Yiyuan Electric APS 3 KW, APC 1 KW, APC 14 KW, APS 4 KW, APC 6 KW User Manual

...
Yiyuan Electric Co., Ltd www.yiyen.com
AP Series
Pure Sine Wave Inverter/Charger
User’s Manual
Version 4.0
1
Yiyuan Electric Co., Ltd www.yiyen.com
Table of Contents
1. Important Safety Information ........................................................................................................................ 3
1-1. General Safety Precautions ......................................................................................................................... 3
1-2. Precautions When Working with Batteries ................................................................................................ 3
2-1. General Information ................................................................................................................................... 4
2-2. Application.................................................................................................................................................. 4
2.3 Mechanical Drawing .................................................................................................................................... 5
2-4. Features ....................................................................................................................................................... 9
2.5 Electrical Performance ................................................................................................................................. 9
2.5.1 Invert .................................................................................................................................................. 9
2.5.2 AC Charger ........................................................................................................................................ 9
2.5.3 Transfer ............................................................................................................................................ 12
2.5.4 Auto frequency adjust ...................................................................................................................... 13
2.5.5 Solar Charger* ................................................................................................................................. 13
2.5.6 Automatic Voltage Regulation* ...................................................................................................... 15
2.5.7 Power Saver ..................................................................................................................................... 16
2.5.8 Protections........................................................................................................................................ 18
2.5.9 Remote control ................................................................................................................................. 18
2.5.10 LED Indicator & LCD ................................................................................................................... 19
2.5.11 Audible Alarm ............................................................................................................................... 21
2.5.12 FAN Operation............................................................................................................................... 21
2.5.13 DIP Switches .................................................................................................................................. 22
2.5.14 Other features ................................................................................................................................. 23
3 Installation..................................................................................................................................................... 25
3.1 Location .............................................................................................................................................. 25
3.2 DC Wiring ........................................................................................................................................... 25
3.3 AC Wiring ........................................................................................................................................... 26
3.4 Grounding ........................................................................................................................................... 27
3.5 Install Flange ....................................................................................................................................... 28
4 Troubleshooting Guide ................................................................................................................................. 30
5 Warranty ....................................................................................................................................................... 32
Appendix 1 ....................................................................................................................................................... 33
2
Yiyuan Electric Co., Ltd www.yiyen.com
1. Important Safety Information
WARNING! Before using the Inverter, you need to read and save the safety instructions.
1-1. General Safety Precautions
1-1-1.Do not expose the Inverter to rain, snow, spray, bilge or dust. To reduce risk of hazard, do not cover or obstruct the ventilation openings. Do not install the Inverter in a zero-clearance compartment. Overheating may result. Allow at least 30CM(11.81 inches) of clearance around the inverter for air flow. Make sure that the air can circulate freely around the unit. A minimum air flow of 145CFM is required. 1-1-2. To avoid a risk of fire and electronic shock. Make sure that existing wiring is in good electrical condition; and that wire size is not undersized. Do not operate the Inverter with damaged or substandard wiring. 1-1-3. This equipment contains components which can produce arcs or sparks. To prevent fire or explosion do not install in compartments containing batteries or flammable materials or in locations which require ignition protected equipment. This includes any space containing gasoline-powered machinery, fuel tanks, or joints, fittings, or other connection between components of the fuel system. See Warranty for instructions on obtaining service. 1-1-4. Do not disassemble the Inverter/Charger. It contains no userserviceable parts. Attempting to service the Inverter/Charger yourself may result in a risk of electrical shock or fire. Internal capacitors remain charged after all power is disconnected. 1-1-5. To reduce the risk of electrical shock, disconnect both AC and DC power from the Inverter/Charger before attempting any maintenance or cleaning. Turning off controls will not reduce this risk
CAUTION: Equipment damage
The output side of the inverter’s AC wiring should at no time be connected to public power or a generator. This condition is far worse than a short circuit. If the unit survives this condition, it will shut down until corrections are made. Installation should ensure that the inverter’s AC output is, at no time, connected to its AC input.
Warning: Limitations On Use
SPECIFICALLY, PLEASE NOTE THAT THE APC SERIES INVERTER/CHARGER SHOULD NOT BE USED IN CONNECTION WITH LIFE SUPPORT SYSTEMS OR OTHER MEDICAL EQUIPMENT OR DEVICES.
1-2. Precautions When Working with Batteries
1-2-1. If battery acid contacts skin or clothing, wash immediately with soap and water. If acid enters eye, immediately flood eye with running cold water for at least 20 minutes and get medical attention immediately. 1-2-2. Never smoke or allow a spark or flame in vicinity of battery or engine. 1-2-3. Do not drop a metal tool on the battery. The resulting spark or short-circuit on the battery of other electrical part may cause an explosion. 1-2-4. Remove personal metal items such as rings, bracelets, necklaces, and watches when working with a lead-acid battery. A lead-acid battery produces a short-circuit current high enough to weld a ring or the like to metal, causing a severe burn. 1-2-5. To reduce the risk of injury, charge only rechargeable batteries such as deep-cycle lead acid, lead antimony, lead calcium gel cell, absorbed mat, NiCad/NiFe or Lithium battery. Other types of batteries may burst, causing personal injury and damage.
3
Yiyuan Electric Co., Ltd www.yiyen.com
2. Introduction
2-1. General Information
APC Series Pure Sine Wave Inverter is a combination of an inverter, battery charger and AC auto-transfer switch into one complete system with a peak conversion efficiency of 88%. It is packed with unique features and it is one of the most advanced inverter/chargers in the market today. It features power factor corrected, sophisticated multi-stage charging and pure sine wave output with unprecedentedly high surge capability to meet demanding power needs of inductive loads without endangering the equipment.
For the regular model, when utility AC power cuts off(or falls out of acceptable range), the transfer relay is de-energized and the load is automatically transferred to the Inverter output. Once the qualified AC utility is restored, the relay is energized and the load is automatically reconnected to AC utility. The APC Series Inverter is equipped with a powerful charger of up to 90Amps (depending on model). The overload capacity is 300% of continuous output for up to 20 seconds to reliably support tools and equipment longer
Another important feature is that the inverter can be easily customized to Battery priority via a DIP switch, this helps to extract maximum power from battery in renewable energy systems. Thus, the APC Series Pure Sine Wave Inverter is suitable for Renewable energy system,Utility, RV, Marin and Emergency appliances.
To get the most out of the power inverter, it must be installed, used and maintained properly. Please read the instructions in this manual before installing and operating.
2-2. Application
Power tools–circular saws, drills, grinders, sanders, buffers, weed and hedge trimmers, air compressors. Office equipment – computers, printers, monitors, facsimile machines, scanners. Household items – vacuum cleaners, fans, fluorescent and incandescent lights, shavers, sewing machines. Kitchen appliances – coffee makers, blenders, ice markers, toasters. Industrial equipment – metal halide lamp, high – pressure sodium lamp. Home entertainment electronics – television, VCRs, video games, stereos, musical instruments, satellite equipment.
