YASKAWA CIMR-D2A0020, CIMR-D2A0005, CIMR-D2A0010, CIMR-D4A0010, CIMR-D4A0005 Quick Start Manual

...
YASKAWA D1000 Series
Power Regenerative Converter
Quick Start Guide
Type: CIMR-D Models: 200 V Class, Three-Phase Input: 5 to 130 kW
400 V Class, Three-Phase Input: 5 to 630 kW
To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance. Ensure the end user receives this manual.
MANUAL NO. TOEP C710656 06A
Copyright © 2013 YASKAWA ELECTRIC CORPORATION.
No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of Yaskawa. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, Yaskawa assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
2 YASKAWA ELECTRIC TOEP C710656 06A YASKAWA Power Regenerative Converter - D1000 Quick Start Guide

Table of Contents

1 PREFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 MECHANICAL INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3 HARMONIC FILTER MODULE INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4 ELECTRICAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5 USING THE DIGITAL OPERATOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
6 POWERING UP THE CONVERTER. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
7 OPERATION WITH THE DRIVE CONNECTED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
8 PARAMETER TABLE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
9 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
10 UL STANDARDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
YASKAWA ELECTRIC TOEP C710656 06A YASKAWA Power Regenerative Converter - D1000 Quick Start Guide 3

1 Preface

W ARNING
DANGER
W ARNING
CAUTION
CIMR-AA2A0021FAA
200V 3Phase 5.5kW/3.7kW
S/N:
危 険
据え付け、運転の前には必ず取扱説明書を読むこと。 通電中および電源遮断後5分以内はフロントカバー を外さない事。 400V級インバータの場合は、電源の中性点が接地 されていることを確認すること。(対応) 保守・点検、配線を行う場合は、出力側開閉器を 遮断後5分待って実施してください。
けが.感電のおそれがあります。
高温注意
インバータ上部、両側面は高温になります。 触らないでください。
AVERTISSMENT
NPJT31470-1
Lire le manuel avant l'installation. Attendre 5 minutes après la coupure de l'alimentation, pour permettre la décharge des condensateurs. Pour répondre aux exigences , s assurer que le neutre soit relié à la terre, pour la série 400V. Après avoir déconnécte la protection entre le driver et le moteur, veuillez patienter 5 minutes avain d’effectuer une opération de montage ou de câblage du variateur.
Risque de décharge électrique.
Surfaces Chaudes
Dessus et cotés du boitier Peuvent devenir chaud. Ne Pas toucher.
WARNING
Read manual before installing. Wait 5 minutes for capacitor discharge after disconnecting power supply. To conform to requirements, make sure to ground the supply neutral for 400V class. After opening the manual switch between the drive and motor, please wait 5 minutes before inspecting, performing maintenance or wiring the drive.
Risk of electric shock.
Hot surfaces
Top and Side surfaces may become hot. Do not touch.
LO RE
F2F1
ESC
RUN STOP
ENTERRESET
ALM
DIGITAL OPERATOR JVOP-180
1Preface
Yaskawa manufactures products used as components in a wide variety of industrial systems and equipment. The selection and application of Yaskawa products remain the responsibility of the equipment manufacturer or end user. Yaskawa accepts no responsibility for the way its products are incorporated into the final system design. Under no circumstances should any Yaskawa product be incorporated into any product or design as the exclusive or sole safety control. Without exception, all controls should be designed to detect faults dynamically and fail safely under all circumstances. All systems or equipment designed to incorporate a product manufactured by Yaskawa must be supplied to the end user with appropriate warnings and instructions as to the safe use and operation of that part. Any warnings provided by Yaskawa must be promptly provided to the end user. Yaskawa offers an express warranty only as to the quality of its products in conforming to standards and specifications published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS OFFERED. Yaskawa assumes no liability for any personal injury, property damage, losses, or claims arising from misapplication of its products. This manual is designed to ensure correct and suitable application of D1000-Series power regenerative converters. Read this manual before attempting to install, operate, maintain, or inspect a unit and keep it in a safe, convenient location for future reference. Be sure you understand all precautions and safety information before attempting application.

