Xmark XLX Users Manual

Have
you:
• Pulled network and power cable?
• Resolved power supply requirements?
• Selected Exciter orientation and position?
If you answered, “No,” to any of these questions, refer to the Hugs Installation Manual before installing.
Read these instructions thoroughly before installing the Exciter.
!
Faulty installation can lead to system failure.
Materials Required
Materials Required
• Exciter. Includes door contact, ferrite core (p/n 28A2029-0A2)
and terminal blocks.
• Facility fl oor plan indicating Exciter position and installation
orientation, and network wiring path.
• 105 network terminator (p/n 805A2401) required to terminate
network. Two provided with each Controller (p/n 805A2201) or Laptop Controller (p/n 805A2202).
• Suitable mounting hardware, such as wall anchors
• Optional: Passive infrared sensor for open doorways where door
contact cannot be used. Refer to Chapter 2 of the Hugs Instal-
lation Manual (p/n 805I0301) for important limitations on using PIR sensors.
Specifi cations
Specifi cations
Frequency 312.5 kHz
Supply 10-30 VDC
Current Draw 200 mA @ 24 VDC, 800 mA maximum
Relay Outputs (2) 30 VDC, 1 A, NO or NC
Detection radius Adjustable, up to 11 ft.
Communications LonWorks two-wire
Temperature - operating 32° to 122° F (0° to 50° C)
Large Exciter Instructions
Part Number 805A6201
Installation Considerations
Installation Considerations
Avoid metal—Do not install the Exciter behind or within 2 inches (50 mm) of metal objects, including metal doors. These objects block the detection area of the Exciter.
Use door contacts—Door contacts are required to minimize nuisance alarms.
Confi gure nearby Exciters as slaves—Exciters installed within 30 feet (9 m) of each other must be confi gured as master and slave. Up to four slaves may be connected to one master.
Use the supplied ferrite core—Wrap the power cable around the supplied ferrite core, as explained in the instructions. Failure to do so will void the user’s authority to operate the equipment.
Observe temperature and humidity restrictions—Refer to the Specifi cations table.
Leave slack in the cable—Leave at least 10 ft. (3 m) of slack in the communication and power cable to allow for adjustments in the location of the Exciter.
No user adjustments to internal circuitry—Tampering may cause component or system failure, or both, and will void the
warranty.
Temperature - storage -40° to 176° F (-40° to 80° C)
Humidity 0 - 90% RH @ 70° F (21° C)
Dimensions Approx 20.7 x 10.9 x 2.3 in. (526 x 275 x 60 mm)
Weight Approximately 6 lbs. (2.7 kg)
309 Legget Drive, Ottawa, ON K2K 3A3, Canada or 808 Commerce Park Drive, Ogdensburg, NY 13669 USA
Telephone: 1-613-592-4642 Facsimile: 1-613-592-4296 Web Site: www.xmarksystems.com
Important Reference Documents
Important Reference Documents
• Hugs Installation Manual (p/n 805I0301)
Refer to Chapter 2 of the Hugs Installation Manual for detailed information on detection areas, installation options, master/slave confi gurations and software settings.
• Hugs System Manual (p/n 805U1601)
• Exciter Tester Sheet (p/n 805U2101)
© 2002 Instantel Inc. All Rights Reserved. Instantel and Hugs are registered trademarks of Instantel Inc. in North America. The hearts logo and Xmark are trademarks of Instantel Inc. Xmark is a division of Instantel Inc. Printed in Canada. November 2002. 805U6201 Rev B.
Installing the Exciter
Installing the Exciter
• Ensure that the power supply and network are turned
!
off to prevent electrical shock or damage to equip­ment.
• Touch your hand to ground to discharge any electro­static charge before handling the Exciter.
1 Locate and record the LonWorks identifi cation number onto the
facility fl oor plan indicating the Exciter’s position and network wiring path. Use the tear-away sticker on the Exciter’s Neuron ID label.
2 Install the supplied door contact or PIR sensor according to the
manufacturer’s instructions and connect it to the terminal, as shown in the wiring diagrams. Connect the LonWorks Network IN, Network OUT, and Power Supply to the terminal blocks, as shown in the wiring diagrams. Wrap the Power Supply cable around Item B (ferrite core); DO NOT use substitutes.
If the Exciter is at the end of the network, then terminate the net-
work segment with Item A (105 terminator). Refer to Figure
1, and insert the terminals into the connectors on the Exciter.
Note: If installing keypads or accessory devices, or if using a
master/slave confi guration, proceed to the relevant sections on the opposite page, and then return to steps 3 and 4.
Installing Keypads
Installing Keypads
Refer to the wiring diagrams below and the manufacturer’s instructions. Keypads may be connected to either master or slave Exciter.
Notes:
• Either one Wiegand or two Corby keypads can be connected to an Exciter.
• The Wiegand and Corby keypads cannot be connected to the same Exciter.
• The Wiegand keypad requires a 12 VDC power supply; set the central Power Supply to 12 V for this application.
• Corby keypads may be powered at 12 or 24 VDC. If connected at 24 V, they require a 1 kW, 1/4 resistor connected between the power supply and each keypad LED. Refer to Figure 2 below.
Installing Accessory Devices
Installing Accessory Devices
Each Exciter has two 30 VDC, 1 Amp, NO or NC relays for con­trolling accessory devices, such as magnetic door locks and high output alarms.
Refer to the wiring diagrams and the manufacturer’s instructions for installation procedures. Devices may be connected to either master or slave Exciters; connect devices to the master Exciter’s relays fi rst, then connect additional devices to the slave Exciter, starting with the closest.
Note: Accessory devices require their own power supply.
Figure 1: Wiring the terminal block
3 Ensure that the status LED of the Exciter (located on the bottom
of the case) will be visible. Refer to the facility fl oor plan for location, and using the Exciter as a template mark the location of the four mounting holes. Drill the holes.
4 Mount the Exciter:
A Install in the four mounting holes:
4 hollow wall anchors
B Insert into the wall anchors, leaving 3/8 in. (0.5 cm) of the
shaft exposed:
4 No. 12 wood screws x 2 in. long
C If using surface wire conduit, attach the four supplied
bumpons (Item B in Figure 1) to the underside of the Exciter.
D Align the Exciter with the mounting screws, and while lightly
pressing, slide until it is securely in place. Insert the supplied screw caps.
Installation is complete. Proceed to Final Steps below.
Master/Slave Installations
Master/Slave Installations
Master and slave Exciters are installed and connected to the Lon­Works network in the same way as other Exciters, with the following additions:
• All Exciters in master/slave group are connected in series through their M/S and ground terminals using 20 AWG wire, as shown in the wiring diagrams.
For slave Exciters using their own ID numbers, the following is also required, as shown in Figure 2:
• The mag lock (or elevator hold) outputs are wired to the relays on both the master and the slave to ensure that all doors in the vicinity will lock when a tag is present.
• Door contacts are wired together in series to the door contact input on both the master and the slave. The result is that when any door in a master/slave confi guration is open, the system behaves as if all doors are open: an alarm will occur if a tag is at a door in the vicinity of a door that is open.
Final Steps
Final Steps
Do not supply power to the Exciter or any other network device until all connections are complete.
!
Once all devices are installed, power up the Exciter and other devices. In the Xmark software, run Auto Confi gure to install the new devices, and then confi gure them for operation.
The coverage area of each Exciter must also be checked.
Refer to the Hugs Installation Manual (p/n 805I0301) for detailed information on how to complete these steps.