EXI Wireless Systems, ConfidentialPage 5 of 33July 27, 1999
Page 6
“Halo” System: Communication Protocol970-00002-000
1. Document Purpose
This document describes a communication protocol used by “HALO” system.
This document is written after the system design has been finished and the objective is to describe structure
of the system protocol, not only to people directly involved in the software and firmware design but to
other technical personnel as well, involved in other aspects of system design, installation or technical
support.
EXI Wireless Systems, ConfidentialPage 6 of 33July 27, 1999
Page 7
“Halo” System: Communication Protocol970-00002-000
2. Introduction
“Hallo” system is specialized data gathering and control system which is using different communication
media and protocols to achieve its tasks. The system consists of several major building blocks – Host,
Controllers (Elevators, Receivers) and Tags.
Data that are gathered are information sent by the Tags.
The system can be used in different applications and some of them include:
• Patient monitoring (P-Tag)
This is primary application for the “Hallo” system. It can be used in the hospitals to prevent babies
abduction or to restrict movement for certain groups of patients that need to be monitored (e.g. Alzheimer
patients).
• Asset monitoring (A-Tag)
The “ Hallo” system can be used to prevent or warn of any unauthorized assets relocation (e.g. a notebook
computer which shouldn’t leave the room or the building).
• Distress monitoring (D-Tag)
In this application D-Tags are used to signal some abnormal situation and they are activated by person who
is carrying it. (e.g. a nurse threatened by a violent patient)
Each one of these Tags is using the same protocol and has virtually the same functionality within the
system. The difference is in peripheral sensing circuitry which will determine how are they activated. In
order to simplify this protocol description, all of them will be referred to just as Tags.
EXI Wireless Systems, ConfidentialPage 7 of 33July 27, 1999
Page 8
“Halo” System: Communication Protocol970-00002-000
RIM
RIM
RIM
RIM
Tag
Tag
Tag
Tag
Tag
Tag
Tag
Tag
Tag
3. System Architecture
The “Hallo’ system can be classified into the group of data gathering and control systems and its
components could be divided into 3 major groups:
• Host (Computer)
• Data gathering and control nodes (Controllers, Elevators, Receivers, Printer Interface, Programmers)
• Sensors (P-Tag, A-Tag, D-Tag)
Figure 1 shows how these units are organized within the system.
3.1. Host
Figure 1
Host PC
Controller
Elevator
Receiver
Receiver
The Host is Windows based User Interface running on a PC. It serves as a terminal from which the user can
monitor the system operation and exercise available controls. There can be only one Host and it is acting as
a Master device within the system. The Host must be equipped with the EIA-485 / EIA-232 converter in
order to be able to communicate to the rest of the system.
3.2. Data Gathering and Control Nodes
There are 3 types of the nodes in this group and they vary in their functionality, but one feature is common
among all of them; they are all able to communicate to the Tags and to the Host. These are two completely
different communication paths and will be examined in details in this document
EXI Wireless Systems, ConfidentialPage 8 of 33July 27, 1999
Page 9
“Halo” System: Communication Protocol970-00002-000
3.2.1. Controller
The Controller is used to monitor and control the area in which it is installed, usually near the door. It
generates the “field of coverage” around itself and any Tag entering this field will be registered by the
Controller (Tag In the Field (TIF) alarm). The other Controller’s task is to register if any of the Tags are
sending TIC alarm. When the Tag enters this mode depends on particular type of the Tag, but the
communication principle is always the same.
These alarms are passed to the Host via “RS-485 Interface Module” (RIM) which serves as an interface to
the RS-485 based network.
The Controller can be programmed to respond or not to a particular Tag, and when it does respond it can
take certain actions; lock / unlock the door, activate audible alarm and control any external device via the
relay.
3.2.2. Elevator
The Elevator node is special version of the Controller node. While the Controller is intended to cover the
area near the door, the elevator application has to be approached differently to avoid false alarm triggering
due to somebody just walking near the elevator and to avoid installing separate Controller on the every
floor, just to mention two most important reasons.
The Elevator communication to the Host is almost identical to the Controller.
3.2.3. Receiver
The Receiver is a node which will respond to TIC alarms only. It has limited control functionality (one
relay) and it can not receive any commands from the Host. The idea behind the Receiver concept is to
blanket the building with low cost nodes in order to reliably register TIC alarm. The Controllers could be
used for this purpose but they are not cost effective.
The Receiver communicates with the Host in similar fashion as the Controller but with limited
functionality.
3.3. Sensors
Tags are the only sensors in this system (if we disregard door open / closed sensing by a Controller and an
Elevator). There could be different types of tags within the system as discussed earlier, but all of them have
common characteristic to be able to communicate to the Controllers, Elevators or Receivers by using
common protocol.
3.4. Communication
There are 4 different communication protocols used in this system and the difference among them is
determined mostly by communication media used.
Figure 2
Control Lines
485 Comm
HOSTTAGCONTROLLERRIM
Comm
Weigand
Comm
RF Comm
EXI Wireless Systems, ConfidentialPage 9 of 33July 27, 1999
Page 10
“Halo” System: Communication Protocol970-00002-000
3.4.1. RF Communication
RF communication is taking place between Controllers, Elevators, Receivers on the one side an the Tags
on the other. This is two-way communication accomplished on 433.92 MHz in one direction and 307 kHz
in the other.
3.4.2. Weigand Communication
Weigand protocol is used between Controllers, Elevators, Receivers and corresponding RIMs. This is
unidirectional, 2-wire protocol and each line is used to transfer either ‘ones’ or ‘zeros’.