Applicable Documentation

The following manuals are available for D1000 series:
YASKAWA D1000 Series Power Regenerative Converter Quick Start Guide (TOEP C710656 06) (This document)
This guide is packaged together with the product and contains basic information required to install and wire the converter, in addition to an overview of fault diagnostics, maintenance, and parameter settings. It is meant to get the converter ready for a trial run with the application and for basic operation.
YASKAWA D1000 Series Power Regenerative Converter Technical Manual (SIEP C710656 06)
This manual is available for download on our documentation website, www.yaskawa.eu.com. It provides detailed information on parameter settings, functions, and MEMOBUS/Modbus specifications. Use this manual to expand the functionality of the converter and to take advantage of higher performance features.

General Warnings

Read and understand this manual before installing, operating or servicing this unit. The unit must be installed according to this manual and local codes.
The following conventions are used to indicate safety messages in this manual. Failure to heed these messages could result in serious or fatal injury or damage to the products or to related equipment and systems.
Indicates a hazardous situation, which, if not avoided, will result in death or serious injury.
Indicates a hazardous situation, which, if not avoided, could result in death or serious injury.
Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury.
4 YASKAWA ELECTRIC TOEP C710656 06A YASKAWA Power Regenerative Converter - D1000 Quick Start Guide
1 Preface
NOTICE
DANGER
W ARNING
Indicates a property damage message.

