- test case does not apply to the test object ................. : N/A
- test object does meet the requirement ....................... : P (Pass)
- test object does not meet the requirement ................. : F (Fail)
www.tuv.com Page 3 of 90 Report No.: CN22UKC1 001
Copy of marking plate:
Remark: Date code: YY represents month of manufacture, XX represents year.
General remarks
This report shall not be reproduced, except in full, without the written approval of the Issuing testing
laboratory.
“(see Enclosure #)” refers to additional information appended to the report.
“(see appended table)” refers to a table appended to the report.
Throughout this report a point is used as the decimal separator.
Summary of testing:
All models were tested and fulfilled the test specifications.
The tested model was complied with the test standards UL 998 & CSA C22.2 No. 104; and the built-in
power supply was complied with the test standards UL 1310 & C22.2 No. 223.
Mass of equipment (kg) ............................... : N/A
Test case verdicts
Test case does not apply to the test object : N/A
Test item does meet the requirement ......... : P(ass)
Test item does not meet the requirement ... : F(ail)
Testing
Date of receipt of test item .......................... :
Date(s) of performance of test .................... :
See cover page
See cover page
General product information:
The submitted test sample was marked or declared or designed by the client as a Ultrasonic Humidifier for
household and indoor use, with ratings of 110/120VAC, 50/60Hz.
injection type, steam type, and the like. The humidifiers may be
Standard for Electric Heating Appliances, UL 499, and the CSA
The actual electrical conducting medium that
www.tuv.com
Page 4 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
1 Humidifiers
1.1 These requirements cover humidifiers rated 600 V or less, and
P
P
intended to be used in accordance with the National Electrical
Code (NEC), ANSI/NFPA 70, and the Rules of the Canadian
Electrical Code (CEC), Part I, C22.1.
1.2 These requirements cover humidifiers intended for residential
Household and indoor used.
P
and commercial use. This includes humidifiers of the
centrifugal atomizing type, evaporative-media type, water-
for installation in a room, mounted on a wall or a ceiling, or for
duct or plenum mounting.
1.3 These requirements apply to equipment that includes an
N/A
electric heating element to heat air or water, or both.
1.4 These requirements do not apply to evaporative coolers that
N/A
are also intended to be used for cooling.
1.5 These requirements do not apply to portable, electrode-type
N/A
products, such as vaporizers, which are covered by the
Standard for Household Cooking and Liquid-Heating
Appliances, CAN/CSA-C22.2 No. 64.
2 Definitions P
2.1 The following definitions apply in this Standard: P
2.2 Circuit, extra-low-voltage - A circuit that has an ac potential of
P
not more than 30 V (42.4 peak), and power of 100 VA or less;
or 30 V dc supplied by a primary battery; or supplied by a
Class 2 transformer; or supplied by a combination of a
transformer and fixed impedance that, as a unit, complies with
all the performance requirements for a Class 2 transformer. A
circuit that is derived from a circuit which exceeds 30 V by
connecting resistance or impedance, or both, in series with the
supply circuit to limit the voltage and current, is not considered
to be an extra-low-voltage circuit.
2.3 Circuit, hazardous voltage - A circuit having characteristics in
P
excess of those of an extra-low-voltage circuit.
2.4 Combination temperature-regulating and temperature-limiting
N/A
thermostat - A thermostat whose function is to regulate the
temperature under normal conditions of use, and that also
serves to prevent a hazard that might result from conditions of
abnormal operation of the heater.
2.5 Enclosure - The enclosure that houses the electrical
P
components, live parts and/or moving parts. It may be an
integral part of the component, a separate item, part of the
ultimate enclosure, or the ultimate enclosure (e.g., the outer
cabinet).
2.6 Heater element - A complete or partial assembly of a heating
N/A
element, an electrical insulation (e.g., refractory, mica), a metal
sheath, a glass or quartz envelope or panel, thermal insulation,
and a frame or adaptor for holding the assembly together and
fastening it in the heater; and leads or terminal connections, or
both, which may or may not include bolts and nuts.
2.7 Heating element -
N/A
is intended to be heated by an electric current.
2.8 Humidifier - Equipment that is designed to increase the relative
P
humidity of air.
limiting device in a system, the failure of which
For products intended for use in Canada, general requirements
www.tuv.com
Clause Requirement Test Result - Remark Verdict
2.9 Junction block - A wiring device that encloses splices between
wires and that may provide a receptacle for connecting a
component of the equipment.
2.10 Portable Equipment - Equipment designed to not be used in a
fixed position and receiving current through a flexible cord or
cable and an attachment plug.
2.11 Safety-circuit - A circuit that includes contacts of any controls
integral with, or external to, the equipment that are intended to
prevent unsafe operation of the equipment due to circuit wiring
becoming grounded, open circuited, or short circuited, such as:
a) A device to prevent overheating of a motor due to
overload (including locked rotor);
b) A temperature limit switch, the failure of which to operate
might result in an unsafe operation; or
c) A pressure-
to operate might result in an unsafe condition.
2.12 Temperature-limiting thermostat - A thermostat that functions
only under conditions that produce abnormal temperatures.
The failure of such a thermostat might result in a hazard.
2.13 Temperature-regulating thermostat - A thermostat that
functions only to regulate the temperature under normal
conditions of use. The failure of such a thermostat would not
result in a hazard.
2.14 User servicing - Any form of servicing that is likely to be
performed by personnel other than those who are trained to
maintain the product. Some examples include routine cleaning,
filter replacement, and replacement of an accessible fuse or
lamp.
3 General P
3.1 Components P
3.1.1 Except as indicated in Clause 3.1.2, a component of a product
covered by this Standard shall comply with the requirements
for that component. See Annex A for a list of Standards
covering components used in the products covered by this
Standard. A component shall comply with the CSA
International and the Underwriters Laboratories, Inc.
standards.
3.1.2 A component is not required to comply with a specific
requirement that:
a) Involves a feature or characteristic not required in the
application of the component in the product covered by this
standard, or
b) Is superseded by a requirement in this standard. P
3.1.3 A component shall be used in accordance with its rating
established for the intended conditions of use.
3.1.4 Specific components are incomplete in construction features or
restricted in performance capabilities. Such components are
intended for use only under limited conditions, such as certain
temperatures not exceeding specified limits, and shall be used
only under those specific conditions.
3.1.5
are given in CAN/CSA-C22.2 No.0.
3.1.6 Products covered by this standard shall comply with the
referenced installation codes and standards noted in Clause
3.2.
Page 5 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
N/A
P
N/A
N/A
N/A
N/A
N/A
N/A
N/A
P
P
P
P
P
P
CONSTRUCTION
4 General
P
deflecting means in the path of the moving air, shall include the
d by explicit instructions for
www.tuv.com
Page 6 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
3.2 Reference publications P
3.3 Units of measurement P
3.3.1 The values given in SI (metric) units shall be normative. Any
P
other values given shall be for information purposes only.
3.4 Terminology P
3.4.1 In the following text, a requirement that applies only to a
P
particular type of humidifier is so identified by a specific
reference in that requirement to the type or types of humidifiers
involved. Absence of such specific reference or use of the term
"product" indicates that the requirement applies to all types of
humidifiers unless the context indicates otherwise.
P
4.1 A product shall be completely assembled when it is shipped
P
from the factory.
Exception: A product may be shipped partially disassembled,
No such parts N/A
to facilitate packaging or installation, if proper assembly can be
accomplished without a risk of fire, electric shock, or injury to
persons, and each part is marked as required by Clause 76.3.
4.2 A product intended for mounting to the ceiling, floor, or wall
Portable appliance N/A
shall have provisions for such mounting. All required fittings
such as brackets, hangers, or the like, necessary for mounting
shall be furnished with the product.
Exception: Parts commonly available for the mounting of the
N/A
product need not be provided if mounting instructions that refer
to such parts are furnished in accordance with Clause 76.8.
4.3 A humidifier that is intended for mounting on the hot air plenum
Not such appliance N/A
or duct of a furnace, and that requires the installation of an air
necessary deflecting means as a part or accessory of the
humidifier, and shall be accompanie
the installation of the means so as to avoid impairment of the
function of the furnace.
5 Enclosures P
5.1 General P
5.1.1 Products shall be constructed so that they have the strength
and rigidity necessary to resist the abuse to which they may be
subjected, without increasing the risk of fire, electric shock, or
injury to persons, due to partial collapse with resultant
reduction of spacings, loosening or displacement of parts, or
other defects.
5.1.2 In determining compliance with Clause 5.1.1, all elements that
contribute to the enclosing function, including enclosures of
individual components and the exterior (decorative) cabinet,
shall be considered.
P
P
nonferrous metal, for a hole having a 6.4 mm (1/4 in) maximum
the requirements of Clause 5.2.1, an enclosure of
ard Methods of Tests
www.tuv.com
Clause Requirement Test Result - Remark Verdict
5.1.3 Enclosures made in the form of grilles, etc, of wire or sheet
metal, and intended to accommodate air flow required for the
operation of the equipment, shall be considered to comply with
Clause 5.1.1, if they provide resistance to deflection or impact
that would be acceptable to the requirements specified in
Clause 5.1.4 for enclosures of sheet metal.
5.1.4 Cast and sheet-metal sections of an enclosure shall not be
thinner than specified in Table 1.
Exception: Thinner metal may be used provided the surface
under consideration is curved, ribbed, or otherwise reinforced
to provide mechanical strength equivalent to that required.
5.1.5 A metal plate or metal plug used to cover an unused conduit
opening or other hole that is required to be covered in the
enclosure shall have a thickness not less than:
a) 0.35 mm (0.014 in) if steel, or 0.48 mm (0.019 in) if
dimension; and
b) 0.68 mm (0.027 in) if steel, or 0.81 mm (0.032 in) if
nonferrous metal, for a hole having a 34.9 mm (1-3/8 in)
maximum dimension. A closure for a larger hole shall have a
thickness no less than that required for the enclosure of the
product. Such plates or plugs shall be securely mounted.
5.2 Nonmetallic materials P
5.2.1 Enclosures or parts of equipment manufactured, of nonmetallic
materials, shall not cause a risk of fire, electric shock, or injury
to persons, because of susceptibility to ignition or melting by
electrical disturbances within, or because of deterioration from
aging effects, or exposure to the operating environment.
5.2.2 Enclosures shall be considered to comply with Clause 5.2.1 if: UL certified plastic material
a) They comply with the flammability test specified in the
Standard for Polymeric Materials - Use in Electrical Equipment
Evaluation, UL 746C, and the CSA Standard for Evaluation of
Properties of Polymeric Materials, CAN/CSA-C22.2 No. 0.17;
b) They have temperature ratings not less than the
maximum temperatures to which they may be exposed during
normal operation; and
c) The equipment is in compliance with Clauses 5.2.3, 5.2.4,
and 5.2.5.
5.2.3 In addition to
polymeric material having in any unbroken section an exposed
surface greater than 0.93 m2 (10 ft2), or a single dimension
greater than 1.83 m (6 ft), shall have maximum flame spread
rating of:
a) 200 for a portable product, and N/A
b) 50 for a product intended to be permanently connected to
the electrical supply.
5.2.4 The flame spread rating mentioned in Clause 5.2.3 shall be
determined in accordance with the requirements in the
Standard for Test for Surface Burning Characteristics of
Building Materials, UL 723, or the radiant panel test
requirement in accordance with the Standard Test Method for
Surface Flammability of Materials Using a Radiant Heat
Energy Source, ASTM E162, or the Stand
for Surface Burning Characteristics of Building Materials and
Assemblies, CAN/ULC-S102.
Page 7 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
No such enclosure N/A
No metal enclosure N/A
N/A
N/A
N/A
N/A
P
P
used
P
P
P
N/A
N/A
N/A
surrounding equipment enclosure may be of material that is not
to prevent a risk of electric shock, complies with the impact test
www.tuv.com
Page 8 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
5.2.5 Where bare live parts of electrical components, such as switch
No such part N/A
terminals, are individually enclosed with metal, or insulating
tube or sleeving that complies with VW-1 flammability
requirements in accordance with the Standard for Extruded
Insulating Tubing, UL 224 and CSA C22.2 No. 198.1, or the
Standard for Coated Electrical Sleeving, UL 1441 and CSA
C22.2 No. 198.3, respectively; or polymeric material that
complies with the requirements of the vertical burning test for
classifying materials 5 VA in accordance with the Standard for
Tests for Flammability of Plastic Materials for Parts in Devices
and Appliances, UL 94, and Flammability Rating of 5V (500
W), in the CSA Standard for Evaluation of Properties of
Polymeric Materials, CAN/CSA-C22.2 No. 0.17, the
more flammable than material classed as HB as specified in
CAN/CSA-C22.2 No. 0.17, and HB as specified in UL 94,
provided:
a) The equipment does not employ open-coil heaters; N/A
b) Internal wiring within the surrounding equipment
N/A
enclosure complies with flame test classification VW-1 as
referenced in the Reference Standard for Electrical Wires,
Cables, and Flexible Cords, UL 1581, and FT1 of the CSA
Standard for Test Methods for Electrical Wires and Cables,
C22.2 No. 0.3;
c) Splices within the surrounding equipment enclosure are
N/A
made with insulated wire connectors that are resistant to
loosening due to vibration; and
d) The surrounding equipment enclosure, where relied upon
N/A
requirements of Clause 59.
5.3 Enclosure integrity P
5.3.1 The enclosure of a product shall reduce the likelihood that
P
molten metal, burning insulation, flaming particles, or the like
will fall on combustible materials, including the surface upon
which the product is supported.
5.3.2 The requirement in Clause 5.3.1 necessitates the use of a
No barrier necessary N/A
barrier under wiring, unless it is neoprene- or thermoplasticinsulated, and under a motor unless:
a) The structural parts of the motor or the product provide
N/A
the equivalent of such a barrier;
b) The protection provided with the motor is such that no
N/A
burning insulation or molten material falls to the surface that
supports the product when the motor is energized under each
of the following fault conditions:
1) Open main winding; N/A
2) Open starting winding; N/A
3) Starting switch short-circuited; and N/A
4) Capacitor of permanent-split capacitor motor short-
N/A
circuited – the short circuit is to be applied before the motor is
energized, and the rotor is to be locked.
6 Doors and Covers
N/A
www.tuv.com
Clause Requirement Test Result - Remark Verdict
c) The motor is provided with a thermal motor protector, that
is, a protective device that is sensitive to temperature and
current that keeps the temperature of the motor windings from
exceeding 125°C (257°F) under the maximum load under
which the motor runs without causing the protector to cycle,
and from exceeding 150°C (302°F) with the rotor of the motor
locked; or
d) The motor complies with the requirements for impedance-
protected motors in the Standard for Impedance Protected
Motors, UL 1004-2, and the CSA Standard for Motors with
Inherent Overheating Protection, C22.2 No. 77.
5.3.3 The requirements in Clause 5.3.1 will also necessitate that a
switch, a relay, a solenoid, or the like, be individually and
completely enclosed.
Exception No. 1: The terminals of a switch, a relay, a solenoid,
or the like need not be completely enclosed.
Exception No. 2: A component need not be completely
enclosed if:
a) Malfunction of the component would not result in a risk of
fire or
b) There are no openings in the bottom of the product
enclosure.
5.3.4 The barrier mentioned in Clause 5.3.2 shall be horizontal, shall
be located as illustrated in Figure 1, and shall have an area not
less than that described in the illustration. Openings for
drainage, ventilation, and the like, that would not permit molten
metal, burning insulation, or the like, to fall on combustible
material, may be employed in a barrier.
5.3.5 If an opening for ventilation is provided in the enclosure of a
product or an externally mounted component, and if the
product is intended to be recessed into a wall or false ceiling,
such an opening shall not allow venting into concealed space.
Page 9 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
N/A
N/A
No such part N/A
N/A
N/A
N/A
N/A
N/A
No a recessed mount
product
N/A
6.1 Doors and covers that give access to uninsulated live
hazardous voltage parts shall be secured firmly in place, and
shall require the use of a tool or key to open them or shall be
provided with an interlocking mechanism; however,
components having covers that comply with their respective
standards do not require additional enclosures.
6.2 An interlocking mechanism complies with the requirements of
Clause 6.1 if it:
a) Secures the cover in the closed position when engaged
and
b) Must be engaged before parts in a hazardous voltage
circuit can be energized.
6.3 Accessibility shall be afforded to all parts that require normal
servicing or adjustment (for example, controls, filters, oiling of
bearings, adjustment of belts) when the equipment is installed
as intended. Covers or access panels giving access to such
parts that are required to be removed for routine maintenance
shall not expose uninsulated live parts.
6.4 The assembly shall be arranged so that any overcurrent
protective device that can be replaced or reset as required is
accessible without removal of parts other than the service
covers or panels.
No such part N/A
N/A
N/A
N/A
No such part N/A
N/A
temperature or pressure control) may be accessible without the
than 4.4 N (1 lbf), and shall be rotated or angled before, during,
www.tuv.com
Clause Requirement Test Result - Remark Verdict
6.5 The door or cover of an enclosure shall be hinged, sliding type,
pivoted, or the equivalent, and not intended for removal, if it
gives access to any overcurrent protective device. If more than
one door or cover has to be opened to provide access to the
overcurrent protective device, only one of these needs to
comply with this requirement.
Exception: A cover, panel, door, or other part of an enclosure
that, because of its function or size, obviously must be in place
to complete the overall enclosure, need not be hinged, sliding
type, or pivoted.
6.6 A cover as specified in Clause 6.5 is not required if fuses only
of the following types are enclosed:
a) Fuses connected in extra-low-voltage circuits; N/A
b) Extractor type fuses that have their own enclosures; N/A
c) Control circuit fuses provided that the control circuit loads
(other than fixed loads, such as pilot lamps) are housed in the
same enclosure as the fuses; or
d) Supplementary type fuses rated 2 A or less used in small,
auxiliary resistance heater circuits having a maximum rating of
100 W.
6.7 The reset button or lever of manual resettable devices (for
example, the operating handle of a circuit breaker, the reset
button of a motor protector, the reset button of a pressure
switch, the adjusting screw or knob of an adjustable
Page 10 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
No such part N/A
N/A
N/A
N/A
N/A
N/A
use of a tool, provided that the resetting of the device does not
result in exposure to uninsulated live hazardous voltage parts
or moving parts.
7 Accessibility of Uninsulated Hazardous Voltage Live Parts
and Film-Coated Wire
7.1 To reduce the risk of unintentional human contact with an
uninsulated live part or film-coated wire, louvers or other
openings in the enclosure of a product, and openings in a
motor, shall be so designed, located, or baffled as to comply
with the requirements specified in Table 2.
7.2 With respect to the requirement in Clause 7.1, insulated brush
caps do not require additional enclosure.
7.3 In determining compliance with Clauses 7.1 and 7.2, any
doors, covers, or components that are intended to be removed
for routine maintenance purposes, or that may be removed,
without using a tool, by the user to attach an accessory, to
make an operating adjustment, or for other reasons, shall be
removed.
7.4 In cord-connected humidifiers where the enclosure of a fan is
completed by a drum supporting the evaporating medium, a
marking in accordance with Clause 75.19 shall be acceptable.
7.5 The probes illustrated in Figures 2 – 5 shall be applied to any
depth that the opening enables and with a force not greater
P
Live parts enclosed in
enclosure
N/A
No such part N/A
N/A
P
P
and after insertion through the opening to any position that is
required to examine the product or motor. The probe illustrated
in Figure 2 shall be applied in any possible configuration, and,
when required, the configuration shall be changed after
insertion through the opening.
7.6 With reference to the requirements in Table 2, an indirectly
accessible motor is a motor:
N/A
b) That is located at such a height or is otherwise guarded or
No live part could be contact
www.tuv.com
Clause Requirement Test Result - Remark Verdict
a) That is accessible only by removing a part of the outer
enclosure of a product, such as a guard or panel, that can be
removed without using a tool; or
enclosed so that it is unlikely to be contacted.
7.7 With reference to the requirements in Tables 2 and 3, the
minor dimension of an opening is the diameter of the largest
cylindrical probe having a hemispherical tip that can be
inserted through the opening perpendicular to the plane of the
opening with a force not greater than 22 N (5 lbf).
7.8 If Table 2 specifies a probe to be used to judge the
accessibility of an uninsulated live part or film-coated wire, the
probe shall not contact such a part or wire when inserted
through an opening in the enclosure of a product or motor as
described in Clause 7.5.
7.9 If Table 2 does not specify that a probe is to be used to judge
the accessibility of an uninsulated live part or film-coated wire,
such a part or wire shall not be:
a) Within “X” mm (inches) of the perimeter of an opening in
the enclosure of a product or a motor; or
b) Within the volume generated by projecting the perimeter
“X” mm (inches) normal to its plane. “X” equals five times the
minor dimension of the opening, but not less than the values
specified in Table 2. Please see Clause 7.7 and Figure 6.
7.10 Each lampholder shall be wired so that the screw shell will be
connected to the conductor intended to be connected to the
grounded conductor of the power-supply circuit.
8 Protection Against Risk of Injury to Persons – Mechanical
Protection
8.1 All moving parts (for example, fan blades, blower wheels,
pulleys, and belts) that, if accidentally contacted, could cause
bodily injury, shall be guarded against accidental contact.
8.2 Openings in external enclosures or guards provided for
compliance with the requirements specified in Clause 8.1 shall
be acceptable if they prevent the probe, illustrated in Figure 7,
from making contact with moving parts. The probe shall be
inserted at any angle and with a force of 4.4 N (1 lbf).
Exception: Openings of 25.4 mm (1 in) or larger shall be
guarded such that the distance from an opening to the moving
part is in accordance with Table 3.
8.3 An interlocking mechanism that operates to disconnect power
to the drive motor when a cover or panel is removed or opened
to provide access to moving parts is considered to provide the
protection required by Clause 8.1.
8.4 An enclosure or guard over a rotating member, such as a fan
blade, shall retain a part that, because of breakage or other
reason, might become loose or separate from a rotating part,
and shall retain foreign objects that might be struck and
propelled by the rotating member.
8.5 A guard or portion of an enclosure acting as a guard for a part
presenting a risk of injury to persons shall be:
a) Mounted to the assembly so that the part cannot be
operated with a guard removed;
b) Secured to the assembly using fasteners requiring a tool
for removal; or
Page 11 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
N/A
N/A
P
P
by probe
P
P
N/A
No lampholder N/A
P
P
P
N/A
No such device N/A
P
P
N/A
P
www.tuv.com
Page 12 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
c) Provided with interlocks to protect against access.
N/A
Perforated sheet steel or expanded steel mesh used to cover
openings shall give equivalent mechanical strength to that of a
blank sheet of the thickness that will be required when
determining compliance with Table 1.
8.6 A fan blade of conventional construction shall be acceptably
P
guarded if:
a) The relationship between the weight (W) of the fan blades
N/A
and hub in kilograms, the radius ® in millimeters, and the
speed (N) in revolutions per minute is such that K in the
formula
is less than 29,032; and N/A
b) The guarding is such that the probe illustrated in Figure 7
P
cannot touch the leading edge of the blade and hub when
inserted with a force of 4.4 N (1 lbf) through any opening in the
guard. For a reversible fan, both edges are leading edges.
9 Protection Against Risk of Injury to Persons – Materials P
9.1 When breakage of materials used for the enclosure, frame,
P
guard, or the like might result in a risk of injury, the materials
shall have such properties that meet the demands of expected
loading conditions. See Impact, Clause 59.
10 Protection Against Risk of Injury to Persons – Switches,
P
Controls, and Interlocks
10.1 A device that automatically starts a product, such as a timer,
No such device P
an automatically reset overload-protective device, or the like,
shall not be employed if such a device and its operations can
cause or result in injury to persons.
10.2 The requirement in Clause 10.1 shall necessitate the use of an
N/A
interlock if moving parts or the like would result in a risk of
injury to persons upon the automatic starting or restarting of a
motor. A product shall be constructed so as to reduce the
likelihood of unintentional operation of any such part.
10.3 Each function of a multiple-function product shall be taken into
N/A
consideration in determining compliance with Clause 10.2.
10.4 If unintentional operation of a switch can result in a risk of
N/A
injury to persons, the actuator of the switch shall be located or
guarded so that such operation is unlikely. The actuator of
such a switch may be guarded by recessing, use of ribs,
barriers, or the like.
10.5 A risk of injury to persons shall not result when a product that
No such switch N/A
is provided with a switch that can be locked in the “on” position
is connected to the electrical source of supply when the
product is in an at-rest position and the switch is in the “on”
position.
10.6 The “off” position of a switch other than a momentary-contact
N/A
type shall be such that the operator can determine by visual
inspection that the product is off.
10.7 An interlock provided to reduce the risk of electric shock shall
N/A
be constructed and installed so that it is reliable and complies
with the requirements in Clause 10.8 or 10.9.
