­vides greater on site flexibility to match comfort requirement.
SIMPLE CONTROL CIRCUIT - A low voltage printed circuit board contains a diagnostic indicator light and a low voltage terminal strip. An additional set of pin connectors is also pro­vided to simplify the field interface of external controls. Mate­n-lock plug connectors are used. The electrical control box is not located in the compressor compartment. The controls are mounted on a Control-Tilt control panel to allow the access cover to be removed for trouble shooting and maintenance without affecting the normal system operating pressures. All wiring internal to the unit is color/number coded.
PROTECTED COMPRESSOR - The compressor is internally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protect the com­pressor if undesirable operating conditions occur.
EXCLUSIVE COIL DESIGN - Grooved copper tubes and enhanced aluminum fin construction improves heat transfer for maximum efficiency and durability.
HEAT EXCHANGERS - Are corrosion-resistant, aluminized­steel tubular construction to provide long-life, trouble-free operation. The unique blow-through design also assures that condensate does not collect in humid areas when in the cool­ing cycle. This adds to longer heat exchanger life and higher long term efficiencies.
POST PURGE INDUCED DRAFT COMBUSTION - Exhausts combustion products from the heat exchanger upon comple­tion of the heating cycle to prolong the heat exchanger life.
SELF DIAGNOSTIC FAN CONTROL MODULE - Due to this self diagnostic control, less on site time is required to trouble shoot these units.
compartment has an additional large panel with a built-in handle tab. Removing this panel will allow the blower assem­bly to slide-out for easy removal for maintenance and ease of trouble shooting.
REPLACEMENT PARTS - The installer has no need to carry an inventory of unique parts or needs special training to replace any of the components parts for these units. All are easily obtained from Source 1 or other part houses.
SYSTEM INTEGRATION - Each unit has the internal ability to integrate an electronic air cleaner or humidifier to work in conjunction with the base unit.

FIELD-INSTALLED ACCESSORIES

PROPANE CONVERSION KIT - Kit includes burner orifices,
gas valve conversion and installation instructions necessary to field convert unit from natural gas to propane.
HIGH ALTITUDE CONVERSION KIT (Natural Gas/Propane)
- Kit includes all necessary labels and instructions to field alter units with natural gas/propane for installation above 2000 feet. Burner orifices must be obtained from Source 1 Parts. Propane Conversion Kit must be obtained separately.
ECONOMIZER DOWN DISCHARGE / SUPPLY KIT - Modu­lating integrated economizer provides simultaneous opera­tion between the mechanical cooling and economizer operation. Independent blade design insures proper control and less than 1% leak rate. Includes hood and mesh bird screen filter integrated into the hood, dry bulb sensor and relief damper. Separate field accessories of single enthalpy and dual enthalpy are also available. A built-in barometric relief of 25% is provided.
SINGLE ENTHALPY SENSOR - Sensor replaces dry bulb sensor standard in economizer kit. Provides improved econo­mizer operation by sensing the dry bulb temperature from outdoors plus the enthalpy content of the outdoor air.
SPARK TO PILOT IGNITION - Provides faster heat delivery. This ignition is highly reliable, durable and eliminates nui­sance lockouts.
MULTI PORT IN-SHOT BURNERS - No field adjustment is required to mix the air and gas. These burners are con­structed of high-grade corrosion-resistant, aluminized-steel.
LOW MAINTENANCE - Long life, permanently lubricated condenser and evaporator fan motor bearings need no annual maintenance adding greater reliability to the unit. Blower assembly can be easily cleaned by the unique Slip­Track slide-out blower assembly.
SECURED SERVICE ACCESS PORTS - Protected, exter­nally mounted, re-usable service access ports are provided on both the high and low lines for ease of evacuating and charging the system. No final field mounting required.
EASY SERVICE ACCESS - A large, single panel covers the electrical and gas controls makes servicing easy. The blower
4 Johnson Controls Unitary Products
DUAL ENTHALPY SENSOR - Additional sensor to single enthalpy sensor. Sensor senses both the return air tempera­ture dry bulb and humidity in conjunction with the single enthalpy to determine the most economical mix. Single Enthalpy sensor also required.
