AManual Released5/99
B3412 and Notes on Windows CE Added10/99
CTouchscreen updates7/02
Trademark Inf ormation
Brand or product names are registered trademarks of their respective owners.
Windows is a registered trademark of Microsoft Corp. in the United States and other countries.
Copyright Information
This document is copyrighted by XYCOM AUTOMATION Incorporated (Xycom) and shall not be reproduced or
copied without expressed written authorization from Xycom.
The information contained within this document is subject to change without notice.
United States FCC Part 15, Subpart B, Class A EMI Compliance Statement:
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are d esigned t o provide rea sonable p rotection agains t harmfu l interferen ce when th e equipm ent is op erated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful
interferen ce in which case the user will be required to correc t the interference at his own expense.
For European Users - WARNING:
This is a Class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take
adequate measures.
The connection of non-shielded equipment interface cables to this equipment will invalidate FCC EMI and European Union EMC
compliance and may result in elect romagnetic interference and/or susc eptibility levels which are in violation of regulations which
apply to the legal operation of this device. It is the responsibility of the system integrator and/or user to apply the following directions which relate to instal l ation and configuration:
1. All interface cables must include shielded cables. Braid/foil type shields are recommended. Communication cable connectors must be
metal, ideally zinc die-cast backshell types, and provide 360 degree protection about the interface wires. The cable shield braid must be
terminated directly to the metal connector shell, ground drain wires alone are not adequate.
2. Protective measures for power and interface cables as described within this manual must be applied. Do not leave cables connected to unused
interfaces or disconnected at one end. Changes or modifications to this device not expressly approved by the manufacturer could void the user’s
authority to operate the equipment.
3. EMC compliance is, in part, a function of PCB design. Third party add-on AT/XT peripheral PCB assemblies installed within this appara-
tus may void EMC compliance. FCC/CE compliant PCB assemblies should always be used where possible. XYCOM can accept no responsibility for the EMC performance of this apparatus after system integrator/user installation of PCB assemblies not manufactured and/or
expressly tested and approved for compliance by XYCOM. It is the responsibility of the system integrator/user to ensure that installation
and operation of such devices does not void EMC compliance.
2
Table of Contents
Chapter 1 – System Overview.................................................................................................................... 6
Standard Features......................................................................................................................................................6
Optional Features ......................................................................................................................................................7
Unpacking the System...............................................................................................................................................8
Preparing for the Tests ............................................................................................................................................ 10
Running the Tests....................................................................................................................................................12
Front Panel..............................................................................................................................................................13
3408T/3410T Front Panel .................................................................................................................................... 13
3408KP Front Panel .............................................................................................................................................14
3410KP and 3410KPT Front Panel......................................................................................................................16
3412KPT Front Panel...........................................................................................................................................18
3412KP Front Panel .............................................................................................................................................19
Back Panel...............................................................................................................................................................21
Power Panel.............................................................................................................................................................22
3408/3410 Power Panels......................................................................................................................................22
Creating a Customized Logo...................................................................................................................................27
Installing Video Drivers..........................................................................................................................................34
Using a Touchscreen...............................................................................................................................................35
Specifying a Touchscreen Port.............................................................................................................................36
Calibrating the Touchscreen .................................................................................................... .............................37
Creating a Power Cable........................................................................................................................................... 39
AC Power Cable...................................................................................................................................................39
DC Power Cable...................................................................................................................................................40
Installing the System into a Panel............................................................................................................................42
System Power .......................................................................................................................................................42
Line Voltage Variation.........................................................................................................................................43
Mounting the Unit ................................................................................................................................................44
Power Supply..........................................................................................................................................................50
AC Power Supply.................................................................................................................................................50
DC Power Supply.................................................................................................................................................50
Group Ratings.......................................................................................................................................................53
Power Switch........................................................................................................................................................54
Operation and Maintenance..................................................................................................................................55
Control Keypad.......................................................................................................................................................57
Function and Alpha Modes...................................................................................................................................58
Cursor Control Keypad............................................................................................................................................59
Loading the Keypad Utility.....................................................................................................................................62
Using the Keypad Utility.........................................................................................................................................62
Main Menu..............................................................................................................................................................63
Macros Keypad Type Menu.................................................................................................................................64
Xycom Recommended Hard Drive Preventative Maintenance ...............................................................................74
Replacing the Fuse..................................................................................................................................................75
Chemical Compatibility...........................................................................................................................................75
Appendix B – Pinouts...............................................................................................................................82
Parallel Port Connector ...........................................................................................................................................82
Mouse Port Connector.............................................................................................................................................83
Power Connector.....................................................................................................................................................84
Appendix D – Installing the IDE Flash Drive...........................................................................................93
Installing the IDE Flash Drive.................................................................................................................................93
Configuring the IDE Flash Drive............................................................................................................................. 94
5
3408/3410/3412 Series Industrial PC System Manual
Chapter 1 - System Overview
The 3408, 3408KP, 3410, 3410KP, 3410KPT, 3412KP(T) and 3412T Industrial PCs
combine a PC/AT computer with a flat-panel display to offer a powerful, compact package for the factory floor and other harsh environments.
The units feature an open architecture to meet a variety of applications requiring both a
powerful PC and a durable industrial enclosure. The units’ front panels–sealed to NEMA
4/4X/12–are protected by an impact-resistant shield.
The units’ processor boards combine all the functions of an IBM PC/AT-compatible
computer on an industrially hardened circuit board. Refer to the Xycom Automation
CHIP4e+ CPU manual for more information on processor and hardware features.
Standard Features
The units offer the following standard features:
• 3.3-inch (3408 and 3408KP) and 3.5-inch (3410, 3410KP,3410KPT, 3412T and
3412KP(T)) mounting depth
• Flat-panel displays
• 7.7-inch STN flat-panel display, 640x480 (3408 and 3408KP)
• 10.4-inch TFT flat-panel display (3410, 3410KP and 3410KPT)
• 12.1-inch flat panel color display, 800x600 (SVGA) 3412T, 3412KP(T)
• CHIP4e+ board, which supports the latest 5x86 technology
• 133 MHz AMD5x86 processor
• 72-pin EDO DRAM SIMM site support (16, 32, and 64 MB)
• PCI 64-bit video controller, 1-MB video RAM
• PCI-bus IDE controller
• 10BASE-T/100 BASE-TX Ethernet controller
Note
Refer to the board manual for more information on the system’s Ethernet
capabilities.
• Numerous I/O ports
• RS-232 and RS-232/RS-485 COM ports
• Parallel port
• PS/2 mouse and keyboard ports
• IrDA-compatible infrared port (not supported by Windows CE)
• AC input power
6
• Flash BIOS
• External floppy connector
• PC/104 expansion site, allowing you to stack two PC/104 boards
• Status LEDs: Power, Disk, COM and Input (3408T, 3410T)
• MS-DOS
NT® or Windows CE)
• NEMA 4/4X/12 sealed front panel
• Class I, Division 2 hazardous location approval (not available on units with fieldbus
or control options installed)
The 3408KP, 3410KPand 3412KP also include function, control, numeric, alpha, and
cursor control keypads.
Optional Features
The following optional features are available:
• Windows 95,Windows NT or Windows CE preinstalled
• Windows NT touchscreen driver (serial port only; included if Windows NT is or-
dered preinstalled)
• OS/2 touchscreen driver (serial port only)
• Hot installable external floppy drive(not supported by Windows CE)
• 24-volt DC power supply
• 10- or 20-Mbyte IDE Flash drives
• NEMA 4-sealed panel-mount door for front access to keyboard and external floppy
port connectors (with mounting hardware)
â
(MS-DOS is not included if you order Windows
®
95, Windows
7
3408/3410/3412 Series Industrial PC System Manual
Unpacking the System
The following list pertains to a basic PC-only system. If a Xycom
Automation OpenHMI or OpenCNTRL workstation has been purchased,
a more complete packing list may be found in a separate Quickstart
manual.
When you remove the system from its box, verify that you have the parts listed below.
Save the box and inner wrapping in the event you need to reship the unit.
• 3408, 3408KP, 3410, 3410KP, 3410KPT, 3412T or 3412KP(T)
• Cable clamp and screw (for strain relief of power cord)
• Four standoffs and four 4-40 screws for mounting PC/104 expansion cards
• Documentation Library CD-ROM
• Utility disks
• Business reply card
Note
If you ordered the system with a touchscreen installed, you will also receive a touchscreen driver and manual. These items can be found on the Xycom Documentation CD
which is shipped with the unit.
Quick Start-up
The following steps pertain to a basic PC-only system. If a Xycom
Automation OpenHMI or OpenCNTRL workstation has been purchased,
more complete instructions are included in a separate Quickstart manual.
This section provides the steps to get the system operating, without explaining system
capabilities and options.
Disconnect the power cord before making any adjustments to the inside
or outside of the computer.
Perform the following steps to prepare the system for use:
Note
Warning
8
1. Attach optional equipment following the instructions in Chapter 3.
2. Attach the power cord from the power receptacle to a properly grounded 90-250
VAC, 50-60 Hz outlet. (See Chapter 3, Creating a Power Cable.)
3. Turn on power to the unit. The system will boot up into the operating system.
4. On the 3408 unit, adjust the contrast by using the contrast keys on the front panel.
On the 3408KP unit, adjust the contrast by pressing and holding the “F/A” key, and
then pressing the left or right arrow key to increase or decrease contrast.
Note
You cannot manually adjust contrast on 3410/12 units with active color
flat-panel displays; the contrast is adjusted automatically.
5. Install application software via the external floppy, the network, or the IR port.
9
3408/3410/3412 Series Industrial PC System Manual
Chapter 2 - Testing
If your system ships with MS-DOS, Xycom Automation provides diagnostic tests to verify system hardware functions. If a test fails, either you do not have the correct default
setting or there has been a hardware failure. Check the default settings and run the tests
again. If another failure occurs, contact Xycom Automation’s Product Repair and Customization Department (see Chapter 6).
Unexpected failures may occur if you run Xycom Automation diagnostics with device drivers or memory resident programs (TSRs) installed
on the system. Remove these before running any diagnostic tests.
Make sure the BIOS setup menus are configured properly (default settings). To access
the setup menus,
• Press
• Make the necessary changes by following the on-screen directions.
• Press
• Press ENTER twice to save the setup and exit.
Refer to your CPU manual for more information on the BIOS setup menus.
F2after the memory tests.
ESC.
Note
Preparing for the Tests
You need the following equipment to test your system:
• Floppy disk drive
• IBM PC/AT or PS/2-compatible keyboard
• 3.5-inch, DS/DD (bootable) Xycom Automation system test disk (Xycom Automa-
tion part number 99290-001)
• Centronics-compatible printer cable
• Parallel printer (Centronics-style interface)
• Two serial loopback test connectors (refer to Figure 2-1 for pinouts)
• 3.5-inch, DS/HD (1.44 Mbyte) disk, formatted
Perform the following steps before starting the tests:
1. Place the CPU board jumpers to the factory-set positions. Refer to your CPU manual
for these settings.