3.4.3. Control Lines Communication
This is again unidirectional protocol. Four lines are used to send information from the RIM to the
Controller, and they can be configured as either individual control lines or to form control code to transfer
different commands to the Controller
3.4.4. EIA-485 Communication
Controllers, Elevators and Receivers can not directly communicate to the Host. They need interface which
enables them to join the network. This interface is RIM and it converts Weigand protocol to the EIA-485
(in one direction, and EIA-485 protocol into Control Lines protocol in the other direction).
This is multidrop differential protocol which supports up to 256 nodes on the bus. The nodes are
communicating over a twisted pair cable and they should be distributed following the bus topology (EIA485 standard). The communication speed can be set to 3 different baud rates, 9600, 19200 or 57600 baud,
but this has to be set in the factory prior the system is shipped to the customer. Default baud rate setting is
57600 baud.
Some specifications of this protocol and comparison to the EIA 232 protocol is presented in Table 1.
Table 1
RS232RS485
Cabling
Number of Devices
Communication Mode
Max. Distance50 feet at 19.2 Kbps4000 feet at 100 Kbps
Max. Data Rate19.2 Kbps for 50 feet10 Mpbs for 50 feet
SignalingunbalancedBalanced
Mark (data 1)
Space (data 0)
Input Level Min.+/- 3 V0.2 V difference
single endedmulti-drop
1 transmit
1 receive
full duplexHalf duplex
-5 V min.
-15 V max.
5 V min.
15 V max.
256 transmitters
256 receivers
1.5 V min. (B>A)
5 V max. (B>A)
1.5 V min. (A>B)
5 V max. (A>B)
EXI Wireless Systems, ConfidentialPage 10 of 33July 27, 1999
Page 11
“Halo” System: Communication Protocol970-00002-000
4. RF Communication Protocol
All communication between the Tags and the Controllers is taking place across RF communication media.
Two frequencies are used:433.92 MHz and 307 kHz.
• 433.92 MHz Communication
This is a frequency which is used to transfer information from the Tag to the Controller. The guaranteed
range is 30 feet.
• 307 kHz Communication
This is a “field of coverage” which is modulated in order to send information from the Controller to the
Tag. The range of this field depends on a particular application and is usually set by the installer but it can
not exceed 10 feet.
There are two types of information that need to be transferred from the Tag to the Controller, “Tag in the
Field” (TIF) alarm and “Tag Initiated Communication” (TIC) alarm. These two alarms are actually the
essence of the whole “Halo” system.
4.1. Tag in the Field (TIF Alarm)
The Controller needs to know when any Tag enters the “field of coverage”. This information is then used to
take certain action or not, depending on the system setup.
4.1.1. Field of coverage
The Controller generates the “field of coverage” around itself continuously. It is transmitting “wakeup
word” every 100 ms and waits for the response from any potential Tags that could enter this field or the
Tags already in the field previously “named”.
A form of PWM is used to represent ‘zeros’ and ‘ones’. As shown in the Figure 2, a logical ‘1’ is
represented as 2 ms gap between pulses, and a logical ‘0’ as 3 ms gap between pulses. The pulse itself is
500 µs wide.
Figure 2 also illustrates how the “field of coverage” is formed. The Controller alternates between plain
“wakeup word” (97 Hex) and “wakeup + respond word” (97 + 03 Hex). Only the plain “wakeup word”
followed by 20 ms of silence (no pulses) can power up Tag’s processor but not “wakeup + respond word”.
This is important so that Controller wouldn’t be confused with the response it receives from the Tag, not
knowing is it the Tag just powered up or the Tag already “named”. Any pulse that comes within 20 ms after
the plain “wakeup word” (either from the noise or “respond” portion of the “wakeup + respond word” will
advance the hardware counter and microprocessor will not be powered up.
The Tag must receive all 9 pulses of the “wakeup word” and if it misses any of these pulses, the hardware
counter will reset and it will wait for the next plain “wakeup word”.
After it is powered up, the microprocessor will set one of its lines and maintain its own power supply. If
this line is not set within 40 ms it will be powered down again.
EXI Wireless Systems, ConfidentialPage 11 of 33July 27, 1999
Page 12
“Halo” System: Communication Protocol970-00002-000
‘1’
‘0’
2 ms
3 ms
500 µs
‘0’
‘0’
‘1’
‘1’
‘1’
‘1’
‘1’
‘0’
WAKEUP
‘0’
‘0’
‘1’
‘1’
‘1’
‘1’
‘0’
‘1’
‘0’
‘1’
RESPOND
WAKEUP
WORD
WORD
WAKEUP
WAKEUP
WAKEUP
WAKEUP
Figure 2 Wakeup Word
WAKEUP + RESPOND
100 ms100 ms
WAKEUP
+
RESPOND
WAKEUP
+
RESPOND
+
RESPOND
4.1.2. Bit By Bit Interrogation
Upon power up the microprocessor waits for the next “wakeup word”. If there would be no ‘unnamed” tags
in the field the next word would be “wakeup + respond word”. However in this case, there is at least one
“unnamed” tag in the field and this will change Controller’s response.
The new Tag (or Tags if there is more then one new Tag) will respond with the pulse (“blip”) immediately
after it receives first 8 bits (9 pulses) from the Controller. When the Controller receives this “blip”, it
knows there is an unknown Tag in the field and instead of continuing with the “RESPOND” command
(0011), it sends “BIT BY BIT” command (0110). Only “unnamed” Tags will find this command of interest
and prepare for the BBB interrogation that follows.