10.8 An interlock shall be such that it cannot be defeated readily: No interlock switch used N/A
a) Without damaging the product; N/A
b) Without making a connection or alteration to the wiring; N/A
c) Without a tool; or N/A
means shall be positioned so as to result in the least stability. If
distributed evenly between the handles so that each handle will
www.tuv.com
Page 13 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
d) With a material that is commonly available, such as
N/A
adhesive tape, string, and a conventional extension cord set.
10.9 A product having an interlock to reduce the risk of electric
N/A
shock that does not comply with the requirements in Clause
10.8 shall be marked as specified in Clause 75.25, and during
intended operation and user servicing of the product:
a) The interlock shall not be likely to be defeated by
N/A
improper disassembly, for example, removal of the wrong
screws during removal of the cover;
b) The cover in which the interlock is mounted shall not
N/A
rotate by its own weight during any stage of its removal or
replacement, if such rotation gives access to a live part, or
damages the interlock or the cover;
c) The act of removal or replacement of the interlocked
N/A
cover shall not subject the user to unintentional contact with
live parts; and
d) Misapplication of the interlocked cover shall not result in a
N/A
risk of electric shock unless such misapplication is obvious
during and after replacement of the cover.
11 Protection Against Risk of Injury to Persons – Surface
P
Temperatures
11.1 During the Normal-Temperature Test, Clause 57, the
Test complied P
temperature of a surface that may be contacted by the user
shall not exceed the applicable value specified in Table 4. If
the test is conducted at a room temperature other than 25°C
(77°F), the results are to be corrected to that temperature.
12 Stability P
12.1 A portable product shall not overturn when positioned in its
P
most unstable condition, with or without water, and tipped
through an angle of 10 degrees from the horizontal.
12.2 The product shall be levelled on a horizontal surface. The side
P
of the product that will result in the most severe test shall be
raised until the product is tipped through an angle of 10
degrees. For the test, casters, wheels, and other supporting
adjustable feet are provided, they shall be adjusted to the
same height. The product shall be blocked to prevent sliding
during the test.
13 Strength of Handles N/A
13.1 A handle used to support or carry a product shall withstand a
force equal to four times the weight of the product when filled
with water without breakage or damage to the handle, its
securing means, or that portion of the enclosure to which it is
attached, for a period of 1 minute. The load shall be uniformly
applied over a 76 mm (3 in) width at the center of the handle,
without clamping. The load shall be gradually applied so that
the total test load will be reached in 5 – 10 seconds.
13.2 If more than one handle is furnished, the force shall be
carry a load proportional to the load it would carry when the
product is lifted by the handles. If the product has more than
one handle, but can be carried by only one handle at a time,
each handle shall support the entire test load.
No handle N/A
N/A
s installation instructions, using the hardware and
the product, or the product itself plus three times its own weight
15 Mechanical Assembly
P
www.tuv.com
Clause Requirement Test Result - Remark Verdict
14 Strength of Mounting
14.1 The mounting means of a product intended for wall or ceiling
mounting shall withstand a force equal to four times the weight
of the product without breakage of or damage to the mounting
means, its securing means, and that portion of the product to
which it is attached. Results shall be acceptable if the product
and mounting systems remain in place with no evidence of
damage or permanent distortion.
14.2 The product shall be mounted in accordance with the
manufacturer’
construction as described. The force – four times the weight of
– shall be applied through a 76 mm (3 in) wide strap at the
dimensional center of the product and shall be increased in a 5
– 10 second interval until a load equal to the weight of the
product plus three times its weight, but not less than 4.5 kg (10
lbs), is applied to the mounting system. The load shall be
sustained for 1 min.
14.3 With reference to Clause 14.2, if no wall constructions are
specified, 3/8-inch trade size plaster board (dry wall, gypsum
board) on nominal 2 by 4 inch wood studs spaced on 406 mm
(16 in) centers shall be used as the support surface. The
hardware shall be applied as specified in the instructions, and
if not otherwise indicated, the securing screws shall be
positioned between the studs and secured into the
plasterboard. An adjustable product shall be adjusted to the
position that will give the maximum projection from the wall.
Page 14 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
Portable product
N/A
N/A
N/A
N/A
15.1 A product shall be assembled in accordance with the
requirements of this Clause so that it will not be adversely
affected by the vibration of intended operation.
15.2 A switch, a lampholder, an attachment-plug receptacle, a
motor-attachment plug, or similar component shall be securely
mounted and shall be prevented from shifting or turning.
Exception No. 1: A switch need not be prevented from turning
if all four of the following conditions are met:
a) The switch is of a plunger or other type that does not tend
to rotate when operated. A toggle switch is considered to be
subject to forces that tend to rotate the switch during intended
operation of the switch;
b) Means for mounting the switch make it unlikely that
operation of the switch will loosen it;
c) Spacings are not reduced below the minimum acceptable
values if the switch rotates; and
d) Intended operation of the switch is by mechanical means
rather than by direct contact by persons.
Exception No. 2: A lampholder of the type in which the lamp
cannot be replaced, such as a neon pilot or indicator light in
which the lamp is sealed in by a nonremovable jewel, need not
be prevented from turning if rotation cannot reduce spacings
below the minimum acceptable values.
15.3 Means for preventing the rotation mentioned in Clause 15.2
shall consist of more than friction between surfaces; for
example, a lock washer may be used to prevent turning of a
small stem-mounted switch or other device having a singlehole mounting means.
P
No such part N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
www.tuv.com
Page 15 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
15.4 Uninsulated live parts and wiring shall be kept away from
P
moving parts such as relays and contactors by clamping,
routing, or equivalent means that will provide permanent
separation.
15.5 An uninsulated live part, including a terminal, shall be secured
P
to the supporting surface by a method other than friction
between surfaces so that it will not be likely to turn or shift in
position if such motion may result in the reduction of spacings
below the minimum acceptable values. The security of contact
assemblies shall be such that their continued alignment will be
maintained.
15.6 Friction between surfaces shall not be the sole means of
N/A
reducing the likelihood of shifting or turning of live parts, but a
lock washer shall be acceptable.
15.7 An uninsulated live part, including a terminal, shall be secured
P
to the supporting surface by method other than friction
between surfaces so that it will not be likely ot turn or shift in
position if such motion ay result in the reduction of spacings
below the minimum acceptables values. The security of
contact assemblies shall be such that their continued
alignment is maintained.
15.8 Friction between surfaces shall not be the sole means of
N/A
reducting the likelihood of shifting or turning of live parts, but a
lock washer shall be acceptable.
16 Liquid-Containing Parts N/A
16.1 If the deterioration or breakage of any part that contains,
N/A
conducts, or otherwise contacts a liquid can result in a risk of
fire, electric shock, or injury to persons, the part shall be
resistant to the liquid under all conditions of use. See LiquidContainer Test, Clause 68.
Exception: Gaskets employed to: N/A
a) Prevent water entry into an electrical compartment, or N/A
b) Prevent hot water leakage external to the product, N/A
are not required to comply with the test of Clause 68 when the
N/A
gasket is normally dry during operation and complies with the
requirements of Gasket Test, Clause 67.
16.2 In addition to complying with Clause 16.1, a polymeric material
Not such appliance N/A
used to support electrodes in liquid-containing cylinders shall
be subjected to the tests specified in (a) to (e):
a) A flammability test in accordance with the method for HB
N/A
materials in the Standard for Tests for Flammability of Plastic
Materials for Parts in Devices and Appliances, UL 94, and HB
materials in the CSA Standard for Evaluation of Properties of
Polymeric Materials, CAN/CSA-C22.2 No 0.17;
b) A mold stress relief test, as specified in Clause 73; N/A
c) High-voltage-arc tracking, in accordance with the
N/A
requirements in the Standard for Polymeric Materials - Use in
Electrical Equipment Evaluations, UL 746C, and CAN/CSAC22.2 No. 0.17;
Exception: This test need not be conducted if a 12.7 mm (1/2
P
in) spacing is provided between live parts.
d) Comparative tracking index (CTI) under moist conditions,
P
in accordance with the requirements in UL 746C, and
CAN/CSA-C22.2 No. 0.17. The CTI value shall be a minimum
of 100 V;
18 Cord
-
Connected Products
P
mounted humidifiers may
19 Permanently Connected Products
N/A
www.tuv.com
Page 16 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
e) Relative thermal index (RTI), in accordance with the
P
requirements in UL 746C and CAN/CSA-C22.2 No. 0.17. The
material shall not exceed the general use temperature for
required properties.
17 Protection Against Corrosion N/A
17.1 If corrosion of a part may result in a risk of fire, electric shock,
No such part N/A
or injury to persons, such a part shall be plated, painted, or the
equivalent. Phosphate treatment with an oil or wax coating
may be used for protecting magnets and armatures. Oil
treatment may be used for steel springs. Stainless steel shall
be acceptable without additional protection if it is polished or
treated when necessary.
17.2 Metals shall be used in combinations that are galvanically
N/A
compatible if galvanic action may adversely affect any cabinet,
enclosure, or other parts.
17.3 Each hinge and other attachment shall be resistant to
N/A
corrosion.
18.1 Equipment other than plenum or duct-
P
be cord connected if:
a) The voltage rating does not exceed 250 V; See rating label P
b) It will start and operate as intended from a circuit with a
N/A
30 A overcurrent protection (see Starting Test, Clause 55); or
c) The marked rating does not exceed 24 A. P
18.2 Plenum or duct-mounted humidifiers may be cord connected if: N/A
a) The voltage rating does not exceed 150 V; N/A
b) The current rating does not exceed 12 A; N/A
c) A branch circuit overcurrent protection of not more than
N/A
15 A is required for satisfactory starting and operating; and
d) The design does not require that field wiring connections
N/A
operating at above 30 V shall be made at the time of
installation to a furnace control or to a control for the humidifier.
Cord connected product
19.1 A product intended for permanent connection to the power-
N/A
supply circuit shall have provision for connection of one of the
wiring systems acceptable for the product, in accordance with
the National Electrical Code, ANSI/NFPA 70, and the
Canadian Electrical Code, Part I, C22.1.
the supply is attached shall be such that supply conductors can
www.tuv.com
Page 17 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
19.2 Equipment shall have provision for the connection of conduit or
N/A
conduits of a size suitable for the supply circuit conductors
needed to connect the unit in accordance with Table 2,
Allowable Ampacities for Not More Than 3 Copper Conductors
in Raceway or Cable, and Table 4, Allowable Ampacities for
Not More Than 3 Aluminum Conductors in Raceway or Cable,
in the Canadian Electrical Code, Part I, C22.1, and Table 31016, Allowable Ampacities of Insulated Conductors Rated 0
through 2000 Volts, 60°C through 90°C (140°F through 194°F)
Not More Than Three Current-Carrying Conductors in
Raceway, Cable, or Earth (Directly Buried) Based on Ambient
Temperatures of 30°C (86°F), in the National Electric Code,
ANSI/NFPA 70, basing the minimum conductor size on 125
percent of the rated current of the product. Please see Tables
5 and 6 for further information. It is assumed that aluminum
conductors may be used, unless the product is marked in
accordance with Clause 78.2.
19.3 A metal plate to which conduit is to be attached in the field
N/A
shall be not less than 0.78 mm (0.0307 in) thick if uncoated
steel, not less than 0.88 mm (0.0346 in) thick if galvanized
steel, and not less than 1.14 mm (0.045 in) thick if nonferrous
metal.
19.4 A knockout shall be provided with a flat surrounding surface for
N/A
seating of a conduit bushing, and shall be located so that
installation of a bushing at any knockout likely to be used
during installation will not result in spacings between
uninsulated live parts and the bushing of less than those
required by Clause 42, Spacings.
19.5 A single field wiring opening may be provided for hazardous
N/A
voltage and extra-low-voltage field supply circuits, and the
construction of the equipment at the point where the conduit of
be installed in compliance with the requirements of Clause 29,
Separation of Circuits.
19.6 Equipment which incorporates more than one independent
N/A
internal circuit, and is designed for connection to more than
one source of electrical power supply, shall have each internal
circuit provided with means for connection to the supply, and
shall be marked in accordance with Clause 75.29.
19.7 An outlet or terminal box in which connections to the power
N/A
supply circuit will be made shall be located so that, after the
product has been installed as intended, such connections will
be readily accessible for inspection.
19.8 No electrical components shall be mounted on a part such as
N/A
the cover of a wiring terminal compartment that must be
removed to make or inspect field-wiring connections.
19.9 The space provided at terminals or leads intended for the
N/A
connection of supply conductors, or other conductors to be
connected at the time of installation, shall be sufficient for
acceptable installation as defined in Clause 19.10, including
the accommodation of the necessary splices.
19.10 An acceptable installation shall: N/A
a) Be possible using ordinary tools suitable for the
N/A
installation; and
b) Not require installed conductors to be forced into contact
N/A
with uninsulated live parts, or with noncurrent-carrying parts
likely to be grounded.
www.tuv.com
Page 18 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
A trial installation may be performed to determine compliance
N/A
with these requirements.
19.11 The wiring terminal compartment shall incorporate suitable
N/A
means for the connection thereto of a grounding conductor.
19.12 A terminal compartment that is intended for the connection of a
N/A
power-supply raceway and that is mounted integrally with the
product shall be attached so as to be prevented from turning
with respect to the product.
19.13 Wiring space or other compartments intended to enclose wires
N/A
shall be free of any sharp edge, burr, fin, moving part, or the
like that may damage the conductor insulation.
19.14 If field-wiring connections are to be made to a motor terminal
N/A
compartment, the compartment shall comply with the
requirements in the Standard for Rotating Electrical Machines General Requirements, UL 1004-1, and the CSA Standard for
Motors and Generators, C22.2 No. 100.
20 Leads and Terminals
20.1 A terminal for field adjustment, such as a voltage-tap change
Cord connected product
No such terminal N/A
N/A
terminal, is not considered to be a field-wiring terminal. A wire
intended for connection to a field-adjustment terminal and its
method of connection, such as a pressure-terminal connector,
soldered loop, crimped eyelet, or the like, shall be factory
assembled and provided as part of the product.
20.2 A field-wiring terminal shall be provided with a pressure-
N/A
terminal connector, firmly bolted or held by a screw.
Exception: A wire-binding screw may be employed at a
N/A
terminal intended to accommodate a 5.3 mm2 (10 AWG) or
smaller conductor if upturned lugs or the equivalent are
provided to hold the wire in position.
20.3 A wiring terminal shall accommodate connection of a supply
N/A
conductor having an ampacity of at least 125 percent of the
rated current of the product in accordance with the National
Electrical Code, ANSI/NFPA 70, and the Canadian Electrical
Code, Part I, C22.1.
20.4 Wiring terminals to which supply conductors will be attached in
N/A
the field shall be prevented from turning. The use of
lockwashers shall not be considered an effective way to
prevent turning of terminals.
20.5 A wire-binding screw shall thread into metal. No such screw N/A
20.6 A wire-binding screw at a wiring terminal shall not be smaller
N/A
than No. 10.
Exception: A No. 8 screw may be used at a terminal intended
N/A
only for the connection of a 2.1 mm2 (14 AWG) or smaller
conductor, and a No. 6 screw may be used at a terminal
intended for connection of a 1.3 or 0.82 mm2 (16 or 18 AWG)
conductor only.
20.7 2.1 mm2 (14 AWG) is the smallest size of conductor that shall
N/A
be used for branch-circuit wiring, and thus is the smallest
conductor that is to be anticipated at a terminal for connection
of a branch-circuit conductor.
20.8 The terminals of a control may be employed for the connection
N/A
of supply-circuit conductors provided that they comply with
Clause 20.6.
A lead shall not be more than two AWG wire sizes smaller than
conductors, in accordance with the marking required by Clause
supply conductor and employing a lampholder
www.tuv.com
Page 19 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
20.9 A terminal plate tapped for a wire-binding screw shall be of
N/A
metal at least 0.76 mm (0.030 in) thick. There shall be two or
more full threads in the metal, which may be extruded if
necessary to provide the threads.
20.10 A wire connector may thread into a terminal plate if the threads
N/A
are not stripped by applications of the torque specified in Table
7 to the wire connector.
20.11 Upturned lugs or a copper washer shall be capable of retaining
N/A
a supply conductor under the head of the screw or washer
when the supply conductor is sized for the ampacity indicated
in Clause 20.3.
20.12 If leads are provided instead of terminals for connection to
Attachment plug provided N/A
supply circuit conductors, they shall not be more than two
AWG wire sizes smaller than the copper supply conductors to
which they are to be connected, but not smaller than 0.82 mm
2
(18 AWG), nor less than 152 mm (6 in) in length.
Exception: The lead may be less than 152 mm long if it is
N/A
evident that the use of a longer lead may result in a risk of fire
or electric shock.
20.13
N/A
a copper supply conductor to which it is to be connected.
20.14 It shall be assumed that wire having the specified temperature
N/A
rating will be installed for the power-supply conductors to a
product marked in accordance with Clause 78.1. Otherwise, it
shall be assumed that 75°C (167°F) wire will be used.
20.15 Field-wiring terminals shall be acceptable for copper supply
N/A
conductors or for either aluminum or copper supply
78.2.
20.16 The distance between a pressure terminal connector intended
for field wiring and the wall of an enclosure toward which the
conductor is directed or through which the conductor may pass
shall be as specified in Table 8.
Exception: Spacings may be less where a wall or other
obstruction lies outside the area occupied by a conductor that
is bent or deflected to a radius not less than the distance
specified in Table 8.
20.17 A permanently connected product intended for connection to a
grounded powerof the screw-shell type, a single-pole switch, or a single-pole
automatic control shall have one terminal or lead identified for
the connection of the grounded conductor of the supply circuit.
The identified terminal or lead shall be connected to the screw
shell of each lampholder and shall not be connected to any
single-pole switch or single-pole overcurrent protective device
other than automatic controls without a marked "off" position.
20.18 A terminal intended for the connection of a grounded powersupply conductor shall be made of, or plated with, a metal that
is substantially white in color, or be identified by the word
"white" or the letter "W" marked next to the terminal. The
terminal shall be readily distinguishable from the other
terminals, or proper identification of the terminal shall be
clearly shown in some other manner, such as on an attached
wiring diagram.
20.19 A lead intended to be connected to a grounded power-supply
conductor shall be finished to show a white or gray color, and
shall be readily distinguishable from the other leads.
N/A
N/A
N/A
N/A
N/A
The flexible cord shall have a voltage rating of not less than the
The flexible cord shall be of a type as specified in Table 9, or of
www.tuv.com
Clause Requirement Test Result - Remark Verdict
21 Flexible Cords P
21.1 A cord-connected product shall be provided with a flexible
cord, 1.5 - 3.0 m (5 - 10 ft) long, and an attachment plug cap,
for connection to the power-supply circuit.
21.2
rated voltage of the product, and it shall have an ampacity not
less than the current rating of the product marked as specified
in Clause 74.1.
21.3 The flexible cord may be attached to the product permanently,
or it may be in the form of a separate cord set with means for
connection to the product. If the latter construction is used, the
product shall not be provided with terminal pins that will
accommodate a standard flatiron or appliance plug.
21.4
a type equally serviceable for the application.
21.5 An attachment plug shall have a current rating of not less than
125 percent of the rated current of the product and a voltage
rating equal to the rated voltage of the product. If the product is
adaptable for use on two or more different values of voltage by
field alteration of internal connections, the attachment plug
provided shall be acceptable for the voltage for which the
product is connected when shipped from the factory.
21.6 If the equipment is intended to be grounded as specified in
Grounding, General, Clause 31.1, the supply cord shall have
an additional conductor for grounding purposes that is:
a) Colored green or green/yellow; N/A
b) Terminated in a grounding pin or blade in the attachment-
plug; and
c) Connected to the equipment so that it will comply with
Clause 31.1.
21.7 A cord-connected product that employs an Edison-base
lampholder or a manually operated single-pole switch shall be
provided with a polarized or grounding type attachment plug.
21.8 If a switching device or a pilot device that controls a switch
operates to interrupt the main supply circuit, it shall, when
open, disconnect all ungrounded power-supply conductors.
21.9 The attachment plug of the power supply cord of an appliance
provided with a 15- or 20-ampere general-use convenience
receptacle shall be of the 3-wire grounding type. The
attachment plug of the power supply cord of an appliance
provided with either a manually operated, line-connected,
single pole switch for appliance on-off operation, or an Edisonbase lampholder shall be of the polarized or grounding type.
21.10 When a 3-wire grounding-type attachment plug or a 2-wire
polarized attachment plug is provided, the attachment plug
connections shall comply with Figure 8, and the polarity
identification of the flexible cord shall comply with Table 10.
21.11 The conductor of the power supply cord that is intended to be
grounded shall have the screw shell of an Edison-base
lampholder and the terminal or lead receptacle intended to be
grounded connected to it. Table 10 identifies the supply cord
conductor intended to be grounded.
22 Strain Relief P
Page 20 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
P
P
Permanently attached P
P
P
No grouding N/A
N/A
N/A
No lampholder used N/A
N/A
No general-use
convenience receptacle
N/A
N/A
N/A
construction is such that the cord may be subjected to stress or
www.tuv.com
Page 21 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
22.1 Strain relief shall be provided so that a mechanical stress on a
P
flexible cord will not be transmitted to terminals, splices, or
internal wiring. See Strain-Relief Test, Clause 62.
22.2 A metal strain-relief clamp or band without auxiliary protection
No such device N/A
shall be acceptable with a Type SJ, SJO, SJT, SJTO, S, SO,
ST, or STO cord. A metal strain-relief clamp or band shall be
acceptable with Type SP-2 or lighter duty rubber-insulated
cord, and Type SPT-2 cord, only if auxiliary nonconducting
mechanical protection is provided over the cord.
22.3 Unless previously investigated and found to be acceptable, a
No clamp used P
clamp of any material shall not be acceptable for use on a
Type SPT-2 or SVT flexible cord. For a heavier duty
thermoplastic-insulated cord, a clamp may be used; in such
cases auxiliary insulation shall not be required unless it is
judged that the clamp may damage the cord insulation.
Exception: A clamp may be used on a Type SPT-2 or SVT
N/A
cord if protected by varnished cloth tubing, phenolic material,
vulcanized fiber material, or the equivalent under the clamp,
subject to the investigation described in the Cable-Clamp Test,
Clause 64.
22.4 If a knot in a supply cord serves as strain relief, it shall not be
Bushing used N/A
made in the conductors from which a jacket has been stripped,
and the surface against which the knot may bear or with which
it may come into contact shall be free from burrs, projections,
and sharp edges.
22.5 Means shall be provided to reduce the risk that the flexible
P
cord could be pushed into the product through the cord-entry
hole when such displacement:
a) Damages the cord; P
b) Exposes the cord to a temperature higher than that for
P
which it is rated; or
c) Reduces spacings, such as to a metal strain-relief clamp,
P
below the minimum values in 42.2.
See Power-Supply Cord Push-Back Relief Test, Section 63. P
23 Bushings P
23.1 Where a flexible cord passes through an opening in a wall,
Bushing used P
barrier, or enclosure, there shall be a bushing or the equivalent
that is reliably secured in place. This bushing shall be provided
with a smooth, rounded surface against which the cord may
bear. If the cord is Type SP-2 or SPT-2 or other type lighter
than SVT, if the wall or barrier is of metal, and if the
motion, an insulating bushing shall be provided.
23.2 Ceramic materials and some molded compositions are
generally acceptable for insulating bushings but separate
bushings of wood or hot-molded shellac-and-tar compositions
shall not be acceptable.
23.3 A vulcanized fiber bushing no thinner than 1.2 mm (3/64 in),
formed and secured in place so that it will not be adversely
affected by conditions of moisture, may be employed.
23.4 A separate soft-rubber, neoprene, or polyvinyl chloride bushing
may be employed in the frame of a motor or in the enclosure of
a capacitor attached to a motor, but not elsewhere in the
product, provided the bushing is:
a) Not less than 1.2 mm (3/64 in) thick; N/A
N/A
N/A
No such part N/A
respect to exposure to oil, grease, moisture, or other conditions
www.tuv.com
Clause Requirement Test Result - Remark Verdict
b) Mounted in a hole that is smooth and free from sharp
edges; and
c) Located so that it will not be exposed to oil, grease, oily
vapor, or other substances having a harmful effect on the
compound used (unless of an oil-resistant compound).
23.5 A bushing of any of the materials mentioned above may be
employed at any point in a product if used in conjunction with a
type of cord for which an insulating bushing is not required.
23.6 A bushing of the same material as the cord insulation and
molded integrally with the cord shall be acceptable on a Type
SP-2 or heavier cord if the built-up section is not less than 1.6
mm (1/16 in) thick at the point where the cord passes through
the hole.
23.67 An insulated metal grommet shall be acceptable in place of an
insulating bushing, provided the insulating material is not less
than 0.8 mm (1/32 in) thick and completely fills the space
between the metal of the grommet and the metal in which it is
mounted.
24 Current-Carrying Parts P
24.1 Metal employed as a current-carrying part shall be silver,
copper, copper alloy, or other material acceptable for the
application.