2. Plug the female end of the AC power cable into the bottom of the unit and the male
end into a properly grounded outlet.
10
3. Connect the serial loopback connector(s) and the printer cable to the appropriate
connectors and connect a PC/AT or PS/2 keyboard. Figure 2 -1 illustrates the wiring
necessary for the loopback connection.
Figure 2-1. Serial Loopback Connections
4. Make sure the BIOS setup menus are set to the default settings.
11
3408/3410/3412 Series Industrial PC System Manual
Running the Tests
To run the tests, insert the diagnostics disk into drive A. Turn on the computer (the diagnostics program will boot-up). Figure 2 -2 illustrates the Main Menu.
Copyright 1990-1996, Xycom Automation, Inc. All rights reserved.
Diagnostic Tests Sequence/Selection Menu (Rel. xx)
1. WILL pause on error
2. SINGLE PASS test mode
3. Save setup to file
4. Extract setup from a file
A)RAM Test
B)Video RAM Test
C)Extended RAM Test
D)Real Time Clock Test
E)COM1 Serial Port Test
F)COM2 Serial Port Test
G)COM3 Serial Port Test
H)COM4 Serial Port Test
I)Math Coprocessor Test
J)Video Adjustments Test
[ENTER]=START TESTING
Use the letters to move the cursor and select/deselect, or use the arrow keys to move, then
use the [SPACE] key to select/deselect a test or function.
5. Auto-select tests
6. Deselect all tests
7. Quit and exit to DOS
8. Return to previous screen
K)Video Interface Test
L)Speaker Port Test
M)LPT1: Printer Port Test
N)LPT2: Printer Port Test
O)C: Hard Drive Interface Test
P)D: Hard Drive Interface Test
Q)A: Floppy Drive Interface Test
R)B: Floppy Drive Interface Test
S)Keyboard, Keypad Tests
≡ = Test Selected
Figure 2-2. Main Menu
12
Note
Please read the DIAG.TXT file on the diagnostics disk for detailed information about the tests.
Chapter 3 - – Installation
This chapter describes how to install the 3408, 3410 and 3412 systems and their available options.
Front Panel
The 3408, 3410 and 3412 units come with a NEMA 4/4X/12 sealed front panel. The
panel protects the system’s interior when the system is properly panel mounted.
3408T/3410T Front Panel
DISPLAY
IR PORTCONTRAST
FeatureDescription
13
ADJUST
Figure 3-1. 3408T/3410T Front Panel
3408/3410/3412 Series Industrial PC System Manual
FeatureDescription
DisplayThe 3408T ships with a 7.7-inch STN passive color LCD flat-panel display with
an impact-resistant shield.
The 3410T ships with a 10.4-inch TFT active matrix color LCD flat-panel.
IR (Infrared) PortThe IR port transceiver is located behind this window. The port is IrDA and
ASKIR compliant, allowing you to connect the unit to any IrDA-compatible device. You must load special software (not included) to use this feature. When
enabled through the BIOS Setup menu, the IR link is designed to operate at a
distance of 0 to 1 meter. Note: COM2 is not available for other use when you
select the IR port in the BIOS Setup menus.
Diagnostic LEDsPowerOn (green) when there is power to the unit.
DiskOn (green) when the computer module is accessing the disk drive.
COMOn (green) when there is communication on one of the computer
module’s serial ports, including communication between the computer
module and the touchscreen (if attached to COM2) or a serial mouse.
InputOn (green) when the unit has a touchscreen. This LED gets brighter
when it detects a touch input.
Contrast Control KeysThese two keys control the contrast. The left key decreases contrast; the right
key increases contrast. Note: You cannot manually adjust contrast on
3410/12T units with TFT active color flat-panel displays; contrast is adjusted
automatically on these units.
3408KP Front Panel
14
Figure 3-2. 3408KP Front Panel
Note
Refer to Chapter 4 for information on using the keypads, and Chapter 5
for information on reprogramming the keys (not currently applicable to
Windows CE).
FeatureDescription
DisplayThe 3408KP ships with a 7.7-inch STN passive color LCD flat-panel
display with an impact-resistant shield.
IR (Infrared) PortThis port is IrDA and ASKIR compliant, allowing you to connect the
unit to any IrDA-compatible device. You must load special software
(not included) to use this feature. When enabled through the BIOS
Setup menu, the IR link is designed to operate at a distance of 0 to
1 meter. Note: COM2 is not available for other use when you select
the IR port in the BIOS Setup menus.
Function/Alpha KeypadsThe keypads provide function keys F1-F20, as well as uppercase
letters A-T. These keys are relegendable (refer to CustomizingKeypad Inserts later in this chapter).
Control/Alpha keypadThis keypad provides the CTRL, SHIFT, INS, ALT, TAB, DEL, F/A, SPACE,
and + keys, as well as the uppercase letters U-Z. (The
INS, ALT, TAB, and DEL keys are relegendable.)
The
F/A key toggles the keypads between function and alpha mode.
When the
When you press and hold the
F/A key is not pressed, the keypads are in function mode.
F/A key, the keypads are in alpha
mode (refer to Figure 3-2 to determine the location of the alpha
characters).
You can also use the
display. To do this, hold down the
F/A key to adjust contrast on the flat-panel
F/A key while pressing a cursor
control key.
Numeric keypadThis keypad provides numbers 0-9, as well as a decimal point and
a minus sign.
Cursor control keypadThis keypad controls cursor movement. It also provides contrast
control when used in conjunction with the
F/A key.
CTRL, SHIFT,
15
3408/3410/3412 Series Industrial PC System Manual
3410KP and 3410KPT Front Panel
Figure 3-3. 3410KP Front Panel
FeatureDescription
DisplayThe 3410KP ships with a 10.4-inch TFT active matrix color
LCD flat-panel. An optional touchscreen (KPT) is also available.
IR (Ifrared) PortThis port is IrDA and ASKIR compliant, allowing you to con-
nect the unit to any IrDA-compatible device. You must load
special software (not included) to use this feature. When enabled through the BIOS Setup menu, the IR link is designed
to operate at a distance of 0 to 1 meter. Note: COM2 is not
available for other use when you select the IR port in the
BIOS Setup menus.
PF/Function/Alpha KeypadsThe keypads provide function keys F1-F20, PF keys 1-12 (PF
keys 7-12 also include punctuation symbols), as well as uppercase letters A-Z. These keys are relegendable (refer to
Customizing Keypad Inserts later in this chapter).
Control keypadThis keypad provides the CTRL, SHIFT, INS, ALT, TAB, DEL, F/A,
SPACE, and + keys. (The CTRL, SHIFT, INS, ALT, TAB, and DEL
keys are relegendable.) These keys work the same as they
do on a keyboard.
The
F/A key toggles the keypads between function and alpha
mode. When the
function mode. When you press and hold the
F/A key is not pressed, the keypads are in
F/A key, the
keypads are in alpha mode (refer to Figure 3-3 to determine
the location of the alpha characters).
16
FeatureDescription
Numeric keypadThis keypad provides numbers 0-9, as well as a decimal point
and a minus sign.
Cursor control keypadThis keypad controls cursor movement.
Keyboard Port (front access)The 3410KP provides both front- and rear-accessible PS/2
keyboard connectors. The front-accessible connector is lo-
cated on the lower right side of the front panel. The rear ac-
cessible connector is located on the side of the unit.
Note
A pointing device using the auxiliary port may not operate reliably in
conjunction with an 84-key keyboard. Use of this combination is not
recommended.
Note
Only one keyboard port on the 3410KP can be used at a time.
17
3408/3410/3412 Series Industrial PC System Manual
3412KPT Front Panel
TOUCHSCREEN
(OPTIONAL)
POWER DISK
IR PORT
IR PORT POWER DISK
Figure 3-4. 3412KPT Front Panel
INPUT
COM
COM
INPUT
FeatureDescription
DisplayThe 3412 comes standard with a 12.1-inch TFT flat panel. Impact-resistant
shields protect the displays from breakage. If a touchscreen is factory installed,
the touchscreen is backed by heat-annealed safety glass replacing the impact-
resistant shield.
System Status LEDsIn this application, the system status LEDs are not enabled.
IR (Infrared)The IR port transceiver is loc ated behind this window. The 3412 IR por t is Ir DA,
and ASK-IR compliant. You can connect the 3412 to any IrDA compatible de-
vice, if you load special software (not included). T he inf r ared ( IR) link oper ates
at a distance of 0 to 1 meter and is capable of 115 K baud transfer rates. En-
able the interface through the BIOS setup m enus .
sen, COM2 is not available. Correspondingly, if COM2 is in use by the touchscreen the
IR is not operational.
Note: When the IR port is cho-
18
3412KP Front Panel
Figure 3-5. 3412KP Front Panel
FeatureDescription
DisplayThe 3510KP/3512KP comes with a 10.4-inch (640 x 420) TFT
flat panel display or a 12.1-inch SVGA (800 x 600) TFT flat
panel display.
Diagnostic LEDsIn this application, the system status LEDs are not enabled.
Function and User-Defined KeysThese 32 relegendable function keys (64 using the F/A keys)
provide easy access to familiar routines. (F/A keys can be used
for alpha and symbol entry). See the Customizing Keypad In-
serts section in this chapter for details on customizing your key-
pad inserts.
Numeric/Cursor Control KeypadThe purpose of data entry keypads are for entering data and
moving the cursor.
PF10 Key (Keypad Configuration Key)This key reconfigures your keypad.
Keyboard Port (3510KP/3512KP)
(front access)
The 3510KP/3512KP provides both front and rear accessible
PS/2 keyboard connectors. The front accessible connector is
located on the lower right side of the front panel. The rear ac-
cessible connector is located on the side of the unit.
Note: Only one keyboard port on the 3510/3512KP can be used
at a time.
Note: The installation of the touchscreen driver determines
whether a second pointing device will function correctly. If you
are using a mouse with a touchscreen, please review the
Touchscreen Driver Installation instructions.
19
3408/3410/3412 Series Industrial PC System Manual
3408/3410/3412 I/O Panel
Floppy Drive Option
not Available with Windows CE
Figure 3-6. 3408/3410/3412 I/O Panel
FeatureDescription
Parallel port (LPT1)This port provides a standard PC-compatible interface to printers and other de-
vices. Note: Printing is not supported by units with Windows CE..
COM1 portCOM1 is RS-232/485 compatible. The nine pin lower connector is RS/232. The
upper connector is the RS/485 version of the same port. You can only use one of
these connectors at a time since they are attached to the same logical port.
COM2 portCOM2 is dedicated to the IR port, the touchscreen controller, or the 25-pin con-
nector. Only one option can be used at a time. An external pushbutton reset option
is available. Consult the CPU board manual for the jumper that controls this option.
Ethernet PortThis port provides a 10BASE-T/100BASE-TX autosensing Ethernet connection.
Keyboard portThis port allows you to attach a PS/2-style keyboard.
Mouse portThis port allows you to attach a PS/2-style mouse. If the unit has a factory-installed
touchscreen, this port may be unavailable for other use.
Note
A pointing device using the auxiliary port may not operate reliably in
conjunction with an 84-key keyboard. Use of this combination is not
recommended.