The purpose of this interrogation is to overcome collision problems among different Tags if they try to
communicate to the Controller at the same time. In total 24 bits (3 bytes) need to be transferred from the
Tag to the Controller. This is Tag’s ID number.
One and only one Tag will finish interrogation and it will be the Tag with the highest ID number among all
“unnamed” Tags. All other Tags will, one by one, drop out of this interrogation after they try to send the ’0’
bit when there is a Tag which is sending the ‘1’ bit at the same time. This is the main principle of the BBB
interrogation and detailed description of this protocol can be found in the document “Bit By Bit
Interrogation: Protocol Description, EXI, 1999”.
EXI Wireless Systems, ConfidentialPage 12 of 33July 27, 1999
Page 13
“Halo” System: Communication Protocol970-00002-000
BBB
‘1’
‘0’
WAKEUP
‘0’
‘0’
‘1’
‘1’
‘1’
‘1’
‘0’
‘1’
‘0’
‘1’
RESPOND
After it transmits all 24 bits of the ID word (3 bytes are treated as one ID word) in the PWM format, the
Tag sends additional byte in a NRZ (non return to zero) format. This is a checksum of the previous ID word
which will be used by the Controller to ensure that the received ID number is correct.
The main characteristic of the NRZ code is that bits are represented by the duration of the logic state and
not by the logic state itself. A logic ‘1’ is a logic state with duration of 500 µs, and a logic ‘0’ lasts for 250
µs. More about this code can be found in the document “Bit By Bit Interrogation: Protocol Description,
EXI, 1999”.
The checksum is calculated by using “Cyclic Redundancy Code” and this code is describe in details in the
document “Halo” Cyclic Redundancy Check, Algorithm Implementation, EXI, 1999”.
Upon receiving the checksum byte, the Controller will issue either ACK (1010) response or REPEAT
(1111) response depending if calculated checksum has matched received checksum or not. If it receives
ACK response, the Tag knows that the ID number was successfully received by the Controller and it will
not respond anymore to the BBB command. This will enable the Tag with the next sequentially lower ID to
finish BBB interrogation next time.
If the Controller respond with REPEAT, the Tag knows that the checksum did not match and it will retry
next time when it receives “wakeup word”.
Figure 3 illustrates BBB interrogation.
Figure 3. Controller TX and RX signals
Wakeup Word
1 0 0 1 0 1 1 1 0 1 1 0 0 1 1 0 0 1 0 1 1 1 0 1 0
Figure 2 Controller TX and RX signals
4.1.3. Respond Command
Command
Blip
Bit-By-BitACK
DataCRC
The Tags which ID number has been retrieved by the Controller are called “named” tags. These tags will
respond to the “wakeup + respond word”, so that the Controller knows if there is anymore Tags in the field
and when they are all gone outside the field of coverage. If there is no “respond” pulses after “wakeup +
respond word” the Controller will terminate TIF alarm and return to the idle mode.
TX
Figure 4 illustrates the Tags response to the “wakeup + respond word”. All tags present in the field and
“named” will respond with the same “blip” (350 µs wide).
TX
RX
RX
EXI Wireless Systems, ConfidentialPage 13 of 33July 27, 1999
RESPOND
Page 14
“Halo” System: Communication Protocol970-00002-000
‘1’
‘0’
WAKEUP
‘0’
‘0’
‘1’
‘1’
‘1’
‘1’
‘1’
‘0’
‘0’
‘1’
RESET
4.1.4. Reset Command
The Reset command is issued by the Elevator when the door closes. The Elevator needs to know which
Tags are inside the Elevator and in order to force them to send their ID numbers again, it resets them all.
The Elevator will repeat this every time when the door opens and closes.
The Tags are in the sleep mode most of the time while in the field (to preserve power). They wake up once
every second to check if the field is still present. If they receive RESET command (0101) they will reset its
own internal flags which prevent them from responding to the BBB command, and become effectively
“unnamed”.
The Elevator sends RESET command 14 times in a row in order to catch all Tags which were in the sleep.
This RESET commands are spread across 1.4 seconds time interval, and because the Tag is waking up
every I second, all Tags present in the field should be reset.
Figure 4 shows the RESET command
Figure 4 RESET command
4.2. Tag Initiated Communication (TIC alarm)
Besides being able to detect Tags presence within the “field of coverage”, the other important system’s
feature is to detect when the Tag is in the alarm mode. The conditions that will lead to this alarm mode are
different for different types of Tags. Actually all differences between Tags originate from one characteristic
– how is the alarm generated.
• P-Tag
The P-Tag is attached to the hand of the patient whose movement needs to be monitored and restricted (e.g.
newborn babies). Movement restriction is enforced by the TIF alarm but in order to be effective the P-Tag
must stay attached to the patient all the time. The removal of the P-Tag from the body will generate the TIC
alarm. The P-Tag is attached to the body with the elastic band and it is detecting body capacitance.
• A-Tag
The A-Tag is attached to the asset which movement is restricted (e.g. instrument that should not leave the
building). The movement restriction violation is monitored by the TIF alarms but it can be effective only
while the A-Tag is attached to the protected object. This is ensured by gluing the A-Tag to the asset and if it
is attempted to be removed, the plunger switch will close and generate the TIC alarm.
• D-Tag
The D-Tag is used by the user (e.g. nurse) as a “call for a help” when this person is in a distress. When the
D-Tag is pressed it will close the switch and generate the TIC alarm.
EXI Wireless Systems, ConfidentialPage 14 of 33July 27, 1999
Page 15
“Halo” System: Communication Protocol970-00002-000
4.2.1. Message format
The Tag (any of the above) is powered down most of the time and it powers up only when it enters the
“field of coverage” (TIF) or when it needs to generate the TIC alarm.
