YASKAWA CIMR-A2A0110, CIMR-A2A0138, CIMR-A2A0169, CIMR-A2A0211, CIMR-A2A0250 Quick Start Manual

...
Page 1
YASKAWA AC Drive A1000
High Performance Vector Control Drive
Quick Start Guide
MANUAL NO. TOEP C710616 27D
Type: CIM R- ACA Models:
200 V Class: 0.4 to 110 kW 400 V Class: 0.4 to 630 kW
Page 2
2 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
Copyright © 2008 YASKAWA ELECTRIC CORPORATION.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of Yaskawa. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, Yaskawa assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
Page 3
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 3
Table of Contents
1 SAFETY INSTRUCTIONS AND GENERAL WARNINGS . . . . . . . . . . . . . . . . . . . . . . . 4
2 MECHANICAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3 ELECTRICAL INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4 KEYPAD OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5 START UP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6 PARAMETER TABLE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
7 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
8 SAFE DISABLE INPUT FUNCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
9 UL STANDARDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Page 4
4 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
1 Safety Instructions and General Warnings
1 Safety Instructions and General Warnings
Yaskawa Electric supplies component parts for use in a wide variety of industrial applications. The selection and application of Yaskawa products remain the responsibility of the equipment designer or end user. Yaskawa accepts no responsibility for the way its products are incorporated into the final system design. Under no circumstances should any Yaskawa product be incorporated into any product or design as the exclusive or sole safety control. Without exception, all controls should be designed to detect faults dynamically and fail safely under all circumstances. All products designed to incorporate a component part manufactured by Yaskawa must be supplied to the end user with appropriate warnings and instructions as to the safe use and operation of that part. Any warnings provided by Yaskawa must be promptly provided to the end user. Yaskawa offers an express warranty only as to the quality of its products in conforming to standards and specifications published in the manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS OFFERED. Yaskawa assumes no liability for any personal injury, property damage, losses, or claims arising from misapplication of its products.
Applicable Documentation
The following manuals are available for A1000 series drives:
General Warnings
The following conventions are used to indicate Safety messages in this manual:
A1000 Series AC Drive Technical Manual
This manual provides detailed information on parameter settings, drive functions, and MEMOBUS/ Modbus specifications. Use this manual to expand drive functionality and to take advantage of higher performance features.
A1000 Series AC Drive Quick Start Guide (this book)
Read this manual first. This guide is packaged together with the product. It contains basic information required to install and wire the drive, in addition to an overview of fault diagnostics, maintenance, and parameter settings. Use the information in this book to prepare the drive for a trial run with the application and for basic operation.
W ARNING
Read and understand this manual before installing, operating or servicing this drive.
All warnings, cautions, and instructions must be followed.
All work must be performed by qualified personnel.
The drive must be installed according to this manual and local codes.
Heed the safety messages in this manual.
The operating company is responsible for any injuries or equipment damage resulting from failure to heed the warnings in this manual.
W ARNING
Indicates a hazardous situation, which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury.
NOTICE
Indicates a property damage message.
CIMR-AA2A0021FAA
200V 3Phase 5.5kW/3.7kW
S/N:
危 険
据え付け、運転の前には必ず取扱説明書を読むこと。 通電中および電源遮断後5分以内はフロントカバー を外さない事。 400V級インバータの場合は、電源の中性点が接地 されていることを確認すること。(対応) 保守・点検、配線を行う場合は、出力側開閉器を 遮断後5分待って実施してください。
けが.感電のおそれがあります。
高温注意
インバータ上部、両側面は高温になります。 触らないでください。
AVERTISSMENT
NPJT31470-1
Lire le manuel avant l'installation. Attendre 5 minutes après la coupure de l'alimentation, pour permettre la décharge des condensateurs. Pour répondre aux exigences , s assurer que le neutre soit relié à la terre, pour la série 400V. Après avoir déconnécte la protection entre le driver et le moteur, veuillez patienter 5 minutes avain d’effectuer une opération de montage ou de câblage du variateur.
Risque de décharge électrique.
Surfaces Chaudes
Dessus et cotés du boitier Peuvent devenir chaud. Ne Pas toucher.
WARNING
Read manual before installing. Wait 5 minutes for capacitor discharge after disconnecting power supply. To conform to requirements, make sure to ground the supply neutral for 400V class. After opening the manual switch between the drive and motor, please wait 5 minutes before inspecting, performing maintenance or wiring the drive.
Risk of electric shock.
Hot surfaces
Top and Side surfaces may become hot. Do not touch.
LO RE
F2F1
ESC
RUN STOP
ENTERRESET
ALM
DIGITAL OPERATOR JVOP-180
Page 5
1 Safety Instructions and General Warnings
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 5
Safety Warnings
W ARNING
Electrical Shock Hazard
Do not attempt to modify or alter the drive in any way not explained in this manual.
Yaskawa is not responsible for the damage caused by modification of the product made by the user. Failure to comply could result in death or serious injury from operation of damaged equipment.
Do not touch any terminals before the capacitors have fully discharged.
Failure to comply could result in death or serious injury. Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the
power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe level.
Do not allow unqualified personnel to use equipment.
Failure to comply could result in death or serious injury. Maintenance, inspection, and replacement of parts must be performed only by authorized personnel familiar with
installation, adjustment, and maintenance of AC drives.
Do not change wiring, remove covers, connectors or options cards, or attempt to service the drive with power applied to the drive.
Failure to comply could result in death or serious injury. Disconnect all power to the drive and check for unsafe voltages before servicing.
Always ground the motor-side grounding terminal.
Improper equipment grounding could result in death or serious injury by contacting the motor case.
Do not perform work on the drive while wearing loose clothing, jewelry or without eye protection.
Failure to comply could result in death or serious injury. Remove all metal objects such as watches and rings, secure loose clothing, and wear eye protection before beginning
work on the drive.
Never short the output circuits of the drive.
Do not short the output circuits of the drive. Failure to comply could result in death or serious injury.
Make sure the protective earthing conductor complies with technical standards and local safety regulations.
When an EMC filter is installed or with models CIMR-A4A0414 and larger, the leakage current exceeds 3.5 mA. Therefore according to IEC 61800-5-1 automatic power supply interruption in case of discontinuity of the protective earthing conductor must be provided or a protective earthing conductor with a cross section of at least 10 mm
2
(Cu) or
16 mm
2
(Al) must be used.
Use appropriate equipment for residual current monitoring/detection (RCM/RCD).
This drive can cause a residual current with a DC component in the protective earthing conductor. Where a residual current operated protective or monitoring device is used for protection in case of direct or indirect contact, always use an RCM or RCD of type B according to IEC 60755.
Sudden Movement Hazard
Stay clear of the motor during rotational Auto-Tuning. The motor may start operating suddenly.
During automatic starting of equipment, the machine may start moving suddenly, which could result in death or serious injury.
System may start unexpectedly upon application of power, resulting in death or serious injury.
Clear all personnel from the drive, motor, and machine area before applying power. Secure covers, couplings, sh aft keys, and machine loads before applying power to the drive.
Page 6
1 Safety Instructions and General Warnings
6 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
Fire Hazard
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire. Ve rify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.
Do not use improper combustible materials in drive installation, repair or maintenance.
Failure to comply could result in death or serious injury by fire. Attach the drive or braking resistors to metal or other noncombustible material.
Do not connect the AC power line to the output terminals of the drive.
Failure to comply could result in death or serious injury by fire as a result of drive damage from line voltage application to output terminals.
• Do not connect AC line power to output terminals U, V, and W.
• Make sure that the power supply lines are connected to main circuit input terminals R/L1, S/L2, T/L3 (or R/L1 and S/ L2 for single-phase power).
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
Crush Hazard
Use a dedicated lifter when transporting the drive by a lifter.
Improper lifter may cause the drive to drop, resulting in serious injury.
Only allow qualified personnel to operate a crane or hoist to transport the drive.
Failure to comply could result in death or serious injury from falling equipment.
CAUTION
Crush Hazard
Do not carry the drive by the front cover.
Failure to comply may result in minor or moderate injury from the main body of the drive falling.
Burn Hazard
Do not touch the heatsink or braking resistor hardware until a powered-down cooling period has elapsed.
NOTICE
Equipment Hazard
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
Do not perform a withstand voltage test on any part of the unit.
Failure to comply could result in damage to the sensitive devices within the drive. Use power off resistance checks to determine shortcircuits.
Do not operate damaged equipment.
Failure to comply could result in further damage to the equipment. Do not connect or operate any equipment with visible damage or missing parts.
W ARNING
Page 7
1 Safety Instructions and General Warnings
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 7
Precautions for CE Low Voltage Directive Compliance
This drive has been tested according to European standard EN61800-5-1, and it fully complies with the Low Voltage Directive. The following conditions must be met to maintain compliance when combining this drive with other devices:
Do not use drives in areas with pollution higher than severity 2 and overvoltage category 3 in accordance with IEC664. Ground the neutral point of the main power supply for 400 V Class drives.
If a fuse is blown or equipment for residual current monitoring/detection (RCM/RCD) is tripped, check the wiring and the selection of the peripheral devices.
Contact your supplier if the cause cannot be identified after checking the above.
Do not restart the drive until 5 minutes passes and CHARGE lamp is OFF or immediately operate the peripheral devices if a fuse is blown or equipment for residual current monitoring/detection (RCM/RCD) is tripped.
Check the wiring and the selection of peripheral devices to identify the cause. Contact your supplier before restarting the drive or the peripheral devices if the cause cannot be identified.
For models CIMR-A4A0930 and 4A1200, make sure to install a fuse and equipment for residual current monitoring/detection (RCM/RCD).
Failure to comply may result in serious damage to the facilities in case the drive is defected.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance. Use shielded twisted-pair wires and ground the shield to the ground terminal of the drive.
Do not carelessly connect parts or devices to the drives braking transistor terminals.
Failure to comply could result in damage to the drive or braking circuit. Carefully review instruction manual TOBP C720600 00 when connecting a braking option to the drive.
Do not modify the drive circuitry.
Failure to comply could result in damage to the drive and will void warranty. Yaskawa is not responsible for modification of the product mad e by the user. This product must not be modified.
Check all the wiring to ensure that all connections are correct after installing the drive and connecting other devices.
Failure to comply could result in damage to the drive.
Improper application of devices on drive output circuits can damage the drive
Do not connect unapproved LC or RC interference suppression filters, capacitors, ground fault circuits, or overvoltage protection devices to the drive.
Fire Hazard
Install adequate branch circuit short circuit protection per applicable codes.
The drive is suitable for circuits capable of delivering not more than 100,000 RMS symmetrical Amperes, 240 Vac maximum (200 V Class) and 480 Vac maximum (400V Class). Inadequate branch short circuit protection damage or serious injury by fire.
NOTICE
Page 8
8 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
2 Mechanical Installation
2 Mechanical Installation
Upon Receipt
Perform the following tasks after receiving the drive:
• Inspect the drive for damage. If the drive appears damaged upon receipt, contact your supplier.
• Verify receipt of the correct model by checking the information on the nameplate. If you have received the wrong model, contact your supplier.
Installation Environment
For optimum performance life of the drive, install the drive in an environment that meets the conditions listed below.
Installation Orientation and Spacing
Always install the drive in an upright position. Leave space around the unit for proper cooling as shown in the figure on the right.
Note: Several units can be installed closer together than shown in the figure by
using “Side-by-Side” mounting. For details refer to the Technical Manual.
Environment Conditions
Installation Area
<1> Models CIMR-A4A0930 and 4A1200 are rated at 5.9 m/s
2
.
Indoors
Ambient Temperature
-10°C to +40°C (IP20/NEMA Type 1 Enclosure)
-10°C to +50°C (IP00 Enclosure) Drive reliability improves in environments without wide temperature fluctuations. When using the drive in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air temperature inside the enclosure does not exceed the specified levels. Do not allow ice to develop on the drive.
Humidity
95% RH or less and free of condensation
Storage Temperature
-20 to +60°C
Surrounding Area
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight
Altitude
1000 m, up to 3000 m with derating (for details, refer to the Technical Manual)
Vibration
10 to 20 Hz at 9.8 m/s2 <1> 20 to 55 Hz at 5.9 m/s2 (Models CIMR-2A0004 to 2A0211 and 4A0002 to 4A0165) or,
2.0 m/s
2
(Models CIMR-A2A0250 to 2A0415 and 4A0208 to 4A1200)
Orientation Install the drive vertically to maintain maximum cooling effects.
50 mm
50 mm
30 mm 30 mm
120 mm
120 mm
Ai
r
Page 9
2 Mechanical Installation
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 9
Instructions on Installation of Models CIMR-A4A0930 and 4A1200
Read the following precautions and instructions before installing the largest-capacity models, 4A0930 and 4A1200.
WARNING! Be sure to observe the following instructions and precautions. Failure to comply could result in minor or moderate injury and damage to the drive from falling equipment.
• Vertical suspension of the drive should be used only for temporarily lifting the drive for installation in the enclosure panel. Do not vertically suspend for transportation of the drive.
• Before vertical suspension, make sure that the drive front cover, terminal blocks and other drive components are securely fixed with screws.
• Do not subject the drive to vibration or impact greater than 1.96 m/s
2
(0.2 G) while it is suspended by the wires.
• Do not overturn the drive.
• Do not leave the drive for a long time while it is suspended by the wires
Procedure for Vertical Wire Suspension of the Drive
• Use the wire of a length that ensures a 50 degree or wider suspending angle, as illustrated in the figure below. The maximum allowable load of the eye bolts for suspension cannot be guaranteed when the drive is suspended with the wires at an angle less than 50 degrees.
• When lifting the drive with a crane after wires are passed to hold it, make sure to follow the procedure described below.
1. Remove the four eye bolts from the drive side panels, and fix them securely on the top panel (See the figure
below.).
2. Pass wire through the holes of all the four eye bolts (See the figure below).
3. Take up the slack in the wires gradually with a crane, and when the wires are confirmed to have stretched tight,
hoist the drive.
4. When ready to install the drive in the enclosure panel, lower the drive. Halt lowing once when the drive has
reached near the floor, and then lower the drive again very slowly.
Eye bolt
Eye bolt
Wires
Suspending angle: 50 degree or greater
Page 10
2 Mechanical Installation
10 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
Dimensions
IP20/NEMA Type 1 Enclosure Drives
Note: IP20/NEMA Type 1 Enclosure drives are equipped with a top protective cover. Removing this cover voids NEMA Type 1
protection but still keeps IP20 conformity.
Model
CIMR-A
Fig.
Dimensions (mm)
Weight
(kg)
W H D W1 H0 H1 H2 H3 D1 t1 t2 d
2A0004
1
140 260 147 122 248 6 – 38 5 – M5 3.1
2A0006 140 260 147 122 248 6 – 38 5 – M5 3.1 2A0010 140 260 147 122 248 6 – 38 5 – M5 3.2 2A0012 140 260 147 122 248 6 – 38 5 – M5 3.2 2A0021 140 260 164 122 248 6 – 55 5 – M5 3.5 2A0030 140 260 167 122 248 6 – 55 5 – M5 4.0 2A0040 140 260 167 122 248 6 – 55 5 – M5 4.0 2A0056 180 300 187 160 284 8 – 75 5 – M5 5.6 2A0069 220 350 197 192 335 8 – 78 5 – M6 8.7 2A0081 2 220 365 197 192 350 335 8 15 78 5 – M6 9.7 4A0002
1
140 260 147 122 248 6 – 38 5 – M5 3.2
4A0004 140 260 147 122 248 6 – 38 5 – M5 3.2 4A0005 140 260 147 122 248 6 – 38 5 – M5 3.2 4A0007 140 260 164 122 248 6 – 55 5 – M5 3.4 4A0009 140 260 164 122 248 6 – 55 5 – M5 3.5 4A0011 140 260 164 122 248 6 – 55 5 – M5 3.5 4A0018 140 260 167 122 248 6 – 55 5 – M5 3.9 4A0023 140 260 167 122 248 6 – 55 5 – M5 3.9 4A0031 180 300 167 160 284 8 – 55 5 – M5 5.4 4A0038 180 300 187 160 284 8 – 75 5 – M5 5.7 4A0044 220 350 197 192 335 8 – 78 5 – M6 8.3
W1
1.5
H
H1
H2
W
D
D1
t1
H2
W1
1.5
H
H0
H1
W
D1
D
t1
H3
Figure 1
Figure 2
4-d
4-d
Page 11
2 Mechanical Installation
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 11
IP00 Enclosure Drives
Model
CIMR-A
Fig.