PRESSURE SWITCH UPGRADE KIT - Contains screw in type High pressure, Low Pressure/Loss of Charge switch, freeze protection switch and lockout relay. Switches are placed onto existing scharder ports located in the unit by fur­nished adapters. When abnormal conditions are sensed through the pressure switches, the unit will lock out prevent­ing any further operation until reset or problem is corrected. Package agency approved.
HAIL GUARD KIT - Kit contains protective grilles made of expanded aluminum with full perimeter frame. Sloped hoods are also included to assure maximum protection.
ANTI SHORT CYCLE TIMER - Automatically prevents the compressor from restarting for 5 minutes after cycled off.Not
292443-XTG-D-0508
required if Thermostat 2ET07700224 and 2ET04700224 are used.
MOTORIZED FRESH AIR DAMPER - Designed for duct mounted side supply/return and unit mounted down supply/ return applications. Damper capable of providing 0% through 50% of outdoor air (field supplied). Closes on power loss, includes hood and screen assembly.
FILTER / FRAME KIT (Single Phase only) - Kit contains the necessary hardware to field install return air filters into the base unit. Pre-cut filter racks and appropriate cleanable stan­dard size filters are shipped in one kit. The fiter rack is suit­able for either 1” or 2” filters (1” filter is supplied). This kit is available for single phase horizontal or vertical duct applica­tion only. Standard in all 3 phase models
RECTANGLE TO ROUND ADAPTERS - Kit includes one supply and one return air rectangle to round duct adapter. Adapters are preformed and designed to fit over current duct openings on the base unit. Transition is from side square duct opening to 14" round duct opening.
ROOF CURBS - NRCA approved curbs provide proper fit to base unit for rooftop installations. Curbs are designed to be assembled through hinge pins in each corner. Kit also pro­vides seal strip to assure a water tight seal. 8 and 14 inch high roof curbs are available.
MANUAL OUTDOOR DAMPER - Provides 0% through 50% outdoor air capability (field adjustable). Designed for duct mounted side supply/return applications. Includes hood and screen assembly.
WALL THERMOSTAT - The units are designed to operate with 24-volt electronic and electro-mechanical thermostats. All units can operate with single stage heat / single stage cool thermostats - with or without the economizer.
LOW AMBIENT KIT - Kit provides necessary hardware to convert unit to operate in cooling cycle down to 0 F. Standard unit operation 45 F.
TRANSFORMER KIT - Kit provides necessary hardware to pro­vide single phase models from factory furnished 40 VA trans­former capability to 75 VA transformer capability. (Required on installations with economizer or motorized damper.)
DIRECT DRIVE
CONDENSER FAN
MOTOR
BLOW-THROUGH DESIGN
WITH RELIABLE ALUMINIZED
STEEL TUBULAR HEAT
EXCHANGERS
LONG-LASTING POWDER PAINT
FINISH
REAR & BOTTOM
RETURN AIR
AND SUPPLY AIR
DUCT OPENINGS
HEAVY GAUGE REMOVEABLE
BASE RAILS
3-SPEED DIRECT DRIVE
BLOWER MOTOR WITH
SLIDE-OUT BLOWER ASSEMBLY
POWER VENTER MOTOR
HIGH VOLTAGE
TERMINAL BLOCK
HIGHLY EFFICIENT
ENHANCER
COPPER TUBE/ALUMINUM FIN
EVAPORATOR COIL
HIGHLY EFFICIENT ENHANCED COPPER TUBE/ALUMINUM FIN