4
Yiyuan Electric Co., Ltd www.yiyen.com
2.3 Mechanical Drawing
APC/APS 1KW to 3KW Models
5
Yiyuan Electric Co., Ltd www.yiyen.com
APC/APS 4KW to 6KW Models
6
Yiyuan Electric Co., Ltd www.yiyen.com
APV 1KW to 3KW Models
7
Yiyuan Electric Co., Ltd www.yiyen.com
APV 4KW to 6KW Models
8
Yiyuan Electric Co., Ltd www.yiyen.com
2-4. Features
High overload ability up to 300% of rated power(20 sec) Low quiescent current, low power “ Power Saving Mode ” to conserve energy 4-step intelligent battery charging, PFC(Power Factor Correction) for charger 8 pre set battery type selector plus de-sulphation for totally flat batteries Powerful charge rate up to 90Amp, selectable from 0%-100% 10 ms typical transfer time between battery and AC, guarantees power continuity Smart remote control 15s delay before transfer when AC resumes, extra protection for loads when used with generator Allows start up and through power with depleted batteries 30A/40A through current ability Multiple controlled cooling fan Extensive protections against various harsh situations 13VDC battery recover point, dedicated for renewable energy systems
2.5 Electrical Performance
2.5.1 Invert
Topology
The APC inverter/charger is built according to the following topology. Invert: Full Bridge Topology. Charge: Isolate Boost Topology Because of high efficiency Mosfets and 16bit, 4.9MHZ microprocessor and heavy transformers, it outputs PURE SINE WAVE AC with an average THD of 15% (min 5%, max 25%) depending of load connected and battery voltage. The peak efficiency of APC series is 88%.
Overload Capacity
The APC series inverters have different overload capacities, making it ideal to handle demanding loads. 1 For 110%<Load<125%(±10%), no audible alarm in 14 minutes, beeps 0.5s every 1s in the 15th minute, and Fault(Turn off) after the 15th minute. 2 For 125%<Load<150%(±10%), beeps 0.5s every 1s and Fault(Turn off) after the 1 minute. 3 For 300%Load>150%(±10%), beeps 0.5s every 1s and Fault(Turn off) after 20s.
Caution:
After the inverter is switched on, it takes a finite time for it to self diagnose and get ready to deliver full power. Hence, always switch on the load(s) after a few seconds of switching on the inverter. Avoid switching on the inverter with the load already switched on. This may prematurely trigger the overload protection. When a load is switched on, it may require initial higher power surge to start. Hence, if multiple loads are being powered, they should be switched on one by one so that the inverter is not overloaded by the higher starting surge if all the loads are switched on at once.
2.5.2 AC Charger
APC Series is equipped with an active PFC (Power Factor Corrected) multistage battery charger. The PFC
9
Yiyuan Electric Co., Ltd www.yiyen.com feature is used to control the amount of power used to charge the batteries in order to obtain a power factor
as close as possible to 1. Unlike other inverters whose max charging current decreases according to the input AC voltage, APC series charger is able to output max current as long as input AC voltage is in the range of 164-243VAC(95-127VAC for 120V model), and AC freq is in the range of 48-54Hz(58-64Hz for 60Hz model). The APC series inverter has a very rapid charge current available, and the max charge current can be adjusted from 0%-100% via a liner switch to the right of the battery type selector. This will be helpful if you are using our powerful charger on a small capacity battery bank. Choosing 0 in the battery type selector will disable charging function.
There are 3 main stages: Bulk Charging: This is the initial stage of charging. While Bulk Charging, the charger supplies the battery with controlled constant current. The charger will remain in Bulk charge until the Absorption charge voltage (determined by the Battery Type selection) is achieved. Software timer will measure the time from A/C start until the battery charger reaches 0.3V below the boost voltage, then take this time asT0 and T0×10 = T1. Absorb Charging: This is the second charging stage and begins after the absorb voltage has been reached. Absorb Charging provides the batteries with a constant voltage and reduces the DC charging current in order to maintain the absorb voltage setting. In this period, the inverter will start a T1 timer; the charger will keep the boost voltage in Boost CV mode until the T1 timer has run out. Then drop the voltage down to the float voltage. The timer has a minimum time of 1 hour and a maximum time of 12 hours. Float Charging: The third charging stage occurs at the end of the Absorb Charging time. While Float charging, the charge voltage is reduced to the float charge voltage (determined by the Battery Type selection*). In this stage, the batteries are kept fully charged and ready if needed by the inverter. If the A/C is reconnected or the battery voltage drops below 12Vdc/24Vdc/48Vdc, the charger will reset the cycle above. If the charge maintains the float state for 10 days, the charger will deliberately reset the cycle to protect the battery.
10
Yiyuan Electric Co., Ltd www.yiyen.com
Switch setting
Description
Boost / Vdc
Float / Vdc
0
Charger Off
1
Gel USA
14.0
13.7
2
AGM 1
14.1
13.4
3
AGM 2
14.6
13.7
4
Sealed lead acid
14.4
13.6
5
Gel EURO
14.4
13.8
6
Open lead acid
14.8
13.3
7
Calcium
15.1
13.6
8
De sulphation
15.5 (4 Hours then Off)
9
Not used
Battery type selector
12Vdc Mode (*2 for 24Vdc ; *4 for 48Vdc)
De-sulphation
The de-sulphation cycle on switch position 8 is marked in red because this is a very dangerous setting if you do not know what you are doing. Before ever attempting to use this cycle you must clearly understand what it does and when and how you would use it. What causes sulphation? This can occur with infrequent use of the batteries, nor if the batteries have been left discharged so low that they will not accept a charge. This cycle is a very high voltage charge cycle designed to try to break down the sulphated crust that is preventing the plates from taking a charge and thus allow the plates to clean up and accept a charge once again.
Charging depleted batteries
The APC series inverter allows start up and through power with depleted batteries.
11
Yiyuan Electric Co., Ltd www.yiyen.com
Model
Current
Model
Current
1KW12Vdc230Vac
35±5A
1KW12Vdc120Vac
35±5A
1KW24Vdc230Vac
20±5A
1KW24Vdc120Vac
15±5A
1.5KW12Vdc230Vac
45±5A
1.5KW12Vdc120Vac
45±5A
1.5KW24Vdc230Vac
25±5A
1.5KW24Vdc120Vac
25±5A
2KW12Vdc230Vac
65±5A
2KW12Vdc120Vac
60±5A
2KW24Vdc230Vac
30±5A
2KW24Vdc120Vac
30±5A
2KW48Vdc230Vac
20±5A
2KW48Vdc120Vac
15±5A
3KW12Vdc230Vac
80±5A
3KW12Vdc120Vac
80±5A
3KW24Vdc230Vac
45±5A
3KW24Vdc120Vac
40±5A
3KW48Vdc230Vac
30±5A
3KW48Vdc120Vac
25±5A
4KW12Vdc230Vac
105±5A
4KW12Vdc120Vac
100±5A
4KW24Vdc230Vac
65±5A
4KW24Vdc120Vac
50±5A
4KW48Vdc230Vac
35±5A
4KW48Vdc120Vac
30±5A
5KW24Vdc230Vac 5KW24Vdc230Vac(Split Phase)
70±5A
5KW48Vdc230Vac 5KW48Vdc230Vac(Split Phase)
40±5A
6KW24Vdc230Vac 6KW24Vdc230Vac(Split Phase)
85±5A
6KW48Vdc230Vac 6KW48Vdc230Vac(Split Phase)
55±5A
For 12VDC model, after the battery voltage goes below 10V, if the switch is still(and always) kept in "ON" position, the inverter is always connected with battery, and the battery voltage doesnt drop below 2V, the inverter will be able to charge the battery once qualified AC inputs. Before the battery voltage going below 9VDC, the charging can activated when the switch is turned to Off, then to ON. When the voltage goes below 9VDC, and you accidently turn the switch to OFF or disconnect the inverter from battery, the inverter will not be able to charge the battery once again, because the CPU lose memory during this process. Start up without battery function can be customized upon request.