Dimensions (mm)
Weight
(kg)
W H D W1 H1 H2 D1 t1 t2 d
2A0110
3
250 400 258 195 385 7.5 100 2.3 2.3 M6 21
2A0138 275 450 258 220 435 7.5 100 2.3 2.3 M6 25 2A0169 325 550 283 260 535 7.5 110 2.3 2.3 M6 37 2A0211 325 550 283 260 535 7.5 110 2.3 2.3 M6 38 2A0250 450 705 330 325 680 12.5 130 3.2 3.2 M10 76 2A0312 450 705 330 325 680 12.5 130 3.2 3.2 M10 80 2A0360 500 800 350 370 773 13 130 4.5 4.5 M12 98 2A0415 500 800 350 370 773 13 130 4.5 4.5 M12 99 4A0058 250 400 258 195 385 7.5 100 2.3 2.3 M6 21 4A0072 275 450 258 220 435 7.5 100 2.3 2.3 M6 25 4A0088 325 510 258 260 495 7.5 105 2.3 3.2 M6 36 4A0103 325 510 258 260 495 7.5 105 2.3 3.2 M6 36 4A0139 325 550 283 260 535 7.5 110 2.3 2.3 M6 41 4A0165 325 550 283 260 535 7.5 110 2.3 2.3 M6 42 4A0208 450 705 330 325 680 12.5 130 3.2 3.2 M10 79 4A0250 500 800 350 370 773 13 130 4.5 4.5 M12 96 4A0296 500 800 350 370 773 13 130 4.5 4.5 M12 102 4A0362 500 800 350 370 773 13 130 4.5 4.5 M12 107 4A0414 4 500 950 370 370 923 13 135 4.5 4.5 M12 125 4A0515
5 670 1140 370 440 1110 15 150 4.5 4.5 M12
216
4A0675 221 4A0930
6 1250 1380 370 1110 1345 15 150 4.5 4.5 M12
545
4A1200 555
D
Figure 6
D1
D
t2
H1
H2
H
4-d
W1
W
Max 7.7Max 7.7
t1
W1
4-d
H1
H
H2
Max 10 Max 10
W
t2
t1
D1
D
Figure 3
Figure 4
Figure 5
D1
W
H1
H2
H
Max 6Max 6
4-d
t2
t1
W1
220 220
330 330
8-d
440
W1
H1
H
W
H2
D
Max 6Max 6
D1
t1
t2
Page 12
12 YA SKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
3 Electrical Installation
3 Electrical Installation
The figure below shows the main and control circuit wiring.
<1> Remove the jumper when installing a DC reactor. Models CIMR-A2A110 through 0415 and 4A0058 through 1200 come with a built-in DC
reactor. <2> Never short terminals SP and SN as doing so will damage the drive. <3> Disconnect the wire jumper between H1 - HC and H2 - HC when utilizing the Safe Disable input.
Three-phase power supply 200 to 400 V 50/60 Hz
R/L1 S/L2
T/L3
Main
Switch
Fuse
EMC Filter
+
+
+
++
M
U/T
1
V/T2
W/T
U
V
W
3
Ground
Terminals -, +1, +2, B1, B2 are for connection options. Never connect power supply lines to these terminals
DC reactor
(option)
UX
Thermal relay
(option)
+
+
+
++
+
UX
S
1
S2
S3
S4
S5
S6
S7
MP
DM
DM
RP
A
1
A2
A3
0
V
AC
R
R
S
S
IG
H
1
H2
HC
Drive
B112
B2
2 kΩ
S8
SC
0 V
0 V
AC
FM
AM
AC
E (G)
S
1
S2
<1>
<3>
+24 V
+V
MA
M
1
M2
MB
MC
Jumper
Braking resistor (option)
Forward Run / Stop
Reverse Run / Stop
External fault
Fault reset
Multi-speed step 1
Multi-speed step 2
External Baseblock
Jog speed
Multi-function
digtial inputs
(default setting)
Sink / Source mode selection wire link (default: Sink)
CN5-C
CN5-B
CN5-A
Option card connectors
Pulse Train Input (max 32 kHz)
Shield ground terminal
Multi-function analog/ pulse
train inputs
Power supply +10.5 Vdc, max. 20 mA
Analog Input 1 (Frequency Reference Bias)
-10 to +10 Vdc (20 kΩ)
Analog Input 2 (Frequency Reference Bias)
-10 to +10 Vdc (20 kΩ) 0 or 4 to 20 mA (250 Ω)
Analog Input 3 / PTC Input (Aux. frequency reference)
-10 to +10 Vdc (20 kΩ)
V
Power supply, -10.5 Vdc, max. 20 mA
Safety switch
MEMOBUS/Modbus
comm. RS485/422
max. 115.2 kBps
Safe Disable inputs
Wire
jumper
Open
Safety relay /
controller
Termination resistor
(120 Ω, 1/2 W)
DIP Switch S2
Fault relay output 250 Vac, max. 1 A 30 Vdc, max 1 A (min. 5 Vdc, 10 mA)
Multi-function relay output (During Run) 250 Vac, max. 1 A 30 Vdc, max 1 A (min. 5 Vdc, 10 mA)
Multi-function pulse train output (Output frequency) 0 to 32 kHz (2.2 kΩ)
Multi-function analog output 1 (Output frequency)
-10 to +10 Vdc (2mA) or 4 to 20 mA
Multi-function analog output 2 (Output current)
-10 to +10 Vdc (2mA) or 4 to 20 mA
EDM (Safety Electronic Device Monitor)
Main Circuit
Control Circuit
shielded line
twisted-pair shielded line
main circuit terminal
control circuit terminal
R/L1
S/L2
T/L3
Motor
Shielded
Cable
M3
M4
Multi-function relay output (Zero Speed) 250 Vac, max. 1 A 30 Vdc, max 1 A (min. 5 Vdc, 10 mA)
M5
M6
Multi-function relay output (Speed Agree 1) 250 Vac, max. 1 A 30 Vdc, max 1 A (min. 5 Vdc, 10 mA)
SP
SN
AM
FM
V
I
V
I
DIP Switch S1 A2 Volt/Curr. Sel
DIP Switch S4 A3 Analog/PTC Input Sel
PTC
AI
Off
On
DIP Switch S2 Term. Res. On/Off
Jumper S3 H1, H2 Sink/Source Sel.
Jumper S5 FM/AM Volt./Curr. Selection
Terminal board jumpers and switches
FM
+
AM
<2>
Page 13
3 Electrical Installation
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 13
Wiring Specification
Main Circuit
Use the fuses and line filters listed in the table below when wiring the main circuit. Make sure not to exceed the given tightening torque values.
Model
CIMR-A
EMC Filter
[Schaffner]
Main Fuse
[Bussmann]
Recom.
Motor cable
(mm2)
Main Circuit Terminal Sizes
R/L1,S/L2,T/L3,
U/T1,V/T2,W/T3,
– , +1, +2
+3 B1, B2
2A0004
<1> Connect two of the same filters in parallel. Refer to the Technical Manual for details.
FS5972-10-07
FWH-70B
2.5 M4
M4
M4
2A0006 2A0010
FS5972-18-07
2A0012 2A0021
FS5972-35-07
FWH-90B
2A0030 FWH-100B 6
M5
2A0040
FS5972-60-07
FWH-200B
10
2A0056
16
M6
M5 M6
2A0069
FS5972-100-35
M8
2A0081
FWH-300A
25
2A0110
FS5972-170-40
35 M8
M8
2A0138 FWH-350A 50
M10
M10
2A0169
FS5972-250-37 FWH-400A
70
M10
2A0211 95 2A0250
FS5972-410-99
FWH-600A
95 × 2P
M12 M12
2A0312 FWH-700A 2A0360
FS5972-600-99
FWH-800A 240
2A0415 FWH-1000A 300 4A0002
FS5972-10-07
FWH-40B
2.5 M4
M4
M4
4A0004 FWH-50B 4A0005
FWH-70B
4A0007 4A0009
FS5972-18-07 FWH-90B
4A0011 4A0018
FS5972-35-07
FWH-80B
M5
4A0023 FWH-100B 4 4A0031 FWH-125B
6M5
M5
M6
4A0038
FS5972-60-07
FWH-200B
4A0044
FWH-250A
16
M6
M8
4A0058
M8
M8
4A0072
FS5972-100-35 25
4A0088
M10
4A0103
FS5972-170-40
35
4A0139 FWH-350A 50
M10 M10
4A0165 FWH-400A 70 4A0208 FS5972-250-37 FWH-500A 95 4A0250
FS5972-410-99
FWH-600A 120
4A0296 FWH-700A 185
M12 M12
4A0362 FWH-800A 240 4A0414
FS5972-600-99
FWH-800A 95 × 2P
M12
4A0515 FWH-1000A 150 × 2P 4A0675 FS5972-800-99 FWH-1200A 95 × 4P 4A0930 FS5972-600-99 <1> FWH-1200A 120 × 4P 4A1200 FS5972-800-99 <1> FWH-1600A (95 × 4P) × 2
Page 14
3 Electrical Installation
14 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
Tightening Torque Values
Tighten the main circuit terminals using the torque values provided by the table below.
Control Circuit
The control terminal board is equipped with screwless terminals. Always use wires within the specification listed below . For safe wiring it is recommended to use solid wires or flexible wires with ferrules. The stripping length respecti vely ferrule length should be 8 mm.
EMC Filter Installation
This drive has been tested in accordance with European standards EN61800-3. In order to comply to the EMC standards, wire the main circuit as described below.
1. Install an appropriate EMC noise filter to the input side. See the table in Main Circuit on page 13 or refer to the
Technical Manual for details.
2. Place the drive and EMC noise filter in the same enclosure.
3. Use braided shield cable for the drive and motor wiring.
4. Remove any paint or dirt from ground connections for minimal ground impedance.
5. Install an DC reactor at drives smaller than 1 kW for compliance with the EN61000-3-2. Refer to the Technical Manual or contact your supplier for details.
Terminal Size M4 M5 M6 M8 M10 M12
Tightening Torque (N"m) 1.2 to 1.5 2.0 to 2.5 4.0 to 6.0 9.0 to 11.0 18.0 to 23.0 32.0 to 40.0
Wire Type Wire size (mm2)
Solid 0.2 to 1.5
Flexible 0.2 to 1.0
Flexible with ferrule 0.25 to 0.5
L3L3L2L2L1L1L3 L2 L1
E
L3
L2
L1
PE
Make sure the ground wire is grounded
Enclosure panel
Metal plate
Grounding surface
(remove any paint or sealant)
Drive
Grounding surface (remove any paint or sealant)
Motor cable (braided shield cable, max. 10 m)
Cable clamp
Ground plate (scrape off any visible paint)
EMC noise filter
Motor
Ground the cable shield
Page 15
3 Electrical Installation
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 15
Main and Control Circuit Wiring
Wiring the Main Circuit Input
Consider the following precautions for the main circuit input.
• Use fuses recommended in Main Circuit on page 13 only.
• If using a ground fault circuit breaker, make sure that it can detect both DC and high frequency current.
• If using an input switch is used, make sure that the switch does not operate not more than once every 30 minutes.
• Use insulation caps when wiring the drive with crimp terminals. Take particular care to ensure that wiring does not touch neighboring terminals or the surrounding case.
• Insulation barriers are packaged with drive models CIMR-A4A0414 through 1200 to provide added protection between terminals. Yaskawa recommends using the insulation barriers provided to ensure proper wiring.
• Use a DC reac tor or AC reactor on the input side of the drive: –To suppress harmonic current. –To improve the power factor on the power supply side. –When using an advancing capacitor switch. –With a large capacity power supply transformer (over 600 kVA).
Wiring the Main Circuit Output
Consider the following precautions for the output circuit wiring.
• Do not connect any other load than a 3 phase motor to the drives output.
• Never connect a power source to the drives output.
• Never short or ground the output terminals.
• Do not use phase correction capacitors.
• If using a contactor between the drive and motor, it should never be operated when the drive is outputting a voltage. Operating while there is voltage output can cause large peak currents, thus tripping the over current detection or damage the drive.
Ground Connection
Take the following precautions when grounding the drive.
• Never share the ground wire with other devices such as welding machines, etc.
• Always use a ground wire, that complies with electrical equipment technical standards. Keep ground wires as short as possible. Leakage current is caused by the drive. Therefore, if the distance between the ground electrode and the ground terminal is too long, potential on the ground terminal of the drive will become unstable.
• When using more than one drive, do not loop the ground wire.
Control Circuit Wiring Precautions
Consider the following precautions for wiring the control circuits.
• Separate control circuit wiring from main circuit wiring and other high-power lines.
• Separate wiring for control circuit terminals M1-M2, M3-M4, M5-M6, MA, MB, MC (contact output) from wiring to other control circuit terminals.
• For external control pow er supply use a UL Listed Class 2 power supply.
• Use twisted-pair or shielded twisted-pair cables for control circuits to prevent operating faults.
• Ground the cable shields with the maximum contact area of the shield and ground.
• Cable shields should be grounded on both cable ends.
• If flexible wires with ferrules are connected they might fit tightly into the terminals. To disconnect them, grasp the wire end with a pair of pliers, release the terminal using a straight-edge screw driver, turn the wire for about 45°, and pull it gently out of the terminal. For details, refer to the Technical Manual. Use this procedure for removing the wire link between HC, H1 and H2 when the Safe Disable function is utilized.
Page 16
3 Electrical Installation
16 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
Main Circuit Terminals
Note: Confirm the following when wiring models CIMR-A4A0930 and 4A1200:
" Remove the jumpers shorting terminals R/L1-R1/L11, S/L2-S1/L21, and T/L3-T1/L31 when operating with 12-phase
rectification. Refer to the Technical Manual for more information. " When operating without 12-phase rectification, properly wire terminals R1/L11, S1/L21, and T1/L31 in addition to terminals R1/L1, S1/L2, and T1/L3.
Control Circuit Terminals
The figure below shows the control circuit terminal arrangement. The drive is equipped with screwless terminals.
There are three DIP switches and two jumpers, S1 to S5, located on the terminal board.
Terminal Type
Function200 V Class
Model
CIMR-A
2A0004 to 2A0081 2A0110 to 2A0138 2A0169 to 2A0415
400 V Class 4A0002 to 4A0044 4A0058 to 4A0072 4A0088 to 4A0675 4A0930, 4A1200
R/L1, S/L2, T/L3
Main circuit power supply input
Main circuit power
supply input
Connects line power to the drive
R1/L11, S1/L21, T1/L31 not available
U/T1, V/T2, W/T3
Drive output Connects to the motor
B1, B2
Braking resistor not available
Available for connecting a braking resistor or a braking resistor unit option
+2
• DC reactor connection (+1, +2) (remove the shorting bar between +1 and +2)
• DC power supply input (+1, −)
not available
For connection
• of the drive to a DC power supply (terminals +1 and – are not CE or UL approved)
• of braking options
• connection of a DC reactor
+1, –
• DC power supply input (+1, −)
• DC power supply input (+1, −)
• Braking transistor connection (+3, −)
+3
not available
Grounding terminal
S1 Terminal A2 Signal Selection
S2 RS422/485 Termination Resistor
S3
Safe Disable Input Sink/Source/External Supply Selection
S4 Termin al A3 Analog/PTC Input Selection
MA MB MC
M1 M2 M5
M3 M6 M4
E(G)
HC H1 H2 DM+DM- IG R+ R- S+ S-
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
V+ AC V- A1 A2 A3 FM AM AC MP RP AC
Use a straight-edge screwdriver with a blade width of max 2.5 mm and a thickness of max 0.6 mm to
release the terminals
S2
S3
S1
S4
S5
V
I
V
I
Current Voltage
Off
On
Source Sink
External 24 Vdc
Power Supply
A
nalog Input PTC Input
PTC
AI
PTC
AI
Page 17
3 Electrical Installation
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 17
Control Circuit Terminal Functions
S5 Terminal FM/AM Signal Selection
Type No. Terminal Name (Function) Function (Signal Level) Default Setting
Multi-Function Digital Inputs
S1
Multi-function input 1 (Closed: Forward run, Open: Stop)
Photocoupler 24 Vdc, 8 mA Use the wire link between terminals SC and SN or SC and SP to select between sinking, sourcing mode, and the power supply.
