Brand or product names are registered t r ademarks of their respective own er s.
Windows is a registered trademark of Microsoft Corp. in the United States and other countries.
Copyright Information
This document is copyrighted by Xycom Automation Incorporated (Xycom Automation) and shall not be reproduced or copied without expressed written authorization from Xycom Automation.
The information contained within this document is subject to change without notice. Xycom Automation does not guarantee the accuracy of the
information and makes no commitment toward keeping it up to date.
United States FCC Part 15, Subpart B, Class A EMI Compliance Statement:
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are des igned to pr ovide reason able protec tion aga inst h armful in terference when the equ ipment i s operated in a commerci al environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful
interferen ce in which case the user will be required to correct the interference at his own expense.
For European Users:
WARNING
This is a Class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take
The connection of non-shielded equipment interface cables to this equipment will invalidate FCC EMI and European Union EMC compliance
and may result in electromagnetic interference and/or susceptibility levels which are in violation of regulations which apply to the legal operation
of this device. It is the responsibility of the system integrator and/or user to apply the following directions which relate to installation and configuration:
1. All interface cables must include shielded cables. Braid/foil type shields are recommended. Communication cable connectors must be
metal, ideally zinc die-cast backshell types, and provide 360 degree protection about the interface wires. The cable shield braid must be
terminated directly to the metal connector shell, ground drain wires alone are not adequate.
2. For systems other than Pentium II logic board (AHIP6+): In those cases where an external mouse is used, the snap-on ferrite bead provided
(P/N 116046) must be installed on the mouse cable at the host end in order to comply with relevant EMI regulations.
3. Protective measures for power and interface cables as described within this manual must be applied. Do not leave cables connected to
unused interfaces or disconnected at one end. Changes or modifications to this device not expressly approved by the manufacturer could
void the u ser’s authority to operate the equipment.
4. EMC compliance is, in part, a function of PCB design. Third party add-on AT/XT peripheral PCB assemblies installed within this appara-
tus may void EMC compliance. FCC/CE compliant PCB assemblies should always be used where possible. XYCOM AUTOMATION can
accept no responsibility for the EMC performance of this apparatus after system integrator/user installation of PCB assemblies not manufactured and/or expressly tested and approved for compliance by XYCOM AUTOMATION. It is the responsibility of the system integrator/user to ensure that installation and operation of such devices does not void EMC compliance.
Xycom Automation
Technical Publications Department
750 North Maple Road
Saline, MI 48176–1292
734-429-4971 (phone)
734-429-1010 (fax)
2
Table of Contents
Chapter One – Introduction........................................................................................................................5
With AHIP6+ board ...............................................................................................................................................5
With AHIP370+ board...........................................................................................................................................5
On all units .............................................................................................................................................................5
Unpacking the System...............................................................................................................................................7
Chapter Two – Testing................................................................................................................................ 9
Preparing for the Tests ..............................................................................................................................................9
Running the Tests....................................................................................................................................................11
Chapter Three - Installation...................................................................................................................... 12
System Components................................................................................................................................................ 12
SDRAM and Additional SDRAM Dual In-Line Memory Modules (DIMMs)..................................................... 20
PC/AT or PCI Boards...........................................................................................................................................20
Front Access Keyboard and Floppy Connectors...................................................................................................23
Serial AUX...........................................................................................................................................................25
Creating a Custom Logo..........................................................................................................................................25
Using a Touchscreen...............................................................................................................................................31
Video Expansion.....................................................................................................................................................35
AC Power Cable...................................................................................................................................................39
Mounting the Unit.............................................................................................................. .....................................41
Class I Locations..................................................................................................................................................44
Class II Locations.................................................................................................................................................44
Chapter Four – Keypad Utility Program..................................................................................................48
Loading the Keypad Utility.....................................................................................................................................48
Using the Keypad Utility.........................................................................................................................................48
Main Menu..............................................................................................................................................................49
Appendix B – Block Diagrams.................................................................................................................65
Appendix C – Pinouts............................................................................................................................... 67
Keyboard Port Connectors......................................................................................................................................67
Aux Port Connector.................................................................................................................................................67
Dual USB Connector (USB1) .................................................................................................................................67
Parallel Port Connector (LPT1)...............................................................................................................................68
Serial Port Connectors.............................................................................................................................................68
Appendix D – Replacing Flat-Panel Display Bulbs................................................................................71
4
Chapter One – Introduction
Product Overview
The 3500 series of flat panel industrial PCs with 6-slot ISA/PCI expansion include the
3515, 3515T, 3515KPM, and 3512KPM models. These industrial PCs offer a powerful,
compact package for the factory floor and other harsh environments. The 3515 is an industrial PC with a display only (touchscreen optional). The 3512KPM and 3515KPM is
an industrial PC with a display, integrated keypads, and an integrated mouse.
They feature an open architecture to meet a wide variety of applications that require both
a powerful PC and a durable industrial front panel. The PCs integrate a computer card
cage, mass storage, display, and power supply in a truly industrial form. Their modular
design allows easy access to expansion boards, jumpers, power supply, flat panel display, and disk drives.
The front panel of every model is sealed to NEMA 4/4X/12, and the flat panel display is
protected by an impact-resistant shield.
Chapter Two - Testing
Standard Features
With AHIP6+ board
• Pentium® III technology
• PCI 64 bit video controller, 2 MB video RAM
• PCI local-bus IDE controller
• Two 168-pin SDRAM DIMMs that support 32, 64, 128, and 256 MB options
• Two USB ports
• 100MHz front side bus with Pentium III processors
With AHIP370+ board
• Celeron ® technology
• AGP 64 bit video controller, 2 MB video RAM
• PCI local-bus IDE controller
• Two 168-pin SDRAM DIMMs that support 32, 64, 128, and 256 MB options
• Two USB ports
On all units
Two serial COM ports
• COM 1
• RS-232 or RS-485 (DB9 connector)
• RS-232 (DB25 connector)
5
3500 Series Flat Panel Industrial PC
• Flat panel display
• 15-inch flat panel, 1024x768 resolution (3515T and 3515KPM)
• Two PCI slots (4.8” maximum length with AHIP6+ board)
• IR Port (IrDA and ASKIR compatible)
• Rear PS/2 keyboard port and AUX port (also a front PS/2 keyboard port on
3512KPM and 3515KPM)
• Status LEDs
• Power
• Disk
• Com
• Input
• 3.5-inch internal IDE hard drive
• MS-DOS
®
• Front panel sealed to meet NEMA 4/4X/12 specifications when panel mounted in a
suitable fire and electrical enclosure.
• Approved for use in Class I, Division 2 hazardous locations
• Autosensing AC power supply
• Side power connector with retainer bracket
Optional Features
• Touchscreen resistive technology with less than 1.5% linearity error
• Higher capacity IDE hard drives and solid state drives
• 3512KPM
• 40 relegendable function keys (80 with the F/A function)
• Numeric, PC control, and alpha keypads
• Integrated mouse
• 3515KPM
• 40 relegendable function keys (80 with the F/A function)
• Numeric, PC control, and alpha keypads
• Windows start menu and pop-up menu keys
• Integrated mouse
6
• Flat-panel display
• 15.0-inch TFT flat panel (3515 and 3515KPM)
• 12.1-inch TFT flat panel (3512KPM)
• CD-ROM (internal)
• Pre-installed PCI 10/100 Base-T Ethernet card
• External floppy drive 9000-EXF
• Front mount floppy kit 9000-FFK
• Front access panel for floppy port and keyboard port 9000-FKA
• Preloaded Microsoft
Unpacking the System
When you remove the system from its box, verify that you have the parts listed below.
Save the box and inner wrapping in the event you need to reship the unit.
• 3515, 3515KPM, or 3512KPM unit
• AC power connector
Chapter Two - Testing
Windows 95 or Windows NT® operating system
• Power connector retainer bracket with AC power supply
• Sixteen 10-32 hex nuts (2 spares)
• Clip-on Ferrite for AUX cables
• Documentation kit, which includes:
• Diagnostic software disk (only on units shipped with DOS)
• VGA utility disk
• 3515/3512KPM manual
• CPU manual
• Business reply card
If you ordered the system with a touchscreen installed, you will also receive a touchscreen driver disk and manual. If you ordered a CD-ROM installed, you will receive the
driver disk. If you ordered a 3512KPM or 3515KPM, you will receive a mouse disk and
manual. If you ordered the system with an Ethernet card you will receive a driver disk.
Quick Start-up
This section provides the steps to get your unit up and running without explaining the
capabilities and options of the system.
Turn off power to the unit and disconnect the power cord before making
any adjustments to the inside or the outside of the computer.
Perform the following steps to prepare the system for use.
Warning
7
3500 Series Flat Panel Industrial PC
1. Attach an optional keyboard to the keyboard port.
2. Attach other optional equipment following the instructions in Chapter 3.
3. Attach the power cord from the power receptacle to a properly grounded 115/230
VAC, 50-60 Hz outlet or a 24 VDC outlet, whichever applies (Refer to the Creatinga Power Cable section in Chapter 3 for more information.)
4. Turn on the power to the unit. Depending on your operating system, one of the fol-
lowing will occur:
• In DOS, the system will boot up at the C: prompt
• In Windows 95 or Windows NT the License Agreement will be displayed
5. Install application software via the floppy, a network connection, the IR port, or a
CD-ROM.
8
Chapter Two – Testing
On units with MS-DOS installed, diagnostic tests are provided as a tool to verify the operation of system hardware functions. If any of these tests fails, either you do not have
the correct default setting or there is a failure. Check the default settings and run the tests
again. If another failure occurs, contact Xycom Automation’s Product Repair & Customization Department (see Chapter 5).
Remove any device drivers or memory resident programs (TSRs) installed on the system before running Xycom Automation diagnostic
tests. If you do not, unexpected failures may occur.
The diagnostic disk does not provide an option to test a CD-ROM drive.
Chapter Two - Testing
Note
Make sure the BIOS setup menus are configured properly (factory set configuration).
To enter the BIOS setup menus,
1. Press
2. Make the necessary changes by following directions on the screen.
3. Press
4. Press ENTER twice to save the settings and exit the BIOS setup menus.
Refer to your CPU manual for more information on the BIOS setup menus.
F2after the POST RAM test has completed.
ESC.
Preparing for the Tests
You need the following equipment to test your system:
• Floppy disk drive
• Xycom Automation System Test Disk (3.5-inch, DS/DD bootable disk, Xycom
Automation part number 99290-001)
• Centronics-compatible printer cable
• Parallel printer (Centronics-style interface)
• Two serial loopback test connectors (refer to Figure 2-12-1 for pinouts)
• Formatted 3.5-inch, DS/HD disk (1.44 MB)
• IBM PC/AT or PS/2 compatible keyboard
9
3500 Series Flat Panel Industrial PC
Perform the steps below before starting the system tests:
1. Place the CPU board jumpers and switches to the factory set positions. Refer to your
CPU manual for these settings.
2. Plug the female end of the AC power cable into the side of the unit and the male end
into a properly grounded outlet.
3. Connect the serial loopback connector(s) and the printer cable to the appropriate
connectors and connect a PC/AT or PS/2 keyboard. Figure 2-1 illustrates the wiring
necessary for the loopback connection.
4. Default the CMOS setup to the factory settings.
10
Figure 2-1. Serial Loopback Connections
Running the Tests
To run the test, insert the diagnostics disk into drive A. Turn on the computer (the diagnostics program will boot-up). Figure 2-2 shows the Main Menu.