20
To maintain a safe condition, do not use an external keyboard or mouse
port when the unit is operating in a hazardous environment.
Back Panel
Figure 3-7 illustrates the back panel on the 3408,3410 and 3412 units.
Warning
Flop
py Drive Option not Available with
Windows CE
21
Figure 3-7. 3408/3410/3412 Back Panel
Warning
You must disconnect the power cable, floppy cable, and any other external cables connected to the unit before removing the back cover.
3408/3410/3412 Series Industrial PC System Manual
FeatureDescription
Back coverThe back cover has five notches that slide into corresponding
slots on the display carrier, as well as three screws that secure it
to the unit.
External floppy disk drive (optional)You can install an external floppy disk drive to the back of the
unit. It connects to the floppy connector on the bottom of the
unit.
Panel mounting studsThere are studs on the back of the unit for panel mounting.
Power Panel
This section describes the power panels on the 3408, 3410 and 3412 units.
3408/3410 Power Panels
22
Figure 3-8. 3408 Power Panel
Figure 3-9. 3410/12 Power Panel
FeatureDescription
Power connectorThe power receptacle is a three-pin connector. Refer to Haz-
ardous Location Installations section later in this chapter for
special installation instructions.
External floppy drive connectorThe 26-pin floppy drive connector lets you connect an optional
external floppy drive.
Installing Internal Hardware Options
Warning
You must disconnect the power cable, floppy cable, and any other external cables connected to the unit before removing the back cover.
DRAM Single In-line Memory Modules (SIM Ms)
23
You can order your system CPU factory-configured for many DRAM configurations.
You can reconfigure DRAM capacity by changing the DRAM SIMMs on your CPU
board.
The CHIP4e+ has one 72-pin in-line memory module (SIMM) site in which to add memory. Due to the CPU speed, DRAM access time should be 70 ns or less, and must be 60
ns to run with the fastest memory setting.
3408/3410/3412 Series Industrial PC System Manual
The CHIP4e+ can accommodate 4, 8, 16, 32, or 64 Mbytes of DRAM. You may use 1M
x 32, 2M x 32, 4M x 32, 8M x 32, and 16M x 32 DRAM SIMM sizes.
The following tables list recommended DRAM manufacturers, along with the respective
part numbers.
The illustration below shows how to install DRAM SIMMS on the CHIP4e+.
24
25
DRAM Installation
3408/3410/3412 Series Industrial PC System Manual
PC/104 Boards
PC/104 cards must be installed and configured at the factory for units
with the Windows CE operating system.
The PC/104 connector supports a 16-bit interface. The connectors are placed on the
board so that PC/104 stack-through interface boards can be used.
Four standoffs are already attached to the CPU board. If you want to stack a second
PC/104 card on the first, you need the four standoffs contained in the documentation kit.
Installation of PC/104 cards may void EMC and hazardous locations
compliance. This is a function of the PC/104 card design. It is the system
integrator/user’s responsibility to verify compliance before installing any
given card.
Note
Note
Note
To prevent vibration failures, always use the locking screw to attach
PC/104 cards.
Perform the following steps to install the PC/104 card:
1. Disconnect the power cable, floppy cable, and any other external cables.
2. On a protective surface, lay the unit on its front panel.
3. Unscrew the three back cover mounting screws (refer to Figure 3-7 for positioning
information).
4. Slide the back cover toward the I/O panel, and lift off.
5. Attach the PC/104 card to the four preinstalled standoffs. If you want to install a
second PC/104 card, you must attach the standoffs included in the documentation kit
to the first PC/104 card.
6. If you need to connect the cards to something outside the unit, remove the access
plate on the I/O panel. You can then pass cables through this area.
26
Installing External Hardware Options
y
(
)
This section explains how to install external hardware options.
External Floppy Drive
Note
To avoid corruption, do not attach the external floppy drive with a disk
installed.
There are four screw holes on the back of the unit to mount an external floppy disk drive
(9000-EXF). Refer to Figure 3-7.
Note
Make sure the floppy drive cable is able to reach the external floppy
connector on the system before making the cutout.
Creating a Customized Logo
You may place a customized label on the unit. Figure 3-10 provides the dimensions and
recommended requirements for a customized label.
0.55 (13.97)
2.05 (52.07)
NOTE: All dimensions ar e in inches (mm)
RECOMMENDED MATERIAL: 0.007 (0.176) thick
ester with 3M #468 a dhesive on far side
pol
Figure 3-10. Logo Label Dimensions
Once you have created a customized label, place it over the “Xycom Automation” label
(inside the recessed area).
0.06
1.52
(4 Places)
Your Logo On
Entire Surface
27
3408/3410/3412 Series Industrial PC System Manual
Creating Customized Keypad Inserts
You can customize your 3408 and 3410 keypads with keypad inserts. The following figures provide the necessary dimensions and recommended requirements to create customized keypad inserts.
3408KP Keypad Inserts
28
Figure 3-11. 3408KP F1-F12 Insert Dimensions
Figure 3-12. 3408KP F13-F20 Insert Dimensions
1.083
(
(27.5)
0.828
(21.0)
FAR
SIDE
.510
(13.0)
TYP.
.545
(13.8)
TYP.
.145
(3.7)
TYP.
2.722
(69.1)
NEAR
SIDE
1.266
(32.2)
PF1
UXVYW
PF2
PF3
PF6PF5PF4
Z
Note: All dimensions in inches (mm)
Material: .007
.178) thick polyester
Figure 3-13. 3408KP Control Key Insert Dimensions
.074
(1.9)
.090 (2.3)
RAD
29
3408/3410/3412 Series Industrial PC System Manual
Figure 3-14 illustrates how to install the 3408KP keypad inserts.
The system comes with MS-DOS. You can also order the system preinstalled with Windows 95, or Windows NT or as an integrated workstation with Windows CE and industrial HMI software. Table 3-1 indicates the formats in which preinstalled operating systems are provided.
Table 3- 1. Operating System Formats
Operating SystemsFormat
DOSDisk
Windows 95CD ROM
Windows NTCD ROM
If you want to install a new operating system or re-install a current operating system, refer to the operating system’s manual for directions.
33
3408/3410/3412 Series Industrial PC System Manual
An external CD-ROM drive may be required to load additional drivers
on Windows 95 and Windows NT-equipped systems.
Installing Ethernet Drivers
If Windows 95 or Windows NT 4.0 is pre-installed on your system, Ethernet drivers are
installed on your hard drive in the C:\netdrv directory.
If you want to use Ethernet capabilities with Windows 95, your system
must have BIOS revision level 1.1 or higher.
If MS-DOS is installed on your system, the Ethernet drivers are supplied on your hard
drive in the C:\netdrv directory, but they are not installed.
Note
Note
To install the MS-DOS Ethernet drivers,
1. At the C: prompt, type “cd netdrv”.
2. Once the C:\netdrv path is specified, type “setup”.
3. Follow the on-screen instructions to complete installation.
If you install Windows NT 4.0 on your system, the Ethernet drivers that
are provided with Windows NT 4.0 do not work with the Ethernet controller on 3408/3410 units. You must use the drivers provided by Xycom
Automation.
These drivers can be found on the Intel 558 Ethernet Drivers disk that
ships with your system. Refer to the Msnt40.txt file in the A:\Info\Ms directory on this disk for installation information.
Consult the Info directory on the drivers disk for additional installation information. If
Windows CE is on your system, you can not change the currently installed and configured drivers.
Installing Video Drivers
Note
34
Video drivers and the expansion utilities are on the disk included with the documentation
kit as well as on the hard drive.
The video drivers are in the following directories for systems with DOS:
The appropriate drivers are copied to the hard drive under C:\VIDDRV for systems with
Windows 95 or Windows NT installed.
Using a Touchscreen
Xycom Automation’s touchscreen complies with environmental specifications and
maintains a NEMA 4 seal when panel mounted. It remains operational even after 30 million touches.
These touchscreen instructions do not apply to units with the Windows
CE operating system. To calibrate the touchscreen, refer to the Quickstart guide for your Windows CE workstation.
Installing Touchscreen Drivers
Note
Depending upon the date of purchase, the Xycom Automation unit will have one of two
possible touchscreen controllers:
• The Microtouch Controller P/N 114084
• The Xycom ControllerP/N 140554
These controllers function similarly. However, the following sections require attention to
the type of controller installed.
Microtouch Controller
If a touchscreen is factory installed, you will receive a disk with MS-DOS
and Windows 95 touchscreen drivers. If Windows 95 is preinstalled on
your system with a touchscreen, the touchscreen driver has already been
installed. If you ordered the Windows NT option, a copy of the driver is
provided on disk, as well as on the hard drive (c:\touchdrv). You must purchase touchscreen drivers for OS/2 (3408-DRVOS/2) separately.
The Windows 95 touchscreen driver supports the COM2 and mouse ports.
The Windows NT touchscreen driver only supports COM2.
If you change the operating system, you must install the corresponding
touchscreen driver software. Refer to the touchscreen manual for instructions.
35
3408/3410/3412 Series Industrial PC System Manual
Xycom Controller
If a touchscreen is factory installed, you will receive a CD with MS-DOS
and Windows touchscreen drivers.
If you change the operating system, you must install the corresponding
touchscreen driver software. Refer to the touchscreen manual for instructions.
Specifying a Touchscreen Port
You must disconnect the power cable, floppy cable, and any other external cables connected to the unit before removing the back cover.
Depending upon the date of purchase, the Xycom Automation unit will have one of two
possible touchscreen controllers:
Warning
• The Microtouch Controller P/N 114084
• The Xycom ControllerP/N 140554
These controllers function similarly. However, the following sections require attention to
the type of controller installed.
Microtouch Controller
Note
If the touchscreen is factory-installed along
with MS-DOS or Windows 95, the
touchescreen is configured for the mouse
port, making the mouse port unavailable for
other use. If Windows NT is factory installed, the touchscreen is configured for
COM2, making COM2 unavailable for
other use.
Perform the following steps to reconfigure the port used by the touchscreen
controller:
1. Disconnect the power cable and other external cables
and remove the back cover as described in the PC/104Boards section earlier in this chapter.
36
2. Remove the touchscreen controller card. Figure 3-19A
shows the touchscreen controller card and its jumper
set.
Figure 3-19A. Touchscreen Controller Card
3. Reconfigure Jumpers J1-J5. Position A = COM2; posi-
tion B = PS/2 mouse.
4. Reinstall the touchscreen controller card, and then re-
place the back cover.
5. Reconnect any external cables you removed in step 1
and the power cable.
6. Reboot the computer.
7. Referring to the touchscreen manual, do the following:
• Load the touchscreen drivers.
• Reconfigure the touchscreen driver for COM2.
• Recalibrate the touchscreen.
Xycom Controller
Perform the following steps to reconfigure the port used by the touchscreen
controller:
1. Disconnect the power cable and other external ca-
bles and remove the back cover as described in the
PC/104Boards section earlier in this chapter.
2. Remove the touchscreen controller card Figure 3-
19B shows the touchscreen controller card and its
jumper set.