Charging current for each model
The charging capacity will go to peak in around 3 seconds, this may probably cause a generator to drop frequency, making inverter transfer to battery mode. It is suggested to gradually put charging load on the generator by switching the charging switch from min to max, together with the 15s switch delay, our inverter gives the generator enough time to spin up.
Caution:
Pls turn the charge current control switch gently to avoid breakage due to over-turning.
2.5.3 Transfer
12
Yiyuan Electric Co., Ltd www.yiyen.com
Rated Voltage
12 Vdc
24Vdc
Rated charge current (includes load
current)
60Amp
Load current
15Amp
Input voltage range
15-30Vdc
30-55Vdc
Max DC input Current
60Amp
Max. PV open circuit array voltage
30Vdc
55Vdc
Overload protection (DC load)
2.0 * I(Rated)>5s
1.5 * I(Rated) >20s
1.25 * I(Rated) temperature controlled
Typical idle consumption
At idle < 10mA
Bulk charge
14.6Vdc (default)
29.2Vdc (default)
Floating charge
13.4Vdc (default)
26.8Vdc (default)
Equalization charge
14.0Vdc (default)
28.0Vdc (default)
While in the Standby Mode, the AC input is continually monitored. Whenever AC power falls below the VAC Trip voltage (154 VAC, default setting), the inverter automatically transfers back to the Invert Mode with minimum interruption to your appliances - as long as the inverter is turned on. The transfer from Standby mode to Inverter mode occurs in approximately 10 milliseconds. And it is the same time from Inverter mode to Standby mode. Though it is not designed as a computer UPS system, this transfer time is usually fast enough to hold them up. There is a 15-second delay from the time the inverter senses that continuously qualified AC is present at the input terminals to when the transfer is made. This delay is built in to provide time for a generator to spin-up to a stable voltage and avoid relay chattering. The inverter will not transfer to generator until it has locked onto the generator’s output. This delay is also designed to avoid frequent switch when input utility is unstable.
2.5.4 Auto frequency adjust
The inverter is designed with Auto Frequency adjust function. The factory default configuration for 220/230/240VAC inverter is 50Hz and 60Hz for 100/110/120VAC inverter. While the output freq can be easily changed once a qualified freq is applied to the inverter. If you want to get 60Hz from a 50Hz inverter, just input 60Hz power, and the inverter will automatically adjust the output freq to 60Hz and vice versa.
NOTE: The inverter will output factory set freq after it restarts. Customers who can only accept one freq should specify the freq when ordering.
2.5.5 Solar Charger*
For APV series, there is a solar charger built in.
Listed below is the spec for solar charger
Table 1 Electrical Specifications @ 25(77)
13
Yiyuan Electric Co., Ltd www.yiyen.com
Over charge disconnect
14.8Vdc
29.6Vdc
Over charge recovery
13.6Vdc
27.2Vdc
Over discharge disconnect
10.8Vdc (default)
21.6Vdc (default)
Over discharge reconnect
12.3Vdc
24.6Vdc
Lead acid battery settings
Adjustable
NiCad battery settings
Adjustable
Low voltage reconnect
12.0-14.0Vdc
24.0-28.0Vdc
Low voltage disconnect
10.5-12.5Vdc
21.0-25.0Vdc
Ambient temperature
0-40(32-104) full capacity; 4060(104-140) de-rating
Altitude
Operating 5000 m, Non-Operating 16000 m
Protection class
IP21
Terminal size (fine/single wire)
#8 AWG
Maximum Power Point Tracking (MPPT) Function
Maximum Power Point Tracking, frequently referred to as MPPT, is an electronic system that operates the Photovoltaic (PV) modules in a manner that allows the modules to produce all the power they are capable of. The PV-seeker Charge controller is a microprocessor-based system designed to implement the MPPT. And it can increase charge current up to 30% or more compared to traditional charge controllers (see figure
1).
Figure 1 Current, Power vs. Voltage Characteristics
The Charge controller built in is with 12/24V battery voltage auto detecting function. For 12VDC inverter, the output voltage of solar charger will be accordingly 12VDC, and the qualified DC input volt range is 15v-30VDC.
14
Yiyuan Electric Co., Ltd www.yiyen.com
Any-Power Solution AVR Function
Any-Power Solution Series
LV (NA/JPN)
HV (INTL)
Acceptable Input Voltage Range (Vac)
0-160
0-300
Nominal Input Voltages (Vac)
100
110
120
220
230
240
(A) Line low loss N/W (On battery)
75/65
84/72
92/78
168/14
3
176/15
0
183/156
(B) Line Low comeback N/W (On Boost)
80/70
89/77
97/83
178/15
3
186/16
0
193/166
(C) Line 2nd boost threshold (On Boost)
**
**
**
**
**
**
(D) Line 2nd boost comeback (On normal)
**
**
**
**
**
**
(E) Line 1st boost threshold (On Boost)
90
99
108
198
207
216
For 24VDC inverter, the output voltage of solar charger will be accordingly 24VDC, and the qualified DC input volt range is 30V-55VDC. If the voltage falls out of this range, the charger will not work properly. Special attention should be paid to this when configuring the solar array.
2.5.6 Automatic Voltage Regulation*
The automatic voltage regulation function is only for APS Pure Sine Wave Inverter/ Charger which is a combination of APC inverter and Automatic Voltage Regulator. Instead of simply bypassing the input AC to power the loads, the APS series inverter stabilizes the input AC voltage to a range of 230V/120V±10%. Connected with batteries, the APS inverter will function as a UPS with max transfer time of 10 ms. With all the unique features from the inverter and AVR, it brings you long-term trouble free operation beyond your expectation.
APS Series AVR Function Introduction
15
Yiyuan Electric Co., Ltd www.yiyen.com
(F) Line 1st boost comeback (On normal)
93
103
112
205
215
225
(G) Line buck comeback (On Normal)
106
118
128
235
246
256
(H) Line buck threshold (On Buck)
110
121
132
242
253
264
(I) Line high comeback (On Buck)
115
127
139
253
266
278
(J) Line high loss (On Battery)
120
132
144
263
276
288
Power saver on
Power saver off
Power saver on(Load detected)
2.5.7 Power Saver
There are 2 different working statuses for APC inverter: Power On and Power Off. When power switch is in Unit Off position, the inverter is powered off. When power switch is turned to either of Power Saver Auto or Power Saver Off, the inverter is powered on. Power saver function is to dedicated to conserve battery power when AC power is not or little required by the loads. In this mode, the inverter pulses the AC output looking for an AC load (i.e., electrical appliance). Whenever an AC load (greater than 25 watts) is turned on, the inverter recognizes the need for power and automatically starts inverting and output goes to full voltage. When there is no load (or less than 25 watts) detected, the inverter automatically goes back into search mode to minimize energy consumption from the battery bank. In Power saver on mode, the inverter will draw power mainly in sensing moments, thus the idle consumption is significantly reduced. The inverter is factory defaulted to detect load for 250ms in every 30 seconds. This cycle can be customized to 3 seconds thru the SW3 on DIP switch.