Safety Messages

Heed the safety messages in this manual.
Failure to comply will result in death or serious injury.
The operating company is responsible for any injuries or equipment damage resulting from failure to heed the warnings in this manual.
Electrical Shock Hazard
Do not install, wire, maintain, or inspect the product or replace parts while the power supply is turned on.
Failure to comply will result in death or serious injury.
Disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned off. After shutting off the power, wait for at least the amount of time specified on the unit before touching any components.
Do not turn on the power supply or supply power to the input-side AC reactor or to the harmonic filter (harmonic filter module) only.
Voltage will remain in the internal capacitor and will result in death or serious injury. Always connect a unit as shown in the Standard Connection Diagram before you turn on the power supply.
Sudden Movement Hazard
System may start unexpectedly upon application of power, resulting in death or serious injury.
Clear all personnel from the converter, drive, motor and machine area before applying power to the converter. Secure covers, couplings, shaft keys and machine loads.
Electrical Shock Hazard
Do not attempt to modify or alter the unit in any way not explained in this manual.
Failure to comply could result in death or serious injury.
Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified.
Do not allow unqualified personnel to perform work on the converter.
Failure to comply could result in death or serious injury.
Installation, maintenance, inspection, and servicing must be performed only by authorized personnel familiar with installation, adjustment, and maintenance of converters.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Always use a ground wire that complies with technical standards on electrical equipment and minimize the length of the ground wire.
Improper equipment grounding may cause dangerous electrical potentials on equipment chassis, which could result in death or serious injury.
YASKAWA ELECTRIC TOEP C710656 06A YASKAWA Power Regenerative Converter - D1000 Quick Start Guide 5
1 Preface
CAUTION
W ARNING
Make sure the protective earthing conductor complies with technical standards and local safety regulations.
Because the leakage current exceeds 3.5 mA in model 4A0630, IEC/EN 61800-5-1 states that either the power supply must be automatically disconnected in case of discontinuity of the protective earthing conductor or a protective
2
earthing conductor with a cross-section of at least 10 mm result in death or serious injury.
Use appropriate equipment for residual current monitoring/detection (RCM/RCD).
This drive can cause a residual current with a DC component in the protective earthing conductor. Where a residual current operated protective or monitoring device is used for protection in case of direct or indirect contact, always use an RCM or RCD of type B according to IEC/EN60755.
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
(Cu) or 16 mm2 (Al) must be used. Failure to comply may
Fire Hazard
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the unit matches the voltage of the incoming power supply before applying power.
When installing an IP00/IP20 converter in a closed panel or cabinet, sufficiently cool the panel or cabinet with a cooling fan or air conditioner so that the air temperature entering the unit is 50°C or cooler.
Failure to comply could result in overheating and fire.
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire.
Do not install the unit to a combustible surface. Never place combustible materials on the unit.
Crush Hazard
Only allow qualified personnel to operate a crane or hoist to transport the unit.
Failure to comply may result in serious injury or death from falling equipment.
Do not carry the converter by the front cover or the terminal cover.
Failure to comply may result in minor or moderate injury from the main body of the converter falling.
Hold the specified locations when carrying a harmonic filter module by hand.
Holding any other location when carrying the harmonic filter module could cause the module could fall and cause injury.
Carry all standard configuration and peripheral devices in a method suitable for the weight of the device.
Incorrectly handling devices could cause them to fall and result in injury or damage to the device.
6 YASKAWA ELECTRIC TOEP C710656 06A YASKAWA Power Regenerative Converter - D1000 Quick Start Guide
1 Preface
NOTICE
3
Do not disconnect the wiring to the unit and harmonic filter module while the unit is outputting a voltage.
Improper equipment sequencing could result in damage to the unit.
When connecting a unit, use a power supply with a capacity that is the same or higher than the capacity calculated by the power supply capacity selection formula below.
Power supply capacity × Input power supply rated voltage × Rated AC input current / 1000
Failure to comply could result in damage to the unit.
Observe proper electrostatic discharge procedures (ESD) when handling the converter, circuit boards, and CMOSIC.
Failure to comply may result in ESD damage to the unit circuitry.
Do not perform a withstand voltage test on any part of the unit.
Failure to comply could result in damage to the sensitive devices within the unit.
Do not operate damaged equipment.
Failure to comply could result in further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
Install adequate branch circuit short circuit protection per applicable codes.
Failure to comply could result in damage to the unit.
The converter is suitable for circuits capable of delivering not more than 100,000 RMS symmetrical Amperes, 240 Vac maximum (200 V Class) and 480 Vac maximum (400 V Class).
Prevent foreign matter such as metal shavings or wire clippings from falling into the unit during drive installation and project construction.
Failure to comply could result in damage to the unit. Place a temporary cover over the top during installation. Be sure to remove the temporary cover before start-up, as the cover will reduce ventilation and cause the unit to overheat.
Never lift the unit up while the cover is removed.
This can damage the terminal board and other components.
Do not perform signal checks during operation.
Failure to comply could result in damage to the unit.
Check the following items before you turn on the power supply.
Failure to comply could result in damage to the unit and filter module.
• Is the power supply voltage correct? 200 V Class: AC190 to 240 V 50/60 Hz 400 V Class: AC380 to 480 V 50/60 Hz
• Are the unit and the control devices connected properly (e.g., is the phase order correct)?
• Is the phase order correct between the main circuit terminals (R/L1, S/L2, and T/L3) on the unit and the power supply voltage detection terminals (r1/ 11, 1/ 21, and t1/ 31).
• Are the control circuit terminals on the unit connected properly to the control devices?
• Are the Run Commands for the unit and the control devices turned off?
Replace the cooling fan correctly according to instructions in this manual.
Incorrect cooling fan mounting direction will prevent sufficient cooling of the unit and could damage internal circuits.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance.
Use shielded, twisted-pair wires and ground the shield to the ground terminal of the unit.
YASKAWA ELECTRIC TOEP C710656 06A YASKAWA Power Regenerative Converter - D1000 Quick Start Guide 7
1 Preface
NOTICE
Do not modify the circuitry of the unit and the filter module.
Failure to comply could result in damage to the unit and will void warranty.
Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified.
Check all the wiring to ensure that all connections are correct after installing the unit and connecting any other devices.
Failure to comply could result in damage to the unit.
To get the full performance life out of the electrolytic capacitors and circuit relays, refrain from switching the unit power supply off and on more than once every 30 minutes.
If a fuse is blown or equipment for residual current monitoring/detection (RCM/RCD) is tripped, check the wiring and the selection of the peripheral devices.
Contact your supplier if the cause cannot be identified after checking the above.
Do not restart the unit or immediately operate the peripheral devices if a fuse is blown or an RCD is tripped.
Check the wiring and the selection of peripheral devices to identify the cause.
Contact your supplier before restarting the unit or the peripheral devices if the cause cannot be identified.
Do not expose the unit to halogen group disinfectants.
Failure to comply may cause damage to the electrical components in the unit.
Do not pack the unit in wooden materials that have been fumigated or sterilized.
Do not sterilize the entire package after the product is packed.