Copyright 1990-1996, Xycom Automation, Inc. All rights reserved.
Chapter Two - Testing
Diagnostic Tests Sequence/Selection Menu (Rel. xx)
1. WILL pause on error
2. SINGLE PASS test mode
3. Save setup to file
4. Extract setup from a file
A)RAM Test
B)Video RAM Test
C)Extended RAM Test
D)Real Time Clock Test
E)COM1 Serial Port Test
F)COM2 Serial Port Test
G)COM3 Serial Port Test
H)COM4 Serial Port Test
I)Math Coprocessor Test
J)Video Adjustments Test
[ENTER]=START TESTING
Use the letters to move the cursor and select/deselect, or use the arrow keys to move, then
use the [SPACE] key to select/deselect a test or function.
Figure 2-2. Main Menu
5. Auto-select tests
6. Deselect all tests
7. Quit and exit to DOS
8. Return to previous screen
K)Video Interface Test
L)Speaker Port Test
M)LPT1: Printer Port Test
N)LPT2: Printer Port Test
O)C: Hard Drive Interface Test
P)D: Hard Drive Interface Test
Q)A: Floppy Drive Interface Test
R)B: Floppy Drive Interface Test
S)Keyboard, Keypad Tests
≡ = Test Selected
Please read the DIAG.TXT file on the diagnostics disk for detailed information about the tests.
Avoid repeated running of any hard disk diagnostic utility if you use the
Solid State (Flash) drive option. The Flash drive has a limited number of
writes to each logical sector. Repeated writes from a diagnostic utility
will prematurely shorten the life of the drive.
Note
Note
11
3500 Series Flat Panel Industrial PC
Chapter Three - Installation
System Components
This section describes the components on the unit to help you locate features relevant
to installation.
3515 Front Panel
The 3515 comes with a NEMA 4/4X/12 and IP65 sealed front panel with a TFT (Figure
3-3) display. The panel protects the system’s interior when the system is properly panel
mounted.
TOUCH
SCREEN
(OPT IONAL)
POWER DISK COM INPUT
IR P O R T
IR PORT POWER DISK
COM
INPU T
Figure 3-1. 3515 TFT Active Display Front Panel
12
Chapter Three - Installation
FeatureDescription
DisplayThe 3515 comes standard with a 15-inch TFT flat panel. Impact-resistant shields
protect the displays from breakage. If a touchscreen is factory installed, the
touchscreen is backed by heat-annealed safety glass replacing the impactresistant shield.
System Status LEDsThe 3515 features four status LEDs on the front panel, which you can use to
monitor system operation.
PowerThere is power to the 3515.
DiskThe computer module is accessing the disk drive.
COMThere is communication activity on one of the computer module’s serial
ports, including communication between the computer module and the
touchscreen (if on COM2) or a serial device.
InputThe unit has a touchscreen and the LED gets brighter when touch input
is detected.
During power-up, firmware on the processor board checks the hardware configuration against the configuration stored in the CMOS memory.
IR (Infrared)The IR port transceiver is loc ated behind this window. The 3515 IR por t is Ir DA,
and ASK-IR compliant. You can connect the 3515 to any IrDA compatible device, if you load special software (not included). T he inf r ared ( IR) link oper ates
at a distance of 0 to 1 meter and is capable of 115 Kbaud transfer rates. Enable
the interface through the BIOS setup m enus.
COM2 is not available. Correspondingly, if COM2 is in use by the touchscreen the IR is
not operational.
Note: When the IR port is chosen,
13
3500 Series Flat Panel Industrial PC
3512KPM and 3515KPM Front Panel
The 3512KPM (Figure 3-2) and 3515KPM (figure 3-3) comes with a NEMA 4/4X/12
sealed front panel. The panel protects the system’s interior when the system is properly
panel mounted.
FLAT-PANEL
DISPLAY
PROGRAMMABL E
FUNCTION KEYS
(PF1-PF10)
CONFIGURATION
KEY (PF10)
xycom
PF1
A
PF2
B
PF3
C
PF4
D
PF5
E
PF6
F
PF7
G
PF8
H
PF9
I
PF10
J
F1 F2F5 F6 F7 F8 F9 F10
F3 F4
KLOPQRST
MN
F11F12F13F14F15F16F17F18F19F20
UVWXYZ
PROGRAMMABLE
FUNCTION KEYS
(PF11-PF20)
CTR L
SHIFT
ALT
TAB
F
SPACE
/
A
123
456
789
.
0
PgUp
HOME
PgDn
ENTER
ESC
DEL
BACKSPACE
PF11
(
PF12
)
PF13
?
PF14
PF15
%
PF16
$
PF17
@
PF18
<
PF19
>
PF20
~
POWER DISK COM INPUT
:
/
\
*
F/A KEY
NUMERIC
KEYPAD
=
+
CURSOR
CONTROL
SYSTEM
STATUS
LEDS
KEYBOARD &
IR-PORT ACCESS DOOR
Figure 3-2 3512KPM Front Panel with Keypad
Figure 3-3. 3515KPM Front Panel with Keypad
FUNCTION KEYS (F1-F20)MOUSE
14
Chapter Three - Installation
FeatureDescription
DisplayThe 3512KPM comes standard with a 12.1-inch TFT flat panel. The 3515KPM
comes standard with a 15-inch TFT flat panel. Impact-resistant shields protect the
display from breakage. If a touchscreen is factory installed, the touchscreen is
backed by heat-annealed safety glass replacing the impact-resistant shield.
System Status LEDsYou can use LEDs on the front panel to monitor system operation.
PowerLit when there is power
DiskLit when the computer is accessing the disk drive.
COMLit when there is communication activity on one of the serial ports, in-
cluding communication between the computer module and the touchscreen (if on COM2) or a serial device.
InputLit when the unit has a touchscreen; the LED gets brighter when a touch
input is detected or a key is pressed.
F/A key Lit when alpha characters are being returned.
During power-up, firmware on the processor board checks the hardware configu-
ration against the configuration stored in the CMOS memory.
Function and UserDefined Keys
The 40 relegendable function keys (80 using the F/A key) provide easy access to
familiar routines. (The F/A key can be used for alpha and symbol entry). See theCustomizing Keypad Inserts section in this chapter for details on customizing your
keypad inserts.
Numeric/Cursor
The data entry keypads are for entering data and moving the cursor.
Control Keypad
Windows keys
(3515KPM only)
These keys access the star t menu and pop-up menus in the Windows NT or 95
operating system.
F/A KeyWhen the LED is lit, alpha characters are r eturned.
PF10 Key (Keypad
This key configures your keypad.
Configuration)
Keyboard Port (front
access)
The 3512KPM and 3515KPM support one PS/2 keyboard, located on the lower
left side of the front panel. On the 3512KPM the port is behind an ac c ess door .
When using this por t, the side por t cannot be us ed.
MouseThe built-in pointing device is located on the right-hand side of the front panel. It
operates in the same manner as a conventional mouse. Refer to the mouse diskette and manual supplied with your documentation kit. This mouse consists of
three basic parts:
Left mouse keyServes the same function as the left button on a conventional
mouse.
Mouse domeMoves the pointer around the screen. Press the edge of the
dome that corresponds to the direction in which you wish to
move the pointer.
Right mouse keyServes the same function as the right button on a conven-
tional mouse.
15
3500 Series Flat Panel Industrial PC
I/O Panel
Figure 3-4 illustrates the I/O Panel on the right side of the 3515 and 3512KPM.
LID LATCH (2)
(on back)
EXPANSION
SLOTS (6)
LID
ETHERNET
PORT
(OPTIONAL)
SAFETY
RETENTION
SCREW (2)
MOUNTING
STUD (14)
FRONT
PANEL
COM 2
RS-232
PARALLELRS-232
COM 1
RS-485
AUX
KEYBD
USB1
VIDEO
3.5"
FLOPPY
DRIVE
5.25"
DRIVE BAY
KNOCK OUT
OR CD-ROM
VENT
FILTER
(on bottom)
Figure 3-4. 3515/3512KPM I/O Panel
FeatureDescription
Parallel PortThe parallel printer port (LPT1) is a stacked DB-25 pin female connector.
This port provides a standard PC compatible printer interface. An external
push-button reset option is available. Consult the CPU board manual for
the jumper which controls this option.
COM PortsCOM1 consists of two connectors (RS-232 and RS-485) attached to one
logical port. Only one connector can be used at a time. COM2 consists of
one connector (RS-232).
Keyboard PortThe keyboard port is a PS/2 stacked mini-din that allows you to attach a
PC/AT keyboard at the side of the unit. Do not use in a hazardous environment. Note: You cannot use both keyboard ports on units that have
more than one keyboard port.
USB PortUSB (Universal Serial Bus) is a "plug-and-play" interface between a com-
puter and add-on devices (such as audio players, joysticks, keyboards,
telephones, scanners, and printers). With USB, a new device can be
added to your computer without having to add an adapter card or even
having to turn the computer off. USB supports a data speed of 12 megabits
per second. This speed will accommodate a wide range of devices, including MPEG-2 video devices, data gloves, and digitizers.
16
Chapter Three - Installation
FeatureDescription
AUX PortThe AUX port is a PS/2 stacked mini-din that allows you to attach a serial
device (such as a mouse) at the side of the unit. The AUX port is the upper
connector. If you receive a unit with a touchscreen, this port is covered with
a label stating that the port is not functional as shipped.
Note: The AUX port is not available on the 3512KPM or 3515KPM. Also,
when MS-DOS is installed, the touchscreen on the 3515T is fac tor y c onfigured for the AUX port. Plugging in a serial device while the touchscreen is attached will cause an err or mes s age during boot up and neither device will work. The touchsc reen mus t be rec onfigur ed for us e on
COM2 for the AUX port to be functional.
Video PortThe video port is a 15-pin D-sub VGA connector at the side of the unit.
This connector supports any standard VGA connection. The video port is
disabled when shipped. This port is active if an LCD flat panel is not connected. A jumper can be used to switch between the VGA port and the
LCD. To use both a video display on the video port and the flat panel display, you must enable “Simultaneous Video” (only available on the TFT
version) on the Advanced Menu in the BIOS setup menus. Refer to the
CPU manual for details.
CD Drive (Optional)There is a 5¼-inch drive-bay knockout for a CD drive.
Caution: If you have a CD-ROM installed, use of controls, adjustments, or the performance of procedures other than those specified
herein may result in hazardous ra diation exposure.
Floppy DriveThe 3.5-inch internal floppy drive is on the I/O side. The systems have a
front mounted external floppy drive option and a front mounted
floppy/keyboard access option. Do not order the unit with an internal floppy
drive if you want to use these options.
Expansion SlotsThere are six slots available: five ISA slots, one PCI bus expansion slot or
four ISA, and two PCI bus expansion slots. Note: If the optional Ethernet
card is installed, only five slots are available.
Ethernet Port (optional)The Ethernet port provides a 10BASE-T/100BASE-TX auto sensing
Ethernet connection.
17
3500 Series Flat Panel Industrial PC
Back Panel
Figure 3-5 illustrates the system’s back panel.
SAFETY
RETENTION
SCREW (4)
LID
LID LATCH (2)
MOUNTING
STUD (14)
BACK PANEL
If your system has a touchscreen, keypad, keypad LED, or mouse cable,
disconnect the cable(s) from the CPU board before removing the back of
the unit from the front bezel.
To remove the lid, lift the two latches along the top of the back panel.
To remove the front panel, use a Phillips-head screwdriver and remove the four screws
located in the top and bottom corners (refer to Figure 3-5).