S2
Multi-function input 2 (Closed: Reverse run, Open: Stop)
S3
Multi-function input 3 (External fault, N.O.)
S4
Multi-function input 4 (Fault reset)
S5
Multi-function input 5 (Multi-step speed reference 1)
S6
Multi-function input 6 (Multi-step speed reference 2)
S7
Multi-function input 7 (Jog reference)
S8
Multi-function input 8 (External baseblock)
SC
Multi-function input common
SN Multi-function input 0 V 24 Vdc power supply for digital inputs, 150 mA max (if no digital
input option DI-A3 is used) Never short terminals SP and SN as doing so will damage the drive.
SP Multi-function input 24 Vdc
Safe Disable Inputs
H1
Safe Disable input 1
24 Vdc, 8 mA One or both open: Drive output disabled Both closed: Normal operation Internal impedance: 3.3 kΩ Off time of at least 1 ms Disconnect the wire jumpers shorting terminals H1, H2, and HC to use the Safe Disable inputs. Set the S3 jumper to select between sinking, sourcing mode, and the power supply.
H2
Safe Disable input 2
HC
Safe Disable function common Safe disable function common
Analog Inputs / Pulse Train
Input
RP
Multi-function pulse train input (Frequency reference)
Input frequency range: 0 to 32 kHz Signal Duty Cycle: 30 to 70% High level: 3.5 to 13.2 Vdc, low level: 0.0 to 0.8 Vdc Input impedance: 3 kΩ
+V
Power supply for analog inputs 10.5 Vdc (max allowable cur rent 20 mA)
-V
Power supply for analog inputs -10.5 Vdc (max allowable current 20 mA)
A1
Multi-function analog input 1 (Frequency reference bias)
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
A2
Multi-function analog input 2 (Frequency reference bias)
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ) 4 to 20 mA, 0 to 20 mA (input impedance: 250
Ω)
Voltage or current input must be selected by DIP switch S1 and H3-09
A3
Multi-function analog input 3 / PTC Input (Auxiliary frequency reference)
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ) Use switch S4 on the control terminal board to select between analog input or PTC input. If PTC is selected, set H3-06 = E.
AC
Frequency reference common 0 V
E (G)
Ground for shielded lines and option cards
Fault Relay
MA
N.O.
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A Minimum load: 5 Vdc, 10 mA
MB
N.C. output
MC
Fault output common
AM
FM
V
I
V
I
AM
FM
FM/AM: Voltage Output FM: Current Output
AM: Voltage Output
...
Page 18
3 Electrical Installation
18 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
NOTICE: The terminals HC, H1, H2 are used for the Safe Disable function. Do not remove the wire link between HC, H1, or H2 unless the Safe Disable function is used. Refer to Safe Disable Input Function on page 35 when using this function.
NOTICE: The wiring length to the terminals HC, H1 and H2 should not exceed 30 m.
Multi-Function Digital Output
M1
Multi-function digital output (During run)
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A Minimum load: 5 Vdc, 10 mA
M2 M3
Multi-function digital output (Zero speed)
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A Minimum load: 5 Vdc, 10 mA
M4 M5
Multi-function digital output (Speed agree 1)
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A Minimum load: 5 Vdc, 10 mA
M6
Monitor Output
MP
Pulse train output (Output frequency) 32 kHz (max)
FM
Analog monitor output 1 (Output frequency)
-10 to +10 Vdc, 0 to +10 Vdc, or 4 to 20 mA Use jumper S5 on the control terminal board to select between voltage or current output at terminals AM and FM. Set parameters H4-07 and H4-08 accordingly when changing the jumper setting.
AM
Analog monitor output 2 (Output current)
AC
Monitor common 0 V
Safety Monitor Output
DM+
Safety monitor output
Outputs status of Safe Disable function. Closed when both Safe Disable channels are closed. Up to +48 Vdc 50 mA
DM-
Safety monitor output common
Type No. Terminal Name (Function) Function (Signal Level) Default Setting
Page 19
4 Keypad Operation
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 19
4 Keypad Operation
Digital Operator and Keys
The digital operator is used to program the drive, to start/stop it, and to display fault information. The LEDs indicate the drive status.
Keys and Functions
Key Name Function
Function Key (F1, F2)
The functions assigned to F1 and F2 vary depending on the menu that is currently displayed. The name of each function appears in the lower half of the display window.
ESC Key
• Returns to the previous display.
• Moves the cursor one space to the left.
• Pressing and holding this button will return to the Frequency Reference display.
RESET Key
• Moves the cursor to the right.
• Resets the drive to clear a fault situation.
RUN Key
Starts the drive in the LOCAL mode. The Run LED
• is on, when the drive is operating the motor.
• flashes during deceleration to stop or when the frequency reference is 0.
• flashes quickly the drive is disabled by a DI, the drive was stopped using a fast stop DI or a run command was active during power up.
Up Arrow Key Scrolls up to display the next item, sel ects parameter numbers and increments setting values.
Down Arrow Key
Scrolls down to display the previous item, selects parameter numbers and decrements setting values.
STOP Key Stops drive operation.
ENTER Key
• Enters parameter values and settings.
• Selects a menu item to move between displays.
LO/RE Selection Key
Switches drive control between the operator (LOCAL) and the control circuit terminals (REMOTE). The LED is on when the drive is in the LOCAL mode (operation from keypad).
ALM LED Light
On: When the drive detects a fault. Flashing:
• When an alarm occurs.
• When oPE is detected.
• When a fault or error occurs during Auto-Tuning.
LO RE
F2F1
ESC
RUN STOP
ENTERRESET
ALM
DIGITAL OPERATOR JVOP-180
F1
F2
ESC
RESET
RUN
STOP
ENTER
LO RE
ALM
Page 20
4 Keypad Operation
20 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
Menu Structure and Modes
The following illustration explains the operator keypad menu structure.
Figure 1.1
<1> Pressing will start the motor. <2> Drive cannot operate the motor. <3> Flashing characters are shown as . <4> X characters are shown in this manual. The LCD Operator will display the actual setting values. <5> The Frequency Reference appears after the initial display which shows the product name. <6> The information that appears on the display will vary depending on the drive.
- MODE -
U1-01= 0.00Hz
U1-02= 0.00Hz U1-03= 0.00A
DRV
FREF (OPR)
Rdy
-MONITR-
FREF (d1-01)
U1-01= 000.00Hz
<3>
<4>
0.0050.00
0.00Hz
DRV
←→
FWD
Rdy
- MODE -
U1-01= 0.00Hz
U1-02= 0.00Hz U1-03= 0.00A
DRV
Monitor Menu
Rdy
- MODE - PRG
Modified Consts
HELP
HELP
DATA
- MODE - PRG
Quick Setting
DATA
HELP
- MODE - PRG Rdy
Auto-Tuning
DATA
HELP
- MODE - PRG
DATA
Programming
AUTO
-MONITR-
U1 -01= 0.00Hz
U1-02= 0.00Hz U1-03= 0.00A
DRV
Monitor
JOG FWD FWD/REV
Rdy
-MONITR-
U1- 01 = 0.00Hz
U1-02= 0.00Hz U1-03= 0.00A
DRV
Frequency Ref
JOG FWD FWD/REV
Rdy
-MONITR-
U1- 02 = 0.00Hz
U1-03= 0.00A U1-04= 0
DRV
Output Freq
JOG FWD FWD/REV
Rdy
-MONITR-
U2 -01= oC
U2-02= oPr U2-03= 0.00Hz
DRV
Fault Trace
JOG FWD FWD/REV
Rdy
JOG FWD FWD/REV
JOG FWD
FWD
FWD
FWD
FWD
FWD/REV
Modified
X Parameters
LSEQ LREF
LSEQ LREF
LSEQ LREF
LSEQ LREF
LSEQ LREF
LSEQ LREF
YAS K A WA
A1000
A1000
XXXVX.X/X.XkW
XX.XX/XX.XXA
<XXXXXXXXX>
Initial Display <5>
<6>
Programming Mode <2> Drive Mode <1>
RUN
0
Page 21
5 Start Up
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 21
5Start Up
Drive Setup Procedure
The illustration below shows the basic setup procedure. Each step is explained more detailed on the following pages.
Power On
Before turning on the power supply,
• Make sure all wires are connected properly.
• Make sure no screws, loose wire ends or tools are left in the drive.
• After turning the power on, the drive mode display should appear and no fault or alarm should be displayed.
Control Mode Selection (A1-02)
There are three control modes available. Select the control mode that best suits the application the drive will control.
Control Mode Parameter Main Applications
V/f Control for Induction Motors
A1-02 = 0
(default)
• General variable speed applications, particularly useful for running multiple motors from a single drive.
• When replacing a drive in which parameter settings are unknown.
V/f Control with PG Speed Feedback
A1-02 = 1
• For general-purpose applications that do not require high dynamic response but high speed accuracy.
• This mode should be used if the motor parameters are unknown and Auto-Tuning cannot be performed.
Open Loop V ector Contr ol A1-02 = 2
• General variable speed applications
• Applications requiring high precision, high speed control
Closed Loop Vector Control
<1>
A1-02 = 3
• For general, variable-speed applications that requiring precise speed control down to zero speed, fast torque response, or precise torque control.
• A speed feedback signal from the motor is required.
Install and wire the drive as explained.
Turn the power on.
Set the control mode.
Set/check the basic parameters: * b1-01, b1-02 for frequency reference and RUN command source * H1-, H2-, H3-, H4-, H6- to configure the I/Os * Frequency reference values * C1-, C2- for Acceleration/Deceleration times and S-curves
Run the motor without load, check the operation and verify, if the
upper controller (e.g. PLC,...) commands to the drive work as
desired.
Connect the load, run the motor and check the operation
Fine tune and set application parameters (e.g. PID,...) if necessary.
Final check the operation and verify the settings.
Drive is ready to run the application
START
Perform Auto-Tuning or set the motor data manually.
Initialize the drive if necessary using parameter A1-01.
Select Normal / Heavy Duty
Page 22
5 Start Up
22 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
Normal / Heavy Duty Selection (C6-01)
The drive supports two ratings, Normal Duty and Heavy Duty. Both have different output current ratings (refer to the catalog or the Technical Manual). Set the Duty mode in accordance with the application.
Auto-Tuning (T1-)
Auto-Tuning automatically sets up the motor data relevant drive parameters. Three different modes are supported.
Open Loop Vector Control for PM <1>
A1-02 = 5
Derated torque-load applications employing permanent magnet motors (SPM, IPM) and energy savings.
Advanced Open Loop Vector Control for PM <1>
A1-02 = 6 This control mode can be used to operate an IPM motor for constant torque applications.
Closed Loop Vector Control for PM
<1>
A1-02 = 7
• This mode can be used for high precision control of a PM motor in constant torque or variable torque applications.
• A speed feedback signal is required.
<1> For explanations of these control modes, refer to the Technical Manual.
Mode Heavy Duty Rating (HD) Normal Duty Rating (ND)
C6-01 01
Application
Applications with a constant torque like extruders, conveyors and cranes. High overload capability might be needed.
Applications where the torque increases with the speed like fans or pumps. High overload tolerance is normally not needed.
Overload capability (OL2) 150% of drive rated current for 60 s 120% of drive rated current for 60 s L3-02 Stall Prevention during
Acceleration
150% 120%
L3-06 Stall Prevention during Run
150% 120%
Default carrier frequency 2 kHz 2 kHz Swing PWM
Type Setting Application Conditions and Benefits
Control Mode (A1-02)
V/f (0)
V/f w/PG
(1)
OLV (2) CLV (3)
Rotational Auto-
Tuning
T1-01 = 0
• Motor can be decoupled from the load and rotate freely while Auto-Tuning is performed.
• Motor and load can not be decoupled but the motor load is below 30%.
• Rotational Auto-Tuning gives the most accurate results, and is therefore highly recommended if possible.
N/A N/A YES YES
Stationary Auto-
Tuning 1
T1-01 = 1
• Motor and load can not be decoupled and the load is higher than 30%.
• A motor test report listing motor data is not available.
• Automatically calculates motor parameters needed for vector control.
N/A N/A YES YES
Stationary Auto-
Tuning 2
T1-01 = 4
• Motor and load can not be decoupled and the load is higher than 30%.
• A motor test report is available. Once the no- load current and the rated slip have been entered, the drive calculates and sets all other motor-related parameters.
N/A N/A YES YES
Stationary Auto-
Tuning for Line-to-
Line Resistance
T1-01 = 2
• The drive is used in V/f Control and other Auto-Tuning selections not possible.
• Drive and motor capacities differ.
• Tunes the drive after the cable between the drive and motor has been replaced with a cable over 50 m long. Assumes Auto-Tuning has already been performed.
• Should not be used for any vector control modes unless the motor cable has changed.
YES YES YES YES
Control Mode Parameter Main Applications
Page 23
5 Start Up
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 23
For Auto-Tuning enter the Auto-Tuning menu and perform the steps shown in the figure below. The number of name plate data to be entered depends on the selected typ e of Auto-Tuning. This example shows Rotational Auto-Tuning.
If Auto-Tuning can not be performed for some reason (no-load operation impossible etc.), then set up the maximum frequency and voltage in the E1- parameters and enter the motor data manually into the E2- parameters.
NOTICE: The Safe Disable inputs must be closed during Auto-Tuning.
External Reference Selection and Acceleration/ Deceleration Times
Frequency Reference Selection (b1-01)
Set parameter b1-01 according to the frequency reference used.
Rotational Auto-
Tuning for V/f
Control
T1-01 = 3
• Recommended for applications using Speed Estimation Speed Search or using the Energy Saving function in V/f Control.
• Assumes motor can rotate while Auto-Tuning is executed. Increases accuracy for certain functions like torque compensation, slip compensation, Energy Saving, and Speed Search.
YES YES N/A N/A
CAUTION
Do not touch the motor until the Auto-Tuning is finished. Failure to comply may result in minor or moderate injury. Voltage is still applied to the motor during the tuning
process, even thought the motor may not be rotating.
b1-01 Reference source Frequency reference input
0 Operator keypad
Set the frequency references in the d1- parameters and use digital inputs to switch over between different reference values.
1 Analog input Apply the frequency reference signal to terminal A1, A2, or A3. 2 Serial Comm. Serial Communications using the RS422/485 port 3 Option Card Communications option card 4 Pulse input Set the frequency reference at terminal RP using a pulse train signal.
Type Setting Application Conditions and Benefits
Control Mode (A1-02)
V/f (0)
V/f w/PG
(1)
OLV (2) CLV (3)
- MODE -
End
Tune Successful
DRV
FWD RESET
Enter the Auto-
Tuning Mode
Select the tuning
method
Set up all name
plate data
The tuning start
display appears
During the tuning the
display flashes
After successful tuning
“End” is displayed
Drive mode
display
- A.TUNE -
T1-01= 0
0
Standard Tuning
PRG
Entry Accepted
Tuning Mode Sel
FWD
- A.TUNE -
T1-01= 0
0
Standard Tuning
PRG
Tuning Mode Sel
ESC FWD DATA
- MODE -
U1-01= 0.00Hz
U1-02= 0.00Hz U1-03= 0.00A
DRV
FREF (OPR)
Rdy
JOG FWD FWD/REV
LSEQ LREF
HELP
- MODE - PRG
Auto-Tuning
DATA
AUTO
FWD
“0”
- A.TUNE -
T1-07= 1450RPM
(0 ~ 24000)
PRG
Rated Speed
ESC FWD DATA
“1750RPM”
- A.TUNE -
T1-02= X.XXkW
(0.00 ~ 650.00)
PRG
Mtr Rated Power
ESC FWD DATA
“X.XXkW”
- A.TUNE -
0.00 Hz/ 0.00A Tuning Ready ?
DRV
Auto-Tuning
ESC FWD
Press RUN key
- A.TUNE -
X.XX Hz/ X.XXA
DRV
Tune Proceeding
FWD

RUN
Page 24
5 Start Up
24 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
Run Command Selection (b1-02)
Set parameter b1-02 according to the run command used.
