Yingli Solar YL220C-25b, YL250P-29b, YL215D-25b, YL260D-30b, YL315D-36b Installation And User Manual

...
Yingli Solar PV Modules, Installation and User Manual
page 1
This manual applies to photovoltaic modules (“PV modules”, also commonly known as solar panels) manufactured by Yingli Green Energy Holding Co. Ltd. (“Yingli Solar”), and is explicitly written for qualified professionals (“Installer” or “Installers”), including without limitation licensed electricians and RAL Certified PV Installers.
INTRODUCTION
Thank you for choosing Yingli Solar as your PV module provider. We appreciate your business! This manual contains important information pertaining to the electrical and mechanical installation and maintenance of PV modules, and contains safety information that you must read carefully and be familiar with before handling, installing, and/or maintaining Yingli Solar PV modules.
Yingli Solar does not assume responsibility and expressly disclaims liability for losses, damages, or expenses arising out of, or in any way connected with this Installation and User Manual. Yingli Solar assumes no responsibility for any infringement of patents or other rights of third parties, which may result from using Yingli Solar PV modules. No license is granted expressly or by implication or under any patent or patent rights. The information in this manual is believed to be reliable, but does not constitute an expressed or implied warranty. Yingli Solar reserves the right to make changes to its PV modules and other products, their specifications, or this manual without prior notice.
Yingli Solar and its subsidiaries are not liable for any damages caused by inappropriate installation, use, or maintenance of Yingli Solar PV modules, including without limitation damages, losses, and expenses caused by non­observance of the instructions of this manual or caused by or in connection with products of other manufacturers.
Yingli Solar PV modules are designed to meet the requirements for the standards IEC 61215 and IEC 61730, application class A. Modules rated for use in this application class may be used in systems operating at greater than 50 V DC or 240 W, where general contact access is anticipated. Modules qualified for safety through IEC 61730-1 and IEC 61730-2 and within this application class are considered to meet the requirements for safety class II. In the course of the PV module certification process, the compliance of this manual with the certification requirements has been verified by an independent certification laboratory.
This Installation and User Manual is available in dierent languages. In cases of discrepancy between versions, the English language version shall control.
Failure to comply with the requirements listed in this manual will invalidate the Limited Warranty for PV Modules as provided by Yingli Solar at the time of sale to the direct customer. Additional recommendations are provided to enhance safety practices and performance results. Please provide a copy of this manual to the PV system owner for their reference, and inform them of all relevant aspects of safety, operation, and maintenance.
SAFETY
General
You must understand and follow all applicable local, state, and federal regulations and standards for building construction, electrical design, fire, and safety, and must check with local authorities to determine applicable permitting requirements before attempting to install or maintain PV modules.
Rooftop PV systems should only be installed on dwellings that have been formally analyzed for structural integrity, and confirmed to be capable of handling the additional weighted load of PV system components, including PV modules, by a certified building specialist or engineer.
For your safety, do not attempt to work on a rooftop until safety precautions have been identified and taken, including without limitation fall protection measures, ladders or stairways, and personal protective equipment (PPE).
For your safety, do not install or handle PV modules under adverse conditions, including without limitation strong or gusty winds, and wet or frosted roof surfaces.
The flat-plate PV module construction consists of a laminated assembly of solar cells encapsulated within an insulating material with a rigid glass surface and an insulated substrate. The laminated assembly is supported by an aluminum frame that is also used for mounting the module. See Figure 1 for an illustration of the PV module components.
Figure 1: Module components and cross-section of the laminated assembly
Electrical
PV modules can produce current and voltage when exposed to light of any intensity. Electrical current increases with higher light intensity. DC voltage of 30 Volts or higher is potentially lethal. Contacting the live circuitry of a PV system operating under light can result in lethal electric shock.
Junction Box
Cable
Connector
Cell
Frame
1
1. Aluminum Frame
2. Glass
3. Encapsulating EVA
4. PV Cell
5. Backsheet
2
3
5
4
YINGLISOLAR.COM
YINGLI SOLAR PV MODULES
Installation and User Manual
Revision Date Apr 19th, 2016 | Applicable for IEC certified products
Yingli Solar PV Modules, Installation and User Manual
page 2
De-energize PV modules by removing them entirely from light or by covering their front surface with an opaque material. Regard the safety regulations for live electrical equipment when working with modules that are exposed to any light. Use insulated tools and do not wear metallic jewelry while working with PV modules.