Bottom Panel
The features on the bottom panel are listed below.
FeatureDescription
Product ID Label
Vent and FilterThe bottom of the unit contains a vent and filter for circulation. This
Figure 3-5. Back Panel
Note
The product ID label is located on the back panel. This label contains
the model number and serial number of the unit.
aids in the cooling of the internal components.
18
Power Panel
Chapter Three - Installation
EXHAUS T
FAN
VENT
FILTER
(on botto m)
MONITOR
AUXILIAR Y
OUTLET
POWER
RECEPTACLE
RETAINER
BRACKET
MOUNTING
STUD (2)
FRONT
PANEL
EXHAUST
FAN
VENT
FILTER
(on bottom)
100-120V~ 3A MA X .
200-240V~ 2A MA X .
50/60Hz
Figure 3-6. Unit with AC Power Supply
LID
LATCH (2)
(on back)
LID
(on top)
FAN
FILTER
RETENTION
SCREW (2)
MOUNTING
STUD (14)
LID
LATC H (2)
(on back)
LID
(on top)
DC POWER
STRIP
+24VDC
0VDC
CHASSIS
GROUND
RETAINER
BRACKET
MOUNTING
STUD (2)
FRONT
PANEL
FAN
FILTER
+24 0V
RETENTION
SCREW (2)
MOUNTING
STUD (14)
Figure 3-7. Unit with DC Power Supply
19
3500 Series Flat Panel Industrial PC
FeatureDescription
Power ReceptacleThe AC power receptacle is a three-pin connector on the left side of
the unit; the DC power supply uses a terminal block.
Monitor Auxiliary Power OutletThe outlet is intended for use only in testing situations, outside haz-
ardous locations, and is covered by a retainer bracket for safety reasons. Note: A flat panel display and a CRT cannot be used simulta-
neously on a display. Simultaneous video is only available on TFT
systems with the “Simultaneous Video” utility program, or configured
in the BIOS setup menus..
Retainer Bracket (AC) or PClamp (DC)
Fan and FilterThe fan and filter, located on the left side panel, are cooling system
Exhaust FanThe exhaust fan is a cooling system component.
Vent FilterThe vent and filter is a cooling system component to allow air to circulate.
With an AC power supply, this bracket can be screwed into the two
studs, as shown in 3-21, to retain the power connector and to cover
the Monitor Auxiliary outlet. If an optional DC power supply is installed,
use the P-Clamp to provide power cord strain relief.
Warning: Absence of this bracket may result in a disengaged
power connector. If this occurs, an explosion may result in a
hazardous environment.
components. The filter is replaceable and can be removed for cleaning.
Installation Options
This section describes how to install internal and external hardware options.
Internal Hardware Options
Turn off the unit and remove power before installing internal hardware.
To install internal hardware options unlatch and remove the lid.
SDRAM and Additional SDRAM Dual In-Line Memory Modules
(DIMMs)
You can order your unit CPU factory-configured for many configurations of SDRAM.
You can reconfigure the SDRAM capacity by changing the SDRAM DIMMs on your
board. For more information, refer to the CPU manual.
PC/AT or PCI Boards
1. Check that the memory and I/O configuration of the board you want to install do not
conflict with the CPU and I/O memory maps in your CPU board manual.
Caution
2. Using the two latches, remove the lid.
3. Remove the ORB screw and blank ORB from the desired track.
20
Chapter Three - Installation
4. Slide the PC/AT or PCI expansion board into a corresponding rail.
5. Push the board into the backplane connectors.
Note
Do not force the boards or apply uneven pressure.
6. Secure the board by installing the screw through the hole in the board’s metal ORB
and into the top of the track.
7. Replace and relatch the lid.
Caution
On Pentium II equipped units, do not block the CPU fan when installing
a card in the slot closest to the processor. The processor may overheat.
External Hardware Options
The 3515 and 3512KPM supports front access to keyboard and floppy drive connectors
with the 9000-FKA kit and front access to an externally mounted floppy drive with the
9000-FFK kit.
To maintain a safe condition, do not use an external keyboard or mouse or
USB port devices when the unit is operating in a hazardous environment.
Externally Mounted Floppy Drive
The connector for the external floppy is mounted in the location of the internal floppy
bay. Since the 3515/3512KPM supports one floppy drive, you cannot use the external
floppy option if the unit has an internal floppy drive.
The floppy drive access door is provided for installations using the filler with cutout, or
panel mount installations that provide a cutout for the front mounted floppy drive. See
Figure 3-8 for cutout dimensions.
Make sure the floppy drive cable reaches the floppy connector on the
unit before making the cutout.
Warning
Note
21
3500 Series Flat Panel Industrial PC
Figure 3-8. Front Mounted Floppy Cutout Dimensions
Mount the floppy drive access door to the filler plate or the panel, using the four mounting nuts as shown in Figure 3-9. Torque the nuts to 35 in/lb. (3.95 Newton Meters).
Figure 3-9. Floppy Drive - Front Mounting Option
Figure 3-10 shows an overhead view of the Front Floppy Kit with the floppy drive
mounted into the rack.
Note
Do not attach the drive with a disk installed to avoid corrupting a disk
when using the external floppy drive.
22
Chapter Three - Installation
Figure 3-10. Floppy Drive - Front Mounting Option (top view)
Front Access Keyboard and Floppy Connectors
You can access these keyboard and floppy drive connectors with the 9000-FKA kit in
installations that provide a cutout for the front mounted connections, you must install
the 9000-FKA kit. The kit’s keyboard cable connects to a PS/2 stacked mini-din located on the side of the unit. The floppy drive cable connects to a port mounted in the
internal floppy bay. Since the 3500 series only supports one floppy drive, you cannot
use the external floppy option if the unit has an internal floppy drive. See Figure 3-11
for cutout dimensions.
Note
Make sure the keyboard and floppy drive cables reach the ports on the
unit before making the cutout.
23
3500 Series Flat Panel Industrial PC
Figure 3-11. Front Mounted Connectors Cutout Dimensions
Mount the front floppy and keyboard access kit to the plate or the panel as shown (3-12).
Torque the nuts to 35 in/lb. (3.95 Newton Meters).
Figure 3-12. Front Floppy and Keyboard Access Option
The 3500 series supports one floppy drive. If you want to use the floppy
drive connector, the unit cannot have an internal floppy drive. (The external floppy’s connector is mounted in the internal floppy bay.)
24
Note
Serial AUX
If an auxiliary device is used, the ferrite included in the documentation kit must be installed to maintain CE compliance.
The AUX port is disabled when a touchscreen is factory installed.
Creating a Custom Logo
This section provides the necessary information to create a custom logo.
3515
After you create a label, remove the Xycom Automation label and place your custom
logo label in the pocket. Refer to Figure 3-13 for the dimensions and recommended requirements.
Chapter Three - Installation
Note
Figure 3-13. 3515 Logo Label Dimensions
3512KPM/3515KPM
After you create a label, remove the Xycom Automation label and place your custom
logo label in the pocket. Refer to Figure 3-14 for label dimensions.
Figure 3-14. 3512KPM/3515KPM Logo Label Dimensions
You can customize your keypad with keypad inserts. Refer to Figure 3-15 and Figure 316 for insert dimensions and installation.
Figure 3-15. Keypad Inserts with Dimensions (PF1 - PF20)
26
Chapter Three - Installation
Figure 3-16. Keypad Insert with Dimensions (F1 - F20)
Figure 3-15 provides information on positioning keypad inserts.
27
3500 Series Flat Panel Industrial PC
Figure 3-17. Keypad Insert Position
Installing Operating Systems
The system CPU comes with MS-DOS standard. The pre-installed operating systems are
provided in the following format:
Operating SystemsFormat
DOSDiskette
Windows 95CD ROM
Windows NTCD ROM
If you want to install a new operating system or re-install a current operating system, refer to the operating system’s manual for directions.
If you need to reinstall Windows NT system, you must have an internal
CD-ROM drive or an external parallel port CD-ROM drive as Windows
NT only ships on a CD-ROM disk.
28
Note
Installing Drivers
This section describes how to install the drivers associated with the 3500 series.
Ethernet Drivers
If Windows 95 or Windows NT 4.0 is pre-installed on your system and you ordered the
Ethernet card option, Ethernet drivers are installed on your hard drive in the C:\netdrv directory.
If you want to use Ethernet capabilities with Windows 95, your system
must have BIOS revision level 1.1 or higher.
If MS-DOS is installed on your system, the Ethernet drivers are supplied on your hard
drive in the C:\netdrv directory, but they are not installed.
To install the MS-DOS Ethernet drivers,
Chapter Three - Installation
Note
1. At the C: prompt, type “cd netdrv”.
2. Once the C:\netdrv path is specified, type “install”.
3. Follow the on-screen instructions to complete installation.
If you install Windows 3.1 on your system, Xycom Automation provides the Ethernet
drivers. They can be found on the Ethernet Drivers disk that ships with your system.
If you install Windows NT 4.0 or Windows 95 on your system , the
Ethernet drivers that are provided do not work with the Ethernet controller
installed. You must use the drivers provided by Xy com Automation. These
drivers can be found on the Ethernet Drivers disk that ships with your
system.
Consult the Info directory on the drivers disk for additional installation information.
Video Drivers
Video drivers for each operating system are on the diskettes included with the documentation kit. To install a video driver, refer to the INSTALL.TXT file on the diskette for
your operating system.
Note
29
3500 Series Flat Panel Industrial PC
Touchscreen Drivers
Depending upon the date of purchase, the Xycom Automation unit will have one of two
possible touchscreen controllers:
• The Microtouch Controller P/N 114084
• The Xycom ControllerP/N 140554
These controllers function similarly. However, the following sections require attention to
the type of controller installed.
Microtouch Controller
If the touchscreen is factory-installed, you will receive a disk with MSDOS and Windows 95 touchscreen drivers. If Windows 95 or Windows
NT is factory-installed, the touchscreen drivers are provided. If you
change the operating system, you must install the corresponding touchscreen driver software. Refer to the touchscreen manual for instructions.
Note
Xycom Controller
If the touchscreen is factory-installed, you will receive a CD with MSDOS and Windows touchscreen drivers. If Windows is factory-installed,
the touchscreen drivers are provided. If you change the operating system,
you must install the corresponding touchscreen driver software. Refer to
the touchscreen manual for instructions.
CD-ROM Drivers
A CD-ROM driver disk comes with the CD-ROM option, as well as the preinstalled
driver for the operating system you have selected. If you change operating systems and
need help loading the required CD-ROM driver, contact Xycom Automation technical
support at 1-800-289-9266 x450.
If the Windows or Windows NT operating system is factory installed, then
touchscreen is set up on COM2, making
this port unavailable.
If you need to reinstall Windows NT, you must have an internal CDROM drive or an external parallel port CD-ROM drive as Windows NT
only ships on a CD-ROM disk.
30
Note
Use of controls, adjustments or the performance of procedures other than
those specified herein may result in hazardous radiation exposure.
Miscellaneous Drivers
Refer to your operating system and peripheral manuals for information on installing
drivers related to these items.
Using a Touchscreen
The Xycom Automation touchscreen, based on resistive membrane technology, consists
of two layers with transparent, conductive coatings on the facing sides. Finger or stylus
pressure causes the outer layer to make electrical contact with the inner layer. Xycom
Automation’s touchscreen complies with environmental specifications and maintains a
NEMA 4 seal when panel mounted. It remains operational even after 30 million touches.