The TIC alarm range should be much longer than a TIF alarm and this is accomplished with some tradeoffs.
The most important factor is that TIC communication can not be 2-way communication due to the nature
of the Tags 2-way communication (field of coverage has limited range). This determines the format of the
TIC message sent from the Tag to the Controller.
To improve the chances that the message will go through (without the acknowledgment it can not be
guarantied nor the Tag knows if the message has been received correctly by the Controller), it is sent in 3
bursts and 5 times within each burst as shown in the Figure 5. This is 15 ID messages in total sent every
time when the TIC is generated. If any of these messages comes through, the transmission is successful.
After receiving each one of these ID messages the Controller compares received checksum with calculated
CRC and if they are the same, ignores all other messages with the same ID number for next 2 seconds.
The message is formatted in the NRZ code (same protocol as described earlier). Each individual ID
message consists of 3 ID bytes (coded as 6 BCD numbers) and one byte for the checksum (same CRC
calculation as described for “Bit-By-Bit” protocol).
After each burst (with 5 ID messages) the microprocessor goes into the sleep mode. The bursts are
generated every 850 ms (Figure 5a).
Figure 5b illustrates one of the bursts. The ID messages are separated with 2 ms of silence. This time is
used by the Controller to calculate the CRC.
The ID message format is shown in the Figure 5c. There are 4 bytes in the NRZ code where a logic ‘0’ is
represented with the 250 µs pulse and a logic ‘1’ with the 500 µs pulse. Each byte is terminated with the
“stop bit”. There is 1 ms gap between each byte.
EXI Wireless Systems, ConfidentialPage 15 of 33July 27, 1999
Page 16
“Halo” System: Communication Protocol970-00002-000
Figure 5 TIC Alarm
850 ms
a)
2 ms
b)
1 ms
c)
ID 1ID 3ID 2CHECKSUM
4.2.2. ID number format
Three ID bytes carry information about 6 ID characters in the BCD format (Hexadecimal numbers 0 – F) as
presented in the Figure 6a. All ID numbers are generated as sequential decimal numbers with the exception
of the first character which is always the same for the particular type of Tag
The format of the ID numbers for different tags is as follows:
P-Tag⇒ Cxxxxx
A-Tag⇒ Axxxxx
D-Tag⇒ Dxxxxx
Where “xxxxx” is a sequential decimal number.
EXI Wireless Systems, ConfidentialPage 16 of 33July 27, 1999
Page 17
“Halo” System: Communication Protocol970-00002-000
WEIGAND 1
WEIGAND 0
5. Weigand Communication Protocol
The Controller communicates to the Host PC through the “RS-485 Interface Module” (RIM). The RIM
sends information to the Controller via control lines and receives information from the Controller via the
Weigand lines. These two communications could take place at the same time due to multitasking nature of
the Controller’s and RIM’s firmware.
5.1. General
Weigand communication protocol is unidirectional protocol developed for card readers. Information is
transferred over two data lines, one used to transfer ‘zeroes’ and the other for ‘ones’. Timing is strictly
defined and is shown in the Figure 7.
Figure 7 Weigand Protocol
50 µs
1 ms
11001110
1 ms
Both lines are pulled high in the idle state so that receiver can detect line failure (if it stays low for more
then 50 µs). The signals in the Figure 7 represent one byte of data (CB Hex). Only one line can be pulled
low every 1 ms.
Because the receiver of this signal is sampling these two lines within tightly controlled 47 µs loops (once
every 47 µs), it is very important to keep the timing of these signals on target, especially duration of the 50
µs low pulse. If this pulse would happen to be shorter then 47 µs it could be missed by the receiver.
5.2. Weigand Messages
All information that Controller needs to pass to the Host PC is packed into the 32 bit long, predefined
packets and sent to the RIM over the Weigand lines. The format of these packets is shown in the Table 1
and each one of these fields will be discussed separately.
EXI Wireless Systems, ConfidentialPage 17 of 33July 27, 1999
Page 18
“Halo” System: Communication Protocol970-00002-000
PARITY
Table 2 Weigand Message
FieldLengthDescription
Even Parity Bit1Parity Bit + next 16 bits = 0
Control Code4Defines message type
Door Bit11 = Door Open, 0 = Door Closed
Maglock Bit11 = Maglock On, 0 = Maglock Off
Data 18Dependant on message type
Data 28Dependant on message type
Data 38Dependant on message type
Odd Parity Bit1Odd Bit + previous 16 bits = 1
Total32
5.2.1. Parity Bits (Even and Odd)
These two one-bit fields are used for error detection and they are starting and terminating the packet.
The “Even Parity Bit” is calculated for the first 16 bits. They are added in the Boolean algebra without
Carry (0+0=0, 0+1=1, 1+0=1, 1+1=0) and if this result is 0 the “Even Parity Bit” is set to ‘1’ and vice
versa.
The “Odd Parity Bit” is calculated for the last 16 bits and if this result is 0, the “odd Parity Bit” is set to ‘1’
and vice versa.
Figure 8 illustrates how are these bits calculated. The same calculation is conducted on the receiving side
(RIM) and if received and calculated parity bits match, the transmission is considered successful.
Figure 8
Σ
OPB
+
= 1
EVEN
BIT
Σ + EPB = 0
ODD
PARITY
BIT
EXI Wireless Systems, ConfidentialPage 18 of 33July 27, 1999
Page 19
“Halo” System: Communication Protocol970-00002-000
5.2.2. Control Code
This 4-bit field identifies message type. A content of three data bytes (Data 1, Data 2 and Data 3) is
determined by this field.