Acceleration/ Deceleration Times and S-Curves
There are four sets of acceleration and deceleration times which can be set in the C1- parameters. The default activated accel/decel times are C1-01/02. Adjust these times to the appropriate values required by the application. If necessary S-curves can be activated in the C2- parameters for softer accel/decel start and end.
Reference and Run Source
The drive has a LOCAL and a REMOTE mode.
If the drive is operated in the REMOTE mode, make sure that the correct sources for the frequency reference and run command are set in parameters b1-01/02 and that the drive is in the REMOTE mode.
The LED in the LO/RE key indicates where the Run command is input from.
I/O Setup
Note: The default setting functions can be seen in the connection diagram on page 12.
Multi-Function Digital Inputs (H1-)
The function of each digital input can be assigned in the H1- parameters.
Multi-Function Digital Outputs (H2-)
The function of each digital output can be assigned in the H2- parameters. The setting value of these parameters consist of 3 digits, where the middle and right digit set the function and the left digit sets the output characteristics (0: Output as selected; 1: Inverse output).
Multi-Function Analog Inputs (H3-)
The function of each analog input can be assigned in the H3- parameters. Input A1 and A3 are set for -10 to +10 Vdc input. A2 is set for 4-20 mA input.
NOTICE: If the input signal level of input A2 is switched between voltage and current, make sure that DIP switch S1 is in the correct position and parameter H3-09 is set up correctly.
NOTICE: When using analog input A3 as PTC input, set DIP switch S4 to PTC and parameter H3-06 = E.
Multi-Function Analog Outputs (H4-)
Use the H4- parameters to set up the output value of the analog monitor outputs and to adjust the output signal levels. When changing signal levels in parameter H4-07/08, make sure jumper S5 is set accordingly.
b1-02 Reference source Run command input
0 Operator keypad RUN and STOP keys on the operator 1 Multi-Function digital input Multi-Function digital input 2 Serial Comm. Serial Communications using the RS422/485 port 3 Option Card Communications option card
Status Description
LOCAL The Run/ Stop command and the frequency reference are entered at the operator keypad.
REMOTE
The Run command source entered in parameter b1-02 and the frequency reference source entered in parameter b1-01 are used.
LO/RE LED Description
ON Run command is issued from operator.
OFF Run command is issued from a different source than the operator.
Page 25
5 Start Up
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 25
Test Run
Perform the following steps to start up the machine after all parameter settings have been done.
1.
Run the motor without load and check if all input, outputs and the sequence work as desired.
2. Connect the load to the motor.
3. Run the motor with load and make sure that there is no vibrations, hunting or motor stalling occurs.
After taking the steps listed above, the drive should be ready to run the application and perform the basic functions. For special setups like PID control etc. refer to the Technical Manual.
Page 26
26 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
6 Parameter Table
6 Parameter Table
This parameter table shows the most important parameters. Default settings are bold type. Refer to the Technical Manual for a complete list of parameters.
No. Name Description
Initialization Parameters
A1-01
Access Level Selection
0: View and set A1-01 and A1-04. U- parameters can also be viewed. 1: User Parameters (access to a set of parameters selected by the user, A2-01 to A2-32)
2: Advanced Access (access to view and set all parameters)
A1-02
Control Method Selection
0: V/f Control
1: V/f Control with PG 2: Open Loop Vector Control 3: Closed Loop Vector Control 5: Open Loop Vector Control for PM 6: Advanced Open Loop Vector Control for PM 7: Closed Loop Vector Control for PM
A1-03
Initialize Parameters
0: No initialization
1110: User Initialize (parameter values must be stored using parameter o2-03) 2220: 2-wire initialization 3330: 3-wire initialization 5550: oPE04 error reset
Operation Mode Selection
b1-01
Frequency Reference Selection 1
0: Digital operator
1: Analog input terminals
2: MEMOBUS/Modbus communications 3: Option PCB 4: Pulse input (terminal RP)
b1-02
Run Command Selection 1
0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications 3: Option PCB
b1-03
Stopping Method Selection
0: Ramp to stop
1: Coast to stop 2: DC Injection Braking to stop 3: Coast with timer 9: Simple Positioning Stop
b1-04
Reverse Operation Selection
0: Reverse enabled.
1: Reverse disabled.
b1-14
Phase Order Selection
0: Standard
1: Switch phase order (reverses the direction of the motor)
DC Injection Braking
b2-01
DC Injection Braking Start Frequency
Sets the frequency at which DC Injection Braking starts when “Ramp to stop” (b1-03 = 0) is selected.
b2-02
DC Injection Braking Current
Sets the DC Injection Braking current as a percentage of the drive rated current.
b2-03
DC Injection Braking Time at Start
Sets DC Injection Braking (Zero Speed Control when in CLV/PM) time at start. Disabled when set to 0.00 seconds.
b2-04
DC Injection Braking Time at Stop
Sets DC Injection Braking time at stop.
Acceleration/ Deceleration
C1-01
Acceleration Time 1
Sets the time to accelerate from 0 to maximum frequency.
C1-02
Deceleration Time 1
Sets the time to decelerate from maximum frequency to 0.
C1-03 to
C1-08
Acceleration/ Deceleration Time 2 to 4
Set the accel/decel times 2 to 4 (set like C1­01/02).
C2-01
S-Curve Characteristic at Accel Start
S-curve at acceleration start.
C2-02
S-Curve Characteristic at Accel End
S-curve at acceleration end.
C2-03
S-Curve Characteristic at Decel Start
S-curve at deceleration start.
C2-04
S-Curve Characteristic at Decel End
S-curve at deceleration end.
Slip Compensation
C3-01
Slip Compensation Gain
Sets the gain for the motor slip compensation function used for motor 1.
C3-02
Slip Compensation Primary Delay Time
Adjusts the slip compensation function delay time used for motor 1.
Torque Compensation
C4-01
Torque Compensation Gain
Sets the gain for the automatic torque (voltage) boost function and helps to produce better starting torque. Used for motor 1.
C4-02
Torque Compensation Primary Delay Time
Sets the torque compensation filter time.
Carrier Frequency
C6-01
Drive Duty Selection
0: Heavy Duty (HD) for constant torque applications.
1: Normal Duty (ND) for variable torque applications.
C6-02
Carrier Frequency Selection
1: 2.0 kHz
2: 5.0 kHz 3: 8.0 kHz 4: 10.0 kHz 5: 12.5 kHz 6: 15.0 kHz 7: Swing PWM1 (Audible sound 1) 8: Swing PWM2 (Audible sound 2) 9: Swing PWM3 (Audible sound 3) A: Swing PWM4 (Audible sound 4) B to E: No setting possible F: User defined (determined by C6-03 through C6-05)
Frequency Reference
d1-01 to
d1-16
Frequency Reference 1 to 16
Sets the frequency reference for the drive. Setting units are determined by parameter o1-03.
No. Name Description
Page 27
6 Parameter Table
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 27
d1-17
Jog Frequency Reference
Sets the Jog frequency reference. Setting units are determined by parameter o1-03.
V/f Pattern for Motor 1
E1-01
Input Voltage Setting
This parameter must be set to the power supply voltage. WARNING! Drive input voltage (not motor voltage) must be set in E1-01 for the protective features of the drive to function properly. Fa ilure to do so may result in equipment damage and/or death or personal injury.
E1-04
Maximum Output Frequency
These parameters are only applicable when E1-03 is set to F. To set li nea r V/f chara cteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. Ensure that the four frequencies are set according to these rules: E1-09 E1-07 < E1-06 ≤ Ε1−11 ≤ E1-04
Note: Some parameters may not be available depending on the control mode.
• E1-07, E1-08 and E-10 are available only in the following control modes: V/f Control, V/f with PG, Open Loop Vector.
• E1-11, E1-12 and E-13 are available only in the following control modes: V/f Control, V/f with PG, Open Loop Vector, Closed Loop Vector.
E1-05
Maximum Volt ag e
E1-06
Base Frequency
E1-07
Middle Output Frequency
E1-08
Middle Output Frequency Volt ag e
E1-09
Minimum Output Frequency
E1-10
Minimum Output Frequency Volt ag e
E1-13 Base Voltage
Motor 1 Parameters
E2-01
Motor Rated Current
Sets the motor nameplate full load current in Amps. Automatically set during Auto-Tuning.
E2-02
Motor Rated Slip
Sets the motor rated slip. Automatically set during Auto-Tuning.
E2-03
Motor No-Load Current
Sets the no-load current for the motor. Automatically set during Auto-Tuning.
E2-04
Number of Motor Poles
Sets the number of motor poles. Automatically set during Auto-Tuning.
E2-05
Motor Line-to-Line Resistance
Sets the phase-to-phase motor resistance. Automatically set during Auto-Tuning.
E2-06
Motor Leakage Inductance
Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage. Automatically set during Auto-Tuning.
Multi-Function Digital Inputs
H1-01 to
H1-08
Multi-Function Digital Input Terminal S1 to S8 Function Selection
Selects the function of terminals S1 to S8.
Note: Major functions are listed at the end of the table.
No. Name Description
Output Voltage (V)
Frequency (Hz)
E1-05 E1-12
E1-13
E1-08
E1-10
E1-09 E1-07 E1-06 E1-11 E1-04
Multi-Function Digital Outputs
H2-01
Terminal M1­M2 function selection
Set the function for the relay output M1­M2.
H2-02
Terminal M3­M4 function selection
Sets the function for the relay output M3­M4.
H2-03
Terminal M5­M6 function selection
Sets the function for the relay output M5­M6.
H2-06
Watt Hour Output Unit Selection
Outputs a 200 ms pulse signal when the watt-hour counter increases by the units selected.
0: 0.1 kWh units
1: 1 kWh units 2: 10 kWh units 3: 100 kWh units 4: 1000 kWh units
Note: Major functions are listed at the end of the table.
Multi-Function Analog Inputs
H3-01
Terminal A1 Signal Level Selection
0: 0 to 10 V
1: –10 to 10 V
H3-02
Terminal A1 Function Selection
Sets the function of terminal A1.
H3-03
Terminal A1 Gain Setting
Sets the level of the input value selected in H3-02 when 10 V is input at terminal A1.
H3-04
Terminal A1 Bias Setting
Sets the level of the input value selected in H3-02 when 0 V is input at terminal A1.
H3-05
Terminal A3 Signal Level Selection
0: 0 to 10 V 1: –10 to 10 V
H3-06
Terminal A3 Function Selection
Sets the function of terminal A3.
H3-07
Terminal A3 Gain Setting
Sets the level of the input value selected in H3-06 when 10 V is input at terminal A3.
H3-08
Terminal A3 Bias Setting
Sets the level of the input value selected in H3-06 when 0 V is input at terminal A3.
H3-09
Terminal A2 Signal Level Selection
0: 0 to 10 V 1: –10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA Note: Use DIP switch S1 to set input terminal A2 for a current or a voltage input signal.
H3-10
Terminal A2 Function Selection
Sets the function of terminal A2.
H3-11
Terminal A2 Gain Setting
Sets the level of the input value selected in H3-10 when 10 V (20 mA) is input at terminal A2.
H3-12
Terminal A2 Bias Setting
Sets the level of the input value selected in H3-10 when 0 V (0 or 4 mA) is input at terminal A2.
H3-13
Analog Input Filter Time Constant
Sets a primary delay filter time constant for terminals A1, A2, and A3. Used for noise filtering.
No. Name Description
Page 28
6 Parameter Table
28 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
H3-14
Analog Input Terminal Enable Selection
Determines which of the analog input terminals will be enabled when a digital input programmed for “Analog input enable” (H1- = C) is activated. 1: Terminal A1 only 2: Terminal A2 only 3: Terminals A1 and A2 only 4: Terminal A3 only 5: Terminals A1 and A3 6: Terminals A2 and A3
7: All terminals enabled
Multi-Function Analog Inputs
H4-01
Multi-Function Analog Output Terminal FM Monitor Selection
Selects the data to be output through multi­function analog output terminal FM. Set the desired monitor parameter to the digits available in U-. For example, enter “103” for U1-03.
H4-02
Multi-Function Analog Output Terminal FM Gain
Sets the signal level at terminal FM that is equal to 100% of the selected monitor value.
H4-03
Multi-Function Analog Output Terminal FM Bias
Sets the signal level at terminal FM that is equal to 0% of the selected monitor value.
H4-04
Multi-Function Analog Output Terminal AM Monitor Selection
Selects the data to be output through multi­function analog output terminal AM. Set the desired monitor parameter to the digits available in U-. For example, enter “103” for U1-03.
H4-05
Multi-Function Analog Output Terminal AM Gain
Sets the signal level at terminal AM that is equal to 0% of the selected monitor value.
H4-06
Multi-Function Analog Output Terminal AM Bias
Sets the bias value added to the terminal AM output signal.
H4-07
Multi-Function Analog Output Terminal FM Signal Level Selection
0: 0 to 10 V
1: -10 to 10 V 2: 4 to 20 mA
H4-08
Multi-Function Analog Output Terminal AM Signal Level Selection
0: 0 to 10 V
1: -10 to 10 V 2: 4 to 20 mA
Pulse Input Setting (Freq.)
H6-02
Pulse Train Input Scaling
Sets the terminal RP input signal frequency that is equal to 100% of the value selected in H6-01.
H6-03
Pulse Train Input Gain
Sets the level of the value selected in H6-01 when a frequency with the value set in H6­02 is input.
H6-04
Pulse Train Input Bias
Sets the level of the value selected in H6-01 when 0 Hz is input.
Pulse Output Setting
H6-06
Pulse Train Monitor Selection
Select the pulse train monitor output function (value of the - part of U-). Example: To select U5-01, set 501.
No. Name Description
H6-07
Pulse Train Monitor Scaling
Sets the terminal MP output signal frequency when the monitor value is 100%. To have the pulse trai n monitor output equal the output frequency, set H6-06 to 102 and H6-07 to 0.
Motor Protection
L1-01
Motor Overload Protection Selection
0: Disabled
1: General purpose motor (standard fan cooled)
2: Drive dedicated motor with a speed range of 1:10 3: Vector motor with a speed range of 1:100 4: PM motor with variable torque 5: PM motor with constant torque control 6: General purpose motor (50 Hz) The drive may not be able to provide protection when multiple motors are used, even if overload is enabled in L1-01. Set L1-01 to 0 and install separate thermal relay to each motor.
L1-02
Motor Overload Protection Time
Sets the motor thermal overload protection (oL1) time.
Stall Prevention
L3-01
Stall Prevention Selection during Acceleration
0: Disabled.
1: General purpose. Acceleration is paused as long as the current i s above the L3-02 setting.
2: Intelligent. Accelerate in the shortest possible time without exceeding the L3-02 level. Note: Setting 2 is not available when using OLV/PM.
L3-02
Stall Prevention Level during Acceleration
Used when L3-01 = 1 or 2. 100% is equal to the drive rated current.
L3-04
Stall Prevention Selection during Deceleration
0: Disabled. Deceleration at the active deceleration rate. An ov fault may occur.
1: General purpose. Deceleration is paused when the DC bus voltage exceeds the Stall Prevention level.
2: Intelligent. Decelerate as fast as possible while avoiding ov faults. 3: Stall Prevention with braking resistor. Stall Prevention during deceleration is enabled in coordination with dynamic braking. 4: Overexcitation Deceleration. Decelerates while increasing the motor flux. 5: Overexcitation Deceleration 2. Adjust the deceleration rate according to the DC bus voltage. 6: Enabled. Decelerates adjusting the deceleration rate according to the output current and the DC bus voltage.
No. Name Description
Page 29
6 Parameter Table
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 29
L3-05
Stall Prevention Selection during Run
0: Disabled. Drive runs at a set frequency. A heavy load may cause speed loss.