37
3408/3410/3412 Series Industrial PC System Manual
A
B
CO
J1
J2
J3
J4
JUMPERS
J5
J7
J8
J9
2
1
TOUCH SCREEN
NTROL CONN.
40
39
Figure 3-20B. Touchscreen Controller Card
3. Reconfigure Jumpers J1-J9. Position A = COM2;
position B = PS/2 mouse.
4. Reinstall the touchscreen controller card, and then
replace the back cover.
5. Reconnect any external cables you removed in step
1 and the power cable.
6. Reboot the computer.
7. Referring to the touchscreen manual, do the fol-
lowing:
• Uninstall the UPDD Touch driver.
• Locate the Touch-Base Serial Mode driver on
the Xycom DOC CD.
• Follow the instructions in the readme.txt file for
the serial mode UPDD driver.
Calibrating the Touchscreen
Depending upon the date of purchase, the Xycom Automation unit will have one of two
possible touchscreen controllers:
• The Microtouch Controller P/N 114084
• The Xycom ControllerP/N 140554
These controllers function similarly. However, the following sections require attention to
the type of controller installed.
38
Microtouch Controller
If you need to recalibrate the touchscreen, refer to the sections in the touchscreen manual that explain calibrating the
touchscreen and using the diagnostic utility.
Note
The touchscreen and controller are a
matched pair calibrated at the factory.
Xycom Controller
If you need to recalibrate the touchscreen, run the Pointer
Devices Control Panel applet. Select Help for details about
calibrating. For best results, use the 25 point calibration
setting with Start In At set to 0.
You need to calibrate the touchscreen if
• The cursor does not follow the movement of your finger or pen
• You adjust the size of the video image or change the video mode
Creating a Power Cable
This section describes how to create both an AC and a DC power cable.
AC Power Cabl e
You must create an AC power cable to supply power to units with AC power supplies.
You will need the following materials:
• A three-position power connector (supplied)
• A braid/foil shielded power cable, terminated at power source end, with three 18 (1.0
mm), 16 (1.3 mm), or 14 (1.6 mm) AWG solid or stranded copper wire, rated 80º C
or better.
Perform the following steps to create the cable:
1. Cut the wire cable to the desired length.
2. Strip 0.25-inch (6 mm) of insulation from the end of the conductor wire. No bare
wire should be exposed when the cable is connected to the workstation.
3. Tin the wire ends with solder if using stranded wire. This will keep the wire from
fraying.
39
3408/3410/3412 Series Industrial PC System Manual
When inserting the wire ends of the power cable into the block plug, be
sure there is no exposed wire. Trim the wire ends of the cable or cut a
new cable if necessary.
4. Insert the three wire ends of the power cable into the three holes of the block plug.
Insert the Protective Earth GND ground, L1, and L2/N wires into the corresponding
holes, as shown in Figure 3-21. Be sure that no bare wires are exposed.
Figure 3-21. AC Power Connector
Warning
5. Tighten the three screws above the wires to hold them firmly in place.
Never tighten the three screws of the block plug when the cable is connected to a power source. The screws are conductive and have full contact with the cable wire.
6. Use a cable clamp and #6-32 screw (provided) to secure and provide strain relief to
the power cable. When installing the power cable to the unit, use the securing screws
on each side of the plug. This strain relief is mandatory for hazardous locations compliance.
Be sure to completely loosen the two securing screws on the plug when
disconnecting the power cord from the unit.
DC Power Cable
You must create a DC power cable to supply power to units with DC power supplies.
You will need the following materials:
Warning
Warning
40
• A three-position power connector (supplied)
• A braid/foil shielded power cable with three 18 (1.0 mm), 16 (1.3 mm), or 14 (1.6
mm) AWG solid or stranded copper wire, rated 80º C or better.
Perform the following steps to create the cable:
1. Cut the wire cable to the desired length.
2. Strip 0.25-inch (6 mm) of insulation from the end of the conductor wire. No bare
wire should be exposed when the cable is connected to the workstation.
3. Tin the wire ends with solder if using stranded wire. This will keep the wire from
fraying.
Warning
When inserting the wire ends of the power cable into the block plug, be
sure there is no exposed wire. Trim the wire ends of the cable or cut a
new cable if necessary.
4. Insert the three wire ends of the power cable into the three holes of the block plug.
Insert the Protective Earth GND ground, + (positive), and - (return) wires into the
corresponding holes, as shown in Figure 3-22. Be sure that no bare wires are exposed.
41
Figure 3-22. DC Power Connector
5. Tighten the three screws above the wires to hold them firmly in place.
Warning
Never tighten the three screws of the block plug when the cable is connected to a power source. The screws are conductive and have full contact with the cable wire.
6. Use the aluminum cable clamp (provided) to terminate the DC cable shield and pro-
vide strain relief. The aluminum cable clamp is designed to accommodate cable with
¼-inch (6.4 mm) O.D.
7. The DC cable shield must be terminated to chassis ground (PE) at the 3408 end. A
pigtail termination will not provide enough EMI suppression in those installations
where the DC cable exits a metal enclosure.
To terminate the braided cable shield, the braid must be dressed back over the cable
insulation 1/2 inch (13 mm). The aluminum clamp must then be placed over the
braid/insulation. Use the #6-32 screw (provided) to secure the clamp to the chassis in
3408/3410/3412 Series Industrial PC System Manual
the female pem located on the side of the power connector opening. When installing
the power cable to the unit, use the securing screws on each side of the plug.
Warning
Be sure to completely loosen the two securing screws on the plug when
disconnecting the power cord from the unit.
Installing the System into a Panel
The system’s rugged design allows it to be installed in most industrial environments. The
system is generally placed in a NEMA 4/4X/12 enclosure to protect against contaminants
such as dust, moisture, etc. Metal enclosures also help minimize the effects of electromagnetic radiation that nearby equipment can generate.
System Power
Using isolation transformers on the incoming AC power line to the system is always a
good practice. An isolation transformer is especially desirable in cases in which heavy
equipment is likely to introduce noise onto the AC line. The isolation transformer can
also serve as a step-down transformer to reduce the incoming line voltage to a desired
level. The transformer should have a sufficient power rating (units of volt-amperes) to
supply the load adequately.
Proper grounding is essential to all safe electrical installations. Refer to the relevant federal, state/provincial, and local electric codes which provide data such as the size and
types of conductors, color codes and connections necessary for safe grounding of electrical components. The code specifies that a grounding path must be permanent (no solder),
continuous, and able to safely conduct the ground-fault current in the system with minimal impedance (minimum wire required is 18 AWG, 1 mm).
Observe the following practices:
• Separate ground wires (P.E. or Protective Earth) from power wires at the point of
entry to the enclosure. To minimize the ground wire length within the enclosure, locate the ground reference point near the point of entry for the plant power supply.
• All electrical racks or chassis and machine elements should be Earth Grounded in in-
stallations where high levels of electrical noise can be expected. The rack/chassis
should be grounded with a ground rod or attached to a nearby Earth structure such as
a steel support beam. Connect each different apparatus to a single Earth Ground
point in a “star” configuration with low impedance cable. Scrape away paint and
other nonconductive material from the area where a chassis makes contact with the
enclosure. In addition to the ground connection made through the mounting bolt or
stud, use a one-inch metal braid or size #8 AWG wire to connect between each chassis and the enclosure at the mounting bolt or stud.
42
Excessive Heat
The systems withstand temperatures from 0º to 50º C. They are cooled by convection, in
which a vertical column of air is drawn in an upward direction over the surface of its
components. To keep the temperature in range, the cooling air at the base of the system
must not exceed 50° C. Allocate proper spacing between internal components installed in
the enclosure.
When the air temperature is higher than the specified maximum in the enclosure, use a
fan or air conditioner to lower the temperature.
Electrical Noise
Electrical noise is seldom responsible for damaging components, unless extremely high
energy or high voltage levels are present. However, noise can cause temporary malfunctioning which can result in hazardous machine operation in certain applications. Noise
may be present only at certain times, may appear at widely-spread intervals, or in some
cases may exist continuously.
Noise commonly enters through input, output, and power supply lines and may also be
coupled through the capacitance between these lines and the noise signal carrier lines. This
usually results from the presence of high voltage or long, close-spaced conductors. When
control lines are closely spaced with lines carrying large currents, the coupling of magnetic
fields can also occur. Use shielded cables to help minimize noise. Potential noise generators include switching components, relays, solenoids, m otors, and motor starters.
Refer to the relevant Federal, State/Provincial, and local electric codes, which provide
data such as the size and types of conductors, color codes and connections necessary for
safe grounding of electrical components. It is recommended that high- and low-voltage
cabling be separated and dressed apart. In particular, AC cables and switch wiring should
not be in the same conduit with all communication cables.
Line Voltage Variation
The power supply section of the unit is built to sustain line fluctuations of 90-250 VAC
and still allow the system to function within its operating margin. As long as the incoming voltage is adequate, the power supply provides all the logic voltages necessary to
support the processor, memory, and I/O.
When the installation is subject to unusual AC line variations, use a constant voltage
transformer to prevent the system from shutting down too often. However, a first step
toward the solution of the line variations is to correct any possible feed problem in the
distribution system. If this correction does not solve the problem, use a constant voltage
transformer.
The constant voltage transformer stabilizes the input voltage to the systems by compensating for voltage changes at the primary in order to maintain a steady voltage at the secondary. When using a constant voltage transformer, check that the power rating is sufficient to supply the unit.
43
3408/3410/3412 Series Industrial PC System Manual
Mounting Considerations
Once you have established a location for the unit, consider the following when selecting
an enclosure:
• Select a NEMA-rated enclosure, and place the unit to allow easy access to the system
ports.
• Account for the unit’s depth when choosing the depth of the enclosure.
• Provide a NEMA 4 seal by mounting the unit in an approved enclosure that has a 14
gauge (0.075"/1.9 mm thick) steel or (0.125"/3.2 mm thick) aluminum front face.
• Mount the unit in an upright position.
• Place the unit at a comfortable working level.
• Consider locations of accessories such as AC power outlets and lighting (interior
lighting and windows) for installation and maintenance convenience.
• Prevent condensation by installing a thermostat-controlled heater or air conditioner.
• Avoid obstructing the air flow to allow for maximum cooling.
• Place any fans or blowers close to the heat-generating devices. If using a fan, make
sure that outside air is not brought inside the enclosure unless a fabric or other reliable filter is used. This filtration prevents conductive particles or other harmful contaminants from entering the enclosure.
• Do not select a location near equipment that generates excessive electromagnetic in-
terference (EMI) or radio frequency interface (RFI) (equipment such as high- power
welding machines, induction heating equipment, and large motor starters).
• Do not place incoming power line devices (such as isolation or constant voltage
transformers, local power disconnects, and surge suppressers) near the system. The
proper location of incoming line devices keeps power wire runs as short as possible
and minimizes electrical noise transmitted to the unit.
• Make sure the location does not exceed the unit’s shock, vibration, and temperature
specifications (refer to Appendix A for specifications).
• Install the unit in the panel in such a way as to ensure that it does not cause a hazard
from uneven mechanical loading.