There are two groups of message types, messages which carry Tag’s ID number and all others. An overview
of all message types is presented in the Table 2.
Table 3
Message TypeControl
Normal0 (0000)ABCDEF
Bypassed4 (0100)ABCDEF
TIF Alarm1 (0001)ABCDEF
Loiter3 (0011)ABCDEF
Host Alarm is ON2 (0010)ABCDEF
Unlock Req. is ON5 (0101)ABCDEF
Status12 (1100)Noise CounterInput StatesDevice Status
11 (1011)Version #Mode / OptionID Range
Data 1Data 2Data 3
Tag ID (byte 1)Tag ID (byte 2)Tag ID (byte 3)
‘ID’ Messages
Messages which carry Tag ID number are prioritized not according to their code numbers but rather as
shown in the above table (‘Normal’ is the lowest priority and ‘Test Mode’ is the highest priority).
5.2.2.1. Normal
Message sent when the “good” Tag enters the field of coverage. “Good” Tag will not trigger the alarm.
5.2.2.2. Bypassed
This message is sent when the Controller enters ‘bypass’ mode. In this mode Tags can enter the field of
coverage without triggering the alarm. This mode is enabled by the user from the keypad or the RBC. If not
interrupted by the user, this mode will expire after 60 seconds and the Controller will revert into the
Normal mode.
5.2.2.3. TIF Alarm
This message is sent when the “bad” Tag enters the field of coverage. “Bad” Tag triggers the alarm.
5.2.2.4. Loiter
Message sent when the field is occupied for more then 1 minute with no new Tags coming in.
EXI Wireless Systems, ConfidentialPage 19 of 33July 27, 1999
Page 20
“Halo” System: Communication Protocol970-00002-000
5.2.2.5. Host Alarm ON
Message which informs the host that its command to set the alarm has been received and that the Controller
is in the alarm mode.
5.2.2.6. Unlock Request ON
Message which informs the Host that its command to unlock the door has been received and the door is
unlocked.
5.2.2.7. TIC Alarm
Message sent when TIC alarm is received from the Tag. This is the message with the highest priority when
the system is in the normal operating mode (not in the Test mode)
5.2.2.8. Test Mode
Message sent when the Controller is in the Test mode (set by the switch inside the Controller). No alarms
are set in this mode and it is usually used to set the field of coverage.
‘No ID’ Messages
These messages carry information about the system status. They have lower priority then ID messages.
5.2.2.9. Pin Number Entry
This message carries to the Host up to 6 keys entered from the keypad. To distinguish between a key “0”
and no key, the key “0” is coded as “A” (1010 Hex), and no key is coded as “0” (0000 Hex). If more then 6
keys are entered, only last 6 are sent to the controller.
5.2.2.10. Event (Door Open)
Message applicable to Elevators only. It is sent when the elevator door opens. This message is passed to the
RIM every time when the door changes state, but the RIM sends this message to the Host only if the
Elevator door has not changed its state for some time.
5.2.2.11. Switch Configuration
This message carries information about the Controller setup selectable by the installer by rotary switches
and about firmware version. Three data bytes are assigned as follows:
1. Version Number (Version of firmware)
2. Mode / Option
Following table illustrates Mode switch configuration and related modes of operation.
Table 4
ModeController FunctionResponse
0Test ModeAlarm ends on its own – fixed bypass time
1Patient Monitoring with RBCContinuos alarm – fixed bypass time
2Patient Monitoring with RBCAlarm ends on its own – fixed bypass time
EXI Wireless Systems, ConfidentialPage 20 of 33July 27, 1999
Page 21
“Halo” System: Communication Protocol970-00002-000
3Patient MonitoringContinuos alarm – fixed bypass time
4Patient MonitoringAlarm ends on its own – fixed bypass time
5Article Surveillance - ProtectionAlarm ends on its own – bypass extended
6Article Surveillance – ProtectionAlarm ends on its own – bypass extended
7, 8, 9Reserved (Article Surveillance–Monitoring)
AAuthorized Entry4 second release
BAuthorized Entry8 second release
CAuthorized EntryReleased while Tag in the field
D,E,FNo Function
Modes 1 and 2 will only allow bypass when the field is cleared of Tags and the user enters a sequence
of key presses on the RBC. Modes 3 and 4 and modes 5 and 6 are for Keypad entry. Pinpad can be used
with any of the modes.
3. ID Range
This field is defined by the “ID Range” rotary switch on the Controller. It determines which Tags will
trigger the TIF alarm (“bad” Tags) and which will be ignored (“good” Tags).
For options 2 – D, “High_ID” and “Low_ID” rotary switches are used to determine range in which
Tags are active. When one of these options is chosen, this field (ID Range rotary switch) selects which
digit of Tag’s 6 digit ID number is making selection. Tag’s ID number is organized as ABCDEF where
each character represents one digit of the ID number.
Possible settings are presented in Table 4.