1: Decel time 1. Uses the deceleration time set to C1-02 while Stall Pr evention is performed.
2: Decel time 2. Uses the deceleration time set to C1-04 while Stall Prevention is performed.
L3-06
Stall Prevention Level during Run
Enabled when L3-05 is set to 1 or 2. 100% is equal to the drive rated current.
Induction Motor Auto-Tuning
T1-01
Auto-Tuning Mode Selection
0: Rotational Auto-Tuning 1: Stationary Auto-Tuning 1 2: Stationary Auto-Tuning for Line-to-Line Resistance 3: Rotational Auto-Tuning for V/f Control (necessary for Energy Savings and Speed Estimation Speed Search) 4: Stationary Auto-Tuning 2 8: Inertia Tuning (perform Rotational Auto­Tuning prior to Inertia Tuning) 9: ASR Gain Tuning (perform Rotational Auto-Tuning prior to ASR Gain Auto­Tuning)
T1-02
Motor Rated Power
Sets the motor rated power as specified on the motor nameplate.
T1-03
Motor Rated Volt ag e
Sets the motor rated voltage as specified on the motor nameplate.
T1-04
Motor Rated Current
Sets the motor rated current as specified on the motor nameplate.
T1-05
Motor Base Frequency
Sets the rated frequency of the motor as specified on the motor nameplate.
T1-06
Number of Motor Poles
Sets the number of motor poles as specified on the motor nameplate.
T1-07
Motor Base Speed
Sets the rated speed of the motor as specified on the motor nameplate.
T1-08
PG Number of Pulses Per Revolution
Set the number of pulses per revolution for the PG being used (pulse generator or encoder).
T1-09
Motor No­Load Current (Stationary Auto-Tuning)
Sets the no-load current for the motor. After setting the motor capacity to T1-02 and the motor rated current to T1-04, this parameter will automatically display the no­load current for a standard 4 pole Yaskawa motor. Enter the no-load curre nt as indicated on the motor test report.
T1-10
Motor Rated Slip (Stationary Auto-Tuning)
Sets the motor rated slip. After setting the motor capacity to T1-02, this parameter will automatically displa y the motor slip for a standard 4 pole Yaskawa motor. Enter the motor slip as indicated on the motor test report.
T1-11
Motor Iron Loss
Sets the iron loss for determining the Energy Saving coefficient. The value is set to E2-10 (motor iron loss) set when the power is cycled. If T1-02 is changed, a default value appropriate for the motor capacity that was entered will appear.
No. Name Description
Monitor Description
U1-01 Frequency Reference (Hz) U1-02 Output Frequency (Hz) U1-03 Output Current (A) U1-05 Motor Speed (Hz) U1-06 Output Voltage Reference (Vac) U1-07 DC Bus Voltage (Vdc) U1-08 Output Power (kW) U1-09 Torque Reference (% of motor rated torque)
U1-10
Displays the input terminal status.
U1-11
Displays the output terminal status.
U1-12
Verifies the drive operation status.
U1-13 Terminal A1 Input Level U1-14 Terminal A2 Input Level U1-15 Terminal A3 Input Level U1-16 Output Frequency after Soft Starter U1-18 oPE Fault Parameter U1-24 Input Pulse Monitor
Fault Trace
U2-01 Current Fault U2-02 Previous Fault U2-03 Frequency Reference at Previous Fault U2-04 Output Frequency at Previous Fault
U1 - 10=
00000000
Digital input 1 (terminal S1 enabled)
Digital input 2 (terminal S2 enabled)
Digital input 3 (terminal S3 enabled)
Digital input 4 (terminal S4 enabled)
Digital input 5 (terminal S5 enabled)
Digital input 6 (terminal S6 enabled)
Digital input 7 (terminal S7 enabled)
Digital input 8 (terminal S8 enabled)
1
1
1
1
1
1
1
1
U1 - 11=
00000000
Multi-Function Digital Output (terminal M1-M2)
Digital Output (terminal M3-M4)
Digital Output (terminal M5-M6)
Multi-Function
Multi-Function
Not Used
Fault Relay (terminal MA-MC closed
MA-MC open)
1
1
1
1
U1 - 12=
00000000
During run
During zero-speed
During REV
During fault reset signal input
During speed agree
Drive ready
During alarm detection
During fault detection
1 1
1 1
1 1
1
1
Page 30
6 Parameter Table
30 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
U2-05 Output Current at Previous Fault U2-06 Motor Speed at Previous Fault U2-07 Output Voltage at Previous Fault U2-08 DC Bus Voltage at Previous Fault U2-09 Output Power at Previous Fault U2-10 Torque Reference at Previous Fault U2-11 Input Terminal Status at Previous Fault U2-12 Output Terminal Status at Previous Fault U2-13 Drive Operation Status at Previous Fault U2-14 Cumulative Operation Time at Previous Fault U2-15 Soft Starter Speed Reference at Previous Fault U2-16 Motor q-Axis Current at Previous Fault U2-17 Motor d-Axis Current at Previous Fault U2-20 Heatsink Temperature at Previous Fault
Fault History
U3-01 to
U3-04
First to 4th Most Recent Fault
U3-05 to
U3-10
5th to 10th Most Recent Fault
U3-11 to
U3-14
Cumulative Operation Time at 1st to 4th Most Recent Fault
U3-15 to
U3-20
Cumulative Operation Time at 5th to 10th Most Recent Fault
NOTE: The following faults are not recorded in the error log. CPF00 to 03, Uv1, and Uv2
DI/DO Sel. Description
Digital Input Function Selections
3 Multi-step speed reference 1 4 Multi-step speed reference 2 5 Multi-step speed reference 3
6
Jog reference selection (higher priority than multi-step
speed reference) 7 Accel/decel time selection 1 F Through mode (Set when a terminal is not used)
14 Fault reset (Reset when turned ON)
20 to 2F
External fault; Input mode: N.O. contact / N.C. contact,
Detection mode: Normal/during operation
Digital Output Function Selections
0
During Run (ON: run command is ON or voltage is being
output) 1 Zero Speed 2 Speed Agree 1 6 Drive Ready EFault F Through mode
10 Minor fault (Alarm) (ON: Alarm displayed)
Monitor Description
Page 31
7 Troubleshooting
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 31
7 Troubleshooting
General Fault and Alarms
Faults and alarms indicate problems in the drive or in the machine. An alarm is indicated by a code on the data display and the flashing ALM LED. The drive output is not necessarily
switched off. A fault is indicated by a code on the data display and the ALM LED is on. The drive output is always switched off
immediately and the motor coast to stop. To remove an alarm or reset a fault, trace the cause, remove it and reset the drive by pushing the Reset key on the
operator or cycling the power supply. This lists up the most important alarms and faults only. Please refer to the Technical Manual for a complete list.
Digital Operator AL FLT Cause Corrective Action
Base Block
The software base block function is assigned to one of the digital inputs and the input is off. The drive does not accept Run commands.
• Check the digital inputs function selection.
• Check the upper controller sequence.
Control Fault
The torque limit was reached during deceleration for longer than 3 s. when in Open Loop Vector control
• The load inertia is too big.
• The torque limit is too low.
• The motor parameters are wrong.
• Check the load.
• Set the torque limit to the most appropriate setting (L7-01 through L7-04).
• Check the motor parameters.
Control Circuit
Fault
There is a problem in the drive’s control circuit.
• Cycle the drive power supply.
• Initialize the drive.
• Replace the drive if the fault occurs again .
Control Circuit
Fault
There is no terminal board connected to the control board.
• Check if the terminal board is installed properly.
• Uninstall and Reapply the terminal board.
• Change the drive.
Cannot Reset
Fault reset was input when a Run command was active. Turn off the Run command and reset the drive.
Option External
Fault

An external fault was tripped by the upper controller via an option card.
• Remove the fault cause, reset the fault and restart the drive.
• Check the upper controller program.
External Fault
A forward and reverse command were input simultaneously for longer than 500 ms. This alarm stops a running motor.
• Check the sequence and make sure that the forward and reverse input are not set at the same time.
External Faults

• An external fault was triggered by an external device via one of the digital inputs S1 to S8.
• The digital inputs are set up incorrectly.
• Find out why the device tripped the EF. Remove the cause and reset the fault.
• Check the functions assigned to the digital inputs.
Ground Fault
• Ground leakage current has exceeded 50% of the drives rated output current.
• Cable or motor insulation is broken.
• Excessive stray capacitance at drive output.
• Check the output wiring and the motor for short circuits or broken insulation. Replace any broken parts.
• Reduce the carrier frequency.
Safe Disable
Both Safe Disable inputs are open. The drive output is safely disabled and the motor can not be started.
• Check why the upper controller’s safety device disabled the drive. Remove the cause and restart.
• Check the wiring.
• If the Safe Disable function is not utilized for the ISO13849-1, Category 3 PLd, and IEC61508, SIL2 or for disabling the drive, the terminals HC, H1, H2 must be linked.
Safe Disable Fault
Drive output is disabled while only one of the Safe Disable inputs is open. (normally both input signals H1 and H2 should be open)
• One channel is internally broken and does not switch off, even if the external signal is removed.
• Only one channel is switched off by the upper controller.
• Check the wiring from the upper controller and make sure that both signals are set correctly by the controller.
• If the signals are set correctly and the alarm does not disappear, replace the drive.
bb
CF
CPF02 to
CPF24
CPF25
CrST
EF0
EF
EF1 to EF8
GF
Hbb
HbbF
Page 32
7 Troubleshooting
32 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
Output Phase Loss
Output cable is disconnected or the motor winding is damaged. Loose wires at the drive output. Motor is too small (less than 5% of drive current).
• Check the motor wiring.
• Make sure all terminal screws in the drive and motor are properly tightened.
• Check the motor and drive capacity.
Overcurrent
Short circuit or ground fault on the drive output side The load is too heavy. The accel./decel. times are too short. Wrong motor data or V/f pattern settings. A magnetic contactor was switched at the output.
• Check the output wiring and the motor for short circuits or broken insulation. Replace the broken parts.
• Check the machine for damages (gears, etc.) and repair any broken parts.
• Check the drive parameter settings.
• Check the output contactor sequence.
Heatsink Overheat

Surrounding temperature is too high. The cooling fan has stopped. The heatsink is dirty. The airflow to the heatsink is restricted.
• Check the surrounding temperature and install cooling devices if necessary.
• Check the drive cooling fan.
• Clean the heatsink.
• Check the airflow around the heatsink.
Motor Overload
The motor load is too heavy. The motor is operated at low speed with heavy load. Cycle times of accel./ decel. are too short. Incorrect motor rated current has been set.
• Reduce the motor load.
• Use a motor with external cooling and set the correct motor in parameter L1-01
• Check the sequence.
• Check the rated current setting.
Drive Overload
The load is too heavy. The drive capacity is too small. Too mu ch torque at low speed.
• Check the load.
• Make sure that the drive is big enough to handle the load.
• The overload capability is reduced at low speeds. Reduce the load or increase the drive size.
DC Overvoltage

DC bus voltage rose too high. The deceleration time is too short. Stall prevention is disabled. Braking chopper / resistor broken. Unstable motor control in OLV. Too high input voltage.
• Increase the deceleration time.
• Enable stall prevention by parameter L3-04.
• Make sure the braking resistor and braking chopper are working correctly.
• Check motor parameter settings and adjust torque and slip compensation as needed.
• Make sure that the power supply voltage meets the drives specifications.
Input Phase Loss
Input voltage drop or phase imbalance. One of the input phase is lost. Loose wires at the drive input.
• Check the power supply.
• Make sure that all cables are properly fixed to the correct terminals.
Braking Transistor
Fault
The internal braking transistor is broken.
• Cycle the power supply.
• Replace the drive if the fault reoccurs.
Thermistor Disconnect
The motor thermistor is not connected properly. Check the wiring for the thermistor.
DC Undervoltage

The voltage in the DC bus fell below the undervoltage detection level (L2-05). The power supply failed or one input phase has been lost. The power supply is too weak.
• Check the power supply.
• Make sure, that the power supply is strong enough.
Controller
Undervoltage
The drives controller power supply voltage is too low.
• Cycle power to the drive. Check if the fault reoccurs.
• Replace the drive if the fault continues to occur.
DC Charge Circuit
Fault
The charge circuit for the DC bus is broken.
• Cycle power to the drive. Check if the fault reoccurs.
• Replace the drive if the fault reoccurs.
Digital Operator AL FLT Cause Corrective Action
PF
oC
oH or oH1
oL1
oL2
ov
LF
r
r
THo
Uv1
Uv2
Uv3
Page 33
7 Troubleshooting
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 33
Operator Programing Errors
An Operator Programming Error (oPE) occurs when an inapplicable parameter is set or an individual parameter setting is inappropriate. When an oPE error is displayed, press the ENTER button to display U1-18 (oPE fault constant). This monitor will display the parameter that is causing the oPE error.
Auto-Tuning Errors
Digital Operator Cause Corrective Action
Drive capacity and value set to o2-04 do not match. Correct the value set to o2-04. Parameters were set outside the allowable setting range. Set parameters to the proper values.
A contradictory setting is assigned to multi-function contact inputs H1-01 through to H1-08.
• The same function is assigned to two inputs. (this excludes “External fault” and “Not used”)
• Input functions which require the setting of other input functions were set alone.
• Input functions that are not allowed to be used simultaneously have been set.
• Fix any incorrect settings.
• Refer to the Technical Manual for more details.
• The run command source (b1-02) or frequency reference source (b1-01) is set to 3 but no option card is installed.
• The frequency reference source is set to pulse input but H6-01 is not 0.
• Install the required option card.
• Correct the values set to b1-01 and b1-02.
Settings to multi-function analog inputs H3-02 and H3-10 and PID functions conflict.
• H3-02 and H3-10 are set to the same value. (this excludes settings 0 and F)
• PID functions have been assigned to both analog inputs and the pulse input at the same time.
• Fix any incorrect setting.
• Refer to the Technical Manual for more details.
A function has been set that cannot be used in the control mode selected.(might appear after control mode change)
• Fix any incorrect setting.
• Refer to the Technical Manual for more details.
The V/f pattern setting is incorrect.
• Check the V/f pattern settings.
• Refer to the Technical Manual for more details.
One of the following setting errors has occurred while Online Tuning is enabled in OLV (A1-02 = 2):
• E2-02 has been set below 30% of the original default value
• E2-06 has been set below 50% of the original default value
• E2-03 = 0
Make sure E2-02, E2-03, and E2-06 are set the correct values.
Digital Operator Cause Corrective Action
Motor data fault The input motor data are not valid. (e.g. the base frequency and base speed do not fit).
Re-enter the data and repeat Auto-Tuning.
Minor Fault
• The wiring is faulty.
• The load is too heavy.
• Check the wiring.
• Check the load. Always perform Auto-Tuning with the load decoupled from the motor.
The STOP button was pressed and Auto-Tuning was canceled.
Repeat the Auto-Tuning.
Resistance fault
• Wrong input data.
• Auto tuning exceeded the given time frame.
• Calculated values out of range.
• Check the input data.
• Check the wiring.
• Re-enter the data and repeat the Auto-Tuning.
No-Load Current Error
• Incorrect data was entered.
• Auto tuning took too long.
• Calculated values out of range.
Rated Slip Error
• Wrong data input.
• Auto tuning exceeded the given time frame.
• Calculated values out of range.
oPE01
oPE02
oPE03
oPE05
oPE07
oPE08
oPE10
oPE18
Er-01
Er-02
Er-03
Er-04
Er-05
Er-08
Page 34
7 Troubleshooting
34 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
Acceleration error The motor did not accelerate for the specified acceleration time.
• Increase the acceleration time C1-01.
• Check the torque limits L7-01 and L7-02.
Motor speed fault. The torque reference was too high.
• Increase the acceleration time (C1-01).
• If possible, disconnect the load.
Current detection error
• One or all output phases are lost.
• Current is either too low or exceeds the drives rating.
• The current sensors are faulty.
• Check the wiring.
• Make sure, that the drive rating fits to the motor.
• Check the load. (Auto-Tuning should have been performed without the load connected.)