24.2 Iron or steel, if provided with a corrosion-resistant coating, may
be used for current-carrying parts within a motor or associated
governor, but not elsewhere in a product.
Exception: Iron or steel may be used for current-carrying parts
within a component, provided it complies with the requirements
for such a component. See General, Components, Clause 3.1.
25 Internal Wiring P
25.1 The internal wiring of a product shall be acceptable for the
application when considered with respect to the temperature
and voltage to which it is likely to be subjected, and with
Page 22 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
N/A
N/A
N/A
N/A
No such part N/A
P
N/A
N/A
P
of anticipated service.
25.2 Wiring that is routed in the equipment so as to be semiexposed shall have an insulation thickness of not less than
0.79 mm (1/32 in) (nominal) of thermoplastic material.
25.3 Wiring that is routed in the equipment so as to be enclosed
shall have an insulation thickness of not less than:
a) 0.40 mm (1/64 in) (nominal), if of thermoplastic material P
b) 0.79 mm (1/32 in) (nominal), if of rubber or neoprene
material.
25.4 Parallel-conductor appliance wiring shall not be separated into
single conductors for a length greater than 75 mm (3 in) unless
the insulation of the separated wiring has a thickness of 0.7
mm (0.028 in) (nominal) or greater.
25.5 Except as specified in Clause 25.6 and 25.7, conductors shall
have an ampacity acceptable for the particular application and
in accordance with the following:
a) For cord-connected equipment, not less than one-third of
the required ampacity of the power supply cord; or
b) For permanently connected equipment, not less than one-
third of the required ampacity of the branch circuit conductors.
P
P
N/A
No such wire N/A
N/A
N/A
N/A
27 Wiring Connections
P
www.tuv.com
Page 23 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
Note 1: This requirement does not apply to conductors that are
N/A
18 AWG or larger, not more than 1.2 m (4 ft) in length and
provided with overcurrent protection in the equipment at the
point where the smaller conductor receives its supply.
Note 2: This requirement does not apply to conductors that are
N/A
connected between two fixed impedances that reduce the risk
of a high fault current within the conductors (e.g., a conductor
extending between a motor-running capacitor and the startwinding of a permanent split capacitor motor)
Note 3: This requirement does not apply to conductors that are
N/A
a jumper lead between controls and are not longer than 76 mm
(3 in), unless the conductor is located in a control panel.
25.6 For wiring of extra-low voltage circuits, other than safety
P
circuits such as temperature-limiting circuits, the conductor
size is not specified.
25.7 Wiring with 20 AWG conductors shall be acceptable when
N/A
employed as integral leads of components such as
lampholders and solenoids that are rated 60 VA or less.
26 Protection of Wiring P
26.1 The wiring and connections between parts of a product shall
P
be protected or enclosed.
Exception: If flexibility is essential, a flexible cord may be used
N/A
for external interconnection.
26.2 With respect to the requirement in Clause 26.1, wiring shall be
P
considered to be protected or enclosed if it is secured or
located so that it is not likely to be grasped or hooked in such a
manner that it or related electrical connections could be
subjected to undue stress, even though it can be touched by
the probe illustrated in Figure 7. A filter and other parts that are
likely to be removed and replaced during user servicing shall
be removed when the exposure of internal wiring is being
judged.
26.3 Wiring space or other compartments intended to enclose wires
P
shall be free of any sharp edge, burr, fin, moving part, or the
like that can damage the conductor insulation. Wiring in a
factory-wired enclosure, compartment, raceway, or the like
shall be located or protected to reduce the likelihood of contact
with any sharp edge, burr, fin, moving part, or the like that
could damage the conductor insulation.
26.4 A hole through which insulated wires pass in a sheet-metal
No such hole N/A
wall within the overall enclosure of a product shall be provided
with a smooth, rounded bushing or shall have a smooth,
rounded surface upon which the wires may bear to reduce the
likelihood of abrasion of the insulation. A flexible cord used for
external interconnection as described in Clause 26.1 shall be
provided with a bushing and strain relief.
26.5 Insulated wires may be bunched and passed through a single
No such hole N/A
opening in a metal wall within the enclosure of the product.
26.6 Where routine maintenance operations require the removal or
No such operation required N/A
displacement of a part of an assembly to which internal or
interconnecting wiring is attached, the construction shall be
such that the action of removal or displacement shall not result
in damage to the conductors or insulation in the equipment.
lugs, crimped eyelets, soldering all strands of the wire together,
separation from insulated or uninsulated live parts of a different
www.tuv.com
Page 24 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
27.1 If breaking or loosening of an electrical connection could result
P
in a risk of fire or electric shock, it shall be soldered, welded, or
otherwise securely connected. A soldered joint shall be
mechanically secured before soldering.
27.2 The means of connecting stranded internal wiring to a wire-
N/A
binding screw shall be such that loose strands of wire cannot
contact a non-current-carrying metal part or another live part
not always of the same polarity as the wire. This may be
accomplished by use of pressure wire connectors, soldering
or by other equivalent means.
27.3 An internal connection that must be made in the field on a
Not such appliance N/A
cord-connected product that is shipped partially disassembled
shall be by a plug-and-receptacle connector.
27.4 An internal connection that must be made in the field on a
Not such appliance N/A
product intended for permanent connection to the power
supply and shipped partially disassembled shall be made by a
plug-and-receptacle connector, or in accordance with the
relevant requirements of Permanently Connected Products,
Clause 19.
28 Electrical Insulation P
28.1 Material for the mounting of uninsulated hazardous voltage
P
parts shall be heat-resistant, absorption-resistant insulating
material that is suitable for its particular application, and that
will withstand the most severe conditions likely to be
encountered in service. Such materials include porcelain,
phenolic composition, cold-molded composition, or a material
having equivalent electrical and physical properties.
28.2 The acceptability of insulating materials shall include
P
consideration of the following:
a) Mechanical strength; P
b) Dielectric strength; P
c) Insulation resistance; P
d) Heat- and moisture-resistant properties; P
e) The degree of enclosure or protection; and P
f) Other factors that might have a bearing on the risk of fire
P
or electric shock under conditions of intended use.
29 Separation of Circuits P
29.1 Unless having insulation suitable for the highest voltage
P
involved, insulated conductors of different circuits (internal
wiring, including wires in a junction box or compartment) shall
be separated by barriers, or shall be segregated, and shall, in
any case, be separated or segregated from uninsulated live
parts connected to circuits of different voltages. Segregation of
insulated conductors may be accomplished by clamping,
routing, or equivalent means that ensures permanent
circuit.
29.2 There shall be provision for segregating or separating by
barriers, field installed conductors of any circuit from field
installed and factory installed conductors connected to any
other circuit, unless the conductors of both circuits are or will
be insulated for the maximum voltage of either circuit.
No field installed wiring N/A
conductors of different circuits by locating field wiring openings,
installed conductors of a hazardous voltage circuit
limiting device, motor overload protective device,
www.tuv.com
Page 25 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
29.3 Within a compartment that is not a control enclosure junction
No such compartment N/A
box or its equivalent, field-installed extra-low-voltage circuit
conductors may be segregated from factory-installed
routing factory wiring, and locating electrical components so
that the factory conductors are maintained at least 127 mm (5
in) from a line representing intended routing of the extra-lowvoltage conductors. The line shall allow for droop, and shall
connect the opening provided for entrance of the extra-lowvoltage conductors to the terminals or leads to which the
conductors are attached.
29.4 There shall be provision for segregating or separating by
N/A
barriers fieldfrom:
a) Uninsulated live parts connected to a different circuit,
N/A
other than wiring terminals; and
b) Any uninsulated live parts of electrical components such
N/A
as a pressureor other protective device where short circuiting or grounding
may result in unsafe operation of the equipment; except at
wiring terminals.
29.5 There shall be provision for segregating or separating by
N/A
barriers, field-installed conductors of an extra-low-voltage
circuit from:
a) Uninsulated live hazardous voltage circuits; and N/A
b) Wiring terminals and any other uninsulated live parts of
N/A
hazardous voltage electrical components such as a pressurelimiting device, motor overload protective device, or other
protective device where short circuiting or grounding may
result in unsafe operation of the unit.
29.6 The barrier may be removable or have openings for the
N/A
passage of conductors, provided that instructions for the use of
the barrier are a permanent part of the device. Please see
Clause 78.4. In lieu of a barrier, complete instructions may be
provided that, when used in conjunction with the wiring
diagram, will provide for the separation of the circuits of
different voltages.
29.7 Segregation of field-installed conductors from other field-
No such wire N/A
installed conductors and from uninsulated live parts that are
connected to different circuits may be accomplished by
arranging the location of the openings in the enclosure for the
various conductors so that there is no likelihood of the
intermingling of the conductors of parts of different circuits. If
the number of openings in the enclosure:
a) Equals the minimum required for the proper wiring of the
N/A
product, and if each such opening is located opposite a set of
terminals, it shall be assumed that the conductors entering an
opening will be connected to the terminals opposite that
opening;
b) Exceeds the minimum number of openings required for
N/A
proper wiring, the possibility of conductors entering at points
other than opposite the terminals to which they are intended to
be connected and contacting an insulated conductor or
uninsulated live part of a different circuit shall be investigated.
wired, the circuits involved shall be segregated or separated by
www.tuv.com
Page 26 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
29.8 To determine whether a product complies with the requirement
N/A
in Clause 29.7, the product shall be wired as it would be in
service, and in doing so, a reasonable amount of slack shall be
left in each conductor within the enclosure, and no more than
average care shall be used in stowing this slack in the wiring
compartment.
29.9 A barrier used to comply with the requirements in Clauses
No barrier N/A
29.1, 29.2, 29.5, and 29.6 shall:
a) Be of metal not thinner than the enclosure metal, as
N/A
specified in Table 1 or of an insulating material not less than
0.77 mm (0.03 in) thick. Insulating materials used as barriers
shall be thicker if deformation that would defeat the purpose of
the barrier could be readily accomplished;
b) Be securely held in place; and N/A
c) If exposed or otherwise likely to be subjected to
N/A
mechanical abuse, have the necessary mechanical strength.
29.10 Openings in a barrier for the passage of wires shall not be
N/A
larger in diameter than 6.4 mm (1/4 in), and shall not exceed in
number the total number of conductors that will pass through
the barrier. A closure for an opening shall present a smooth
surface wherever an insulated wire may come in contact with
it, and the area of any such opening, with the closure removed,
shall not be larger than required for the passage of the
necessary wires.
29.11 The output of a transformer supplying a Class 2, extra-low-
N/A
voltage circuit, and provided as part of a product, shall not be
interconnected with the output of another such transformer
device. The output of two or more transformer devices
provided as a part of a product may be interconnected if the
voltage and current measurements at the output terminals are
within the limits for a single Class 2, 30 V rms or less
transformer.
29.12 Class 2, extra-low-voltage circuits supplied by two or more
N/A
transformers provided as part of a transformer shall be treated
as separate circuits. If more than one such circuit is to be field-
barriers in accordance with Clauses 29.3 - 29.6, and the
transformer output terminals or leads of each circuit of each
terminals or leads of each circuit shall be marked to warn that
the separation be maintained.
30 Secondary Circuits P
30.1 General P
30.1.1 Each secondary circuit shall be judged by the requirements for
hazardous-voltage circuits.
Exception: A secondary circuit need not be investigated if: P
a) It is not a circuit that is relied upon to reduce a risk of fire,
electric shock, or injury to persons; and
b) It complies with the requirements for an extra-low-voltage
secondary circuit, as described in Clauses 30.2.1 - 30.2.9.
30.1.2 A wiring compartment or the equivalent for field-wiring
terminals for a secondary circuit shall be separated from a
wiring compartment for other terminals. The use of a barrier or
partition to separate the secondary circuit from the other
terminals shall be acceptable.
P
N/A
P
No such part N/A
potential of 30 V rms (42.4 V peak) or less, and that includes at
power in accordance with Clause 30.2.1, shall not be adversely
www.tuv.com
Clause Requirement Test Result - Remark Verdict
30.1.3 A secondary circuit shall not be connected to the frame of the
product at more than one point.
Exception: A grounding bus of the necessary ampacity that is
used as the return for a secondary circuit may be connected to
the frame at more than one point.
30.1.4 The frame may be used as the return for an extra-low-voltage
circuit.
30.2 Extra-low-voltage circuits P
30.2.1 An extra-low-voltage circuit shall be supplied from: P
a) A Class 2 transformer or N/A
b) An isolating transformer having an open-circuit sinusoidal
least one of the following means, which limit the power
available to the levels specified for Class 2 transformer:
1) A fixed impedance; N/A
2) A noninterchangeable fuse - the largest fuse that fits in
the fuseholder provided - or a marking for fuse replacement
adjacent to the fuseholder in accordance with Clause 75.27;
3) A nonadjustable manually reset circuit protector; or N/A
4) A regulating network. P
30.2.2 With reference to 30.2.1 (b)(1) and (b)(4), if the performance of
a fixed impedance or regulating network may be adversely
affected by the short circuit or open circuit of any single
component in the network, the likelihood of such malfunction
occurring shall be determined by investigation of that
component.
30.2.3 The impedance, the fuse, the protector, or the regulating
network, and the wiring between those items and the isolating
transformer mentioned in Clause 30.2.1 shall be judged as if it
were part of a hazardous-voltage circuit.
30.2.4 A fuse or a circuit protector used to limit the power as specified
in Clause 30.2.1 shall be rated or set at not more than 100/V
Amps, where V is the open-circuit voltage, for a circuit
operating between 20 and 30 V, and at not more than 5.0 A for
a circuit operating at 20 V or less.
30.2.5 An impedance or a regulating network that is used to limit the
current as specified in Clause 30.2.1 shall limit the current
under short-circuit conditions to not more than 8.0 A measured
after 2 minutes.
30.2.6 The performance of a regulating network used to limit the
Page 27 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
N/A
N/A
N/A
P
N/A
P
P
N/A
P
P
affected by either short circuit or open circuit between any two
terminals of any single rectifier, capacitor, transistor, or similar
component in the network.
30.2.7 The wiring in an extra-low-voltage circuit shall be routed away
from the wiring of other circuits or shall be provided with
insulation that is rated for use at the highest of the voltages in
the other circuits.
30.2.8 The wiring in an extra-low-voltage circuit shall be routed away
from the uninsulated live components of other circuits.
30.2.9 Wires and cables that are part of an extra-low-voltage circuit
shall be provided with strain relief if stress on the wire or cable
would cause the internal wiring of the circuits to contact an
uninsulated live part of another circuit.
31 Grounding
P
P
N/A
No grounding
N/A
voltage circuits only, need not
www.tuv.com
Page 28 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
31.1 General
N/A
31.1.1 Each product shall be provided with a means for grounding. N/A
Exception: A portable product that is rated less than 150 V, or
N/A
a product that contains extra-lowhave provision for grounding.
31.1.2 For grounded products, each exposed non-current-carrying
N/A
metal part that may become energized, and each non-currentcarrying metal part within the enclosure that may be exposed
to contact during user-servicing and that may become
energized, shall be electrically connected to:
a) For a permanently connected product, the equipment-
N/A
grounding terminal or lead and
b) For a cord-connected product, the point of connection of
N/A
the grounding conductor of the power-supply cord.
31.1.3 The equipment-grounding terminal or lead shall be connected
N/A
to the frame or enclosure by a positive means, such as by a
bolted or screwed connection. The grounding connection shall
penetrate nonconductive coatings such as paint or vitreous
enamel. The grounding point shall be located so that it is
unlikely that the grounding means will be removed during
normal servicing of the product.
31.2 Permanently connected products
31.2.1 A product intended for permanent electrical connection to the
Cord connected
N/A
N/A
power supply shall have a field-wiring terminal or lead for the
connection of an equipment-grounding conductor.
31.2.2 A wire-binding screw intended for the connection of an
N/A
equipment-grounding conductor shall have a green-colored
head that is hexagonal shaped, slotted, or both, with or without
a secondary means of rotation. A pressure wire connector
intended for connection of such a conductor shall be plainly
identified by marking it "G", "GR", "GND", "Ground",
"Grounding", the grounding symbol (from IEC 60417, Symbol
5019) as illustrated in Figure 8A, or the like, or by a marking on
a wiring diagram provided on the product. The wire-binding
screw or pressure wire connector shall be located so that it is
not likely to be removed during normal servicing of the product.
31.2.3 The surface of an insulated lead intended solely for the
N/A
connection of an equipment-grounding conductor (as noted in
Table 250-122, Minimum Size Equipment Grounding
Conductors for Grounding Raceway and Equipment, of the
National Electrical Code, ANSI/NFPA 70) or equipment
bonding conductor (as noted in Table 16, Minimum Size
Conductors for Bonding Raceways and Equipment, of the
Canadian Electrical Code, Part I, C22.1) shall be green, with or
without one or more yellow stripes, and no other lead shall be
so identified.
31.2.4 A terminal for connection of a product grounding conductor
N/A
shall be capable of securing a conductor of the size specified
in Clause 31.2.6.
31.2.5 A soldering lug, a push-in (screwless) connector, or a quick-
N/A
connect or similar friction-fit connector shall not be used for the
grounding terminal.
screws, handles, and the like, that are located on the outside of
www.tuv.com
Page 29 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
31.2.6 The size of each grounding conductor shall comply with the
N/A
applicable requirements for connection of an equipment
grounding conductor as specified in Table 16, Minimum Size
Conductors for Bonding Raceways and Equipment, of the
Canadian Electrical Code, Part I, C22.1, and Table 250-122,
Minimum Size Equipment Grounding Conductors for
Grounding Raceway and Equipment, of the National Electrical
Code, ANSI/NFPA 70, except that such a conductor need be
no larger than one of the power-supply conductors.
31.3 Cord-connected products N/A
31.3.1 A power-supply cord of a product which is required to be
N/A
grounded, in accordance with Clause 31.1.1, shall include an
equipment-grounding conductor that is green in color, with or
without one or more yellow stripes.
31.3.2 The equipment-grounding conductor of a flexible cord shall be
N/A
connected to the fixed grounding member of an attachment
plug, and shall be connected at its other end, by a screw or
other means not likely to be removed during normal servicing,
to the metal parts required to be grounded. Solder alone shall
not be used for securing the grounding conductor to the
product.
31.3.3 The screw mentioned in Clause 31.3.2 shall be of a corrosion-
N/A
resistant metal, or shall be protected against corrosion. A lock
washer shall be used to reduce the likelihood of the screw
becoming loosened by vibration.
31.4 Bonding of internal parts N/A
31.4.1 On a product required to be grounded, an exposed non-
N/A
current-carrying part that is likely to become energized through
electrical fault shall be bonded to the point of connection of the
field equipment-grounding means.
Exception: The following need not comply with the requirement
N/A
for grounding:
a) Small internal assembly screws or other small fasteners
N/A
such as rivets;
b) Handles for pull-out disconnect switches; N/A
c) Relay and contactor magnets and armatures; N/A
d) Metal parts such as adhesive-attached foil markings,
N/A
the enclosure or cabinet and are isolated from electrical
components or wiring by grounded metal parts so that they are
not likely to become energized, or are separated from wiring
and spaced from uninsulated live parts as if they were
grounded parts;
e) A panel or cover that is insulated from electrical
components and wiring by an insulating barrier of vulcanized
fiber, varnished cloth, phenolic composition, or other moistureresistant material not less than 0.8 mm (1/32 in) thick and
secured in place, or that does not enclose uninsulated live
parts, and wiring is positively separated from the panel or
cover so that it is not likely to become energized; and
f) An isolated metal panel or cover that is separated from
live parts and wiring by grounded or bonded interposing metal,
such that the interposing metal would be subject to the
electrical fault before the isolated metal part in question.
N/A
N/A
for a distance of 102 mm (4 in) shall be considered exposed for
washer
for grounding if a multiple bearing pin type (piano type) hinge is
www.tuv.com
Page 30 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
31.4.2 Guards, baffles, and covers that do not require tools for
N/A
removal shall be removed when determining the exposure to
contact of a part. A part that can be contacted by a
hemispherical-ended 9.5 mm (3/8 in) diameter rod inserted
through an opening in a permanently attached guard or baffle
the purposes of the grounding requirement.
31.4.3 Uninsulated metal parts of a cabinet, electrical enclosure,
N/A
cover, motor frame, mounting bracket, controller mounting
frame and bracket, capacitor, and other electrical components,
interconnecting tubing and piping, valve, plumbing accessory,
and the like shall be electrically bonded together if they may be
contacted by the user or service personnel.
31.4.4 Operations or adjustments that are considered as subjecting
N/A
parts to contact by users shall include those made at the time
of installation or during intended use - including seasonal
adjustments - and operations such as cleaning or replacing a
filter, relamping, replacing a fuse, resetting overload devices,
or oiling motors. These procedures and those specified in
Protection of Service Personnel, Clause 48, shall also be
considered as subjecting parts to contact by service personnel.
31.4.5 A part on the back side of a component mounting panel or a
N/A
part located so as to require major disassembly by using tools
shall not be considered to be exposed to contact by the user,
and such a part shall not be considered exposed to service
personnel unless it is likely that servicing will be done with the
product energized after such disassembly has been
accomplished.
32 Bonding Means
32.1 A hazardous-voltage component, such as a control, that may
No grounding
N/A
N/A
be separated from its intended grounding means after
installation in the end-use product for purposes of testing or
adjustment while the equipment is energized shall be provided
with a bonding terminal or with a bonding conductor that does
not require removal from the component for such testing or
adjustment.
32.2 Bonding shall be accomplished by a positive means, such as
N/A
by metal-to-metal contact of the parts, or by a separate
bonding conductor in accordance with Clauses 32.3 - 32.11.
The bonding connection shall penetrate nonconductive
coatings, such as paint. Bonding around a resilient mount shall
not depend on the clamping action of rubber or similar
material.
32.3 A bolted or screwed connection that incorporates a star
N/A
or serrations under the screw head shall be acceptable for
penetrating nonconductive coatings as required by Clause
32.2. The use of two or more screws, or two full threads
engagement of a single screw in metal, shall comply with
Clause 32.2 if the bonding means depends upon screw
threads.
32.4 Metal-to-metal hinge bearing members for doors or covers
N/A
shall be considered to be means of bonding the door or cover
used.
www.tuv.com
Page 31 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
32.5 A separate component-bonding conductor shall be copper, a
N/A
copper alloy, or other material that may be used as an
electrical conductor. A ferrous metal part in the grounding path
shall be protected against corrosion by enamelling,
galvanizing, plating, or other equivalent means.
32.6 A separate bonding conductor or strap shall be protected from
N/A
damage or shall be located within the confines of the outer
enclosure or frame, and shall not be secured by a removable
fastener user for any purpose other than bonding unless the
bonding conductor is unlikely to be omitted after removal and
replacement of the fastener. The ends of the conductor shall
be in metal-to-metal contact with the parts to be bonded.
32.7 The size of an individual conductor or strap employed to bond
N/A
an electrical enclosure or motor frame shall be determined by
the rating of the overcurrent-protective device of the branch
circuit to which the product will be connected in accordance
with Table 250-122, Minimum Size Equipment Grounding
Conductors for Grounding Raceway and Equipment, of the
National Electrical Code, ANSI/NFPA 70, and Table 16,
Minimum Size Conductors for Bonding Raceways and
Equipment, of the Canadian Electrical Code, Part I, C22.1,
except that such a conductor need not be larger than one of
the power-supply conductors.
32.8 With respect to Clause 32.7, a bonding conductor smaller than
N/A
specified may be used if the conductor does not open when
tested as described in the Bonding-Conductor Test, Clause 71.
32.9 With respect to 32.7, for a cord-connected product, the
N/A
grounding wire in the cord may be the same size as the
current-carrying conductors.
32.10 A bonding conductor to a motor or other electrical component
N/A
need not be larger than the motor circuit conductors or the
conductor supplying the component.
32.11 Bonding conductors in equipment shall have insulation
N/A
equivalent to that of live conductors, if there is any likelihood of
accidental contact with uninsulated live parts.
32.12 Splices shall not be employed in wire conductors used for
N/A
bonding.
32.13 If more than one size of branch-circuit overcurrent device is
N/A
involved, the size of the bonding conductor shall be based on
the rating of the overcurrent device intended to provide groundfault protection for the component bonded by the conductor.
For example, if a motor is individually protected by a branchcircuit overcurrent device smaller than other overcurrent
devices used with the product, a bonding conductor for that
motor shall be sized on the basis of the overcurrent device
intended for ground-fault protection of the motor.
33 Capacitors P
33.1 A capacitor provided as a part of a capacitor motor and a
P
capacitor connected across the line, such as a capacitor for
elimination of radio-frequency interference or power-factor
correction, shall be housed within an enclosure or container
that will reduce the likelihood of mechanical damage of the
plates and that will reduce the likelihood of emission of flame
or molten material resulting from malfunction or breakdown of
the capacitor. The container shall be of metal providing
strength and protection not less than that of uncoated steel
having a thickness of 0.51 mm (0.020 in).
