WORTHINGTON CS200 Operation & Maintenance Instructions

CS200 Control Systems
LABS and K Series Cryostorage Systems Operation & Maintenance Instructions
CAUTION - SAFETY FIRST!
• REVIEW AND UNDERSTAND ALL SAFETY PROCEDURES IN THE “HANDLE WITH CARE” BOOKLET BEFORE ATTEMPTING TO INSTALL, OPERATE OR PERFORM MAINTENANCE ON THIS LN2 CONTROLLER.
• DO NOT ATTEMPT TO USE OR MAINTAIN ANY LIQUID NITROGEN FREEZER UNTIL YOU READ AND UNDERSTAND THESE INSTRUCTIONS.
• DO NOT PERMIT UNTRAINED PERSONS TO USE OR MAINTAIN THIS UNIT.
• IF YOU DO NOT FULLY UNDERSTAND THESE INSTRUCTIONS, CONTACT YOUR SUPPLIER FOR FURTHER INFORMATION.
• BEFORE ATTEMPTING TO OPERATE THIS CONTROLLER WITH ANY WORTHINGTON INDUSTRIES LABS OR K SERIES UNITS, YOU MUST READ THE SEPARATE OPERATING AND SAFETY MANUAL PROVIDED WITH THAT UNIT.
Table of Contents
SAFETY PRECAUTIONS .......................................................................5
Liquid Nitrogen (LN2) ............................................................................................. 5
Extreme Cold - Cautionary Statement ....................................................................... 5
Keep Equipment Area Well Ventilated ..................................................................... 5
Liquid Nitrogen System ......................................................................................... 5
Electrical .............................................................................................................. 5
GENERAL INFORMATION ...................................................................6
CS200 Series Control System Specifications ............................................................ 7
DELIVERY AND RETURNS .................................................................. 10
Unpacking and Inspection .................................................................................... 10
Freight Damage Procedures ................................................................................. 10
Repackaging for Shipment .................................................................................. 10
INSTALLATION ................................................................................. 11
Getting Unit into Service ..................................................................................... 11
Electrical ........................................................................................................... 11
Electromagnetic Compatibility (EMC) .................................................................... 11
Power Supply Connection ................................................................................... 12
Validation .......................................................................................................... 12
OPERATION ....................................................................................13
Initial Fill ........................................................................................................... 13
Control Components ........................................................................................... 13
CS200 Controller Display Guide ........................................................................... 14
Operational Theory ............................................................................................. 14
Alarm Conditions ............................................................................................... 15
Lid Switch .......................................................................................................... 16
Solenoid Valve ................................................................................................... 17
Thermocouples ................................................................................................... 17
Power Supply .................................................................................................... 17
Remote Alarm .................................................................................................... 17
Operating Parameters ......................................................................................... 17
Temperature Monitoring ....................................................................................... 18
Liquid Phase Storage ........................................................................................... 18
Maintenance ...................................................................................................... 18
CONTROLLER OPERATION ................................................................20
Introduction ....................................................................................................... 20
Operation Data .................................................................................................. 20
Communications ................................................................................................. 20
Normal Fill Cycle ............................................................................................... 20
Control Setting Adjustments .................................................................................. 20
Temperature .......................................................................................................26
Battery Operation .............................................................................................. 26
LED Status Wheel ............................................................................................... 26
Lid Switch ........................................................................................................... 26
Menu System ..................................................................................................... 27
Factory Defaults ................................................................................................. 29
Troubleshooting ..................................................................................................30
Interconnection Block Diagram .............................................................................. 30
CS200 Control Systems
Table of Contents
Wiring Diagram ..................................................................................................31
Installation & Setup .............................................................................................. 32
External Connector Ratings ................................................................................... 34
LED Status Wheel Flash Patterns ............................................................................ 35
Temperature Thermocouple Select ......................................................................... 35
Temperature Calibration ...................................................................................... 35
Test Temperature System ....................................................................................... 36
