Wärtsilä JOVYSTAR HP 200-800kVA BAX 4640 E - 2 -

Wärtsilä JOVYSTAR HP 200-800kVA BAX 4640 E - 3 -
General notes
Thank you for choosing the Uninterruptible Power Supply (UPS) of the JOVYATLAS JOVYSTAR E-series.
It represents a reliable protection for the attached loads.
Read this instruction carefully
This operating manual includes safety requirements, instructions for installation, as well as working instructions, to assist
you to get the maximum performance out of the UPS.
Keep this instruction on a safe place
It contains important rules for safe operation of this UPS and information for contacting the manufacturer service, in case
of any questions and problems regarding the UPS.
Keeping or recycling of the packing material
The packing material the UPS was projected with great attention in order to protect the UPS from damages during the
transportation. This material is also useful in case of returning the UPS to the manufacturer.
Damages during the transportation are not covered by the manufacturer guarantee.
Obligation to briefing
This operating instruction must be read carefully by all persons working on the UPS prior to installation and initial startup. It must also be read by all persons operating the UPS. This operating instruction is a composite part of the UPS. The
operator of this device is obliged to communicate these instructions to all personnel transporting, installing, operating or
maintaining the UPS.
Validity of this document
This operating instruction comprises the current technical specification of the UPS at the time of publication. The contents is informational only and do not constitute a subject of contract.
Wärtsilä JOVYATLAS EUROATLAS GmbH reserves the right to make modifications with respect to contents and technical data in these operating instructions without prior notification. Wärtsilä JOVYATLAS EUROATLAS is not committed
to continuously update this document and therefore cannot be held liable for any inaccuracies or inapplicable information
in this operation instruction.
Limited guarantee
Our goods and services are subject to the general delivery terms for products of the electrical industry and our general
sales conditions. We reserve the right to change the contents of information with respect to technical data, operation,
weights and dimensions. Claims regarding the delivery of the products should be issued within one week after reception
along with the packing slip. Later claims will not be accepted.
Wärtsilä JOVYATLAS EUROATLAS GmbH will rescind all obligations such as warranty agreements, service contracts
etc. entered into by Wärtsilä JOVYATLAS EUROATLAS GmbH or its representatives without notice in the event of
maintenance and repairs being carried out with anything other than original spare parts.
Use of this document
This operating manual for the UPS is structured, that all necessary work for starting up, maintaining, repairing and operating the UPS can be performed by qualified personnel.
Copyright
No part of this operating manual may be reproduced or transmitted by any mechanical or electronic means without the
express prior written permission of WÄRTSILÄ JOVYATLAS EUROATLAS GmbH.
Copyright Wärtsilä JOVYATLAS EUROATLAS GmbH 2015. All rights reserved.

Wärtsilä JOVYSTAR HP 200-800kVA BAX 4640 E - 4 -
Table of contents
1 Technical Data 6
1.1 Autonomy Times, Dimensions And Weights 8
2 General Notes 9
2.1 Introduction 9
2.2 Why Using A UPS? 9
3 System description 11
3.1 Rectifier 12
3.2 Inverter 12
3.3 Battery and Battery Charger 12
3.4 Static Bypass 12
3.5 Manual Bypass 12
3.6 Front Panel 12
3.7 Operating status 13
3.7.1 Normal operation 13
3.7.2 Load supplied by bypass due to inverter fault 13
3.7.3 Rectifier failure or mains failure 13
3.7.4 Internal Manual bypass 14
4 Installation 15
4.1 Reception of the UPS 15
4.2 Transport 15
4.3 Setting up 16
4.3.1 Dimensions Wärtsilä JOVYSTAR HP 200-300 kVA 17
4.3.2 Dimensions Wärtsilä JOVYSTAR HP 400 kVA 19
4.3.3 Dimensions Wärtsilä JOVYSTAR HP 500-600 kVA 21
4.3.4 Dimensions Wärtsilä JOVYSTAR HP 800 kVA 23
4.4 Electrical Connections 26
4.4.1 Terminal Board 27
4.4.2 Internal Connections between both switch cabinets: 30
4.4.3 Battery connection 31
5 Operation 32
5.1 Setting Up 32
5.1.1 Start-up troubleshooting 32
5.2 Shut down procedure 33
5.3 Starting the Parallel Redundant System 33
5.4 Switch Off the Parallel Redundant System 33
5.5 Manual bypass procedure 33
5.5.1 Start-up from manual bypass (Single UPS) 34
5.5.2 Initiation of the Manual Bypass in Parallel Redundant Operation 35
5.5.3 Switch Off the Manual Bypass in Parallel Redundant Operation 35
5.6 Front Panel 35
5.6.1 Mimic description 35
5.7 Menu structure 37
5.7.1 Measures 37
5.7.2 Alarms 39
5.7.3 Special 40
5.7.4 Info 43
6 Options 46
6.1 Parallel redundant system 46
6.1.1 Additional hardware 46
6.1.2 System layouts 46
6.2 Battery symmetry monitoring 46
6.3 Relay PCB 47
6.4 SNMP-Adaptor 47
6.5 Shut-down software 48