The supporting means for a heating element shall be evaluated
www.tuv.com
Page 32 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
Exception: The individual container of a capacitor may be of
N/A
sheet metal thinner than 0.51 mm (0.020 in) or may be of other
material if the capacitor is mounted in an enclosure that
houses other parts of the product and is acceptable for the
enclosure of a live part.
33.2 A capacitor employing a liquid dielectric medium shall not
N/A
expel the medium when tested in accordance with the
applicable performance requirements in this Standard,
including faulted overcurrent conditions based on the branch
circuit in which it is used.
34 Coil Windings P
34.1 Each coil winding of a motor, relay, transformer, and the like
P
shall be treated to resist the absorption of moisture by
impregnating, dipping, or brushing with varnish or by other
means.
34.2 Film-coated wire shall not be required to be additionally treated
P
to resist the absorption of moisture, but fiber liners, cloth coil
wrap, and similar materials shall be provided with impregnation
or otherwise treated to resist moisture absorption.
35 Heating Elements
35.1 A heating element shall be supported in an acceptable and
No heating element
N/A
N/A
reliable manner. It shall be protected against mechanical
damage and contact with outside objects.
35.2
N/A
with respect to sagging, loosening, and other adverse
conditions resulting from continuous heating of the element.
35.3 An open-wire element, that is, one consisting of uninsulated
N/A
resistance wire, may be used in a product provided it is
enclosed or protected by barriers or covers that require tools
for removal, and provided it complies with all live part
accessibility requirements. See Accessibility of Uninsulated
Hazardous Voltage Live Parts and Film-Coated Wire, Clause
7.
35.4 Coiled-wire heating elements may be supported on porcelain,
N/A
hook-type insulators, depending upon the stiffness of the coil,
the spacing between hooks, the shape of the hook, or the like.
Porcelain insulators of all types shall be retained in place by
means other than the heating element.
35.5 A heating element intended for operation only in an air stream
N/A
shall be wired or controlled so that the element can be
operated only while under the cooling effect of an air stream. A
product in which the cooling effect of the motion of a part is
necessary to prevent excessive temperatures shall be wired or
controlled so that the element cannot be operated without such
motion.
35.6 A sheathed heating element shall be suitable for the
N/A
applications, and shall comply with the requirements in the
Standard for Sheathed Heating Elements, UL 1030, and the
CSA Standard for Heater Elements, C22.2 No. 72.
36 Motors P
36.1 General P
36.2
Motor overload protection
P
www.tuv.com
Clause Requirement Test Result - Remark Verdict
36.1.1 A motor shall comply with the requirements in the Standard for
Rotating Electrical Machines - General Requirements, UL
1004-1, and the CSA Standard for Motors and Generators,
C22.2 No. 100, and shall be capable of driving the maximum
normal load of the product without a risk of fire or electric
shock.
36.1.2 A brush-holder assembly shall be constructed so that when a
brush is worn out - no longer capable of performing its function
- the brush, spring, and other parts of the assembly shall be
retained to the degree necessary to reduce the likelihood of an
accessible non-current-carrying metal part becoming
energized, and a live part becoming accessible.
36.1.3 Each brush cap shall be secured or located so as to be
protected from mechanical damage that may otherwise occur
during intended use.
36.2.1 All motors shall be protected by thermal or by overcurrent
protective devices, or a combination of these, except as
specified in Clause 36.2.11.
36.2.2 If thermal protection is incorporated it shall comply with the
applicable requirements in the Standard for Thermally
Protected Motors, UL 1004-3, and the CSA Standard for
Motors with Inherent Overheating Protection, C22.2 No. 77.
Note 1: For a product that includes a control as mentioned in
Clause 36.2.3, the duration of the temperature test and the
endurance test, both under locked-rotor conditions, may be
less than that specified but shall not be less than the period of
operation permitted by the product.
Note 2: If the time required to operate a manually reset
protective device through 10 cycles of operation is longer than
the time that the product is likely to be operated during each
use, the number of operations of the device for the
temperature test under locked-rotor conditions may be less
than 10 cycles but shall not be less than 4 cycles.
36.2.3 A motor intended to move air only, by means of an air-moving
fan that is integrally attached, keyed, or otherwise fixed to the
motor shaft, shall not be required to have running overload
protection.
36.2.4 The control mentioned in Note 1 to Clause 36.2.2 shall
positively and reliably limit the length of time the product can
be operated, as, for example, a timer.
36.2.5 For a multispeed motor that uses a separate overloadprotective device to provide running protection, the protection
shall be effective at all intended motor speeds.
36.2.6 The overload protection of a single-speed, continuous duty fan
motor having a marked rating over 746 W output (1 HP) need
not be provided as part of the product if all of the following
conditions exist:
a) The motor is located where it is not affected by an
external source of heat;
b) The motor is to be field-wired to a separate circuit that
does not supply any other loads within the product;
c) The motor overload protection is part of separate, field-
provided motor control equipment that does not require wiring
interconnection to the product, except for the motor circuit; and
Page 33 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
P
N/A
N/A
N/A
N/A
N/A
N/A
P
N/A
N/A
N/A
N/A
N/A
N/A
rated or set to trip at not more than the percentage of the motor
capable of fully protecting the circuit and motor
CSA Standard for Motors with Inherent Overheating Protection,
www.tuv.com
Page 34 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
d) Energization of electric heating elements does not occur
N/A
without motor operation or evidence of air flow.
36.2.7 Compliance with the requirements of Clause 36.2.1 shall be
N/A
considered to be achieved if the protection is provided by a
separate device that is responsive to motor current, and is
nameplate full-load current rating as specified in Table 11.
Exception: If the percentage protection specified in Column A
N/A
of Table 11 does not correspond to the percentage value of an
overload relay of a standard size, the device of the next higher
size may be used. However, the overload device of the next
higher size shall protect against currents exceeding the
percentage values specified in Column B of Table 11.
36.2.8 A three-phase motor shall be provided with overload protection
N/A
as follows:
a) Three overcurrent units or N/A
b) Thermal protectors, a combination of thermal protectors
N/A
and overcurrent units, or another method of protection, where
the specific protective arrangement has been investigated and
found to provide protection under primary, single-phase fault
conditions when power is supplied from transformers
connected wye-delta or delta-wye.
36.2.9 Where the overheating protection of three-phase motors is
N/A
provided by devices that are current responsive only, such
devices shall consist of three current responsive elements
which may be:
a) Connected directly in the motor circuit conductor or N/A
b) Fed by two or three current transformers, and so
N/A
connected that all three phases will be protected.
36.2.10 Overload devices shall consist of one of the following: N/A
a) A separate overload device that is responsive to motor
N/A
current, rated or set at values not greater than the percentages
of the marked full-load current specified in Clause 36.2.6, and
that combines the functions of overload and overcurrent
protection if it is
both under overload and short circuit conditions;
b) A protective device, integral with the motor, responsive to
N/A
motor current, or to both motor current and temperature
providing such device will protect the circuit conductors and
control equipment, as well as the motor;
c) Notwithstanding (a), where the marked service factor of a
N/A
motor is less than 1.15, or where the service factor or service
factor current is not marked on the motor, the rating or setting
of separate overload devices, if used, shall not exceed 115
percent of the full load current of the motor; or
d) An overload protector included as part of the assembly. N/A
36.2.11 Fuses shall not be used as motor overload protective devices
N/A
unless the motor is adequately protected by the fuse of the
highest current rating that can be inserted in the fuseholder.
36.2.12 Impedance protection shall be acceptable, provided the motor: P
a) Complies with the applicable requirements in the
P
Standard for Impedance Protected Motors, UL 1004-2, and the
C22.2 No. 77;
b) Does not overheat when subjected to the performance
tests of this Standard; and
P
www.tuv.com
Clause Requirement Test Result - Remark Verdict
c) Is not installed in a compartment that handles air for
circulation to the conditioned space through a duct system,
unless no smoke is generated under any required test
condition while the rotor of the motor is locked.
36.3 Short circuit protection N/A
36.3.1 Motor overcurrent protective devices and thermal protective
devices shall comply with the applicable short circuit
requirements for the class of protective device.
36.3.2 Except as indicated in Clause 36.3.3, an overcurrent protective
device or a thermal protective device employed on equipment
having more than one motor, or having a motor and
supplementary heater, wired for connection to one supply
circuit, shall withstand short circuit and ground fault conditions,
without creating a risk of fire or electric shock.
36.3.3 The short circuit tests specified in Clauses 36.3.1 and 36.3.2
may be waived if:
a) The thermally protected motor or separately enclosed
motor overload protective device is within an outer cabinet of a
product or section of a product;
b) The motor or device is intended to be protected by the
overcurrent protective device as specified on the unit
nameplate, or provided as part of the product, and which is
acceptable for the branch circuit protection;
c) The assembly is constructed so that flame and molten
metal will be confined within the cabinet; and
d) Combustible material, except electrical insulation or an air
filter, is not located below the motor.
37 Overcurrent Protection P
37.1 No protective device shall be accessible from outside the
product without opening a door or cover. See Clause 6.5.
Exception: The operating handle of a circuit breaker, the
operating button of a manually operable motor protector, and a
similar part may project outside the enclosure.
37.2 No uninsulated live part of a fuseholder other than the screw
shell or clips shall be exposed to contact by a person removing
or replacing a fuse.
Exception: The requirement does not apply if the presence of
the protective device would ordinarily be unknown to the user
of the product because of its location and the omission of
reference to the device in the operating instructions, circuit
diagrams, and the like for the product.
37.3 Plug fuses shall not be used in circuits exceeding 150 V to
ground. The screw shell of a plug type fuseholder and the
accessible contact of an extractor fuseholder shall be
connected toward the load.
37.4 If a product includes an attachment-plug receptacle intended
for general use, and if the overcurrent protection of the branch
circuit to which the product will properly be connected exceeds
that acceptable for the receptacle, each receptacle circuit shall
have overcurrent protection at not more than the rating of the
receptacle provided as a part of the product.
37.5 The overcurrent protection specified in Clauses 37.4 and 37.8 -
37.10 shall be located in each ungrounded conductor and shall
comply with the requirements for branch-circuit protection.
Page 35 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
P
N/A
N/A
N/A
N/A
N/A
N/A
N/A
P
N/A
No fuseholder N/A
N/A
N/A
Not such appliance N/A
Not such appliance N/A
circuit
c) The overcurrent protection in (b) is provided as an integral
38 Protection Against Overheating
N/A
www.tuv.com
Page 36 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
37.6 If a fuse is used for the overcurrent protection referred to in
N/A
Clause 37.5, it shall be a Class CC, G, H, J, K, L, RK, or T
cartridge fuse, a Type S fuse, or the equivalent.
37.7 The rating of the branch-circuit overcurrent-protective device
No such device N/A
shall not exceed the overcurrent protective device rating
marked on the product or, if there is no marking, 20 A for a
product rating not exceeding 13.3 A and 150 percent of the
product rating for a product rating greater than 13.3 A.
Standard ratings for overcurrent protective devices are 15, 20,
25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175,
and 200 A. If 150 percent of the rating of the product does not
equal one of the aforementioned, it shall be assumed that the
next higher rating or setting of overcurrent-protective device
will be employed.
37.8 A product provided with auxiliary-circuit terminals shall
No such circuit N/A
incorporate an overcurrent-protective device in accordance
with Clause 37.5 in each ungrounded conductor connected to
the terminals.
Exception: An overcurrent-protective device is not required as
N/A
part of the product if it is determined that equivalent or better
protection will be obtained from the branch-circuit overcurrentprotective device through which the product will be supplied.
37.9 Each lampholder circuit in a permanently connected product
No lampholder N/A
having a lampholder independent of any heating-element
circuit shall have overcurrent protection rated not more than 20
A in the product, if the overcurrent protection of a branch
to which the product may be properly connected in accordance
with Clause 37.7 would exceed 20 A.
37.10 A product rated more than 48 A shall have the heating-element
Less than 48A N/A
circuits subdivided. Each subdivided circuit shall not exceed a
rating of 48 A, and each shall be provided with overcurrent
protection rated not more than 60 A.
Exception: A product complying with all of the following
N/A
conditions may be subdivided into circuits not exceeding 120 A
each if:
a) The load consists of resistance-type immersion heating
N/A
elements that are contained within a water or steam tank,
provided that the tank bears ASME marking letter H, M, or S in
a clover leaf;
b) Each subdivided circuit is protected at not more than 150
N/A
A; and
N/A
part of the product or is provided by the manufacturer as a
separate assembly for independent mounting and use with the
product.
No such device
38.1 The setting, construction, and location of protection devices
N/A
used to prevent the attainment of unsafe operating
temperatures as the result of either normal or abnormal
operation shall be investigated with respect to all features
bearing on the life and fire hazards involved in actual service.
www.tuv.com
Page 37 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
38.2 Fusible links provided in heaters to prevent the attainment of
N/A
unsafe temperatures due to abnormal operation of heaters
shall be so constructed or enclosed as to prevent tampering
and shall operate without the short-circuiting or grounding of
live parts. Please see Thermal Cutoff Test, Clause 66 for
additional information.
38.3 The reset lever or button of a manual reset protective device
N/A
that is not trip-free shall be recessed or guarded.
38.4 Where a humidifier employs a single magnetically operated
N/A
relay device or contactor that performs the temperature
regulating and limiting function for an electric heating element,
the device shall be rated for at least 250 000 endurance
cycles.
38.5 Except as specified in Clause 38.8, a humidifier employing
N/A
electric heating elements shall be provided with one or more
manually resettable or replaceable backup protective devices
of the type specified in Clause 38.6 that will, with the contacts
of the control described in Clause 38.4, permanently closed,
comply with the abnormal operation test, Clause 65, and the
thermal cutoff test, Clause 66.
38.6 The manually resettable or replaceable protective devices
N/A
specified in Clause 38.5 shall be functionally independent of
the automatically resetting limit control. The following types of
controls comply with this requirement:
a) One or more thermal cut-offs, non-resettable
N/A
temperature-limiting controls, or manually resettable limit
controls connected to open a sufficient number of ungrounded
conductors to permit the unit to comply with the specified
temperature limits and
b) A combination consisting of one or more normally open
N/A
switching device and thermal cut-offs, non-resettable
temperature-limiting controls, or manually resettable limit
controls. The thermal cut-off or limit control shall be connected
in the coil circuit of the switching device.
The combination shall be: N/A
1) Integral with the product, N/A
2) Able to open a sufficient number of ungrounded supply
N/A
conductors to permit the product to comply with the specified
temperature limits and
3) Independent of control by an automatic cycling device
N/A
with the unit.
38.7 Replacement of a thermal cut-off or non-resettable limit control
N/A
shall not necessitate any of the following:
a) Removal of the unit or heater assembly from its
N/A
installation, except removable heating elements or an element
assembly may be withdrawn, or a heater may be partially
withdrawn, to replace a thermal cut-off or non-resettable limit
control, if withdrawal will not result in non-compliance with the
requirements of Clause 38.7 (b), (c), and (d);
b) Disconnection of the field wiring systems; N/A
c) Stretching or similar displacement of the heater element
N/A
wire that could cause permanent displacement or distortion to
the extent that the performance of the heater could be affected
or
d) Release of the heater element wire from its attachment if
N/A
this would result in displacement of the element.
resettable
application, and shall have a current and voltage rating not less
If a switching device or a pilot device that controls a switch with
www.tuv.com
Clause Requirement Test Result - Remark Verdict
38.8 With respect to Clause 38.7, a thermal cut-off or nonlimit control that is not required in order to comply with any of
the requirements in this Standard need not comply with Items
(a) and (b).
38.9 The requirement specified in Clause 38.5 does not apply if no
part of the automatically resetting temperature-limiting control
circuit cycles under intended operating conditions. For
example, an automatically resetting temperature-limiting
control that directly controls a heating element is not required
to be provided with the backup protection specified in Clause
38.5. The backup protection specified in Clause 38.5 is
required for a humidifier employing an electric heating element
that incorporates a switching device whose coil circuit is
controlled by both the temperature-limiting control and
temperature-regulating control for the heater.
39 Receptacles
39.1 A 15- or 20-A attachment-plug receptacle intended for general
use in a product provided with means for grounding shall be of
the grounding type. The grounding contact of the receptacle
shall be electrically connected to metal parts in the
grounding/bonding circuit.
39.2 The face of a receptacle shall: N/A
a) Be flush with or project beyond a nonconductive
surrounding surface or
b) Project at least 0.38 mm (0.015 in) beyond a conductive
surrounding surface.
39.3 Receptacles shall not be provided on products intended to be
duct- or plenum-mounted.
40 Switches and Controllers
40.1 A switch or other control device shall be acceptable for the
Page 38 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
N/A
N/A
No receptacle
N/A
N/A
N/A
N/A
No such device
N/A
N/A
N/A
than that of the load it controls.
40.2 The current rating of a switch that controls an inductive load,
such as a transformer of a fluorescent-lamp ballast, shall not
be less than twice the rated full-load current of the transformer
or ballast, unless the switch has been investigated and found
to be acceptable for the application.
40.3 A switch in a circuit including one or more motors and some
other load and that may break the circuit under locked rotor
conditions shall have a current interrupting capacity not less
than the total of the locked rotor motor current of the largest
motor and the other load.
40.4 A switch shall be of the indicating type. N/A
40.5 The indicating means referred to in Clause 40.4 may be
incorporated on the switch or knob, on an attached plate, or on
the panel on which the switch is mounted.
40.6 A switching device or a pilot that controls a switch may be
marked with the symbols "I" and "O" to represent the "ON" and
"OFF" positions, respectively, of the device.
40.7
a marked or indicated "OFF" position operates to interrupt the
main supply circuit, it shall, when open, disconnect all
ungrounded power-supply conductors.
N/A
N/A
N/A
N/A
N/A
position at least, shall be indicated on or adjacent to the switch.
An electrically operated valve or solenoid shall not create a risk
carrying metal part, shall not be less than specified in Table 13.
carrying metal part is in proximity to an uninsulated
www.tuv.com
Clause Requirement Test Result - Remark Verdict
40.8 If a switch or a control that can be turned manually to an "OFF"
position is used to control one or more functions, its "OFF"
Alternatively, keys or legends may be used for showing the
operating positions of switches; they shall indicate at least the
"OFF" position and shall appear in a conspicuous, permanent
location. No additional marking need appear if the handle is of
such shape or design that the "OFF" position of the switch is
thereby clearly indicated.
40.9 A switch that controls a medium-base lampholder of other than
a pilot or indicating light shall be investigated and found to be
acceptable for use with tungsten-filament lamps.
40.10 A product provided with a power-supply cord and an
attachment plug and employing a motor rated more than 1/3
HP (250 W output) shall be provided with a control for starting
and stopping the motor.
40.11 A speed-control switch shall be provided with a product that
employs a multispeed motor.
40.12 Switches shall be so located or protected that in normal use
they will not be exposed to mechanical damage.
41 Electrically Operated Valves and Solenoids
41.1 An electrically operated valve or solenoid shall be so located,
guarded, or enclosed that it will not be subject to mechanical
damage during the normal operation or servicing of the
equipment.
41.2
of fire if it fails to operate properly.
41.3 If a valve must be cleaned periodically, the construction shall
be such that this operation can be performed without damage
to the electrical parts of the valve or wiring.
42 Spacings P
42.1 The spacings between wiring terminals of opposite polarity,
between a wiring terminal and an uninsulated non-currentcarrying metal part, or between a wiring terminal and
uninsulated live part of opposite polarity shall not be less than
specified in Table 12.
42.2 Other than at wiring terminals, and as noted in Clause 42.7,
the spacing between uninsulated live parts of opposite polarity,
and between an uninsulated live part and a non-current-
Page 39 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
N/A
N/A
N/A
N/A
N/A
No such device N/A
N/A
N/A
N/A
P
P
If an uninsulated live part is not rigidly fixed in position by
means other than friction between surfaces, or if a moveable
non-currentlive part, the construction shall be such that the required
minimum spacing will be maintained.
42.3 The spacings at installer wiring terminals shall apply with the
required size of supply conductors in place, including the use
of aluminum supply conductors.
42.4 The spacings in Table 12 at installer wiring terminals shall not
apply to bars or straps connected to such terminals.
42.5 The spacings through air and over the surface from terminals
and other bare live parts to removable enclosures of metal
shall be not less than 9.5 mm (3/8 in) for voltages not
exceeding 375 V, and not less than 12.5 mm (1/2 in) for
voltages from 376 to 600 V.
N/A
N/A
No such part N/A
made in the field by means of wire connectors, eyelets, and the
unsafe operation of the controlled device, spacings shall be not
wool thermal insulation contain conductive impurities in
44 Wetting Live Parts
P
www.tuv.com
Clause Requirement Test Result - Remark Verdict
42.6 The inherent spacings of a component supplied as part of a
product, such as a snap switch, lampholder, or motor, are
judged under the requirements for that component. The
spacings from a component to another component and to the
enclosure, and the spacings at wiring terminals, are specified
in Tables 12 and 13.
42.7 At terminal screws and studs to which connections may be
like, the spacings shall not be less than those specified in
Table 13 when such connectors, eyelets, and the like are in
such a position that minimum spacings to parts of opposite
polarity and to non-current-carrying metal exist.
42.8 An insulating liner or barrier of vulcanized fiber or similar
material employed in lieu of spacings shall not be less than 0.8
mm (1/32 in) thick, and shall be so located or of such material
that it will not be adversely affected by arcing.
Exception: Fiber not less than 0.4 mm (1/64 in) thick may be
used in conjunction with an air spacing of not less than 50
percent of the spacing required for air alone.
42.9 Where higher than rated voltage is developed in a motor circuit
through the use of capacitors, the rated voltage of the system
shall be employed in applying the spacings indicated in this
standard, unless the developed steady-state voltage measured
in the Normal-Temperature Test, Clause 57, exceeds 500 V, in
which case the developed voltage shall be used in determining
the spacings for the parts affected.
42.10 Bare live parts connected to circuits of different voltage shall
be spaced from one another as though they were parts of
opposite polarity, in accordance with Tables 12 and 13 for the
highest voltage involved.
42.11 For an extra-low-voltage safety circuit, if operation of the
product with a short circuit or grounded circuit may result in
Page 40 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
P
N/A
No such part N/A
N/A
No such circuit N/A
N/A
N/A
less than as specified in Table 13.
42.12 For extra-low-voltage nonsafety circuits, spacings are not
specified.
43 Thermal Insulation
43.1 Thermal insulation shall be of such a nature and located and
mounted or supported so that it will not be adversely affected
by any intended operation of the product.
43.2 Combustible or electrically conductive thermal insulation shall
not contact uninsulated live parts of a product. Some types of
mineralthe form of slag, and shall not be used with uninsulated live
parts.
43.3 Thermal insulation that is not rigid shall be mounted or
supported so that it will not sag.
43.4 Adhesive employed for mounting thermal insulation shall be
investigated and found to be acceptable for use at the
temperature to which it may be subjected.
43.5 Determination of the acceptability of an adhesive shall not be
necessary if the thermal insulation is mechanically supported
by at least one rivet or the equivalent per 929 cm2 (1 ft2) of
material.
N/A
N/A
N/A
N/A
N/A
N/A
N/A
A product having a reservoir intended for filling by an automatic
www.tuv.com
Page 41 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
44.1 There shall be no wetting of electrical parts as a result of any
P
likely condition of normal or abnormal use, such as overfilling,
improper replacement of parts that are moved or removed
during user servicing, malfunction of water-handling systems,
moving or portable products, and the like.
44.2 No electrical part in a product having a reservoir arranged for
P
hand filling by the user shall be wetted during any likely filling
operation.
44.3
N/A
valve shall not allow electrical parts to be wetted when the
valve is held in its open position.
45 Internal Plumbing N/A
45.1 A product connected to a potable water-supply system shall be
N/A
provided with an air-gap fitting as described in Clause 45.2.
45.2 For the air-gap fitting mentioned in Clause 45.1, the minimum
N/A
unobstructed vertical distance through free air between the
lowest opening in the water-inlet device supplying water to the
product and the flood-level rim of the reservoir that receives
the water shall be at least 25.4 mm (1 in) or twice the inside
diameter of the inlet pipe, whichever is greater; or the product
shall comply with the Backflow Test, Clause 70.
45.3 The flood-level rim mentioned in Clause 45.2 shall be the
N/A
highest point in the reservoir from which water overflows.
45.4 Each part of the potable water-supply assembly of a product
N/A
that is in contact with the water, through the discharge terminal
point of the air-gap fitting, shall be constructed of nontoxic and
corrosion-resistant materials.
46 Filters
46.1 A filter provided with a humidifier intended for connection to
N/A
N/A
ducts or plenums shall comply with the requirements in the
Standard for Air Filter Units, UL 900.