CONDENSER COIL
HIGH GRADE
ALUMINIZED
IN-SHOT BURNERS
LOW VOLTAGE
TERMINAL BLOCK
SELF-DIAGNOSTIC CONTROLS
WITH "COMFORT MATCH" SPEED
AUTOMATIC
GAS VALVE
(1/2"- 14NPTI)
CONTROL
DECORATIVE PROTECTIVE COIL GUARD
HIGH EFFICIENCY
COMPRESSOR
RIGIDLY MOUNTED
PILOT ASSEMBLY
FIGURE 2 - UNIT COMPONENT LOCATION
Johnson Controls Unitary Products 5
292443-XTG-D-0508

TABLE 1: PHYSICAL DATA

MODEL
EVAPORATOR
BLOWER
EVAPORATOR
COIL
CONDENSER
FAN
CONDENSER
COIL
CHARGE REFRIGERANT 22 (lbs./oz.) 4 / 12 4 / 3 4 / 9 6 / 0 5 / 4
FILTER
FURNACE
SECTION
COMPRESSOR
TYPE
CENTRIFUGAL BLOWER (Dia. x W. in.) 10 x 8 11 x 10 11 x 10 12 x 11 12 x 11 FAN MOTOR HP (3 Speed) 1/2 3/4 3/4 1 1 ROWS DEEP 22333 FINS PER INCH 13 15 13 13 13 FACE AREA (Sq. Ft.) 3.5 3.5 3.5 4.5 4.5 PROPELLER DIA. (in.) 2222222222 FAN MOTOR HP 1/4 1/4 1/4 1/4 1/4 NOM. CFM TOTAL 2,400 2,400 2,400 3,000 3,000 ROWS DEEP 11111 FINS PER INCH 16 20 20 20 20 FACE AREA (Sq. Ft.) 11.7 11.7 11.7 14.8 14.8
1
FACE AREA (Sq. Ft.) Size (Nominal) 2.6/20x20 2.6/20x20 2.6/20x20 3.3/20x12 3.3/20x12 NATURAL GAS BURNER ORIFICE NO. (Drill Size) 43 43 43 40 40 PROPANE BURNER ORIFICE NO. (Drill Size) 55 55 55 53 53 GAS CONNECTION SIZE HERMETICALLY SEALED
(R = RECIPROCATING, S = SCROLL)
030 036 042 048 060
NPTI 1/2 NPTI 1/2 NPTI 1/2 NPTI 1/2 NPTI
1/2
RRRSS
1. See FILTER/FRAME KIT on page 5.
DNA
6 Johnson Controls Unitary Products
292443-XTG-D-0508

TABLE 2: RATINGS COOLING/GAS HEATING

EER
1
3
SOUND RATING
(dbels)
INPUT
2
(MBH)
MODEL
DNA
030N03606 29 9 78 45 36 80.2 2 25 - 55 030N05606 29 9 78 70 56 80.2 3 30 - 60 036N03606 34.8 8.9 82 45 36 80.4 2 25 - 55 036N05606 34.8 8.9 82 70 56 80.2 3 25 - 55 036N07206 34.8 8.9 82 90 72 80.1 4 30 - 60 036N03625 34.8 8.9 82 45 36 80.4 2 25 - 55 036N03646 34.8 8.9 82 45 36 80.4 2 25 - 55 036N05625 34.8 8.9 82 70 56 80.2 3 25 - 55 036N05646 34.8 8.9 82 70 56 80.2 3 25 - 55 036N07225 34.8 8.9 82 90 72 80.1 4 30 - 60 036N07246 34.8 8.9 82 90 72 80.1 4 30 - 60 042N03606 40.5 9 84 45 36 80.4 2 25 - 55 042N05606 40.5 9 84 70 56 80.2 3 25 - 55 042N07206 40.5 9 84 90 72 80.1 4 30 - 60 042N03625 40.5 9 84 45 36 80.4 2 25 - 55 042N03646 40.5 9 84 45 36 80.4 2 25 - 55 042N05625 40.5 9 84 70 56 80.2 3 25 - 55 042N05646 40.5 9 84 70 56 80.2 3 25 - 55 042N07225 40.5 9 84 90 72 80.1 4 30 - 60 042N07246 40.5 9 84 90 72 80.1 4 30 - 60 048N06506 46.5 8.6 82 80 64 80 3 25 - 55 048N09006 46.5 8.6 82 108 86 80 4 30 - 60 048N11006 46.5 8.6 82 135 108 80 5 35 - 65 048N06525 46.5 8.6 82 80 64 80 3 25 - 55 048N06546 46.5 8.6 82 80 64 80 3 25 - 55 048N09025 46.5 8.6 82 108 86 80 4 30 - 60 048N09046 46.5 8.6 82 108 86 80 4 30 - 60 048N11025 46.5 8.6 82 135 108 80 5 35 - 65 048N11046 46.5 8.6 82 135 108 80 5 35 - 65 060N06506 56.5 8.9 82 80 64 80 3 25 - 55 060N09006 56.5 8.9 82 108 86 80 4 30 - 60 060N11006 56.5 8.9 82 135 108 80 5 35 - 65 060N06525 56.5 8.9 82 80 64 80 3 25 - 55 060N06546 56.5 8.9 82 80 64 80 3 25 - 55 060N09025 56.5 8.9 82 108 86 80 4 30 - 60 060N09046 56.5 8.9 82 108 86 80 4 30 - 60 060N11025 56.5 8.9 82 135 108 80 5 35 - 65 060N11046 56.5 8.9 82 135 108 80 5 35 - 65
NET COOLING CAPACITY
MBH
1. Net Cooling Capacity = ARI 210 standard rating conditions.
2. (dbels) = ARI 270-95
3. Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.
