1.Parts and Functions
Speaker
Nameplate
Call Button
184 mm
124 mm
33 mm
Rainy Cover
2.Terminal Descriptions
ON
1 2
1 2 3
Lock Control Jumper:
Doorstation Code DIP:
Main Connect Port:
To select the lock type: see 5.2.1 , 5.2.2
Total 4 doorstations can be supported,see 6.1
To connect the bus line and the electronic locks.
• BUS: Connect to the bus line, no polarity.
• PL: External lock power input, connect to the power positive(power +).
• S1+, S2+: Lock power(+) output, to connect 2 locks.
• S-: Lock power(-) output, connect to the power(-) input of locks(only when using the camera to power the locks, if using the external power supply for the locks, the S- will not be connected).
Main Connect Port
Doorstation Code DIP
Lock Control Jumper
-1-
4.Mounting
4.1 Mounting Without Rainy Cover
4
PM 3×8 mm
1
2
PA 4×40 mm
1
2
4.2 Mounting With Rainy Cover
1 2 3
1
2
PM 3×8 mm
PA 4×40 mm
3
3
4
3
1
PM 3×8 mm
2
-2-
4.3 Placing Name Label
Press down and move the name label to the right side, then take off the cover. Place the name paper between the cover and the transparent plastic base.then put the cover back to the panel.
5.System Wiring and Connections
5.1 Basic Connection
BUS PL S1+ S2+ S-
monitor
DPS PS4
-
+
-3-
5.2 Electric Lock Connection
connect one lock
connect two locks
5.2.1 Door Lock Controlled with Internal Power
Note:
1. Electronic lock of Power-on-to-unlock type should be used.
2. The door lock is limited to 12V, and holding current must be less than 250mA.
3. The door lock control is not timed from Exit Button(EB)
4. The
Unlock Mode
Parameter of Monitro must be set to 0 (by default)
connect two locks
1 2 3
Jumper position in 1-2
BUS PL S1+ S2+ S-
EB
BUS PL S1+ S2+ S-
-
+
EB
EB
5.2.2 Door Lock Controlled with Dry Contact
Note:
1. The external power supply must be used according to the lock
2. The inside relay contact is restricted to AC or DC 24V/3A
3. The jumper must be taken off before connecting
4. Setup the
Unlock Mode
• Power-on-to-unlock type:Unlock Mode=0 (by default)
• Power-off-to-unlock type:Unlock Mode=1
connect one lock
Take off the Jumper
BUS PL S1+ S2+ S-
of Monitor for different lock types
1 2 3
BUS PL S1+ S2+ S-
1 2 3
Jumper position in 1-2
-
lock #2
+
-
lock #1
+
1 2 3
Take off the Jumper
+
-
Power supply
+
+
-
+
-
Power supply
lock #2
-
+
lock #1
-
-4-
5.2.3 How to setup the unlock parameter in Monitor
monitor
intercom
setup
exit
1.Press MENU button two times to enter th e MAIN ME NU page ,t hen press setup item
Unlock Time 1
Unlock Mode 0
Exit
6.Use item, use
/ to select the
/ to change the value of the item.select Exit it em,pres s MENU butto n to save the settings automatically.
Outdoor Tone -- 01
Intercom Tone -- 05
Monitor Time -- 1min
Advanced Set...
Auto Record -- OFF
Exit
2 . S elec t Adv a n ced Set ... item and pre ss MENU button to enter,a password will be asked
Hardware ver 0302
Software ver 0168
Voltage 22.4V
Manufacture 00.0T
Restore to default
Exit
5.Press UNLOCK button and hold for 2s
Password:
0
* * *
3.The default password is 2008 press decrease the value,Press
/ button to increase/
/ button to select the location,after finishing,press MENU button to enter next step.
Slave Addr Set -- 0
Guard Unit Set -- 0
Date/Time Set...
Other Settings...
Information...
Exit
4.Select Information...item and press MENU button to enter next page.