• Incorporate a readily accessible disconnect device in the fixed wiring on permanently
connected equipment.
• Avoid overloading the supply circuit.
Mounting the Unit
Once the conditions in the preceding sections have been met, perform the following steps
to mount the unit:
1. Locate a position for your system that meets the specifications required (see previous
sections and Appendix A).
2. Create a panel cutout. Refer to the dimensions in Figures 3-20 through 3-23.
3. Make sure the area around the cutout is clean and free from metal burrs.
4. Install the unit.
44
5. Attach one end of the power cord to the power receptacle and the other end to a
properly grounded 90-250 VAC, 50-60 Hz or 24 VDC (on DC units) outlet, whichever applies. (See Hazardous Location Installations later in this chapter for more information.)
6. Implement the proper grounding techniques. Establish a ground path from the unit
chassis to the enclosure chassis. A 6-32 threaded ground point hole is provided on
the bottom panel of the unit.
7. Tighten the eight #8-32 nuts on 3408 units to 16 inch-pounds (1.8 Newton-meters;
18 Kgf cm). Tighten the twelve #10-32 nuts on 3410 units to 25 inch-pounds (2.8
Newton-meters; 28 Kgf cm).
8. Turn on power to the unit. The system will boot up to the operating system installed.
Install application software via a floppy drive, the IR port, or a network.
45
3408/3410/3412 Series Industrial PC System Manual
9. System Cutout Dimensions
This section provides system cutout dimensions.
The standard systems ship with an AC power supply; a 24 VDC power supply is optional. This section provides specifications for both AC and DC power supplies.
AC Power Supply
The AC power supply provides 90-250 VAC, 50-60 Hz (autosensing), 1 A maximum at
90 VAC with 35 watts of output throughout the system’s temperature range.
DC Power Supply
The DC power supply accepts +24 VDC input voltage for applications requiring DC input power. The factory-installed power supply module provides +5 V, +12 V, and -12 V
outputs.
Electrical specifications for the power supply are 18 to 36 VDC, 2.5 A maximum at 18
volts.
Expansion Power
Table 3-2 lists the available power from both the AC and DC power supplies.
Table 3- 2. Available Expansion Power
VoltageCHIP4e+ Available Current
+5 V.80 A
+12 V.25 A
- 12 V.25 A
Total not to exceed 6 W
Hazardous Location Installations
Xycom Automation designed the systems to meet Class I, Division 2 Hazardous Location
application requirements. Division 2 locations are locations that are normally nonhazardous, but could potentially become hazardous should accidents expose the area to
flammable vapors, gases, or combustible dusts.
These systems have been designed as non-incendiary devices. They are not intrinsically
safe and should never be operated within a Division 1 (normally hazardous) location
when installed as described here. Nor should any peripheral interface device attached to
these systems be located within Division 1 locations unless approved and/or certified diode barriers are placed in series with each individual signal and DC power line. Any
such installations are beyond the bounds of Xycom Automation design intent. Xycom
Automation accepts no responsibility for installations of this equipment or any devices
attached to this equipment in Division 1 locations.
50
Note
When adding cards to the system, the user must ensure that they meet
operating conditions for Class I, Division 2 hazardous locations.
It is the customer’s responsibility to ensure that the product is properly rated for the location. If the intended location does not presently have a Class, Division, and Group rating, then users should consult the appropriate authorities having jurisdiction to determine
the correct rating for that hazardous location.
In accordance with federal, state/provincial, and local regulations, all hazardous location
installations should be inspected by the authority having jurisdiction, prior to use. Only
technically qualified personnel should install, service, and inspect these systems.
Warning
Suitable for use in Class I, Division 2, Groups A, B, C, and D, and Class
II, Division 2, Groups F and G hazardous locations or non-hazardous locations only.
Warning - Explosion Hazard
Substitution of components may impair suitability for Class I, Class II,
Division 2.
Advertissement Risque D’Explosion
La substitution de composants peut rendre ce materiel inacceptable pour
les emplamements de classe I, II, Division 2.
Warning - Explosion Hazard
Do not disconnect equipment unless the power has been disconnected or
the area is known to be non-hazardous.
Advertissement Risque D’ Explosion
Avant de deconnecter l’equipment, coupler le courant ou s’assurer que
l’emplacement est designe non dangereux.
Advertissement Risque D’ Explosion
Dans les situations hasardees, couper la courant avant de remplacer ou
de cabler les modules.
51
3408/3410/3412 Series Industrial PC System Manual
Warning - Explosion Hazard
When operating in hazardous locations, disconnect power before replacing or wiring modules.
To maintain a safe condition, do not use an external keyboard or mouse
when the unit is operating in a hazardous environment.
Definitions
The following Class and Division explanations are derived from Article 500 (Sections 5
and 6) of the United States National Fire Protection Agency National Electric Code
(NFPA 70, 1990). They are not complete and are included here as a general description
for those not familiar with generic hazardous location requirements.
Warning
People responsible for installing this equipment in hazardous locations are responsible
for ensuring that all relevant codes and regulations related to location rating, enclosure,
and wiring are met.
Class I Locations
Class I locations are those in which flammable gases or vapors are or may be present in
the air in quantities sufficient to produce explosive or ignitable mixtures.
Class II Locations
Class II locations are those that are, or may become, hazardous because of the presence
of combustible dust.
Division 1 Locations
Division 1 locations are those in which flammable or ignitable gases, vapors, or combustible dusts and particles can exist due to the following conditions:
• Normal operating conditions.
• Because of repair, maintenance conditions, leakage, or where mechanical failure or
abnormal operation of machinery or equipment might release or cause explosive or
ignitable mixtures to be released or produced.
• Combustible dusts of an electrically conductive nature may be present in hazardous
quantities.
52
Note
Xycom Automation systems are not suitable for installation within Division 1 locations.
Note
Electrical equipment cannot be installed in Division 1 locations unless it
is intrinsically safe, installed inside approved explosion-proof enclosures, or installed inside approved purged and pressurized enclosures.
Division 2 Locations
Division 2 locations are listed below:
• Class I volatile flammable liquids or flammable gasses are handled, processed, or
used, but confined within closed containers or closed systems from which they can
escape only in cases of accidental rupture or breakdown of such enclosures or systems, or in case of abnormal operation of equipment.
• Ignitable concentrations of Class I vapors or gasses are normally prevented by posi-
tive mechanical ventilation, but which may become hazardous due to mechanical
failure of those ventilation systems.
• Location is adjacent to a Division 1 location.
• Class II combustible dust is not normally in the air in quantities sufficient to produce
explosive or ignitable mixtures. Dust accumulations are normally insufficient to interfere with normal operation of electrical equipment or other apparatus. Combustible dust may be in suspension in the air as a result of the following: infrequent malfunctioning of handling or processing equipment; combustible dust accumulations
on, or in the vicinity of electrical equipment; may be ignitable by abnormal operation
or failure of electrical equipment.
Group Ratings
All electrical equipment that is approved for use in hazardous locations must include a
group rating. Various flammable and combustible substances are divided into these
groups as a function of their individual maximum experimental safe gap (MESG), explosion pressure, and ignition temperature.
Component temperatures and the potential for spark based upon voltage, current, and
circuit characteristics, within electrical equipment, will determine what the equipment
group rating will be. A device approved for installation within Class I, Group A locations
may also be used in Groups B, C, or D.
Approved Class I equipment may not be suitable for Class II installations. Class I includes Groups A, B, C, and D. Class II includes Groups F
and G.
Note
53
3408/3410/3412 Series Industrial PC System Manual
Enclosures
The systems are designed to be installed within clean and dry enclosures for both ordinary and hazardous locations. The front panel meets the requirements of UL and CSA
Type 4, 4X, and 12 enclosures. The enclosure used for Class I hazardous locations
should have a minimum rating of Type 12 (NEMA 12, IP 5X). However, Type 4 (IP 6X)
enclosures are strongly recommended.
Panel flatness and rigidity are important to maintain a proper panel seal. If you are going
to use non-metal type enclosures, such as plastic or fiberglass, install a rigid metal stiffener behind the front panel. Failure to do so may result in an inadequate panel seal due to
flexure of the front panel material between the stud mounts. Tighten the nuts on the
mounting studs per the instructions in the previous section, “Mounting the Unit.”
Requirements for enclosure fittings, conduit, and wiring vary according to the specific
rating of the location and the type of flammable or combustible material involved. Those
requirements are beyond the scope of this document. It is the customer’s responsibility to
ensure that the installation is compliant with codes and regulations that apply to the specific location. Reference NFPA 70, Article 500 for specific regulations in the United
States.
Power Sw itch
The systems do not have a power switch. The amount of input power required by these
systems classifies the power switch as an incendiary device because the voltage and current across the make/break device are capable of creating a spark.
Hazardous location regulations state that a power switch rated for ordinary locations may
be used if it is located in a non-hazardous area. However, limits in cable length between
the workstation and the power switch may apply. Otherwise, the switch must be compliant with Class I, Division 1 requirements (intrinsically safe). These switches are built in
a manner that prevents the possibility of a spark when contacts are made or broken.
Use suitable UL-listed and/or CSA-certified Class I, Division 1 switches in hazardous
locations. These switches are available from a number of sources. It is the customer’s responsibility to ensure that the power switch selected for the installation has the correct
hazardous location rating for the location in which it is installed.
Cable Connections
Division 2 hazardous location regulations require that all cable connections be provided
with adequate strain relief and positive interlock. Never connect or disconnect a cable
while power is applied at either end of the cable.
All communication cables should include a chassis ground shield. This shield should include both copper braid and aluminum foil. The D-sub style connector housing should be
a metal conductive type (e.g., molded zinc), and the ground shield braid should be well
terminated directly to the connector housing. Do not use a shield drain wire.
54
The outer diameter of the cable must be suited to the inner diameter of the cable connector strain relief to ensure that a reliable degree of strain relief is maintained. Always
secure the D-Sub connectors to the workstation mating connectors via the two screws located on both sides.
Never connect or disconnect the communication cables while power is
applied at either end of the cable. This may result in an incendiary spark.
Permanent damage to the workstation communication components may
occur.
Operation and Maintenance
The systems have been designed to comply with relevant spark ignition tests. However,
the workstation front panel membrane switches are the only make/break components intended to be used by the operator in normal operation.
To maintain a safe condition, do not use an external keyboard or mouse
when the unit is operating in a hazardous environment.
Warning
Warning
Always observe the following rules with respect to hazardous location installations:
1. Always install the workstations within an enclosure suitable for the specific applica-
tion. General-purpose enclosures may be acceptable for Class I applications, but are
never acceptable for Class II applications. Type 4 (IP 65) enclosures are recommended even when not required by regulations.
2. Keep enclosure doors or openings closed at all times to avoid the accumulation of
foreign matter inside the workstation.
3. Never subject the unit to any installation or service procedures unless power is re-
moved and the area is non-hazardous. This includes installing or removing power
cables or communication cables, or removing the unit’s back cover.
4. Only technically qualified service personnel should perform installation and service.
These workstations are designed to require no service in the course of normal operation by an operator.