47 Pressure Vessels and Parts Subjected to Pressure
47.1 If the equipment includes pressure vessels having an inside
Not such appliance N/A
N/A
diameter over 152 mm (6 in) and an internal volume over
0.0425 m3 (1.5 ft3), and operating at more than 103 kPa (15
psig), they shall comply with the CSA Standard for Boiler,
Pressure Vessel, and Pressure Piping Code, B51, and shall be
designed, tested, and stamped in accordance with the ASME
Boiler and Pressure Vessel Code for a design pressure no less
than the pressure determined in accordance with Clause 47.2.
Exception: A pressure vessel that is not covered by the
N/A
inspection procedure of the ASME Code, because of its
application, and that complies with the requirements in Clause
47.2, need not be certified and marked as specified.
47.2 A part or assembly that is subject to air or vapor pressure
N/A
(including the pressure in a vessel containing only a
superheated fluid) during normal or abnormal operation shall
withstand, as described in Tests on Parts Subject to Pressure,
Clause 72, a pressure equal to the highest of the following that
is applicable to the particular vessel:
device shall
www.tuv.com
Clause Requirement Test Result - Remark Verdict
a) Five times the pressure corresponding to the maximum
setting of a pressure-reducing valve provided as part of the
product, but not more than five times the marked maximum
supply pressure from an external source and not more than
five times the pressure setting of a pressure-relief valve or
other device provided as a part of the product.
b) Five times the marked maximum supply pressure from an
external source, but not more than the limits specified in (a).
c) Five times the pressure setting of a required pressure-
relief device.
d) Five times the maximum pressure that can be developed
by an air compressor that is part of the product, unless the
pressure is limited by a pressure-relief device as described in
(a).
e) Five times the working pressure marked on the part. N/A
f) Five times the maximum pressure that can be developed
in a nonenclosed system or vessel. (A nonenclosed system or
vessel is a system or vessel using an overflow open to the
atmosphere.)
47.3 A section of a pressure system constructed of continuous
tubing or lengths of tubing connected by hard soldered,
brazed, or welded joints shall be considered to comply with the
requirements in Clause 47.2 if the thickness of tubing is not
less than the applicable value specified in Table 14.
47.4 A pressure vessel bearing the CRN or ASME Code inspection
symbol shall be considered to comply with the requirements in
Clause 47.2 if it is marked with a value of working pressure not
less than that to which it is subjected during normal or
abnormal conditions.
47.5 A means for relieving pressure shall be provided for all parts in
which pressure may be generated by an external fire.
47.6 A pressure-relief device, such as a fusible plug, soldered joint,
nonmetallic tubing, or other equivalent pressure-relief means,
may be employed to comply with the requirement in Clause
47.5.
47.7 There shall be no shutoff valve between a pressure-relief
means and the part it is intended to protect.
47.8 A vessel having an inside diameter of more than 76.2 mm (3
in) and subject to air or steam pressure generated or stored
within the product shall be protected by a pressure-relief
device.
47.9 The start-to-discharge pressure setting of the relief
not be higher than the working pressure marked on the vessel.
The discharge rate of the device shall be sufficient to relieve
the pressure.
47.10 Each pressure-relief device shall: N/A
a) Be connected as close as possible to the pressure vessel
or part of the product it is intended to protect;
b) Be installed so that it is readily accessible for inspection
and repair and cannot readily be rendered inoperative so that it
will not perform its intended function; and
c) Have its discharge opening located and directed so that: N/A
1) Operation of the device will not deposit moisture on a live
part or on insulation or a component that may be adversely
affected by such moisture and
2) It is not likely to scald persons. N/A
Page 42 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
and a transformer, if these coils and windings are provided with
48.2
Construction
N/A
access of the mechanism, and not located within 152 mm (6 in)
www.tuv.com
Clause Requirement Test Result - Remark Verdict
47.11 A pressure-relief device having an adjustable setting is judged
on the basis of its maximum setting unless the adjusting
means is sealed at a lower setting.
47.12 A pressure-relief device is considered to be a pressureactuated valve or rupture member intended to automatically
relieve excessive pressures.
47.13 If a system is open to the atmosphere and the opening to the
atmosphere is used as a pressure-relief means, the opening
shall be capable of relieving the pressure at the maximum
generating capacity and shall discharge in a manner so that
the steam is directed in an area that is not likely to cause a risk
of electric shock or injury to persons.
48 Protection of Service Personnel No such service N/A
48.1 General N/A
48.1.1 The intent of this section is to reduce the risk of electric shock
or injury to service personnel performing service functions of a
mechanical nature on an energized product. Such functions do
not in themselves require exposure of live parts or moving
parts capable of causing injury, but it is often necessary to
perform these functions with the product energized.
48.1.2 The following are not considered to be uninsulated live parts
for the purposes of this section:
a) Coils and windings of a controller, a relay, and a solenoid,
Page 43 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
N/A
N/A
N/A
N/A
N/A
N/A
insulating overwrap;
b) Enclosed motor windings; N/A
c) Terminals; and N/A
d) Splices with insulation and insulated wire. N/A
48.2.1 An uninsulated live part or a moving part that can cause a risk
of injury to persons within the enclosure shall be located,
guarded, or enclosed so as to reduce the risk of unintentional
contact by service personnel performing mechanical service
functions that may have to be performed with the product
energized.
48.2.2 Examples of mechanical service functions that may have to be
performed with the product energized are:
a) Adjusting a water control valve; N/A
b) Adjusting the setting of a temperature, humidity, or a
water or pressure control with or without a marked dial setting;
c) Resetting a control trip mechanism; and N/A
d) Adjusting an airflow damper. N/A
48.2.3 An adjustable or resettable electrical control or manual
switching device shall be located or oriented with respect to an
uninsulated live part or a moving part that presents a risk of
injury to persons so that manipulation of the mechanism for
adjustment, resetting, or other service operations can be done
in the intended direction of access if an unguarded,
uninsulated live part or a moving part that presents a risk of
injury to persons is not located in front, in the direction of
N/A
N/A
N/A
N/A
on any side or behind the mechanism.
48.2.4 With reference to Clause 48.2.3, only uninsulated live parts in
a hazardous-voltage circuit shall be considered.
N/A
with respect to grounded metal parts, so that it is accessible for
through the control assembly enclosure shall be located so that
www.tuv.com
Page 44 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
48.2.5 An electrical control component that may require examination,
N/A
adjustment, servicing, or maintenance while energized excluding voltage measurements other than at jacks or
terminals specifically intended for that purpose - shall be
located and mounted with respect to other components, and
electrical service functions without subjecting service
personnel to a risk of electric shock from an adjacent
uninsulated live part or injury to persons from an adjacent
moving part.
48.2.6 Accessibility and protection from a risk of electric shock and
N/A
injury to persons shall be obtained by mounting the control
components in an assembly so the unimpeded access is
provided to each component through an access cover or panel
in the outer cabinet, and the cover of the control assembly in
accordance with the following items and Figure 9:
a) No component in the control assembly shall be located
N/A
more than 356 mm (14 in) from the plane of the access
opening in the outer cabinet.
b) An uninsulated live part outside the control assembly
N/A
projected clear space - other than a live part within a control
panel - or an unguarded moving part, shall be located no
closer than 152 mm (6 in) from any side of the access area.
The projected clear space shall be considered to be bounded
on the sides by the projection of the smallest rectangular
perimeter surrounding the outside edge of the components or
control enclosure when provided. The access area shall be
considered to be bounded on the sides by the projection of the
perimeter of the access opening in the outer cabinet to the
closest rectangular perimeter surrounding the outside edge of
the component or control enclosure.
c) The volume generated by the projected clear space of the
N/A
control assembly to the access opening in the outer cabinet,
within the access area, shall be completely free of
obstructions, including wiring.
d) Access to the components in the control assembly shall
N/A
not be impeded in the direction of access by other components
or by wiring in the assembly.
e) An extractor-type fuseholder and a snap switch mounted
N/A
there is unimpeded access to these components through the
access opening in the outer cabinet and so that they are not
immediately adjacent to an uninsulated live part outside the
control assembly enclosure, unless the live part is guarded.
48.2.7 A component or control may be rotated or otherwise displaced
for service if the electrical control components are accessible
for service as required.
48.2.8 Other arrangements of component location or guarding that
provide the required access to electrical control components
shall also be acceptable.
48.2.9 The electrical components referred to in Clauses 48.2.3 -
48.2.8 include the following:
a) Fuses; N/A
b) Adjustable or resettable overload relays; N/A
c) Manual or magnetic motor controllers; N/A
d) Magnetically operated relays; N/A
N/A
N/A
N/A
www.tuv.com
Clause Requirement Test Result - Remark Verdict
e) Adjustable or resettable pressure or temperature
controllers;
f) Manual switching devices; N/A
g) Clock timers; N/A
h) Incremental voltage taps; and N/A
i) Motor-speed tap terminals for variable-speed motors. N/A
Such components in an extra-low-voltage circuit shall comply
with the requirements in Clause 48.2.1 in their relation to
uninsulated live parts in a hazardous-voltage circuit and to
moving parts capable of causing injury to persons.
Exception: Under certain conditions, some of the components
referred to in this Clause are not required to be accessible for
service. The following are examples of such components:
a) A nonadjustable magnetic motor controller or a
magnetically operated relay that is inaccessible for service
while energized because it is located behind a subbase or
equivalent, and is not visible when the access panel is
removed;
b) Enclosed potential or current-type single phase motor-
starting relay;
c) An incremental voltage tap or motor-speed-control tap for
a variable-speed motor; and
d) A contact with bare live parts of the voltage or speed tap
to affect the speed or voltage change, such as an uninsulated
screw or quick-connect terminal.
49 Duct- and Plenum-Mounted Products
49.1 The requirements in Clause 50 apply to duct- and plenummounted products intended for commercial or residential use.
A duct- or plenum-mounted product shall also comply with all
of the applicable requirements in Clauses 1 - 48 of this
Standard.
50 Construction of Duct- and Plenum-Mounted Products
50.1 Installation
50.1.1 A product intended to be duct-mounted by the user shall be
constructed so that it can be installed mechanically by means
of ordinary tools (such as a screwdriver, a drill, and the like)
and electrically by means of plug-in connections available on
the furnace or as part of the building wiring.
50.1.2 The construction of a duct- or plenum-mounted product
intended to be installed by qualified service personnel shall be
such that:
a) The mechanical installation can be accomplished by
means of tools normally available at the installation site or by
means of tools provided by the manufacturer as part of the
installation kit; and
b) The electrical connections can be readily accomplished
by making use of existing terminals and connections in the
furnace or as part of the building wiring.
50.1.3 If a product is intended to obtain its power supply from a
furnace, the method of wiring shall be such that the internal
wiring and internal components of a furnace are not altered.
50.2 Polymeric material
Page 45 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Not such appliance N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Characteristics of Building Materials, UL 723, and the Standard
Methods of Test for Surface Burning Characteristics of Building
www.tuv.com
Page 46 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
50.2.1 A polymeric material that is used in a product intended to be
N/A
duct-or plenum-mounted, where the polymeric material of the
product is exposed to duct air, shall have a flame-spread rating
of 25 or less, and a smoke developed rating of 50 or less in
accordance with the Standard for Test for Surface Burning
Materials and Assemblies, CAN/ULC-S102. A small part, such
as the wheel on which the water-absorbing medium is
mounted, the float or float valve, a knob, or a slinger, is not
required to have the specified ratings or be included in the
surface-area calculation as specified in Clause 50.2.2(b).
50.2.2 A polymeric material employed in a residential duct- or plenum-
N/A
mounted product where the product is exposed to the duct or
plenum air is determined to comply with the requirements in
Clause 50.2.1 when:
a) The material has no single dimension greater than 1.83 m
N/A
(6 ft);
b) The sum of the surface areas exposed to the air stream
N/A
on all such materials in the product is not more than 0.93 m2
(10 ft2); and
c) One of the following conditions exists: N/A
1) The material has a flammability classification of 5VA in
N/A
accordance with the Standard for Tests for Flammability of
Plastic Materials for Parts in Devices and Appliances, UL 94,
and 5VA in accordance with the CSA Standard for Evaluation
of Properties of Polymeric Materials, C22.2 No. 0.17 or
2) Results that comply with the intent of the requirement are
N/A
obtained when the material is subjected to an enclosure
flammability 127-mm (5-inch) flame test as described in the
Standard for Polymeric Materials - Use in Electrical Equipment
Evaluations, UL 746C, and 5VA in CSA Standard C22.2 No.
0.17.
50.3 Evaporation pad
50.3.1 An evaporative pad for use in a duct-mounted product shall be
N/A
N/A
Class 1 or 2, and shall not be treated with a chemical that is
water soluble.
50.4 Supply cord
50.4.1 A product intended for mounting in or on an exhaust duct or
N/A
N/A
plenum may be provided with a power-supply cord if:
a) The cord is N/A
1) A 3-conductor, Type SJT or heavier duty type rated for at
N/A
least 105°C (221°F);
2) Terminated in a properly rated grounding attachment
N/A
plug; and
3) No longer than 1.83 mm (6 ft); and N/A
b) Installation instructions, as described in Clause 78.8, are
N/A
included with the product.
PERFORMANCE N/A
51 General Test Parameters P
51.1 General P
Exception: Leakage current need not be measured at terminals
www.tuv.com
Page 47 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
51.1.1 Except as otherwise required, one representative sample of
P
the equipment shall be subjected to the applicable tests of this
Standard.
51.1.2 The order of the tests, as far as applicable, shall correspond to
P
the Leakage-Current Test, Clause 52 to the Mold Stress-Relief
Test, Clause 73, but not so as to require unnecessary
samples.
51.2 Voltage P
51.2.1 Except as otherwise specified, humidifiers shall be tested at a
Rated 50/60Hz P
frequency of 60 Hz, and at the voltages, maintained at the unit
supply connections, as specified in Table 15. Units rated at
other than 60 Hz frequencies are to be tested at their rated
voltages and frequencies.
51.3 Ambient temperatures P
51.3.1 Except as otherwise provided in this Standard, equipment may
P
be tested in any convenient ambient temperature between 20
and 40°C (68 and 104°F).
52 Leakage-Current Test P
52.1 When tested in accordance with Clauses 52.2 - 52.7, the
P
leakage current of a cord-connected product rated 240 V or
less shall not be more than:
a) 0.5 mA for a portable product and P
b) 0.75 mA for all other products. N/A
52.2 All exposed conductive surfaces shall be tested for the
P
presence of leakage currents. The leakage currents from these
surfaces are to be measured to the grounded supply conductor
individually as well as collectively if simultaneously accessible,
and from one surface to another if simultaneously accessible.
Parts shall be considered to be exposed surfaces unless
guarded by an enclosure considered acceptable to reduce the
risk of electric shock as described in the Accessibility of
Uninsulated Hazardous Voltage Live Parts and Film-Coated
Wire, Clause 7. Surfaces shall be considered simultaneously
accessible if they can be readily contacted.
P
of an extra-low-voltage circuit.
52.3 If a conductive surface other than metal is used for the
P
enclosure or part of the enclosure, the leakage current shall be
measured using metal foil with an area of 100 x 200 mm (4 x 8
in), in contact with the surface. If the surface is less than 100 x
200 mm, the metal foil shall be the same size as the surface.
The foil shall not remain in place long enough to affect the
temperature of the products.
52.4 The measurement circuit for leakage current shall be as
P
illustrated in Figure 10. The measurement instrument is
defined in (a) - (c) below. The meter that is actually used for a
measurement need only indicate the same numerical value for
a measurement as would the defined instrument. The meter
used need not have all the attributes of the defined instrument.
a) The meter shall have an input impedance of 1500 ohms
P
resistive shunted by a capacitance of 0.15 microfarad.
b) The meter shall indicate 1.11 times the average of the
P
full-wave rectified composite waveform of the voltage across or
current through the resistor.
speed, temperature, or humidity controls shall be
www.tuv.com
Page 48 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
c) Over a frequency range of 0 - 100 KHz, the measurement
P
circuitry shall have a frequency response-ratio of indicated to
actual value of current - equal to the ratio of the impedance of
a 1500 ohm resistor shunted by a 0.15 microfarad capacitor to
1500 ohms. At an indication of 0.5 or 0.75 mA, the
measurement shall have an error of not more than 5 percent at
60 Hz.
52.5 Unless the meter is being used to measure leakage from one
P
part of a product to another, the meter shall be connected
between the accessible parts and the grounded supply
connector.
52.6 A sample of the product shall be tested for leakage current
P
starting with the as-received condition, as-received being
without prior energization except as may occur as part of the
production-line testing, and with its grounding conductor open
at the attachment plug. The supply voltage shall be adjusted to
the voltage specified in Figure 10. The test sequence with
reference to the measuring circuit - Figure 10 - shall be as
follows:
a) With switch S1 open, the product shall be connected to
P
the measuring circuit. Leakage current shall be measured
using both positions of switch S2, and with the product
switching devices in all of their intended operating positions.
b) Switch S1 shall then be closed, energizing the product,
P
and within 5 seconds the leakage current shall be measured
using both positions of switch S2 and with the product
switching devices in all of their intended operating positions.
c) The leakage current shall then be monitored until thermal
P
stabilization. Both positions of switch S2 shall be used in
determining this measurement. Thermal stabilization shall be
obtained by operation as in the Normal-Temperature Test,
Clause 57.
d) After thermal stabilization, switch S1 shall be opened to
P
de-energize the product. Monitoring of leakage current shall
continue until the leakage current stabilizes or decreases after
de-energizing the product, using both positions of switch S2.
52.7 Products with
P
tested at low, medium, and high settings of the controls.
53 Humidity-Conditioning Test P
53.1 A product shall be conditioned for 48 hours in air having a
P
relative humidity of 88 ± 2 percent at a temperature of 32 ±2°C
(90 ±4°F). After conditioning:
a) A cord-connected product rated for a nominal 240 V
P
supply or less shall comply with the requirements in Clause
52.1 in a repeated leakage current test; and
b) A product other than as mentioned in (a) shall have an
N/A
insulation resistance of 50,000 ohms or more between live
parts and interconnected non-current-carrying metal parts.
53.2 A sample of the product shall be heated to a temperature just
P
above 34°C (93°F) to reduce the likelihood of condensation of
moisture during conditioning. The heated sample shall be
placed in the humidity chamber and conditioned as specified in
Clause 53.1.
53.3 Following conditioning: P
54 Operation Test
P
ause
when connected to a supply circuit at the required test voltages
www.tuv.com
Page 49 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
a) A cord-connected product rated for a nominal 240 V
P
supply or less shall be tested as described in Clause 52.6. The
test shall be discontinued when the leakage current stabilizes
or decreases;
b) The insulation resistance of a product other than as
N/A
described in (a) shall be measured as described in Clause
53.4.
53.4 Ordinarily, insulation resistance shall be determined by using a
P
high-resistance voltmeter and a 250 V, direct-current circuit.
54.1 A product shall be operated for 24 hours in cycles of 15
P
minutes on and 45 minutes off, with water circulating through it
in the intended manner. Immediately upon conclusion of the
final on cycle of the 24-hour period, the leakage current or
insulation resistance shall be measured as described in Cl
53.2. The leakage current or insulation resistance, as
applicable, shall comply with the requirement in (a) or (b) of
Clause 53.1.
Exception: This requirement does not apply to a steam-type
N/A
product.
54.2 A steam-type product shall be tested as described in Clause
N/A
54.3. The leakage current shall not exceed 0.5 mA and there
shall be no evidence of deterioration of the physical properties
of the enclosure.
54.3 One sample of a steam-type product shall be supplied with
N/A
water and operated continuously for 30 days at rated voltage
and rated frequency. At the end of the 30 days, the sample
shall be subjected to the Leakage-Current Test, Clause 52.
55 Starting Test P
55.1 A product shall start and operate as intended on a circuit
P
protected by a fuse as specified in Clause 55.2. During this
test, the fuse shall not open. Also, any overload protector
provided as part of the product shall not trip.
55.2 The fuses required by Clause 55.1 shall: P
a) For cord-connected equipment, be the same rating as the
P
attachment plug of the supply cord. The fuses shall be the time
delay type, if equipment marking so specifies; and
b) For equipment intended for permanent connection to the
N/A
supply, be either of the same rating as marked on the
equipment or, if not marked, be of the same rating as the
maximum permitted for motor-branch circuits in the National
Electrical Code, ANSI/NFPA 70, and the Canadian Electrical
Code, Part I, C22.1. The fuses shall be the time delay type, if
equipment marking so specifies.
55.3 To determine compliance with Clause 55.1, the equipment,
P
and rated frequency, shall be capable of starting, from
standstill to normal operating speed(s), three consecutive
times without blowing the fuse, with the equipment initially at
room temperature.
55.4 The equipment shall start and run under all normal speed
control settings.
56 Input Test P
P
and also with water present so that the product is functioning in
securely held in thermal contact with the surface of the material
thermocouple in place. If a metal surface is involved, brazing or
stabilized temperatures have been established (no more than 1
www.tuv.com
Page 50 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
56.1 When tested as described in Clauses 56.2 and 56.3, the input
P
in amperes or watts or kilowatts to a product shall not be more
than 110 percent of the rated value of the product, except that
for single-phase motors with marked rating of 3 A or less, the
input may be not more than 120 percent of the rated value.
56.2 The input measurement shall be made with the equipment dry,
P
the intended manner.
56.3 If the humidifier includes heater(s) the input shall also be
N/A
measured with the heater(s) in operation.
57 Normal-Temperature Test P
57.1 All products P
57.1.1 When a product is tested as described in Clauses 57.1.2 -
P
57.2.4, the temperature at any point shall not be high enough
to:
a) Cause a risk of fire; P
b) Damage any material used; or P
c) Exceed the maximum acceptable temperatures specified
P
in Table 16.
57.1.2 Temperatures shall be measured by means of thermocouples
P
consisting of wires not larger than 24 AWG (0.21 mm2). When
thermocouples are used in determining temperatures of an
electrical product, it is common practice to employ
thermocouples consisting of 30 AWG (0.05 mm2) iron and
constantan wires and a potentiometer-type indicating
instrument, and such equipment shall be used whenever
referee temperature measurements by thermocouple are
necessary.
57.1.3 A thermocouple junction and adjacent lead wire shall be
P
to be measured, such as securely taping or cementing the
soldering the thermocouple to the metal might be necessary.
For a thermocouple-measured temperature of a coil of an
alternating-current motor having a frame diameter of 178 mm
(7 in) or less, the thermocouple shall be mounted on the
integrally applied insulation on the conductor.
57.1.4 A temperature shall be considered to be constant when three
P
successive readings taken at 10 minutes intervals indicate that
percent net increase between the last two readings). If the
temperatures measured are within 5 percent of the values
specified in Table 16, the test shall be continued until two
successive 10-minute readings indicate constant temperatures.
57.1.5 Ordinarily, coil or winding temperatures shall be measured by
P
thermocouples. However, if the coil is inaccessible for
mounting thermocouples, such as one immersed in sealing
compound, or if the coil wrap includes thermal insulation or
more than two layers of cotton not more than 0.8 mm (1/32 in)
thick, the resistance method is to be used.
57.1.6 When the change-of-resistance method is used, determination
N/A
of the temperature rise of a winding shall be calculated by the
following formula:
in which: N/A
Δt is the temperature rise of the winding in °C;
N/A
When required, the value of R at shutdown shall be determined
mentioned in Clause 57.1.11 shall be corrected as described in
If a corrected temperature exceeds the value specified in Table
reversing switch is thrown, the requirement applies at the lower
www.tuv.com
Clause Requirement Test Result - Remark Verdict
R is the resistance of the coil at the end of the test in ohms; N/A
r is the resistance of the coil at the beginning of the test in
ohms;
k is 234.5 for copper and 225.0 for electrical conductor grade
(EC) aluminum. Values of the constant (k) for other conductors
shall be determined;
t1 is the ambient temperature at the beginning of the test in °C;
and
t2 is the ambient temperature at the end of the test in °C. N/A
57.1.7
by taking several resistance measurements at short intervals,
beginning as quickly as possible after shutdown. A curve of the
resistance values and the time shall be plotted and
extrapolated to give the value of R at shutdown.
57.1.8 All values for temperature rises in Table 16 are based on an
assumed ambient temperature of 25°C (77°F). However, tests
that are conducted at any ambient temperature within a range
of 10 - 40°C (50 - 104°F) shall comply with the intent of this
requirement.
57.1.9 A short length of rubber- or thermoplastic-insulated flexible
cord exposed to a temperature of more than 60°C (140°F),
such as at terminals, shall be acceptable if supplementary
heat-resistant insulation of acceptable dielectric strength and
temperature rating is employed on the individual conductors of
the cord to reduce the likelihood of deterioration of the
conductor insulation.
57.1.10 If a test is conducted at an ambient temperature other than
25°C (77°F), an observed temperature other than as
Page 51 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
N/A
N/A
N/A
P
P
N/A
P
Clause 57.1.12. Neither a corrected temperature, as specified
in Clause 57.1.12, nor an observed temperature as specified in
Clause 57.1.11, shall exceed the values specified in Table 16.