Table 5 “ID Range” Switch
OptionActive TagsMode: 1,2,3,4,5,6Mode: A,B,C
0Don’t act on any TagsNo Tags are stoppedNo Tags authorized
1Act on all TagsAll Tags are stoppedAll Tags authorized
2Tag Selection on digit ASelected Tags are stoppedSelected = Alarm
3Tag Selection on digit BSelected Tags are stoppedSelected = Alarm
4Tag Selection on digit CSelected Tags are stoppedSelected = Alarm
5Tag Selection on digit DSelected Tags are stoppedSelected = Alarm
6Tag Selection on digit ESelected Tags are stoppedSelected = Alarm
7Tag Selection on digit FSelected Tags are stoppedSelected = Alarm
8Tag Selection on digit ASelected Tags can passSelected = Pass
9Tag Selection on digit BSelected Tags can passSelected = Pass
ATag Selection on digit CSelected Tags can passSelected = Pass
BTag Selection on digit DSelected Tags can passSelected = Pass
CTag Selection on digit ESelected Tags can passSelected = Pass
DTag Selection on digit FSelected Tags can passSelected = Pass
E, FNot used
Only options 0 and 1 will not use switches “High_ID” and “Low_ID” to select particular range of Tag
Ids (these two options deal with all Tags). All other “ID Range” switch settings will use them as
illustrated in Table 4.
EXI Wireless Systems, ConfidentialPage 21 of 33July 27, 1999
Page 22
“Halo” System: Communication Protocol970-00002-000
Table 6 “High_ID” and “Low_ID” Switch
Switch SettingSelected Tags
High_ID > Low_IDAll Tags with selected digit (switch ID Range) equal or between the
two numbers are selected.
High_ID < Low_IDAll Tags with selected digit (switch ID Range) lower then or equal
to “High_ID” and all Tags with selected digit greater or equal of
“Low_ID” are selected
High_ID = Low_IDOnly Tags with selected digit (switch ID Range) equal “High_ID”
(or “Low_ID”) are selected
5.2.2.12. Status
Status message carries information about Controller’s status, input states and RF noise level. These
messages are requested by the Host every 30 seconds to confirm that the Controller is still present on the
bus and functioning properly. The Controller will send this message on its own if any parameter is changed
(as with any other message).
There are three data bytes in the Status message:
1. Noise Counter
Indicates number of times the Controller has detected signal on its receiver but that was not legitimate
data. The Controller is sampling receiver every 50 µs. This counter decrements over time (10 times
faster then it increments) if noise goes away. When the noise counter reaches 100, the Status message
is sent, and then again when the counter gets back to zero.
2. Input States
This byte describes the state of all inputs to the Controller as shown in the Table 6
Table 7 Input States
BitInput NameFunction
Bit 7Not used
Bit 6Strobe0 – ignore other host inputs
1 – host inputs active (override, unlock, alarm)
Bit 5Override0 – override request
1 – no override request
Bit 4Unlock0 – lock release request
1 – no lock release request
Bit 3Bypass key1 – bypass key pressed
Bit 2Reset key1 – reset key pressed
Bit 1Alarm0 – host alarm request
1 – no host alarm request
EXI Wireless Systems, ConfidentialPage 22 of 33July 27, 1999
Page 23
“Halo” System: Communication Protocol970-00002-000
Bit 0Door0 – door closed
1 – door open
When in the idle mode, the Input States field equals 73 Hex.
3. Device Status
This byte describes the Controller’s state.
Table 8 Device Status
bitStateDescription
Bit 7Not used
Bit 6RF field occupiedTag is in the field, regardless if it generates alarm or not.
Bit 5OverrideHost requested. Controller releases the maglock, turn off
alarm relay and both LEDs and stop all interrogation.
Bit 4UnlockHost requested. Maglock is released, current alarm is cleared.
Bit 3BypassController is in the bypass mode.
Bit 2Host alarmHost requested. Maglock, alarm LED and relay activated,
Bit 1TIC alarmTIC received from the Tag
Bit 0TIF alarmTIF received from the Tag
EXI Wireless Systems, ConfidentialPage 23 of 33July 27, 1999
Page 24
“Halo” System: Communication Protocol970-00002-000
6. Signal lines communication
The Weigand protocol which is unidirectional is used to transfer information from the Controller to the
RIM. Some information (mostly Host requests) need to be passed from the RIM to the Controller. There
are 4 signal lines that are used for this purpose and the Controller monitors these lines every 12.8 ms.
There are two modes of operation for the Control lines. When the “Strobe” line is high, the other 3 lines are
treated individually, and when the “Strobe” is low they are treated as a 3-bit command for the Controller.
Signal lines functionality is shown in the Table 8.
Table 9
Functionality
Strobe
Override
Unlock
0000Return to normal mode, end any other mode
0001Send current status
Alarm
0010Send switch settings
0011Start bypass
0100Reset all Tags in the field and reread them
0101Remote reset key press, clears distress alarm
0110Enter Reader mode / acknowledge Tag
0111Retransmit Tag (only until next Tag comes in)
10xxStart Override
1x0xStart Unlock (Controller only)
Start Bypass (Elevator only)
1xx0Start Host alarm
When there is a need to transfer the command to the Controller some timing guidelines must be followed
as illustrated in the Figure 9. This is necessary in order to preserve integrity of command lines and the fact
that even when control lines are reset to their normal state (all 3 high), the Controller needs this
information to operate properly.
After the “Strobe” signal returns to high state, the signals on the control lines should return to their
previous state before the “Strobe” signal become low. They should be returned within 52 ms from the
rising edge of the “Strobe” signal.
NOTE: Receiver is not able to respond to this communication since it has no control input lines
EXI Wireless Systems, ConfidentialPage 24 of 33July 27, 1999
Page 25
“Halo” System: Communication Protocol970-00002-000
NameMinTypicalMax
Figure 9
Lines
Control CodeIndividual
T
S
T
D
T
S
T
D
T
H
T
H
13 ms50 ms25 ms
1 ms13 ms40 ms
13 ms25 ms50 ms
Individual
Lines
OVERRIDE
UNLOCK
ALARM
STROBE
EXI Wireless Systems, ConfidentialPage 25 of 33July 27, 1999
Page 26
“Halo” System: Communication Protocol970-00002-000
7. EIA-485 Communication
Information between Controller and the Host computer are exchanged across twisted pair cable driven by
EIA-485 transceivers. The Controller can not communicate directly to the Host but rather through the RIM
which is a network adapter for the Controller. On the Host side, the PC has an EIA-485 network card to
make this link compatible.