Wärtsilä JOVYSTAR HP 200-800kVA BAX 4640 E - 5 -
6.6 Temperature compensation 48
6.7 MODBUS-Adapter 48
6.8 Manual Bypass for JST HP 400-800 kVA 48
7 Maintenance 49
7.1 Visual checks 49
7.2 Functional test 49
7.3 Inspection of battery 50
7.3.1 Information about battery operation 50
7.3.2 Battery operating instructions 51
8 Status messages and alarms 51
8.1 Measures in case of problems 57
9 Customer service 58
10 Appendix 58

Wärtsilä JOVYSTAR HP 200-800kVA BAX 4640 E - 6 -
1 Technical Data
Output apparent power (cos φ = 0,9)
Output active power (cos φ = 1)
Rated output voltage
- Tolerance static, symmetric load
- Tolerance static, asymmetric load
- Tolerance dynamic load (20 % → 100 % → 20 %)
- Correction time after load step
3 x 380/220 V 3 x 400/230 V 3 x 415/240 V
±1 %
±2 %
±5 %
< 20 ms
Rated output frequency
- Tolerance at free running quartz oscillator
- Tolerance at inverter-synchronization with mains
Rated output current (cos φ = 0,9)
Rated output current (cos φ = 1,0)
THDU (according to IEC EN 62040-3)
- Linear load
- Non linear load
3 x 400/230 V +15 % -20 %
Input current (at 100 % load, without battery charging)
Input current (at 100 % load, max. battery current)
Input power factor (at 100 % load)
Input current THD (at 100 % load)
Compensation charging voltage
Max. battery charging current (at 100 % load)
Max. battery charging current with activated DCM
(Dynamic charging mode, only at partial load)
Battery charging characteristic
Overload capability/Output short circuit characteristic
Overload capability inverter
>100 % to 125 % to 10 min
> 125 % to 150 % to 1 min
> 150 % to 199 % to 10 s
= 200 % for 100 ms
Overload capability static bypass
150 % continuously
1000 % to 1 cycle
Short circuit characteristic (Bypass is available)
Immediate transfer to the bypass
Short circuit characteristic (Bypass is not available)
1. Current limitation to 200 % for 100 ms
2. Current limitation to 125 % for another 5 s
EMV-class according to IEC EN 62040-2
Class of protection according to IEC EN 62040-3
Efficiency normal mode (at 100 % load)
Efficiency battery mode (at 100 % load)
Efficiency eco-mode (Offline-mode)
Max. crest factor without power reduction
Heat dissipation
(at 100 % load and rated input voltage)
Requirements to the installation position
Max. installation altitude without power reduction
Power reduction for installation altitude according to
IEC EN 62040-3
1 % every 100 m above 1000 m up to 5000 m
Required air cooling volume
UPS operating ambient temperature
Battery ambient temperature
(recommended battery ambient temperature, see also
battery operating instruction)
Battery storage temperature
Relative humidity (non condensing)

Wärtsilä JOVYSTAR HP 200-800kVA BAX 4640 E - 7 -
Output apparent power (cos φ = 0,9)
Output active power (cos φ = 1)
Rated output voltage
- Tolerance static, symmetric load
- Tolerance static, asymmetric load
- Tolerance dynamic load (20 % → 100 % → 20 %)
- Correction time after load step
3 x 380/220 V 3 x 400/230 V 3 x 415/240 V
±1 %
±2 %
±5 %
< 20 ms
Rated output frequency
- Tolerance at free running quartz oscillator
- Tolerance at inverter-synchronization with mains
Rated output current (cos φ = 0,9)
Rated output current (cos φ = 1,0)
THDU (according to IEC EN 62040-3)
- Linear load
- Non linear load
3 x 400/230 V +15 % -20 %
Input current (at 100 % load, without battery charging)
Input current (at 100 % load, max. battery current)
Input power factor (at 100 % load)
Input current THD (at 100 % load)
Compensation charging voltage
Max. battery charging current (at 100 % load)
Max. battery charging current with activated DCM
(Dynamic charging mode, only at partial load)
Battery charging characteristic
Overload capability/Output short circuit characteristic
Overload capability inverter
>100 % to 125 % for 10 min
> 125 % to 150 % for 1 min
= 150 % for 10 s
Overload capability static bypass
150 % continuously
1000 % for 1 cycle
Short circuit characteristic (Bypass is available)
Immediate transfer to the bypass
Short circuit characteristic (Bypass is not available)
1. Current limitation to 150 % for 150 ms
2. Current limitation to 125 % for another 5 s
EMV-class according to IEC EN 62040-2
Class of protection according to IEC EN 62040-3
Efficiency normal mode (at 100 % load)
Efficiency battery mode (at 100 % load)
Efficiency eco-mode (offline-mode)
Max. crest factor without power reduction
Heat dissipation
(at 100 % load and rated input voltage)
Requirements to the installation position
Max. installation altitude without power reduction
Power reduction for installation altitude according to
IEC EN 62040-3
1 % every 100 m above 1000 m up to 5000 m
Required air cooling volume
UPS operating ambient temperature
Battery ambient temperature
(recommended battery ambient temperature, see also
battery operating instruction)
Battery storage temperature
Relative humidity (non condensing)