57.1.11 An observed temperature limited by an automatic temperature
control or by a process such as the boiling of water or the
introduction of a liquid at a fixed temperature shall not be
corrected.
57.1.12 An observed temperature shall be corrected by addition [if the
ambient temperature is lower than 25°C (77°F)] or subtraction
(if the ambient temperature is higher than 25°C) of the
difference between 25°C and the ambient temperature.
57.1.13
16, at the request of the manufacturer the test may be
repeated at an ambient temperature closer to 25°C (77°F).
57.1.14 The product shall be operated under each condition of normal
service. For a multispeed product, this includes operation at
each speed, and for a reversible product, it includes operation
in both directions. If a reversible product continues to operate
in the same direction, but at a slower speed when the
speed as well as at the normal speed. Operation shall be
continued until temperatures have become constant. Please
see Clause 57.1.4.
57.1.15 The temperature test is to be conducted with the product dry
as well as with water as intended. The requirement in Clause
57.1.1 shall apply for both conditions.
Exception: A product that is permanently connected to a water
supply need not be operated without water.
N/A
P
P
P
P
N/A
beyond the back and one side of the product. The product shall
highest temperatures. This test shall be continued until ultimate
www.tuv.com
Page 52 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
57.1.16 A product having a regulating means that operates in response
P
to the relative humidity of the air so as to cause intermittent
operation shall have the regulator bypassed or defeated during
the normal temperature test.
57.1.17 A product that has an adjustable humidifying output shall be
P
operated at the maximum output for the normal temperature
test.
57.1.18 Controls that are actuated by either room temperature or
P
humidity shall be shunted out of the circuit to obtain maximum
normal condition.
57.1.19 A stationary or fixed product where one of the following
N/A
applies, shall be tested in alcove:
a) It is obviously not intended for duct- or plenum-mounting; N/A
b) The product is marked in accordance with Clause 76.2, or
N/A
leads itself to such installation.
57.1.20 The walls of the alcove shall consist of nominal 9.5 mm (3/8 in)
N/A
plywood, the inside surfaces of which shall be painted dull
black. The alcove shall consist of two sides, a back, and a top,
and shall be of such dimensions as to extend 0.61 m (2 ft)
be located as close to the sides of the alcove as its
construction will permit, and it shall be located so that
maximum heating of the walls will occur. A product marked in
accordance with Clause 76.2 shall be spaced away from the
sides of the alcove as specified in the marking.
57.1.21 For the temperature test, a separate controller - a controller
N/A
that is not a physical part of the product - that is intended for
installation in a wall shall be mounted as follows. The controller
shall be secured inside its own enclosure, if provided;
otherwise it shall be installed inside the smallest standard
flush-type outlet box that will accommodate it, and the box
shall be mounted in a simulated wall section as illustrated in
Figure 12.
57.2 Duct- or plenum-mounted products
57.2.1 The temperature test of a product (whether intended for
Not such product N/A
N/A
residential or commercial applications), that could be mounted
in or on a furnace duct or plenum, shall be conducted with the
product mounted in or on a duct or plenum with the intended
water supply connected. The temperature of the outlet air from
the furnace during the test shall be maintained at 93°C (199°F)
for a residential-type product, and at 121°C (250°F) for any
other products. A product marked in accordance with Clause
78.5 shall not be tested in or on a duct or plenum.
57.2.2 A product intended for residential applications, and for duct- or
N/A
plenum-mounting, shall be tested as described in Clause
57.2.3, and there shall be no emission of flame, smoke, or
molten metal, nor shall the fuse in the grounding connection
open.
57.2.3 The product shall be mounted in the intended manner and non-
N/A
current-carrying metal parts shall be connected to ground
through a 3 A fuse. The product shall be operated without
water in the mode of operation most likely to result in the
results are obtained.
If the instructions involve disassembly of any parts for cleaning,
approximately 0.5 kg (1.18 lbs) shall be allowed to fall vertically
a risk of injury to persons, shall be constructed of such material
www.tuv.com
Page 53 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
57.2.4 A grid consisting of nine thermocouples of identical length,
N/A
wired in parallel, shall be installed in the furnace outlet duct to
measure the temperature of the furnace outlet air. The
arrangement shall be such that one thermocouple will be
located centrally in each of nine equal rectangular duct areas
in a plane perpendicular to the axis of the duct. The grid shall
be located not more than 152 mm (6 in) downstream from the
location nearest the furnace at which no thermocouple will be
directly affected by radiation from a heating element, and the
humidifier air-inlet shall be located 152 mm downstream from
the grid.
58 Disassembly and Reassembly Test P
58.1
P
it shall be determined that the product is unlikely to be
reassembled in a manner that will result in a risk of fire, electric
shock, or injury to persons.
59 Impact P
59.1 A part as described in Clause 9.1 shall be subjected to an
P
impact of 2 J (1.5 ft-lbs) on any surface that is exposed to a
blow during intended use, and:
a) The performance of the product shall not be adversely
P
affected so that a risk of fire or electric shock is introduced and
b) A moving part presenting a risk of injury to persons shall
P
not be exposed to contact as determined by use of the probe
illustrated in Figure 7 and Table 3.
A component such as a pilot lamp, a lens, a control knob, or
N/A
the like need not be subjected to the impact test.
59.2 A smooth steel sphere, 51 mm (2 in) in diameter and weighing
P
from rest through a distance of 381 mm (15 in) to strike the
part being tested.
For a part that cannot be struck from above by the freely falling
P
sphere, the sphere shall be suspended by a cord and allowed
to fall as a pendulum through a vertical distance of 381 mm.
Only one impact shall be applied at a given point.
60 Rotating Members
60.1 A rotating part, the breakage or loosening of which may create
N/A
N/A
and in such a manner as to reduce the likelihood of its
breakage or loosening.
60.2 A product having a series motor shall be tested as described in
N/A
Clause 60.3, and no part that could cause an injury shall
become loosened.
Exception: A test need not be conducted if a review of the
N/A
manufacturer's specifications indicates that the part or parts
are adequately strong.
60.3 For the test discussed in Clause 60.2, a product having a
N/A
series motor shall be operated for 1 minute at the no-load
speed resulting from application of 130 percent of rated
voltage.
61 Dielectric Voltage-Withstand Test P
enters the layer. This opposite polarity test is not required to be
current test potential of 1414
V for equipment rated 250 V or less or 1414 V plus 2.828 times
62 Strain
-
Relief Test
P
62.1
General
P
www.tuv.com
Clause Requirement Test Result - Remark Verdict
61.1 A product shall withstand, without breakdown, a 40 - 70 Hz
potential applied for 1 minute between hazardous-voltage live
parts and dead metal parts and between live parts of
hazardous-voltage and extra-low voltage circuits. The test
potential shall be 1000 V plus twice the rated voltage.
Exception: The test potential for units rated at not more than
1/2 HP (373 W output) shall be 1000 V.
61.2 Equipment using an extra-low-voltage circuit shall withstand,
without breakdown, a 40 - 70 Hz potential of 500 V applied for
1 minute between the extra-low-voltage circuit and dead metal
parts. When components such as a temperature limiting
device, motor overload protective device or other protective
device where a short or grounded circuit may result in a risk of
fire, electric shock, or injury to persons are used in the extralow-voltage circuit, the dielectric voltage-withstand test shall
also be conducted between live parts of opposite polarity.
61.3 With reference to Clause 61.2, the test between extra-lowvoltage parts of opposite polarity shall be conducted on
magnet coil windings after breaking the inner coil lead where it
Page 54 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
P
N/A
P
P
conducted on the complete assembly as long as the
components have been separately subjected to this test.
61.4 A 500 V-A or larger transformer, the output voltage of which is
essentially sinusoidal and is capable of being varied, shall be
used to determine compliance with the requirements in
Clauses 61.1 - 61.3. The applied potential shall be increased
gradually from zero until the required test value is reached and
shall be held at that volume for 1 minute. The requirement of a
500 V-A or larger transformer is not required when the high
potential testing equipment maintains the specified high
potential voltage at the equipment during the duration of the
test.
61.5 When the charging current through a capacitor or capacitortype filter connected across-the-line, or from line-to-earth
ground, is large enough to make it impossible to maintain the
required alternating-current test potential, the capacitors and
capacitor-type filters can be tested as described in Clause
61.6.
61.6 The capacitors and capacitor-type filters specified in Clause
61.5 shall be subjected to a directthe rated circuit voltage for equipment rated at more than 250
V. The direct-current test potential shall be maintained for 1
minute without breakdown.
61.7 Components providing a direct current path in parallel with the
insulation to be tested, such as discharge resistors for filter
capacitors and voltage limiting devices, may be disconnected
during the test.
P
P
P
N/A
62.1.1 The strain-relief means provided on the flexible cord of a
product shall be tested as described in Clause 62.1.2. During
this test, there shall be no such movement of the cord as to
indicate that stress would have been transmitted to the
connections.
P
www.tuv.com
Page 55 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
62.1.2 The connections of the cord within the product shall be
P
disconnected. A 15.9 kg (35 lb) weight shall be suspended on
the cord and supported by the product so that the strain-relief
means will be stressed from any angle that the construction of
the product permits. The stress shall be applied for 1 minute.
62.2 Through-cord switch N/A
62.2.1 The connections between the terminals of a through-cord
N/A
switch and the flexible cord shall withstand a 133 N (30 lbf)
pull, applied for 1 minute between the cord and the switch,
without detachment of a conductor from a terminal and without
exposing the uninsulated conductor of the cord.
63 Power-Supply Cord Push-Back Relief Test P
63.1 To determine compliance with Clause 22.5, a product shall be
P
tested in accordance with Clause 63.2 without occurrence of
any of the conditions specified in Clause 22.5 (a) - (c).
63.2 The power-supply cord shall be held 25 mm (1 inch) from the
P
point where the cord emerges from the product. It shall then be
pushed back with casual force until either:
a) The cord buckles or P
b) The force required to push the cord into the product
P
exceeds 25 N (5.6 lbf).
64 Cable-Clamp Test N/A
64.1 If a clamp is used with Type SPT-2 or SVT cords as mentioned
N/A
in the exception to Clause 22.3, six samples of the clamp that
have been secured to the cord in the intended manner shall be
investigated to determine if they are acceptable for the
application. Three samples shall be subjected to the dielectric
voltage-withstand and strain-relief tests in the as-received
condition. The other three samples shall be placed in an air
oven for 168 hours. The oven temperature shall be 10°C
(18°F) higher than the temperature rating of the insulation of
the cord, but not less than 100°C (212°F). The samples shall
comply with the dielectric voltage-withstand test requirements
in Clause 61.1, the value of applied potential being based on
the rating of the product. The potential shall be applied
between the clamp and all conductors spliced together. After
cooling to room temperature, the conditioned samples shall
comply with the Strain-Relief Test, Clause 62.
65 Abnormal Operation Test P
65.1 General P
65.1.1 If the conditions of normal operation are not representative
P
also of abnormal conditions likely to be encountered in actual
service, the product shall not cause a risk of fire, electric
shock, or injury to persons when operated under such
abnormal conditions.
65.1.2 The conditions resulting from abnormal operation of a product
P
shall be confined by the enclosure when the product is
subjected to tests such as blocked armature in a relay,
transformer burnout, stalled rotor, operation without liquids, or
other conditions that may be encountered in service.
66 Thermal Cutoff Test
www.tuv.com
Clause Requirement Test Result - Remark Verdict
65.1.3 An electrode-type product shall be operated as described in
Clause 65.1.4 until ultimate results are obtained. The results
shall not be acceptable if a nonintegral branch-circuit protector
trips during the test. After the test, the product shall comply
with the Starting Test, Clause 55 and the Input Test, Clause
56.
Exception: A product need not be subjected to this test if the
water-level-limiting device operates for 100,000 cycles with no
mechanical or electrical malfunction or significant pitting or
burning of the contacts.
65.1.4 The product shall be mounted as intended and connected to a
source of rated voltage. The drain valve shall be blocked
closed, the water-inlet valve blocked open, each water-levellimiting device shall be bypassed, and the electrodes are to be
electrically connected. In addition, the product shall be
mechanically and electrically isolated from any ground means.
If the hardness of the water may be a factor, the test shall be
performed with a solution of 0.5 g (0.018 oz) of calcium sulfate
(CaSO4) per litre of distilled water. The product shall be
operated until ultimate results are obtained.
65.1.5 A product that is permanently connected to a water supply
shall be operated without water.
66.1 A thermal cutoff shall open the circuit in the intended manner
without causing the short-circuiting of live parts and without
causing live parts to become grounded to the enclosure when
the product is tested as described in Clause 66.2. Opening of
the fuse in the grounding circuit is also not acceptable.
66.2 The enclosure of the product shall be connected through a 3 A
fuse to ground and any other thermally-operated control
devices in the product shall be short-circuited. The supply
voltage shall be as described in Clause 51.2. The product shall
be operated with separate thermal cutoffs five times. Each
thermal cutoff shall perform as intended.
67 Gasket Test
67.1 A material covered in Table 17 that is used for gaskets to, N/A
a) Prevent water entry into an electrical compartment or N/A
b) Prevent hot water leakage external to the product, N/A
shall have physical properties as specified in Table 17 before
and after accelerated aging under the conditions specified in
Table 18.
Gaskets are not required to have physical properties as
specified in Table 17 when the gasket is normally wet during
operation and complies with the test of Clause 68.
67.2 A gasket of material other than those covered in Table 17 shall
be nonabsorptive and shall provide equivalent resistance to
aging and temperature.
68 Liquid-Container Test N/A
68.1 If the deterioration or breakage of a liquid container, seal, or
similar component could increase the risk of electric shock, the
component shall be resistant, as determined by investigation,
to deterioration from the liquid intended to be used in contact
with that component.
Page 56 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
tensile strength and elongation before and after conditioning as
elongation measured before the conditioning, and not less than
A component as mentioned in Clause 68.3 shall be conditioned
of total operating time, the maximum dry operating temperature
www.tuv.com
Page 57 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
68.2 The test procedure for determining whether a component
N/A
complies with the requirements in Clause 68.1 depends upon
the material of which it is composed, its size, shape, mode of
application in the product, and the like. The test procedure
shall include visual inspection for determination of cracks,
deformation, and the like, after accelerated aging, and a
comparison of hardness, tensile strength, and elongation
before and after accelerated aging.
68.3 With reference to Clause 68.2, a component of rubber,
N/A
neoprene, or thermoplastic shall be tested to compare its
described in Clauses 68.4 and 68.5. The tensile strength and
elongation after the conditioning described in Clause 68.4 shall
not be less than 50 percent of the tensile strength and
60 percent after the conditioning described in Clause 68.5.
68.4 A component as mentioned in Clause 68.3 shall be immersed
N/A
for 7 days in the liquid used with the material at a temperature
not less than 10°C (18°F) higher than the maximum wet
operating temperature of the material measured under
intended operating conditions but not less than 70°C (158°F).
68.5
N/A
in an air-circulating oven at the temperature and for the
number of days specified in Table 19. The maximum wet
operating temperature of the material measured under
intended operating conditions shall be used.
Exception: When dry operating time is greater than 5 percent
N/A
shall be used.
68.6 As an alternative to air oven tests as specified in Table 19, the
N/A
acceptability of a liquid container, seal, or diaphragm may be
determined by means of an aging test of the complete product
under service conditions. The duration of the test shall be
representative of the expected service life of the product.
69 Flooding of Live Parts Test N/A
69.1 To determine whether malfunction or breakdown of a timer
N/A
switch, float- or pressure-operated switch, or the like will result
in a risk of electric shock, the product shall be conditioned as
described in Clauses 69.2 and 69.3. The results are not
acceptable if:
a) During and after the conditioning: N/A
1) There is obvious wetting, as described in Clause 69.5, of
N/A
any electrical component; and
2) For a portable or stationary product when evaluated as
N/A
described in Clause 69.4, the leakage current exceeds 5.0 mA;
and
b) After the conditioning, the product: N/A
1) Does not comply with the requirements of the Dielectric
N/A
Voltage-Withstand Test, Clause 61; and
2) For a permanently connected product, the insulation
N/A
resistance between current-carrying parts and exposed noncurrent-carrying metal parts is less than 50,000 ohms.
conditioning, the product shall be tested for compliance with (a)
Backflow from the reservoir of the product into the water supply
at 635 mm (25 in) of mercury vacuum, the shutoff
www.tuv.com
Page 58 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
69.2 The product shall be connected to a water supply. The timer
N/A
switch shall be defeated and the product started. If no
automatic shutoff means is provided, the fill shall be continued
for an additional 15 minutes following the first evidence of
overflow of the reservoir. If a float- or pressure-operated switch
is provided as an automatic shutoff means, actuation of the fill
switch to terminate the fill will also terminate the test. If both a
timer and fill switch are provided, a second test shall be
conducted as described above with the timer operating as
intended and with the fill switch defeated. Both during the after
of Clause 69.1, and after conditioning, it shall be tested for
compliance with (b) of Clause 69.1.
69.3 A rubber barrier or rim seal of a reservoir shall not be removed
N/A
when a test is being conducted to simulate malfunction or
breakdown of a timer switch or of a float- or pressure-operated
switch.
69.4 A portable or stationary product shall be investigated using the
N/A
method described in Clauses 52.2 - 52.6; however, with the
concurrence of those concerned, the duration of the test may
be shortened.
69.5 Obvious wetting signifies wetting by a stream, spray, or
N/A
dripping of water on the component that obviously will be
repeated during each flooding test, but does not signify wetting
by random drops of water that may wet the component by
chance.
70 Backflow Test
70.1 A product that is intended to be connected to a potable water
N/A
N/A
supply shall be tested as described in Clauses 70.2 and 70.3.
system shall not occur during the test.
70.2 With any valve-closing mechanisms on the product, including a
check valve or backflow control, removed or bypassed, a
vacuum tank with a minimum capacity of 379 L (100 US gal)
and equipped with a vacuum pump, gauge, and shutoff valve,
shall be connected to the water-supply hoses. The product
shall be filled with water to the flood level rim and shall be
operated as it would be during intended use. A check valve or
backflow control need not be removed or bypassed if it
complies with the requirements in Clause 70.4.
70.3 With the tank
valve shall be opened rapidly until there is 0 mm (0 in) of
mercury vacuum. The vacuum pump shall then be operated
until either 635 mm (25 in) of vacuum or its limit is reached.
This operation shall be repeated twice - for a total of three
operations. The results shall not be acceptable if there is
evidence of liquid in the vacuum tank.
N/A
N/A
ube shall be connected as closely as is possible to
shall then be calculated by dividing the drop in potential in volts
www.tuv.com
Page 59 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
70.4 To determine whether a check valve or backflow control need
N/A
not be removed or bypassed in accordance with the exception
to Clause 70.2, it shall be tested as follows. A vacuum tank
with a minimum capacity of 379 L (100 US gal) and equipped
with a vacuum pump, gauge, and shutoff valve, shall be
connected to the inlet of a backflow prevention device. A
transparent t
the outlet of the device. The free end of the transparent tube
shall be submerged in water. A 0.813 mm (0.032 in) diameter
wire shall be inserted through the backflow prevention device
to interrupt its closing. Test results shall be acceptable if no
water is drawn into the transparent tube when a constant
vacuum of 635 mm (25 in) of mercury is applied for 30
seconds. The test shall be conducted three times.
71 Bonding-Conductor Test
71.1 A conductor or strap used to bond an electrical enclosure or
N/A
N/A
motor frame and that has a smaller cross-sectional area than
required by Clause 32.7 shall comply with the following
requirements:
a) The conductor or strap shall not open its circuit when
N/A
carrying for 2 minutes a current equal to twice the branchcircuit overcurrent device rating, but not less than 40 A; and
b) None of three samples of the conductor or strap selected
N/A
at random shall open during a limited short-circuit test while
carrying the current as specified in Table 20, and while in
series with a fuse as described in Clause 71.2.
71.2 The circuit for the test described in Clause 71.1(b) shall have a
N/A
power factor of 0.9 to 1.0, and shall be limited to the current
and voltage specified in Table 20. The open-circuit voltage of
the test circuit shall be 100 - 105 percent of the specified
voltage. The circuit shall be connected through a
nonrenewable fuse, the characteristics of which are such that
the fuse will not open in less than 12 seconds when carrying
twice its rated current. The fuse shall have a current rating
equal to that of the branch-circuit overcurrent device to which
the product will be connected, but not less than 20 A. One test
shall be performed on each of three samples of the bonding
conductor.
71.3 The resistance between two parts connected by a bonding
N/A
conductor shall not be more than 0.1 ohms.
71.4 Any acceptable resistance measuring instrument may be used
N/A
to determine whether the product complies with the
requirement in Clause 71.3. If unacceptable results are
obtained, an alternating current of at least 20 A from a power
supply of not more than 12 V shall be passed from the point of
connection of the equipment-grounding means to the metal
part in the grounding circuit, and the resulting drop in potential
shall be measured between the two points. The resistance
by the current in amperes passing between the two points. The
grounding conductor of a power-supply cord shall not be
included in this measurement.
72 Tests on Parts Subject to Pressure
No such part N/A
RATINGS
www.tuv.com
Page 60 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
72.1 To determine that a part or assembly complies with the
N/A
requirement in Clause 47.2, two samples of the part shall be
subjected to a hydrostatic-pressure test. During this test, the
part shall not burst or leak.
Exception: Leakage or rupture of nonmetallic fluid-transfer
N/A
lines, their connections, or gaskets during the pressure test is
acceptable if a repeat test conducted with the fluid they are
intended to contain shows no evidence of presenting risk of
electric shock or injury to persons. Consideration is to be given
to the possibility of wetting of any live electrical part or
insulation.
72.2 Each sample shall be filled with water so as to exclude air, and
N/A
then connected to a hydraulic pump. The pressure shall be
raised gradually to the specified test value and shall be held at
that value for 1 minute.
72.3 A part supported or actuated hydraulically that could result in a
N/A
risk of fire, electric shock, or injury to persons due to pressure
loss, shall comply with the requirements in Clause 72.2 when
tested at a pressure equal to five times the maximum pressure
capable of being developed in the system.
72.4 If a pressure-relief device is required to comply with the
N/A
requirements for Pressure Vessels and Parts Subjected to
Pressure, Clause 47, the control used to limit the pressure in
the vessel shall operate under rated load for 100,000 cycles of
operation and shall prevent the pressure from exceeding 90
percent of the relief-device setting under any condition of
intended operation.
73 Mold Stress-Relief Test P
73.1 Conditioning, as described in Clause 73.2 for polymeric
P
materials used as enclosures, shall not cause softening of the
material as determined by handling immediately after the
conditioning, nor shall there be shrinkage, warpage, or other
distortion of the enclosure, as judged after cooling to room
temperature, that results in any of the conditions specified in
(a) - (d):
a) Reduction of electrical spacings below those specified in
P
Spacings, Clause 42;
b) Exposure of uninsulated parts as judged by the
P
requirements in Protection Against Risk of Injury to Persons Mechanical Protection, Clause 8;
c) Defeating the integrity of the enclosure; or P
d) Causing interference with the intended operation of the
P
equipment.
This test is not required for rigid thermosetting materials. P
73.2 One sample of the complete enclosure or part or an
P
appropriate section of the assembly is to be placed in a fulldraft circulating-air oven maintained at a uniform temperature
at least 10°C (18°F) higher than the maximum temperature
rating of the material measured, but not less than 70°C (158°F)
in any case. The sample is to remain in the oven for 7 hours.
After its removal from the oven and return to room
temperature, the sample is to be examined for compliance with
Clauses 68.1 and 68.2.
P
nationally accepted conventional code, or in a code affirmed by
www.tuv.com
Page 61 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
74 Electrical Ratings P
74.1 A product shall be rated in volts, amperes, and frequency -
P
expressed in one of the following terms: hertz, Hz, cycles-persecond, cps, cycles/second, or c/s. If the product is intended
for operation on a polyphase circuit, the number of phases of
the intended supply circuit shall also be included. See also
Clause 75.13.
A cord-connected product may be rated in watts or kilowatts
P
instead of amperes if the overall full-load power factor is 0.80
or more or if the rating of the cord-connected product is 50 W
or less.
MARKING AND INSTRUCTIONS P
Advisory Note: In Canada, there are two official languages;
P
English and French. Annex B lists acceptable French
translations of the markings specified in this Standard. All
markings required by this Standard may have to be in other
languages to conform with the language requirements where
the product is to be used.
75 Identification and Ratings P
75.1 Markings shall be as follows. All wording shall be equivalent to
P
that in the following Clauses.
75.2 A product shall be legibly and permanently marked where
P
readily visible, without the use of tools, with:
a) The manufacturer's name, trade name, or trademark; P
b) Date or other dating period of manufacture not exceeding
P
any three consecutive months;
c) A distinctive catalog or model number of the equivalent;
P
and
d) The electrical rating. P
The manufacturer's identification may be in a traceable code if
N/A
the product is identified by the brand or trademark of a private
labeler. The date of manufacture may be abbreviated, in a
the manufacturer.