Note: The minimum power of a load to take inverter out of sleep mode (Power Saver On) is 25 Watts.
The whole AP Series inverter is designed with extraordinarily low idle power consumption which is
0.8-1.8% of its rated power.
16
Yiyuan Electric Co., Ltd www.yiyen.com
Model NO
Power Saver Off
Power Saver On (3Secs)
Power Saver On (30Secs)
1012E
12.5
7.5
5.3
1012
12.5
7.5
5.3
1024E
15
8.4
5.4
1024
16.5 9 6
1512E
12.5
7.5
5.3
1524E
15
8.4
5.4
1512
13.5 8 5.8
1524
16.5 9 6
2012E
25
11.7
5.7
2012
28
12.7
5.8
2024E
24.5
11.5
5.7
2024
26.5
12.2
5.8
2048E
25
11.7
5.7
2048
28
12.7
5.8
3012E
50
20
6.5
3012
55
21.7
6.7
3024E
38.5
16.2
6.2
3024
46.5
18.9
6.4
3048E
45
18.4
6.4
3048
50
20
6.5
4012
44.5
18.2
6.4
4024E
48
19.4
6.5
4024
52.5
20.9
6.6
4048E
48
19.4
6.5
4048
55.5
21.9
6.7
5024E
62.5
24.2
7
5048E
68.5
26.2
7.2
6024E
76.8
29
7.4
6048E
80.7
30.3
7.6
AP Series Idle Power Consumption(in Watts)
Note: Model NO ending with E represents 230Vac output one, model NO without E represents 120Vac output one For more detailed technical information, please contact the supplier.
When in the search sense mode, the green power LED will blink and the inverter will make a ticking sound. At full output voltage, the green power LED will light steadily and the inverter will make a steady humming sound. When the inverter is used as an “uninterruptible” power supply the search sense mode function should be defeated.
Exceptions Some devices when scanned by the load sensor cannot be detected. Small fluorescent lights are the most
17
Yiyuan Electric Co., Ltd www.yiyen.com common example. (Try altering the plug polarity by turning the plug over.) Some computers and
sophisticated electronics have power supplies that do not present a load until line voltage is available. When this occurs, each unit waits for the other to begin. To drive these loads either a small companion load must be used to bring the inverter out of its search mode, or the inverter may be programmed to remain at full output voltage.
2.5.8 Protections
The APC series inverter is equipped with extensive protections against various harsh situations/faults. These protections include: AC Input over voltage protection/AC Input low voltage protection Low battery alarm/High battery alarm Over temperature protection/Over load protection Short Circuit protection (1s after fault) Back feeding protection
When Over temperature /Over load occur, after the fault is cleared, the master switch has to be reset to restart the inverter. The Low battery voltage trip point can be customized from defaulted value of 10VDC to 10.5VDC through the SW1 on the DIP switch. The inverter will go to Over temp protection when the heat sink temp. ≥105ºC (221), and will go to Fault (shutdown Output) after 30 seconds. After temp drop to 90ºC (194), the switch has to be reset to activate the inverter. The APC series Inverter is with back feeding protection which avoids presenting an AC voltage on the AC input terminal in Invert mode. After the reason for fault is cleared, the inverter has to be reset to start working.
2.5.9 Remote control
Apart from the switch panel on the front of the inverter, an extra switch panel connected to the RJ11 port at the DC side of the inverter thru a standard telephone cable can also control the operation of the inverter.
If an extra switch panel is connected to the inverter via
“remote control port”, together with the panel on the inverter
case, the two panels will be connected and operated in parallel. Whichever first switches from “Off” to “Power saver off” or “Power saver on”, it will power the inverter on. If the commands from the two panels conflict, the inverter will accept command according to the following priority: Power saver on> Power saver off> Power off Only when both panels are turned to “Unit Off” position, the inverter will be powered off.
WARNING
18
Yiyuan Electric Co., Ltd www.yiyen.com
Above sticker is on APC/APS 1KW to 6KW models, and APV 1KW to 3KW models.
Never cut the telephone cable when the cable is attached to inverter and battery is connected to the inverter. Even the inverter is turned off, this will damage the remote PCB inside if the cable is short circuited during cutting.
2.5.10 LED Indicator & LCD
19
Yiyuan Electric Co., Ltd www.yiyen.com
Above sticker is on APV 4-6KW models.
SHORE POWER ON
GREEN LED lighting on AC Mode
INVERTER ON
GREEN LED lighting on Inverter Mode
FAST CHARGE
Yellow LED lighting on Fast Charging Mode
FLOAT CHARGE
GREEN LED lighting on Float Charging Mode
OVER TEMP TRIP
RED LED lighting on Over Temperature
OVER LOAD TRIP
RED LED lighting on Over Load
POWER SAVER ON
GREEN LED lighting on Power Saver Mode (Power Saver Load 25W)
Greeting message of Welcome to
The Inverter can be customized into LCD type. The LCD will display the following content:
20
Yiyuan Electric Co., Ltd www.yiyen.com
AC Status & Input Voltage AC: abnormal is displayed when AC input is not qualified.
Output Voltage/Frequency and Output Current( in percentage) in Inverter mode
Battery voltage
Battery Voltage Low
Inverter green LED Lighting, and the buzzer beep 0.5s every 5s.
Battery Voltage High
Inverter green LED Lighting, and the buzzer beep 0.5s every 1s, and Fault after 60s.
Invert Mode Over-Load
(1)110%<load<125%(±10%), No audible alarm in 14 minutes, Beeps 0.5s every 1s in 15th minute and Fault after 15 minutes; (2)125% <load<150%(±10%), Beeps 0.5s every 1s and Fault after 60s; (3)Load>150%(±10%), Beeps 0.5s every 1s and Fault after 20s;
Over Temperature
Heat sink temp. ≥105ºC(221), Over temp red LED Lighting, beeps 0.5s every 1s;
Note: When the inverter is in Battery Priority mode, AC:abnormal will also be displayed when the inverter finishes a complete charging circle and switches to inverter mode. In AC mode, the LCD will not display the status of AC load.
2.5.11 Audible Alarm
2.5.12 FAN Operation
For 1-3KW, there is one multiple controlled DC fan which starts to work according to the following logics. For 4-6KW, there is one multiple controlled DC fan and one AC fan. The DC fan will work in the same way as the one on 1-3KW, while the AC fan will work once there is AC output from the inverter.