Test Level Sensors ................................................................................................ 36
Alarms and Error Conditions ................................................................................ 37
System Alarms .................................................................................................... 37
Test Alarms ........................................................................................................ 37
Logging ............................................................................................................. 37
Display Brightness ............................................................................................... 38
Making Adjustments to the CS200 Series Control System Sensor Assembly ............... 38
Removing/Installing the Solenoid Valve ................................................................. 39
Removing/Installing the Controller 10K/24K Units ................................................. 39
Removing/Installing the Thermocouple .................................................................. 40
Removing/Installing the Sensor Probes .................................................................. 40
Making Adjustments to the Level Settings ............................................................... 40
Removing/Installing the Solenoid Valve ................................................................. 41
REPLACEMENT PARTS ...................................................................... 42
Plumbing Assembly ............................................................................................. 42
Controller Assembly ............................................................................................ 43
TROUBLESHOOTING ........................................................................45
Symptoms ......................................................................................................... 45
Controller Will Not Turn ON ............................................................................... 45
High Liquid Level ................................................................................................ 45
Indicates Low LN2 Supply ..................................................................................... 46
Indicates Open Sensor ......................................................................................... 46
Temperature Reading 10° to 20° Warm ................................................................. 46
Fill Solenoid Cycles On and Off ............................................................................ 47
Solenoid Makes Excessive Humming Noise ............................................................ 47
Lid Open Alarm .................................................................................................. 47
QCF (Quick Chill Feature) Will Not Operate ......................................................... 47
Auto Defog Feature Will Not Operate ..................................................................47
Push Buttons Will Not Respond ............................................................................48
Liquid Level Readout is Incorrect ........................................................................... 48
Power Failure Alarm ........................................................................................... 48
SERVICE AND MAINTENANCE HISTORY LOG ....................................49
APPENDIX ....................................................................................... 50
EN Compliance Tables .........................................................................................50
EC Declaration of Conformity ............................................................................... 54
Warranty ........................................................................................................... 55
Labels ................................................................................................................ 55
CS200 Control Systems
Safety Precautions
Liquid Nitrogen
Nitrogen is an inert, colorless, odorless, and tasteless gas making up four-fifths of the air you breathe – and can be very dangerous. Air is roughly one-fifth oxygen. Liquid nitrogen is at a temperature of -196°C (-320°F) under normal atmospheric pressure. Cryogenic freezers are used in LN2 service only.
Extreme Cold - Cautionary Statement
Accidental contact of liquid nitrogen or cold issuing gas with the skin or eyes may cause a freezing injury similar to frostbite. Handle the liquid so it won’t splash or spill. Protect your eyes and cover the skin where the possibility of contact with the liquid, cold pipes and equipment, or cold gas exists. Safety goggles or a face shield should be worn when operating this equipment. Insulated gloves that can be easily removed and long sleeves are recommended for arm protection. Trousers without cuffs should be worn outside boots or over the shoes to shed spilled liquid.
Keep Equipment Area Well Ventilated
Although nitrogen is non-toxic and non-flammable, it can cause asphyxiation in a confined area without adequate ventilation. Any atmosphere not containing enough oxygen for breathing can cause dizziness, unconsciousness, or even death. Nitrogen, a colorless, odorless, and tasteless gas that cannot be detected by the human senses, will be inhaled normally as if it were air. One (1) liter of liquid nitrogen is equivalent to 24.6 scf of nitrogen gas. Without adequate ventilation, the expanding nitrogen will displace the normal air resulting in death.
Liquid Nitrogen System
The liquid nitrogen supply pressure at the inlet to the freezer should be in the range of 10 psig (0.7 bar/69 kPa) to 20 psig (1.4 bar/138 kPa) for optimum performance. Higher operating pressures will increase transfer losses and create excessive turbulence of the liquid in the freezer, which can generate false signals to the liquid level controller causing the freezer to under-fill. In “liquid phase” storage applications, excessive turbulence can cause splashing which could result in personal injury and/or damage to the freezer. When installing piping or fill hose assemblies, make certain a suitable safety relief valve is installed in each section of plumbing between any two isolation points. Trapped liquefied gas will expand greatly as it warms and may burst hoses or piping causing damage or personal injury. A relief valve is installed in the freezer plumbing to protect the line between the customer-supplied shut-off valve and the freezer solenoid valve. Relief valves can be piped to the outside of the building.
WARNING: The following safety precautions are for your protection. Before installing, operating, or maintaining this unit read and follow all safety precautions in this section and in reference publications. Failure to observe all safety precautions can result in property damage, personal injury, or possibly death.