55
3408/3410/3412 Series Industrial PC System Manual
Safety A gency A pprov al
The 3408, 3410 and 3412 systems have been designed to meet the following standards:
• Underwriters Laboratories Inc., UL 1604 Standard for Safety
Electrical equipment for use in Class I and Class II, Division 2, and Class III hazardous (classified) locations
•Underwriters Laboratories Inc.,UL 1950
Information Technology Equipment
• Canadian Standard Association, Specification C22.2 No. 213-M1987
Non-incendiary electrical equipment for use in Class I, Division 2 hazardous locations
• Canadian Standards Association, Specification C22.2 No. 950
The 3408KP, 3410KP and 3412KP include function/alpha, control/alpha, numeric, and
cursor control keypads.
Control Keypad
3408KP
This keypad provides seven control keys, six alpha keys (U-Z) and the space and + keys.
CTRL, SHIFT, INS, ALT, TAB, DEL, SPACE, and + keys provide the same functions as they
The
do on a standard PC/AT-compatible keyboard.
Six of the keys are relegendable, as shown in Figure 4 -1. Refer to the Creating Custom-ized Keypad Inserts section in Chapter 3 for detailed information.
3410KP/3412KP
This keypad provides seven control keys, and the space and + keys. The CTRL, SHIFT, INS,
ALT, TAB, DEL, SPACE, and + keys provide the same functions as they do on a standard
PC/AT-compatible keyboard. Six of the keys are relegendable, as shown in Figure 4 -2.
Refer to the Creating Customized Keypad Inserts section in Chapter 3 for detailed information.
57
Figure 4-1. 3408KP Control/Alpha Keypad
3408/3410/3412 Series Industrial PC System Manual
Figure 4-2. 3410KP Control Keypad
Alternate Configuration
The workstation comes with an alternate insert that you may use for these six relengendable keys. This alternate insert replaces the PC control key labels with function
key labels. Your unit is shipped with batch files (see Batch Utility Mode in Chapter 5)
that you can use with the keypad utility to re-map the keys.
Function and Alpha Modes
The F/A key is unique to the 3408KP and 3410KP units. When you press and hold this
key, the keypad switches to alpha mode. This allows you to access the alpha characters
A-Z, as well as punctuation symbols on 3410KP units (as noted in the blue letters located
in the bottom right-hand corner of the keys).
On 3408KP units, the default setting for alpha characters is uppercase. If
you want to use lowercase alpha characters, you must reprogram the
keypads using the keypad utility (refer to Chapter 5 for more detailed information).
When the F/A key it is not being pressed, the keypads are in function mode (as noted in
the white letters located in the top left-hand corner of the keys).
On 3408KP units, you cannot access the CTRL, SHIFT, INS, ALT, TAB, and
DELkeys in alpha mode. This means that you cannot use these keys in
combination with alpha keys (for example, you cannot use the CTRL+C
key combination).
Note
Note
58
Contrast Control
You can use the cursor control keys in conjunction with the F/A key to control the contrast on 3408KP passive color flat-panel display units. To do this, hold down the
while pressing a cursor control key.
Numeric Keypad
The numeric keypad features numbers 0-9, plus the decimal and minus sign characters.
F/A key
Figure 4-3. Numeric Keypad
Cursor Control Keypad
The cursor control keypad features 10 cursor control keys: BACKSPACE, PREV, NEXT, ESC,
ENTER, HOME (the center key), and the up, down, right, and left arrow keys.
You can use the cursor control keys in conjunction with the F/A key to control the contrast on 3408KP passive color flat-panel display units.
Figure 4-4. Cursor Control Keypad
59
3408/3410/3412 Series Industrial PC System Manual
Function/Alpha Keypads
3408KP
The 20 function/alpha keys (F1-F20, A-T,) on the 3408KP are relegendable. Refer to the
CreatingCustomized Keypad Inserts section in Chapter 3 for detailed information.
3410KP
Figure 4-5. 3408KP Function/Alpha Keypads
The 32 PF/function/alpha keys (PF1-PF12, F1-F20, and A-Z and punctuation symbols) on
the 3410KP are relegendable. Refer to the Creating Customized Keypad Inserts section
in Chapter 3 for detailed information.
PF1-PF6 keys are equal to CTRL+F1 through CTRL+F6. PF7-PF12 are equal to ALT+F1
The
through ALT+F6.
60
Figure 4-6. 3410KP PF/Function/Alpha Keypads
61
3408/3410/3412 Series Industrial PC System Manual
Chapter 5 - – Keypad Utility
3408KP/3410KP/3412KP
Note
The information in this chapter does not apply to units running the Windows CE operating system.
The Keypad Utility lets users redefine all keypad keys with new scan codes using utility
software. Use an external full-stroke PC/AT keyboard to access the utility (you cannot
redefine the keyboard).
The keypad switch arrays are disabled while the k ey pad utility is running.
Loading the Keypad Utility
You need MS-DOS 3.2 or higher to run the keypad utility. It will not
work if you are running Windows 95 or Windows NT. However, the
keypad utility will run under Windows 95 in DOS mode.
You can run this utility directly from the disk or copy it onto your hard drive. To run the
keypad utility from the disk, change the directory to the appropriate drive and type
kputil. To load the utility onto your hard drive, create a subdirectory for the files, and
copy all the files on the disk into that subdirectory. Enter the subdirectory and type kpu-til.
Using the Keypad Utility
Note
Note
62
The keypad utility uses a menu bar and pull-down menu system. All menu bars are displayed across the top of the screen. “Xycom KP Utility” and the current menu titles are
shown at the bottom of the screen (see Table 5-1). A full-stroke keyboard is needed to
enter keystrokes while recording a new key macro, editing an existing macro, and enter-
ing utility commands. You can redefine all keys on the keypads. While the utility is running, the keypads are disabled.
Dialog boxes appear for user prompts and to display error and user advice messages.
Two keys allow you to exit the menus:
•
ESC moves to the previous menu or out of the utility from the Main Menu.
F1 returns to the current menu headings in some of the menus where Exit can be cho-
•
sen to exit this menu.
Keys specific to each menu are shown at the bottom of each screen.
Startup
Type kputil to run the full keypad utility.
Utility Batch Mode
You can also use a batch file to reprogram keypads. This feature is useful if you wish to
reprogram many units with customized keypad macros without having to enter the full
keypad utility for each unit. Once the full utility has been used to create and save keypad
macros, the files containing these macros can be included on a disk with the keypad utility and then used to reprogram other units from a batch file.
The command keypad filename runs the keypad utility batch mode. “Filename”
is the file containing the new keypad macros. The filename extension must be included.
For example, in a batch file, the command keypad def3408PC.pkm or3408HMI.pkm would reprogram the keypad on the 3408KP with default values for the
numeric keypad. After programming, the system will reboot.
Main Menu
Table 5-1 illustrates the Main Menu.
ExitFilesMacrosUploadDownloadUtilities
Xycom KP Utility: MAIN L-Arrow, R-Arrow, Enter
Table 5-1. Main Menu
63
3408/3410/3412 Series Industrial PC System Manual
Exit
Exit closes open files and exits the utility. ESC can also be used for this purpose and for
exiting the other menus.
Files Menu
You can save files containing keypad macro sets (a macro for each key) on disk, and then
loaded them into memory to view, edit, teach, or download to the keyboard controller.
Some of these files may be included in the utility package for use in reconfiguring the
keypads for different software packages, and as templates for defining completely new
keypad macro sets.
When you choose Files, a pull-down menu displays that provides the following choices:
Open, Close, Save, Save As, Delete, and Exit. The following table describes the menu
commands.
CommandDescription
OpenOpens a file that contains a macro set for the keypad and loads the con-
tents into memory. Any macro set in memory is overwritten. Once loaded,
the macro set is available to edit, view, teach, or download to the keyboard controller.
CloseClears the macro set from memory and closes the file from which they
came.
SaveCopies the macro set from memory back into its original file. The original
file contents are overwritten.
Save AsCreates a new file under the specified name and copies the macro set
from memory into it. For example, to define different sets of codes, save
each set under a different name and download the one you wish to use.
DeleteDeletes a file.
ExitReturns to the Main Menu.
Macros Keypad Type Menu
When you select Macros, a pull down menu displays and provides the following choices:
Function Keys, Alpha Keys, and Exit. Also, another pull down menu displays the following choices once the Macros menu is chosen: Exit, View, Teach, and Edit.
You must have a macro file in memory before the Macros Menu is available. To load a macro file, Open a file or Upload macros.
CommandDescription
Function KeysSelects the function keys on the keypad to either view, edit, or teach.
Alpha KeysSelects the alpha keys on the keypad to either view, edit, or teach.
ExitReturns to the main menu.
64
Note
Macros Edit Menu
CommandDescription
ExitReturns to the Main Menu.
ViewLets you view, but not edit, the macro for the selected key. When View is chosen, the
Exit option is displayed on the menu bar and a graphic representation of the chosen
keypad is shown. Select Exit from the View Menu to return to the Macros Menu. To
select a key to view, use the arrow keys to position the cursor on the desired key and
ENTER. The macro is displayed as two lines: ASCII and code. The ASCII line
press
displays each keycode as the keys it represents on the full-stroke keyboard. Special
labels are used for certain keys (e.g., Spc for space bar, UAr for up arrow, and bk for
the break code prefix). The code line is displayed in either Hex or decimal. There is a
one-to-one correspondence between the ASCII and code lines.
While viewing the macro, the menu bar displays two options: Exit and Hex/Decimal.
Exit returns to the View Menu, while Hex/Decimal toggles between displaying the
macro in hex or decimal format. When Hex is chosen, the keycodes are displayed as
hexadecimal value scan codes. When Decimal is chosen, the keycodes are displayed
as the decimal equivalent of the hex codes.
For example, the macro abc would be displayed as 1C F0 1C 32 F0 32 21 F0 21 in
hex, and 28 240 28 50 240 50 33 240 33 in decimal.
TeachAllows you to record up to 105 keystrokes in a macro. When selected, a graphic rep-
resentation of the keypad currently in memory displays. Menu bar choices are Exit,
ASCII/Hex/Decimal, and Click ON/OFF. Exit returns to the Macros menu.
ASCII/Hex/Decimal specifies the format to display the keystrokes as they are entered.
Default is ASCII. Click is not supported.
To select a key to define, use the arrow keys to position the cursor on the desired key
and press
ternal full-stroke keyboard in a macro assigned to the chosen key. As the keys are
entered, they are displayed using the chosen format.
to the Teach Menu, so you cannot record the
in a macro by using the editor. Changes made to the macros in the Teach Menu are
not programmed until you select Download.
ENTER. After you select a key, the utility records every keystroke on the ex-
ESC stops recording and returns
ESC key. However, ESC can be included
65
3408/3410/3412 Series Industrial PC System Manual
CommandDescription
EditDisplays a graphic representation of the keypad in memory and a menu bar displaying
Exit, Click, and ON/OFF. Exit returns to the Macros menu. Click is not supported. To
select a key to edit, use the arrow keys to position the cursor on the desired key and
ENTER.
press
In edit mode, the macro is displayed as two lines. The top line (the edit line) displays
the macro in either hex or decimal format and is the line in which the editing takes
place. The bottom line displays the macro in ASCII format; it is not user configurable.