21
Yiyuan Electric Co., Ltd www.yiyen.com
Condition
Enter Condition
Leave condition
Speed
HEAT SINK TEMPERATURE
T ≤ 60(140)
T > 65(149)
OFF
65(149) T < 85 (185)
T 60(140) or T ≥ 85(185)
50%
T > 85(185)
T ≤ 80(176)
100%
CHARGER CURRENT
I 15%
I ≥ 20%
OFF
20%< I ≤ 50%Max
I15% or I > 50%Max
50%
I > 50%Max
I ≤ 40%Max
100%
LOAD Percentage (INV MODE)
Load < 30%
Load ≥ 30%
OFF
30% ≤ Load < 50%
Load ≤ 20% or Load ≥ 50%
50%
Load 50%
Load ≤ 40%
100%
Switch NO
Switch Function
Position: 0
Position: 1
SW1
Low Battery Trip Volt
10.0VDC
10.5VDC
*2 for 24VDC, *4 for 48VDC
SW2(230V)
AC Input Range
184-253VAC
154-264VAC(40Hz+)
SW2(120V)
AC Input Range
100-135VAC
90-135VAC(40Hz+)
SW3
Load Sensing Cycle
30 seconds
3 seconds
SW4
Battery/AC Priority
Utility Priority
Battery Priority
So when the inverter is in power saver mode, the AC fan will work from time to time in response to the pulse sent by the inverter in power saver mode.
The Operation of DC fan at the DC terminal side is controlled in the following logic:
Allow at least 30CM of clearance around the inverter for air flow. Make sure that the air can circulate freely around the unit. Fan noise level <60db at a distance of 1m
2.5.13 DIP Switches
On the DC end of inverter, there are 4 DIP switches which enable users to customize the performance of the device.
Low Battery Trip Volt:
Deep discharge of the lead acid battery leads to high losses in capacity and early aging. In different applications, different low voltage disconnection level is preferred. For example, for solar application, user intended to have less DOD to prolong the battery cycle life. While for mobile application, users intend to have more DOD to reduce battery capacity and on board weight. For 12VDC model, the Low Battery Trip Volt is set at 10.0VDC by default. It can be customized to
10.5VDC using SW1, this is to prevent batteries from over-discharging while there is only a small load applied on the inverter. *2 for 24VDC, *4 for 48VDC
AC Input Range:
There are different acceptable AC input ranges for different kinds of loads. For some relatively sensitive electronic devices, a narrow input range of 184-253VAC (100-135V for
22
Yiyuan Electric Co., Ltd www.yiyen.com 120VAC model) is required to protect them.
While for some resistive loads which work in a wide voltage range, the input AC range can be customized to 154-253VAC (90-135V for 120VAC model), this helps to power loads with the most AC input power without frequent switches to the battery bank. In order to make the inverter accept dirty power from a generator, when the SW2 is switched to position 1, the inverter will bypass an AC input with a higher voltage(164-264Vac for 230Vac model) and wider frequency (40Hz plus for 50Hz/60Hz). Accordingly, the AC charger will also work in a higher voltage(174-254Vac for 230Vac model) wider freq range (43Hz plus for 50Hz/60Hz). This will avoid frequent switches between battery and generator. But some sensitive loads will suffer from the low quality power. The pros and cons should be clearly realized.
Load Sensing Cycle:
The inverter is factory defaulted to detect load for 250ms every 30 seconds. This cycle can be customized to 3 seconds through the SW3 on DIP switch.
AC/Battery Priority:
Our inverter is designed AC priority by default. This means, when AC input is present, the battery will be charged first, and the inverter will transfer the input AC to power the load. Only when the AC input is stable for a continuous period of 15 days will the inverter start a battery inverting cycle to protect the battery. After 1 normal charging cycle ac through put will be restored. For more info, pls refer to our manual at AC Charging Section. The AC Priority and Battery Priority switch is SW4. When you choose battery priority, the inverter will invert from battery despite the AC input. Only when the battery voltage reaches the low voltage alarm point(10.5Vdc for 12Vdc, 21Vdc for 24Vdc, 42Vdc for 48Vdc) will the inverter transfer to AC Input, charge battery, and switch back to battery when the battery is fully charged. This function is mainly for wind/solar systems using utility power as back up. The AC/Battery Priority function can be activated by sliding the switch even when the inverter is in operation.
Note: In battery priority mode, when qualified AC inputs for the first time, the inverter will only go into battery priority mode after a cycle of bulk charging and absorb charging is finished. The inverter will not go into float charging mode.
2.5.14 Other features
Battery voltage recovery start
After low battery voltage shut off(10V for 12V model or 20V for 24V model or 40V for 48V model), the inverter is able to restore to work after the battery voltage recovers to 13V/26V/52V(with power switch still in On position). This function helps to save the users extra labor to reactivate the inverter when the low battery voltage returns to acceptable range in renewable energy systems.
WARNING
Never leave the loads unattended, some loads (like a Heater) may cause accidents in such cases. It is better to shut everything off after low voltage trip than to leave your load in the risk of fire. Nobody wants to return home, finding house surrounded by fire trucks, and naughty neighborhood kids toasting hot dogs against his house.
23
Yiyuan Electric Co., Ltd www.yiyen.com
Auto Gen Start(optional)
The inverter can be customized to start up a generator when battery voltage goes low. When the inverter goes to low battery alarm, it can send a signal to start a generator, and turn the generator off after battery charging is finished. The auto gen start feature will only work with generators designed to work with this feature. There is an open/close relay that will short circuit the positive and negative cable from a generator. The input DC voltage can vary, but the Max current the relay can carry is 16Amp.
Conformal Coating
The entire line of inverters have been processed with a conformal coating on the PCB, making it water, rust, and dust resistant. While these units are designed to withstand corrosion from the salty air, they are not splash proof.
24
Yiyuan Electric Co., Ltd www.yiyen.com
Rate Current
DC cable
Model
200Amp Max
8AWG*2*2
1012/1024/1512/1524/2024/2048/3048
300Amp Max
8AWG*3*2
2012/3024/4024/4048/5048/6048
400Amp Max
8AWG*4*2
3012/5024/6024
WARNING
The torque rating range for DC terminal is 12.5NM-20.5NM(9.25-15.19 pound-foot), and the suggested torque rating is 17NM(12.6 pound-foot). Over torquing may cause the bolt to break.
In the event of reverse polarity the unit could be totally destroyed which is not covered under warranty!
The inverter contains capacitors that may produce a spark when first connected to battery. Do not mount in a confined a battery or gas compartment.
3 Installation
3.1 Location
Follow all the local regulations to install the inverter. Please install the equipment in a location of Dry, Clean, Cool with good ventilation. Working temperature: 10 to 40(-14to 104) Storage temperature: 40 to 70(-40to 158) Relative Humidity: 0%to 95%non-condensing Cooling: Forced air
3.2 DC Wiring
It is suggested the battery bank be kept as close as possible to the inverter. The following table is a suggested wiring option for 1 meter DC cable.
Please find the following minimum wire size. In case of DC cable longer than 1m, please increase the cross section of cable to compensate for a drop in voltage and DC ripple.
Reducing RF interference
To reduce the effect of radiated interference, twist the DC cables. To further reduce RF interference, shield the cables with sheathing /copper foil / braiding.
Taping battery cables together to reduce inductance
Do not keep the battery cables far apart. In case it is not convenient to twist the cables, keep them taped together to reduce their inductance. Reduced inductance of the battery cables helps to reduce induced voltages. This reduces ripple in the battery cables and improves performance and efficiency.
25
Yiyuan Electric Co., Ltd www.yiyen.com
Wiring Option 1
230V single phase/120V single phase Input: Hot line+Neutral+Ground Output: Hot line+Neutral+Ground
Wiring Option 2
230V split phase Input: Hot line+ Hot line +Ground Output: Hot line+ Hot line +Neutral
3.3 AC Wiring
We recommend using 10 to 5Awg wire to connect to the ac terminal block. When in AC mode the AC input power will supply both the loads and AC charger, a thicker wire gauge for AC Input is required. Pls consult a qualified electrician about the specific wire gauge required in terms of wire material and inverter power.
