Wartsila Jovyline 625, Jovyline 1200, Jovyline 2200 Operating Manual

BAX 3522 E
Operating Manual
UPS Systems
Wärtsilä
JOVYLINE 625/1200/2200
UPS-Division
Operating Manual Wärtsilä JOVYLINE 625/1200/2200 BAX 3522 E page 2
Important information!
Please read this manual carefully before installation.
Pay attention to each special hint within the separate chapters to avoid later disturbances of the device right from the start.
In case of problems please contact our Service department.
In favour of our environment: Please preserve the packing in case a servicing should arise or carry it to a suited recycling circle.
UPS-Division
Operating Manual Wärtsilä JOVYLINE 625/1200/2200 BAX 3522 E page 3
Chapter Contents page ______________________________________________________________________________________
1. Technical Data 4
Table 1: type-specific data 4
2. Security 5
3. Description of the UPS-system 6
3.1 Preface 6
3.2 Description of the system 7
3.3 Front- and back views of the Wärtsilä JOVYLINE 625/1200/2200 7
4. Installation 11
5. Operation of the UPS-system 12
6. Alarms 13
7. Software options 13
8. Computer interface connection 14
9. Replacing of batteries 14
10. Troubleshooting 15
______________________________________________________________________________________
Attention!
Please inspect the contents of the packing for damages in transit and completeness right away after delivery.
Delivery accessories UPS JOVYLINE 625 / 1200 / 2200 1 pc. OFFLINE UPS-system 1 pc. Mains cable, grey/white interface cable, two-poled connection cable
for analogous modem/telephone - connection
UPS-Division
Operating Manual Wärtsilä JOVYLINE 625/1200/2200 BAX 3522 E page 4
1. Technical data
1.1 Table 1: Typespecifical data
UPS (nominal power) 625 VA 1200 VA 2200 VA Input voltage / mains voltage 230 V +20% -25% Mains frequency
50 / 60 Hz
5% (automatic switch-over)
Output voltage 230V Output frequency
50 / 60 Hz
0,5% (at battery operation)
Voltage regulation of the output voltage
AVR increases the output voltage by 15% over input voltage, if the input voltage sinks within –9% up to – 25%. AVR decreases the output voltage by 13% compared with the input voltage, if the input voltage increases within +9% up to +25%
Time for switch over 2-4 ms including detection time 10 Base-T Cable Port network (UTP, RJ-45) compatible plugs Protection against spikes 320 Joule, 2ms Overload protection UPS switches off after 110% overload for 60 sec. and
130% overload for 3 sec.
Short circuit protection UPS switches off immediately or input protection gets released Input protection Protection against overload and short circuit
Type of battery Lead battery, closed maintenance-poor
12V / 7Ah (JOVYLINE 625) 24V / 7Ah (JOVYLINE 1200 /
JOVYLINE 2200)
Charging duration battery 4 hours up to 90% of nominal capacity Protection installations battery Automatic selftest and protection against discharging, display for
defect batteries
Autonomy time 10-30 min. (in dependency on the computer load) Weight UPS 6,5 kg 13,4 kg 15,9 kg
Dimension (w x h x d) in mm 97 x 320 x 135 130 x 382 x 192 130 x 382 x 192 Mains input connection Connection acc. IEC 320
Alarm, battery charging Slow bleeping tone (ca. 0,47Hz) Alarm, battery discharged Quick bleeping-tone (ca. 1,824Hz) Alarm, overload Permanent sound Interface RS-232 Bi-directional com. Port Rules for construction security: VDE, TÜV, CE , Surrounding terms
Placing
1000m above sea level acc. to EN 62040-3
Surrounding terms General
humidity 0 - 95% non condensing, acc. to table DIN 40040
0-48°C
Decibel level acc. to ISO 7779 < 40 dbA
Technical modifications be possible
UPS-Division
Operating Manual Wärtsilä JOVYLINE 625/1200/2200 BAX 3522 E page 5
2. Security To avoid an electric shock you have to disconnect the UPS from the mains
before connection of the computer to the UPS.
In case of works on the UPS you have to secure that the UPS is in OFF-modus
and disconnected from mains. The I/O switch at the back of the UPS has to be in OFF-position. After that you can open the UPS and disconnect the batteries.
Don’t put the batteries into fire – they could explode. Don’t open the battery-blocks. The acid inside these blocks injures skin and
eyes.
Even a multicellular battery can lead to an electrical shock. Therefore don’t touch
both poles at the same time. Before works at the battery you have to secure, that there are no metallic things such as rings, bracelets etc. at your arms and hands which could lead to a short circuit at the poles of the battery. A short circuit on the battery can produce a very high short circuit current which leads usually to bad burns and the UPS will ignite.
Don’t connect the mains input with the mains output of the UPS. The UPS could
be damaged.
Attention! Improper handling of the UPS implies a higher risk of electrical shock. Even after
disconnection of the UPS from the mains there may be voltage at the output! Attention! Only authorised persons are allowed to open the UPS. Don’t remove the covering of
the UPS. Avoid the danger of an electrical shock. There is no component part within the UPS which has to be replaced by the user.
Warning! To avoid fire please use only the integrated original fuses! Warning! To reduce the risk of fire or electrical shock the UPS shouldn’t placed in areas with
to high temperatures or humidity. It’s recommendable to install the UPS insides of air-conditioned rooms.