Precautions for CE Low Voltage Directive Compliance

This drive has been tested according to European standard IEC/EN61800-5-1, and it fully complies with the Low Voltage Directive.
Do not use converters in areas with pollution higher than severity 2 and overvoltage category 3 in accordance with IEC/EN664.
Ground the neutral point of the main power supply for 400 V Class converters.
8 YASKAWA ELECTRIC TOEP C710656 06A YASKAWA Power Regenerative Converter - D1000 Quick Start Guide

2 Mechanical Installation

D1000
YEU
D1000
Model
Input specifications Output specifications MASS Lot number Serial number
VAJ123456 IP00
EUJ710800
:
: AC3PH 200-240V 50/60Hz 15A : AC3PH 200-240V 50/60Hz 15A : 6.5 kg : 6W3050-2-100 : J0073D207410100
MODEL
INPUT OUTPUT MASS O / N S / N
YASKAWA ELECTRIC CORPORATION
MADE IN JAPAN
2-1 Kurosaki-shiroishi, Yahatanishi-Ku, Kitakyushu 806-0004 Japan
PASS
FILE NO: E131457
2 Mechanical Installation

Upon Receipt

Perform the following tasks after receiving the converter and the filter module:
• Inspect the converter and the harmonic filter module for damage. If the converter or the harmonic filter module appear damaged upon receipt, contact the shipper immediately.
• Verify receipt of the correct model by checking the information on the nameplate.
• If you have received the wrong model or the converter or the harmonic filter module does not function properly, contact your supplier.

Nameplate

CIMR-DC2A0005BAA
:
Model Rated output capacity Input specifications Output specifications MASS Lot number Serial number
MODEL RATED OUTPUT CAPACITY : 40kW REV : A INPUT
: AC3PH 200-240V 50/60Hz 15A
OUTPUT
: DC330V 15A
MASS
: 5 kg
O / N
: 6W3050-2-100
S / N
: J0073D207410100 IP20
FILE NO: E131457
YASKAWA ELECTRIC CORPORATION
2-1 Kurosaki-shiroishi, Yahatanishi-Ku, Kitakyusyu 806-0004 Japan
PRG : 1010
VAJ123456
PASS
MADE IN JAPAN
Software version
<1>
Figure 1
<1> The address of the head office of Yaskawa Electric Corporation (responsible for product liability) is shown on the nameplate.
Figure 1 Converter Nameplate Information Example
Figure 2 Harmonic Filter Module Nameplate Information Example
YASKAWA ELECTRIC TOEP C710656 06A YASKAWA Power Regenerative Converter - D1000 Quick Start Guide 9
2 Mechanical Installation
A
C
A
BB
C
Side Clearance Top/Bottom Clearance
D
D

Installation Environment

Install the unit in an environment matching the specifications in Tab le 1 to help prolong the optimum performance life of the converter.
Table 1 Installation Environment
Environment Conditions
Installation Area Indoors
IP00 Open Type enclosure: -10°C to +50°C IP20 Open Type enclosure: -10°C to +40°C
Ambient Tempe rature
Humidity 95% RH or less and free of condensation Storage
Tempe rature
Surrounding Area
Altitude 1000 m or lower, up to 3000 m with derating. Refer to the Technical Manual for details.
Vibration
Orientation Install the converter vertically to maintain maximum cooling effects.
Converter reliability improves in environments without wide temperature fluctuations. When using the converter in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air temperature inside the enclosure does not exceed the specified levels. Do not allow ice to develop on the converter or the harmonic filter module.
-20°C to +60°C
Install the converter and the harmonic filter module in an area free from:
• oil mist and dust
• metal shavings, oil, water, or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight.
2
10 to 20 Hz at 9.8 m/s 10 to 20 Hz at 9.8 m/s 10 to 20 Hz at 5.9 m/s
, 20 to 55 Hz at 5.9 m/s2 (2A0005 to 2A0050, 4A0005 to 4A0100)
2
, 20 to 55 Hz at 2.0 m/s2 (2A0065 to 2A0130, 4A0130 to 4A0370)
2
, 20 to 55 Hz at 2.0 m/s2 (4A0630)
NOTICE: Avoid placing unit peripheral devices, transformers, or other electronics near the unit as the noise created can lead to erroneous operation. If such devices must be used in close proximity to the unit, take proper steps to shield the unit from noise.
NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the unit during installation. Failure to comply could result in damage to the unit. Place a temporary cover over the top of the unit during installation. Remove the temporary cover before drive start-up, as the cover will reduce ventilation and cause the unit to overheat.