Chapter Three - Installation
Caution
The touchscreen interface module circuit impresses a voltage across the conductive
coatings. When the touchscreen is pressed the circuit converts from analog to x and y
digital coordinate positions and then passes the x and y codes to the installed touchscreen
driver. The touchscreen Monitor Mouse driver emulates a Microsoft pointer.
Note
Refer to the touchscreen manuals (included in the Documentation kit)
for complete driver installation details.
Depending upon the date of purchase, the Xycom Automation unit will have one of two
possible touchscreen controllers:
• The Microtouch Controller P/N 114084
• The Xycom ControllerP/N 140554
These controllers function similarly. However, the following sections require attention to
the type of controller installed.
Microtouch Controller
Note
If touchscreen is factory installed along with
MS-DOS, the touchscreen is set up on the AUX
port, making this port unavailable.
If the Windows 95 or Windows NT operating
system is factory installed, then touchscreen is
set up on COM2, making this port unavailable.
31
3500 Series Flat Panel Industrial PC
A
B
CO
J1
J2
JUMPERS
J3
J4
J5
If you want to reconfigure the touchscreen to use the COM2
port, perform the following steps:
1. Disconnect the power.
2. Remove the lid.
3. Remove the touchscreen controller card (see Figure 3-18A).
TCTRL1
1
TOUCHSCREEN
NTROL CONN.
Figure 3-18A. Touchscreen controller card
39
4. Reconfigure jumpers J1-J9. Position A = COM2. Position B
= PS/2 AUX. (Note: all jumpers must be in the A or B position).
5. Reinstall the touchscreen controller card.
6. Reboot the computer.
7. Using the touchscreen manual, do the following:
• Load the touchscreen drivers
• Reconfigure the touchscreen driver for COM@
• Recalibrate the touchscreen
8. Replace the lid.
Note
If you ordered Windows 95 or NT on your system, the COM2 port is not available.
32
Xycom Controller
A
CO
For VNHS with the AHIP6 board: If touchscreen is factory installed, the touchscreen is set
up on the AUX port, making this port unavailable.
If you want to reconfigure the touchscreen to use the COM2
port, perform the following steps:
1. Disconnect the power.
2. Remove the lid.
3. Remove the touchscreen controller card (see Figure 3-18B).
J1
J2
J3
J4
JUMPERS
J5
J7
J8
J9
Chapter Three - Installation
Note
B
2
1
TOUCH SCREEN
NTROL CONN.
Figure 3-18B. Touchscreen controller card
40
39
4. Reconfigure jumpers J1-J9. Position A = COM2. Position B
= PS/2 AUX. (Note: all jumpers must be in the A or B position).
5. Reinstall the touchscreen controller card.
6. Reboot the computer.
7. Using the touchscreen manual, do the following:
• Uninstall the UPDD Touch driver.
• Locate the Touch-Base Serial mode driver on the Xy-
com DOC CD.
• Follow the instructions on the readme.txt file for the se-
rial mode UPDD driver.
8. Replace the lid.
33
3500 Series Flat Panel Industrial PC
Specifying the Port
To reconfigure the touchscreen driver for COM2, uninstall the Universal Pointer Device
Driver (UPDD).
To reinstall UPDD for serial mode:
1. Locate the Xycom Documentation CD.
2. Search the CD for Touch-Base touch drivers.
3. Locate the Touch Serial Mode folder.
4. Follow the installation instructions in the readme.txt file
Calibrating the Touchscreen
Depending upon the date of purchase, the Xycom Automation unit will have one of two
possible touchscreen controllers:
• The Microtouch Controller P/N 114084
• The Xycom ControllerP/N 140554
These controllers function similarly. However, the following sections require attention to
the type of controller installed.
Microtouch Controller
If you need to recalibrate the touchscreen, refer to the sections in the touchscreen manual that explain calibrating the
touchscreen and using the diagnostic utility.
Note
The touchscreen and controller are a
matched pair calibrated at the factory.
Xycom Controller
If you need to recalibrate the touchscreen, run the Pointer
Devices Control Panel applet. Select Help for details about
calibrating. For best results, use the 25 point calibration
setting with Start In At set to 0.
You need to calibrate the touchscreen if
• The cursor does not follow the movement of your finger or pen
• You adjust the size of the video image or change the video mode
34
Video Expansion
This section deals with the hardware expansion capability of the video controller chip in
DOS applications.
It is not necessary to read this section if you are a Windows 95, Windows NT, or OS/2 user, do not plan to run DOS applications, and have
not modified the default expansion mode in the BIOS setup menus.
Unlike a CRT, a flat panel display has a fixed horizontal and vertical resolution. There
are many DOS video modes whose resolution is less than that of a flat panel display. To
more efficiently make use of the flat panel display’s active area, it is necessary to employ
an expansion technique that stretches the lower resolution information to fill the higher
resolution of the display. For example, DOS defaults to VGA video mode 3+. This is an
80 column, 25 row text only screen whose effective resolution is 640 dots x 400 scan
lines. Because of this, the 1024 x 768 display of the unit will be partially filled by the
640 x 400 resolution of this particular mode. By enabling the expansion function, these
lower resolutions will better utilize the display by stretching the information in an attempt to fill the display. Operating systems such as Microsoft Windows 3.X, Windows
95, and Windows NT use display drivers to handle the different flat panel displays. Expansion is not necessary since there is a specific driver for each resolution.
Chapter Three - Installation
Note
Expansion does not add any resolution to the existing information; it simply stretches the
information to better fit the display. Text and graphic screens can look somewhat grainy
after expansion.
You can turn expansion off in the BIOS setup menus, or by executing an included utility
program. See the table below for the three utility programs included to allow expansion
to be turned on, turned off, and set back to the BIOS default state and what effect they
have on the display.
Vert:Vertical only expansion is invoked
Vert/Hor:Vertical and Horizontal expansion is invoked
Expansion Default:The video BIOS default on power up
a
Text expansion cannot be turned off.
a
35
3500 Series Flat Panel Industrial PC
On a 1024 x 768 display, the stretching algorithm does not completely fill the display
horizontally or vertically. You can achieve a greater vertical text expansion by changing
to VGA mode 3* (see Note below). This is an 80 column, 25 row text mode with an effective resolution of 640 x 350. The 350 lines stretch better to fill the 768 line display.
The utility disk includes the MOD3_350.EXE utility, allowing you to
switch to VGA mode 3*. The MOD3_400.EXE utility allows you to
change the mode back to the DOS default of 3+.
Windows may come up with a blank screen when using Windows 3.X on a unit, with expansion turned on either through the BIOS setup m enus or using the E XP_ON .EXE utility .
There are two available options (second option being the best) to resolve this situation:
Note
• Press the
press any key to return to Windows. The Windows screen should appear.
• Turn off the expansion.
• Default to factory settings in the BIOS setup menus.
• Use the appropriate utility as shown in the Video Expansion Options table.
For further assistance, call Xycom Automation technical support at 1800-289-9266.
CTRL-ALT-DEL keys simultaneously. When the Windows message appears,
Mounting Considerations
This section describes issues you must address before placing the unit inside an enclosure.
Consider the following points and precautions:
• Select an enclosure and place the unit to allow easy access to the ports.
• Account for the unit’s depth when choosing the depth of the enclosure.
• Provide a NEMA 4 seal by mounting the unit in an approved enclosure with a 14
gauge (0.075"/1.9mm thick) steel or (0.125"/3.2mm thick) aluminum front face.
• Mount the unit in an upright position.
• Place the unit at a comfortable working level.
• Consider locations of accessories such as AC power outlets and lighting (interior
lighting and windows) for installation and maintenance convenience.
• Prevent condensation by installing a thermostat-controlled heater or air conditioner.
• To allow for maximum cooling, avoid obstructing the airflow.
• Place any fans or blowers close to the heat generating devices. If using a fan, ensure
that outside air is not brought inside the enclosure unless a fabric or other reliable
filter is used. This filtration prevents conductive particles or other harmful contaminants from entering the enclosure.
Note
36
Enclosures
Chapter Three - Installation
• Do not select a location near equipment that generates excessive electromagnetic in-
terference (EMI) or radio frequency interface (RFI) (equipment such as high power
welding machines, induction heating equipment and large motor starters).
• Place incoming power line devices (such as isolation or constant voltage transform-
ers, local power disconnects, and surge suppressers) away from the unit.
• The proper location of incoming line devices keeps power wire runs as short as pos-
sible and minimizes electrical noise transmitted to the unit.
• Make sure the location does not exceed the unit’s shock, vibration, and temperature
specifications.
• Install in the panel in such a way as to ensure that it does not cause a hazard from
uneven mechanical loading.
• Avoid overloading the supply circuit
The systems are designed for installation within a clean and dry enclosure for both ordinary and hazardous locations. The front panel meets the requirements for Type 4, 4X,
and 12 enclosures. The enclosure used for Class I hazardous locations should have a
minimum rating of Type 12 (NEMA 12, IP 5X). However, Type 4 (IP 6X) enclosures are
strongly recommended.
The floppy disk/keyboard port access door must be closed and latched at
all times to maintain a proper seal against water and dust.
Panel flatness and rigidity are important to maintain a proper panel seal. If you are using
non-metal type enclosures, such as plastic or fiberglass, install a rigid metal stiffener behind the front panel. Failure to do so may result in an inadequate panel seal due to flexure of the front panel material between the stud mounts. Tighten the nuts on the mounting studs to 25-inch pounds.
The requirements for enclosure fittings, conduit, and wiring vary according to the specific rating of the location and the type of flammable or combustible material involved.
Those requirements are beyond the scope of this document and it is the responsibility of
the customer to ensure that their installation is compliant with codes and regulations that
apply to their specific location. Reference NFPA 70, Article 500 for specific regulations
in the United States.
System Power
On the average, the temperature within the system is 7-10°C higher than that outside the
enclosure. When the ambient (exterior) temperature reaches 42°C, the system’s power
supply will begin to derate at a rate of 3.25 watts per increase of 1°C.
Warning
The unit is rated to work at temperatures up to 50°C (at 50ºC, no more than 100 watts of
expansion can be added to the system).
Refer to the table below for more information.
37
3500 Series Flat Panel Industrial PC
VoltageAvailable Current
AHIP6+
+3.3 VDC10.6A
+5 VDC10.6A
+12 VDC4.88A
-12 VDC0.76A
-5 VDC0.50A
a
Total expansion power not to exceed 100 watts
b
Combined 3.3V and 5V expansion is 10.6A
a
b
b
It is a good idea to use isolation transformers on the system’s incoming AC power line. An
isolation transformer is especially desirable in cases where heavy equipment is likely to introduce noise onto the AC line. The isolation transformer can also serve as a step-down
transformer to reduce incoming line v oltag e to a desired lev el. The transform er should have
a sufficient power rating (units of volt-am peres) to supply the load adequately .
Proper grounding is essential to all safe electrical installations. Refer to the relevant Federal, State, Provincial, and local electric codes which provide data such as the size and
types of conductors, color codes and connections necessary for safe grounding of electrical components. The code specifies that a grounding path must be permanent (no solder),
continuous, and able to safely conduct the ground-fault current in the system with minimal impedance (minimum wire required is 18 Awg, 1 mm).
Observe the following practices:
• Separate ground wires (P.E. or Protective Earth) from power wires at the point of
entry to the enclosure. To minimize the ground wire length within the enclosure, locate the ground reference point near the point of entry for the plant power supply.