Wärtsilä JOVYSTAR HP 200-800kVA BAX 4640 E - 8 -
1.1 Autonomy Times, Dimensions And Weights
NOTE:
Up to five charging/discharging cycles are necessary for obtaining the specified autonomy times. Afterwards the battery is well formatted and its maximum capacity is available.
Total weight of battery cabinet [kg]
Total weight of battery cabinet [kg]
Total weight of battery cabinet [kg]
Total weight of battery cabinet [kg]
Total weight of battery cabinet [kg]
Total weight of battery cabinet [kg]
Total weight of battery cabinet [kg]
All data refer to standard-battery (lifetime 10-12 years)

Wärtsilä JOVYSTAR HP 200-800kVA BAX 4640 E - 9 -
2 General Notes
It is mandatory to fulfil al works and safety requirements according to rules and instructions described herein for protecting the personnel working at the UPS as well as maintaining optimal duty-cycles of the UPS. All personnel installing/deinstalling, starting up, and maintaining the unit must be familiar with and observe these safety regulations. Only qualified
personnel may carry out the described work with suitable and intact tools, equipment, test equipment and materials.
Important instructions are highlighted by "CAUTION:", "ATTENTION:", "NOTE:" and indented text.
CAUTION:
This symbol identifies all working and operational procedures requiring absolute compliance to avoid any
danger to personnel.
ATTENTION:
This symbol identifies all working and operational procedures requiring absolute compliance to prevent
any damage to the UPS or some of its components.
NOTE:
This symbol identifies technical requirements and additional information requiring the operator's attention.
2.1 Introduction
Congratulations for chosen a UPS out of the JOVYSTAR E series! This type of static UPS incorporates the latest state of
technology in power electronics and digital signal processing. The UPS offers the optimal solution for problems in power
supply of computer-systems. UPS of this series are capable to communicate with different computer operating systems
through a standardized RS232-interface. The necessary software as well as additional hardware like SNMP-adapter or
MODBUS-adapter for remote control of the UPS is available as an option.
JOVYSTAR E UPS are real online systems (UPS-classification VFI SS 111 acc. IEC 62040-3), which prevents the attached loads from mains disturbances like spikes, blackouts and voltage variations. The products are screened by an
effective quality management system.
Therefore the JOVYSTAR E offers a perfect solution for various power supply problems; the reliability of the product is
our major goal since over 60 years of experience in secured power supply and techniques.
The scope of this manual is to describe the UPS and to guide the installer and the user through the correct installation.
The installer and the user will have to read this manual with care and attention and correctly carry-out the instructions
provided, especially those relevant to security according to the local standards and regulations.
NOTE:
The manufacturer declines all responsibility for damages to people or equipment deriving from nonfulfilment of the instructions mentioned in this manual.
2.2 Why Using A UPS?
The reliable power supply is one of the major issues when installing computer-based process controlling systems. The
main reasons of all disturbances are:
- Spikes, produced by switching devices in the mains distribution
- High frequency superposition caused by welding machines, fluorescence radiation, copy machines and other,
- Voltage variations, due to load variations of big inductive consumers, such as lifts, transformers, machines
and others,
- Voltage breakdown, due to disturbances in the mains,
- Frequency variations, caused by using separate power supply units.
The range of disturbances for the attached loads begins with data errors or storing-loss and extends to hardware failure
or even production blackouts. Therefore the quality of power supply is an important factor for the reliability of electronic
data processing equipment or any other sensitive loads.

