Worldwide Electric Corporation IXHHI5-18-184TC Data Sheet

AC INDUCTION MOTOR DATA SHEET UL EXPLOSION PROOF MOTORS
CC 038A
REVISED 01/30/17
MODEL NUMBER
IXHHI5-18-184TC
HORSEPOWER
5
RPM / POLES
1800 / 4
VOLTAGE / PHASE
230 / 460 V / 3
FRAME
184TC
ENCLOSURE / DEGREE OF PROTECTION
TEFC / IP54
FREQUENCY
60 HZ
FULL LOAD SPEED
1760 RPM
SERVICE FACTOR
1.15
INSULATION CLASS
F Class N Varnish
FULL LOAD AMPS; 230 / 460
13.0 / 6.5 A Usable On 208 V At 14.4 A
LOCKED ROTOR CURRENT (% Full Load)
760 / 760 %
NEMA CODE LETTER
J
EFFICIENCY / POWER FACTOR
LOAD
EFF.
P.F.
100 %
89.5 %
80.0 %
75 %
89.7 %
76.0 %
50 %
88.2 %
67.0 %
DUTY CYCLE
S1 / Continuous
TORQUE
FULL LOAD
LRT
BDT
14.8 lb.ft.
210 %
260 %
NEMA DESIGN
B
MOMENT OF INERTIA
LOAD (Max.)
MOTOR
77.124 lb.ft.2
0.309 lb.ft.2
SOUND PRESSURE LEVEL ( No Load 1 M From Motor)
64 dB(A)
MAX. SHAFT VIBRATION
0.08 In/Sec – Peak Velocity
NUMBER OF STARTS (Hot / Cold)
2 Hot / 3 Cold
MAX. ELEVATION
3300 Ft. Above Sea Level
TEMPERATURE RISE (At Full Load)
80° C
DRIVE-END BEARING
6206ZZC3
OPPOSITE DRIVE-END BEARING
6206ZZC3
GREASE TYPE
Mobil Polyrex EM
MOUNTING
F1, W6, W8, B3, V5, V6
ROTATION
Bi-Directional
APPROXIMATE WEIGHT
121 lbs.
AREA CLASSIFICATION
Class I, Division 1, Groups C and D
TEMPERATURE CODE WITH THERMOSTAT USE
T4
TEMPERATURE CODE AT 40°C AMBIENT
T2C
TEMPERATURE CODE AT 55°C AMBIENT
T2B
THERMOSTAT TYPE
Normally Closed
INVERTER RATING
4:1 CT (Constant) / 10:1 CT (Intermittent-1 Hour) / 10:1 VT
INSULATION TYPE
Hyundai Inverter Shield, Meets NEMA MG1 Part 31
UL CERTIFICATION NUMBER
E216236