• All electrical racks or chassis and machine elements should be Earth Grounded in in-
stallations where high levels of electrical noise are expected. Ground the chassis
with a ground rod or attach to a nearby Earth structure such as a steel support beam.
Each different apparatus should be connected to a single Earth Ground point in a
“star” configuration with low impedance cable. Scrape away paint and other nonconductive material from the area where a chassis makes contact with the enclosure.
In addition to the ground connection made through the mounting bolt or stud, use a
one-inch metal braid or size #8 AWG wire to connect between each chassis and the
enclosure at the mounting bolt or stud.
Excessive Heat
The system withstands operating temperatures from 0º to 50º C (32º to 122º F). To keep
the temperature in the specified range, the air at the base of the system must not exceed
50°C. Allocate proper spacing between internal components installed in the enclosure.
When the air temperature is higher than 50ºC in the enclosure use a fan or air conditioner.
38
Electrical Noise
Electrical noise is seldom responsible for damaging components, unless extremely high
energy or high voltage levels are present. However, noise can cause temporary malfunctions that can result in hazardous machine operation in certain applications. Noise may
be present at certain times, may appear between widely spread intervals, or in some
cases, may exist continuously.
Noise commonly enters through input, output, and power supply lines and may also be
coupled through the capacitance between these lines and the noise signal carrier lines. This
usually results from the presence of high voltage or long, close-spaced conductors. When
control lines are closely spaced with lines carrying large currents, the coupling of magnetic
fields can also occur. Use shielded cables to help minimize noise. Potential noise generators include switching components, relays, solenoids, m otors, and motor starters.
Refer to the relevant Federal, State, Provincial, and local electric codes. These codes
provide data such as the size and types of conductors, color codes and connections necessary for safe grounding of electrical components. It is recommended that the high voltage and low voltage cabling be separated and dressed apart. In particular, the AC cables
and switch wiring should not be in the same conduit with all communication cables.
Chapter Three - Installation
Line Voltage Variation
The unit’s power supply is built to operate with output voltage ranges of 100-120 VAC
and 200-240 VAC with an AC power supply and 19-30 VDC with a DC power supply,
and still allow the system to function within its operating margin. As long as the incoming voltage is adequate, the power supply provides all the logic voltages necessary to
support the processor, memory, and I/O.
In cases in which the installation is subject to unusual AC line variations, use a constant
voltage transformer to prevent the system from shutting down too often. However, a first
step toward the solution of the line variations is to correct any possible feed problem in
the distribution system. If this correction does not solve the problem, use a constant voltage transformer.
The constant voltage transformer stabilizes the input voltage to the unit by compensating
for voltage changes at the primary in order to maintain a steady voltage at the secondary.
When using a constant voltage transformer, check that the power rating is sufficient to
supply the system.
Creating a Power Cable
This section describes how to create both an AC and a DC power cable.
AC Power Cable
A power cable must be created to supply power to the unit. The materials needed are:
• A three-position power connector (supplied)
• A braid/foil shielded power cable, terminated at power source end, with three 18 (1.0
mm), 16 (1.3 mm), or 14 (1.6 mm) Awg solid or stranded copper wires, rated 80ºC or
better
39
3500 Series Flat Panel Industrial PC
Perform the following steps to create and attach the cable:
1. Cut wire cable to the desired length.
2. Strip 0.25-inch (6 mm) of insulation from the end of the conductor wire. No bare
wire should be exposed when the cable is connected to the workstation.
3. Tin the wire ends with solder if using stranded wire. This will keep the wire
from fraying.
Figure 3-19. 3515 AC Power Connector.
Warning
When inserting the wire ends of the power cable into the block plug, be
sure there is no exposed wire. Trim the wire ends of the cable or cut a
new cable if necessary.
Figure 3-20. Internal View of 3515 AC Power Connector
4. Insert the three wire ends of the power cable into the hole of the connector plug.
Bend the Protective Earth ground (PE) wire, the neutral (N) wire, and the line (L)
wire around the corresponding screw. Be sure that no bare wires are exposed.
5. Tighten the three screws above the wires to hold them firmly in place.
Never tighten the three screws of the block plug when the cable is connected to a power source. The screws are conductive and have full contact with the cable wire.
40
Warning
Chapter Three - Installation
6. Use the screw provided to secure and strain-relief the power cable inside the con-
nector. Plug the power cable into the power supply located on the side of the unit.
7. Once the power cable and other optional interface cables are installed, installation
is complete.
Note
When disconnecting the power cord from the unit, be sure to completely
loosen the two securing screws on the retainer bracket.
Cable Retainer Bracket
Once you have created the power cable, attach the retainer bracket that secures the cable
connector to the unit. You must use this retainer bracket in hazardous locations.
Warning
Absence of this bracket can allow a power connector to become disengaged. An explosion could result if this occurs in the presence of a hazardous environment.
1. Plug the completed cable into the system’s power supply.
2. Place the retainer bracket over the connector so that the shorter sides wrap around
the connector and the screw holes on the large flange line up with those on the case.
3. Insert the two 6-32 screws and tighten to the standard torque (11-in/lb).
Figure 3-21. 3515/3512KPM Cable Retainer Bracket
Warning
The connector retainer bracket must be placed around the cable connector and screwed into the 3515/3512KPM case.
Mounting the Unit
The system’s rugged design allows it to be installed in most industrial environments. The
unit is generally placed in a NEMA 4/4X/12 enclosure to protect against contaminants
41
3500 Series Flat Panel Industrial PC
such as dust, moisture, etc. Metal enclosures also help minimize the effects of electromagnetic radiation that may be generated by nearby equipment.
Once the conditions in the preceding sections have been met, follow the instructions below to
mount the unit:
1. Locate a position for your system that meets the specifications required (see previous
sections and Appendix A).
2. Cut the hole according to the cutout dimensions in Figure 3-22.
3. Make sure the area around the cutout is clean and free from metal burrs.
4. Install the unit.
5. Attach the power cable making sure that the 3515/3512KPM enclosure is grounded
through the power cable.
6. On a system with an AC power supply, attach the connector retainer bracket; on a system
with a DC power supply, attach the aluminum p-clamp.
7. Implement the proper grounding techniques. Establish a ground path from the
3515/3512KPM chassis to the enclosure chassis. A 6-32 threaded ground point (
is provided on the left back of the front panel (as viewed from the front) of the unit.
There is also an internal ground point (
) hole
).
8. Tighten the 14-#10 nuts to 27 inch pounds (3.0456 Newton-meters).
If you use the CD-ROM, use of controls, adjustments, or the performance of procedures other than those specified herein, may result in hazardous radiation exposure.
System Cutout Dimensions
Caution
42
Figure 3-22. System Cutout Dimensions
Hazardous Locations Installations
Xycom Automation designed the systems with the intention of meeting the requirements
of Class I, Division 2 Hazardous Locations applications. Division 2 locations are those
locations that are normally non-hazardous, but potentially hazardous should an accident
expose the area to flammable vapors, gases or combustible dusts.
These systems are non-incendiary dev ices. They are not intrinsically safe and should never
be operated within a Division 1 (normally hazardous) location when installed as described
here. Nor should any peripheral interface device attached to these system s be located within
Division 1 locations unless approved and/or certified diode barriers are placed in series
with each individual signal and DC power line. Any such installations are beyond the
bounds of Xycom Automation design intent. Xycom Automation accepts no responsibility
for installations of this equipment or any devices attached to this equipment in Division 1
locations.
Note
It is the customer’s responsibility when adding additional cards that they
meet operating conditions for Class I, Division 2 hazardous locations.
Chapter Three - Installation
It is the responsibility of the customer to ensure that the product is properly rated for the
location. If the intended location does not presently have a Class, Division, and Group
rating, then users should consult the appropriate authorities having jurisdiction in order
to determine the correct rating for that Hazardous Location.
In accordance with Federal, State/Provincial, and Local regulations, all hazardous location installations should be inspected by the appropriate authority having jurisdiction
prior to use. Only technically qualified personnel should install, service, and inspect
these systems.
Warning
Suitable for use in Class I, Division 2 Groups A, B, C, and D, and Class
II, Division 2, Groups F and G hazardous locations or non-hazardous locations only.
Warning - Explosion Hazard
Substitution of components may impair suitability for Class I, Class II,
Division 2.
Advertissement Risque D’ Explosion
La substitution de composants peut rendre ce materiel inacceptable pour
les emplamements de classe I, II, Division 2.
43
3500 Series Flat Panel Industrial PC
Do not disconnect equipment unless the power has been switched off or
the area is known to be non-hazardous.
Advertissement Risque D’ Explosion
Avant de deconnecter l’equipment, coupler le courant ou s’assurer que
l’emplacement est designe non dangereux.
When in hazardous locations, turn off power before replacing or wiring
modules.
Advertissement Risque D’ Explosion
Dans les situations hasardees, couper la courant avant de remplacer ou
de cabler les modules.
Warning - Explosion Hazard
Warning - Explosion Hazard
Definitions
Warning
To maintain a safe condition, do not use an external keyboard or mouse or
USB port devices when the unit is operating in a hazardous environment.
The following Class and Division explanations are derived from Article 500 (Sections 5
and 6) of the United States National Fire Protection Agency National Electric Code
(NFPA 70, 1990). They are not complete and are included here only for a general description for those not familiar with generic hazardous locations’ requirements.
Persons responsible for the installation of this equipment in Hazardous Locations are responsible for ensuring that all relevant codes and regulations related to location rating,
enclosure, and wiring are met.
Class I Locations
Class I locations are those in which flammable gases or vapors are or may be present in
the air in quantities sufficient to produce explosive or ignitable mixtures.
Class II Locations
Class II locations are those that are, or may become, hazardous because of the presence
of combustible dust.
44
Chapter Three - Installation
Division 1 Locations
A Division 1 location is one in which flammable or ignitable gasses, vapors, or combustible dusts and particles can exist due the following conditions:
• Normal operating conditions.
• Because of repair, maintenance conditions, leakage, or where mechanical failure or
abnormal operation of machinery or equipment might release or cause explosive or
ignitable mixtures to be released or produced.
• Combustible dusts of an electrically conductive nature may be present in hazardous
quantities.
Note
Xycom Automation 3515/3512KPM systems are not suitable for installation within Division 1 locations.
Note
Electrical equipment cannot be installed in Division 1 locations unless
they are intrinsically safe, installed inside approved explosion-proof enclosures, or installed inside approved purged and pressurized enclosures.
Division 2 Locations
• Class I volatile flammable liquids or flammable gasses are handled, processed, or
used, but confined within closed containers or closed systems from which they can
escape only in cases of accidental rupture or breakdown of such enclosures or systems, or in case of abnormal operation of equipment.
• Ignitable concentrations of Class I vapors or gasses are normally prevented by posi-
tive mechanical ventilation, but which may become hazardous due to mechanical
failure of those ventilation systems.
• Location is adjacent to a Division 1 location.
• Class II combustible dust is not normally in the air in quantities sufficient to produce
explosive or ignitable mixtures. Dust accumulations are normally insufficient to interfere with normal operation of electrical equipment or other apparatus. Combustible dust may be in suspension in the air as a result of the following: infrequent malfunctioning of handling or processing equipment; combustible dust accumulations
on, or in the vicinity of electrical equipment; may be ignitable by abnormal operation
or failure of electrical equipment.
Groups
All electrical equipment that is approved for use in hazardous locations must include a
group rating. Various flammable and combustible substances are divided into these
groups as a function of their individual maximum experimental safe gap (MESG), explosion pressure, and ignition temperature.