In order to avoid arcing and electrical shock, do not disconnect electrical connections under load. Faulty connections can also result in arcing and electrical shock. Keep connectors dry and clean, and ensure that they are in proper working condition. Never insert metallic objects into the connectors, or modify them in any way in order to secure an electrical connection.
Do not touch or handle PV modules with broken glass, separated frames or a damaged backsheet unless the PV modules are first disconnected and you are wearing proper PPE. Avoid handling PV modules when they are wet unless cleaning the PV modules as directed in this manual. Never touch electrical connections that are wet without protecting yourself with insulated gloves.
Transport and Handling
Yingli Solar PV modules must be transported in the supplied packaging only and kept in the packaging until they are ready to be installed. Protect pallets against movement and exposure to damage during transportation. Secure pallets from falling over. Do not exceed the maximum height of pallets to be stacked, as indicated on the pallet packaging. Store pallets in a cool and dry location until the PV modules are ready to be unpackaged.
Figure 2: Pallet of PV modules
Yingli Solar PV modules are heavy, and should be handled with care. PV modules shall be handled at the frame; never use the junction box or cables as a grip. Do not exert mechanical stress on the cables. Never step on PV modules or drop or place heavy objects on them. Be careful when placing PV modules on hard surfaces, and secure them from falling. Broken glass can result in personal injury. PV modules with broken glass cannot be repaired and must not be used. Broken or damaged PV modules must be handled carefully and disposed of properly.
For unpacking PV modules from the Yingli Solar supplied packaging, first remove the pallet lid (after removing securing straps, if provided). Remove PV modules one at a time by sliding them up the channel in the package (see Figure 3). You may need to secure the remaining PV modules in the pallet packaging to prevent them from falling over.
Figure 3: Removing PV modules from a pallet
Check PV modules for damage due to transportation before they are installed; do not install damaged modules. Contact the company you purchased the Yingli
Solar PV modules from in order to obtain information on making claims for defective PV modules.
PV module surfaces are susceptible to damage that could aect the performance or safety of the PV module; do not damage or scratch the PV module surfaces, and do not apply paint or adhesive to any of the surfaces, including the frame. For your safety, do not disassemble or modify Yingli Solar PV modules in any way. Doing so may degrade performance or cause irreparable damage and will void any applicable warranties.
If it is necessary to store PV modules prior to installation, the PV modules should remain inside the packaging and protected from exposure that could compromise the durability of the packaging.
Fire
Yingli Solar PV Modules have a Class C fire resistance rating in accordance with the IEC 61730-2 certification. When PV modules are mounted on rooftops, the roof must have a fire resistant covering suitable for this application. PV modules are electrical generating devices that may aect the fire safety of a building.
The use of improper installation methods and/or defective parts may result in the unexpected occurrence of an electrical arc during operation. In order to mitigate the risk of fire in this event, PV modules should not be installed near flammable liquids, gases, or locations with hazardous materials.
In the event of a fire, PV modules may continue to produce a dangerous voltage, even if they have been disconnected from the inverter, have been partly or entirely destroyed, or the system wiring has been compromised or destroyed. In the event of fire, inform the fire crew about the particular hazards from the PV system, and stay away from all elements of the PV system during and after a fire until the necessary steps have been taken to make the PV system safe.
APPLICATION INFORMATION
Application Restrictions
Yingli Solar PV modules must be mounted on appropriate mounting structures positioned on suitable buildings, the ground, or other structures suitable for PV modules (e.g. carports, building facades or PV trackers). PV modules must not be mounted on moving vehicles of any kind. Yingli Solar PV modules must not be installed in locations where they could be submerged in water.
Yingli Solar PV modules must not be sited in locations where aggressive substances such as salt or salt-water, or any other type of corrosive agent, could aect the safety and/or performance of the PV modules. Although some types of Yingli Solar PV modules have passed the IEC 61701 salt-mist corrosion test with a salt concentration of 5% by weight, galvanic corrosion can occur between the aluminum frame of the PV module and mounting or grounding hardware if such hardware is comprised of dissimilar metals. Yingli Solar recommends that only stainless steel and aluminum metal directly contact PV modules in seaside installations to limit corrosion.
Artificially concentrated light must not be directed on Yingli Solar PV modules.