Installation Orientation and Spacing

Figure 3 shows the installation distance required to maintain sufficient space for airflow and wiring. Install the heatsink
against a closed surface to avoid diverting cooling air around the heatsink.
Figure 2
A – 50 mm minimum C – 120 mm minimum B – 30 mm minimum D – Airflow direction
Figure 3 Correct Installation Spacing (Single)
10 YASKAWA ELECTRIC TOEP C710656 06A YASKAWA Power Regenerative Converter - D1000 Quick Start Guide
2 Mechanical Installation
Installation Screws
Refer to Exterior and Mounting Dimensions on page 13 for the sizes of the installation screws.

Precautions and Instructions for Installation

Read the following precautions and instructions before installing models 4A0270 to 4A0630.
WARNING! Crush Hazard. Observe the following instructions and precautions. Failure to comply could result in serious injury or death from falling equipment.
Only use vertical suspension to temporarily lift the drive during installation to an enclosure panel.
Do not use vertical suspension to transport the converter.
Use screws to securely affix the converter front cover, terminal blocks, and other converter components
prior to vertical suspension.
Do not subject the converter to vibration or impact greater than 1.96 m/s2 (0.2 G) while it is suspended by the wires.
Do not attempt to flip the converter over while it is suspended by the wires.
Do not leave the converter unattended while it is suspended by the wires.
Horizontal Suspension of Models 2A0065 to 2A0130 and 4A0130 to 4A0370
To make a wire hanger or frame for use when lifting the converter with a crane, lay the converter in a horizontal position and pass a wire through the holes of the four eye bolts.
NOTICE: Damage to Equipment. When lifting the drive, confirm that the spring washer is fully closed. Failure to comply may deform or damage the drive when lifted.
Figure 3
B
A
A – No space between drive and washer C – Space between drive and washer B – Spring washer: Fully closed D – Spring washer: Open
Figure 4 Details of Spring Washers
D
C
Vertical Suspension of Models 2A0065 to 2A0130 and 4A0130 to 4A0630
Models 2A0065 to 2A0130 and 4A0130 to 4A0370
When vertical suspension of the drive is required in an enclosure panel, the orientation of the eye bolts for these drive models can be easily changed by turning the eye bolts counterclockwise 90 degrees.
Figure 4
Figure 5 Adjusting Angle of Eye Bolts
YASKAWA ELECTRIC TOEP C710656 06A YASKAWA Power Regenerative Converter - D1000 Quick Start Guide 11
2 Mechanical Installation
次回用
Wire
Suspending angle: 50° or greater
Eye bolt
次回用
Model 4A0630
When suspending model 4A0630 unit with wires, make sure to follow the procedure described below.
WARNING! Crush Hazard. Use an adequate length of wire to ensure a 50° or wider suspension angle as illustrated in Figure 7. The maximum allowable load of the eye bolts cannot be guaranteed when the converter is suspended with the wires at angles less than 50°. Failure to comply may result in serious injury or death from falling equipment.
1. Remove the four eye bolts from the unit side panels and fix them securely on the top panel.
Figure 5
Eye bolt
Figure 6 Eye Bolt Repositioning
2. Pass wire through the holes of all four eye bolts.
Figure 6
Figure 7 Suspension Wire Angle Example
3. Gradually take up the slack in the wires and hoist the unit after the wires are stretched tight.
4. Lower the unit when ready to install in the enclosure panel. Stop lowering the unit when it is near the floor then
begin lowering the unit again very slowly until the unit is placed correctly.
12 YASKAWA ELECTRIC TOEP C710656 06A YASKAWA Power Regenerative Converter - D1000 Quick Start Guide