Component temperatures and the potential for spark based upon voltage, current, and
circuit characteristics, within electrical equipment, will determine what the equipment
45
3500 Series Flat Panel Industrial PC
group rating will be. A device approved for installation within Class I, Group A locations
may also be used in Groups B, C, or D.
Approved Class I equipment may not be suitable for Class II installations. Class I includes Groups A, B, C, and D. Class II includes Groups
F, and G.
Power Sw itch
The systems do not have a power switch. The amount of input power required by these
systems classifies a power switch as an incendiary device because the voltage and current across the make/break device are capable of creating a spark.
Hazardous locations’ regulations require that a power switch rated for ordinary locations
may be used if it is located in an area specified as non-hazardous. However, limits in cable length between the workstation and the power switch may apply. Otherwise the
switch must be compliant with Class I, Division 1 requirements (intrinsically safe).
These switches are built in a manner that prevents the possibility of a spark when contacts are made or broken.
Note
Use suitable UL listed and/or CSA Certified Class I, Division 1 switches in hazardous
locations. These switches are available from a wide number of sources. It is the responsibility of the customer to ensure that the power switch selected for their installation has
the correct hazardous locations rating for the location in which it is installed.
Cable Connections
Division 2 hazardous locations’ regulations require that all cable connections be provided with adequate strain relief and positive interlock. USB connections can never be
used in hazardous location installations, because USB connectors do not provide adequate strain relief. Never connect or disconnect a cable while power is applied at either
end of the cable.
All communication cables should include a chassis ground shield. This shield should include both copper braid and aluminum foil. The D-sub style connector housing should be
a metal conductive type (e.g., molded zinc) and the ground shield braid should be well
terminated directly to the connector housing. Do not use a shield drain wire.
The outer diameter of the cable must be suited to the inner diameter of the cable connector strain relief in order to ensure that a reliable degree of strain relief is maintained.
Always secure the D-Sub connectors to the 3515/3512KPM workstation-mating connectors via the two screws located on both sides.
Warning
Never connect or disconnect the communication cables while power is
applied at either end of the cable. This may result in an incendiary spark.
Permanent damage to the workstation communication components may
occur.
46
Operation and Maintenance
The systems have been designed for compliance with relevant spark ignition tests. However, please note that the workstation front panel contrast adjustment tactile switches and
keyboard connector are the only make/break components intended to be exercised by the
operator in the course of normal operation.
To maintain a safe condition, never use an external keyboard or m ouse or
USB port devices when the unit is operating in a hazardous environment.
Always observe the following rules with respect to hazardous location installations:
1. Always install the workstations within an enclosure suitable for the specific applica-
tion. General-purpose enclosures may be acceptable for Class I applications but are
never acceptable for Class II applications. Type 4 (IP 65) enclosures are recommended even when not required by regulations.
2. If present, keep enclosure doors or openings closed at all times, to avoid the accu-
mulation of foreign matter inside the workstation.
Chapter Three - Installation
Warning
3. Never subject the unit to any installation or service procedures unless power is re-
moved and the area is known to be non-hazardous. This includes the installation or
removal of power cables, communication cables, or removal of the rear cover of the
unit.
Only technically qualified service personnel should perform all installation and service.
These workstations are designed to require no service in the course of normal operation
by an operator.
Safety A gency A pprov al
The Xycom Automation systems are designed to meet the following standards:
• Underwriters Laboratories Inc., UL 1604 Standard for Safety
Electrical equipment for use in Class I and Class II, Division 2, locations
• Underwriters Laboratories Inc., UL 1950, Information Technology Equipment
• Canadian Standard Association, Specification C22.2 No. 213-M1987
Non-incendiary electrical equipment for use in Class I, Division 2 hazardous locations
• Canadian Standards Association, Specification C22.2 No. 950
Information Technology Equipment
• EN 60950, Information Technology Equipment
47
3500 Series Flat Panel Industrial PC
Chapter Four – Keypad Utility Program
The Keypad Utility lets users redefine all keypad keys with new scan codes using utility
software. Use an external full-stroke PC/AT keyboard to access the utility (you cannot
redefine the keyboard).
Note
The keypad switch arrays are disabled while the k ey pad utility is running.
Loading the Keypad Utility
Note
You need MS-DOS 3.2 or higher to run the keypad utility. It will not
work if you are running Windows 95 or Windows NT. However, the
keypad utility will run under Windows 95 in DOS mode.
You can run this utility directly from the disk or copy it onto your hard drive. To run the
keypad utility from the disk, change the directory to the appropriate drive and type
kputil. To load the utility onto your hard drive, create a subdirectory for the files, and
copy all the files on the disk into that subdirectory. Enter the subdirectory and type
kputil.
Using the Keypad Utility
The keypad utility uses a menu bar and pull-down menu system. All menu bars are displayed across the top of the screen. “Xycom Automation KP Utility” and the current
menu titles are shown at the bottom of the screen (see Figure 4-1).
A full-stroke keyboard is needed to enter keystrokes while recording a new key macro,
editing an existing macro, and entering utility commands. You can redefine all keys on
the keypads. While the utility is running, the keypads are disabled.
Dialog boxes appear for user prompts and to display error and user advice messages.
Two keys allow you to exit the menus:
ESC moves to the previous menu or out of the utility from the Main Menu.
•
F1 returns to the current menu headings in some of the menus where Exit can be cho-
•
sen to exit this menu.
Keys specific to each menu are shown at the bottom of each screen.
48
Startup
Type kputil to run the full keypad utility.
Utility Batch Mode
You can also use a batch file to reprogram keypads. This feature is useful if you wish to
reprogram many units with customized keypad macros without having to enter the full
keypad utility for each unit. Once the full utility has been used to create and save keypad
macros, the files containing these macros can be included on a disk with the keypad utility and then used to reprogram other units from a batch file.
The command keypad filename runs the keypad utility batch mode. “Filename”
is the file containing the new keypad macros. The filename extension must be included.
For example, in a batch file, the command keypad def3512kpm.pkm would reprogram the keypad on the 3512KPM with default values for the numeric keypad. After
programming, the system will reboot.
Main Menu
Chapter Four–Keypad Utility Program
Figure 4-1 illustrates the Main Menu.
ExitFilesMacrosUploadDownloadUtilities
Xycom Automation KP Utility: MAIN L-Arrow, R-Arrow, Enter
Figure 4-1. Main Menu
Exit
Exit closes open files and exits the utility. ESC can also be used for this purpose and for
exiting the other menus.
49
3500 Series Flat Panel Industrial PC
Files Menu
You can save files containing keypad macro sets (a macro for each key) on disk, and then
loaded them into memory to view, edit, teach, or download to the keyboard controller.
Some of these files may be included in the utility package for use in reconfiguring the
keypads for different software packages, and as templates for defining completely new
keypad macro sets.
When you choose File, a pull-down menu will display the following choices: Open,
Close, Save, Save As, Delete, and Exit. The following table describes the menu commands.
CommandDescription
OpenOpens a file that contains a macro set for the keypad and loads the con-
CloseClears the macro set from memory and closes the file from which they
SaveCopies the macro set from memory back into its original file. The original
Save AsCreates a new file under the specified name and copies the macro set
DeleteDeletes a file.
ExitReturns to the Main Menu.
tents into memory. Any macro set in memory is overwritten. Once loaded,
the macro set is available to edit, view, teach, or download to the keyboard controller.
came.
file contents are overwritten.
from memory into it. For example, to define different sets of codes, save
each set under a different name and download the one you wish to use.
Macros Keypad Type Menu
When you select Macros, a pull down menu displays and provides the following choices:
Function Keys, Alpha Keys, and Exit. Also, another pull down menu displays the following choices once the Macros menu is chosen: Exit, View, Teach, and Edit.
You must have a macro file in memory before the Macros Menu is available. To load a macro file, open a file or upload macros.
CommandDescription
Function KeysSelects the function keys on the keypad to either view, edit, or teach.
Alpha KeysSelects the alpha keys on the keypad to either view, edit, or teach.
ExitReturns to the main menu.
Note
50
Chapter Four–Keypad Utility Program
Macros Edit Menu
CommandDescription
ExitReturns to the Main Menu.
ViewAllows you to view, but not edit, the macro for the selected key. When View is chosen,
the Exit option is displayed on the menu bar and a graphic representation of the chosen keypad is shown. Select Exit from the View Menu to return to the Macros Menu.
To select a key to view, use the arrow keys to position the cursor on the desired key
and press
displays each keycode as the keys it represents on the full-stroke keyboard. Special
labels are used for certain keys (e.g., Spc for space bar, UAr for up arrow, and bk for
the break code prefix). The code line is displayed in either Hex or decimal. There is a
one-to-one correspondence between the ASCII and code lines.
While viewing the macro, the menu bar displays two options: Exit and Hex/Decimal.
Exit returns to the View Menu, while Hex/Decimal toggles between displaying the
macro in hex or decimal format. When Hex is chosen, the keycodes are displayed as
hexadecimal value scan codes. When Decimal is chosen, the keycodes are displayed
as the decimal equivalent of the hex codes.
For example, the macro abc would be displayed as 1C F0 1C 32 F0 32 21 F0 21 in
hex, and 28 240 28 50 240 50 33 240 33 in decimal.
TeachAllows you to record up to 105 keystrokes in a macro. When selected, a graphic rep-
resentation of the keypad currently in memory displays. Menu bar choices are Exit,
ASCII/Hex/Decimal, and Click ON/OFF. Exit returns to the Macros menu.
ASCII/Hex/Decimal specifies the format to display the keystrokes as they are entered.
Default is ASCII. Click is not supported.
To select a key to define, use the arrow keys to position the cursor on the desired key
and press
ternal full-stroke keyboard in a macro assigned to the chosen key. As the keys are
entered, they are displayed using the chosen format.
to the Teach Menu, so you cannot record the
in a macro by using the editor. Changes made to the macros in the Teach Menu are
not programmed until you select Download.
ENTER. The macro is displayed as two lines: ASCII and code. The ASCII line
ENTER. After you select a key, the utility records every keystroke on the ex-
ESC stops recording and returns
ESC key. However, ESC can be included
CommandDescription
EditDisplays a graphic representation of the keypad in memory and a menu bar displaying
Exit, Click, and ON/OFF. Exit returns to the Macros menu. Click is not supported. To
select a key to edit, use the arrow keys to position the cursor on the desired key and
ENTER.
press
In edit mode, the macro is displayed as two lines. The top line (the edit line) displays
the macro in either hex or decimal format and is the line in which the editing takes
place. The bottom line displays the macro in ASCII format; it is not user configurable.
This line keeps track of which part of the macro you are editing, and is updated by the
utility as editing takes place.
The insert, delete, and cursor control keys are active for editing. When a key is selected from the Edit Macro option, the menu bar displays the following choices: Exit,
Cut, Copy, Paste, Codes, Hex/Decimal, and I/O (Insert/Overtype). The macro for the
chosen key is also displayed.
Cut deletes a sequence of scan codes from the macro. To select a section to cut:
1. Place the cursor on the first character to cut.
2. Press
3. Press
F1 and selectCUT.
ENTER. Cut should still be highlighted, but the cursor will appear on the Edit
line. Move the cursor on the last character to cut and press
ENTER.
51
3500 Series Flat Panel Industrial PC
The last character of every macro is the end of the macro (EOM) and cannot be deleted.