75.3 A marking that is required to be permanent shall be molded,
die-stamped, paint-stenciled, stamped, or etched metal that is
permanently secured, or indelibly stamped on pressuresensitive labels secured by adhesives that comply with the
applicable portions of the requirements in the Standard for
Marking and Labeling Systems, UL 969, and the CSA
Standard for Adhesive Labels, C22.2 No. 0.15.
75.4 With reference to Clause 75.2, the repetition time cycle of a
date code shall not be less than 15 years. The date code shall
not require reference to the manufacturer's records to
determine when the product was manufactured.
75.5 If a manufacturer produces or assembles a product at more
than one factory, each finished product shall have a distinctive
marking by which it may be identified as the product of a
particular factory.
75.6 If the product employs a single motor as its only electric
energy-consuming component, and the motor nameplate is
readily visible with all parts of the product, including the motor,
in place, the electrical rating given on the motor nameplate
need not be duplicated elsewhere on the product.
P
P
N/A
N/A
proper wiring connections are plainly evident, wiring
www.tuv.com
Clause Requirement Test Result - Remark Verdict
75.7 Unless the
terminals shall be marked or the equipment shall be provided
with a suitable wiring diagram to indicate the connections.
75.8 If a product employs a dual-voltage motor, and if the motor
nameplate is used to give the electrical ratings of the product
as described in Clause 75.6, a marking or other means shall
be provided to indicate the voltage for which it is connected
when shipped from the factory. This marking need not be
permanent. If the product employs an attachment plug,
instructions or markings shall be provided to indicate the type
of plug that should be used if the product is reconnected for an
alternate voltage.
75.9 Each part of a product that is not completely assembled when
shipped from the factory shall be marked to indicate the other
parts with which it is intended to be used. For small parts
shipped in an envelope or other package, the marking may be
on the package.
75.10 A small part need not be marked if improper assembly or
attachment of the part, or omission of the part from the
product, would not result in a risk of fire, electric shock, or
injury to persons.
75.11 The catalog number or equivalent designation marked on the
individual part shall be acceptable for the marking required by
Clause 75.9.
75.12 If compliance of a product with any requirement in this
Standard depends upon the functioning of a replaceable
thermal cutoff:
a) The cutoff or link shall be marked with the name or
trademark of the manufacturer of the device and with its
catalog designation or equivalent; and
b) The product shall be marked with a statement that a
replacement link should be of the same type and rating as the
one provided in the product.
75.13 A product using steam under pressure shall be permanently
marked with the maximum pressure rating.
75.14 Cord-connected equipment that requires a time-delay fuse for
starting shall be clearly marked to indicate the type and rating
of the fuse required.
75.15 Motor-operated equipment to be permanently connected to the
power supply shall be marked:
a) For equipment having a single motor, with or without an
electric heater, with the rated full load current of the motor, in
amperes, and of the heater, with its input amperes or watts at
marked voltage; and
b) For equipment having more than one motor, with or
without an electric heater, with
1) The rated full load current in amperes of each motor; N/A
2) The input amperes or watts of the heater, at marked
voltage;
3) The minimum power supply circuit ampacity for each
hazardous voltage circuit; and
4) The maximum overcurrent protective device size for each
hazardous voltage circuit.
75.16 Cautionary markings and instructions shall be permanent and
legible and shall be located on a part that cannot be removed
without impairing the operation of the product.
Page 62 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
Cord connection N/A
No such motor N/A
No such part N/A
N/A
N/A
No such component N/A
N/A
N/A
Not such appliance N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
A marking intended to reduce the risk of injury to a person shall
injury to persons where they may be inadvertently contacted by
"CAUTION: RISK OF ELECTRIC SHOCK. DISCONNECT THE
www.tuv.com
Clause Requirement Test Result - Remark Verdict
75.17 Cautionary markings and instructions intended to instruct the
operator shall be legible and clearly visible to the operator
during use of the product. Other such markings for servicing
instructions shall be legible and clearly visible when such
servicing is being accomplished.
75.18 A marking that is required to be permanent shall meet the
requirements of Clause 75.3. Usage, handling, storage, and
the like, of the product shall be considered in the determination
of the permanence of the marking.
75.19 A residential duct- or plenum-mounted product shall be
permanently marked to indicate that it is for residential use
only.
75.20
be prefixed by the word "CAUTION", "WARNING", or
"DANGER" in capital letters not less than 3.2 mm (1/8 in) high.
This word shall be followed by a brief description of the risk,
such as "risk of electric shock", and the measures that should
be taken to reduce the risk. The words in such a marking shall
be in letters not less than 1.6 mm (1/16 in) high.
75.21 The minimum circuit ampacity required by Clause 75.14(b)(3)
shall be determined as follows. All concurrent load conditions
shall be considered in the determinations. Whichever load
condition provides the highest value shall be used:
a) For a motor group only, a load consisting of two or more
motors, the rated current of the largest motor multiplied by 125
percent, added to the rated currents of all of the other motors;
and
b) for a combination load, a load consisting of one or more
motors, electric heaters, and any other loads, the sum of the
rated currents multiplied by 125 percent.
75.22 The maximum current rating of overcurrent protection for each
hazardous voltage circuit, as required by Clause 75.14(b)(4),
for units having more than one motor, or one or more motors
and other loads, operated from a single supply source, shall be
determined as follows. All concurrent load conditions shall be
considered in the determinations. The rated current of the
largest motor shall be multiplied by 2.25. To that shall be
added the rated current of any other concurrent loads involved
in the circuit. Whichever load condition provides the highest
value shall be used for Clause 75.14(b)(4).
75.23 If cleaning or similar servicing by the user, including
replacement of a fusible link, requires disassembly by means
of a tool and, if such disassembly involves the exposure of an
enclosed or protected live part or a part that involves the risk of
Page 63 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
P
N/A
N/A
N/A
N/A
N/A
N/A
N/A
P
the user, the product shall be permanently marked with a
warning that such servicing shall be done only with the product
disconnected from the electrical supply.
75.24 Where bare live parts are exposed when a door or cover is
removed, the door or cover shall be marked with the following
or its equivalent:
APPLIANCE FROM THE ELECTRIC SUPPLY BEFORE
REMOVING THIS COVER."
75.25 If a product has a moving part that can cause an injury to a
person, a switch other than a momentary contact switch that
controls the motor that drives the part shall have a plainly
marked off position.
N/A
N/A
N/A
www.tuv.com
Page 64 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
75.26 A product that incorporates an interlock device complying with
N/A
Clause 10.8 shall be marked where it is readily visible during
any approach to defeat the interlock to indicate the general
location of the interlock. The marking shall include the word
"WARNING" and the following or the equivalent: "This cover is
provided with an interlock to reduce the risk of electric shock.
Do not defeat its purpose or attempt to service without
removing cover completely".
75.27 A 2-wire, 220 - 240 V product intended for connection to a
N/A
circuit operating at 150 V or less to ground shall be marked
with the word "WARNING" and the following or the equivalent:
"To reduce the risk of electric shock, do not connect to a circuit
operating at more than 150 V to ground".
75.28 There shall be replacement marking adjacent to each fuse or
N/A
fuseholder that is intended to reduce the risk of fire. The
marking shall be readily visible during replacement of the fuse,
and shall consist of the word "CAUTION" and the following or
the equivalent: "To reduce the risk of fire, replace only with
same size and type________fuse". The rating of the fuse shall
be marked in the blank space. For a fuse that is soldered in
place and is perceptible during user servicing, the marking
shall also include the following or the equivalent: "To be
replaced only by qualified service personnel".
75.29 If available space does not permit locating a fuse replacement
N/A
marking adjacent to a fuse or fuseholder, or if more than one
fuse or fuseholder requiring marking is employed, the marking
other than the rating may be at some other location readily
visible during replacement of the fuse.
75.30 Equipment requiring multiple hazardous voltage power supply
N/A
connections shall be marked, in letters not less than 3.2 mm
(1/8 in) high: "CAUTION: THIS EQUIPMENT HAS MORE
THAN ONE CONNECTION TO THE POWER SUPPLY(IES).
DISCONNECT ALL REMOTE POWER SUPPLY
CONNECTIONS BEFORE SERVICING", or the equivalent.
This marking shall be located on all panels providing access to
hazardous voltage uninsulated live parts.
75.31 If the value of the rating determined by applying Clause 75.21
N/A
does not equal a standard current rating of overcurrent
protective device, the marked maximum rating shall be the
next lower standard rating. If the computed value of the
overcurrent protective device is less than the minimum
ampacity of the supply circuit, as determined in accordance
with Clause 75.20, the marked rating of the device shall be
increased to the largest standard overcurrent protective device
rating appropriate for the marked minimum circuit ampacity.
75.32 The maximum current rating of the branch-circuit overcurrent-
N/A
protective device of a non-motor operated appliance shall not
exceed 20 A for a product rating not exceeding 13.3 A and 150
percent of the product rating for a product rating greater than
13.3 A. Standard ratings for overcurrent protective devices are
15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125,
150, 175, and 200 A. If 150 percent of the rating of the product
does not equal one of the aforementioned, it shall be assumed
that the next higher rating or setting of over-current-protective
device will be employed.
76 Informational and Instructional Markings
See manual
P
fuse as described in Clause 55.1, the product shall
Clause 57.1.19 and an adjacent surface is necessary to reduce
alcove from reaching a temperature higher than 90°C when the
77 Operating Instructions
P
www.tuv.com
Page 65 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
76.1 If a product will not start and attain intended running speed
N/A
when connected to a circuit protected by an ordinary - not a
time-delay be plainly and permanently marked "If connected to a circuit
protected by a fuse, use a time-delay fuse with this product" or
with an equivalent wording.
76.2 If a minimum spacing between a product as described in
N/A
the likelihood of the surface from reaching a temperature
higher than 90°C (194°F) when the product is operated as
intended, the product shall be marked "Do not install less than
_______mm (_______in) from a (vertical, horizontal, or the
like) surface". The value necessary to prevent the sides of the
product is tested as described in Normal-Temperature Test,
Clause 57, shall be marked in the allocated space. The
statement shall be legible and shall be located so that it will be
clearly visible during installation and examination of the powersupply connections.
76.3 Unless the proper method of assembly is obvious, a product
N/A
shipped from the factory partially disassembled shall be
provided with clear and detailed assembly instructions.
76.4 An instruction sheet, manual, or booklet shall bear the words
P
"READ AND SAVE THESE INSTRUCTIONS" in all capital
letters, and this wording shall appear above any other written
materials.
76.5 Wiring instructions provided with a product shall not conflict
N/A
with any other requirement in this Standard.
76.6 If servicing or replacement of any component of a product
N/A
requires the removal or disconnection of any protective device,
the instructions provided with the product shall state that such
device shall be replaced in its proper position.
76.7 If user servicing or cleaning operations are contemplated, the
P
instructions shall point out that the source of electrical supply
shall be disconnected prior to beginning any such service or
cleaning operation.
76.8 Complete, clear instructions shall be provided for the
Not such appliance N/A
installation of a product intended to be mounted in a window
frame or to a wall or ceiling. The instructions shall indicate the
correct use of all hardware supplied with the product, and shall
include a step-by-step outline of the mechanical and electrical
operations that must be performed for proper installation and
operation.
77.1 Operating instructions shall be provided with the product that
include the following:
a) Information regarding the risks of fire, electric shock, or
injury to persons that may exist due to use of the product. The
instructions shall caution the user to place the product and
connected cord so that the product is not likely to be upset.
b) Information regarding the potential risk of electric shock
due to overfilling or cleaning the product and removal of the
heating element portion of the product without disconnecting
the power-supply cord.
P
P
P
If a removable barrier or one that has openings for the passage
mechanical and electrical alterations that may be necessary for
www.tuv.com
Clause Requirement Test Result - Remark Verdict
c) Instructions regarding cleaning the product including any
need for disassembly (and reassembly) and any need for the
use of additives.
78 Field Wiring
78.1 If the temperature in the terminal box or the compartment
intended for the supply connections exceeds 75°C (167°F)
during the operational tests, a value suitable for the
temperature measured shall be marked.
The marking shall state, "USE CONDUCTORS SUITABLE
FOR AT LEAST _____°C (____°F)" or the equivalent.
78.2 Other than as indicated in Clause 78.3, a field-wiring terminal
shall be marked "Use copper conductor only," "For use with
aluminum or copper conductors," or with an equivalent
statement appropriate for the terminal. This marking shall be
independent of all other marking on terminal connectors, and
shall be visible during and after installation.
78.3 A terminal intended for the connection of an equipmentgrounding conductor shall not be identified as acceptable for
aluminum conductors.
78.4
of conductors is used to comply with the requirement in Clause
29.4, instructions for use of the barrier shall be provided with
the product.
78.5 A product shall be marked to indicate its intended use. A
permanently connected product not intended for duct- or
plenum-mounting shall be permanently marked "Do not
connect to a duct or plenum" or with equivalent wording.
78.6 If an extra-low-voltage device or part thereof is intended to be
wired in the field, and is intended to become part of either:
a) A Class 1 circuit or N/A
b) A Class 2 circuit wired with Class 1 wiring, N/A
the terminals of the device shall be marked accordingly. N/A
An extra-low-voltage device, or part thereof, that is acceptable
for either a Class 1 or a Class 2 circuit is not required to be so
marked.
78.7 An extra-low-voltage switching or power-consuming device, or
part thereof, that is intended to be wired in the field to become
part of a Class 2 circuit, shall be marked accordingly.
Exception: An extra-low-voltage power-supply device that
includes a transformer shall not be required to be so marked.
78.8 Complete instructions shall be provided that clearly cover the
installation of a product intended for duct- or plenum-mounting.
Such instructions shall include the proper use of all hardware
supplied with the product, and a step-by-step outline of the
Page 66 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
P
No field wiring
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
proper installation and operation.
78.9 If the manufacturer's wiring diagram indicates that a product
may be field connected so as to utilize the blower motor of a
furnace, the wiring diagram shall indicate specific terminals,
such as "Fan Switch Terminals" and "Thermostat Terminals"
for making connection to the electrical circuit of a furnace. The
wiring arrangement shall not affect the intended operation of
the furnace-control system in the heating cycle and shall not
necessitate alteration of factory-installed wiring of the furnace.
78.10 Installation instructions provided with a product as specified in
Clause 78.8 shall include
N/A
N/A
www.tuv.com
Page 67 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
a) The method of installation and user maintenance; N/A
b) A statement that the product is to be located so that
N/A
connection can be made to the source of electrical supply
without the use of an extension cord; and
c) If intended for electrical interconnection, a wiring diagram,
N/A
and the intended location of the field-wiring compartment.
TABLES AND FIGURES P
TABLES P
FIGURES P
SUPPLEMENT SA - SMART ENABLED HUMIDIFIERS N/A
SA1 Scope N/A
SA1.1 These requirements apply to humidifiers intended to receive
N/A
and respond to communication signals or data relating to
power billing rate or demand response or communication
signals from a remote user interface, such as a smart phone or
computer.
SA1.2 Appliances covered by SA1.1 are commonly identified as
N/A
"smart" appliances or "smart enabled" and may interact with
the "Smart Grid," as described by the US Energy
Independence and Security Act of 2007, or other
communication networks not identified as "Smart Grid."
SA1.3 These requirements contemplate "smart enabled" technology
N/A
as described by the U. S. Energy Independence and Security
Act of 2007 that is integral with the appliance or incorporated
as an accessory (wired to the appliance or wireless with a
corresponding appliance receiver) on the appliance or in the
same occupancy as the appliance.
SA1.4 These requirements supplement those specified in this
N/A
Standard.
SA1.5 These requirements encompass accessory devices to which
N/A
multiple appliances may communicate and be smart enabled
by providing direction for investigation of such devices in
addition to the requirements of standards generally applicable
to those devices.
SA1.6 These requirements do not address the integrity of any output
N/A
signal or data to the network devices or interoperability with
other devices.
SA1.7 These requirements do not apply to communication network
N/A
devices that control appliances via general purpose power
ON/OFF, building wiring devices, panelboard mounted
devices, or utility meters.
SA1.8 These requirements apply to wired or wireless remote
N/A
commands from the user by way of:
a) Controls only capable of communicating within line-of-
N/A
sight of the appliance (e.g. infrared wireless);
b) Short range controls only capable of communicating
N/A
within proximity or same occupancy of the appliance but not
necessarily within line-of-sight (e.g. short-wave radio
frequency); or
c) Long range telecommunication controls without proximity
N/A
limits (e.g. WiFi, local area networks, wide area networks).
SA1.9 These requirements may for example include, but are not
N/A
limited to, the following remote initiated functions:
SA2.1.1 Controls that respond to external communication signals or
data shall comply with the construction and performance
requirements of the Standard for Automatic Controls for
Household and Similar Use, Part 1: General Requirements, UL
60730-1; and the Standard for Automatic Electrical Controls for
Household and Similar Use - Part 1: General Requirements,
CAN/CSA-E60730-1. The controls are tested as an operating
(regulating) control utilizing the parameters specified in Table
SA2.1. If the control also incorporates protective (limiting)
functions, these control functions shall be evaluated to the
requirements for protective controls.
SA2.1.2 With respect to SA2.1.1, the requirement is not applicable to
controls located in low voltage circuits where the maximum
power available does not exceed 15 W. This does not exempt
the control from investigation for compliance with SA3.1.
SA2.1.3 With respect to SA2.1.1, compliance with the Standard for
Solid-State Controls for Appliances, UL 244A, taking into
account criteria comparable to that specified in Table SA2.1 is
considered to fulfill this requirement. Compliance with the
Standard for Automatic Electrical Controls for Household and
Similar Use, Part 1: General Requirements, UL 60730-1, the
Standard for Automatic Electrical Controls for Household and
Similar Use - Part 1: General Requirements, CAN/CSAE60730-1 and/or the applicable Part 2 standard from the UL
60730 and CAN/CSA-E60730 series fulfills the UL 244A
requirements.
SA2.1.4 With respect to SA2.1.1, a communication device that is not
integral with the appliance control (e.g. on a separate printed
wiring board) and complying with the Standard for Information
Technology Equipment - Safety - Part 1: General
Requirements, UL 60950-1 or CAN/CSA C22.2 No. 60950considered to fulfill this requirement.
SA2.1.5 For the purposes of application of the Standard for Automatic
Controls for Household and Similar Use, Part 1: General
Requirements, UL 60730-1, and the Standard for Automatic
Electrical Controls for Household and Similar Use - Part 1:
General Requirements, CAN/CSA-E60730-1, EMC emissions
testing of H23 is not applicable to controls that are integral with
the appliance or incorporated as an accessory (wired or
wireless) on the appliance or in the same occupancy as the
appliance.
Page 68 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
N/A
N/A
N/A
N/A
N/A
N/A
N/A
SA2.1, the control shall remain operational and comply with the
, and the Standard for Automatic Electrical Controls
SA2.4
Communication conductors and cables
www.tuv.com
Clause Requirement Test Result - Remark Verdict
SA2.1.6 With respect to the Endurance Testing indicated in Table
Electric Strength Test of the Standard for Automatic Controls
for Household and Similar Use, Part 1: General Requirements,
UL 60730-1
for Household and Similar Use - Part 1: General
Requirements, CAN/CSA-E60730-1.
SA2.1.7 When the control enclosure forms part of the overall appliance
enclosure, the enclosure material shall have a flammability
rating in accordance with Clause 5.2.
SA2.2 Separation of circuits
SA2.2.1 The separation of communication circuits from power and
control circuits shall be evaluated for risk of electric shock in
accordance with Clause 29, Separation of Circuits.
SA2.3 Communication and display devices
SA2.3.1 An external communication or display device, such as a router
or monitor, provided as an accessory for use with the
appliance, shall comply with the Standard for Information
Technology Equipment - Safety - Part 1: General
Requirements, UL 60950-1, or CAN/CSA C22.2 No. 60950-1.
SA2.3.2 The power supply cord of an external communication or
display device shall comply with this Standard or the Standard
for Information Technology Equipment - Safety - Part 1:
General Requirements, UL 60950-1, or CAN/CSA C22.2 No.
60950-1, except Types NISP-2, NISPE-2, and NISPT-2 are not
permitted.
SA2.3.3 With respect to SA2.3.2, the requirement is not applicable to
external communication or display devices powered via
connection to communication or data ports on the appliance
which are located in low voltage circuits. See SA2.4.
SA2.3.4 If the external communication or display device is grounded via
bonding with the appliance enclosure, the bonding
requirements of this Standard shall be applied.
SA2.3.5 Grounding connections for external communication or display
devices shall be made before power connections and shall
disconnect only after power connections are disconnected
("make first, break last").
SA2.3.6 Functional grounding shall not be relied upon for equipment
grounding or bonding. Functional grounding is grounding of a
point in an appliance or in a system that is necessary for a
purpose other than safety.
SA2.3.7 When power is supplied to an external communication or
display device by an interconnecting supply cord, it shall
comply with Clauses 21.2 - 21.4 and 21.6 of this Standard and
be supplied with a bushing(s) and strain relief as described in
Clauses 22 and 23.
SA2.4.1 External communication conductors and cables shall comply
with the Standard for Information Technology Equipment Safety - Part 1: General Requirements, UL 60950-1, or
CAN/CSA C22.2 No. 60950-1.
SA2.4.2 Communication conductors and cables within the appliance
shall be evaluated as internal wiring in accordance with this
appliance standard.
Page 69 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
connectors, such as NEMA or IEC standardized configurations,
www.tuv.com
Clause Requirement Test Result - Remark Verdict
SA2.5 Communication connectors
SA2.5.1 Communication connectors and data ports accessible to the
user and service personnel shall comply with the Standard for
Information Technology Equipment - Safety - Part 1: General
Requirements, UL 60950-1, or CAN/CSA C22.2 No. 60950-1.
Otherwise, communication connectors and data ports shall be
evaluated in accordance with this Standard.
SA2.5.2 With the exception of communication-on-power-line
technology, an appliance plug, flatiron plug, jumbo appliance
plug, motor attachment plug or other conventional power cord
shall not be used for communication circuit connections.
SA2.6 Smart enabled or remote operation
SA2.6.1 Any functionality enabled in response to external
communication or data signals shall be considered when
determining the normal and abnormal conditions of the
appliance.
SA2.6.2 The appliance shall include a means for the consumer to
override any smart enabled or remote operation commands. A
flexible supply cord with an attachment plug can serve as the
override means if the appliance:
a) Is portable; N/A
b) Does not employ a motor rated more than 1/3 HP (250 W
output);
c) Does not have a switch or control with a marked OFF
position; and
d) Is provided with instructions for unplugging the appliance
to override smart enabled or remote functions.
SA2.6.3 A control on the appliance shall require manual adjusted
setting before the appliance can be operated in a smart
enabled or remote operation mode. Examples for initiating this
setting include, but are not limited to, pressing a button,
pressing and holding a button, activating a switch or latch, setup and connection to a local WiFi network, etc. Once a smart
or remote operation mode is enabled, it may remain in this
state until mode of operation is manually disabled. See SA3.3.
Note 1: This requirement is not applicable to a control only
capable of communicating to the appliance within line-of-sight.
Note 2: This requirement is not applicable to appliances with
remote functions limited to monitoring only.
SA3 Functional Safety
SA3.1 Controls actuated in response to external communication or
data signals shall not introduce a hazardous operating
condition or a state that may lead to a hazardous operating
condition beyond that which exists through manual controls
and operating conditions.
SA3.2 With respect to SA3.1, the control shall not: N/A
a) Render inoperative any protective control or protective
control function within the appliance;
b) Alter the response to or expected performance of user
actuation of controls, movement of doors, covers or lids or
contact with external and functional surfaces of the appliance
resulting in exposure of hazardous electrical parts, moving
parts, normally inaccessible hot parts, or radiation;
Page 70 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
of the appliance protective control(s) and therefore is incapable
s determined using the communication
SA5
Markings and Instructions
www.tuv.com
Clause Requirement Test Result - Remark Verdict
c) Alter the order of appliance control response (e.g. force a
protective control to operate where normally another control
would respond reset any protective manual reset temperature
control or shutoff feature); or
d) Supersede the response of any protective (limiting)
control.
SA3.3 Compliance with SA2.6.3 and SA3.1 shall be determined using
methods appropriate for determining the performance and
reliability of protective control functions in accordance with
Clauses 37, 38, and 40.
SA3.4 With respect to SA3.3, the performance and reliability
evaluation is not required if it is obvious from examination of
circuit diagram(s) that the control operates wholly independent
of adversely affecting their operation.
SA4 Resistance to Electro Magnetic Phenomena (Immunity)
SA4.1 The appliance protective (limiting) control functions shall
remain operable when subjected to conducted or radiated
emissions from integral communication circuitry of the smart
enabled control or any accessory thereof.