Design Recommendations
Yingli Solar recommends that PV modules be mounted at a minimum tilt angle of 10 degrees to allow for proper self-cleaning from normal rain showers.
Partial or complete shading of a PV module or modules can significantly reduce system performance. Yingli Solar recommends minimizing the amount of shade throughout the year to increase the amount of energy produced by the PV modules.
Lightning protection is recommended for PV systems that are to be installed in locations with high probability of lightning strikes.
High system voltages could be induced in the event of an indirect lightning strike, which could cause damage to PV system components. The open area of wire loops should be minimized, as shown in Figure 4, in order to reduce the risk
Series wiring (voltage additive)
Parallel wiring (current additive)
Fully engage and lock
Cap
+
Yingli Solar PV Modules, Installation and User Manual
page 4
Figure 7: Electrical circuitry of cells and bypass diodes
In the event of a known or suspected diode failure, installers or maintenance providers should contact the company the PV modules were purchased from. Never attempt to open the junction box of a Yingli Solar PV module yourself.
PV Array Grounding
For optimal performance, Yingli Solar recommends that the negative pole of the PV array be connected to ground.
Equipment Grounding
The frame of the PV module, as well as any exposed non-current-carrying metal parts of fixed equipment that are able to become energized by the PV system, must be connected to the equipment grounding conductor (EGC) in order to prevent electrical shock. Even when applicable regulations, code requirements, and standards do not require safety-related grounding, Yingli Solar recommends grounding all PV module frames in order to ensure the voltage between electrically conductive equipment and earth ground is zero in all circumstances.
Proper equipment grounding is achieved by bonding all exposed non-current­carrying metal equipment continuously to one another using an appropriately sized EGC or racking system that can be used for integrated grounding (see Option B in Grounding Methods below).
Yingli Solar PV modules employ a coated aluminum frame for corrosion resistance. In order to properly ground the module frame, the coating must be penetrated.
The potential for corrosion due to the electrochemical action between dissimilar metals in contact is minimized if the electrochemical voltage potential between the dissimilar metals is low. The grounding method must not result in the direct contact of dissimilar metals with the aluminum frame of the PV module that will result in galvanic corrosion. An addendum to UL Standard 1703 “Flat Plate Photovoltaic Modules and Panels” recommends metal combinations not exceed an electrochemical potential dierence of 0.5 Volts.
The frame rails have pre-drilled holes marked with a grounding sign, as illustrated in Figure 8. These holes should be used for grounding purposes and must not be used for mounting the PV modules. Do not drill additional holes into the frame rails.
Figure 8: Grounding hole detail
The following grounding methods are available:
Option A: Screw Assembly (see Figure 9)
1. A grounding screw assembly must be attached at a designated grounding hole location using only stainless steel hardware. Insert an M5 stainless steel screw first through the stainless steel cup washer, and then through the grounding hole.
2. Loosely engage a stainless steel backing nut and toothed lock washer to the
screw.
Figure 9: Grounding screw assembly detail
3. Bend the EGC into an omega (Ω) shape to tightly fit between the partially
installed screw head and cup washer. The EGC shall be exclusively in contact with stainless steel.
4. Tighten the screw to 2.3 N∙m torque. The toothed lock washer should be
visibly engaged to the frame.
5. Route the appropriately sized EGC in such a way as to avoid contact with the
aluminum module frame.
Option B: Racking Manufacturer Integrated Grounding Methods
Yingli Solar PV modules can be grounded by bonding PV modules to a grounded racking system. Integrated grounding methods must be certified for grounding PV modules and must be installed in accordance with the specified instructions of their respective manufacturers.
Option C: Additional Third-party Grounding Devices
Yingli Solar PV modules can be grounded using third party grounding devices so long as they are certified for grounding PV modules and the devices are installed according to the manufacturer’s specified instructions.
MECHANICAL INSTALLATION
General
Yingli Solar PV Modules have been certified for a maximum static load on the back of the module of up to 2400 Pa (i.e. wind load) and a maximum static load on the front of the module of up to either 2400 Pa or 5400 Pa (i.e. wind and snow load), depending on the module type (please refer to the data sheet for this information).
Mounting structures and other mechanical parts must be designed and approved to withstand the design wind and snow loads applicable for a particular site. Yingli Solar PV modules must not be subjected to forces from the substructure, including forces caused by thermal expansion.