7.1. General
The EIA-485 is a hardware specification which determines physical layer only, and doesn’t specify
communication protocol used but imposes some limitations to that protocol in regards to maximum
communication speed, maximum number of nodes allowed on the bus and how these nodes could be
interconnected.
The maximum communication speed and the distance across these nodes are communicating, are closely
linked together and by increasing one parameter, the other must be decreased.
The maximum number of nodes is determined by electrical properties of transceivers and the maximum
number today is 256. These nodes must be linked following a bus topology and the bus must be terminated
at each end to avoid reflections which could significantly degrade network performance.
7.2. Network performance
The 485 network used by the Halo system can operate on three different speeds: 9600, 19200 and 57600
baud. This is selectable by a jumper in the RIM on the one side, and through the Halo program that is
running on the Host PC on the other.
Maximum of 99 nodes is allowed on the bus and the Host is a master. The Host is polling slave nodes in a
round robin fashion. As a consequence of this type of communication, higher number of nodes means that
the system response will be slower.
The system response will slow down even more if the Host software is configured for the non-existing
nodes or if some nodes on the bus are powered down or unable to communicate. For every node that
doesn’t respond to the Host’s request (for any reason), the system response is prolonged approximately 600
ms (the Host waits that long for the response).
If the node responds on the Host’s request, the next request (for the next node) is sent after 55 ms (55 ms is
internal PC tick and messages can not be sent more often). This indicates that expected polling rate is 110
ms per device in a case of reliable communication.
If the Host upon receiving the message sent by the RIM sends “Ack” for that message, but that “Ack” is not
received by the RIM, next time when the Host requests the message from the RIM, the RIM will send the
same message. This could cause additional delay for the message to be displayed on the computer screen.
EXI Wireless Systems, ConfidentialPage 26 of 33July 27, 1999
Page 27
“Halo” System: Communication Protocol970-00002-000
1
RESPONSE
ACKNOWLEDGMENT
2
RESPONSE
ACKNOWLEDGMENT
1
Figure 10 shows network traffic in a case of two devices on the bus with reliable communication.
Maximum number of nodes to be polled is 9 per second in ideal condition (all node responses are
received). “Host Request” message packet and “RIM” response packet are separated from each other 100 µs
only, and not as shown in the Figure 10.
Figure 10
FULL CYCLE: 2x110 ms = 220 ms
55 ms55 ms55 ms55 ms
HOST
REQUEST
RIM 1
HOST
HOST
REQUEST
RIM 2
HOST
HOST
REQUEST
7.3. Communication parameters
UARTS on both sides (Master and Slave) are configured for asynchronous full duplex mode. Byte format is
1 start bit, 8 data bits and 1 stop bit. Both UARTs transmit and receive LSb first. Standard communication
speed is 57.6 kbaud what refers to 17.36 µs per bit.
7.4. Message format
Messages are initiated by the Host computer and the RIM responds to most of them but not all. Messages in
both directions have the same format and the difference among them is in data they carry (different type and
length of data), but the message structure is the same.
Table 10 illustrates format of these messages.
Table 10 485 Message Format
BytesFieldDescription
1SOHStart of Header (01 Hex)
1LengthLength of message from (including) a message type to (including)
checksum.
1Message TypeUpper 2 bits: message number
EXI Wireless Systems, ConfidentialPage 27 of 33July 27, 1999
Page 28
“Halo” System: Communication Protocol970-00002-000
Lower 6 bits: message type
1Network
Address
XDataMessage contents. Number of bytes is variable, it could be 0.
1ChecksumAll bytes added and inverted
Note: SOH character (01 Hex) defines start of the message and in a case that the same value (01 Hex) is
part of the rest of the message that byte is converted by using ESC character in the following
manner:
This conversion is done to avoid byte “01” Hex within the message to be considered as a start of the
new message.
The “Message Type” field is divided into two sub-fields, one is actual message type and the other (upper
two bits) is a counter (“message number”) which is advanced every time when the message is sent to the
particular RIM. Upon receiving the message from the host, the RIM advances its own message counter
which should be in sync with the received “message number”. If these two counters do not match, it
indicates to the RIM that it has missed at least one message from the Host.
Logical address assigned by the Host
7.5. Message Structure
All messages types are initiated by the Host, but not all of them are sent by the Host. Four message types
are sent by the Host, and the rest is sent by the RIMs as a response to Host’s messages. All message types
are listed in the Table 11
Table 11 Message Types
Asign
Network
Address
Length66444 + (N * 4)3
Type234567
AddressNetwork
Address
DataSerial
Number
Test Node
Presence
0000 or
Serial
Number
Node
Present
Network
Address
Firmware
version #
Send /
Request
Data
Network
Address
Control
Byte
Device
Data
Network
Address
Status byte
Host Ack
Network
Address
7.5.1. Assign Network address
This message is sent by the Host when the network is configured. Part of network setup is to assign
network address to each device on the bus (each RIM). In order to do this, installer needs to know RIM’s ID
number (6 digit number). This message is then sent to that particular RIM which will use this number in all
future communication to the Host.