SA4.2 Compliance with SA4.1 i
circuit source(s) adjusted to its maximum factory setting(s) in
addition to any intermediate settings that are determined to
present a risk to the acceptable operation of the protective
control function. The protective (limiting) control function shall
be tested in accordance with H.26.4 - H26.14 of the Standard
for Automatic Controls for Household and Similar Use, Part 1:
General Requirements, UL 60730-1 and the Standard for
Automatic Electrical Controls for Household and Similar Use Part 1: General Requirements, CAN/CSA-E60730-1, as
appropriate.
SA4.3 With respect to SA4.2, if it is determined that the source within
the appliance or its accessory(ies) produces emissions
addressed by the standard test conditions of Electromagnetic
compatibility (EMC) requirements - immunity, H.26 of the UL
60730-1 and CAN/CSA-E60730-1, it is not necessary to repeat
the tests.
SA5.1 Accessory devices shall be marked with the manufacturer's
name (or symbol), a part or catalog number, and electrical
ratings. Literature packaged with the accessory shall identify
the appliance(s) for which it is intended to be used. Additional
literature or markings shall be required, as applicable, when
applying requirements from the following standards:
a) UL 60730-1 and CAN/CSA-E60730-1; and/or N/A
b) UL 60950-1 or CAN/CSA C22.2 No. 60950-1. N/A
SA5.2 With respect to SA5.1, accessories not affecting compliance of
the appliance with Clause SA3 need not identify the intended
appliances.
SA5.3 With respect to SA5.1, battery operated devices may be
marked with information identifying the appropriate battery(ies)
in lieu of electrical ratings.
SA5.4 All electrical and communication cable connections shall be
identified for their purpose.
Page 71 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
The manual means of actuating delayed or remote operation of
carrying metal parts of the product that are likely to
C2 Production Line Dielectric Voltage
-
Withstand Tests
www.tuv.com
Clause Requirement Test Result - Remark Verdict
SA5.5 Literature packaged with the appliance shall identify the
intended accessory device(s). A specific part or catalog
number is not required if the manufacturer identifies a "family"
of devices and limits the identification of devices within that
family to those which are investigated in combination with the
appliance.
SA5.6 With respect to SA5.3, accessories not affecting compliance of
the appliance with SA3 are not required to be identified.
SA5.7
the appliance shall be clearly indicated via marking adjacent to
the user actuator. See SA2.6.3.
Note: Not required when the attachment plug is used to serve
as the enable and disable means in accordance with SA2.6.2.
SA5.8 User instructions provided with the appliance shall identify
accessories, their method of connection, operation and any
precautions to be taken in their use. The means to enable
delayed or remote operation shall be identified, including an
illustration depicting the location of the actuating means with
information on how to enable or disable the function.
SA5.9 An illustration shall not be required to be included in the
instruction manual when the attachment plug is used to serve
as the enable and disable means in accordance with SA2.6.2.
Instructions shall indicate how the attachment plug is to be
used to enable and disable the product.
Page 72 of 90
UL 998 & CSA C22.2 No. 104
Report No.: CN22UKC1 001
N/A
N/A
N/A
N/A
N/A
N/A
C1 Grounding-Continuity Test N/A
C1.1 Each product that has a power-supply cord having a grounding
C1.2 Any indicating device, such as an ohmmeter, a battery-and-
C1.3 Only a single test needs to be conducted if the accessible
C2.1 Each product shall withstand without electrical breakdown, as
a) Between the primary wiring, including connected
Annex A
Standards for components
Annex B P
French translations and markings P
Annex C
Manufacturing and Production Tests
conductor shall be tested, as a routine production-line test, to
determine that grounding continuity exists between the
grounding blade of the attachment plug and the accessible
non-currentbecome energized.
buzzer combination, or the like, may be used to determine if
the product complies with the grounding continuity requirement
in Clause C1.1.
metal selected is conductively connected by design to all other
accessible metal.
a routine production-line test, the application of a potential at a
frequency within the range of 40 - 70 Hz, or a DC potential:
components, and accessible dead metal parts that are likely to
become energized; and
N/A
N/A
N/A
P
P
P
P
P
P
P
www.tuv.com
Page 73 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
b) Between primary wiring and accessible extra-low-voltage,
P
42.4 V peak or less, metal parts, including terminals.
C2.2 The production-line test shall be conducted in the time and at
P
the potential specified in either Condition A or Condition B of
Table C1.
C2.3 For equipment employing extra-low-voltage circuits, the test
P
shall be conducted with the extra-low-voltage circuit connected
to the cabinet, chassis, or other dead metal part so that the
potential applied between the hazardous-voltage live parts and
dead metal parts is simultaneously applied between
hazardous-voltage live parts and extra-low-voltage circuits.
C2.4 The test shall be conducted when the product is fully
P
assembled. It is not intended that the product be unwired,
modified, or disassembled for the test.
C2.5 With respect to Clause C2.4, a part, such as a snap cover or
N/A
friction-fit knob, that interferes with the performance of the test
shall not be required to be in place.
C2.6 With respect to Clause C2.4, the test is not prohibited from
N/A
being performed before final assembly when the test
represents that for the completed product. Any component not
included shall not affect the results with respect to
determination of possible risk of electric shock resulting from
misfiring, defective component, insufficient spacings, and
similar conditions.
C2.7 Solid-state and similar components that are capable of being
No such circuit N/A
damaged by a secondary effect (induced voltage surge,
excessive heating and similar adverse conditions) of the test
may be short-circuited by means of a temporary electrical
jumper or the test may be conducted without the component
electrically connected, as long as the wiring and terminal
spacings are maintained. Additionally, components providing a
direct-current path in parallel with the insulation to be tested
(primary to dead-metal) may be disconnected during the test.
Examples of such components are discharge resistors for filter
capacitors and voltage limiting devices such as transient
voltage suppressors (other than capacitors).
C2.8 The test equipment shall have: P
a) A means of indicating the test potential; P
b) An audible or visual indicator of electrical breakdown; and P
c) Either a manually reset device to restore the equipment
P
after electrical breakdown or an automatic reject feature of any
noncomplying unit.
When an AC test potential is applied, the test equipment shall
P
include a transformer having an essentially sinusoidal output.
C2.9 When the output of the test-equipment transformer is less than
P
500 V-A, the equipment shall include a voltmeter in the output
circuit to directly indicate the test potential.
C2.10 When the output of the test-equipment transformer is 500 V-A
P
or more, the test potential may be indicated:
a) By a voltmeter in the primary circuit or in a tertiary-
P
winding circuit;
b) By a selector switch marked to indicate the test potential;
P
or
terminal shall be connected to
www.tuv.com
Page 74 of 90
Report No.: CN22UKC1 001
UL 998 & CSA C22.2 No. 104
Clause Requirement Test Result - Remark Verdict
c) By a marking in a readily visible location to indicate the
P
test potential for equipment having a single test-potential
output. When a marking is used without an indicating
voltmeter, the equipment shall include a positive means, such
as an indicator lamp, to indicate that the manually reset switch
has been reset following a dielectric breakdown.
C2.11 Test equipment other than that described in C2.6 - C2.8
N/A
complies with the intent of the requirement when found to
accomplish the intended factory control.
C2.12 During the test: P
a) The primary switch shall be in the on position; P
b) Both sides of the primary circuit of the product shall be
P
connected together and to one terminal of the test equipment;
and
c) The second test-equipment
P
accessible dead metal.
C2.13 A product having circuits that are resistive, high-impedance
N/A
windings, or similar parts that are not subject to excessive
secondary-voltage build-up in case of electrical breakdown
during the test, may be tested:
a) In the off position, or in the on position with only one side
N/A
of the primary circuit connected to the test equipment when the
product has a single-pole primary switch or
b) With only one side of the primary circuit connected to the
N/A
test equipment, when the product is not provided with a singlepole primary switch.
www.tuv.com
Page 75 of 90
Report No.: CN21979V 001
UL 1310
Clause Requirement Test Result - Remark Verdict
7 Mechanical Assembly P
8 Enclosure p
9 Protection Against Corrosion No such part N/A
10 Switches No switch N/A
11 Protective Devices P
12 Components P
13 Coil Insulation P
14 Input Connection p
15 Output Connections P
16 Accessibility of Live Parts Considered in end product
P
17 Live Parts P
18 Strain Relief N/A
19 Internal Wiring P
20 Separation of Circuits P
21 Insulating Materials P
22 Printed Wiring Boards P
23 Grounding No grounding N/A
24 Spacings P
PERFORMANCE P
25 General P
www.tuv.com
Page 76 of 90
Report No.: CN21979V 001
UL 1310
Clause Requirement Test Result - Remark Verdict
26 Leakage Current Test P
27 Leakage Current Test and Dielectric Voltage Withstand Test
P
After Humidity Exposure
28 Maximum Output Voltage Test P
29 Maximum Input Test P
30 Output Current and Power Test P
31 Calibration of Overcurrent Protection Devices Test N/A
32 Full-Load Output Current Test P
33 Normal Temperature Test P
34 Dielectric Voltage Withstand Test P
35 Endurance Test on Overcurrent- and Overtemperature-
N/A
Protective Devices
36 Overload and Endurance Tests on Switches and Controls N/A
37 Overload Test on Secondary Switches N/A
38 Operation Test N/A
39 Abnormal Tests P
40 Tests on Insulating Materials P
41 Strain Relief Test Considered in end product N/A
42 Push-Back Relief Test Considered in end product N/A
43 Direct Plug-In Blade Secureness Test N/A
44 Direct Plug-In Security of Input Contacts Test N/A
45 Security of Output Connectors Test N/A
46 Abuse Tests Considered in end product N/A
47 Bonding Conductor Test N/A
MANUFACTURING AND PRODUCTION TESTS N/A
48 Dielectric Voltage Withstand Test N/A
49 Grounding Continuity Test N/A
RATING P
50 General P
MARKING N/A
51 General Component power supply,
N/A
part of end product
52 Cautionary and Warning Markings N/A
53 Application of Labeling N/A
www.tuv.com
Clause Requirement Test Result - Remark Verdict
INSTRUCTIONS N/A
Page 77 of 90
Report No.: CN21979V 001
UL 1310
54 Instruction Manual Component power supply,
part of end product
55 – 66 OUTDOOR USE Indoor used N/A
67 - 72 PERMANENTLY-CONNECTED UNITS FOR CONNECTION
TO A WIRING SYSTEM
73-90 PERMANENTLY-CONNECTED UNITS FOR INSTALLATION
IN AN OUTLET BOX
81-82 POWER UNITS FOR INSTALLATION IN AIR-HANDLING
SPACES
83-89 POWER UNITS SUPPLIED FROM INFORMATION
TECHNOLOGY EQUIPMENT DATA PORTS
90- 98 FLUSH DEVICE COVER PLATES WITH INTEGRAL POWER
SUPPLY
N/A
N/A
N/A
N/A
N/A
N/A
www.tuv.com
Page 78 of 90
Report No.: CN21979V 001
C22.2 No. 223
Clause Requirement Test Result - Remark Verdict
4 Construction P
4.1 General requirements P
4.2 General P
4.3 Sources of Fire Hazard P
4.4 Enclosures P
4.5 Mechanical Assembly P
4.6 Supply Connections P
4.7 Internal Wiring P
4.8 Electrical Insulating Materials P
4.9 Transformers and Magnetic Components P
4.10 Switches No switch N/A
4.11 Electrical Spacings P
4.12 Output Connections P
4.13 Strain Relief and Blade Retention N/A
4.14 Open-Circuit Secondary Voltage P
4.15 Provisions for Limiting Output Current P
4.16 Secondary Circuit Protection P
4.17 Grounding and Bonding No Grounding N/A
4.18 Printed Wiring Boards P
4.19 Deleted -
4.20 Ground-Fault Circuit Interrupters No Such device N/A
4.21 Backfeed protection Not such appliance N/A
5 Marking
Component power supply,
N/A
part of end product
5.1 Permanent and visible markings N/A
5.2 Applicable warnings N/A
5.3 Polarity N/A
5.4 Telephone type output connectors for designated use N/A
5.5 Telecommunication applications N/A
5.6 Duty cycle N/A
5.7 Toy power supply N/A
5.8 Outdoor Use N/A
6 Tests P
6.1 General P
6.2 Test Conditions P
6.3 Rating P
6.4 Temperature (Normal) P
www.tuv.com
Clause Requirement Test Result - Remark Verdict
6.5 Dielectric Strength P
6.6 Leakage Current P
6.7 Secondary Circuit Protection N/A
6.8 Abnormal P
6.9 Drop and Impact P
6.10 Strain Relief and Blade Retention N/A
6.11 Overload and Endurance (Primary Circuit Switches) N/A
6.12 Securement of Components P
6.13 Securement of removable, folding, or retractable blades N/A
6.14 Insulating material P
6.15 Compression (rod) N/A
6.16 Deformation (non-metallic enclosures) N/A
6.17 Rain N/A
Page 79 of 90
C22.2 No. 223
Report No.: CN21979V 001
6.18 Water immersion N/A
6.19 UV Exposure Conditioning N/A
www.tuv.com
Page 80 of 90
List of Critical Components:
Object/part
no.
Plug
Manufacturer/
Trademark
CHING CHENG WIRE
MATERIAL CO LTD
(Alternative)
ZHONGSHANCITY
HONGSHANCHUAN
POLYMER MATERIALS
CO LTD
(Alternative)
SHENZHEN HENGWELL ELECTRIC CO
LTD
Power cord
CHING CHENG WIRE
MATERIAL CO LTD
(Alternative)
ZHONGSHANCITY
HONGSHANCHUAN
POLYMER MATERIALS
CO LTD
(Alternative)
SHENZHEN HENGWELL ELECTRIC CO
LTD
(Alternative)
ZHONGSHANCI TY
HONGSHANCHU AN
POLYMER MATERIALS
CO LTD
Connector on
PCB (AC IN)
SHENZHEN LILUTONG
CONNECTOR CORP.,
LTD.
Connector on
PCB(DC
E I DUPONT DE
NEMOURS & CO INC
OUT)
Enclosure
CHI MEI
CORPORATION
Control
panel, Water
CHI MEI
CORPORATION
tank, Housing
of sensor
Gasket
SHIN-ETSU SILICONE
TAIWAN CO LTD
Tubing
DONGGUAN LING
FREE HARDWARE
PLASTICS PRODUCT
CO LTD
PCB
Kingboard
Laminates(Macao
commercial offshore)Ltd
Report No.: CN22UKC1 001
Type/Model Technical Data Standard
Mark(s) of
Conformit
y
EL-451A
HSC-201
AC 125V, 10A
AC 125V, 10A
UL 817, CSAC22.2 No. 21
UL 817
CAN/CSA-
UL
E88446
UL
E334525
C22.2 No. 21
DHT11
AC 125V, 10A
UL 817
CAN/CSA-
UL
E312615
C22.2 No. 21
SPT-2 AC 300V,
18AWG x 2C,
105°C
UL62
CSA-C22.2 No.
49
UL
E162604
SPT2 AC 300V,
18AWG x 2C,
105°C
SPT-2 AC 300V,
18AWG x 2C,
105°C
SPT-2
300V, 2X18AWG,
105°C
LLT-M15
10A, 300V, 18AWG
UL62
CSA-C22.2 No.
49
UL62
CSA-C22.2 No.
49
UL 62, CSA
C22.2 No. 49
UL 2238
UL
E470030
UL
E312632
UL
E470030
UL
E481414
FR70G25V0
PA66, V-0, 130°C
UL94, UL 746C,
CSA C22.2 No.
UL
E41938
0.17
GC-8400A(a)
PA-765(+)
PC, V-0, 120°C. Min.
thickness 2.0 mm.
ABS, V-1, 80°C. Min.
Thickness 1.5mm.
UL94, UL 746C,
CSA C22.2 No.
0.17
UL94, UL 746C,
CSA C22.2 No.
UL E56070
UL E56070
0.17
KE-931TU
SI, HB, 150°C.
UL94, UL 746C,
CSA C22.2 No.
UL
E174951
0.17
LING FREE
PTFE TUBE
300V, 200°C
UL 224
UL
E352366
(300V)
KB-3150, KB4150, KB-5150,
KB-7150
94V-0,130°C
UL 94, UL 746
UL
E123995
www.tuv.com
Object/part
no.
(Alternative)
Current fuse
(F1)
(Alternative)
(Alternative)
(Alternative)
(Alternative)
(Alternative)
(Alternative)
(Alternative)
(Alternative)
(Alternative)
Y capacitor
(CY1, CY2)
(Alternative)
Inductor
(LF1)
-Winding
Page 81 of 90
Manufacturer/
Trademark
SHANDONG JINBAO
TECH-INNOV
Type/Model Technical Data Standard
ZD-95(G)F ZD90F
CORPORATION
DONGGUAN CHEVRON
SET
ELECTRONIC
TECHNOLOGY CO LTD
LITTELFUSE INC 392 +, &
Zhongshan Lanbao
TSP
Electrical
Conquer Electronics Co.,
MST
Ltd.
Dongguan Better
932
Electronics Technology
Co., Ltd.
Dongguan Hongda
2009
Electronic Technology
Co., Ltd.
Suzhou Walter
2010
ElectronicCo. Ltd.
XC Electronics (Shen
5TE
Zhen)Corp. Ltd.
Shenzhen Lanson
SMT
ElectronicsCo. Ltd.
DONGGUAN HONGDA
52T
ELECTRONIC
TECHNOLOGY CO LTD
SHANTOU HEYE
CD, CE
ELECTRONIC CO LTD
SHANTOU HIGH-NEW
CD, CE
TECHNOLOGY
DEVELOPMNT ZONE
SONGTIAN
ENTERPRISE CO LTD
ZHONGSHAN CITY
RL0608-130L
XINWEITE
ELECTRONICS
FACTORY
HUZHOU JUCHENG
QA/155
ELECTRONICS
CO.,LTD
94V-0,130°C
250V, T2A
250V, T2A
250V, T2A
250V, T2A
250V, T2A
250V, T2A
250V, T2A
250V, T2A
250V, T2A
250V, T2A
AC250V, 2200PF,
125°C
AC250V, 2200PF,
125°C
15uH
155ºC
Report No.: CN22UKC1 001
Mark(s) of
Conformit
y
UL 94, UL 746
UL 248-1,
CSA-C22.2 No.
UL
E141940
UL
E358589
248.1
UL 248-1,
UL E67006
CSA-C22.2 No.
248.1
UL 248-1,
CSA-C22.2 No.
UL
E485357
248.1
UL 248-1,
CSA-C22.2 No.
UL
E82636
248.1
UL 248-1,
CSA-C22.2 No.
UL
E300003
248.1
UL 248-1,
CSA-C22.2 No.
UL
E318938
248.1
UL 248-1,
CSA-C22.2 No.
UL
E56092
248.1
UL 248-1,
CSA-C22.2 No.
UL
E249609
248.1
UL 248-1,
CSA-C22.2 No.
UL
E221465
248.1
UL 248-1,
CSA-C22.2 No.
UL
E318938
248.1
UL 60384-14,
CSA E60384-
UL
E472346
14
UL 60384-14,
CSA E60384-
UL
E208107
14
UL 998, CSA
C22.2 No. 104
Tested
with
appliance
UL 1446
UL
E484764
www.tuv.com
Object/part
no.
-Bobbin
-Insulation
tape
Transformer
T1
-Bobbin
-Winding
(Alternative)
(Alternative)
-Triple
insulated
winding
(Alternative)
-Insulation
Tape
(Alternative)
(Alternative)
(Alternative)
-TEFLON
TUBE
(Alternative)
Page 82 of 90
Manufacturer/
Trademark
CHANGSHU SOUTHEAST PLASTIC CO LTD
DONGGUAN BLEN
ELECTRONIC
TECHNOLOGY CO LTD
ZHONGSHAN CITY
XINWEITE
ELECTRONICS
FACTORY
CHANG CHUN
PLASTICS CO.,LTD
SHANTOU SHENGANG
ELECTRICAL
INDUSTRIAL CO LTD
DONG GUAN YIDA
INDUSTRIAL CO LTD
PACIFIC ELECTRIC
WIRE & CABLE
(SHENZHEN) CO LTD
Shenzhen Darun Science
and Technology Co., Ltd
WUHU OULY
ELECTRONICS CO LTD
DONGGUAN BLEN
ELECTRONIC
TECHNOLOGY CO LTD
JINGJIANG JINGYANG
INSULATING PRODUCT
CO LTD
SUZHOU MAILADUONA
ELECTRIC MATERIAL
CO LTD
SHENZHEN XINHUAHUI
ADHESIVE
TECHNOLOGY CO LTD
ZIGONG
ZHONGDIANCHENGUA
NG NEW MATERIAL CO
LTD
FLUOTECH
INDUSTRIAL
(HUIZHOU) CO LTD
Report No.: CN22UKC1 001
Type/Model Technical Data Standard
PF2D1-851J
V-0,150ºC, min. 1.5
mm thick
UL94, UL
746C, CSA
C22.2 No. 0.17
BL002
YK-055C
130ºC
Input:ac120V~ac240V
50Hz,60Hz:
UL 510A
UL 998, CSA
C22.2 No. 104
Output 1: DC34V,
0.8A
Output 2: DC12V,
0.2A;
Class B
T375J
V-0, 150ºC, min. 0.75
mm thick
UL94, UL
746C, CSA
C22.2 No. 0.17
xUEW/155, QA-
x/155
QA-1/155,
155°C
155ºC
UL1446
UL 1446
2UEW/155
UEWH/U
DRTIW-B
TIW-B
BL002
JY-133
JY312#
HMT803
CG-S
TFT
180ºC
130ºC
130ºC
130ºC
130ºC
130ºC
130ºC
600V, 200ºC
300V, 200ºC
UL 1446
UL 2353
UL 2353
UL 510A
UL 510A
UL 510A
UL 510A
UL 224
UL 224
Mark(s) of
Conformit
y
UL
E136137
UL
E480647
Test with
appliance
UL
E59481
UL
E239508
UL
E344055
UL
E201757
UL
E335841
UL
E466302
UL
E480647
UL
E309872
UL
E188295
UL
E328315
UL
E493457
UL
E175982
www.tuv.com
Object/part
no.
DC Fan
DC Suction
pump
Internal wire
(Alternative)
(Alternative)
(Alternative)
Ultrasonic
generator
UV LED
Label
Page 83 of 90
Manufacturer/
Trademark
Zhongshan Ningling
Type/Model Technical Data Standard
5015
Electronic Technology
Co., Ltd.
JINGNUO
GUANG DONG XIN
QT-150L/H
1007/2468
LONG ENTERPRISE CO
ZHONGSHAN HE YI
1007/2468
ELECTRICAL
APPLIANCES
FACTORY
ZHONGSHAN CITY
1007/2468
BOYU WIRE CO LTD
FOSHAN SHUNDE
1007/2468
BEIJIAO HUA DA
ELECTRIC INDUSTRIAL
CO LTD
HUNAN JIAYEDA
JYD
ELECTRONICS CO.,
LTD
Hubei DUVTEK
Technology Co., Ltd.
L280-
PSC1F20M001
Various Various
Report No.: CN22UKC1 001
12V, 0.04A,
2800RPM±10%
DC12V, 100mA
22-26AWG, 80°C,
300V
22-26AWG, 80°C,
300V
22-26AWG, 80°C,
300V
22-26AWG, 80°C,
300V
Φ20mm, 1.65-1.75
MHz
5-7V, 2-4mW, 270285nm
Min. 60°C, suitable for
applied surface.
UL 998, CSA
C22.2 No. 104
UL 998, CSA
C22.2 No. 104
UL 758, CSA
C22.2 No. 210
UL 758, CSA
C22.2 No. 210
UL 758, CSA
C22.2 No. 210
UL 758, CSA
C22.2 No. 210
UL 998, CSA
C22.2 No. 104
UL 998, CSA
C22.2 No. 104
UL 969
Mark(s) of
Conformit
y
Tested
with
appliance
Tested
with
appliance
UL
E207567
UL
E313976
UL
E314089
UL
E124622
Test with
appliance
Test with
appliance
UL
www.tuv.com
Product photos
Page 84 of 90
Report No.: CN22UKC1 001
Figure 1: Overview
location
www.tuv.com
Page 85 of 90
Report No.: CN22UKC1 001
Rating label
Figure 2: Overview
www.tuv.com
Page 86 of 90
Report No.: CN22UKC1 001
Figure 3: Overview
Figure 4: Control panel view
www.tuv.com
Page 87 of 90
Figure 5: Overview
Report No.: CN22UKC1 001
Figure 6: Internal view
www.tuv.com
Page 88 of 90
Figure 7: PCB view
Report No.: CN22UKC1 001
Figure 8: Overview
www.tuv.com
Page 89 of 90
Figure 9: Internal view
Report No.: CN22UKC1 001
Figure 10: Internal view
www.tuv.com
Page 90 of 90
Figure 11: Internal view
Report No.: CN22UKC1 001
Figure 12: Pump view
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.