The mounting method must not result in the direct contact of dissimilar metals with the aluminum frame of the PV module that will result in galvanic corrosion. An addendum to UL Standard 1703 “Flat Plate Photovoltaic Modules and Panels” recommends metal combinations not exceed an electrochemical potential dierence of 0.5 Volts.
Yingli Solar PV modules can be mounted in landscape or portrait orientation, as illustrated in Figure 10, provided that the mounting method follows one of the acceptable methods listed below.
Grounding Holes ø0.236in (6mm)
PV Laminate
Backing Nut
Toothed Lock Washer or KEPS Nut
Cup Washer
Aluminum Frame
Screw
Equipment Grounding Conductor
Landscape Orientation
Portrait Orientation
Screw
Backing Nut
Nut Washer
PV Laminate
Mounting Rail
Aluminum Frame
Yingli Solar PV Modules, Installation and User Manual
page 6
Yingli Solar PV modules are designed to withstand high snow loads. However, if removing snow is desired to enhance production, use a brush to gently remove snow. Do not try to remove frozen snow or ice from PV modules.
DECOMMISSIONING
The dismantling of PV systems must be performed with the same care and safety precautions used during the initial installation. The PV system can generate hazardous voltage even after the system has been disconnected. Follow safety regulations for working with live electrical equipment.
RECYCLING
Yingli Solar is a member of PV Cycle, the European association for voluntary take back and recycling of PV modules. Please contact PV Cycle at www. pvcycle.org for details regarding the recycling process.
© Yingli Green Energy Holding Co. Ltd. InstallationManual_IEC_EN_20160419_V03
YINGLISOLAR.COM NYSE:YGE
Yingli Green Energy Holding Co., Ltd.
service@yingli.com Service hotline:+86-312-2188055 Complaints hotline:+86-312-8922216
Yingli Solar PV Modules, Installation and User Manual
page 7
The information in this supplement is believed to be reliable, but does not constitute an expressed or implied warranty. Yingli Solar reserves the right to make changes to its PV modules and other products, their specifications, or this supplement without prior notice.
This supplement to the installation manual does not contain information about some older module series no longer being manufactured by Yingli Solar. If you require information about such modules, please contact Yingli Solar.
This supplement refers to modules of the following types:
Table 1: Module types
FAMILY YGE 60 Cell Series 2 YGE 72 Cell Series 2 PANDA 50 Cell
Series
PANDA 60 Cell
Series 2
PANDA 72 Cell
NH Series
YLM 50 Cell
Series
YLM 60 Cell
40mm Series
YLM 72 Cell 40mm
Series
TYPE YL250P-29b YL300P-35b YL220C-25b YL260C-30b YL310C-36b YL215D-25b YL260D-30b YL315D-36b
YL255P-29b YL305P-35b YL225C-25b YL265C-30b YL315C-36b YL220D-25b YL265D-30b YL320D-36b
YL260P-29b YL310P-35b YL230C-25b YL270C-30b YL320C-36b YL225D-25b YL270D-30b YL325D-36b
YL265P-29b YL315P-35b YL235C-25b YL275C-30b YL325C-36b YL230D-25b YL275D-30b YL330D-36b
YL270P-29b
YL320P-35b YL240C-25b YL280C-30b YL330C-36b YL235D-25b YL280D-30b YL335D-36b
YL275P-29b YL325P-35b
YL245C-25b YL285C-30b YL335C-36b YL240D-25b YL285D-30b YL340D-36b
YL280P-29b YL330P-35b
YL250C-25b YL290C-30b YL340C-36b YL345D-36b
YL285P-29b YL335P-35b
YL295C-30b YL345C-36b
YL290P-29b YL340P-35b YL300C-30b YL350C-36b
YL345P-35b YL355C-36b
YL350P-35b YL360C-36b
YINGLI SOLAR PV MODULES
Module Supplement
Revision Date July 20th, 2016 | Applicable for IEC certified products.