• Replace the drive.
Leakage Inductance Error Drive was unable to complete tuning for leakage inductance within 300 s.
• Check all wiring and correct any mistakes.
• Double check the motor rated current value that was entered to T1-04 for Auto-Tuning.
• Check the motor rated current value written on the motor nameplate and enter the correct value.
Excessive V/f Setting
• The torque reference exceeded 20% during Auto-Tuning.
• The calculated no-load current is above 80% of the motor rated current.
• Check the V/f pattern setting.
• Perform Auto-Tuning without the load connected.
• Check the input data and repeat Auto-Tuning.
Motor iron-core saturation alarm
• Calculated core saturation values out of range.
• Incorrect data was entered.
• Check the input data.
• Check the motor wiring.
• Perform Auto-Tuning without load connected.
Rated current alarm Check the input data and repeat tuning.
Adjusted Slip Calculation Error The slip that was calculated is outside the allowable range.
• Make sure the data entered for Auto-Tuning is correct.
• Execute Rotational Auto-Tuning instead. If not possible, try Stationary Auto-Tuning 2.
Resistance Tuning Error The resistance value that was calculated is outside the allowable range.
• Double check the data that was entered for the Auto-Tuning process.
• Check the motor and motor cable connection for faults.
Leakage Inductance Alarm The leakage inductance value that was calculated is outside the allowable range.
Double check the data that was entered for the Auto-Tuning process.
No-Load Current Alarm
• The entered no-load current value was outside the allowable range.
• Auto-Tuning results were less than 5% of the motor rated current.
• Check and correct faulty motor wiring.
• Double check the data that was entered for the Auto-Tuning process.
Digital Operator Cause Corrective Action
Er-09
Er-11
Er-12
Er-13
End1
End2
End3
End4
End5
End6
End7
Page 35
8 Safe Disable Input Function
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 35
8 Safe Disable Input Function
Specifications
Precautions
DANGER! Improper use of the Safe Disable function can result in serious injury or even death. Make sure the whole system or machinery that the Safe Disable function is used in complies with safety requirements. When implementing the Safe Disable function into the safety system of a machine, a thorough risk assessment for the whole system has to be carried out to assure it complies with relevant safety norms (e.g., EN95 4/ISO13849, IEC61508, EN/IEC62061,...).
DANGER! When using a PM motor, even if the dr ive output is shut off by the Safe Disable function, a break down of two output transistors can cause current to flow through the motor winding, resulting in a rotor movement for a maximum angle of 180 degree (electrically). Make sure such a situation would have no effect on the safety of the application when using the Safe Disable function. This is not a concern with induction motors.
DANGER! The Safe Disable function can switch off the drive output, but does not cut the drive power supply and cannot electrically isolate the drive output from the input. Always shut off the drive power supply when performing maintenance or installations on the drive input side as well as the drive output side.
DANGER! When using the Safe Disable inputs, make sure to remove the wire links between terminals H1, H2, and HC that were installed prior to shipment. Failing to do so will keep the Safe Disable circuit from operating properly and can cause injury or even death.
DANGER! All safety features (including Safe Disable) should be inspected daily and periodically. If the system is not operating normally, there is a risk of serious personal injury.
DANGER! Only a qualified technician with a thorough understanding of the drive, the instruction manual, and safety standards should be permitted to wire, inspect, and maintain the Safe Disable input.
NOTICE: From the moment terminal inputs H1 and H2 have opened, it takes up to 1 ms for drive output to shut off completely. The sequence set up to trigger terminals H1 and H2 should make sure that both terminals remain open for at least 1 ms in order to properly interrupt drive output.
NOTICE: The Safe Disable Monitor (output terminals DM+ and DM-) should not be used for any other purpose than to monitor the Safe Disable status or to discover a malfunction in the Safe Disable inputs. The monitor output is not considered a safe output.
NOTICE: When utilizing the Safe Disable function, use only the EMC filters recommended in
EMC Filter Installation on page 14.
Using the Safe Disable Function
The Safe Disable inputs provide a stop function in compliance with “Safe Torque Off” as defined in the IEC61800-5-2. Safe Disable inputs have been designed to meet the requirements of the ISO1384 9-1, Category 3 PLd, and IEC61508, SIL2.
A Safe Disable Status Monitor for error detection in the safety circuit is also provided.
Safe Disable Circuit
The Safe Disable circuit consists of two independent input channels that can block the output transistors. In addition, it provides a monitoring channel that indicates the status of those two input channels.
The input can either use the drive internal power supply or an external power supply. Use jumper S3 on the terminal board to select between Sink or Source mode with either internal or external power supply.
A single photocoupler output is available to monitor the status of the Safe Disable terminals. Refer to Control Circuit
Terminal Functions on page 17 for signal specifications when using this output.
Inputs / Outputs
Two Safe Disable inputs and one EDM output according to ISO13849-1 Cat. 3 PLd, IEC61508 SIL2.
Operation Time Time from input open to drive output stop is less than 1 ms.
Failure Probability
Demand Rate Low
PFD = 5.15E
-5
Demand Rate High or
Continuous
PFH = 1.2E
-9
Performance Level
The Safe Disable feature satisfies all requireme nts of perfor mance level d (PLd) as defined by ISO13849-1 (this includes DC from EDM).
Page 36
8 Safe Disable Input Function
36 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
Disabling and Enabling the Drive Output (“Safe Torque Off”)
The diagram below illustrates the Safe Disable input operation.
Entering the “Safe Torque Off” State
Whenever either one Safe Disable input or both inputs open, the motor torque is shut off by switching off the drive output. If the motor was running before the Safe Disable inputs opened, then the motor will coast to stop, regardless of the stopping method set in parameter b1-03.
Notice that the “Safe Torque Off” state can only be achieved using the Safe Disable function. Removing the Run command stops the drive and shuts the output off (baseblock), but does not create a “Safe Torque Off” status.
Note: To avoid an uncontrolled stop during normal operation, make sure that the Safe Disable inputs are opened first when the motor
has completely stopped.
Returning to Normal Operation after Safe Disable
The Safe Disable function can only be deactivated when a Run command is not active. When Safe Disable was activated during stop, normal operation can be resumed by simply turning on both Safe Disable
inputs (i.e., by deactivating “Safe Torque Off”). When Safe Disable was activated during run, first the Run command has to be removed and then the Safe Disable inputs
have to be turned on before the drive can be restarted.
Safe Disable Monitor Output Function and Digital Operator Display
The table below explains the drive output and Safe Disable monitor state depending on the Safe Disable inputs.
Safe Disable Input Status Safe Disable Status
Monitor,
DM+ - DM-
Drive Output Status Digital Operator Display
Input 1, H1-HC Input 2, H2-HC
OFF OFF OFF
Safely disabled, “Safe
Torque Off”
Hbb (flashes)
ON OFF ON
Safely disabled, “Safe
Torque Off”
HbbF (flashes)
24V
Safety Outputs
Power Module
PN
M
Gate Block 2
Gate Block 1
Control
Circuit
Main Power
H1
H2
HC
Drive
Jumper S3
Setting:
SOURCE
>=1
DM+
DM-
Feedback
Safety Relay or PLC
w
ith safety functionality
H1, H2 Input
Drive Output
ON (Safe Disable off)
Normal operation
OFF (Safe Disable activated)
Safe Torque-Off
Run Command
Run Stop
Baseblock (Not Safe!)
Output
Frequency
Motor coasts
to stop
Run Command must be
released to deactivate
Safe Disable
Drive is ready for
operation
Page 37
8 Safe Disable Input Function
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 37
Safe Disable Status Monitor
With the Safe Disable monitor output (terminals DM + and DM-), the driv e provides a safety status feedback signal. This signal should be read by the device that controls the Safe Disable inputs (PLC or a safety relay) in order to prohibit leaving the “Safe T orque Off” status in case the safety circuit malfunctions. Refer to the instruction manual of the safety device for details on this function.
Digital Operator Display
When both Safe Disable inputs are open, Hbb will flash in the digital operator display. Should only one of the Safe Disable channels be on while the other is off, HbbF will flash in the display to indicate that
there is a problem in the safety circuit or in the drive. This display should not appear under normal conditions if the Safe Disable circuit is utilized properly. Refer to General Fault and Alarms on page 31 to resolve possible errors.
OFF ON ON
Safely disabled, “Safe
Torque Off”
HbbF (flashes)
ON ON ON
Baseblock, ready for
operation
Normal display
Safe Disable Input Status Safe Disable Status
Monitor,
DM+ - DM-
Drive Output Status Digital Operator Display
Input 1, H1-HC Input 2, H2-HC
Page 38
38 YA SKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
9 UL Standards
9UL Standards
UL Standards Compliance
The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product testing and evaluation, and determined that their stringent standards for product safety have been met. For a product to receive UL certification, all components inside that product must also receive UL certification.
UL/cUL Mark
This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The conditions described below must be met to maintain compliance when using this drive in combination with other equipment:
Note: Model CIMR-A4A1200 is UL compliant when the air entering the drive-installed panel or cabinet is 45°C or less. For more
information, contact your nearest Yaskawa representative or our sales office.
Installation Area
Do not install the drive to an area greater than pollution degree 2 (UL standard).
Main Circuit Terminal Wiring
Yaskawa recommends using closed-loop crimp terminals on all drive models. UL/cUL approval requires the use of closed-loop crimp terminals when wiring the drive main circuit terminals on models CIMR-A2A0110 to 2A0415 and 4A0058 to 4A1200. Use only the tools recommended by the terminal manufacturer for crimping.
The wire gauges listed in the tables below are Yaskawa recommendations. Refer to local codes for proper wire gauge selections.
Note: The mark indicates the terminals for protective ground connection. (as defined in IEC60417-5019)
Grounding impedance; 200 V: 100 Ω or less 400 V: 10 Ω or less
Model
CIMR-A
Terminal
For Europe and
China <1>
For U.S.A<2> For Asia <3>
Screw
Size
Tightening
Torque
N"m (lb.in.)
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2
Recommen
ded Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2
2A0004 2A0006 2A0010
R/L1, S/L2, T/L3 2.5 2.5 to 6 14 14 to 10 2 2 to 5.5
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/ T3
2.5 2.5 to 6 14 14 to 10 2 2 to 5.5
–, +1, +2 2.5 to 6 14 to 10 2 2 to 5.5 B1, B2 –2.5 to 6–14 to 1022 to 5.5
2.5 2.5 to 6 10 14 to 10 2 2 to 5.5
2A0012
R/L1, S/L2, T/L3 2.5 2.5 to 6 12 14 to 10 2 2 to 5.5
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/ T3
2.5 2.5 to 6 14 14 to 10 2 2 to 5.5
–, +1, +2 2.5 to 6 14 to 10 2 2 to 5.5 B1, B2 –2.5 to 6–14 to 1022 to 5.5
2.5 2.5 to 6 10 14 to 10 3.5 2 to 5.5
2A0021
R/L1, S/L2, T/L3 4 2.5 to 6 10 12 to 10 5.5 3.5 to 5.5
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/ T3
2.5 2.5 to 6 10 12 to 10 3.5 3.5 to 5.5
–, +1, +2 4 to 6 12 to 10 5.5 3.5 to 5.5 B1, B2 –2.5 to 6–14 to 1022 to 5.5
4 4 to 6 10 12 to 10 3.5 3.5 to 5.5
Page 39
9 UL Standards
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 39
2A0030
R/L1, S/L2, T/L3 6 4 to 16 8 10 to 6 14 5.5 to 14
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/ T3
6 4 to 16 8 10 to 6 8 5.5 to 14
–, +1, +2 6 to 16 10 to 6 14 5.5 to 14 B1, B2 4 to 6 14 to 10 3.5 2 to 5.5
6 6 to 10 8 10 to 8 5.5 5.5 to 8 M5
2 to 2.5
(17.7 to 22.1)
2A0040
R/L1, S/L2, T/L3 10 6 to 16 6 8 to 6 14 14
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/ T3
10 6 to 16 8 8 to 6 14 8 to 14
, +1, +2 –16– 61414 B1, B2 4 to 6 12 to 10 5.5 3.5 to 5.5
10 6 to 10 8 10 to 8 5.5 5.5 to 8 M 5
2 to 2.5
(17.7 to 22.1)
2A0056
R/L1, S/L2, T/L3 16 16 to 25 4 6 to 4 22 14 to 22
M6
4 to 6
(35.4 to 53.1)
U/T1, V/T2, W/ T3
16 16 to 25 4 6 to 4 14 14 to 22 –, +1, +2 16 to 25 6 to 4 22 14 to 22 B1, B2 6 to 10 10 to 6 14 5.5 to 14 M5
2 to 2.5
(17.7 to 22.1)
16 10 to 16 6 8 to 6 8 8 to 14 M6
4 to 6
(35.4 to 53.1)
2A0069
R/L1, S/L2, T/L3 25 16 to 25 3 4 to 3 30 22 to 30
M8
9 to11
(79.7 to 97.4)
U/T1, V/T2, W/ T3
16 16 to 25 3 4 to 3 22 14 to 30 –, +1, +2 25 4 to 3 30 22 to 30 B1, B2 10 to 16 8 to 6 14 8 to 14 M5
2 to 2.5
(17.7 to 22.1)
16 16 to 25 6 6 to 4 8 8 to 22 M6
4 to 6
(35.4 to 53.1)
2A0081
R/L1, S/L2, T/L3 35 25 to 35 2 3 to 2 38 30 to 38
M8
9 to11
(79.7 to 97.4)
U/T1, V/T2, W/ T3
25 25 to 35 2 3 to 2 30 22 to 38 –, +1, +2 25 to 35 3 to 2 38 30 to 38 B1, B2 –16– 61414M5
2 to 2.5
(17.7 to 22.1)
16 16 to 25 6 6 to 4 14 14 to 22 M6
4 to 6
(35.4 to 53.1)
2A0110
<4>
R/L1, S/L2, T/L3 35 25 to 50 1/0 3 to 1/0 38 30 to 50
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/ T3
35 25 to 50 1/0 3 to 1/0 38 30 to 50 –, +1 35 to 50 2 to 1/0 60 38 to 60
B1, B2 16 to 50 6 to 1/0 22 14 to 50
16 16 to 25 6 6 to 4 14 14 to 38
2A0138
<4>
R/L1, S/L2, T/L3 50 35 to 70 2/0 1 to 2/0 60 50 to 60
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/ T3
50 35 to 70 2/0 1 to 2/0 60 50 to 60 –, +1 50 to 70 1/0 to 3/0 80 60 to 80
B1, B2 25 to 70 4 to 2/0 30 22 to 60
25 25 4 4 22 22 to 38 M8
9 to 11
(79.7 to 97.4)
Model
CIMR-A
Terminal
For Europe and
China <1>
For U.S.A<2> For Asia <3>
Screw
Size
Tightening
Torque
N"m (lb.in.)
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2
Recommen ded Gauge AWG, kcmil
Applicable
Gauge
AWG, kcmil
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2
Page 40
9 UL Standards
40 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
Note: Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a continuous maximum
allowable temperature of 75°C 600 V UL approved vinyl sheathed insulation. Ambient temperature should not exceed 40°C.