Note:
must connect DPC-D242 correctly before setting
•
the parameter will be saved in DPC-D242 automatically,so you need only set on one monitor
•
-5-
5.3 Multi Doorstations Connection
monitors
4# Camera
BUS PL S1+ S2+ S-
ON
1 2
3# Camera
BUS PL S1+ S2+ S-
ID=01ID=11
ON
1 2
DBC4
BUS
2# Camera
BUS PL S1+ S2+ S-
A B C D
ID=10
ON
1 2
1# Camera
BUS PL S1+ S2+ S-
DPS
ID=00
PS5
85~260VAC
ON
1 2
-6-
5.4 Multi Monitors Connection
5.4.1 Basic IN-OUT Wiring Mode
ON
1 2 3 4 5 6
Code=15, DIP-6=on
ON
1 2 3 4 5 6
Code=14, DIP-6=off
ON
1 2 3 4 5 6
Code=0, DIP-6=off
monitor
monitor
monitor
DPS
ID=00
ON
1 2
PS5
85~260AC
-7-
5.4.2 With DBC-4 Wiring Mode
ON
1 2 3 4 5 6
Code=15, DIP-6=on
monitor
ON
1 2 3 4 5 6
Code=14, DIP-6=on
monitor
HI
OUT
IN
DBC-4
A B C D
ON
1 2 3 4 5 6
Code=13, DIP-6=on
ON
1 2 3 4 5 6
Code=3, DIP-6=on
ON
1 2 3 4 5 6
Code=1, DIP-6=on
monitor
monitor
monitor
ON
1 2 3 4 5 6
Code=12, DIP-6=on
ON
1 2 3 4 5 6
Code=2, DIP-6=on
ON
1 2 3 4 5 6
Code=0, DIP-6=on
monitor
monitor
monitor
DPS
PS5
85~260AC
HI
OUT
IN
DBC-4
A B C D
-8-
ID=00
ON
1 2
6.Setup
ON(1)
ON
=
OFF(0)
ON
=
6.1 DIP Switches Settings of Doorstation
Total2bits ontheDIP switchescanbe congured.The switchescanbe modiedettherbeforeor after
installation.
Bit state Descriptions
1
1 2
ON
2
ON
ON
1 2
ON
1 2
Defaultsetting,ID=0(00),settotherstDoorStation.
ID = 1(10), set to the second Door Station.
ID = 2(01), set to the third Door Station.
ID = 3(11), set to the fourth Door Station.
6.2 DIP Switches Settings of Monitor
Thereare6bitswitchesintotal.TheDIPswitchesareusedtoconguretheUserCodeforeachMonitor.
Bit-6 is line terminal switch, which have to be set to ON if the Monitor is in the end of the line(bus), otherwise set to OFF.
Bit state Setting Bit state Setting
ON
1 2 3 4 5 6
The monitor is not at the e n d of the bus.
ON
1 2 3 4 5 6
The monitor is at the end of the bus.
-9-
Bit-1 to Bit-5 are used to User Code setting. The value is from 0 to 31, which have 32 different codes .
Bit state User Code Bit state User Code Bit state User Code
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
Code=0 Code=11 Code=22
Code=1
Code=2
Code=3
Code=4
Code=5
Code=6
Code=7
Code=8
Code=9
Code=10
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
Code=12
Code=13
Code=14
Code=15
Code=16
Code=17
Code=18
Code=19
Code=20
Code=21
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
Code=23
Code=24
Code=25
Code=26
Code=27
Code=28
Code=29
Code=30
Code=31
6.3 Notices
Name Discription Useage
PS5-24V
PS4-24V
Power supply,85~260Vac input,24Vdc/3A output,10 DIN modeules
Power supply,85~260Vac input,24Vdc/1A output,for basic kit only,4 DIN modules
-10-
Con nect with multi doorsta tions or multi monitors(up to 2 or above)
Co nnect wit h one door stat ion a nd one monitor(DT16 can be connected two)
7.Cables Requirements
The maximum distance of the wiring is limited in the DT system. Using different cables may also affect the maximum distance which the system can reach.
The farest monitor
monitor
with two or four monitors
monitor
When Monitor quantity < 20
Cable Usage A B C
2
Twisted cable 2x0.75 mm
Twisted cable 2x1 mm
60 60 30
2
80 80 40
When Monitor quantity > 20
Cable Usage A B C
2
Twisted cable 2x1 mm
Twisted cable 2x1.5 mm
Note:If the monitor has been specified the diatance,refer to the parameter.
70 30 20
2
70 50 30
monitor
C
DPS
DBC/DBC-4
B
PS5
A
-11-
8.Specication
Lock Power supply: 12Vdc, 250mA(Internal Power)
Power Consumption: 1W in standby, 5W in working
NO, COM dry contact: Max. 24V dc 3A
Unlocking time: 1 to 9 seconds, set by Monitor
Working temperature: -10ºC ~ 45ºC
Dimension: 184(H)×124(W)×33(D)mm
The design and specications can be changed without notice to the user. Right to
interpret and copyright of this manual are preserved.