MOUNTING REQUIREMENTS
Mounting Method: Bolts and Clamps
Table 2: Mounting requirements
Modules that Require
Four (4) Connection Points
Modules that Require
Six (6) Connection Points
YGE 60 Cell Series 2 YGE 72 Cell Series 2
PANDA 50 cell series PANDA 72 Cell NH Series
PANDA 60 Cell Series 2 YLM 72 Cell 40mm Series
YLM 50 cell series
YLM 60 Cell 40mm Series
ELECTRICAL CHARACTERISTICS
Nameplate ratings are average values. The electrical characteristics are within +/- 10 percent of the indicated values of Isc, Voc, and Pmax under Standard Test Conditions (irradiance of 1000 W/m2, AM 1.5 spectrum, and a cell temperature of 25°C). Refer to module datasheets for specific power output tolerances. Note that not necessarily all power classes are available for all module series given in the first column of Table 3. Please refer to Table 1 to see which power classes actually exist for which module series.
Yingli Solar PV Modules, Installation and User Manual
page 8
Table 3: Electrical characteristics
Series Module P
max
V
mpp
I
mpp
V
oc
I
sc
Max. system
voltage
Max. series fuse
rating
[W] [V] [A] [V] [A] [V] [A]
YGE 72 Cell Series 2
YL350P-35b 350 47.2 9.51 38.2 9.17 1000 15
YL345P-35b 345 47.0 9.45 38.0 9.08 1000 15
YL340P-35b 340 46.7 9.40 37.8 9.00 1000 15
YL335P-35b 335 46.7 9. 34 3 7.6 8.91 1000 15
YL330P-35b 330 46.4 9.29 37. 4 8.84 1000 15
YL325P-35b 325 46. 3 9.24 3 7.3 8.72 1000 15
YL320P-35b 320 37. 0 8.64 46.0 9.18 1000 15
YL315P-35b 315 36.8 8.56 45.7 9.12 1000 15
YL310P-35b 310 36.3 8.53 45.6 8.99 1000 15
YL305P-35b 305 36.1 8.45 45.4 8.9 3 1000 15
YL300P-35b 300 35.8 8.37 45.2 8.86 1000 15
YGE 60 Cell Series 2
YL290P-29b 290 38.6 9.65 31.9 9.12 1000 15
YL285P-29b 285 38.4 9.55 31.6 9.02 1000 15
YL280P-29b 280 38.2 9.45 31.4 8.92 1000 15
YL275P-29b 275 3 7.9 9. 35 31.0 8.90 1000 15
YL270P-29b 270 3 7.9 9.27 3 0.7 8.80 1000 15
YL265P-29b 265 30.5 8.70 37.8 9.18 1000 15
YL260P-29b 260 30.3 8.59 37. 7 9.09 1000 15
YL255P-29b 255 3 0.0 8.49 3 7.7 9.01 1000 15
YL250P-29b 250 29.8 8.39 37. 6 8.92 1000 15
PANDA 72 Cell NH Series
YL360C-36b 360 40.2 8.95 47.8 9. 27 1000 15
YL355C-36b 355 39.8 8.92 47.6 9. 26 1000
15
YL350C-36b 350 39.4 8.89 4 7.4 9.26 1000
15
YL345C-36b 345 39.0 8.85 47. 2 9.26 1000
15
YL340C-36b 340 38.5 8.82 47. 0 9.25 1000
15
YL335C-36b 335 38.1 8.79 46.8 9.25 1000
15
YL330C-36b 330 3 7.7 8 .76 46.6 9.25 1000
15
YL325C-36b 325 37. 3 8 .72 46.4 9.24 1000
15
YL320C-36b 320 36.8 8.69 46.2 9 .24 1000
15
YL315C-36b 315 36.4 8.65 46.0 9.23 1000
15
PANDA 60 Cell Series 2
YL300C-30b 300 32.7 9.16 40.1 9.66 1000
15
YL295C-30b 295 32.4 9.11 39.9 9.62 1000
15
YL290C-30b 290 32.0 9.06 39.6 9.58 1000
15
YL285C-30b 285 31.6 9.01 39.4 9.54 1000
15
YL280C-30b 280 31.3 8.96 39.1 9.5 1000
15
YL275C-30b 275 30.9 8.91 38.8 9.47 1000
15
YL270C-30b 270 30.5 8.85 38.6 9.43 1000
15
YL265C-30b 265 30.1 8.79 38.3 9.37 1000
15