4. AFUE = Annual Fuel Utilization Efficiency.
GAS HEAT CAPACITY / EFFICIENCIES
4
OUTPUT
(MBH)
AFUE
(%)
NUMBER OF
BURNERS
TEMP.
RISE
(°F) RANGE
Johnson Controls Unitary Products 7
292443-XTG-D-0508

TABLE 3: DNA030 COOLING CAPACITIES - 2-1/2 TON

TEMPERATURE
OF AIR ON
CONDENSER COIL
NET CAP.
MBH
TOTAL POWER
INPUT kW
85 °F
95 °F
105 °F
115 °F
125 °F
1
MBH
Sensible Capacity
NET CAP.
MBH
TOTAL POWER
INPUT kW
1
MBH
Sensible Capacit y
NET CAP.
MBH
TOTAL POWER
INPUT kW
1
MBH
Sensible Capacity
NET CAP.
MBH
TOTAL POWER
INPUT kW
1
MBH
Sensible Capacity
NET CAP.
MBH
TOTAL POWER
INPUT kW
1
MBH
Sensible Capacity
86 15.3 19.8 23.6 22.6 18.6 23.6 26.0 24.5 21.9 27.4 28.3 26.4 21.1 26.8 28.6 26.7 20.2 26.2 28.8 26.9 83 14.5 19.0 22.8 21.9 17.0 21.9 25.6 24.2 19.4 24.9 80 13.7 18.2 22.1 21.2 15.3 20.3 24.6 23.6 16.9 22.4 27.2 26.1 17.6 23.3 28.0 26.5 18.3 24.2 77 13.0 17.4 21.3 20.4 13.7 18.7 23.0 22.0 14.5 20.0 24.7 23.6 15.9 21.6 26.3 24.8 17.3 23.3 27.8 25.9 74 12.2 16.7 20.5 19.6 12.1 17.1 21.4 20.4 12.0 17.5 22.2 21.1 14.2 19.9 24.6 23.0 16.4 22.3 26.9 24.9
Bulb °F
Entering Dry
71 - 15.9 19.7 18.8 - 15.5 19.8 18.7 - 15.0 19.8 18.7 - 18.2 22.8 21.3 - 21.3 25.9 24.0 68 - 15.1 19.0 18.1 - 13.8 18.1 17.1 - 12.6 17.3 16.2 - 16.5 21.1 19.6 - 20.4 24.9 23.0
86 17.9 22.3 22.3 21.4 19.9 24.9 24.3 23.4 22.0 27.5 26.4 25.4 21.0 26.7 26.6 25.6 19.9 25.9 26.8 25.8 83 15.6 20.1 80 13.4 17.8 21.0 20.0 15.0 20.0 23.6 22.4 16.6 22.2 26.1 24.8 17.3 23.1 16.5 25.3 18.0 24.0 77 11.1 15.6 18.8 17.7 12.6 17.5 21.1 19.9 14.0 19.5 23.5 22.2 15.5 21.2 24.6 23.5 17.0 23.0 25.8 24.8 74 8.9 13.4 16.5 15.5 10.1 15.1 18.7 17.5 11.3 16.8 20.8 19.5 13.7 19.4 22.8 21.7 16.0 22.0 24.9 23.9
Bulb °F
Entering Dry
71 - 11.1 14.3 13.3 - 12.6 16.2 15.0 - 14.1 18.1 16.8 - 17.6 21.0 19.8 - 21.0 23.9 22.9 68 - 8.9 12.1 11.0 - 10.2 13.7 12.6 - 11.5 15.4 14.1 - 15.8 19.2 18.0 - 20.1 22.9 21.9