Exterior and Mounting Dimensions

W1
H
H1
H2
W
D
D1
t1
Figure 1
4-d
次回用
IP20 Open Type Enclosure Models
2 Mechanical Installation
W1
W
4-d
H0
H1
H2
H3
Figure 2
H
t1
D1
D
Table 2 Dimensions for IP20 Open Type Enclosure: 200 V Class
Model Figure
W H D W1 H0 H1 H2 H3 D1 t1 d
Dimensions mm
2A0005 1 180 300 187 160 284 8 75 5 M5 5
2A0010 1 180 300 187 160 284 8 75 5 M5 5
2A0020 2 220 365 197 192 350 335 8 15 78 5 M6 8
Weight
kg
Table 3 Dimensions for IP20 Open Type Enclosure: 400 V Class
Model Figure
W H D W1 H0 H1 H2 H3 D1 t1 d
4A0005 1 180 300 187 160 284 8 75 5 M5 5
4A0010 1 180 300 187 160 284 8 75 5 M5 5
4A0020 2 220 365 197 192 350 335 8 15 78 5 M6 8
Dimensions mm
Weight
kg
YASKAWA ELECTRIC TOEP C710656 06A YASKAWA Power Regenerative Converter - D1000 Quick Start Guide 13
2 Mechanical Installation
W1
4-d
H1
H
H2
Max 10
W
t1
t1
D1
D
Figure 1
Max 10
D1
D
W
H1
H2
H
Max 6Max 6
6-d
t1
Figure 3
t1
W1
220 220
330 330
8-d
440
W1
H1
W
H2
Max 6
D
D1
t1
Max 6
H
t1
Figure 4
D1
D
t1
H1
H2
H
4-d
W1
W
Max 8Max 8
t1
Figure 2
IP00 Open Type Enclosure Models
Table 4 Dimensions for IP00 Open Type Enclosure: 200 V Class
Model Figure
2A0030 1 275 450 258 220 435 7.5 100 2.3 M6 20
W H D W1 H1 H2 D1 t1 d
Dimensions mm
2A0050 1 325 550 283 260 535 7.5 110 2.3 M6 32
2A0065 2 450 705 330 325 680 12.5 130 3.2 M10 57
2A0090 2 450 705 330 325 680 12.5 130 3.2 M10 61
2A0130 3 500 800 350 370 773 13 130 4.5 M12 85
Model Figure
Table 5 Dimensions for IP00 Open Type Enclosure: 400 V Class
Dimensions mm
W H D W1 H1 H2 D1 t1 d
4A0030 1 275 450 258 220 435 7.5 100 2.3 M6 21
4A0040 1 275 450 258 220 435 7.5 100 2.3 M6 21
4A0060 1 325 550 283 260 535 7.5 110 2.3 M6 34
4A0100 1 325 550 283 260 535 7.5 110 2.3 M6 36
4A0130 3 500 800 350 370 773 13 130 4.5 M12 85
4A0185 3 500 800 350 370 773 13 130 4.5 M12 85
4A0270 3 670 1140 370 440 1110 15 150 4.5 M12 183
4A0370 3 670 1140 370 440 1110 15 150 4.5 M12 194
4A0630 4 1250 1380 370 1100 1345 15 150 4.5 M12 413
Weight
kg
Weight
kg
14 YASKAWA ELECTRIC TOEP C710656 06A YASKAWA Power Regenerative Converter - D1000 Quick Start Guide