WARNING: Maintain adequate ventilation to prevent asphyxiation hazard (see Safety Precautions).
Caution: When installing field fabricated piping, make certain a suitable safety relief valve is installed in each section of piping between any two isolation points.
WARNING: Inlet pressure should not exceed 22 psig (1.5 bar/152 kPa). Higher pressures could result in damage to equipment.
Electrical
• This product is not intended for a life support function.
• This product is intended to be used in hospitals and clinics.
• This product has no Radio Transmitter (Intentional Radiator) functions.
• This product is not intended for electromagnetic shielded rooms only.
WARNING: Electrical shock can kill. Do not attempt any service on these units without first disconnecting the electrical power cord.
CS200 Control Systems
5
General Information
• This product does not intentionally apply RF energy for its function.
• This product does not intentionally receive RF energy for its function.
The liquid level controllers used with these freezers operate from 12 VDC. Disconnect the electrical power cord from the outlet before attempting any service.
For more detailed information concerning safety precautions and safe practices to be observed when handling cryogenic liquids consult CGA publication P-12 “Safe Handling of Cryogenic Liquids” available from the Compressed Gas Association: CGA website: www.cganet.com; CGA customer service +1.703.788.2700; or email customerservice@cganet.com.
General Information
The CS200 SERIES Control System can monitor and control both the liquid nitrogen level and the vapor temperature range in the cryostorage unit you have selected. CS200 SERIES Control Systems are designed to work with Worthington Industries Cryostorage Systems. The features are designed to provide a safe environment for samples while at the same time tracking all relevant information associated with the freezer. This control provides a complete historical record of the environment in your unit and therefore, the environment in which your samples have been stored in this system. This controller features a vacuum fluorescent display. The addition of a liquid nitrogen supply and inventory control racks for systematic retrieval of stored product completes the total Cryostorage System.
Worthington Industries Cryostorage Systems are designed for applications where extremely low temperature storage of biological products is required. They are also appropriate for industrial or other applications where liquid nitrogen temperatures and high capacity are needed.
Before beginning installation or operation of this CS200 SERIES Control System, make sure that you read and understand this manual as well as the operating and safety instructions for the cryostorage unit you will be using with this controller.
CS200 Control Systems
66
General Information
CS200 SERIES Control System Specifications
Specifications
Control Type LN2 Level Control & Temperature Control
Level Measurement
Sensor Type 8-Thermistor Fixed (standard) Range 8 inch range (8-Thermistor) Redundancy Multiple discrete points
Temperature Measurement Sensor Type
Type T Thermocouple
Accuracy Resolution Number of channels Temperature Display Units
Electrical
Input Voltage 100-240 VAC Input Current (max) 1.75 A Input Current (continuous) .5 A Power Consumption (max) 21 W Power Consumption (continuous) 6 W Input Frequency 50/60 Hz Output 12 VD C Control Input Voltage 12 VD C Power cord Available for all countries
Battery
Rating 12 Volt, 18Ah Type AGM Sealed Non-Spillable Short Protection Installed PCB with thermal fuse Battery Cover Vinyl
Solenoid Valve
Input Voltage 12 VD C Input Current .96 amps
Communications
Protocol CryoWire Secure™ Number of Communication Ports 3
1o or 1.5% of reading .1oC 2
o
C, F, K, R
CS200 Control Systems
7
General Information
CS200 SERIES Control System Specifications (cont’d)
User Interface
Display Type Vacuum Fluorescent Display (VFD) Buttons 11 Level, Temperature and Alarm Information VFD “At a Glance” status LED status wheel Filling 1 LED Menu Access 1 LED Language English and German
Control Tests
Power Up Self-Test Control system check Thermistor Status Yes Battery voltage Yes Control voltages Yes Temperature circuit Yes
Alarms
Low Level Alarm Always enabled High Level Alarm Always enabled Sensor Error Alarm Always enabled High Temperature Alarm (T/C #1, T/C #2) Programmable Low Temperature Alarm (T/C#1, T/C#2 ) Programmable Thermocouple Calibration Alarm Always enabled Thermocouple Open Alarm Always enabled Power Failure (Remote only) Always enabled Low LN2 Supply Alarm Programmable Battery Mode Warning Always enabled Lid Open Too Long Alarm Programmable Valve Stuck Open Alarm Programmable Unauthorized Access Warning Programmable LN2 Use Warning Programmable Low Battery Voltage Always enabled Audible Alarm Always enabled Audible Alarm Re-trigger Programmable Visual Alarm Indicator Always enabled Remote Alarm Delay Programmable