86 15.9 20.0 20.6 20.1 17.7 22.3 22.5 21.9 19.6 24.7 24.4 23.8 19.5 24.9 24.7 24.0 19.5 25.1 25.0 24.3 83 14.4 18.5 20.5 19.9 16.1 20.7 80 13.0 17.1 19.6 18.8 14.5 19.1 21.9 21.0 16.1 21.2 24.3 23.3 16.9 22.2 24.6 23.8 17.6 23.2 77 11.5 15.6 18.1 17.3 12.9 17.5 20.3 19.5 14.4 19.5 22.5 21.6 15.5 20.9 23.3 22.5 16.7 22.2 24.0 23.4 74 10.1 14.2 16.6 15.9 11.3 15.9 18.7 17.9 12.6 17.7 20.8 19.8 14.2 19.5 21.9 21.1 15.7 21.3 23.1 22.4
Bulb °F
Entering Dry
71 - 12.7 15.2 14.4 - 14.3 17.1 16.3 - 16.0 19.0 18.1 - 18.2 20.6 19.8 - 20.4 22.1 21.5 68 - 11.3 13.7 13.0 - 12.7 15.5 14.7 - 14.2 17.3 16.3 - 16.8 19.2 18.4 - 19.4 21.2 20.6
86 13.9 17.7 19.0 18.8 15.5 19.7 20.7 20.5 17.2 21.8 22.4 22.1 18.1 23.0 22.7 22.5 19.1 24.2 23.1 22.8 83 13.2 17.0 18.8 18.3 14.8 19.0 20.6 20.2 16.4 21.0 80 12.6 16.3 18.1 17.6 14.1 18.3 20.2 19.7 15.6 20.2 77 11.9 15.7 17.4 16.9 13.3 17.5 19.5 19.0 14.8 19.4 21.6 21.0 15.6 20.5 21.9 21.5 16.3 21.5 22.2 21.9 74 11.2 15.0 16.7 16.3 12.6 16.8 18.8 18.2 13.9 13.6 20.8 20.2 14.7 19.6 21.0 20.6 15.4 20.6 21.3 21.0
Bulb °F
Entering Dry
71 - 14.3 16.1 15.6 - 16.1 18.0 17.5 - 17.8 20.0 19.4 - 18.7 20.2 19.7 - 19.7 20.4 20.1 68 - 13.6 15.4 14.9 - 15.3 17.3 16.7 - 17.0 19.2 18.6 - 17.9 19.3 18.9 - 18.8 19.5 19.2
86 11.9 15.3 17.4 17.5 13.3 17.2 18.9 19.0 14.7 19.0 20.4 20.5 16.7 21.2 20.8 20.9 18.9 23.4 21.3 21.4 83 12.0 15.5 17.0 16.7 13.5 17.3 18.7 18.6 14.9 19.1 80 12.2 15.6 16.6 16.4 13.6 17.4 18.6 18.3 15.0 19.2 20.5 20.2 16.0 20.4 20.9 20.8 16.9 21.7 77 12.3 15.7 16.7 16.5 13.7 17.5 18.7 18.5 15.1 19.4 20.7 20.4 15.6 20.1 20.5 20.4 16.0 20.8 20.4 20.5 74 12.4 15.8 16.9 16.8 13.8 17.6 18.8 18.6 15.3 19.5 20.8 20.5 15.2 19.7 20.1 20.1 15.1 19.9 19.5 19.6
Bulb °F
Entering Dry
71 - 15.9 17.0 16.7 - 17.8 18.9 18.7 - 19.6 20.9 20.7 - 19.3 19.8 19.7 - 19.0 18.6 18.7 68 - 16.0 17.1 16.9 - 17.9 19.1 18.8 - 19.8 21.1 20.8 - 19.0 19.4 19.3 - 18.1 17.7 17.8
750 CFM 875 CFM 1,000 CFM 1,125 CFM 1,250 CFM
WB °F WB °F WB °F WB °F WB °F
72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57