2A0169
<4>
R/L1, S/L2, T/L3 70 50 to 95 4/0 2/0 to 4/0 80 60 to 100
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/ T3
70 50 to 95 4/0 3/0 to 4/0 80 60 to 100
–, +1 35 to 95 1 to 4/0 50 × 2P 50 to 100 +3 50 to 95 1/0 to 4/0 60 50 to 100
35 25 to 35 4 4 to 2 22 22 to 60
9 to 11
(79.7 to 97.4)
2A0211
<4>
R/L1, S/L2, T/L3 95 70 to 95 1/0 × 2P 1/0 to 2/0 100 80 to 100
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/ T3
95 70 to 95 1/0 × 2P 1/0 to 2/0 50 × 2P 50 to 60
–, +1 35 to 95 1 to 4/0 50 × 2P 50 to 100 +3 50 to 95 1/0 to 4/0 80 60 to 100
50 25 to 50 4 4 to 1/0 22 22 to 60
9 to 11
(79.7 to 97.4)
2A0250
<4>
R/L1, S/L2, T/L3 95 × 2P 95 to 150 3/0 × 2P 3/0 to 300 80 × 2P 38 to 150
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/ T3
95 × 2P 95 to 150 3/0 × 2P 3/0 to 300 80 × 2P 38 to 150 –, +1 70 to 150 3/0 to 300 80 × 2P 80 to 150 +3 35 to 150 2 to 300 80 × 2P 30 to 150 M10
18 to 23
(159 to 204)
95 95 to 150 3 3 to 300 22 22 to 150 M12
32 to 40
(283 to 354)
2A0312
<4>
R/L1, S/L2, T/L3 95 × 2P 95 to 150 4/0 × 2P 3/0 to 300 80 × 2P 70 to 150
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/ T3
95 × 2P 95 to 150 3/0 × 2P 3/0 to 300 80 × 2P 70 to 200 –, +1 70 to 150 3/0 to 300 150 × 2P 80 to 150 +3 70 to 150 3/0 to 300 80 × 2P 80 to 150 M10
18 to 23
(159 to 204)
95 95 to 150 2 2 to 300 38 38 to 150 M12
32 to 40
(283 to 354)
2A0360
<4>
R/L1, S/L2, T/L3 240 95 to 300 250 × 2P 4/0 to 600 100 × 2P 80 to 325
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/ T3
240 95 to 300 4/0 × 2P 4/0 to 600 100 × 2P 80 to 325 –, +1 125 to 300 250 to 600 150 × 2P 125 to 325 +3 70 to 300 3/0 to 600 80 × 2P 80 to 325 M10
18 to 23
(159 to 204)
120 120 to 240 1 1 to 350 38 38 to 200 M12
32 to 40
(283 to 354)
2A0415
<4>
R/L1, S/L2, T/L3 120 × 2P 95 to 300 350 × 2P 250 to 600 125 × 2P 100 to 325
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/ T3
300 95 to 300 300 × 2P 300 to 600 125 × 2P 125 to 325 –, +1 150 to 300 300 to 600 200 × 2P 150 to 325 +3 70 to 300 3/0 to 600 100 × 2P 80 to 325 M10
18 to 23
(159 to 204)
120 120 to 240 1 1 to 350 60 60 to 200 M12
32 to 40
(283 to 354)
<1> Gauges listed here are for use in Europe and China. <2> Gauges listed here are for use in the United States. <3> Gauges listed here are for use in Asia except for China. <4> Drive models CIMR-A2A0110 to 4A0415 require the use of closed-loop crimp terminals for UL/cUL compliance. Use only the tools
recommended by the terminal manufacturer for crimping.
Model
CIMR-A
Terminal
For Europe and
China <1>
For U.S.A<2> For Asia <3>
Screw
Size
Tightening
Torque
N"m (lb.in.)
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2
Recommen
ded Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2
Page 41
9 UL Standards
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 41
Model
CIMR-A
Terminal
For Europe and
China <1>
For U.S.A<2> For Asia <3>
Screw
Size
Tightening
Torque
N"m (lb.in.)
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2
Recommen ded Gauge AWG, kcmil
Applicable
Gauge
AWG, kcmil
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2
4A0002 4A0004
R/L1, S/L2, T/L3 2.5 2.5 to 6 14 14 to 10 2 2 to 5.5
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/ T3
2.5 2.5 to 6 14 14 to 10 2 2 to 5.5
–, +1, +2 2.5 to 6 14 to 10 2 2 to 5.5 B1, B2 2.5 to 6 14 to 10 2 2 to 5.5
2.5 2.5 to 4 12 14 to 12 2 2 to 5.5
4A0005 4A0007 4A0009
R/L1, S/L2, T/L3 2.5 2.5 to 6 14 14 to 10 2 2 to 5.5
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/ T3
2.5 2.5 to 6 14 14 to 10 2 2 to 5.5
–, +1, +2 2.5 to 6 14 to 10 2 2 to 5.5 B1, B2 2.5 to 6 14 to 10 2 2 to 5.5
2.5 2.5 to 6 10 14 to 10 3.5 2 to 5.5
4A0011
R/L1, S/L2, T/L3 2.5 2.5 to 6 12 14 to 10 2 2 to 5.5
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/ T3
2.5 2.5 to 6 14 14 to 10 2 2 to 5.5
–, +1, +2 2.5 to 6 14 to 10 2 2 to 5.5 B1, B2 2.5 to 6 14 to 10 2 2 to 5.5
2.5 2.5 to 6 10 14 to 10 3.5 2 to 5.5
4A0018
R/L1, S/L2, T/L3 2.5 2.5 to 16 10 12 to 6 3.5 2 to 14
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/ T3
2.5 2.5 to 16 10 12 to 6 3.5 2 to 14
–, +1, +2 4 to 16 12 to 6 3.5 2 to 14 B1, B2 4 to 6 12 to 10 2 2 to 5.5
2.5 2.5 to 6 10 14 to 10 3.5 2 to 5.5 M5
2 to 2.5
(17.7 to 22.1)
4A0023
R/L1, S/L2, T/L3 4 2.5 to 16 10 10 to 6 5.5 3.5 to 14
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/ T3
4 2.5 to 16 10 10 to 6 5.5 3.5 to 14
–, +1, +2 4 to 16 12 to 6 5.5 3.5 to 14 B1, B2 4 to 6 12 to 10 2 2 to 5.5
4 4 to 6 10 12 to 10 3.5 3.5 to 5.5 M5
2 to 2.5
(17.7 to 22.1)
4A0031
R/L1, S/L2, T/L3 6 6 to 16 8 8 to 6 14 5.5 to 14
M5
2 to 2.5
(17.7 to 22.1)
U/T1, V/T2, W/ T3
6 6 to 16 8 10 to 6 8 5.5 to 8 –, +1, +2 6 to 16 10 to 6 14 5.5 to 14 B1, B2 6 to 10 10 to 8 3.5 2 to 8 M5
2 to 2.5
(17.7 to 22.1)
6 6 to 10 8 10 to 8 5.5 5.5 to 8 M6
4 to 6
(35.4 to 53.1)
4A0038
R/L1, S/L2, T/L3 10 10 to 16 6 8 to 6 14 14
M5
2 to 2.5
(17.7 to 22.1)
U/T1, V/T2, W/ T3
6 6 to 16 8 8 to 6 14 8 to 14 –, +1, +2 6 to 16 6 14 14 B1, B2 6 to 10 10 to 8 5.5 3.5 to 8 M5
2 to 2.5
(17.7 to 22.1)
10 6 to 16 6 10 to 6 8 5.5 to 14 M6
4 to 6
(35.4 to 53.1)
Page 42
9 UL Standards
42 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
4A0044
R/L1, S/L2, T/L3 16 16 to 25 6 6 to 4 14 14 to 22
M6
4 to 6
(35.4 to 53.1)
U/T1, V/T2, W/ T3
16 16 to 25 6 6 to 4 14 14 to 22 –, +1, +2 16 to 25 6 to 4 14 14 to 22 B1, B2 6 to 10 10 to 8 8 5.5 to 8 M5
2 to 2.5
(17.7 to 22.1)
16 10 to 16 6 8 to 6 8 8 to 14 M6
4 to 6
(35.4 to 53.1)
4A0058
<4>
R/L1, S/L2, T/L3 16 10 to 16 4 6 to 4 14 14
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/ T3
16 10 to 16 4 6 to 4 14 14 –, +1 16 to 35 6 to 1 22 14 to 38
B1, B2 10 to 16 8 to 4 14 8 to 14
16 10 to 16 6 8 to 6 8 8 to 14
4A0072
<4>
R/L1, S/L2, T/L3 16 16 to 25 3 4 to 3 22 14 to 22
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/ T3
25 16 to 25 3 4 to 3 22 14 to 22 –, +1 25 to 35 4 to 1 30 22 to 38
B1, B2 16 to 25 6 to 3 14 14 to 22
16 16 to 25 6 6 14 14 to 22
4A0088
<4>
R/L1, S/L2, T/L3 25 16 to 50 2 3 to 1/0 30 22 to 60
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/ T3
25 25 to 50 2 3 to 1/0 30 22 to 60 –, +1 25 to 50 3 to 1/0 38 30 to 60
+3 16 to 50 6 to 1/0 22 14 to 60
16 16 to 25 4 6 to 4 22 14 to 22
4A0103
<4>
R/L1, S/L2, T/L3 35 25 to 50 1/0 2 to 1/0 38 30 to 60
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/ T3
35 25 to 50 1 2 to 1/0 38 30 to 60 –, +1 25 to 50 3 to 1/0 60 30 to 60
+3 25 to 50 4 to 1/0 30 22 to 60
16 16 to 25 4 6 to 4 22 14 to 22
4A0139
<4>
R/L1, S/L2, T/L3 50 35 to 95 3/0 1/0 to 4/0 60 38 to 100
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/ T3
50 35 to 95 2/0 1/0 to 4/0 60 50 to 100 –, +1 50 to 95 1/0 to 4/0 100 60 to 100
+3 25 to 95 3 to 4/0 50 30 to 100
25 25 4 4 22 22
4A0165
<4>
R/L1, S/L2, T/L3 70 50 to 95 4/0 3/0 to 4/0 80 60 to 100
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/ T3
70 70 to 95 4/0 3/0 to 4/0 80 80 to 100 –, +1 35 to 95 1 to 4/0 50 × 2P 50 to 100
+3 50 to 95 1/0 to 4/0 60 50 to 100
35 25 to 35 4 4 to 2 22 22 to 30
4A0208
<4>
R/L1, S/L2, T/L3 95 35 to 95 300 2 to 300 150 30 to 150
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/ T3
95 35 to 95 300 2 to 300 150 30 to 150 –, +1 35 to 150 1 to 250 80 × 2P 38 to 150
+3 25 to 70 3 to 3/0 80 22 to 80
50 50 to 150 4 4 to 300 22 22 to 150
Model
CIMR-A
Terminal
For Europe and
China <1>
For U.S.A <2> For Asia <3>
Screw
Size
Tightening
Torque
N"m (lb.in.)
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2
Recommen
ded Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2
Page 43
9 UL Standards
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 43
4A0250
<4>
R/L1, S/L2, T/L3 120 95 to 300 400 1 to 600 150 38 to 325
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/ T3
120 95 to 300 400 1/0 to 600 150 38 to 325
–, +1 70 to 300 3/0 to 600 200 80 to 325 +3 35 to 300 1 to 325 125 38 to 325
70 70 to 240 2 2 to 350 22 22 to 200
4A0296
<4>
R/L1, S/L2, T/L3 185 95 to 300 500 2/0 to 600 200 80 to 325
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/ T3
185 95 to 300 500 2/0 to 600 200 80 to 325 –, +1 70 to 300 3/0 to 600 325 80 to 325 +3 35 to 300 1 to 325 150 38 to 325 M10
18 to 23
(159 to 204)
95 95 to 240 2 2 to 350 30 30 to 200 M12
32 to 40
(283 to 354)
4A0362
<4>
R/L1, S/L2, T/L3 240 95 to 300 4/0 × 2P 3/0 to 600 250 80 to 325
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/ T3
240 95 to 300 4/0 × 2P 3/0 to 600 250 80 to 325 –, +1 95 to 300 4/0 to 600 325 100 to 325 +3 70 to 300 3/0 to 600 200 80 to 325 M10
18 to 23
(159 to 204)
120 120 to 240 1 1 to 350 30 30 to 200 M12
32 to 40
(283 to 354)
4A0414
<4>
R/L1, S/L2, T/L3 95 × 2P 95 to 150 300 × 2P 4/0 to 300 100 × 2P 80 to 150
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/ T3
95 × 2P 95 to 150 300 × 2P 4/0 to 300 125 × 2P 80 to 150
–, +1 70 to 150 3/0 to 300 150 × 2P 80 to 150 +3 70 to 150 3/0 to 300 80 × 2P 80 to 150
95 35 to 95 1 1 to 3/0 38 38 to 100
4A0515
<4>
R/L1, S/L2, T/L3 120 × 2P 95 to 150 3/0 × 4P 3/0 to 300 125 × 2P 80 to 150
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/ T3
150 × 2P 95 to 150 4/0 × 4P 3/0 to 300 150 × 2P 80 to 150
–, +1 70 to 150 1/0 to 300 60 × 4P 60 to 150 +3 70 to 150 1/0 to 300 100 × 2P 60 to 150
150 50 to 150 1/0 1/0 to 300 60 50 to 150
4A0675
<4>
R/L1, S/L2, T/L3 95 × 4P 95 to 150 300 × 4P 4/0 to 300 80 × 4P 80 to 150
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/ T3
95 × 4P 95 to 150 300 × 4P 4/0 to 300 80 × 4P 80 to 150
–, +1 70 to 150 1/0 to 300 125 × 4P 60 to 150 +3 70 to 150 1/0 to 300 60 × 4P 60 to 150
95 × 2P 60 to 150 2/0 2/0 to 300 60 70 to 150
4A0930
<4>
R/L1, S/L2, T/L3, R1/L11, S1/L21, T1/L31
120 × 4P 95 to 150 (4/0 × 4P) × 2 3/0 to 300 150 × 4P 125 to 150
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/ T3
120 × 4P 95 to 150 (4/0 × 4P) × 2 3/0 to 300 1 50 × 4P 125 to 150
–, +1 95 to 150 4/0 to 300 (125 × 4P) × 2 100 to 150 +3 95 to 150 4/0 to 300 125 × 4P 100 to 150
120 × 2P 70 to 120 3/0 3/0 to 250 100 80 to 125
Model
CIMR-A
Terminal
For Europe and
China <1>
For U.S.A<2> For Asia <3>
Screw
Size
Tightening
Torque
N"m (lb.in.)
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2
Recommen ded Gauge AWG, kcmil
Applicable
Gauge
AWG, kcmil
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2
Page 44
9 UL Standards
44 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
Note: 1. Model CIMR-A4A1200 is UL compliant when the air entering the drive-installed panel or cabinet is 45°C or less. For more
information, contact your nearest Yaskawa representative or our sales office.
2. Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a continuous maximum allowable
temperature of 75°C 600 V UL approved vinyl sheathed insulation. Ambient temperature should not exceed 40°C.
4A1200
<4>
R/L1, S/L2, T/L3, R1/L11, S1/L21, T1/L31
(95 × 4P) × 2 95 to 150 (300 × 4P) × 2 4/0 to 300 (125 × 4P) × 2 100 to 150
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/ T3
(95 × 4P) × 2 95 to 150 (300 × 4P) × 2 4/0 to 300 (125 × 4P) × 2 100 to 150
–, +1 120 to 150 250 to 300 (150 × 4P) × 2 125 to 150 +3 95 to 150 4/0 to 300 (100 × 4P) × 2 100 to 150
95 × 4P 95 to 120 4/0 4/0 to 250 125 100 to 125
<1> Gauges listed here are for use in Europe and China. <2> Gauges listed here are for use in the United States. <3> Gauges listed here are for use in Asia except for China. <4> Drive models CIMR-A4A0058 to 4A1200 require the use of closed-loop crimp terminals for UL/cUL compliance. Use only the tools
recommended by the terminal manufacturer for crimping.
Model
CIMR-A
Terminal
For Europe and
China <1>
For U.S.A <2> For Asia <3>
Screw
Size
Tightening
Torque
N"m (lb.in.)
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2
Recommen
ded Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
Recommen
ded Gauge
mm
2
Applicable
Gauge
mm
2
Page 45
9 UL Standards
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 45
Closed-Loop Crimp Terminal Recommendations
Yaskawa recommends using closed-loop crimp terminals on all drive models. UL approval requires the use of crimp terminals when wiring the drive main circuit terminals on models CIMR-A2A0110 to 2A0415 and 4A0058 to 4A1200 . Use only crimping tools as specified by the crimp terminal manufacturer . Yaskawa recommends crimp terminals made by JST and Tokyo DIP (or equivalent) for the insulation cap.
The table below matches the wire gauges and terminal screw sizes with Yaskawa - recommended crimp terminals,
tools, and insulation caps. Refer to the appropriate Wire Gauge and Torque Specifications table for the wire gauge and screw size for your drive model. Place orders with a Yaskawa representatives the Yaskawa sales department.