CS200 Control Systems
8
General Information
CS200 SERIES Control System Specifications (cont’d)
Buttons
Power Turns power on/off Fill/Defog Open Valve Stop Close Valve Menu Access Menu Mute Silence audible Enter Save a setting or select a menu choice Back/Exit Leave a setting unchanged or back out of menu. Up arrow Scroll the menu system or increase a value Down arrow Scroll the menu system or decrease a value Left arrow Scroll horizontal menu Right arrow Scroll horizontal menu
Data Collection
Temperature Yes Level Yes Alarms Yes Memory 4 Mb
Dimensions
Display Width 9.5” (241 mm) Display Height 2.0” (50.8 mm) Display Depth 1.31” (33.3 mm) Display Weight .625 lbs (.28 kg) Main Control Width 8.875” (225.4 mm) Main Control Height 6.688” (169.9 mm) Main Control Depth 1” (25.4 mm) Main Control Weight 1.0 lbs (.45 kg) Battery Width 7.25” (184.2 mm) Battery Height 6.375” (161.9 mm) Battery Depth 3.25” (82.6 mm) Battery Weight 12.4 lbs (5.6 kg)
NOTE: Above measurements are for LABS; CS200 controllers are integrated into all K Series models.
CS200 Control Systems
9
Delivery & Returns
Unpacking and Inspection
Inspect shipping containers for external damage. All claims for damage (apparent or concealed) or partial loss of shipment must be made in writing within ten (10) days from receipt of goods. If damage or loss is apparent, please notify the appropriate parties as indicated below:
Domestic LTL Shipments – The customer should notify and file the appropriate damage claims with the carrier. All products are shipped Ex Works.
Domestic UPS Shipments – Any damage should be noted and reported to shipper upon delivery, and Worthington Industries must also be notified. Confirm with Worthington Industries Customer Service the filing procedures for any UPS damage claims.
International Shipments – Any damage and/or claims are to be filed with the carrier. Insurance agent(s) and Customs should also be notified.
In all cases, Worthington Industries should be notified so we can assist if needed in filing damage claims.
Open the shipping containers; a packing list is included with the system to simplify checking that all components, cables, accessories, and manuals were received. Please use the packing list to check off each item as the system is unpacked. Inspect for damage. Be sure to inventory all components supplied before discarding any shipping materials. If there is damage to the system during transit, be sure to file proper claims promptly. Please advise Worthington Industries of such filings. In case of parts or accessory shortages, advise Worthington Industries immediately. Worthington Industries cannot be responsible for any missing parts unless notified within 10 days of shipment.
Freight Damage Procedures
Any freight damage claims are your responsibility. Cryostorage Systems are delivered to your carrier from Worthington Industries’ dock in new condition; when you receive our product you may expect it to be in that same condition. For your own protection, take time to visually inspect
each shipment in the presence of the carrier’s agent before you accept delivery. If any damage is observed, make an appropriate notation on the freight bill. Then, ask the driver to sign the notation before you receive the equipment. You should decline to accept containers that show damage which might affect serviceability.
Repackaging for Shipment
If it is necessary to return any part of the system for repair or replacement, a Material Return Authorization (MRA) number must be obtained from an authorized factory representative before returning the equipment to our service department. Contact your distributor for return authorization. When returning equipment for service, the following information must be provided before obtaining an MRA:
1. System model and serial number, and controller model and serial number.
2. User’s name, company, address, and phone number
3. Malfunction symptoms If possible, the original packing material should be retained for reshipment. If not available, consult
Worthington Industries for shipping and packing instructions. It is the responsibility of the customer to assure that the goods are adequately packaged for return to the factory. All freezers returned to Worthington Industries
must be clean and decontaminated before return.
CS200 Control Systems
10
Installation
Getting Unit into Service
Your Cryostorage System comes with complete instructions for how you should remove the unit from the crate and put it into service. Read both this manual and your Cryostorage System’s manual before beginning any installation. Make sure to follow any required procedures and safety guidelines when you are connecting your Liquid Nitrogen source.