28.1 26.4 24.2 22.6 30.6 28.7 26.3 24.5 32.9 31.0 28.3 26.4 33.2 31.2 28.6 26.7 33.5 31.5 28.8 26.9
2.99 2.95 2.90 2.89 3.03 2.99 2.94 2.93 3.06 3.02 2.97 2.96 3.13 3.09 3.04 3.03 3.20 3.16 3.11 3.10
26.8 25.0 22.3 21.4 29.2 27.3 24.3 23.4 31.7 29.6 26.4 25.4 32.0 29.9 26.6 25.6 32.2 30.1 26.8 25.8
3.18 3.14 3.08 3.07 3.22 3.18 3.1 1 3.11 3.26 3.22 3.15 3.15 3.34 3.30 3.23 3.22 3.42 3.38 3.30 3.30
22.3 21.4 17.5 22.5 24.3 23.4 19.3 24.9 26.4 25.4 19.1 24.9 26.6 25.6 19.0 24.9 26.8 25.8
25.4 23.0 20.6 20.1 27.7 25.0 22.5 21.9 30.0 27.1 24.4 23.8 30.4 27.4 24.7 24.0 30.7 27.8 25.0 24.3
2.94 3.31 3.23 3.24 2.98 3.36 3.28 3.29 3.03 3.41 3.33 3.34 3.10 3.49 3.41 3.42 3.17 3.57 3.48 3.49
22.5 21.8 17.8 22.9 24.4 23.8 18.2 23.5 24.7 24.0 18.6 24.1 25.0 24.3
24.1 20.9 19.0 18.8 26.2 22.8 20.7 20.5 28.3 24.6 22.4 22.1 28.8 25.0 22.7 22.5 29.2 25.4 23.1 22.8
2.70 3.47 3.38 3.40 2.75 3.53 3.44 3.47 2.80 3.60 3.50 3.53 2.86 3.68 3.58 3.61 2.92 3.76 3.66 3.69
22.7 18.9 17.4 17.5 24.7 20.5 18.9 19.0 26.6 22.2 20.4 20.5 27.2 22.6 20.8 20.9 27.7 23.1 21.3 21.4
2.45 3.63 3.53 3.57 2.51 3.71 3.60 3.64 2.56 3.79 3.68 3.72 2.62 3.87 3.76 3.80 2.68 3.96 3.84 3.89
AIR ON EVAPORATOR COIL
28.3 26.4 19.3 25.1 28.6 26.7 19.3 25.2 28.8 26.9
28.8 26.9
26.8 25.8
25.0 24.3
22.4 22.1 17.3 22.2 22.7 22.5 18.2 23.3 23.1 22.8
22.4 21.8 16.4 21.3 22.7 22.3 17.3 22.4 23.1 22.8
20.4 20.5 16.3 20.8 20.8 20.9 17.8 22.5 21.3 21.4
21.3 21.4
1. These capacities are net capacities (the indoor fan heat is deducted).
ALL SENSIBLE CAPACITY
8 Johnson Controls Unitary Products
292443-XTG-D-0508

TABLE 4: DNA036 COOLING CAPACITIES - 3 TON

TEMPERATURE
OF AIR ON
CONDENSER COIL
NET CAP.
MBH
TOTAL POWER
INPUT kW
85 °F
95 °F
105 °F
115 °F
125 °F
1
MBH
Sensible Capacity
NET CAP.
MBH
TOTAL POWER
INPUT kW
1
MBH
Sensible Capacit y
NET CAP.
MBH
TOTAL POWER
INPUT kW
1
MBH
Sensible Capacity
NET CAP.
MBH
TOTAL POWER
INPUT kW
1
MBH
Sensible Capacity
NET CAP.