3 Harmonic Filter Module Installation

C
A
B B B
3 Harmonic Filter Module Installation

Installation Environment

Install the harmonic filter module in an environment matching the specifications in Ta ble 6 to help prolong the optimum performance life of the filter module.
Table 6 Installation Environment
Environment Conditions
Installation Area
Ambient Temperature
Humidity 95% RH or less and free of condensation Storage
Temperature
Surrounding Area
Altitude 3000 m or lower
Vibration
Indoors Install the unit in an environment that does not easily accessible such as control panel.
IP00 Open Type enclosure: -10°C to +50°C Filter module reliability improves in environments without wide temperature fluctuations. When using the filter module in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air temperature inside the enclosure does not exceed the specified levels. Do not allow ice to develop on the filter module.
-20°C to +60°C
Install the filter module in an area free from:
• oil mist and dust
• metal shavings, oil, water, or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight.
2
(20 to 55 Hz)
2.0 m/s
NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the unit and filter module during installation. Failure to comply could result in damage to the unit and the filter module. Place a temporary cover over the top of the unit and the filter module during installation. Remove the temporary cover before unit and filter module start-up, as the cover will reduce ventilation and cause the unit and the filter module to overheat.
Installation Spacing
Figure 8 shows the installation distance required to maintain sufficient space for airflow and wiring.
Figure 7
A – 50 mm minimum C – 120 mm minimum B – 30 mm minimum
Figure 8 Installation Spacing
YASKAWA ELECTRIC TOEP C710656 06A YASKAWA Power Regenerative Converter - D1000 Quick Start Guide 15
3 Harmonic Filter Module Installation
A
Precautions and Instructions for Installation of Harmonic Filter Module
Read the following precautions and instructions before installing a harmonic filter module.
WARNING! Always observe the following precautions. If handled incorrectly, the harmonic filter module may fall, possibly causing injury. Also, the harmonic filter module may be damaged.
Suspend the harmonic filter module with wires only temporarily and only when installing them in a control panel. Do not suspend them when transporting them.
Before you suspend the harmonic filter module, confirm that faceplate, top cover, and other configuration components are securely screwed in place.
Do not place the harmonic filter module on its side.
Do not leave the harmonic filter module suspended with wires for a long period of time.
Attach hooks to the specified locations when suspending the harmonic filter module with wires.
NOTICE: Do not apply excessive force to the top cover when suspending the harmonic filter. The top cover may be deformed. When lifting the module by hand, always use the holding frames and use two people. Failure to comply may damage the module.
Refer to Figure 9 and Figure 10 for details.
Figure 8
A
A
A
Figure 9
B
B
A – Suspension Holes (Two on Each Side) B – Holding Frames (One on Each Side)
Figure 9 Suspension Locations for the Harmonic Filter Module
Figure 10 Holding the Harmonic Filter Module
16 YASKAWA ELECTRIC TOEP C710656 06A YASKAWA Power Regenerative Converter - D1000 Quick Start Guide

Harmonic Filter Module Dimensions

W1
W
H
D1
D
D2
4-d
Figure 1
W
H
±
5
W1
D
4-d
D1
D2
Figure 2
WD
H
±
5
W1 D1 4-dD2
Figure 3
D1000
3 Harmonic Filter Module Installation
Table 7 Dimensions for IP00 Open Type Enclosure: 200 V Class
Model Figure
W H D W1 D1 D2 d
Dimensions mm
EUJ71080 1 209 176 285 160 240 39 M6 6.5 EUJ71081 1 209 184 295 160 250 39 M6 9 EUJ71082 2 232 265 301 203 247 44 M8 14 EUJ71083 2 260 281 305 220 256 39 M8 16 EUJ71084 2 290 348 355 250 314 30 M10 27 EUJ71085 3 290 350 352 254 314 27 M10 38 EUJ71086 3 290 387 352 254 314 27 M10 43 EUJ71087 3 350 500 380 290 350 19 M10 62
Weight
kg
Table 8 Dimensions for IP00 Open Type Enclosure: 400 V Class
Model Figure
W H D W1 D1 D2 d
Dimensions mm
EUJ71088 1 209 176 285 160 240 39 M6 7 EUJ71089 1 209 178 295 160 250 39 M6 9 EUJ71090 2 232 265 301 203 247 44 M8 15 EUJ71091 2 260 293 305 220 256 39 M8 17 EUJ71092 2 260 293 305 220 256 39 M8 19 EUJ71093 2 290 348 355 250 314 30 M10 27 EUJ71094 2 290 385 355 250 314 30 M10 39 EUJ71095 3 350 500 380 290 350 19 M10 64 EUJ71096 3 350 500 380 290 344 25 M10 73
Weight
kg
YASKAWA ELECTRIC TOEP C710656 06A YASKAWA Power Regenerative Converter - D1000 Quick Start Guide 17