Yingli Solar PV Modules, Installation and User Manual
page 9
PANDA 50 Cell Series
YL250C-25b 250 27. 6 9.06 33.3 9.73 1000
15
YL245C-25b 245 27.3 8.97 33.1 9.62 1000
15
YL240C-25b 240 26.9 8.92 32.9 9.50 1000
15
YL235C-25b 235 26.5 8.87 32.6 9.41 1000
15
YL230C-25b 230 26 .1 8.81 32.4 9.3 4 1000
15
YL225C-25b 225 25.8 8.72 32.2 9.15 1000
15
YL220C-25b 220 25.6 8.59 32.0 9.03 1000
15
YLM 72 Cell 40mm
Series
YL345D-36b 345 38.3 9.02 47.7 9.3 8 1000
15
YL340D-36b 340 3 7.9 8.97 4 7.3 9.35 1000
15
YL335D-36b 335 37. 6 8.91 46.9 9.32 1000
15
YL330D-36b 330 37. 2 8.86 46.6 9. 29 1000
15
YL325D-36b 325 36.9 8.81 46.2 9. 27 1000
15
YL320D-36b 320 36.6 8.75 45.9 9.24 1000
15
YL315D-36b 315 36.2 8.69 45.5 9.2 1 1000
15
YLM 60 Cell 40mm
Series
YL285D-30b 285 31.7 9.00 39.6 9.41 1000
15
YL280D-30b 280 31.4 8.91 39. 3 9.3 8 1000
15
YL275D-30b 275 31.2 8.82 38.9 9.34 1000
15
YL270D-30b 270 30.9 8.73 38.6 9.31 1000
15
YL265D-30b 265 30.7 8.6 4 38.3 9. 27 1000
15
YL260D-30b 260 30.4 8.56 38.0 9.24 1000
15
YLM 50 Cell Series
YL240D-25b 240 2 7.1 8.87 32.9 9.41 1000
15
YL235D-25b 235 26.7 8.81 32.5 9.38 1000
15
YL230D-25b 230 26.3 8.75 32.1 9. 34 1000
15
YL225D-25b 225 25.9 8.69 31.7 9.3 1 1000
15
YL220D-25b 220 25.5 8.63 31.3 9.27 1000
15
YL215D-25b 215 25.1 8.57 31.0 9.24 1000
15
Yingli Solar PV Modules, Installation and User Manual
page 10
REAR AND SIDE VIEW DIMENSIONS OF MODULE SERIES WITH 50MM FRAME
UNITS: mm
PANDA 72 Cell NH Series Frame Cross Section
12
32
50
SECTION A–A
Legend
Legend
Grounding holes
Mounting holes
Drainage holes
Mounting tolerance
Yingli Solar PV Modules, Installation and User Manual
page 11
PANADA 50 Cell Series Frame Cross Section
(also valid for YLM 50Cell Series)
12
40
32
SECTION A-A
Legend
Legend
Grounding holes
Mounting holes
Drainage holes
Mounting tolerance
PANDA 60 Cell Series2 YGE 72 Cell Series 2
(also valid for YLM 60Cell 40mm Series) (also valid for YLM 72Cell 40mm Series)
REAR AND SIDE VIEW DIMENSIONS OF MODULE SERIES WITH 40MM FRAME (CONT.)
UNITS: mm
1100
946
990
1960
150
55
A
A
403
40
1960
577577
Grounding holes 8-Φ6
Mounting holes 6-6.5
×
8
Drainage holes 8-3
×
8
100
100100100
100 100
1000
946
990
967
1640
150
55
Drainage holes 8-3
×8
Mounting holes 4-6.5
×8
Grounding holes 8-
Φ6
A
A
336.5
40
1640
100100
100 100
+
-
40
1640
1640
806
850
1030
Mounting holes 4-6.5
×
8
Drainage holes 8-3
×
8
55
100
Grounding holes 8-Ø6
A
A
1000
1000
100
100
Yingli Solar PV Modules, Installation and User Manual
page 12
© Yingli Green Energy Holding Co. Ltd. Module Supplement_IEC_EN_20160720_V03
YINGLISOLAR.COM NYSE:YGE
YGE 60 Cell Series 2 Frame Cross Section
REAR AND SIDE VIEW DIMENSIONS OF MODULE SERIES WITH 35MM FRAME
UNITS: mm
1000
946
990
967
1640
150
55
Drainage holes 8-3
×
8
Mounting holes 4-6.5
×
8
Grounding holes 8-Φ6
A
A
336.5
35
1640
100100
100 100
Legend
12
35
32
SECTION A-A
Legend
Grounding holes
Mounting holes
Drainage holes
Mounting tolerance