MBH
TOTAL POWER
INPUT kW
1
MBH
Sensible Capacity
86 19.8 25.2 29.9 30.3 23.0 28.7 32.0 31.3 26.1 32.1 34.0 32.3 24.8 31.0 34.2 32.5 23.5 29.9 34.4 32.7 83 18.9 24.3 29.0 29.7 21.0 26.7 31.5 31.0 23.1 29.2 80 18.0 23.4 28.1 28.8 19.1 24.8 29.8 30.5 20.1 26.2 31.5 77 17.1 22.4 27.2 27.9 17.1 22.8 27.8 28.6 17.2 23.2 28.5 29.3 18.7 24.9 30.4 30.5 20.2 26.6 32.2 31.6 74 16.1 21.5 26.2 26.9 15.2 20.9 25.9 26.6 14.2 20.2 25.5 26.3 16.7 22.9 28.3 28.4 19.1 25.5 31.1 30.5
Bulb °F
Entering Dry
71 - 20.6 25.3 26.0 - 18.9 23.9 24.7 - 17.3 22.6 23.4 - 20.9 26.3 26.4 - 24.4 30.0 29.4 68 - 19.7 24.4 25.1 - 17.0 22.0 22.7 - 14.3 19.6 20.4 - 18.8 24.3 24.4 - 23.3 28.9 28.3
86 23.8 29.2 31.4 31.2 25.1 30.8 31.8 31.5 26.5 32.4 32.1 31.9 25.1 31.2 32.6 32.4 23.6 30.0 33.2 32.9 83 21.1 26.5 31.2 80 18.4 23.8 28.5 29.3 19.2 24.9 29.8 30.6 20.0 26.0 31.1 77 15.7 21.1 25.9 26.6 16.3 21.9 26.9 27.6 16.8 22.7 27.9 28.7 18.6 24.7 30.0 30.3 20.3 26.7 32.1 31.8 74 13.0 18.5 23.2 23.9 13.3 19.0 23.9 24.7 13.6 19.5 24.7 25.5 16.4 22.5 27.8 28.1 19.2 25.6 31.0 30.7
Bulb °F
Entering Dry
71 - 15.8 20.5 21.2 - 16.0 21.0 21.7 - 16.3 21.4 22.2 - 20.4 25.7 25.9 - 24.5 29.9 29.6 68 - 13.1 17.8 18.5 - 13.1 18.0 18.8 - 13.1 18.2 19.0 - 18.2 23.5 23.8 - 23.4 28.8 28.5
86 21.1 27.2 29.8 28.8 22.4 28.7 30.6 29.5 23.7 30.3 31.3 30.2 23.2 30.1 31.7 30.6 22.8 29.8 32.1 30.9 83 19.4 25.4 29.3 28.4 20.5 26.8 30.3 29.3 21.6 28.2 80 17.7 23.7 27.6 27.0 18.6 24.9 29.0 28.4 19.5 26.1 30.4 29.8 20.1 26.9 31.2 30.4 20.6 27.7 77 15.9 21.9 25.8 25.3 16.6 23.0 27.1 26.5 17.4 24.0 28.3 27.7 18.5 25.3 29.7 28.8 19.6 26.6 31.0 29.8 74 14.2 20.2 24.1 23.5 14.7 21.0 25.1 24.6 15.3 21.9 26.2 25.6 16.9 23.7 28.1 27.2 18.5 25.5 29.9 28.8
Bulb °F
Entering Dry
71 - 18.4 22.3 21.8 - 19.1 23.2 22.7 - 19.8 24.1 23.5 - 22.2 26.5 25.6 - 24.5 28.9 27.7 68 - 16.7 20.6 20.0 - 17.2 21.3 20.7 - 17.7 22.0 21.4 - 20.6 24.9 24.0 - 23.4 27.8 26.7
86 18.5 25.1 28.2 26.4 19.7 26.7 29.4 27.4 20.9 28.2 30.6 28.5 21.4 28.9 30.8 28.7 21.9 29.6 31.0 28.9 83 17.7 24.3 27.4 25.6 18.8 25.8 29.0 27.0 19.9 27.3 80 16.9 23.5 26.6 24.8 17.9 24.9 28.1 26.2 18.9 26.3 29.7 27.7 19.4 26.9 30.3 28.3 19.9 27.6 31.0 28.9 77 16.1 22.7 25.8 24.0 17.0 24.0 27.2 25.4 17.9 25.3 28.7 26.7 18.4 25.9 29.3 27.3 18.8 26.6 30.0 27.9 74 15.3 21.9 24.9 23.2 16.1 23.1 26.4 24.5 17.0 24.3 27.8 25.8 17.4 24.9 28.3 26.3 17.8 25.5 28.9 26.8
Bulb °F
Entering Dry