Wire Gauge
Terminal
Screws
Crimp Terminal
Model Number
Tool
Insulation Cap
Model No.
Code <1>
Machine No. Die Jaw
2 mm
2
14 AWG
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.
Example 1: Models with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so th e user should order two sets of [100-051-272]. Example 2: Models with 4/0 AW G × 2P for both input and output require two sets for input terminals and two sets for output terminals, so the user should order four sets of [100-051-560].
M4 R2-4 YA-4 AD-900 TP-003 100-054-028
3.5 / 5.5 mm
2
12 / 10 AWG
M4 R5.5-4 YA-4 AD-900 TP-005 100-054-029 M5 R5.5-5 YA-4 AD-900 TP-005 100-054-030
8 mm
2
8 AWG
M4 8-4 YA-4 AD-901 TP-008 100-054-031 M5 R8-5 YA-4 AD-901 TP-008 100-054-032
14 mm
2
6 AWG
M4 14-NK4 YA-4 AD-902 TP-014 100-054-033 M5 R14-5 YA-4 AD-902 TP-014 100-054-034 M6 R14-6 YA-5 AD-952 TP-014 100-051-261 M8 R14-8 YA-5 AD-952 TP-014 100-054-035
22 mm
2
4 AWG
M6 R22-6 YA-5 AD-953 TP-022 100-051-262 M8 R22-8 YA-5 AD-953 TP-022 100-051-263
30 / 38 mm
2
3 / 2 AWG
M8 R38-8 YA-5 AD-954 TP-038 100-051-264
50 / 60 mm
2
1 AWG
1/0 AWG
1/0 AWG × 2P
M8 R60-8 YA-5 AD-955 TP-060 100-051-265
M10 R60-10 YF-1, YET-300-1 TD-321, TD-311 TP-060 100-051-266
1 AWG × 2P 2 AWG × 2P
M10 38-L10 YF-1, YET-150-1 TD-224, TD-212 TP-038 100-051-556
80 mm
2
2/0 / 3/0 AWG
2/0 AWG × 2P
M10 80-10 YF-1, YET-300-1 TD-323, TD-312 TP-080 100-051-267
3/0 AWG × 2P 3/0 AWG × 4P
M10 80-L10 YF-1, YET-150-1 TD-227, TD-214 TP-080 100-051-557 M12 80-L12 YF-1, YET-300-1 TD-323, TD-312 TP-080 100-051-558
100 mm
2
4/0 AWG
M10 R100-10
YF-1, YET-300-1 YF-1, YET-150-1
TD-324, TD-312 TD-228, TD-214
TP-100 100-051-269
4/0 AWG × 2P 4/0 AWG × 4P
M10 100-L10 YF-1, YET-150-1 TD-228, TD-214 TP-100 100-051-559 M12 100-L12 YF-1, YET-300-1 TD-324, TD-312 TP-100 100-051-560
150 mm
2
250 / 300 kcmil
M10 R150-10 YF-1. YET-150-1 TD-229, TD-215 TP-150 100-051-272 M12 R150-12 YF-1, YET-300-1 TD-325, TD-313 TP-150 100-051-273
250 kcmil × 2P 250 kcmil × 4P 300 kcmil × 2P 300 kcmil × 4P
M10 150-L10 YF-1, YET-150-1 TD-229, TD-215 TP-150 100-051-561
M12 150-L12 YF-1, YET-300-1 TD-325, TD-313 TP-150 100-051-562
200 mm
2
350 kcmil 400 kcmil
M10 200-10 YF-1, YET-300-1 TD-327, TD-314 TP-200 100-051-563 M12 R200-12 YF-1, YET-300-1 TD-327, TD-314 TP-200 100-051-275
350 kcmil × 2P 400 kcmil × 2P
M12 200-L12 YF-1, YET-300-1 TD-327, TD-314 TP-200 100-051-564
325 mm
2
500 kcmil 600 / 650 kcmil 500 kcmil × 2P 600 kcmil × 2P
M10 325-10 YF-1, YET-300-1 TD-328, TD-315 TP-325 100-051-565
M12 325-12 YF-1, YET-300-1 TD-328, TD-315 TP-325 100-051-277
Page 46
9 UL Standards
46 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
Input Fuse Installation
The installation manual specifies that branch circuit protection should be provided by fuses listed in the table below.
Note: Model CIMR-A4A1200 is UL compliant when the air entering the drive-installed panel or cabinet is 45°C or less. For more
information, contact your nearest Yaskawa representative or our sales office.
Model
CIMR-A
Fuse Type
Manufacturer: Bussmann
Model Fuse Ampere Rating (A)
Three-Phase 200 V Class 2A0004 FWH-70B 70 2A0006 FWH-70B 70 2A0010 FWH-70B 70 2A0012 FWH-70B 70 2A0021 FWH-90B 90 2A0030 FWH-100B 100 2A0040 FWH-200B 200 2A0056 FWH-200B 200 2A0069 FWH-200B 200 2A0081 FWH-300A 300 2A0110 FWH-300A 300 2A0138 FWH-350A 350 2A0169 FWH-400A 400 2A0211 FWH-400A 400 2A0250 FWH-600A 600 2A0312 FWH-700A 700 2A0360 FWH-800A 800 2A0415 FWH-1000A 1000
Three-Phase 400 V Class 4A0002 FWH-40B 40 4A0004 FWH-50B 50 4A0005 FWH-70B 70 4A0007 FWH-70B 70 4A0009 FWH-90B 90 4A0011 FWH-90B 90 4A0018 FWH-80B 80 4A0023 FWH-100B 100 4A0031 FWH-125B 125 4A0038 FWH-200B 200 4A0044 FWH-250A 250 4A0058 FWH-250A 250 4A0072 FWH-250A 250 4A0088 FWH-250A 250 4A0103 FWH-250A 250 4A0139 FWH-350A 350 4A0165 FWH-400A 400 4A0208 FWH-500A 500 4A0250 FWH-600A 600 4A0296 FWH-700A 700 4A0362 FWH-800A 800 4A0414 FWH-800A 800 4A0515 FWH-1000A 1000 4A0675 FWH-1200A 1200 4A0930 FWH-1200A 1200 4A1200 FWH-1600A 1600
Page 47
9 UL Standards
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 47
Low Voltage Wiring for Control Circuit Terminals
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. Use a class 2 power supply for the control circuit terminal when not using the internal control power supply of the drive. Refer to NEC Article 725 Class 1, Class 2, and Class 3 Remote-Control, Signaling, and Power Limited Circuits for requirements concerning class 1 circuit conductors and class 2 power supplies.
Drive Short-Circuit Rating
This drive is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes, 600 Vac maximum (Up to 240 V in 200 V class drives , up to 480 V for 400 V class drives) when protected by Bussmann Type FWH fuses as specified in Input Fuse Installation on page 46.
Drive Motor Overload Protection
Set parameter E2-01 (motor rated current) to the appropriate value to enable motor overload protection. The internal motor overload protection is UL listed and in accordance with the NEC and CEC.
E2-01 Motor Rated Current
Setting Range: Model Dependent Default Setting: Model Dependent Parameter E2-01 (motor rated current) protects the motor if parameter L1-01 is not set to 0 (default is 1, enabling
protection for standard induction motors). If Auto-Tuning has been performed successfully, the motor data entered to T1-04 is automatically written into parameter
E2-01. If Auto-Tuning has not been performed, manually enter the correct motor rated current to parameter E2-01.
L1-01 Motor Overload Protection Selection
The drive has an electronic overload protection function (oL1) based on time, output current, and output frequency, which protects the motor from overheating. The electronic thermal overload function is UL-recognized, so it does not require an external thermal relay for single motor operation.
This parameter selects the motor overload curve used according to the type of motor applied.
When connecting the drive to more than one motor for simultaneous operation, disable the electronic overload protection (L1-01 = 0) and wire each motor with its own motor thermal overload relay.
Input / Output Terminal Signal Power Supply Specifications
Open Collector Outputs DM+, DM- Requires class 2 power supply. Digital inputs S1-S8, SN, SC, SP, HC, H1, H2 Use the internal LVLC power supply of the drive. Use class 2 for external power supply. Analog inputs / outputs +V, -V, A1, A2, A3, AC, AM, FM Use the internal LVLC power supply of the drive. Use class 2 for external power supply.
Setting Description
0 Disabled Disabled the drive’s internal motor overload protection.
1 Standard fan cooled motor (default)
Selects protection characteristics for a standard self cooled motor with limited cooling capabilities when running below the rated speed. The motor overload detection level (oL1) is automatically reduces when running below the motor rated speed.
2
Drive duty motor with a speed range of 1:10
Selects protection characteristics for a motor with self-cooling capability wi thi n a speed range of 10:1. The motor overload detection level (oL1) is automatically reduced when running below 1/10 of the motor rated speed.
3 Vector motor with a speed range of 1:100
Selects protection characteristics for a motor capable of cooling itself at any speed — including zero speed (externally cooled motor). The motor overload detection level (oL1) is constant over the entire speed range.
4
Permanent Magnet motor with variable torque
Selects protection characteristics for a variable torque PM motor. The motor overload detection level (oL1) is automatically reduces when running below the motor rated speed.
5
Permanent Magnet motor with constant torque
Selects protection characteristics for a constant torque PM motor. The motor overload detection level (oL1) is constant over the whole speed range.
6 Standard fan cooled motor (50 Hz)
Selects protection characteristics for a standard self cooled motor with limited cooling capabilities when running below the rated speed. The motor overload detection level (oL1) is automatically reduces when running below the motor rated speed.
Page 48
9 UL Standards
48 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
Enable the motor overload protection (L1-01 = 1 to 5) when connecting the drive to a single motor , unless another motor overload preventing device is installed. The drive electronic thermal overload function causes an oL1 fault, which shuts off the output of the drive and prevents additional overheating of the motor. The motor temperature is continually calculated as long as the drive is powered up.
L1-02 Motor Overload Protection Time
Setting Range: 0.1 to 5.0 min Factory Default: 1.0 min Parameter L1-02 determines how long the motor is allowed to operate before the oL1 fault occurs when the drive is
running at 50 Hz and at 150% of the full load amp rating (E2-01) of the motor. Adjusting the value of L1-02 can shift the set of oL1 curves up the y axis of the diagram below, but will not change the shape of the curves.
Precautionary Notes on External Heatsink (IP00 Enclosure)
When using an external heatsink, UL compliance requires that exposed capacitors in the main circuit are covered to prevent injury to surrounding personnel.
The portion of the external heatsink that projects out can either be protected with the enclosure, or with the appropriate capacitor cover after drive installation is complete. Use the table below to match drive models and capacitor cover. Capacitor covers can be ordered from a Yaskawa representative or directly from the Y askawa sales department. The table below lists available capacitor covers.
10
7
3
1
0.4
0.1
0 100 200150
Cold Start
Hot Start
Motor Current (%) (E2-01=100 %)
Time (min)
Page 49
9 UL Standards
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide 49
Note: Model CIMR-A4A1200 is UL compliant when the air entering the drive-installed panel or cabinet is 45° or less. For more
information, contact your nearest Yaskawa representative or our sales office.
Drive Model
CIMR-A
Code Number Model Figure
2A0110
<1> Requires two sets.
100-061-273 ECAT31875-11
7
2A0138 100-061-274 ECAT31876-11 2A0169
100-061-275 ECAT31877-11
2A0211
2A0250
100-061-277 ECAT31726-11
2A0312 2A0360
100-061-278 ECAT31698-11
2A0415 4A0058 100-061-273 ECAT31875-11 4A0072 100-061-274 ECAT31876-11 4A0088
100-061-276 ECAT31878-11
4A0103 4A0139
100-061-275 ECAT31877-11
4A0165 4A0208 100-061-277 ECAT31726-11 4A0250
100-061-278 ECAT31698-11
4A0296 4A0362 4A0414 100-061-279 ECAT31740-11 4A0515
100-061-280 ECAT31746-11
4A0675 4A0930
100-061-281
<1> ECAT31741-11 8
4A1200
Drive (outside panel)
Opening to capacitors
Drive (inside panel)
Installation screw
Figure 7
Capacitor cover
Page 50
9 UL Standards
50 YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
Drive (outside panel)
Opening to capacitors
Drive (inside panel)
Installation screw
Capacitor cover
Figure 8
YECcom mon
Page 51
Revision History
The revision dates and the numbers of the revised manuals appear on the bottom of the back cover.
Date of
Publication
Rev. No. Section Revised Content
August 2010 All Revision: Review and corrected entire documentation
Chapter 1 Deletion: Descriptions on UL/cUL standards compliance Chapter 2
Chapter 3
Addition: Larger drive capacities added along with corresponding data
Three-phase 400V: CIMR-AC4A0930 and 1200 Chapter 8 Revision: Safe Disable Input Function Chapter 9 Addition: UL Standards
June 2009 All Revision: Review and corrected entire documentation
Chapter 2 Chapter 3
Addition: Larger drive capacities added along with corresponding data
Three-phase 400V: CIMR-AC4A0414 to 0675
February 2009 All Revision: Review and corrected entire documentation
Chapter 2 Chapter 3
Addition: Larger drive capacities added along with corresponding data
Three-phase 200V: CIMR-AC2A0250 to 0415
Three-phase 400V: CIMR-AC4A0208 to 0362
October 2008 −−First edition
MANUAL NO.ޓTOEP C710616 27B
Published in Japan February 2009 08-10 1
Date of publication
Date of original publication
Revision number
3
2
1
Page 52
EUROPEAN HEADQUARTERS YASKAWA EUROPE GmbH
Hauptstrasse 185, 65760 Eschborn, Germany Phone: +49 (0)6196 569 300 Fax: +49 (0)6196 569 398 E-mail: info@yaskawa.de Internet: http://www.yaskawa.eu.com
YASKAWA ENGINEERING EUROPE GmbH
Hauptstrasse 185, 65760 Eschborn, Germany Phone: +49 (0)6196 569 520 Fax: +49 (0)6196 888 598 E-mail: support@yaskawa.de Internet: http://www.yaskawa-eng.eu.com
MANUFACTURING FACILITY YASKAWA ELECTRIC UK LTD.
1 Hunt Hill, Orchardton Woods, Cumbernauld G68 9LF, United Kingdom Phone: +44 (0)12 36 735 000ޓޓFax: +44 (0)12 36 458 182
U.S.A. YASKAWA AMERICA, INC.
2121 Norman Drive South, Waukegan, IL 60085, U.S.A. Phone: (800) YASKAWA (927-5292) or +1 847 887 7000 Fax: +1 847 887 7310 Internet: http://www.yaskawa.com
JAPAN YASKAWA ELECTRIC CORPORATION
New Pier Takeshiba South Tower, 1-16-1, Kaigan, Minatoku, Tokyo, 105-6891, Japan Phone: +81 (0)3 5402 4502 Fax: +81 (0)3 5402 4580 Internet: http://www.yaskawa.co.jp
DRIVE CENTER (INVERTER PLANT)
2-13-1, Nishimiyaichi, Yukuhashi, Fukuoka, 824-8511, Japan Phone: 81-930-25-3844 Fax: 81-930-25-4369 Internet: http://www.yaskawa.co.jp
YASKAWA ELECTRIC CORPORATION
In the event tha t the en d user of this produc t is to be the militar y and said p roduct i s to be employed in any weapons systems or the manufactu re thereo f, the expo rt wi ll fall u nder th e relevant regula tions a s stipu lated in the For eign Exc hange a nd Foreign Trade Regulati ons. Therefore , be sur e to follow all pr ocedure s and s ubmit al l relevant docume ntation accord ing to any and all rul es, regu lations and law s that may apply.
Specif ications are su bject t o chang e without notic e for ongoing pr oduct m odifica tions a nd impro vements.
© 2008 -2010 YASKAWA ELECTRIC CORPORATION. All right s reser ved.
YASKAWA
10-7-3_YEU
Published in Japan August 2010 08-10
MANUAL NO. TOEP C710616 27D
3
YASKAWA AC Drive A1000
High Performance Vector Control Drive
Quick Start Guide
Loading...