Copy copies a sequence of scan codes from the macro into memory. To select the
section to copy:
1. Place the cursor on the first character to copy. Press F1 and select Copy.
2. Press
3. Move the cursor on the last character to copy and press
The copied item does not appear on the screen until you select
Paste inserts a sequence of scan codes (which were saved in memory using Copy)
into the macro. To paste a sequence of scan codes that were previously copied, position the cursor where you want the text to appear and then press
then press
Codes section in this chapter for a complete code listing. Hex/Decimal toggles between displaying the scan codes in Hex and Decimal formats. Insert toggles between
insert and overtype mode.
ENTER. Copy should still be highlighted, but the cursor will appear on the
Edit line.
ENTER. Codes displays a table of keys and their scan codes in Hex. See the
Upload Menu
Use the Upload Menu to choose which data to load. Choices in this menu are: Combo
Keypad, Keypad Version, and Exit.
ENTER.
Paste.
F1. Select Paste and
CommandDescription
Combo KeypadCommands the keyboard controller to send its entire macro set for the keypad.
Keypad VersionCommands the keyboard controller to send its firmware revision number.
ExitReturns to the Main Menu.
Note
Only one macro set may reside in memory at one time.
A checksum will be calculated during transmission. If an error occurs, an error message
will display.
Download Menu
Note
When you select Download, any macro set previously programmed is
overwritten.
Download sends the set of keypad macros to the keyboard controller. The macro set must
reside in memory before it can be downloaded. A checksum is calculated during transmission and an error message displays if an error occurs.
52
As the macro is sent, the keyboard controller programs its non-volatile memory with the
new macros that become the new key definitions for the keypad. After programming the
system will reboot.
Utilities Menu
When Utilities is selected, a menu bar displays four choices: Func Lock ON, Func Lock
OFF, Clear EEPROM, and Exit.
CommandDescription
Func Lock ONNot available on the 3512KPM or 3515KPM.
Func Lock OFFNot available on the 3512KPM or 3515KPM.
Factory DefaultReprograms the keypad macros to the factory default settings. After
ExitReturns to the Main Menu.
Keypad Scan Codes
The utility’s default keypad keycodes are listed in the following table.
Chapter Four–Keypad Utility Program
completion, the system will reboot.
Default Keypad Keycodes
3512KPMF/A Key LED Off (Function Mode)F/A Key LED On (Alpha Mode)
3512KPMF/A Key LED Off (Function Mode)F/A Key LED On (Alpha Mode)
menu)
NOTES:
• F11-F20 = SHIFT F1-F10
• F21-F30 = CTRL F1-F10
• F31-F40 = ALT F1-F10
• END, LEFT START, and EXPLORE keys are only available for 3515KPM units.
Note
If you make any changes to your keypad and want to set it back to the
default settings, open the pkm file for your unit (e.g., 3512KPM.PKM
for 3512KPM” from the File/Open menu and then download it from the
download menu. Do not save any changes to the default files.
55
Chapter Five - Maintenance
The 3500 series was designed to withstand the harsh environment of the factory floor.
Routine maintenance can help keep your unit in good operating condition. Preventive
maintenance consists of several basic procedures that significantly reduce the chance of
system malfunction. Schedule preventive maintenance along with the regular equipment
maintenance to minimize downtime.
Preventive Maintenance
Following are preventive measures you can take:
• Clean the monitor screen using a nonresidue cleaner such a mild window cleaning
solution or CRT screen cleaner. Take care not to scratch or mar the screen face.
• Clean or change the fan filter periodically to ensure that the air circulating in the unit
is clean. Wash the filter with warm water and dish soap, and let it air dry. Do not
scrub the filter, and do not re-install it into the unit until it is completely dry.
• Base your maintenance schedule on the operating environment of the system (i.e., if
the area is dusty, you should schedule maintenance more often than if it is a dry,
clean area). Check the filter often to determine if it needs to be changed ahead of
schedule.
• Remove dust and dirt from PC components. If dust builds up on heat sinks and cir-
cuitry, an obstruction of heat dissipation could cause the unit to malfunction. If dust
reaches the electronic boards, a short circuit could occur.
• Check the connections to I/O modules, especially in environments where shock
could loosen the connections. Check to see that all plugs, sockets, terminal strips,
and module connections are secure.
• Remove unnecessary articles, such as drawings or manuals, from the unit. They can
obstruct air flow and create hot spots, which causes the system to malfunction.
• Do not place noise generating equipment near the 3515.
• Stock spare partsto minimize downtime resulting from part failure. The spare parts
stocked should be 10 percent of the number of each unit used. The main CPU cards
should have one spare each. Each power supply should have a back-up. In certain
applications where immediate operation of a failed system is required, you may need
to stock an entire spare computer module see figure 5-6, Spare Parts List.
• Replace the module with the correct type. If the new module solves the problem but
the failure recurs, check for inductive loads that may be generating voltage and current spikes and may require external suppression.
Chapter Five - Maintenance
Xycom Recommended Hard Drive Preventative Maintenance
Xycom Automation has recognized that hard drive failures may begin to increase an average of four to five years into the life of most computers used in industrial applications.
57
3500 Series Flat Panel Industrial PC
Therefore, it is our recommendation as a preventative maintenance measure that all hard
drives used in these types of applications be replaced before the four to five year time period to avoid any down time related to hard drive failure.
The purpose of this message is to merely bring this to our customer’s attention, to offer
alternative solutions, and to provide all of our customers with the excellent service they
deserve.
Any questions regarding this issue may be directed to our support center at
support@xycom.com.
Please note Xycom recommends frequent back ups of your hard drive, especially before beginning any
preventative maintenance procedures.
Fuse Replacement
The unit has no accessible fuse. Return the unit to Xycom Automation for fuse replacement.
Fan Filter Replacement
To change the fan filter, remove the grill and filter as illustrated in the figure below.
Clean or replace the filter and snap the assembly back into position.
Do not operate the unit without a fan filter. Dust build-up could cause
the unit to malfunction.
Figure 5-1. Fan Assembly
Caution
Chemical Compatibility
Certain combinations of chemical environments, temperature, and stress can adversely
affect parts made from thermoplastic resin. For this reason material that may come in
58
Chapter Five - Maintenance
contact with the unit should be carefully evaluated under end-use conditions for compatibility. You should also follow the use and compatibility recommendations of the
material manufacturer. The table below lists general, chemical compatibility guidelines.
Figure 5-2. Chemical Compatibility
Chemical ClassEffects
AcidsNo effect under most common conditions of concentration and
temperature.
AlcoholsGenerally compatible at low concentration and room
temperature. Higher concentrations and elevated
temperatures result in etching and attack evidenced by
decomposition.
AlkalisGenerally compatible at low concentration and room
temperature. Higher concentrations and elevated
temperatures result in etching and attack evidenced by
decomposition.
Aliphatic HydrocarbonsGenerally compatible
AminesSurface crystallization and chemical attack. Avoid.
Aromatic HydrocarbonsPartial solvents and severe stress cracking agents. Avoid.
Detergents and CleanersMild soap solutions are compatible. Strong alkaline materials
should be avoided.
EstersCauses severe crystallization. Partial solvents. Avoid.
Greases and
Oils
Halogenated
Hydrocarbons
KetonesCauses severe crystallization and stress cracking. Partial
Silicone Oil and GreasesGenerally compatible up to 85ºC (185º F). Some contain
Pure petroleum types generally compatible. Many additives
used with them are not compatible.
Solvents. Avoid.
solvents. Avoid.
aromatic hydrocarbons which should be avoided.
Compatible Lubricants
The following table lists known compatible lubricants and the manufacturer’s names. If
you want to use a lubricant that is not listed below, contact the appropriate manufacturer
for compatibility.
Figure 5-3. Compatible Lubricants
LubricantsManufacturer
DC® 230
Molykote® 33
Harmony® 68
Security® 68
Lubriplate®
Aero
Dow Corning
Midland, MI 48640
(800) 248-2345
Gulf Oil
Petroleum Prod. Dept.
Pittsburgh, PA 15230
(412) 655-6247
Fisher Bros. Refinery
129 Lockwood Street
Newark, NJ 07105
The following table lists known compatible cleaning agents. If you want to use a cleaning agent that is not listed below, contact the appropriate manufacturer for compatibility.
303 W. Lehigh Ave.
Philadelphia, PA 19133
(215) 666-4000
Wm. J Nye
P.O. Box G-927
New Bedford, MA 02742
(617) 966-6721
GE
Silicone Products
Waterford, NY 12188
(518) 237-3330
P.O. Box 2180
Houston, TX 77092
(713) 680-5712
Figure 5-4. 3515 Compatible Cleaning Agents
TypeAgents
AliphaticsHexane, Heptane, White Kerosene Mineral Spirits,
AlcoholsMethyl, Isopropyl and Isobutyl, 1 + 3 Denatured
Halogenated HydrocarbonsFreons TF & TE
Detergents and CleanersMild Soap and Water Solution, VM&P Naphtha
The above aliphatics, alcohols, and halogenated hydrocarbons should be used only for
wiping or short-term immersion (less than 10 minutes). If parts are immersed completely,
care should be taken to remove last traces of solvent by forced-air drying or rinsing in
hot water.
Noncompatible Cleaning Agents
The following cleaning agents are known to be detrimental to the unit.
Figure 5-5. 3515 Non-compatible Cleaning Agents
Petroleum Ethers (65º C boiling point).
Alcohol.
Fantastik®, Windex®, Joy®, Top Job®, Mr. Clean®,
Formula 409®.
Without touchsc reen
3512KPM Touchscreen Replacement
3515KPM Touchscreen Replacment
Drives
Hard Drive
6480 MB
Solid State (Flash) Drive
16 MB
24 MB
48 MB
3.5”, 1.44 Mbyte floppy drive
CD-ROM Drive
Bulb Replacement Kits
12.1" TFT (#LQ12S 4 1 )
15” TFT (#LQ15XO1W)
15” TFT (#LQ150X1DG16)
CPU Assembly
AHIP370 CPU board
300 MHz Celeron® processor
AHIP6+ CPU board
400 MHz Pentium II processor
450 MHz Pentium II processor
500 MHz Pentium III processor
CPU mounting kit
SDRAM
32 MB
64 MB
128 MB
256 MB
9000-RFC 19” Floppy Door Plate
Filter Media
Media Retainer
Input Power Connector
9000 Accessories
g
External Floppy Kit
9000-EXF
9000-FKA
9000-FFK
a
Consult factory for repair of 3512KPM front panels.
b
Includes touchscreen, front panel, c ont roller, and manual
c
Includes front panel and overlay only
dI
ncludes touchscreen, controller, and m anual
e
AHIP6+ board and processor must be ordered separately.
f
The CPU mounting kit is only required for Pentium III processors.
g
Do not order these accessories if the 3515 ships with an internal floppy.
a
b
c
d
d
132566-001
132579-001
135162-001
139963-001
109456-005
139556-001
139557-001
139558-001
139964-001
139806-001
125155-001
132581-001
139965-001
e
e
139966-001
139785-001
139797-001
139786-001
f
f
139787-001
139967-001
139968-001
139798-001
139788-001
139799-001
139801-001
g
110843-001
110383
110650
139807-001
116074-001
116087-001
116061-001
61
3500 Series Flat Panel Industrial PC
roduct Repair Program/Returning a Unit to Xycom
Automation
Xycom Automation’s Product Repair & Custom ization Departm ent (PR& C) restores equipment to normal operating condition and im plem ents engineering changes that enhance operating specifications. Xycom Automation tests products returned to Xy com with the standard
Xycom Automation test diagnostics.