EXI Wireless Systems, ConfidentialPage 28 of 33July 27, 1999
Page 29
“Halo” System: Communication Protocol970-00002-000
The RIM does not respond to this message, but the Host knows if the message has been successfully
received when the RIM responds next time to other messages sent to its network address. If the RIM does
not respond to those messages, the Host keeps sending “Assign Network Address’ message.
7.5.2. Test Node Presence
This message allows the Host to check if the particular node (RIM) is present on the bus and is it able to
communicate. All nodes are listening to this message, but only one with matching serial number will
respond with its communication firmware version.
7.5.3. Node Present
This message is sent from the RIM as a response to the “Test Node Presence” message. With this response,
the RIM indicates to the Host that is present on the bus and able to communicate. If it still doesn’t have its
network address, the RIM will respond with ‘00’ as the address, and to the Host this will be the signal to
assign network address to this node.
7.5.4. Send / Request Data
This is normal communication message between the Host and the other nodes on the bus. This message
communicates to one node at the time and it is used to send commands to the Controller and as a request to
the same Controller to send its data.
The command for the Controller (control byte) has two fields. First field (bits 6, 5, 4) is used to set
individual Controller’s output lines (Alarm, Unlock, Override) and the other (bits 3, 2, 1 ,0) to request
some action from the Controller. Note that both fields are actually controlling Controller’s output lines
(Strobe, Alarm, Unlock and Override) as described earlier in the chapter “Signal Lines Communication”.
Detail description of the control byte is shown in the Table 12
Table 12 Control byte
7 6 5 4 3 2 1 0
1 x x x x x x x
x 0 0 0 x x x x
x 0 0 1 x x x x
x 0 1 0 x x x x
x 0 1 1 x x x x
Individual Lines
x 1 0 0 x x x x
x x x x 0 0 0 0
H
ostReques
x x x x 0 0 0 1
x x x x 0 0 1 0
x x x x 0 0 1 1
x x x x 0 1 0 0
x x x x 0 1 0 1
t
Prevents ‘01’ (SOH) or ‘1B’ (ESC)
All lines OFF
Alarm line ON
Unlock line ON
Unlock and Alarm ON
Override line ON
Return to idle mode (end bypass, alarm, maglock…)
Send current status
Send switch setting
Start bypass
Re-read Tags (reset all Tags)
Remote “Reset” key press (same as “Reset” key on RBC)
Function
EXI Wireless Systems, ConfidentialPage 29 of 33July 27, 1999
Page 30
“Halo” System: Communication Protocol970-00002-000
x x x x 0 1 1 0
x x x x 0 1 1 1
x x x x 1 0 0 0
Enter Reader mode (Controller only)
Restart Pre-alarm mode (Elevator only)
Retransmit last Tag
None
7.5.5. Device Data
This message is sent as a response to the “Send / Request Data” message. It follows request message
within 150 µs. The length of this message is not predictable and it depends on system activity. Any TIC or
TIF alarms are reported with this message and if multiple TIC or TIF alarms are available in the RIM’s
buffer, they will be all sent within one message.
Fixed portion of “device Data” message includes device “Status byte”. This information is sent every time
regardless if there are any alarms or not. It mostly describes communication quality between Host and the
Controller.
Table 13 Status Byte
bitConditionSetClear
7No Weigands from device1 minute with no WeigandsWeigand comm. OK
6Attached device not connectedWeigand lines lowWeigand lines high
5Problems communicating to HostErrors during receiving on 485“Ack” received
4Last message was out of orderMessages not in sequence“Ack” received
3Lost Weigand messageWeigand parity check failed“Ack” received
2Buffer overflowLost message due to too many
Weigands since last pool
1Designated monitor“Start Monitoring” message“Stop Monitoring” message
0= 0, To prevent ‘01’ or ‘1B’NeverAlways
When TIC or TIF alarm needs to be sent, it is added after the Status byte. The Weigand message received
from the Controller is stripped of parity bits and the rest of the message is shifted to the right for one bit .
The result is four byte field as shown in the Figure 11 First figure shows Weigand message as received
from the Controller, and second one shows same message ready to be appended to the “Device Data”
message.. First two bits are always ‘0’.
“Ack” received
EXI Wireless Systems, ConfidentialPage 30 of 33July 27, 1999
Page 31
“Halo” System: Communication Protocol970-00002-000
DOOR
MAGLOCK
Figure 11
EVEN
PARITY
BIT
CODE
CODETAG ID
DOORMAGLOCK
TAG ID
ODD
PARITY
BIT
EXI Wireless Systems, ConfidentialPage 31 of 33July 27, 1999
Page 32
“Halo” System: Communication Protocol970-00002-000
8. Glossary
ChecksumA number that has been calculated as a function of some message.
CRCCyclic Redundancy Code" or “Cyclic Redundancy Check”.
LSbStands for “Least Significant Bit”. This is bit 0 of a given byte or a word.
MSbStands for “Most Significant Bit”.
MessageSequence of bytes which carry information from one point to the other.
EIA-485Balanced, multidrop, half-duplex communication protocol (former (RS-485)
EIA-232Unbalanced, point-to-point communication protocol.(former (RS-485)
PWMPulse Wide Modulation
BBBBit By bit Interrogation
MaglockDoor lock controlled by the magnetic coil.
RBCRemote Bypass Control
UARTUniversal Asynchronous Receiver and Transmitter
EXI Wireless Systems, ConfidentialPage 32 of 33July 27, 1999
Page 33
“Halo” System: Communication Protocol970-00002-000
9. References
“Bit By Bit Interrogation; Protocol Description”,EXI, 1999
“ROAM II Patient Protection System, RS485 Interface Modules; Functional Requirements Specification”,