71 - 21.1 24.1 22.4 - 22.2 25.5 23.6 - 23.4 26.8 24.8 - 23.9 27.3 25.3 - 24.5 27.9 25.8 68 - 20.3 23.3 21.6 - 21.3 24.6 22.7 - 22.4 25.8 23.8 - 22.9 26.3 24.3 - 23.5 26.9 24.8
86 15.9 23.1 26.6 24.0 17.0 24.6 28.2 25.4 18.1 26.1 29.8 26.8 19.6 27.8 29.8 26.8 21.1 29.5 29.9 26.9 83 16.0 23.2 25.4 22.8 17.1 24.8 27.6 24.8 18.2 26.3 80 16.2 23.3 25.6 22.5 17.3 24.9 27.3 24.1 18.4 26.5 29.0 25.6 18.7 27.0 29.5 26.2 19.1 27.5 77 16.3 23.5 25.7 22.7 17.4 25.0 27.4 24.2 18.5 26.6 29.2 25.8 18.3 26.6 29.0 25.8 18.1 26.5 28.9 25.9 74 16.4 23.6 25.8 22.8 17.6 25.2 27.6 24.4 18.7 26.8 29.3 25.9 17.9 26.1 28.6 25.4 17.1 25.5 27.9 24.9
Bulb °F
Entering Dry
71 - 23.7 26.0 22.9 - 25.3 27.7 24.5 - 26.9 29.5 26.1 - 25.7 28.2 25.0 - 24.5 26.9 23.9 68 - 23.9 26.1 23.1 - 25.5 27.9 24.7 - 27.1 29.6 26.2 - 25.3 27.8 24.6 - 23.5 25.9 22.9
900 CFM 1,050 CFM 1,200 CFM 1,350 CFM 1,500 CFM
WB °F WB °F WB °F WB °F WB °F
72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57
36.7 34.6 31.9 30.3 37.9 35.7 32.9 31.3 39.1 36.9 34.0 32.3 39.4 37.1 34.2 32.5 39.6 37.4 34.4 32.7
3.57 3.51 3.44 3.41 3.64 3.58 3.51 3.48 3.71 3.65 3.58 3.55 3.80 3.73 3.66 3.63 3.88 3.82 3.74 3.71
36.9 34.1 31.4 31.2 37.3 34.5 31.8 31.5 37.7 34.9 32.1 31.9 38.3 35.5 32.6 32.4 39.0 36.1 33.2 32.9
3.77 3.73 3.64 3.61 3.86 3.81 3.72 3.69 3.95 3.90 3.81 3.77 4.03 3.98 3.88 3.85 4.11 4.06 3.96 3.93
31.2 22.2 27.8 31.7 31.5 23.3 29.2 32.1 31.9 22.9 29.0 32.6 32.4 22.5 28.9 33.2 32.9
34.9 32.6 30.7 29.6 35.3 32.9 31.0 29.9 35.6 33.2 31.3 30.2 36.1 33.6 31.7 30.6 36.5 34.0 32.1 30.9
4.00 3.93 3.84 3.83 4.09 4.01 3.93 3.91 4.18 4.10 4.01 3.99 4.26 4.18 4.09 4.07 4.34 4.26 4.17 4.15
33.0 31.0 30.0 28.0 33.3 31.3 30.3 28.2 33.5 31.6 30.6 28.5 33.8 31.8 30.8 28.7 34.0 32.0 31.0 28.9
4.24 4.13 4.05 4.04 4.32 4.22 4.13 4.12 4.41 4.30 4.22 4.21 4.50 4.38 4.30 4.29 4.58 4.47 4.38 4.37
31.0 29.4 29.3 26.4 31.2 29.7 29.6 26.6 31.4 29.9 29.8 26.8 31.5 29.9 29.8 26.8 31.5 30.0 29.9 26.9
4.47 4.33 4.26 4.26 4.55 4.42 4.34 4.34 4.64 4.50 4.42 4.42 4.73 4.59 4.51 4.51 4.82 4.68 4.59 4.60
AIR ON EVAPORATOR COIL
34.0 32.3 22.8 29.0 34.2 32.5 22.4 28.8 34.4 32.7
32.3 20.7 27.0 32.4 32.5 21.3 27.7 33.3 32.7
31.9 20.7 26.9 32.1 32.4 21.4 27.8 33.2 32.9
31.3 30.2 21.6 28.5 31.7 30.6 21.7 28.7 32.1 30.9
32.1 30.9
30.6 28.5 20.4 27.9 30.8 28.7 20.9 28.6 31.0 28.9
29.8 26.8 19.1 27.4 29.8 26.8 20.1 28.5 29.9 26.9
29.9 26.9
1. These capacities are net capacities (the indoor fan heat is deducted).
ALL SENSIBLE CAPACITY
Johnson Controls Unitary Products 9