Follow the steps below to prepare the unit for shipment:
1. Obtain an RMA number for your unit by calling Xycom Autom ation headquarters, Prod-
uct Repair Department at 1-800-289- 9266 or 734- 429- 4971. Have the following inform ation ready:
• Company name, shipping and billing address.
• Type of service desired product repair or product exchange.
• Product model number, part number, quantity, serial number(s) (used to deter-
mine warranty).
• Failure mode and failure systems.
• Purchase order number or repair order number. No product out of warranty
will be returned without a purchase order number.
2. Make sure the front panel assembly is properly attached to the unit.
3. Attach failure information to the unit to speed processing.
4. Place the unit securely in its original packaging or an equivalent heavy-duty box.
5. Mark the RMA number on your purchase order and on the outside of the box.
6. Send the unit to your local Xycom Automation repair center.
62
Appendix A – Technical Specifications
Appendix A – Technical Specifications
Hardware Specifications
Figure A- 1. Hardware Specifications
CharacteristicSpecification
Mechanical
Height
Width
Depth (Mounting Depth)
Weight
Electrical
Power Supply200 watts
Available Power
Passive BackplaneSix full length expansion slots:
MountingPanel Mount or 19" rack mount
Flat Panels12.1" TFT SVGA color display (800 x 600) (3512KPM)
Agency ApprovalsUL1950 and 1604
Regulatory ComplianceCE:EMIEN55022: 1994 Cl ass A
a
Total expansion power not to exceed 100 watts
b
Combined 3.3V and 5V is 10.6A
AC115-230 VAC50-60 Hz6.3A autosensing
a
14.2"
19"
9.75" (9.00”)
42 lbs
+3.3 VDC10.6A
+5 VDC10.6A
+12 VDC4. 88A
-12 VDC0. 76A
-5 VDC0. 50A
Five ISA slots
One PCI bus expansion slot or four ISA
Two PCI bus expansion slot (maximum 4.8” length with AHIP6+)
Note: Only five slots are avail abl e i f the optional Ethernet card is ins talled.
15” TFT XGA color display (1024 x 768) (3515, 3515KPM)
CULC22.2, No. 950 and 213
IMMUNITYEN50082-2:1995
SAFETY E N60950
FCC47 CFR. Part 15, Class A
b
b
Environmental Specifications
CharacteristicSpecification
Temperature
Operating
Nonoperating
Humidity
Operating
Nonoperating
Figure A- 2. Environmental Specifications
0° to 50° C (32° to 122° F)
-20° to 60°C (-4° to 140°F)
20% to 80% RH noncondensing
20% to 80% RH noncondensing
1-
63
3500 Series Flat Panel Industrial PC
Altitude
Operating
Nonoperating
Vibration*
Operating
Nonoperating
a
Shock
Operating
a
These values are with solid state hard dri ves and not rotating media drives.
Nonoperating
CD-ROM and standard hard disk drives should not be used in applications where high levels of shock and vibration are present.
Sea level to 10,000 feet (3048 m)
Sea level to 40,000 feet (12192 m)
5-55 Hz
0.006” peak to peak displacement
56-2000 Hz
1.0g maximum acc el eration
5-55 Hz
0.006” peak-to-peak displacement
56-2000 Hz
2.5 g maximum acc el eration
15g peak acceleration, 11 m sec duration
30g peak acceleration, 11 m sec duration
Note
If a CD-ROM drive is installed, the shock and vibration specifications of
the unit are limited to the shock and vibration specifications of the CDROM drive.
64
Appendix B – Block Diagrams
TOUCHSCREEN
Appendix B – Block Diagrams
DC/AC
INVERTER
DC
LAMP1
LAMP2
INTERNAL
FLOPPY
DRIVE
OPTION
EXTERNAL
FLOPPY
CONNECTOR
OPTION
T/S CONT.
BOARD
TCTRL1
LED BOARD
DCINV1
TCTRL1
PARCOM2
RS-232
PARALLEL
COM1_4
RS232
RS485
KBMS1
AUX
KEYBD
LED
VGA1
FDD2
EXT.
VGA
FLOPPY
P1
6-SLOT BACKPLANE
TCH1
DRAM SOCKETS
AHIPST ONLY
CPU BOARD
BACKPLANE CONNS. (2 PCI)
ATIDE1PCIMG1
FDD1
LEDMSC1
ISA
ISA
ISA
ISA
ISA or
PCI
PCI
HARD
DRIVE
DC INPUT
PWR1 PWR2
IDE1
HDD XXX HDD
HDD
DC
INTERFACE
FPNL1
BOARD
TFT
CN1ACN2A
DC OUT
POWER SUPPLY
AC PLUG
BULB
SHARP 15“ TFT
LCD FLAT PANEL
BULB
FAN
AC IN
CD-ROM
(OPTION)
XXX
XX
Figure B- 1. 3515 TFT System Block Diagram
65
3500 Series Flat Panel Industrial PC
TOUCHSCREEN
DC/AC
INVERTER
DC
LAMP1
LAMP2
INTERNAL
FLOPPY
DRIVE
OPTION
EXTERNAL
FLOPPY
CONNECTOR
OPTION
T/S CONT.
BOARD
TCTRL1
LED BOARD
DCINV1
TCTRL1
PARCOM2
RS-232
PARALLEL
COM1_4
RS232
RS485
KBMS1
KEYBD
LED
VGA1
FDD2
EXT.
VGA
FLOPPY
P1
6-SLOT BACKPLANE
TCH1
DRAM SOCKETS
CPU BOARD
BACKPLANE CONNS. (2 PCI)
ATIDE1PCIMG1
AUX
FDD1
LEDMSC1
ISA
ISA
ISA
ISA
ISA or
PCI
PCI
HARD
DRIVE
DC INPUT
PWR1 PWR2
IDE1
HDD
DC
HDD XXX HDD
TFT
INTERFACE
FPNL1
BOARD
CN1A
POWER SUPPLY
AC PLUG
SHARP 15“ TFT
LCD FLAT PANEL
DC OUT
AC IN
BULB
BULB
FAN
66
CD-ROM
(OPTION)
XXX
XX
Figure B- 2. 3512KPM Block Diagram
Appendix C – Pinouts
This appendix provides the pinouts for the keyboard, AUX, LPT1, COM1, COM2, USB1,
and VGA connectors. The following table defines abbreviations used in this Appendix.
AbbreviationDefinition
NCNo connect
Keyboard Port Connectors
This connector is a standard PS/2-compatible connector.
PinSignal
1AKB_DATA
2ANC
3AGND
4A5VFUSE
5AKB_CLK
6ANC
Appendix C–Pinouts
Aux Port Connector
This PS/2 mini-DIN connector allows you to attach a serial device.
PinSignal
1BAUX_DATA
2BNC
3BGND
4B5VFUSE
5BAUX_CLK
6BNC
You cannot use the AUX port when the touchscreen controller is using it.
Serial ports RS-232 and RS-485 are supported on the AHIP6+ boards. Only one connector can be used at a time. All termination is done outside the unit.
COM1
RS-232RS-485
PinSignalPinSignal
1ADCD11BTXD2ARXD12BTXD+
3ATXD13BTXD TERM 4ADTR14BTXD TERM +
5AGND5BGND
6ADSR16BRXD7ARTS17BRXD+
8ACTS18BRXD TERM +
9ARI19BRXD TERM -
.
68
COM2
Appendix C–Pinouts
Technical Note
For TXD termination, connect a 150Ω, ½ watt resistor from pin 3B to pin
4B, with pin 1B connected to pin 3B and pin 2B connected to pin 4B.
For RXD termination, connect a 150Ω, ½ watt resistor from pin 8B to pin
9B, with pin 6B connected to pin 9B and pin 7B connected to pin 8B.
The COM2 port can be used (only one at a time) for the touchscreen controller, IrDA interface, or RS-232 connector. The BI OS setup determ ines
whether COM2 is used for either the connector or the IrDA interface.
Jumpers on the touchscreen controller select the COM2 port or the AUX
port.
We recommend sending the flat-panel display to Xycom Automation for bulb replacement. However, if you would like to replace the bulbs on site, this appendix provides instructions.
Note
Refer to the label on the back of your unit to determine the flat-panel
display model. If you are unsure which instructions to use, call Xycom Automation Customer Support at 800-289-9266.
3515 TFT Flat-Panel Display (Sharp #LQ150X1DG16 or Samsung
#LTM150XS-T01)
1. Turn off the power source.
2. Using a small Phillips-head screwdriver, loosen the two protruding captive screws
at the top back of the unit, and remove the lid.
FLAT PANEL DISPLAY SCREW (4)
(Remove for access to bulbs)
BULB
CONNECTOR
FLAT
PANEL
DISPLAY
INVERTER
CARD
CARRIER
BULB
CONNECTOR
3. If a touch screen or keypad is installed, disconnect the cable(s) at the top of the
system board.
Figure D- 1. Model #LQ150X1DG16 - Front View
71
3500 Series Flat Panel Industrial PC
4. Set the unit with the front panel down and loosen the four captive screws holding
the front panel to the display adapter plate.
5. While securely holding the front panel, flip the unit over.
6. Lift off the front panel, and set it aside.
7. Unscrew the four screws that attach the flat panel display to the standoffs.
8. Disconnect the bulb connector from the inverter card.
9. Gently lift the left side of the flat panel display, and unscrew the two screws to
disconnect the data interface connector.
10. Turn the display face up on a protective surface.
11. Referring to Figure D-2, remove the two set screws and slide the bulb assemblies
out.
BULB
CONNE CT OR
BULB
AS S EMB L Y
(P artially
pulled ou t )
FLAT
PANEL
DIS P LAY
BULB
CONNE CT OR
72
BULB ASSEMBLY SCRE WS (2)
(R emove to fr e e bul b ass embly from di s play)
Figure D- 2. Model #LQ150X1DG16- Rear View
Appendix D – Replacing Flat-Panel Display Bulbs
Note
Xycom Automation recommends replacing both bulbs at the same
time.
12. Slide the new assemblies into the openings from which the old assemblies were
removed.
13. Repeat steps 1 through 9 in reverse order to reassemble the unit.
3515KPM, KPT, KPMT TFT Flat-Panel (Sharp #LQ150X1DG16 or
Samsung #LTM150XS-T01)
1. Turn off the power source.
2. Unlatch and remove the lid.
3. If a touch screen is installed, disconnect the touch screen cable.
4. Disconnect the KEYPAD1, LEDKB1, and MS2 connectors.
5. Remove the four screws holding the front panel to the display adapter plate.
6. Remove the front panel, and set it aside.
7. Set the unit on the left side (power panel face down).
8. Disconnect the bulb connectors from the inverter.
9. Unscrew the four screws that attach the flat-panel display to the standoffs.
10. Disconnect the data interface cable from the display.
11. Gently lay the flat-panel display facedown on a protective surface next to the unit.
12. Referring to Figure D-3, unscrew the setscrews that secure the bulb assemblies
and slide the bulb assemblies out of the display.
BULB
CONNECTOR
FLAT
PANEL
DISPLA Y
BULB
CONNECTOR
BULB ASSEMBLY
SCREWS (2)
(Remove to free bulb
assembly from display)
BULB
ASSEMBL Y
(Partially
pulled out)
Figure D- 3. Model #LQ150X1DG16
73
3500 Series Flat Panel Industrial PC
13. Insert the new bulb assembly, and fasten the screw to secure.
Note
Xycom Automation recommends replacing both bulbs at the same
time.
14. Reverse steps 1 through 10 to reassemble the unit.