The CS200 SERIES Control System is designed to be operated at normal room temperatures 15° C to 27° C (60° F to 80° F) at a relative humidity level below 50%. The humidity level should be maintained such that the electronics are not exposed to condensation.
The Worthington Industries Cryostorage freezer should be positioned such that the all sides of the unit are easily accessible and the user can easily connect/disconnect the power cord from the wall socket.
Proper ventilation MUST BE adequate to sustain life for those working with or maintaining this equipment.
Electrical
The liquid level controllers used with these freezers operate at 12 VDC. The external power supply has a 120 VAC (50/60 Hz) primary. Disconnect the electrical power cord from the wall outlet before attempting any service.
Electromagnetic Compatibility (EMC)
Although this equipment conforms to the intent of the 2004/108/EC EMC Directive, all medical equipment may produce electromagnetic interference or be susceptible to electromagnetic interference. The following are guidance and manufacturer’s declarations regarding EMC for the CS200 SERIES Control System.
WARNING: Electrical shock can kill. Do not attempt any service on these units without first disconnecting the electrical power cord.
The CS200 SERIES Control System needs special precautions regarding EMC and needs to be installed and put into service according to the EMC information provided in the following pages.
Portable and Mobile RF communications equipment can affect the performance of the CS200 SERIES Control System. Please use the guidelines and recommendations specified in the EN Compliance tables found on pages 50-54.
Other equipment or systems can produce electromagnetic emissions and therefore can interfere with the functionality of the CS200 SERIES Control System. Care should be used when operating the CS200 SERIES Control System adjacent to or stacked with other equipment. If adjacent or stacked use is necessary, the CS200 SERIES Control System should initially be observed to verify normal operation in the configuration in which it will be used.
The electrical cables, external power supplies and accessories listed or referenced in this manual have been shown to comply with the test requirements listed in the EN Compliance tables found on pages 50-54. Care should be taken to use only manufacturer-recommended cables, power supplies and electrical accessories with the C200S SERIES Control System. If a third-party supplier offers cables, external
WARNING: Maintain adequate ventilation to prevent asphyxiation hazard (see Safety Precautions).
WARNING: If the fill fails to stop for any reason, quickly close the liquid supply valve to prevent overfilling until the the problem can be determined.
CS200 Control Systems
11
Installation
WARNING: This equipment is intended for use by healthcare professionals. As with all electrical medical equipment, this equipment may cause radio interference or may disrupt the operation of nearby equipment. It may be necessary to take mitigation measures such as re-orienting or relocating the CS200 SERIES Control System unit or shielding the location.
power supplies and electrical accessories for use with the CS200 SERIES Control System and they are not listed or referenced in this manual, it is the responsibility of that third-party supplier to determine compliance with the standards and tests in the EN Compliance tables found on pages 50–54.
The use of electrical cables and accessories other than those specified in this manual or referenced documents may result in increased electromagnetic emissions from the CS200 SERIES Control System or decreased electromagnetic immunity of the CS200 SERIES Control System.
Power Supply Connection
Connect the power supply to your Cryostorage System and then plug the power supply into a surge-protected wall outlet.
Validation
Some organizations require that equipment be validated periodically. If information is needed on the proper techniques to validate this equipment, please contact your supplier.
CS200 Control Systems
1212
Operation
These instructions are for operators experienced with cryogenic equipment. Before operating the system, become familiar with the safety precautions in this manual and in reference publications. Make certain all applicable provisions set forth in the Installation Section have been followed before placing a system in operation. Study this manual thoroughly. Know the location and function of all system components.
Initial Fill
The Cryostorage System, using the CS200 SERIES Controller, comes preset from the factory. The liquid nitrogen supply pressure at the inlet to the freezer should be in the range of 10 psig (0.7 bar/69 kPa) to 22 psig (1.5 bar/152 kPa) for optimum performance. Higher operating pressures will increase transfer losses and create excessive turbulence of the liquid in the freezer which can generate false signals to the liquid level controller causing the freezer to under fill. In “liquid phase” storage applications, excessive turbulence can cause splashing which could result in personal injury.