There are 3 different ways of connecting to the terminal block depending on the model. All the wirings are CE compliant, Call our tech support if you are not sure about how to wire any part of your inverter.
26
Yiyuan Electric Co., Ltd www.yiyen.com
Wiring Option 3
230V split phase Input: Hot line+ Hot line +Ground Output: Hot line +Neutral
Remark: In such cases, each output hotline can only carry a max of half the rated capacity.
Caution: Wiring Option 2 and Wiring Option 3 are only allowed for split phase models. Pls wire all the other models according to Wiring Option 1.
WARNING
For split phase models, AC input neutral is not required in wiring. Never Connect Input Neutral to Output Neutral. Damage will result which is not covered under warranty.
The output voltage of this unit must never be connected in its input AC terminal, overload or damage may result. Always switch on the inverter before plugging in any appliance.
3.4 Grounding
Connect an AWG 8 gauge or greater copper wire between the grounding terminal on the inverter and the earth grounding system or the vehicle chassis.
WARNING
27
Yiyuan Electric Co., Ltd www.yiyen.com
APC1-1.5KW APS1-1.5KW
APC2-3KW APS2-3KW
APC4-6KW APS4-6KW APS1-3KW
3.5 Install Flange
28
Yiyuan Electric Co., Ltd www.yiyen.com
Side View
APV 4KW-6KW
29
Yiyuan Electric Co., Ltd www.yiyen.com
Indicator on top cover
LED on Remote Switch
Status
Item
SHORE
POWER
ON
INVERT
ER ON
FAST
CHG
FLOAT
CHG
OVER
TEMP
TRIP
OVER LOAD
TRIP
POWER
SAVER
ON
BATT
CHG
INVERTE
R
Alarm
Buzzer
Line
Mode
CC √ × √ × × × × √ × × × CV √ ×
√, blink × × × × √ × × ×
Float √ × × √ × × × √ × × × Standby
× × × × × × × × × ×
Inverter
Mode
Inverter On
× √ × × × × × × √ × ×
Power
Saver
× × × × × × √ × × × ×
Inverter
Mode
Battery
Low
× √ × × × × × × √
Beep 0.5s
every 5s
Battery
High
× √ × × × × × × √
Beep 0.5s
every 1s
Overload
On Invert
Mode
× √ × × × √ × × √
Refer to
Audible
alarm
Over-Temp
On Invert
Mode
× √ × × √ × × × √
Beep 0.5s
every 1s
Over-Temp
On Line
Mode
√ × √ × √ × × √ ×
Beep 0.5s
every 1s
Over
Charge
√ × √ × × × × √ ×
Beep 0.5s
every 1s
Fault
Mode
Fan Lock
× × × × × × × × ×
×
Beep
continuous
Battery
High
× √ × × × × × × √
×
Beep
continuous
Inverter
Mode
Overload
× × × × × √ × × ×
×
Beep
continuous
Output
Short
× × × × × √ × × ×
Beep
continuous
Over-Temp
× × × × √ × × × ×
×
Beep
continuous
Over × × √ × × × × √ × ×
Beep
4 Troubleshooting Guide
Troubleshooting contains information about how to troubleshoot possible error conditions while using the Any Power Combi Inverter & Charger.
The following chart is designed to help you quickly pinpoint the most common inverter failures.
Indicator and Buzzer
30
Yiyuan Electric Co., Ltd www.yiyen.com
Charge
continuous
Back Feed
Short
× × × × × × × × ×
×
Beep
continuous
Symptom
Possible Cause
Recommended Solution
Inverter will not turn on during initial power up.
Batteries are not connected, loose battery-side connections.
Low battery voltage.
Check the batteries and cable connections. Check DC fuse and breaker.
Charge the battery.
No AC output voltage and no indicator lights ON.
Inverter has been manually transitioned to OFF mode.
Press the switch to Power saver on or Power saver off position.
AC output voltage is low and the inverter turns loads OFF in a short time.
Low battery.
Check the condition of the batteries and recharge if possible.
Charger is inoperative and unit will not accept AC.
AC voltage has dropped out-of-tolerance
Check the AC voltage for proper voltage and frequency.
Charger is supplying a lower charge rate.
Charger controls are improperly set.
Low AC input voltage.
Loose battery or AC input connections.
Refer to the section on adjusting the “Charger Rate”.
Source qualified AC power..
Check all DC /AC connections.
Charger turns OFF while charging from a generator.
High AC input voltages from the generator.
Load the generator down with a heavy load. Turn the generator output voltage down.
Sensitive loads turn off temporarily when transferring between grid and inverting.
Inverter's Low voltage trip voltage may be too low to sustain certain loads.
Choose narrow AC voltage in the DIP switch, or Install a UPS if possible.
Noise from Transformer/case*
Applying specific loads such as hair drier
Remove the loads
*The reason for the noise from transformer and/or case
When in inverter mode and the transformer and/or case of the inverter sometimes may vibrate and make noise. The noise may come from transformer. According to the characteristics of our inverter, there is one type of load which will most likely to cause rattles of transformer, that is a half-wave load, load that uses only a half cycle of the power(see figure 1). This trends to cause imbalance of magnetic field of transformer, reducing its rated working freq from 20KHz to, say, maybe 15KHz (it varies according to different loads). This way, the freq of noise falls exactly into the range (200Hz-20KHz) that human ear can sense. The most common load of such kind is hair drier.
31
Yiyuan Electric Co., Ltd www.yiyen.com
Figure 1 If the noise comes from case. Normally when loaded with inductive loads, the magnetic field generated by transformer keeps attracting or releasing the steel case at a specific freq, this may also cause noise. Reducing the load power or using an inverter with bigger capacity will normally solve this problem. The noise willnt do any harm to the inverter or the loads.
5 Warranty
We offer 1 year limited warranty. But the following cases are not covered under warranty.
1 DC polarity reverse.
The inverter is designed without DC polarity reverse protection. A polarity reverse may severely damage the inverter.