This line keeps track of which part of the macro you are editing, and is updated by the
utility as editing takes place.
The insert, delete, and cursor control keys are active for editing. When a key is selected from the Edit Macro option, the menu bar displays the following choices: Exit,
Cut, Copy, Paste, Codes, Hex/Decimal, and I/O (Insert/Overtype). The macro for the
chosen key is also displayed.
Cut deletes a sequence of scan codes from the macro. To select a section to cut:
1. Place the cursor on the first character to cut.
2. Press
3. Press
F1 and selectCUT.
ENTER. Cut should still be highlighted, but the cursor will appear on the Edit
line. Move the cursor on the last character to cut and press
ENTER.
The last character of every macro is the end of the macro (EOM) and cannot be deleted.
Copy copies a sequence of scan codes from the macro into memory. To select the
section to copy:
1. Place the cursor on the first character to copy. Press F1 and select Copy.
2. Press
ENTER. Copy should still be highlighted, but the cursor will appear on the
Edit line.
3. Move the cursor on the last character to copy and press
The copied item does not appear on the screen until you select
ENTER.
Paste.
Paste inserts a sequence of scan codes (which were saved in memory using Copy)
into the macro. To paste a sequence of scan codes that were previously copied, position the cursor where you want the text to appear and then press
then press
ENTER. Codes displays a table of keys and their scan codes in Hex. See the
F1. Select Paste and
Codes section in this chapter for a complete code listing. Hex/Decimal toggles between displaying the scan codes in Hex and Decimal formats. Insert toggles between
insert and overtype mode.
Upload Menu
Use the Upload Menu to choose which data to load. Choices in this menu are: Combo
Keypad, Keypad Version, and Exit.
CommandDescription
Combo KeypadCommands the keyboard controller to send its entire macro set for the keypad.
Keypad VersionCommands the keyboard controller to send its firmware revision number.
ExitReturns to the Main Menu.
Note
Only one macro set may reside in memory at one time.
66
A checksum will be calculated during transmission. If an error occurs, an error message
will display.
Download Menu
When you select Download, any macro set previously programmed is
overwritten.
Download sends the set of keypad macros to the keyboard controller. The macro set must
reside in memory before it can be downloaded. A checksum is calculated during transmission and an error message displays if an error occurs.
As the macro is sent, keyboard controller programs its non-volatile memory with the new
macros which become the new key definitions for the keypad. After programming, the
system will reboot.
Utilities Menu
When Utilities is selected, a menu bar displays four choices: Func Lock ON, Func Lock
OFF, Clear EEPROM, and Exit.
Note
CommandDescription
Func Lock ONNot available on the 3408KP and 3410KP.
Func Lock OFFNot available on the 3408KP and 3410KP.
Factory DefaultReprograms the keypad macros to the factory default settings. After
completion, the system will reboot.
ExitReturns to the Main Menu.
67
3408/3410/3412 Series Industrial PC System Manual
Keypad Scan Codes
Tables 5-2 through 5-8 list the default keypad scan codes produced by the keypad utility.
Table 5- 2. Keypad Codes for Lowercase Letters
KeyEdit Mode in Macros Edit MenuMake CodeBreak Code
If you make any changes to your keypad and want to set it back to the
default settings, open the file titled DEF3408PC.PKM orDEF3408HMI.PKM from the File/Open menu and then download it
from the download menu. Do not save any changes to the default files.
72
Table 5- 9 Keypad Codes for Function Keys F21-F40 or PF1-PF20
SymbolEdit Seq.AT
AT BreakXT MakeXT Break
Make
F21 or PF1FF 1514 05F0 05 F0 141D 3BBB 9D
F22 or PF2FF 1614 06F0 06 F0 141D 3CBC 9D
F23 or PF3FF 1714 04F0 04 F0 141D 3DBD 9D
F24 or PF4FF 1814 0CF0 0C F0 141D 3EBE 9D
F25 or PF5FF 1914 03F0 03 F0 141D 3FBF 9D
F26 or PF6FF 1A14 0BF0 0B F0 141D 40C0 9D
F27 or PF7FF 1B14 83F0 83 F0 141D 41C1 9D
F28 or PF8FF 1C14 0AF0 0A F0 141D 42C2 9D
F29 or PF9FF 1D14 01F0 01 F0 141D 43C3 9D
F30 or PF10FF 1E14 09F0 09 F0 141D 44C4 9D
F31 or PF11FF 1F11 05F0 05 F0 1138 3BBB B8
F32 or PF12FF 2011 06F0 06 F0 1138 3CBC B8
F33 or PF13FF 2111 04F0 04 F0 1138 3DBD B8
F34 or PF14FF 2211 0CF0 0C F0 1138 3EBE B8
F35 or PF15FF 2311 03F0 03 F0 1138 3FBF B8
F36 or PF16FF 2411 0BF0 0B F0 1138 40C0 B8
F37 or PF17FF 2511 83F0 83 F0 1138 41C1 B8
F38 or PF18FF 2611 0AF0 0A F0 1138 42C2 B8
F39 or PF19FF 2711 01F0 01 F0 1138 43C3 B8
F40 or PF20FF 2811 09F0 09 F0 1138 44C4 B8
73
3408/3410/3412 Series Industrial PC System Manual
Chapter 6 - Maintenance
The 3408, 3410 and 3412 units are designed to withstand the harsh environment of the
factory floor. However, preventive and routine maintenance will help keep the system in
good operating condition.
Preventive Maintenance
Preventive maintenance consists of several basic procedures that will reduce the chance
of system malfunction. Schedule preventive maintenance along with the regular equipment maintenance to minimize down time.
Following are some preventive measures you can take:
• Clean the screen using a non-residue cleaner such as a mild window cleaning solu-
tion or CRT screen cleaner. Take care not to scratch or mar the screen face.
• Base your maintenance schedule on the type of environment the system is in (i.e., if
the area is dusty, schedule maintenance more often than if it is a dry, clean area).
• Remove dust and dirt from PC components. If dust builds up on heat sinks and cir-
cuitry, an obstruction of heat dissipation could cause the unit to malfunction. If dust
reaches the electronic boards, a short circuit could occur.
• Check connections to I/O modules, especially in environments where shock could
loosen the connections. Check all plugs, sockets, and module connections.
• Remove unnecessary articles, such as drawings or manuals, from the unit. They can
obstruct air flow and create hot spots, which causes the system to malfunction.
• Do not place noise-generating equipment near the unit.
• Replace the module with the correct type. If the new module solves the problem but
the failure reoccurs, check for inductive loads that may be generating voltage and
current spikes and may require external suppression.
Xycom Recommended Hard Drive Preventative Maintenance
Xycom Automation has recognized that hard drive failures may begin to increase an average of four to five years into the life of most computers used in industrial applications.
Therefore, it is our recommendation as a preventative maintenance measure that all hard
drives used in these types of applications be replaced before the four to five year time period to avoid any down time related to hard drive failure.
The purpose of this message is to merely bring this to our customer’s attention, to offer
alternative solutions, and to provide all of our customers with the excellent service they
deserve.
74
Any questions regarding this issue may be directed to our support center at
support@xycom.com.
Please note Xycom recommends frequent back ups of your hard drive, especially before beginning any
preventative maintenance procedures.
Replacing the Fuse
The 3408, 3410 and 3412 units have no accessible fuse. Return the unit to Xycom Automation for fuse replacement.
Chemical Compatibility
Certain combinations of chemical environments, temperature, and stress can adversely
affect parts made from thermoplastic resin. For this reason, material which may come in
contact with 3408/3410/3412 units should be carefully evaluated under end-use conditions for compatibility. You should also follow the use and compatibility recommendations of the material manufacturer.
Table 6-1 lists general chemical compatibility guidelines.
Table 6 -1. Chemical Compatibility
Chemical ClassEffects
AcidsNo effect under most common conditions of concentration
and temperature.
AlcoholsGenerally compatible at low concentration and room tem-
perature. Higher concentrations and elevated temperatures
result in etching and attack evidenced by decomposition.
AlkalisGenerally compatible at low concentration and room tem-
perature. Higher concentrations and elevated temperatures
result in etching and attack evidenced by decomposition.
Aliphatic HydrocarbonsGenerally compatible
AminesSurface crystallization and chemical attack. Avoid.
Aromatic HydrocarbonsPartial solvents and severe stress cracking agents. Avoid.
Detergents and cleanersMild soap solutions are compatible. Strong alkaline materi-
als should be avoided.
EstersCauses severe crystallization. Partial solvents. Avoid.
Greases and oilsPure petroleum types generally compatible. Many additives
used with them are not compatible.
Halogenated Hydrocar-
bons
KetonesCauses severe crystallization and stress cracking. Partial
Silicone oil and greasesGenerally compatible up to 85º C (185º F). Some contain
Solvents. Avoid.
solvents. Avoid.
aromatic hydrocarbons which should be avoided.
75
3408/3410/3412 Series Industrial PC System Manual
Compatible Lubricants
Table 6 -2 lists known compatible lubricants and the manufacturers’ names. If you want
to use a lubricant that is not listed in the table, contact the appropriate manufacturer to
determine compatibility.
Gulf Oil
Petroleum Prod. Dept.
Pittsburgh, PA 15230
(412) 655-6247
Fisher Bros. Refinery
129 Lockwood Street
Newark, NJ 07105
303 W. Lehigh Ave.
Philadelphia, PA 19133
(215) 666-4000
Wm. J Nye
P.O. Box G-927
New Bedford, MA 02742
(617) 966-6721
GE
Silicone Products
Waterford, NY 12188
(518) 237-3330
P.O. Box 2180
Houston, TX 77092
(713) 680-5712
76
Compatible Cleaning Agents
Table 6-3 lists known compatible cleaning agents. If you want to use a cleaning agent
that is not listed in the table, contact the appropriate manufacturer to determine compatibility.
Table 6 -3. Compatible Cleaning Agents
TypeAgents
AliphaticsHexane, Heptane, White Kerosene Mineral Spirits,
AlcoholsMethyl, Isopropyl and Isobutyl, 1 + 3 Denatured Alco-
Halogenated hydrocarbonsFreons TF & TE
Detergents and cleanersMild Soap and Water Solution, VM&P Naphtha Fan-
Compatible aliphatics, alcohols, and halogenated hydrocarbons should be used only for
wiping or short-term immersion (less than 10 minutes). If parts are in complete immersion, remove all traces of solvent by forced-air drying or rinsing in hot water.
Non-compatible Cleaning Agents
Petroleum Ethers (65º C boiling point)
hol
tastik®, Windex®, Joy®, Top Job®, Mr. Clean®, Formula 409®
Table 6-4 lists cleaning agents known to be detrimental.
Stock spare parts to minimize down time resulting from part failure. The spare parts
stocked should be 10 percent of the number of each unit used. Main CPU cards should
have one spare each. Each power supply should have a back-up. In applications where
immediate operation of a failed system is required, you may need to stock an entire spare
computer module.