Control Components
CS200 Series Control System Components
The CS200 SERIES Control System for the Worthington Industries Cryostorage freezer consists of the following components:
• Main Control Module
• VFD (Vacuum Florescent Display) Module
• Shielded Display Cable
• Wiring Harness Assembly
• Power Supply
• Thermocouple Assembly (Optional Second Thermocouple)
• Sensor Assembly
• Cryogenic Solenoid Valve
• Remote Alarm Plug
• Lid Switch Assembly
• 12 Volt, 18aH battery
• Solenoid Valve Assembly with Freezeguard
• Strainer The CS200 Series Control System is assembled onto the freezer at the factory and completely tested. Refer to
the Quick Start Guide for freezer set-up. Start operation of the control system by plugging the power cord into the wall outlet. Press and hold the POWER button for 2 seconds. The CS200 Series Control System will go through a short startup routine and then start operation. Refer to Figure 2.0 CS200 Controller Display for a description of the controller’s navigation buttons.
CS200 Control Systems
13
Operation
CS200 Controller Display Guide
Status Wheel
VFD Graphics Display
shows information about the freezer
Fill button usend to open the valve
Enter Button “selects” a menu choice or setting
Stop Button used to close the valve
Mutes the
Valve Indicator lights
audible alarm
if the valve is open
Figure 1.0 CS200 Controller Display
Directional Buttons
Increment/decrement values or allow movement through the system
Power Indicator
Back Button
moves out of the menu system or leaves current set-
Menu Indicator
ting unchanged
Power On/Off
Enter/Exit
menu system
Operational Theory
The CS200 SERIES Control System automatically maintains the Liquid Nitrogen (LN2) level and monitors temperature in the Cryostorage freezer. Operational conditions are monitored and any alarm is triggered if necessary. Operations data is stored in memory on the control board.
The CS200 CONTROL SYSTEM uses thermistors to measure the LN2 level within the vessel. A thermistor is a thermal resistor and its resistance changes as the temperature changes. When a thermistor is submerged in LN2, its resistance will be significantly greater than its resistance at room temperature. The control can detect this resistance change and determine the level of the LN2 within the freezer. The CS CONTROL SYSTEM is designed to work with an 8-thermistor assembly. There are four thermistors that can be selected to maintain the LN2 level. These selected thermistors correspond to Low Alarm, Start Fill, Stop Fill and High Alarm. When the LN2 level drops below the Start Fill thermistor, the control opens the solenoid valve allowing LN2 to enter the vessel. This continues until the Stop Fill thermistor is submerged in LN2 at which point the solenoid valve is closed, preventing the flow of additional LN2 into the vessel. The Low Alarm, Start Fill, Stop Fill and High Alarm settings can all be changed by the user through the menu system.
High Level
High Level A
Low Level
Low Level A
Alarm
Alarm
#8
#7
#6
#5Stop Fill
#4
#3Start Fill
#2
#1
CS200 Control Systems
14
Figure 2.0 Factory Default Settings Shown
Operation
The LN2 level is indicated on the display and is determined by the number of thermistors submerged in LN2 according to the table below:
Table 1.0 8-Thermistor Sensor (G=GAS, L=LIQUID)
8-THERMISTOR SENSOR
#1 #2 #3 #4 #5 #6 #7 #8 OFFSET DISPLAY
G G G G G G G G 0 0
L G G G G G G G 0 1 L L G G G G G G 0 2 L L L G G G G G 0 3 L L L L G G G G 0 4 L L L L L G G G 0 5 L L L L L L G G 0 6 L L L L L L L G 0 7 L L L L L L L L 0 8
NOTE - Offset value for LABS94K only = 3.0 in (126 mm).
Alarm Conditions
The CS200 SERIES Control System monitors a number of conditions and provides an alarm if a problem is detected. The alarms are listed below:
Table 2.0 Alarm Conditions
Note: Please see description of the offset. Level displayed may vary depending on the offset setting.
Alarm Problem Detected
Low Level Alarm
High Level Alarm
Sensor Error Alarm
High Temperature Alarm The temperature detected is warmer than the high temperature alarm setting. Low Temperature Alarm The temperature detected is colder than the low temperature alarm setting. Thermocouple Calibration
Alarm
Thermocouple Open Alarm
LN2 level is too low. The low level alarm thermistor on the sensor assembly is not submerged in LN2.