2 Wrong AC wiring
3 Operation in a condensing environment.
4 Operating with an undersized generator or generator with unqualified wave form.
32
Yiyuan Electric Co., Ltd www.yiyen.com
APC Series Inverter&Charger
Electrical Specifications
Model
APC
1KW
APC
1.5KW
APC
2KW
APC
3KW
APC
4KW
APC
5KW
APC
6KW
Inverter
Output
Continuous Output Power
1000W
1500W
2000W
3000W
4000W
5000W
6000W
Surge Rating(20s)
3000W
4500W
6000W
9000W
12000W
15000W
18000W
Capable of Starting Electric Motor
1HP
1.5HP
2HP
3HP
4HP
5HP
6HP
Output Waveform
Pure Sine wave/Same as input(Bypass mode)
Nominal Efficiency
>88%(Peak)
Line Mode Efficiency
>95%
Power Factor
0.9-1.0
Nominal Output Voltage rms
100-110-120Vac / 220-230-240Vac
Output Voltage Regulation
±10% RMS
Output Frequency
50/60Hz ± 0.3Hz
Short Circuit Protection
Yes, Current Limit Function (Fault after 1sec)
Typical transfer Time
10ms(Max)
THD
< 10%
DC Input
Nominal Input Voltage
12.0Vdc
( *2 for 24Vdc, *4 for 48Vdc)
Minimum Start Voltage
10.0Vdc
Low Battery Alarm
10.5Vdc / 11.0Vdc
Low Battery Trip
10.0Vdc / 10.5Vdc
High Voltage Alarm & Fault
16.0Vdc
High DC Input Recovery
15.5Vdc
Low Battery voltage recover
13.0Vdc
Idle Consumption-Search Mode
< 25 W when Power Saver On
Charge
Input Voltage Range
Narrow: 100~135VAC / 194~243VAC;
Wide: 90~135VAC / 164~243VAC;
Input Frequency Range
Narrow: 47-55±0.3Hz for 50Hz, 57-65±0.3Hz for 60Hz
Wide:43±0.3Hz plus for 50Hz/60Hz
Output Voltage
Depends on battery type
Charger Breaker Rating
10A
10A
10A
20A
20A
30A
30A
Max Charge Rate
15A to 85A ±5A , depending on models
Over Charge Protection Shutdown
15.7V for 12Vdc ( *2 for 24Vdc, *4 for 48Vdc)
Appendix 1
33
Yiyuan Electric Co., Ltd www.yiyen.com
Battery type
Fast Vdc
Float Vdc
Gel U.S.A
14.0
13.7
A.G.M 1
14.1
13.4
A.G.M 2
14.6
13.7
Sealed Lead Acid
14.4
13.6
Gel Euro
14.4
13.8
Open Lead Acid
14.8
13.3
Calcium
15.1
13.6
De-sulphation
15.5 for 4hrs
Remote Control
Yes. Optional
Bypass &
Protection
Input Voltage Waveform
Sine wave (Grid or Generator)
Nominal Voltage
120Vac
230Vac
Low Voltage Trip
80V/90V±4%
184V/154V±4%
Low Voltage re engage
90V/100V±4%
194V/164V±4%
High Voltage Trip
140V±4%
253V±4%
High Voltage re engage
135V±4%
243V±4%
Max Input AC Voltage
150VAC
270VAC
Nominal Input Frequency
50Hz or 60Hz (Auto detect)
Low Freq Trip
Narrow: 47±0.3Hz for 50Hz, 57±0.3Hz for 60Hz
Wide:40±0.3Hz for 50Hz/60Hz
Low Freq re engage
Narrow: 48±0.3Hz for 50Hz, 58±0.3Hz for 60Hz
Wide:45±0.3Hz for 50Hz/60Hz
High Freq Trip
Narrow: 55±0.3Hz for 50Hz, 65±0.3Hz for 60Hz
Wide: No up limit for 50Hz/60Hz
High Freq re engage
Narrow: 54±0.3Hz for 50Hz, 64±0.3Hz for 60Hz
Wide: No up limit for 50Hz/60Hz
Output Short circuit protection
Circuit breaker
Bypass breaker rating
10A
15A
20A
30A
30A
40A
40A
Transfer switch rating
30amp for UL & TUV
40amp for UL
Max bypass current
30amp
40amp
Mechanical
Specification
Mounting
Wall mount
Inverter Dimensions(L*W*H)
382*218*179mm
442*218*179mm
598*218*179mm
Inverter Weight
16KG
17KG
20KG
24KG
35KG
45KG
45KG
Shipping Dimensions(L*W*H)
520*315*300mm
580*315*300mm
740*315*300mm
Shipping Weight
18KG
19KG
22KG
26KG
37KG
47KG
47KG
Display
Status LEDs / Status LEDs+LCD
Standard Warranty
1 Year
34
Yiyuan Electric Co., Ltd www.yiyen.com
APS Series Inverter & Charger & AVR
Electrical Specifications
Model
APS
1KW
APS
1.5KW
APS
2KW
APS
3KW
APS
4KW
APS
5KW
APS
6KW
Inverter
Output
Continuous Output Power
1000W
1500W
2000W
3000W
4000W
5000W
6000W
Surge Rating(20s)
3000W
4500W
6000W
9000W
12000W
15000W
18000W
Capable of Starting Electric Motor
1HP
1.5HP
2HP
3HP
4HP
5HP
6HP
Output Waveform
Pure Sine wave/Same as input(Bypass mode)
Nominal Efficiency
>88%(Peak)
Line Mode Efficiency
>95%
Power Factor
0.9-1.0
Nominal Output Voltage rms
100-110-120Vac / 220-230-240Vac
Output Voltage Regulation
±10% RMS
Output Frequency
50/60Hz ± 0.3Hz
Short Circuit Protection
Yes, Current Limit Function (Fault after 1sec)
Typical transfer Time
10ms(Max)
THD
< 10%
DC Input
Nominal Input Voltage
12.0Vdc
( *2 for 24Vdc, *4 for 48Vdc)
Minimum Start Voltage
10.0Vdc
Low Battery Alarm
10.5Vdc / 11.0Vdc
Low Battery Trip
10.0Vdc / 10.5Vdc
High Voltage Alarm & Fault
16.0Vdc
High DC Input Recovery
15.5Vdc
Low Battery Voltage Recover
13.0Vdc
Idle Consumption-Search Mode
< 25 W when Power Saver On
Charge
Input Voltage Range
Narrow: 100~135VAC / 194~243VAC;
Wide: 90~135VAC / 164~243VAC;
Input Frequency Range
Narrow: 47-55±0.3Hz for 50Hz, 57-65±0.3Hz for 60Hz
Wide:43±0.3Hz plus for 50Hz/60Hz
Output Voltage
Depends on battery type
Charger Breaker Rating
10A
10A
10A
20A
20A
30A
30A
Max Charge Rate
15A to 85A ±5A , depending on models
Over Charge Protection Shutdown
15.7V for 12Vdc ( *2 for 24Vdc, *4 for 48Vdc)
Battery type
Fast Vdc
Float Vdc
Gel U.S.A
14.0
13.7
35
Yiyuan Electric Co., Ltd www.yiyen.com
A.G.M 1
14.1
13.4
A.G.M 2
14.6
13.7
Sealed Lead Acid
14.4
13.6
Gel Euro
14.4
13.8
Open Lead Acid
14.8
13.3
Calcium
15.1
13.6
De-sulphation
15.5 for 4hrs
Remote Control
Yes. Optional
Bypass &
Protection
Input Voltage Waveform
Sine wave (Grid or Generator)
Nominal Voltage
120Vac
230Vac
Low Voltage Trip
80V/90V±4%
184V/154V±4%
Low Voltage re engage
90V/100V±4%
194V/164V±4%
High Voltage Trip
140V±4%
253V±4%
High Voltage re engage
135V±4%
243V±4%
Max Input AC Voltage
150VAC
270VAC