Wärtsilä JOVYSTAR HP 200-800kVA BAX 4640 E - 10 -
The best solution for a secure and safe power supply of critical loads is the use of an Uninterruptible Power Supply
(UPS). The UPS:
- Generates a constant voltage supply and frequency,
- Filters, respective suppresses mains disturbances down to a negligible value,
- Guarantees an uninterruptible power supply of the attached loads during a mains
failure for a specified period.
The UPS of the series JOVYSTAR E is a system, is being connected between the mains and the load. It always guarantees a secure power supply to the load over a specified period of time. In comparison to conventional power sources
(mains, motor aggregates, generators*)) the main advantages of the JOVYSTAR E series are as follows:
- Optimal quality of the output voltage,
- Prevention from spikes, superposition, transient over-voltages etc.,
- Prevention from voltage variations and mains failures,
- Prevention from frequency variations,
- Low noise,
- Small, compact design,
- Remote control facility by SNMP-Adapter or MODBUS-Adapter (option)
*) NOTE:
The operation of a UPS system or other electronic consumers at a generator assumes that the planner
was informed of whether an interworking of the generator with the power electronics is without problems
possible before the installation of the entire system.
Some generators are so laid out that an operation with power electronic consumers is not possible because of the additional load with harmonics, power factor and commutation notches. In some cases can it
to troubles as tension imbalance, tendency towards oscillations and to the shut-off of the generator come.
Here it can help, to consult the generator manufacturer and to change the regulator of the generator where
appropriate or to make from the first so-called damping windings into the generator.

Wärtsilä JOVYSTAR HP 200-800kVA BAX 4640 E - 11 -
3 System description
UPS of this series are true on-line, double conversion UPS (classification-code VFI-SS-111); the inverter supplies the
load under normal operating conditions, whether mains is available or not (according to the battery autonomy time).
ATTENTION:
The UPS output is energized even during mains failure, therefore in compliance with the prescriptions of
EN 62040, the installer must label the outlets, plugs or lines supplied by the UPS, making the user aware
of this fact.
This true online concept guarantees great advantage to the user, as it supplies clean, continuously regulated power and
guarantees a stabilized voltage. Thanks to the double conversion principle, the load will be protected from microinterruptions due to excessive mains variation. It prevents damage to the critical load.
Block diagram
Legend of the block diagram:
Input UPS Input terminals (1L1, 1L2, 1L3, PE.)
Input Bypass Bypass input terminals (2L1, 2L2, 2L3, 2N, PE.)
RCB Rectifier Circuit Breaker
SBCB Static Bypass Circuit Breaker
MBCB Manual Bypass Circuit Breaker; only available at 200-300 kVA as standard
equipment, available at 400-800 kVA as option)
BCB Battery Circuit Breaker
OCB Output Circuit Breaker
UPS Output Output terminals (3L1, 3L2, 3L3, 3N, PE.)
Rectifier The IGBT rectifier converts the input AC-voltage into a regulated DC-voltage supply-
ing the inverter and charging the batteries.
Inverter The inverter converts the DC-voltage delivered by the rectifier or by the battery into
an AC-voltage, regulated by Pulse-Width-Modulation. The output of the inverter is
short circuit proof by electronic short-circuit-protection.
Static Switch The static bypass consists of a thyristor-switch. It switches the mains over to the UPS
output. During normal operation the inverter output is switched to the UPS output
while the bypass is blocked. During overload at the UPS output or an inverter failure
the attached loads will be supplied immediately by the bypass.
Manual Bypass The manual bypass feeds the load in case of maintenance or disturbances of the
UPS. The manual bypass is to be used only by qualified personnel under consideration of the described instructions in this manual!