LN2 level is too high. The high level alarm thermistor on the sensor assembly is submerged in LN2.
A problem exists with the level sensor assembly. The control detects an open sensor circuit meaning that the sensor is unplugged or the sensor assembly has been damaged. A Sensor Error will be represented by an “O” within the Thermistor Status menu.
The calibration data is incorrect.
A problem exists with the temperature sensor (thermocouple). The control detects an open circuit meaning that the sensor is unplugged or the sensor assembly has been damaged.
Power Failure No Power.
Low LN2 Supply Alarm
A problem may exist with the LN2 supply connected to the freezer. This alarm occurs if the freezer does not fill within the designated amount of time as determined by the setting on the control. This may occur for a number of reasons including an empty supply cylinder, low pressure in the supply cylinder or a closed shut off valve.
CS200 Control Systems
15
Operation
Alarm Problem Detected
Lid Open Too Long Alarm
Valve Stuck Open Alarm The solenoid valve is stuck open. Unauthorized Access Warning The lid has been opened and an incorrect identification has been entered. LN2 Usage Warning The consumption of LN2 has increased and should be checked. Low Battery Voltage The voltage on the battery is low.
The lid has been opened for a period which is longer than the designated alarm setting.
Audible Alarm Retrigger
Remote Alarm Relay
Operating in Battery Mode Alarm Warning
The audible alarm is retriggered if error conditions still exist when the retrigger timer expires. The retrigger time can be adjusted by the user.
The control provides a relay to provide an external signal that an alarm condition has occurred. The remote alarm timer can be set through the menu system. This setting determines the amount of time an error must be active before the relay is triggered.
The power from the power supply has been disrupted and the control system is oper­ating on battery power.
All alarms include the following:
• The flashing status wheel flashes to signal an error condition
• An audible tone sounds
• The error detected is displayed and scrolled on the screen
• The remote alarm relay changes state to provide a dry contact output signal
Lid Switch
The Lid Switch (Figure 4.0 and 4.1) is attached to the hinge and determines whether or not the lid is open on the freezer. This also allows the control to determine whether to activate the Auto Defog, Quick Chill or Lid Alarm features.
CS200 Control Systems
16
Lid Switch
Figure 3.1 K Series Lid SwitchFigure 3.0 LABS Lid Switch
Operation
Solenoid Valve
These units are designed to work with 12 VDC solenoid valve (see Figures 17.0, 17.1, and 17.2 Plumbing Assemblies on page 42).
Thermocouples
Type T thermocouples monitor the temperature in the freezer. The user may choose to use NONE, 1 or 2 thermocouples with this control at any time. (The unit comes complete with one Thermocouple)
Power Supply
A 12 VDC power supply is supplied for the CS200 SERIES Control System. This system is supplied with a universal power supply that accepts 100/240 VAC (50/60 Hz). UL approval for the system as a whole is not required since the control operates on low voltage. If your power source differs, or is subject to disruption or line surges due to other equipment on line, consult your Worthington Industries representative.
Remote Alarm
If an error condition occurs after a user defined period of time, a remote alarm can be initiated. This is accomplished by connecting a remote device to the remote alarm jack on the rear electrical panel. The 3-pin jack on the back of the unit provides continuity between pin #2 (common) and pin #3 in the normal condition. Continuity between pin #1 and pin #2 is provided in an error condition.
Remote Alarm Connector
Figure 4.0 Remote Alarm Plug Connection
Operating Parameters
When materials are immersed in LN2, they will assume the temperature of the liquid (-196°C/-320°F). When material is stored in the vapor phase over the liquid, the liquid nitrogen vapor is still a very cold refrigerant, but the freezer’s interior temperature increases as product is stored higher above the liquid. This temperature differential is not significant for many biological storage applications, and is affected by the amount of product stored in the freezer, the type, size and material of the inventory control system, and the liquid level in the unit.
The liquid level in the freezer is determined by the position of the of the Thermistor Assembly in the sensor tube. These sensors are set at installation to maintain a specific liquid level. A filling cycle is initiated when the level falls below the Start Fill sensor and is completed when the Stop Fill sensor is reached. This filling cycle repeats when the level fall below the Start Fill sensor. Sensor Probe assignments may be changed on the controller
CS200 Control Systems
17
Loading...
+ 39 hidden pages