Nominal Input Frequency
50Hz or 60Hz (Auto detect)
Low Freq Trip
Narrow: 47±0.3Hz for 50Hz, 57±0.3Hz for 60Hz
Wide:40±0.3Hz for 50Hz/60Hz
Low Freq re engage
Narrow: 48±0.3Hz for 50Hz, 58±0.3Hz for 60Hz
Wide:45±0.3Hz for 50Hz/60Hz
High Freq Trip
Narrow: 55±0.3Hz for 50Hz, 65±0.3Hz for 60Hz
Wide: No up limit for 50Hz/60Hz
High Freq re engage
Narrow: 54±0.3Hz for 50Hz, 64±0.3Hz for 60Hz
Wide: No up limit for 50Hz/60Hz
Output Short circuit protection
Circuit breaker
Bypass breaker rating
10A
15A
20A
30A
30A
40A
40A
Transfer switch rating
30amp for UL & TUV
40amp for UL
Max bypass current
30amp
40amp
AVR
Function
Input AC Voltage Range
90-140V±4%
154-253V±4%
Stabilized Output Voltage
120VAC±10% rms
230VAC±10% rms
Nominal Voltage
110Vac
120Vac
220Vac
230Vac
240Vac
(A) Line Low loss N/W (On Battery)
84/72
92/78
168/143
176/150
183/156
(B) Line Low comeback N/W (On Boost)
89/77
97/83
178/153
186/160
193/166
(C) Line 2nd boost threshold (On Boost)
**
**
**
**
**
(D) Line 2nd boost comeback (On Boost)
**
**
**
**
**
(E) Line 1st boost threshold (On Boost)
99
108
198
207
216
(F) Line 1st boost comeback (On Normal)
103
112
205
215
225
(G) Line buck comeback (On Normal)
118
128
235
246
256
36
Yiyuan Electric Co., Ltd www.yiyen.com
(H) Line buck threshold (On Buck)
121
132
242
253
264
(I) Line high comeback (On Buck)
127
139
253
266
278
(J) Line high loss (On Battery)
132
144
263
276
288
Mechanical
Specification
Mounting
Wall mount
Inverter Dimensions(L*W*H)
382*218*179mm
442*218*179mm
598*218*179mm
Inverter Weight
16KG
17KG
20KG
24KG
35KG
45KG
45KG
Shipping Dimensions(L*W*H)
520*315*300mm
580*315*300mm
740*315*300mm
Shipping Weight
18KG
19KG
22KG
26KG
37KG
47KG
47KG
Display
Status LEDs / Status LEDs+LCD
Standard Warranty
1 Year
37
Yiyuan Electric Co., Ltd www.yiyen.com
APV Series Inverter & Solar Charger
Electrical Specifications
Model
APV
1KW
APV
1.5KW
APV
2KW
APV
3KW
APV
4KW
APV
5KW
APV
6KW
Inverter
Output
Continuous Output Power
1000W
1500W
2000W
3000W
4000W
5000W
6000W
Surge Rating(20s)
3000W
4500W
6000W
9000W
12000W
15000W
18000W
Capable of Starting Electric Motor
1HP
1.5HP
2HP
3HP
4HP
5HP
6HP
Output Waveform
Pure Sine wave/Same as input(Bypass mode)
Nominal Efficiency
>88%(Peak)
Line Mode Efficiency
>95%
Power Factor
0.9-1.0
Nominal Output Voltage rms
100-110-120Vac / 220-230-240Vac
Output Voltage Regulation
±10% RMS
Output Frequency
50/60Hz ± 0.3Hz
Short Circuit Protection
Yes, Current Limit Function (Fault after 1sec)
Typical transfer Time
10ms(Max)
THD
< 10%
DC Input
Nominal Input Voltage
12.0Vdc
( *2 for 24Vdc, *4 for 48Vdc)
Minimum Start Voltage
10.0Vdc
Low Battery Alarm
10.5Vdc / 11.0Vdc
Low Battery Trip
10.0Vdc / 10.5Vdc
High Voltage Alarm & Fault
16.0Vdc
High DC Input Recovery
15.5Vdc
Low Battery Voltage Recover
13.0Vdc
Idle Consumption-Search Mode
< 25 W when Power Saver On
Charge
Input Voltage Range
Narrow: 100~135VAC / 194~243VAC;
Wide: 90~135VAC / 164~243VAC;
Input Frequency Range
Narrow: 47-55±0.3Hz for 50Hz, 57-65±0.3Hz for 60Hz
Wide:43±0.3Hz plus for 50Hz/60Hz
Output Voltage
Depends on battery type
Charger Breaker Rating
10A
10A
10A
20A
20A
30A
30A
Max Charge Rate
15A to 85A ±5A , depending on models
Over Charge Protection Shutdown
15.7V for 12Vdc ( *2 for 24Vdc, *4 for 48Vdc)
Battery type
Fast Vdc
Float Vdc
Gel U.S.A
14.0
13.7
A.G.M 1
14.1
13.4
A.G.M 2
14.6
13.7
Sealed Lead Acid
14.4
13.6
Gel Euro
14.4
13.8
Open Lead Acid
14.8
13.3
Calcium
15.1
13.6
38
Yiyuan Electric Co., Ltd www.yiyen.com
De-sulphation
15.5 for 4hrs
Remote Control
Yes. Optional
Bypass &
Protection
Input Voltage Waveform
Sine wave (Grid or Generator)
Nominal Voltage
120Vac
230Vac
Low Voltage Trip
80V/90V±4%
184V/154V±4%
Low Voltage re engage
90V/100V±4%
194V/164V±4%
High Voltage Trip
140V±4%
253V±4%
High Voltage re engage
135V±4%
243V±4%
Max Input AC Voltage
150VAC
270VAC
Nominal Input Frequency
50Hz or 60Hz (Auto detect)
Low Freq Trip
Narrow: 47±0.3Hz for 50Hz, 57±0.3Hz for 60Hz
Wide:40±0.3Hz for 50Hz/60Hz
Low Freq re engage
Narrow: 48±0.3Hz for 50Hz, 58±0.3Hz for 60Hz
Wide:45±0.3Hz for 50Hz/60Hz
High Freq Trip
Narrow: 55±0.3Hz for 50Hz, 65±0.3Hz for 60Hz
Wide: No up limit for 50Hz/60Hz
High Freq re engage
Narrow: 54±0.3Hz for 50Hz, 64±0.3Hz for 60Hz
Wide: No up limit for 50Hz/60Hz
Output Short circuit protection
Circuit breaker
Bypass breaker rating
10A
15A
20A
30A
30A
40A
40A
Transfer switch rating
30amp for UL & TUV
40amp for UL
Max bypass current
30amp
40amp
Solar Charger
Rated Voltage
12V/24V
Rated Charge Current
60A
Rated Output Current
15A
Self Consumption
< 10mA
Bulk Charge
14.5V(default)
( *2 for 24Vdc)
Floating Charge
13.5V(default)
Equalization Charge
14.0V(default)
Over Charge Disconnection
14.8V
Over Charge Recovery
13.6V
Over Discharge Disconnection
10.8 V(default)
Over Discharge Reconnection
12.3V
Temperature Compensation
- 13.2mV/
Ambient Temperature
0-40(full load) 40-60℃(derating)
Mechanical
Specifications
Mounting
Wall mount
Inverter Dimensions(L*W*H)
598*218*179mm
470*190*340mm
Inverter Weight
21KG
22kg
23KG
27KG
38KG
48KG
49KG
Shipping Dimensions(L*W*H)
740*315*300mm
530*240*390mm
Shipping Weight
23KG
24kg
25KG
29KG
40KG
50KG
51KG
Display
Status LEDs / Status LEDs+LCD
Standard Warranty
1 Year
Specifications in this manual are subject to change without prior notice.