Wärtsilä JOVYSTAR HP 200-800kVA BAX 4640 E - 12 -
ATTENTION:
A handling error of the internal or (if applicable) any external manual bypass could lead to a total
blackout at the output of the UPS!
3.1 Rectifier
It converts the three phase voltage of the AC mains into continuous DC voltage. It uses a three phase fully-controlled
IGBT bridge with a low harmonic absorption. The control electronics uses a 32 bit uP of latest generation that allows to
reduce the distortion of the current absorbed by mains (THDi) to less than 5%. This ensures that the rectifier does not
distort the supply mains, with regard to the other loads; it also avoids unlikely overheating of the cables due to the harmonics circulation.
The rectifier is so sized as to supply the inverter at full load and the battery at the maximum charging current.
3.2 Inverter
It converts the direct voltage coming from the rectifier or from the DC battery into alternating AC voltage stabilized in
amplitude and frequency. The inverter uses IGBT technology with a high changeover frequency of approximately 10
KHz. The control electronics uses a 32 Bit uP of latest generation that, thanks to its Processing capability, generates an
excellent output sine-wave.
Moreover, the fully digitized control of the output sine-wave allows to achieve high performances, among which a very
low voltage distortion even in presence of loads with high crest factor currents.
3.3 Battery and Battery Charger
The battery is installed outside the UPS. It is generally housed in an external battery cabinet. The battery charger logic is
completely integrated in the rectifier’s control electronics. The battery is charged, according to the DIN 41773 Standard,
every time it has been partially or completely discharged. When its full capacity is restored, it is kept floating so as to
compensate for any autodischarge.
3.4 Static Bypass
It serves to transfer the load between INVERTER and MAINS, and vice-versa, without interruption, and uses SCR’s as
power commutation elements.
3.5 Manual Bypass
It provides a solution of bypassing the UPS by itself, supplying the load directly by the mains in case of maintenance or
serious failure.
ATTENTION:
The sequence of switching to bypass must be carried out with respect to the procedure indicated on the
UPS and in the chapter “Operating the UPS”. The manufacturer cannot accept responsibility for damages
arising from incorrect operation.
3.6 Front Panel
The front panel of the UPS, consists of a double row alphanumeric display including 5 function keys, allows the complete
monitoring of the UPS status. A mimic diagram helps to understand the operating status of the UPS. For more information see the chapter “Operation”.

Wärtsilä JOVYSTAR HP 200-800kVA BAX 4640 E - 13 -
3.7 Operating status
The following paragraphs show all the possible operating status of the UPS.
3.7.1 Normal operation
The inverter is supplied by the rectifier, which also charges the battery. The load is supplied by the inverter output directly, via the inverter static switch SSI. The load is in the best conditions in terms of supply Protection.
3.7.2 Load supplied by bypass due to inverter fault
In case of inverter fault, the load is transferred to bypass, emergency line, through the static bypass switch SSB; the
transfer is carried out without interruption.
3.7.3 Rectifier failure or mains failure
The inverter is supplied by the battery for the stated autonomy time; the load, through the inverter static switch SSI, is
supplied directly by the inverter output.

Wärtsilä JOVYSTAR HP 200-800kVA BAX 4640 E - 14 -
3.7.4 Internal Manual bypass
The load is supplied by the input mains through the manual bypass. The operator can work in safety on the UPS to carry
out maintenance or repairing operations.

Wärtsilä JOVYSTAR HP 200-800kVA BAX 4640 E - 15 -
4 Installation
4.1 Reception of the UPS
After reception of the UPS, unpack immediately and carry-out an accurate visual check for any transport-damages.
IMPORTANT:
In case of objections relating to damage incurred during transport these must be immediately notified to
the transportation company after reception of the product.
When the UPS is not installed immediately it must be stored carefully in vertical position, as indicated on
the packing and conserved in a dry and sheltered room in its box so that it is protected from dust.
4.2 Transport
Before positioning the UPS, in order to avoid risks of turnover, it is recommended to move the system only while mounted on the wood pallet. Before the positioning in the final location, remove the pallet from the UPS. The UPS can be lifted
and handled using a pallet truck or a forklift.
ACHTUNG:
Paying attention to the center of gravity of the UPS! The brackets must be long sufficient and far enough
from each other stand.

Wärtsilä JOVYSTAR HP 200-800kVA BAX 4640 E - 16 -
4.3 Setting up
The UPS must be installed in a clean and dry room, preferably not dusty. The user must ensure a proper air conditioning
for cooling the equipment. If the UPS contains the batteries internally the air exchange with the external ambient must
comply with EN 62040, annex N.
Pay attention, that through the weight of the UPS and the batteries the maximum floor loading will not exeeded. You find
informations to the weights and the measurements in the technical data. In addition the site must fulfil the following requests:
- The UPS may be installed only in dry rooms.
- None caustic or acid steam may escape.
- The device supply air temperature may be maximally 40°C.
- Whem batteries are supplied to this UPS installation, the air exchange for these batteries with the external surroundings must according to EN 62040 appendix N.
- The vent holes at the device must not be covered by construction measures or other factors.
- The device is to be protected against direct solar radiation and action of other heat springs.
- The wall- and ceiling-distances as well as the recommended air flow volume (see also technical data) are complying for an optimum cooling of the UPS. An overheating of the system is thus avoided.

Wärtsilä JOVYSTAR HP 200-800kVA BAX 4640 E - 17 -
4.3.1 Dimensions Wärtsilä JOVYSTAR HP E 200-300 kVA

Wärtsilä JOVYSTAR HP 200-800kVA BAX 4640 E - 18 -