Table 6 -4. Non-Compatible Cleaning Agents
ide, Sodium Hydroxide
lethylketone
77
3408/3410/3412 Series Industrial PC System Manual
Table 6-5 provides a list of spare parts along with their Xycom Automation part numbers.
Table 6 -5. 3408/3410/3412 Spare Parts List
DescriptionXycom Automation
Front Panel Assembly
3408T
3408KP
3410T
3410KP
3410KPT
3412T
3412KP
3412KPT
Hard Drive
2.5-inch IDE
8 MB Flash
16 MB Flash
24 MB Flash
48 MB Flash
CHIP4e+ 133 MHz CPU board130034-001
DRAM
4M x 32(16 Mbytes)
8M x 32(32 Mbytes)
16M x 32 (64 Mbytes)
Replacement Bulb Assembly
3408 STN
3410 TFT
3412 TFT
AC Input Power Connector99711-001
External Floppy Kit (9000-EXF)116074-001
Part Number
129969-001
129971-001
130589-001
130548-001
130563-001
139680-001
139681-001
139682-001
129984-001
139626-001
139640-001
139677-001
139678-001
104302
106054
123514
130021-001
121663-001
125155-001
Product Repair Program/Returning a Unit to Xycom Automation
Xycom Automation’s Product Repair and Customization Department (PR&C) restores
equipment to normal operating condition, and implements engineering changes that enhance operating specifications. Returned products are tested with standard Xycom
Automation test diagnostics.
Follow the steps below to prepare the unit for shipment:
1. Obtain an RMA number for your unit by calling your nearest Xycom Automation
Repair Department or Xycom Automation at 1-800-289-9266 or 734-429-4971.
Please have the following information available:
•Company name and shipping and billing addresses
78
• Type of service desired: product repair or product exchange
• Product model number, part number, quantity, serial number(s), and warranty
status
• Failure mode and failure systems
• Purchase order number or repair order number
2. Make sure the front panel assembly is properly attached to the unit.
3. Attach failure information to the unit to speed processing.
4. Place the unit securely in its original packaging or an equivalent heavy-duty box.
5. Mark the RMA number on your purchase order and on the outside of the box.
6. Send the unit to the address given when you receive your RMA number.
79
3408/3410/3412 Series Industrial PC System Manual
Appendix A– Technical Specifications
Hardware Specifications
Table A-1. Hardware Specifications
CharacteristicSpecification
Mechanical
3408T
Height
Width
Length
Weight
3408 KP
Height
Width
Length
Weight
3410T
Height
Width
Length
Weight
3410KP
Height
Width
Length
Weight
3412T
Height
Width
Length
Weight
3412KP(T)
Height
Width
Length
Weight
Electrical
AC Power
DC Power
Power Supply40 watts output
9.0" (front panel)
10.6" (front panel)
4.20" overall; 3.3" behind front panel
9 lbs
9.0" (front panel)
12.0" (front panel)
4.20" overall; 3.3" behind front panel
9 lbs
11.0” (front panel)
13.0” (front panel)
4.5” overall; 3.5” behind front panel
11 lbs
12.25” (front panel)
16.6” (front panel)
4.5” overall; 3.5” behind front panel
12 lbs
11.00”
13.00”
4.5” overall; 3.5” behind front panel
11 lbs
12.25”
16.5”
4.5” overall; 3.5” behind front panel
12 lbs
90 to 250 VAC, 50-60 Hz, autosensing
1A maximum at 90 VAC
18 to 36 V, 24 volts nominal
2.5 A maximum at 18 V
80
CharacteristicSpecification
Available PowerWith CHIP4e+ CPU board
+ 5 V @ .8 A
+12 V @ .25 A
-12 V @ .25 A
Total not to exceed 6 watts
MountingPanel Mount
Flat-Panel Display
3408s
3410s
Agency ApprovalsUL 1950
Regulatory
Compliance
25,000-hour half-life bulbs
7.7" STN passive color LCD
10.4-inch TFT active matrix color LCD
UL1604
CUL C22.2, No. 950
CUL C22.2, No. 213-M1987
FCC 47 CFR. Part 15, Class A
CE
Environmental Specifications
EMIEN55022, Class A
IMMUNITYEN50082-2:1995
SAFETYEN60950
Table 0-2. Environmental Specifications
CharacteristicSpecification
Temperature
Operating
Non-operating
Humidity
Operating
Non-operating
Altitude
Operating
Non-operating
Vibration (no rotating media)
Frequency
Operating
Non-operating
Shock (no rotating media)
Operating
Non-operating
0° to 50° C (32° to 122° F)
-20° to 60°C (-4° to 140°F)
20% to 80% RH non-condensing
20% to 80% RH non-condensing
Sea level to 10,000 feet (3048 m)
Sea level to 40,000 feet (12192 m)
This three-pin connector provides AC or DC input power to the unit.
Ethernet Connector
This eight-pin connector provides 10BASE-T and 100BASE-TX Ethernet connections.
PinSignal
1TX+
2TX3RX+
4Short to pin 5 75ohm to TERMPLANE
5Short to pin 4 75ohm to TERMPLANE
6RX7Short to pin 8 75ohm to TERMPLANE
8Short to pin 7 75ohm to TERMPLANE
PinAC SignalDC Signal
1L+DC
2N-DC
3AC_GNDGND
84
COM1 Connector
This nine-pin connector actually consists of two connectors (RS-232 and RS-485) attached to one logical port. Only one connector can be used at a time.
RS-232 Connector
The lower nine-pin connector provides the RS-232 protocol.
The upper nine-pin connector provides the RS-485 protocol.
PinSignal
1TXD2TXD+
3TXD TERM 4TXD TERM +
5GND
6RXD7RXD+
8RXD TERM +
9RXD TERM -
Note
For TXD termination, connect a 150Ω, ½-watt resistor from pin 3 to pin
4, with pin 1 connected to pin 3 and pin 2 connected to pin 4.
For RXD termination, connect a 150Ω, ½-watt resistor from pin 8 to pin
9 with pin 6 connected to pin 9 and pin 7 connected to pin 8.
85
3408/3410/3412 Series Industrial PC System Manual
COM2 Connector
You can configure this port for use with one of three separate devices: the touch screen
controller, infrared (IR, IrDA) interface, or RS-232 connector. The BIOS setup determines whether COM2 is used for the RS-232 connector or the IR interface. Jumpers on
the touch screen controller select the COM2 or mouse ports. When the touch screen
controller is jumpered for COM2, COM2 is unavailable for other use.
This connector also contains the remote system reset option. A normally open pushbutton switch can be connected to pins 11 and 7. When the switch is pressed, the
PB_RESET* signal is forced to GND, which causes the CPU to reset. To enable this option, you must set jumper J1 to position B.
Appendix C – Replacing Flat-Panel Display
Bulbs
This appendix describes how to replace the bulbs in your flat-panel display.
Note
Refer to the label on the back of your unit to determine which model you
have. If you are unsure which bulb to use, call Xycom Automation Customer Support at 800-289-9266.
power panel, 23
3410KP and 3410KPT Front Panel, 16
3410KP/3412KP, 57
3410KP/3412KP Cutout Dimensions, 49
3410KP/3412KP Keypad Inserts, 31
3410T
back panel, 21
cutout dimensions, 48
front panel, 13
I/O panel, 20
IR port, 14
power panel, 23
3410T/3412T Cutout Dimensions, 48
3412 Units, 91
3412KP Front Panel, 19
3412KPT Front Panel, 18
3465
display, 18
AC Power Cable, 39
AC power supply, 50
AC Power Supply, 50
agency approvals, 81
alpha keys, 15, 16
alpha mode, 15, 16
Alternate Configuration, 58
altitude, 81
back cover, 22
back panel, 21
Back Panel, 21
boards, PC/104, 26
bulbs, flat-panel display, 87
cable connections, 54
Cable Connections, 54
calibrating the touch screen, 39
Calibrating the Touchscreen, 38
chemical compatibility, 75
cleaning agents, 77
lubricants, 76
non-compatible cleaning agents, 77
Class I Locations, 52
Class II Locations, 5 2
cleaning agents
compatible, 77
non-compatible, 77
COM1
connector, 85
port, 20
COM1 Connector, 85
COM2
connector, 86
port, 20
COM2 Connector, 86
Compatible Lubricants, 76
Configuring the IDE Flash Drive, 94
connectors
COM1, 85
COM2, 86
Ethernet, 84
external floppy drive, 84
floppy drive, 23
parallel port, 82
power, 23, 84
PS/2 keyboard port, 83
PS/2 mouse port, 83
serial loopback, 11
UART1. See COM1
UART2. See COM2
contrast control
3400KP, 15, 59
3408/3410/3412 Series Industrial PC System Manual
3400T, 14
3410KP, 16
3410T, 14
control keys, 15, 16
control/alpha keypad, 57
creating a power cable, 39
Creating a Power Cable, 39
Creating Customized Keypad Inserts, 28
cursor control keypad, 59
Cursor Control Keypad, 59
cursor control keys, 15, 17
custom
keypad inserts, 28
logo:, 27
cutout dimensions
3400KP, 47
3400T, 46
3410KP, 49
3410T, 48
DC Power Cable, 40
DC power supply, 50
DC Power Supply, 50
Definitions, 52
diagnostic tests
user-defined, 19
LEDs, 14, 18, 19
line voltage variation, 43
Line Voltage Variation, 43
loading the PKIM utility, 62
logo, customized, 27
lubricants, compatible, 76
maintenance, 74
cleaning the unit, 77
hazardous locations, 55
Maintenance, 74
mounting
studs, 22
mounting considera t ions, 44
Mounting Considerations, 44
mounting the unit, 44, 81
Mounting the Unit, 44
mouse port, 20
Mouse Port Connector, 83
Noise, electrical, 43
numeric keypad, 5 9
Numeric Keypad, 59
numeric keys, 15, 17
operating systems, installation, 33
operation and maintenance, 55
Operation and Maintenance, 55
operation, hazardous locations, 55
panel installation, 42
panel mounting studs, 22
parallel port, 20
parallel port connector, 82
Parallel Port Connector, 82
PC/104 boards, 26
PC/104 Boards, 26
pinouts
power supply, 80
Specifying a Touchscreen Port, 36
Startup, 63
System Overview, 6
system power, 42
System Power, 42
system status LEDs, 18
Technical Specifications, 80
temperature, 81
Testing, 10
touch screen, 8
calibrating, 39
drivers, installation, 35, 36
using, 35
touchscreen, 36, 37
UART1. See COM1. See COM1
UART2. See COM2. See COM2
unit, returning, 78
Unpacking the System, 8
user-defined keys, 19
Using a Touchsc reen, 35
using the PKIM Utility, 62
Utility Batch Mode, 63
vibration, 81
video drivers, 34
Error! Cannot open file referenced on page 3
6-4
Xycom Automation, Inc.
734-429-4971 • Fax: 734-429-1010
http://www.xycomautomation.com
340002(C)
340002(C)
340002(C)340002(C)
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.