4 Electrical Installation

M
D1000
+
-
r1/
11
1/
21
t1/
31
S1
S2
S3
S4
S5
S6
S7
S8
E(G)
RUN-SB
External fault
Fault reset
(Reserved)
(Reserved)
(Reserved)
External Baseblock
Shield ground terminal
STOP
VI
MEMOBUS/ Modbus comm. RS-422/RS-485 max. 115.2 kbps
+
1
-
Converter
Drive
Motor
Multi-function digital inputs (default setting)
+V
A1
A2
A3 AC
(Reserved)
(Reserved)
(Reserved)
Control Circuit
-V
Analog Input 1
Analog Input 2
Analog Input 3
DIP Switch S1
Termination resistor (120 Ω, 1/2 W)
DIP Switch S2
R+
R-
S+
S-
IG
Three­Phase Power Supply
Input AC
<2><3>
reactor
Harmonic filter module
<3>
U
V
W
X
Y
Z
R/L1
S/L2
T/L3
RCD or MCCB
X
Y
Z
R/L1
S/L2
T/L3
r
t
CN5-A
CN5-B
CN5-C
Option card connectors
Ground
Sink
Power supply +10.5 Vdc, max. 20 mA
Power supply, -10.5 Vdc, max. 20 mA
<7>
<4><5>
<1>
<4><5>
MA
MB
MC
Fault relay output 250 Vac, max. 1 A 30 Vdc, max 1 A (min. 5 Vdc, 10 mA)
Multi-function relay output (During MC on) 250 Vac, max. 1 A 30 Vdc, max 1 A (min. 5 Vdc, 10 mA)
Multi-function relay output (Converter Ready) 250 Vac, max. 1 A 30 Vdc, max 1 A (min. 5 Vdc, 10 mA)
Multi-function relay output (During Run)
<6>
250 Vac, max. 1 A 30 Vdc, max 1 A (min. 5 Vdc, 10 mA)
M1
M2
M3
M4
M5
M6
0 V
FM
AM
AC
E (G)
<9>
<9>
Multi-function analog output 1 (Output frequency)
-10 to +10 Vdc (2mA) or 4 to 20 mA
Multi-function analog output 2 (Output current)
-10 to +10 Vdc (2mA) or 4 to 20 mA
FM
AM
SC
+24 V
Sink / Source mode selection wire link (default: Sink)
SP
SN
<8>
shielded line twisted-pair shielded line main circuit terminal control circuit terminal
+
+
YEU
4 Electrical Installation
The figure below shows the main and control circuit wiring.
Figure 10
<1> NOTICE: When installing a noise filter on the converter power supply, use a reactor-type noise filter (without a capacitor), such as
a zero phase reactor, and install it after the MCCB on the power supply side. Do not install a filter with a built-in capacitor as the harmonic components may cause the capacitor to overheat or may damage the capacitor.
Figure 11 Standard Connection Diagram (example: model 2A0030, 2A0130, 4A0030 to 4A0185)
<2> Do not use a line longer than 10 m to connect the input AC reactor and the converter. <3> Use the specified AC reactor and harmonic filter module. Non-specified devices may cause erroneous operation. <4> Do not use a DC bus line that is longer than 5 m to connect the converter and drive. <5> NOTICE: When installing a breaker or contactor on the converter side for an emergency shutoff, confirm that the CHARGE
indicators on the drive and converter are not lit before closing the breaker or contactor on the converter output (DC) side. If the power supply is turned on while there is a voltage charge, an overcurrent will flow and the device may be damaged. Always confirm that the breaker or contactor on the unit output (DC) side is turned on before applying power to the converter.
<6> Sequence the operation so that the converter starts operation before the drive when power is applied. Sequence the stopping
operation to turn off the drive first, then the motor, and finally the converter. Operating the drive without operating the converter or
turning off the power supply unit during operation may trigger a converter fault. <7> Do not connect a power supply to the drive AC power supply terminals (R/L1, S/L2, and T/L3). <8> The connections are shown for sequence connections with no-voltage contacts or NPN transistors for the sequence input signals
(S1 to S8). Use jumper S3 to select between Sink mode and Source mode. The default setting is Sink mode. <9> Multi-function analog outputs work with devices such as analog frequency meters, ammeters, voltmeters, and wattmeters. They are
not intended for use as a feedback-type signal.
18 YASKAWA ELECTRIC TOEP C710656 06A YASKAWA Power Regenerative Converter - D1000 Quick Start Guide
Loading...
+ 39 hidden pages